Reaper Mechanical and electrical operations 129

Embed Size (px)

Citation preview

  • 8/7/2019 Reaper Mechanical and electrical operations 129

    1/16

    Reaper Mechanical and Electrical Operations

    Version 1.29 Last revision 26 Jan 2008

    This document describes the installation, operation and maintenance of mechanical

    and electrical equipment onboard the Reaper.

    All aboard should be familiar with the contents so we can minimise the consequences

    of Mr Cock-up, should he come aboard. An Engine Room Log is kept aboard

    please use it for routine events such as running hours, fuelling, oil/coolant top-ups andthings that you break, fix or change. Daily and Weekly maintenance schedules will

    accompany the log (specimens attached). Comments and updates are most welcome

    (to [email protected], mobile 07764 161891).

    MacPhail.

    mailto:[email protected]:[email protected]
  • 8/7/2019 Reaper Mechanical and electrical operations 129

    2/16

    Engine

    The Reaper is powered by an 8 litre Daewoo L136 (serial no. 404807ENCKM) diesel

    engine. It generates 160 HP at 2200 rpm into a DMT70T 3.46:1 reduction gearbox

    (serial no. 04061129). The manual states a fuel consumption of 32 litres / hour.

    Hydraulic and pneumatic power is taken from a Dong-I E087A/D Take Off (serial no.

    01070035).

    Operation

    START UP

    1) Ensure gearbox in neutral.

    2) Key to ON.

    3) Key to START.

    4) Monitor engine panel and ensure cooling water is discharging.

    SHUT DOWN

    1) Press OFF button.

    2) Key to OFF.

    3) In case of fire the fuel valves may be remotely closed using the two toggles

    next to the bunks in the aft cabin. This may result in the need for the fuel

    system to be bled.

  • 8/7/2019 Reaper Mechanical and electrical operations 129

    3/16

    Bilge pumping

    A bilge alarm float switch is located just above the electric bilge pump, close to the

    base of the air compressor. Two switches on the Bilge Control Panel (a midships of

    the 24v Control Panel) control whether the siren and/or the strobe light on the mitch

    are in armed.

    There are four ways of pumping the bilges.

    Giljector

    Engine cooling water passes through a Venturi system which uplifts bilge water

    which is discharged, together with the cooling water, to the port side. Note that such

    permanent discharge of bilge may be in contravention of harbour bye-laws.

    Deckwash

    Pump 2 is engaged via an electric clutch operated by a 24Vcircuit breaker (a flashing

    LED signals when the clutch is engaged). This normally pumps sea water from the

    port seacock up through to the deck wash hose. The end fitting of the deck wash may

    connect to the fire hose fitting. However valves 4 and 5 can be set so that water is

    drawn instead from the fore and/or aft bilges (see Figure 2). If valves 4 and 6 are left

    in a half open position a back siphon can form which will flood the bilges and sink

    the Reaper. Thus always ensure that valve 5 is fully closed when the bilges are not

    b i d Bil i h ld b ti l it d i th

  • 8/7/2019 Reaper Mechanical and electrical operations 129

    4/16

    Compressed air operation

    < to be completed >

    Hydraulics operation

    < to be completed >

    Electrical

    Refer to Figures 3 and 4

    Batteries

    There are two separate 24V banks of lead acid batteries a starter set and a 150 Ah

    AGM deep cycle lighting set. Both are charged by the alternator through a diode

    splitter they are thus electrically independent. Alternator current is monitored bythe ammeter. The voltmeter can be switched to either battery or to off.

    When shore-side power is on or the diesel generator is running, the batteries can also

    be charged by the (110V input) Centaur 16A battery charger. This is an intelligent

    charger which means two things. First, whilst not good practice, it will not be harmed

    by starting the engine while charging. More importantly, it can be left on indefinitely

    without harming the batteries. Furthermore, the two outputs of the charger are

    i d d t d h b tt ill b h d di t it i t

  • 8/7/2019 Reaper Mechanical and electrical operations 129

    5/16

    of switch S2. As a safety feature, this switch is centre-off and therefore isolates the

    two supplies. Thus, in theory, both shore-side and generator could be energised at the

    same time without causing a bang - only one can be brought into circuit at any onetime. The voltage of whichever source is chosen is shown on the voltmeter (V1).

    The 110-240V transformer may be switched in circuit to provide 240 V to run the

    fridge, toaster and lifes other little essentials and also the emergency submersible

    pump. However power tools or other heavy loads should be run directly from shore-

    side power socket mentioned above. The key to the Anstruther shore-side power

    distribution box is in the fwd cabin.

    How to leave the Reaper

    See Figure 3.

    110V. Switch off shore side power by toggling the leftmost switch in the shore-side

    power panel to Off (up).

    24V. Switch off lighting battery set Isolator Switch (S1 vertical is Off). This

    means that the gas alarm is also switched off and will bleep, and must be reset, when

    the Isolator Switch is switched on again.

    G

  • 8/7/2019 Reaper Mechanical and electrical operations 129

    6/16

    Figures

    oilheatexchanger

    hydraulicheat

    exchanger

    exhaustheat

    exchanger

    P

    P

    F

    deck wash

    2

    engine

    4

    6

    Venturibilgeuplift

    outflow

    Enginecooling

    heatexchanger

    3

    inflow

    5

  • 8/7/2019 Reaper Mechanical and electrical operations 129

    7/16

    4 6

    5AftFwd

    AftF d

    Off

  • 8/7/2019 Reaper Mechanical and electrical operations 129

    8/16

  • 8/7/2019 Reaper Mechanical and electrical operations 129

    9/16

  • 8/7/2019 Reaper Mechanical and electrical operations 129

    10/16

  • 8/7/2019 Reaper Mechanical and electrical operations 129

    11/16

  • 8/7/2019 Reaper Mechanical and electrical operations 129

    12/16

    Appendix 1. Manuals

    Daewoo L136 Operation and Maintenance Manual (65.99897-8080)

    Daewoo L136 Installation Instructions (65.99898-8001B)

    Daewoo L136 Parts Book (65.99898-8082)

    Dong-I Industrial Power Take Off (Model DPO 087) Service Parts List

    Dong-I Industrial Power Take Off (Model DPO 087) Service Manual

    Markon Generator

    Ruggerini Diesel Manual

    Appendix 2. Lubricants (and related) required aboard.

    API CH-4 SAE 15W40 (engine dipstick min-max is 6 litres)

    API CH-4 SAE 30 (PTO)

    API CC SAE 30 (gearbox)API CH-4 SAE 15W40 (generator)

    SAE 15W40 (compressor)

    Hydraulic Fluid

    Antifreeze / corrosion inhibitor.

    Bilgex

    Appendix 3. Spares required aboard

  • 8/7/2019 Reaper Mechanical and electrical operations 129

    13/16

    Weekly engine room check sheet

    Date: Engine hours:

    Checked by:

    Port & Stbd fuel levels

    Check bilges for oil and water add Bilgex if needed

    Check electric bilge pump operation

    Check bilge alarm

    Oil generator SAE 15W40

    Oil engine SAE 15W40

    Oil PTO SAE 30

    Oil gearbox SAE 30Water separator bulb

    Coolant level

    Starting battery charge (v)

    Lighting battery charge (v)

    ______________________

  • 8/7/2019 Reaper Mechanical and electrical operations 129

    14/16

    Monthly engine room check sheet

    Date: Engine hours:

    Checked by:

    Complete weekly check

    Run engine

    Ensure control panel readings within spec

    Check belt tension / wear

    Run deckwash

    Run hydraulics

    Run compressorRun generator

    Check lubricant stocks

    Check battery electrolyte levels

    Grease propeller shaft bearing

    Check seacock filters

    ______________________

  • 8/7/2019 Reaper Mechanical and electrical operations 129

    15/16

  • 8/7/2019 Reaper Mechanical and electrical operations 129

    16/16

    - 16 -

    Start up Shut down

    Ensure emergency fuel valves are open Press OFF button

    Ensure gearbox in neutral Key to OFF

    Key to ON In case of fire close emergency fuel valves

    remotely using the two pull-toggles next to the

    bunks in the aft cabin.

    Key to START

    Monitor engine panel & cooling discharge

    Voltage charging 28-29 V

    engine off 24 V

    Gearbox oil

    pressure

    neutral 2-4 bar

    engaged 20-24 bar

    Water temp 71-85 C Revs 2,200 rpm max

    Oil pressure idling 1 bar

    rated speed 3-5 barEngine Control Panel Notice