RAFT SLAB - PREREQUISITE FOR SUPERSHIELD WATERPROOFING TREATMENT
l The RAFT SLAB that is to be treated should be minimum 7 days old.
SUPERSHIELD SPECIFICATION AND APPLICATION METHODOLOGY
Provide, mix and brush apply two coat of SUPERSHIELD CRYSTALGUARD, single compound Deep Penetrating
Capillary (DPC) waterproofing system that generates a non-soluble crystalline formation of dendritic fibers within
the pores and capillary tracts of the concrete @ 1.5 Kg/m² for two coats on the RAFT SLAB.
1) Surface preparation - The concrete substrate that is to be applied with SUPERSHIELD CRYSTALGUARD must
be free from foreign materials and to be micro cleaned by mechanical means like wire brushing or vacuum
cleaning.
2) Pre-wetting - Concrete surface must be thoroughly saturated with clean water prior to the coating to ensure
moisture presence inside the pores and capillaries and remove any excess water and ensure surface is touch dry
while coating.
3) Mixing of CRYSTALGUARD - Mix SUPERSHIELD CRYSTALGUARD powder with clean water to form a slurry
consistency with 5 parts of powder and 2 parts of water.
4) Application of CRYSTALGUARD - Apply the first coat of SUPERSHIELD CRYSTALGUARD as a slurry
consistency on the concrete surface.
5) Second coat of CRYSTALGUARD - Apply the second coat of SUPERSHIELD CRYSTALGUARD as a slurry
consistency on the first coat after a minimum of 4 hours gap.
Concrete Substrate
Application Methodology
WATERPROOFING SPECIFICATIONS AND METHODOLOGIES
RAFT SLAB 101 2TWO COATS OF CRYSTALGUARD @1.5 Kg/m
RAFT SLAB - 101 Page 1 of 3
Concrete Waterproofing and Durability Enhancement Using Supershield DPC Crystalline Technology
RAFT SLAB
PLAIN CEMENT CONCRETE
SUPERSHIELD CRYSTALGUARDULTIMA COATING
SUPERSHIELD CRYSTALGUARDCOATING
Curing
Watch Points
Performance Criteria
Quality Assurance
l The SUPERSHIELD CRYSTALGUARD coating should be cured with a misty fog spray of clean water, 24 hours
after the application and to be kept moist for minimum 3 days.
Cracks, horizontal, vertical joint sealing, tie hole, pipe penetrations, construction joints, expansion joints and
other defects in the concrete that is to be waterproofed should be treated as per the SUPERSHIELD specification
and application methodology.
Crystalline waterproofing system should meet or exceed the performance requirements as specified herein.
l Crystalline Penetration : Crystallizing capability of waterproofing material shall be evidenced by
independent SEM (Scanning Electron Microscope) photographs documenting penetration of needle like
crystal formation deep within concrete.
l Self-healing capability and permeability resistance : Independent testing performed according to U.S. Army
Corps of Engineers CRD-C48-73 "Permeability of Concrete".
l Testing on the effectiveness of coating from negative side of concrete : Independent testing that
demonstrates the capability of the coating to seal the leakage/dampness from negative side.
l Resistance to chloride ion penetration : Independent testing performed according to ASTM C 1202-03
should exhibit a resistance of 100% better than that of the untreated specimen.
l Potable Water Approval : Independent testing shall be performed according to EN or NSF Standard 61, and
approval for the use of waterproofing material on structures holding potable water shall be evidenced.
A) Manufacturer : Manufacturer should publish a third party product quality assurance certificate from a notified
body with continuous surveillance audit or CE certificate with FPC (Factory Production Control) as per the
harmonized standard EN to prove that the facility from where the material is produced for the project has
undergone the required testing and extensive inspection and is under continuous surveillance by a notified body
appointed by the European Union as per the European norms for the system. Manufacturers who cannot provide
the performance test data specified herein and FPC certificate shall not be considered for the project.
B) Applicator : Waterproofing applicator shall be experienced in the installation of cementitious crystalline
waterproofing materials and shall be approved by the manufacturer in writing.
www.supershieldglobal.com
WATERPROOFING SPECIFICATIONS AND METHODOLOGIES
RAFT SLAB - 101 Page 2 of 3
RAFT SLAB 101 2TWO COATS OF CRYSTALGUARD @1.5 Kg/m
Concrete Waterproofing and Durability Enhancement Using Supershield DPC Crystalline Technology
Warranty
Submittals
A) Manufacturer's Warranty : Manufacturer shall provide standard product warranty executed by authorised
company official.
B) Applicator's Warranty : Applicator shall warrant the waterproofing installation against defects caused by faulty
workmanship or materials for a period of (specify term) years from Date of Substantial Completion. The warranty
will cover the surfaces treated and will bind the applicator to repair, at his expense, any and all leaks through the
treated surfaces which are not due to structural weaknesses or other causes beyond applicator's control such as
fire, earthquake and cyclone.
Product data sheets, Application guidelines, Material safety data sheet, CE certificate, Summary of test reports.
www.supershieldglobal.com
WATERPROOFING SPECIFICATIONS AND METHODOLOGIES
RAFT SLAB - 101 Page 3 of 3
RAFT SLAB 101 2TWO COATS OF CRYSTALGUARD @1.5 Kg/m
Concrete Waterproofing and Durability Enhancement Using Supershield DPC Crystalline Technology
WATERPROOFING SPECIFICATIONS AND METHODOLOGIES
RAFT SLAB 102
Concrete Waterproofing and Durability Enhancement Using Supershield DPC Crystalline Technology
www.supershieldglobal.com
RAFT SLAB - PREREQUISITE FOR SUPERSHIELD WATERPROOFING TREATMENT
l The RAFT SLAB that is to be treated should be minimum 7 days old.
SUPERSHIELD SPECIFICATION AND APPLICATION METHODOLOGY
Provide, mix and brush apply one coat of SUPERSHIELD CRYSTALGUARD, single compound Deep Penetrating
Capillary (DPC) waterproofing system @ 0.75 Kg/m² and one coat of SUPERSHIELD CRYSTALGUARD ULTIMA,
single compound highly concentrated crystalline coating as a top coat that generates a non-soluble crystalline
formation of dendritic fibers within the pores and capillary tracts of the concrete with hard surface finish @ 0.75
Kg/m² on the RAFT SLAB.
1) Surface preparation - The concrete substrate that is to be applied with SUPERSHIELD CRYSTALGUARD/
ULTIMA must be free from foreign materials and to be micro cleaned by mechanical means like wire brushing or
vacuum cleaning.
2) Pre-wetting - Concrete surface must be thoroughly saturated with clean water prior to the coating to ensure
moisture presence inside the pores and capillaries and remove any excess water and ensure surface is touch dry
while coating.
3) Mixing of CRYSTALGUARD - Mix SUPERSHIELD CRYSTALGUARD powder with clean water to form a slurry
consistency with 5 parts of powder and 2 parts of water.
4) Application of CRYSTALGUARD - Apply the first coat of SUPERSHIELD CRYSTALGUARD as a slurry
consistency on the concrete surface.
Concrete Substrate
Application Methodology
ONE COAT OF CRYSTALGUARD & ONE COAT OF CRYSTALGUARD ULTIMA @ 1.5 Kg/m²
RAFT SLAB - 102 Page 1 of 3
RAFT SLAB
PLAIN CEMENT CONCRETE
SUPERSHIELD CRYSTALGUARDSECOND COAT
SUPERSHIELD CRYSTALGUARDFIRST COAT
5) Mixing of CRYSTALGUARD ULTIMA - Mix SUPERSHIELD CRYSTALGUARD ULTIMA powder with clean water
to form a slurry consistency with 5 parts of powder and 2 parts of water.
6) Application of CRYSTALGUARD ULTIMA - Apply one coat of SUPERSHIELD CRYSTALGUARD ULTIMA as a
slurry consistency on the CRYSTALGUARD coating minimum after 4 hours gap as a top coating.
l The SUPERSHIELD CRYSTALGUARD/ ULTIMA coating should be cured with a misty fog spray of clean water,
24 hours after the application and to be kept moist for minimum 3 days.
Cracks, horizontal, vertical joint sealing, tie hole, pipe penetrations, construction joints, expansion joints and
other defects in the concrete that to be waterproofed should be treated as per the SUPERSHIELD specification
and application methodology.
Crystalline waterproofing system should meet or exceed the performance requirements as specified herein.
l Crystalline Penetration : Crystallizing capability of waterproofing material shall be evidenced by
independent SEM (Scanning Electron Microscope) photographs documenting penetration of needle like
crystal formation deep within concrete.
l Self-healing capability and permeability resistance : Independent testing performed according to U.S. Army
Corps of Engineers CRD-C48-73 "Permeability of Concrete".
l Testing on the effectiveness of coating from negative side of concrete : Independent testing that
demonstrates the capability of the coating to seal the leakage/dampness from negative side.
l Resistance to chloride ion penetration : Independent testing performed according to ASTM C 1202-03
should exhibit a resistance of 100% better than that of the untreated specimen.
l Potable Water Approval : Independent testing shall be performed according to EN or NSF Standard 61, and
approval for theuse of waterproofing material on structures holding potable water shall be evidenced.
A) Manufacturer : Manufacturer should publish a third party product quality assurance certificate from a notified
body with continuous surveillance audit or CE certificate with FPC (Factory Production Control) as per the
harmonized standard EN to prove that the facility from where the material is produced for the project has
undergone the required testing and extensive inspection and is under continuous surveillance by a notified body
appointed by the European Union as per the European norms for the system. Manufacturers who cannot provide
the performance test data specified herein and FPC certificate shall not be considered for the project.
B) Applicator : Waterproofing applicator shall be experienced in the installation of cementitious crystalline
Curing
Watch Points
Performance Criteria
Quality Assurance
www.supershieldglobal.com
WATERPROOFING SPECIFICATIONS AND METHODOLOGIES
RAFT SLAB - 102 Page 2 of 3
RAFT SLAB 102
Concrete Waterproofing and Durability Enhancement Using Supershield DPC Crystalline Technology
ONE COAT OF CRYSTALGUARD & ONE COAT OF CRYSTALGUARD ULTIMA @ 1.5 Kg/m²
waterproofing materials and shall be approved by the manufacturer in writing.
A) Manufacturer's Warranty : Manufacturer shall provide standard product warranty executed by authorised
company official.
B) Applicator's Warranty : Applicator shall warrant the waterproofing installation against defects caused by faulty
workmanship or materials for a period of (specify term) years from Date of Substantial Completion. The warranty
will cover the surfaces treated and will bind the applicator to repair, at his expense, any and all leaks through the
treated surfaces which are not due to structural weaknesses or other causes beyond applicator's control such as
fire, earthquake and cyclone.
Product data sheets, Application guidelines, Material safety data sheet, CE certificate, Summary of test reports.
Warranty
Submittals
www.supershieldglobal.com
WATERPROOFING SPECIFICATIONS AND METHODOLOGIES
RAFT SLAB - 102 Page 3 of 3
RAFT SLAB 102
Concrete Waterproofing and Durability Enhancement Using Supershield DPC Crystalline Technology
ONE COAT OF CRYSTALGUARD & ONE COAT OF CRYSTALGUARD ULTIMA @ 1.5 Kg/m²
www.supershieldglobal.com
RAFT SLAB - PREREQUISITE FOR SUPERSHIELD WATERPROOFING TREATMENT
l The RAFT SLAB that is to be treated should be minimum 7 days old.
l The pipe penetrations through the horizontal brick walls should be packed and plastered to a
minimum thickness of 25 mm with the ratio of 1:3 cement mortar.
l The side walls that are of non-concrete should be plastered to a minimum thickness of 25 mm with the ratio
of 1:3 cement mortar to a height of minimum 6" above the nearest floor level.
SUPERSHIELD SPECIFICATION AND APPLICATION METHODOLOGY
Provide, and spray apply one coat of SUPERSHIELD MULTISEAL 100, water based colorless liquid enhanced
with Multiseal technology that forms hydrated and hygroscopic crystals in the pores and capillary tracts of the
concrete with a repellant barrier finish on the surface @ 200 Ml/m² on the RAFT SLAB that are of concrete to the
height of 6" above the filling level.
1) Surface preparation - The concrete substrate that is to be applied with SUPERSHIELD MULTISEAL 100 must
be free from foreign materials and to be micro cleaned by mechanical means like wire brushing or vacuum
cleaning.
2) Pre-wetting - Concrete surface must be thoroughly saturated with clean water prior to the coating to ensure
moisture presence inside the pores and capillaries and remove any excess water and ensure surface is
predominantly dry while coating to enhance SUPERSHIELD MULTISEAL 100 impregnation.
3) Mixing of MULTISEAL 100 - No mixing is required and should not be diluted with water or by any other means.
Concrete Substrate
Application Methodology
WATERPROOFING SPECIFICATIONS AND METHODOLOGIES
RAFT SLAB 103 2ONE COAT OF MULTISEAL 100 @ 200 Ml/m
RAFT SLAB - 103 Page 1 of 3
Concrete Waterproofing and Durability Enhancement Using Supershield Multiseal Technology
RAFT SLAB
PLAIN CEMENT CONCRETE
SUPERSHIELD MULTISEAL 100 COATING
4) Application of MULTISEAL 100 - Apply one coat of SUPERSHIELD MULTISEAL 100 evenly by means of
spraying and ensure the surface is completely impregnated with SUPERSHIELD MULTISEAL 100.
l The SUPERSHIELD MULTISEAL 100 coating should be air cured and protected from water/ rain for atleast 4
hours.
Cracks, horizontal, vertical joint sealing, tie hole, pipe penetrations, construction joints, expansion joints and
other defects in the concrete that to be waterproofed should be treated as per the SUPERSHIELD specification
and application methodology.
Crystalline waterproofing system should meet or exceed the performance requirements as specified herein.
l Crystalline Penetration : Crystallizing capability of waterproofing material shall be evidenced by
independent SEM (Scanning Electron Microscope) photographs documenting penetration of needle like
crystal formation deep within concrete.
l Self-healing capability and permeability resistance : Independent testing performed according to U.S. Army
Corps of Engineers CRD-C48-73 "Permeability of Concrete".
l Testing on the effectiveness of coating from negative side of concrete : Independent testing that
demonstrates the capability of the coating to seal the leakage/dampness from negative side.
l Resistance to chloride ion penetration : Independent testing performed according to ASTM C 1202-03
should exhibit a resistance of 100% better than that of the untreated specimen.
l Potable Water Approval : Independent testing shall be performed according to EN or NSF Standard 61, and
approval for the use of waterproofing material on structures holding potable water shall be evidenced.
A) Manufacturer : Manufacturer should publish a third party product quality assurance certificate from a notified
body with continuous surveillance audit or CE certificate with FPC (Factory Production Control) as per the
harmonized standard EN to prove that the facility from where the material is produced for the project has
undergone the required testing and extensive inspection and is under continuous surveillance by a notified body
appointed by the European union as per the European norms for the system. Manufacturers who cannot provide
the performance test data specified herein and FPC certificate shall not be considered for the project.
B) Applicator : Waterproofing applicator shall be experienced in the installation of cementitious crystalline
waterproofing materials and shall be approved by the manufacturer in writing.
Curing
Watch Points
Performance Criteria
Quality Assurance
www.supershieldglobal.com
WATERPROOFING SPECIFICATIONS AND METHODOLOGIES
RAFT SLAB - 103 Page 2 of 3
RAFT SLAB 103
Concrete Waterproofing and Durability Enhancement Using Supershield Multiseal Technology
2ONE COAT OF MULTISEAL 100 @ 200 Ml/m
Warranty
Submittals
A) Manufacturer's Warranty : Manufacturer shall provide standard product warranty executed by authorised
company official.
B) Applicator's Warranty : Applicator shall warrant the waterproofing installation against defects caused by faulty
workmanship or materials for a period of (specify term) years from Date of Substantial Completion. The warranty
will cover the surfaces treated and will bind the applicator to repair, at his expense, any and all leaks through the
treated surfaces which are not due to structural weaknesses or other causes beyond applicator's control such as
fire, earthquake and cyclone.
Product data sheets, Application guidelines, Material safety data sheet, CE certificate, Summary of test reports.
www.supershieldglobal.com RAFT SLAB - 103 Page 3 of 3
WATERPROOFING SPECIFICATIONS AND METHODOLOGIES
Concrete Waterproofing and Durability Enhancement Using Supershield Multiseal Technology
2ONE COAT OF MULTISEAL 100 @ 200 Ml/m