2012
MCAC-2012-19
R410A DC Inverter VRF For North America
Commercial Air Conditioner Business UnitsMidea Air Conditioning and Refrigeration SectorAdd: West region of Midea commercial air conditioner department, Industry Avenue, Beijiao, Shunde, Foshan, Guangdong, P.R. China Postal code:528311Tel:+86-757-22394101 Fax: +86-757-26338003http://www.midea.com http://www.mideaaircon.com
Corporate Introduction
Midea CAC (MCAC)As a key part of Midea Group, the Midea Central Air Conditioner (CAC) Business Unit is a professional CAC products supplier and commercial products solution expert. Since 1999 Midea central air-conditioner contributes to the commercial product R&D and technology innovation. By cooperating with the international enterprises plus the independent R&D, Midea CAC achieves big success in the commercial air-conditioner market and has established thousands of sample projects all over the world.
Right now Midea CAC is one of the most professional CAC products supplier as well as the professional project solution provider in marketing, sales, project design and after service etc.
MCAC Chongqing factory with 14 product lines concentrates on the water cooled centrifugal / screw/ scroll chillers, Air cooled screw/ scroll chillers, AHU/FCU etc.MCAC Shunde factory with 31 product lines concentrates on the VRF (DC inverter product/ Digital scroll product), split product, heat pump water heater, AHU/FCU etc.
From its humble beginnings in 1968, Midea has developed into a large corporation, covering HVAC, appliances, lighting, industrial components, logistics, and real estate. Its 40 years of relentless growth has brought its global turnover to $14 billion USD in 2009. Consequently, Midea has created over 150,000 jobs both within China and all over the world. In addition to providing affordable goods to consumers worldwide, Midea is a responsible corporate citizen, and has contributed to several social causes. Midea believes in creating value through rapid response to market demands, cost-efficient operations and consumer satisfaction. As a result, Midea wields vast production capacities to meet these demands, a fully integrated manufacturing process, and a comprehensive range of affordable, high-quality products to serve its global customers.
Today, Midea is a home appliance leader in China. The company continues to actively globalize its operation by opening plants in Vietnam, Belarus and Egypt. Additionally, Midea has several forthcoming plants in order to offer enhanced products and services closer to the market.
Midea Group
Midea proudly introduce the R410A DC Inverter VRF products-the DC Inverter V4
Plus and Full DC Inverter Mini VRF.As a new products especially developed for
North America market, they have advantages of high efficiency,good performance
and smart control.Midea R410A DC Inverter VRF products adopt the advanced DC
inverter technology,not only have all the advantages of the VRF system-Energy
saving,Easy installation and Easy management,but also have their particular and
outstanding features. The wide capacity range and numerous of outdoor and
indoor units make they can be applicable for a variety of occasions.
Developed to facilitate more flexible system design for various of buildings
R410A DC Inverter VRF Series
Contents05
22
31
43
58
DC Inverter V4 Plus
Full DC Inverter Mini VRF
Indoor units
Control system
Accessories
R410A DC Inverter VRF 06R410A DC Inverter VRF05
Optimized fan blade shape with new air outlet grille enhanced air flow volume which makes fan performance greatly improved and without increased noise.Also, a higher external static pressure has been achieved optionally-from 0.08in.WG to 0.32in.WG.
New blade with sharp edge and little curve increases the airflow Rate and lowers down vibration and airflow resistance.
Fan grille
New profile fan blade
High performance heat exchanger
High efficiency full DC inverter compressor
Technologies
New structure-enhanced mid-frequency performanceSpecially designed scroll profile for R410A
More compact, weight reduced by 50%
Advanced permanent magnet DC motor improves the low frequency band performance
V4+ series achieves the industry's top class energy efficiency of cooling and heating by utilizing the Brushless Reluctance DC compressor control, DC Fan motor, and improved performance heat exchanger. High efficiency DC inverter compressor saves power consumption by 25%.
The V4 plus which is well flexible designed for applicable for a variety of occasions.Offering a higher capacity up to 51.2ton,meeting requirements of big capacity.It also incorporates numerous outstanding features,a larger capacity range of outdoor units and indoor units,longer level difference and actual piping and high extenal static pressure.The V4 plus VRF product provides a flexible design and easy installation in big-sized and high-rise building for wide application.
DC Inverter V4 Plus
00
0.2 0.4 0.6 0.8 1
0.2
0.4
0.6
0.8
New design
Original design
Frost contrast
Relative frosting rate
Rel
ativ
e w
inda
ge re
sist
ance
Reduce 28%
Reduce 30%
00
200 400 600 800 1000 Re
0.2
0.4
0.6
0.8
New design
Original design
Windage& air flow
Rel
ativ
e w
inda
ge re
sist
ance
New design Original design
High efficiency inner-thread pipe, enhance heater transfer.
DC Inverter V4 Plus
NEWFashionDesign
R410A DC Inverter VRF 08R410A DC Inverter VRF07
DC motor
High
Low
18 steps vector control
High efficiency MDV V4 PLUS with high efficient DC compressor and DC motor, achieved the world’s Top Class energy efficiency.
By adoption of the 180°SineWave Inverter which smooths the rotation of the motor, operation efficiency is improved sharply than traditional sawtooth wave.
Smooth 180°sine wave DC Inverter
DC fan motor
HIGH EFFICIENCYCompressor efficiency
Effic
ienc
y-R
otor
Spe
ed C
urve
New DC motor-centralized winding
Common DC motor-distributing winding
20 40 60 80 100Rotor speed(s-1)
According to the running load and pressure, it controls the speed of DC fan to achieve the min. power consumption.
Used across entire range of models (from 7.2~51.2Ton).Efficiency improvement by up to 45% especially at low speed.
Powerful magnets provide high torque and efficiency and achieve 70% reduction in volume. Main Features
Wide operation Range
V4 PLUS intelligent defrost improve the heat capacity Common sawtooth wave 180° Sine Wave DC inverter
Centralizing winding
Distributing winding
20
40
60
80100
200 1000
45%Increased by
MOTOR SPEED (RPM)
EFFI
CIE
NC
Y (%
)
defrost191.3182.4173.4164.4155.4146.4137.4128.4119.4110.4101.492.483.474.465.456.447.438.429.420.411.42.4
-6.6-15.6-24.6-33.6-42.6-51.6-60.6
Ther
moc
oupl
e te
mp(
°F)
180.4171.4162.4153.4144.4135.4126.4117.4108.499.490.481.472.463.454.445.436.427.418.49.40.4
-8.6-17.6
Ther
moc
oupl
e te
mp(
°F)
Outdoor Temperature
COOLING MODE
HEATING MODE
Outdoor temp. °F(D.B.)
118.4°F
80.6°F-4°F
23°F Outdoor Temperature
No matter in extremely cold winter when outdoor temperature down to as low as -4°For in hot summer when temperature is up to 118°F, the V4+ system will keep stable operation.
-4°F 14°F 32°F 50°F 68°F 86°F 104°F 122°F
R410A DC Inverter VRF 10R410A DC Inverter VRF09
HIGHER RELIABILITY
High efficiency oil balance and oil return technology
In one combination, any of the outdoor unit can run as the master outdoor unit, to realize the equal lifespan among the outdoor units in the combination.
Alternative Cycle Duty operation of outdoor units
Any single unit can be set as the master unit in a multiple system when the previous master unit failed and other units left will keep on operating. This can be set on PCB by DIP switches at site.
Outdoor module Back up operation
From evaporator
Enter condenser
Oil balance pipe between modules
Oil separator
Oil even pipe I
Suction pipe
Refrigerant flow direction
Dis
char
ge p
ipe
Oil even pipe II
Oil balance pipes among modules and individual oil balance by vector control ensure even oil distribution among the modules which keeps compressor running nomally. High effciency centrifugal oil separator(up to 99%)makes oil separate from discharge and go back to compressor.Auto oil return program by monitoring the running time and state of system ensures reliable oil return.
2
noisc
ENHANCED COMFORTIntelligent soft start technology
Nighttime silent operation mode
DC inverter compressor soft start function reduces strike to the electric network. This kind of high-performance and low sound scroll compressor operates at a faster rate when starting, reducing start-up time. It helps the unit to bring the room temperature up to the set level quickly.
Midea's Night Silent Mode feature which is easily set on the PCB board allows the unit to be set to varies time options during Non Peak and Peak operation time optimizing the units noise output. Extra silent operation mode can reduce sound level further, minimum 46.8dB (A).Nighttime silent operation will be activated X hours after the peak temperature during daytime, and it will go back to normal operation after Y hours.
-Model 1→X: 6 hours, Y: 10 hours -Model 2→X: 8 hours, Y: 10 hours-Model 3→X: 6 hours, Y: 12 hours -Model 4→X: 8 hours, Y: 8 hours
Notes: This function can be activatedby setting at site. Temperature(load) curve shown in the graph is just an example.
*1&*2 can be set on PCB board by DIP switch S2.
8:00
100
50
12:00 16:00 20:00 0:00 4:00 8:00
Peak value of ambient temp.
Noi
se d
BLo
ad %
Cap
acity
%
8hrs 10hrs
Night silent ModeMax.-10dB(10Hp)
EndStart
Utilizing the scroll compressor benefits,V4 plus system can reach full load quickly and shorten warm-up or cool-down time for an immediately.
Quick warm-up & cool-down design
1 2 3 4 5 6
600
500
400
300
200
100
Comparison of start by inverter and bytraditional methods
Direct startY-△ startStart by inverter
Starting current(%)
(Sec)
6/10H
ON
1 2 3
NIGHT TM
8/10H
ON
1 2 3
NIGHT TM
8/12H
ON
1 2 3
NIGHT TM
8/8H
ON
1 2 3
NIGHT TM
Fluctuation of room temperature
Cooling operation
1
8, 10HP(7.2,8Ton)
R410A DC Inverter VRFR410A DC Inverter VRF11 12
7.2
8
9.5
11.4
12.8
15.2
16
17.5
19.4
20.8
22.8
24.2
25.6
27.4
28.8
30.3
32.2
34.2
35.6
37
38.4
40.8
41.6
43.1
45
47
48.4
49.8
51.2
MDV-252(8)W/DXN1(B)
MDV-280(10)W/DXN1(B)
MDV-335(12)W/DXN1(B)
MDV-400(14)W/DXN1(B)
MDV-450(16)W/DXN1(B)
MDV-532(18)W/DXN1(B)
MDV-560(20)W/DXN1(B)
MDV-615(22)W/DXN1(B)
MDV-680(24)W/DXN1(B)
MDV-730(26)W/DXN1(B)
MDV-785(28)W/DXN1(B)
MDV-850(30)W/DXN1(B)
MDV-900(32)W/DXN1(B)
MDV-960(34)W/DXN1(B)
MDV-1010(36)W/DXN1(B)
MDV-1065(38)W/DXN1(B)
MDV-1130(40)W/DXN1(B)
MDV-1180(42)W/DXN1(B)
MDV-1235(44)W/DXN1(B)
MDV-1300(46)W/DXN1(B)
MDV-1350(48)W/DXN1(B)
MDV-1432(50)W/DXN1(B)
MDV-1460(52)W/DXN1(B)
MDV-1515(54)W/DXN1(B)
MDV-1580(56)W/DXN1(B)
MDV-1630(58)W/DXN1(B)
MDV-1685(60)W/DXN1(B)
MDV-1750(62)W/DXN1(B)
MDV-1800(64)W/DXN1(B)
13
16
16
16
20
20
24
24
28
28
28
32
32
36
36
36
42
42
42
48
48
54
54
54
58
58
58
64
64
Recommended combination Max. indoor
units nos.
Capacity
(Ton)Model
7.2Ton 8Ton 9.5Ton 11.5Ton 12.8Ton
Outdoor unit combination
FLEXIBILITY DESIGN FOR BIG SIZED BUILDING
The outdoor units capacity range from 7.2~51.2 ton.Maximum 64 indoor units with capacity up to 130% of total outdoor units can be connected as one refrigeration system.
Large capacity for big sized building
Maximum indoor unit quantity
MaximumCapacity51.2Ton
Maximum indoorunit quantity64 sets
15.2,16,17.5,19.4,20.8,22.8,24.2,25.6Ton
40.8,41.6,43.1,45,47,48.4,49.8,51.2 Ton27.4,28.8,30.3,32.2,34.2,35.6,37,38.4Ton
7.2,8Ton 9.5,11.4,12.8Ton
R410A DC Inverter VRF 14R410A DC Inverter VRF13
Long Piping Length
Extra high static pressure – Max. 0.32in.WG and air volume increased by 10%
High static pressure propeller and optimum fan guard are used to adapt forvarious installation environments.Midea now offers up to 0.32in.WG external static pressure units as an option (need customization) while a standard 0-0.08in.WG function is equipped as default.
*Total pipe length is equal to gas pipe or liquid pipe length.*Level difference above 164ft. are not supported by default but are available on request for customized.
Permitted value
Total pipe length*(Actual)
Maximum piping(L)
Piping length
Drop height
Indoor unit to indoor unit drop height
Indoor unit-outdoor
unit drop height
Piping (farthest from the first line pipe branch) equivalent length
Outdoor unit up
Outdoor unit down
230ft.*
230ft.
49ft.
Actual length
Equivalent length
≤24Ton
>24Ton
1148ft.
1640ft.
492ft.
574ft.
131f
t.
Max
imum
pip
ing
actu
al le
ngth
492
ft.
Indo
or u
nit-I
ndoo
r uni
tdr
op h
eigh
t 49f
t.
Out
door
uni
t-Ind
oor u
nit d
rop
heig
ht 2
30ft.
EASIER INSTALLATION AND SERVICECompact Design for Effective Use of Space
Easy to transport
Compact size and light weight design minimizes the installation footprint, reduces the installation floor load, and easier for transportation. For some projects the units can even be transported through the elevator or forklift, lessen access problem at the jobsite.
81.8 Pa
131ft.
Model Btu/h
Type Four-way Cassette Concealed Duct (A5 type) High Pressure Duct Wall-mounted S type Ceilling & Floor Type
MDV-D XX Q4/VN1-D MDV-D XX T2/VN1-CA5 MDV-D XX T1/VN1-B MDV-D XX G/VN1-S MDV-D XX DL/VN1-C
22
28
36
45
56
71
80
90
100
112
140
160
7500
9000
12000
15000
19000
24000
27000
30000
34000
38000
48000
55000
R410A DC Inverter VRF 16R410A DC Inverter VRF15
Simple signal line connection
Remote addressing
Installation is made easier as the communication wiring between indoor & outdoor units can be shared. It’s easy for the user to retrofit the existing system with a centralized control by simply connecting to the outdoor units.
PQE & XYE, just only one group of communication wire of PQE, achieved both of communication for indoor & outdoor unit and network. Reversible communication, central controller can be connected from indoor side or outdoor side as you wish.
Addressing indoor units are able to be done just by pressing the button of the controller.No need to set the address by the DIP switch one by one.Wired controller and wireless controller can enquire and modify every indoor units address.
Easy access
AutomaticallyIdentify
Improved onV4 plus
PreviousDesignNeed To Set The
Address Manually,one By One
01234
56789ABC
D
EF
Reserved checking window on electric control box for convenient spot checking and status enquiry.
Compressors locate at near door position which is convenient for checking or replacing the valves or compressor parts.
P Q E
P Q E P Q E P Q E P Q E P Q E
P Q E
P Q E
X Y E X Y E
Outdoor Units LineupMDV-252(8)W/DXN1(B)
MDV-280(10)W/DXN1(B)
MDV-335(12)W/DXN1(B)
MDV-400(14)W/DXN1(B)
MDV-450(16)W/DXN1(B)
Outdoor Unit
Specifications
208~230V-3Ph-60Hz
86,000
92,000
2
6,870
57
63-9/16
30-1/8
540
R410A
22
Ф1/2
Ф1
208~230V-3Ph-60Hz
96,000
108,000
2
6,870
57
63-9/16
30-1/8
540
R410A
22
Ф1/2
Ф1
208~230V-3Ph-60Hz
114,000
128,000
2
9,080
59
63-9/16
30-1/8
607
R410A
26.5
Ф1/2
Ф1-1/8
208~230V-3Ph-60Hz
136,000
154,000
3
9,080
60
63-9/16
30-1/8
717
R410A
33
Ф1/2
Ф1-1/8
208~230V-3Ph-60Hz
154,000
171,000
3
9,080
60
63-9/16
30-1/8
717
R410A
33
Ф5/8
Ф1-1/8
V-Ph-Hz
Btu/h
Btu/h
Type
Num.
CFM
dB(A)
in.
in.
in.
lbs
lbs
in.
in.
Model
Constituent Unit
Power supply
Capacity
Compressor Configration
Cooling (*1)
Heating (*2)
Width
Hength
Depth
37-25/32 49-7/32
Liquid side
Gas side
Outdoor unit
Dimension
Air flow
Sound level (*3)
Hermetically sealed scroll type
Net weight
Refrigerant
Refrigerant Charged Volume
MDV-252(8)W/DXN1(B) MDV-280(10)W/DXN1(B) MDV-335(12)W/DXN1(B) MDV-400(14)W/DXN1(B) MDV-450(16)W/DXN1(B)
Refrigerant piping
Cooling
Heating
Indoor Outdoor Piping length Level difference
80.6°F DB,60°FWB
68°F DB,60°FWB
95°F DB
42.8°F DB
24.6ft.
24.6ft.
0ft.
0ft.
Notes:1.Nominal conditions
2.Sound level:Anechoic chamber connersion value,measure at the position 3.28ft. at the front of the e unit and 4.92ft. above the floor.3.Refrigerant pipe dim.listed here only for when the total equivalent length <295ft. For the data when total quivalent length ≥295ft. please refer to technical manual.4.The above data may be changed without notice for furture improvement on quality and performance.
R410A DC Inverter VRF 18R410A DC Inverter VRF17
MDV-532(18)W/DXN1(B)
MDV-560(20)W/DXN1(B)
MDV-615(22)W/DXN1(B)
MDV-680(24)W/DXN1(B)
MDV-730(26)W/DXN1(B)
Outdoor Unit
MDV-785(28)W/DXN1(B)
MDV-850(30)W/DXN1(B)
MDV-900(32)W/DXN1(B)
MDV-960(34)W/DXN1(B)
MDV-1010(36)W/DXN1(B)
Outdoor Unit
37-25/32+37-25/32 37-25/32+49-7/32
MDV-400(14)W/DXN1(B)
MDV-400(14)W/DXN1(B)
MDV-400(14)W/DXN1(B)
MDV-450(16)W/DXN1(B)
MDV-450(16)W/DXN1(B)
MDV-450(16)W/DXN1(B)
MDV-280(10)W/DXN1(B)
MDV-280(10)W/DXN1(B)
MDV-400(14)W/DXN1(B)
MDV-280(10)W/DXN1(B)
MDV-280(10)W/DXN1(B)
MDV-450(16)W/DXN1(B)
Specifications
Cooling
Heating
Indoor Outdoor Piping length Level difference
80.6°F DB,60°FWB
68°F DB,60°FWB
95°F DB
42.8°F DB
24.6ft.
24.6ft.
0ft.
0ft.
Notes:1.Nominal conditions
2.Sound level:Anechoic chamber connersion value,measure at the position 3.28ft. at the front of the e unit and 4.92ft. above the floor.3.Refrigerant pipe dim.listed here only for when the total equivalent length <295ft. For the data when total quivalent length ≥295ft. please refer to technical manual.4.The above data may be changed without notice for furture improvement on quality and performance.
MDV-252(8)W/DXN1(B)
MDV-280(10)W/DXN1(B)
208~230V-3Ph-60Hz
182,000
200,000
13,740
61
63-9/16
30-1/8
540+540
R410A
22+22
Ф5/8
Ф1-1/4
MDV-280(10)W/DXN1(B)
MDV-280(10)W/DXN1(B)
208~230V-3Ph-60Hz
192,000
216,000
13,740
61
63-9/16
30-1/8
540+540
R410A
22+22
Ф5/8
Ф1-1/4
MDV-280(10)W/DXN1(B)
MDV-335(12)W/DXN1(B)
208~230V-3Ph-60Hz
210,000
236,000
15,950
62
63-9/16
30-1/8
540+607
R410A
22+26.5
Ф5/8
Ф1-1/4
MDV-280(10)W/DXN1(B)
MDV-400(14)W/DXN1(B)
208~230V-3Ph-60Hz
232,000
262,000
15,950
62
63-9/16
30-1/8
540+717
R410A
22+33
Ф5/8
Ф1-1/4
MDV-280(10)W/DXN1(B)
MDV-450(16)W/DXN1(B)
208~230V-3Ph-60Hz
250,000
279,000
15,950
62
63-9/16
30-1/8
540+717
R410A
22+33
Ф3/4
Ф1-3/8
V-Ph-Hz
Btu/h
Btu/h
CFM
dB(A)
in.
in.
in.
lbs
lbs
in.
in.
Model
Constituent Units
Power supply
Capacity Cooling (*1)
Heating (*2)
Width
Hength
Depth
Liquid side
Gas side
Outdoor unit
Dimension
Compressor Configration
Air flow
Sound level (*3)
Hermetically sealed scroll type
Net weight
Refrigerant
Refrigerant Charged Volume
MDV-532(18)W/DXN1(B) MDV-560(20)W/DXN1(B) MDV-615(22)W/DXN1(B) MDV-680(24)W/DXN1(B) MDV-730(26)W/DXN1(B)
Refrigerant piping
49-7/32+49-7/32 37-25/32+49-7/32+49-7/32
Specifications
Cooling
Heating
Indoor Outdoor Piping length Level difference
80.6°F DB,60°FWB
68°F DB,60°FWB
95°F DB
42.8°F DB
24.6ft.
24.6ft.
0ft.
0ft.
Notes:1.Nominal conditions
2.Sound level:Anechoic chamber connersion value,measure at the position 3.28ft. at the front of the e unit and 4.92ft. above the floor.3.Refrigerant pipe dim.listed here only for when the total equivalent length <295ft. For the data when total quivalent length ≥295ft. please refer to technical manual.4.The above data may be changed without notice for furture improvement on quality and performance.
208~230V-3Ph-60Hz
272,000
308,000
18,160
63
63-9/16
30-1/8
717+717
R410A
33+33
Ф3/4
Ф1-3/8
208~230V-3Ph-60Hz
290,000
325,000
18,160
63
63-9/16
30-1/8
717+717
R410A
33+33
Ф3/4
Ф1-3/8
208~230V-3Ph-60Hz
308,000
342,000
18,160
63
63-9/16
30-1/8
717+717
R410A
33+33
Ф3/4
Ф1-3/8
208~230V-3Ph-60Hz
328,000
370,000
22,820
64
63-9/16
30-1/8
540+540+717
R410A
22+22+33
Ф3/4
Ф1-5/8
208~230V-3Ph-60Hz
346,000
387,000
22,820
64
63-9/16
30-1/8
540+540+717
R410A
22+22+33
Ф3/4
Ф1-5/8
V-Ph-Hz
Btu/h
Btu/h
CFM
dB(A)
in.
in.
in.
lbs
lbs
in.
in.
Model
Constituent Units
Power supply
Capacity Cooling (*1)
Heating (*2)
Width
Hength
Depth
Liquid side
Gas side
Outdoor unit
Dimension
Compressor Configration
Air flow
Sound level (*3)
Hermetically sealed scroll type
Net weight
Refrigerant
Refrigerant Charged Volume
MDV-785(28)W/DXN1(B) MDV-850(30)W/DXN1(B) MDV-900(32)W/DXN1(B) MDV-960(34)W/DXN1(B) MDV-1010(36)W/DXN1(B)
Refrigerant piping
R410A DC Inverter VRF 20R410A DC Inverter VRF19
MDV-1065(38)W/DXN1(B)
MDV-1130(40)W/DXN1(B)
MDV-1180(42)W/DXN1(B)
MDV-1235(44)W/DXN1(B)
MDV-1300(46)W/DXN1(B)
Outdoor UnitMDV-1350(48)W/DXN1(B)
MDV-1432(50)W/DXN1(B)
MDV-1460(52)W/DXN1(B)
MDV-1515(54)W/DXN1(B)
MDV-1580(56)W/DXN1(B)
Outdoor Unit
MDV-400(14)W/DXN1(B)
MDV-400(14)W/DXN1(B)
MDV-450(16)W/DXN1(B)
MDV-400(14)W/DXN1(B)
MDV-450(16)W/DXN1(B)
MDV-450(16)W/DXN1(B)
MDV-280(10)W/DXN1(B)
MDV-400(14)W/DXN1(B)
MDV-450(16)W/DXN1(B)
MDV-280(10)W/DXN1(B)
MDV-335(12)W/DXN1(B)
MDV-450(16)W/DXN1(B)
MDV-400(14)W/DXN1(B)
MDV-400(14)W/DXN1(B)
MDV-400(14)W/DXN1(B)
MDV-450(16)W/DXN1(B)MDV-450(16)W/DXN1(B)MDV-450(16)W/DXN1(B)
MDV-252(8)W/DXN1(B)MDV-280(10)W/DXN1(B)MDV-450(16)W/DXN1(B)MDV-450(16)W/DXN1(B)
MDV-280(10)W/DXN1(B)MDV-280(10)W/DXN1(B)MDV-450(16)W/DXN1(B)MDV-450(16)W/DXN1(B)
MDV-280(10)W/DXN1(B)MDV-335(12)W/DXN1(B)MDV-450(16)W/DXN1(B)MDV-450(16)W/DXN1(B)
MDV-280(10)W/DXN1(B)MDV-400(14)W/DXN1(B)MDV-450(16)W/DXN1(B)MDV-450(16)W/DXN1(B)
37-25/32+37-25/32+49-7/32+49-7/32 49-7/32+49-7/32+49-7/32 37-25/32+49-7/32+49-7/32+49-7/3237-25/32 49-7/32+49-7/32+49-7/32
Specifications
Cooling
Heating
Indoor Outdoor Piping length Level difference
80.6°F DB,60°FWB
68°F DB,60°FWB
95°F DB
42.8°F DB
24.6ft.
24.6ft.
0ft.
0ft.
Notes:1.Nominal conditions
2.Sound level:Anechoic chamber connersion value,measure at the position 3.28ft. at the front of the e unit and 4.92ft. above the floor.3.Refrigerant pipe dim.listed here only for when the total equivalent length <295ft. For the data when total quivalent length ≥295ft. please refer to technical manual.4.The above data may be changed without notice for furture improvement on quality and performance.
208~230V-3Ph-60Hz
364,000
407,000
25,030
65
63-9/16
30-1/8
540+607+717
R410A
22+26.5+33
Ф3/4
Ф1-5/8
208~230V-3Ph-60Hz
386,000
433,000
25,030
65
63-9/16
30-1/8
540+717+717
R410A
22+33+33
Ф3/4
Ф1-5/8
208~230V-3Ph-60Hz
408,000
462,000
27,240
65
63-9/16
30-1/8
717+717+717
R410A
33+33+33
Ф3/4
Ф1-5/8
208~230V-3Ph-60Hz
426,000
479,000
27,240
65
63-9/16
30-1/8
717+717+717
R410A
33+33+33
Ф3/4
Ф1-5/8
208~230V-3Ph-60Hz
444,000
496,000
27,240
65
63-9/16
30-1/8
717+717+717
R410A
33+33+33
Ф3/4
Ф1-5/8
V-Ph-Hz
Btu/h
Btu/h
CFM
dB(A)
in.
in.
in.
lbs
lbs
in.
in.
Model
Constituent Units
Power supply
Capacity Cooling (*1)
Heating (*2)
Width
Hength
Depth
Liquid side
Gas side
Outdoor unit
Dimension
Compressor Configration
Air flow
Sound level (*3)
Hermetically sealed scroll type
Net weight
Refrigerant
Refrigerant Charged Volume
MDV-1065(38)W/DXN1(B) MDV-1130(40)W/DXN1(B) MDV-1180(42)W/DXN1(B) MDV-1235(44)W/DXN1(B) MDV-1300(46)W/DXN1(B)
Refrigerant piping
Specifications
Cooling
Heating
Indoor Outdoor Piping length Level difference
80.6°F DB,60°FWB
68°F DB,60°FWB
95°F DB
42.8°F DB
24.6ft.
24.6ft.
0ft.
0ft.
Notes:1.Nominal conditions
2.Sound level:Anechoic chamber connersion value,measure at the position 3.28ft. at the front of the e unit and 4.92ft. above the floor.3.Refrigerant pipe dim.listed here only for when the total equivalent length <295ft. For the data when total quivalent length ≥295ft. please refer to technical manual.4.The above data may be changed without notice for furture improvement on quality and performance.
208~230V-3Ph-60Hz
462,000
513,000
27,240
65
63-9/16
30-1/8
717+717+717
R410A
33+33+33
Ф3/4
Ф1-5/8
208~230V-3Ph-60Hz
490,000
542,000
31,900
66
63-9/16
30-1/8
540+540+717+717
R410A
22+22+33+33
Ф7/8
Ф1-3/4
208~230V-3Ph-60Hz
500,000
558,000
31,900
66
63-9/16
30-1/8
540+540+717+717
R410A
22+22+33+33
Ф7/8
Ф1-3/4
208~230V-3Ph-60Hz
518,000
578,000
34,110
66.5
63-9/16
30-1/8
540+607+717+717
R410A
22+26.5+33+33
Ф7/8
Ф1-3/4
208~230V-3Ph-60Hz
540,000
604,000
34,110
66.5
63-9/16
30-1/8
540+717+717+717
R410A
22+33+33+33
Ф7/8
Ф1-3/4
V-Ph-Hz
Btu/h
Btu/h
CFM
dB(A)
in.
in.
in.
lbs
lbs
in.
in.
Model
Constituent Units
Power supply
Capacity Cooling (*1)
Heating (*2)
Width
Hength
Depth
Liquid side
Gas side
Outdoor unit
Dimension
Compressor Configration
Air flow
Sound level (*3)
Hermetically sealed scroll type
Net weight
Refrigerant
Refrigerant Charged Volume
MDV-1350(48)W/DXN1(B) MDV-1432(50)W/DXN1(B) MDV-1460(52)W/DXN1(B) MDV-1515(54)W/DXN1(B) MDV-1580(56)W/DXN1(B)
Refrigerant piping
R410A DC Inverter VRF 22R410A DC Inverter VRF21
MDV-1630(58)W/DXN1(B)
MDV-1685(60)W/DXN1(B)
MDV-1750(62)W/DXN1(B)
MDV-1800(64)W/DXN1(B)
Specifications
Outdoor Unit
Cooling
Heating
Indoor Outdoor Piping length Level difference
80.6°F DB,60°FWB
68°F DB,60°FWB
95°F DB
42.8°F DB
24.6ft.
24.6ft.
0ft.
0ft.
Notes:1.Nominal conditions
2.Sound level:Anechoic chamber connersion value,measure at the position 3.28ft. at the front of the e unit and 4.92ft. above the floor.3.Refrigerant pipe dim.listed here only for when the total equivalent length <295ft. For the data when total quivalent length ≥295ft. please refer to technical manual.4.The above data may be changed without notice for furture improvement on quality and performance.
MDV-450(16)W/DXN1(B)MDV-450(16)W/DXN1(B)MDV-450(16)W/DXN1(B)MDV-450(16)W/DXN1(B)
MDV-400(14)W/DXN1(B)MDV-400(14)W/DXN1(B)MDV-450(16)W/DXN1(B)MDV-450(16)W/DXN1(B)
MDV-400(14)W/DXN1(B)MDV-400(14)W/DXN1(B)MDV-400(14)W/DXN1(B)MDV-450(16)W/DXN1(B)
MDV-400(14)W/DXN1(B)MDV-450(16)W/DXN1(B)MDV-450(16)W/DXN1(B)MDV-450(16)W/DXN1(B)
208~230V-3Ph-60Hz
562,000
633,000
36,320
67
63-9/16
30-1/8
717+717+717+717
R410A
33+33+33+33
Ф7/8
Ф1-3/4
208~230V-3Ph-60Hz
580,000
650,000
36,320
67
63-9/16
30-1/8
717+717+717+717
R410A
33+33+33+33
Ф7/8
Ф1-3/4
208~230V-3Ph-60Hz
598,000
667,000
36,320
67
63-9/16
30-1/8
717+717+717+717
R410A
33+33+33+33
Ф7/8
Ф1-3/4
208~230V-3Ph-60Hz
616,000
684,000
36,320
67
63-9/16
30-1/8
717+717+717+717
R410A
33+33+33+33
Ф7/8
Ф1-3/4
V-Ph-Hz
Btu/h
Btu/h
CFM
dB(A)
in.
in.
in.
lbs
lbs
in.
in.
Model
Constituent Units
Power supply
Capacity Cooling (*1)
Heating (*2)
Width
Hength
Depth
49-7/32+49-7/32+49-7/32+49-7/32
Liquid side
Gas side
Outdoor unit
Dimension
Compressor Configration
Air flow
Sound level (*3)
Hermetically sealed scroll type
Net weight
Refrigerant
Refrigerant Charged Volume
MDV-1630(58)W/DXN1(B) MDV-1685(60)W/DXN1(B) MDV-1750(62)W/DXN1(B) MDV-1800(64)W/DXN1(B)
Refrigerant piping
Full DC Inverter Mini VRF
The mini VRF product is a highly efficient solution for small commercial buildings that requiring heating and cooling system up to 7 zones in one outdoor unit.This is a flexible system that bridges the capacity gap between VRF and Multi systems-ideal for commercial and private applications.
Full DC Inverter Mini VRF
NEWFashionDesign
R410A DC Inverter VRF 24R410A DC Inverter VRF23
Never ending development of Midea’s technologies will satisfy you’re your expectations. Each of this year’s new technologies were considered to provide you the most efficient and convenient air conditioners.
High efficiency and Energy-saving, thanks to the DC inverter compressor and DC fan motor. Inverter systems save energy as continuous operation offers the same capacity with lower power consumption. This benefits all occupants by maintaining even room temperatures, as well as the environment by reduc-ing energy consumption.
Compressor efficiency
Effic
ienc
y-R
otor
Spe
ed C
urve
New DC motor-centralized winding
Common DC motor-distributing winding
20 40 60 80 100Rotor speed(s-1)
Centralizing winding
Distributing winding
Main Technologies
Compressor (Twin Rotary) structure
Midea Mini VRF with intelligence control that gives you independent zoning control with maximum flexibility. The Advantage of Midea Mini VRF is that a single outdoor unit supports up to 6 indoor units. Use your backyard more wisely with much more space available created by less number of outdoor units.
Optimally design the fan shape and Noise-reducing designed discharge air grille increase the air volume and reduce the running noise.
High efficiency full DC inverter compressor
Low noise full DC fan motor
Highly Efficient DC Motor:
- Creative motor core design
- High density neodymium magnet
- Concentrated type stator
-Wider operating frequency range
Better balance and Extremely Low Vibration:
- Twin eccentric cams
- 2 balance weights
Highly Stable Moving Parts:
- Optimal material matching rollers and vanes
-Optimize compressor drive technology
- Highly robust bearings
-Compact structure
Panasonic DC fan motor :-Wider fan speed adjustment-lower noise-lower power consumption
DC motor
AC motor
2000
20
40
60
80
100
300 400 500 600
MOTOR SPEED (RPM)
EFFI
CIE
NC
Y (%
)
700 800 900 1000
Approx.40%increase
Approx.20%increase
Max. 5 indoor units for a 36000Btu/h outdoor unit installationMax. 7 indoor units for a 47500Btu/h outdoor unit installation
High performance heat exchanger
The coils are special blue coated to enhance its durability. These special coated layers serve as protection against corrosion from air, water and other corrosive agents. Blue fin coil has 3 times higher resistance against corrosion. This special coating assures longer coil live for years of reliable comfort.
Hydrophilic Blue Fin Coil
Application flexibility-various Indoor units
Improved noise reducing design
Newly Designed Fan Guard Powerful Large Propeller
DC motor efficiency
(comparison with a conventional AC motor)
New designed fan
Air deflector
New designed grilling
Powerful magnets provide high torque and efficiency and achieve 70% reduction in volume.
DC fan motor structure
R410A DC Inverter VRF 26R410A DC Inverter VRF25
Main Features Auto addressing
More convenience in installation
Benefits of using R410A refrigerant
Addressing indoor units are able to be done just by pressing the button of the controller.No need to set the address by the DIP switch one by one.Wired controller and wireless controller can enquiry and modify every indoor units address.
Smooth control
Wide operation temperature range
The operation range of the Mini VRF system works to reduce limitations on installation locations. The opera-tion temperature range for heating goes all the way down to 5°F, while cooling can be performed with outdoor temperatures as high as 118.4°F. Both these achievements are due to the employment of a high pressure dome-type compressor.
By using all inverter-driven compressors, Midea is able to significantly reduce the electrical and mechanical stresses that are placed on fixed-speed compressors during start-up. Current absorption on an inverter-driven compressor is smoothed out at start-up thus reducing the wear on the electrical and mechanical com-ponents and increasing reliability.
To suit the variety of rooms found in small offices and shops,the Mini VRF system offers wide range of indoor and outdoor units .mini VRF indoor and outdoor units are almost as easy to install as residential air conditioning systems , making them ideal for small offices and shops .
Offering four direction space for installation to connect pipes and wirings for meet a variety installation request.
Zero ozone-depleting potential
Significant increase in energy efficiency.
Reduced pressure loss for improved performance.
Making continuous efforts to stay eco-friendly, midea's air conditioners use R-410A, an environmentally friendly refrigerant to help rid the air of pollutants and restrain the use of materials with high global warming potential (GWP). Incorporating the Energy efficient, non-ozone-depleting R410A refrigerant in air conditioning systems delivers multiple benefits:
Up to 118.4°F in cooling mode and down to 5°F in heating mode.
32 50 68 86 104 12214-4
COOLING MODE
HEATING MODE
Outdoor temp. °F(D.B.)
118.4°F
80.6°F5°F
5°F
AutomaticallyIdentify
Improved onMini VRF
PreviousDesignNeed To Set The
Address Manually,one By One
01234
56789ABC
D
EF
0
Blend of twotypes with similar
boiling points
Approximately same boiling point
High boiling point
Blend of threetypes with different
boiling points
Degradationlikely
Degradationunlikely
R32 R125 R134a
R410A
R407C
Comparison of refrigerantboiling points (liquid and gas)
Start-up using all inverter-driven compressor
Fixed-speed unit: sudden start-up
Before start-up
After start-up
Little lowering of oil surface
Temporary fall in oil surface due to sudden outflow of refrigerant and oil
Fixed-speed unit: c. 3 times normal drive
Inverter: almost same as during normal drive
Fixed-speed unit: 5-7 times drive current
No more than inverter drive current
Inverter: gradual start-up
Start > Drive
Start > Drive
Compressor
Inverter
Fixed-speed unit
Start > Drive
Compressordrive
Piping stress
Compressor oil surface
Compressor current
75.2
Front side Back sideRight side Bottom side
Fat pipe
°F
No matter in extremely cold winter when outdoor temperature gets as low as 5°F or in hot summer when temperature is up to 118.4°F, the mini VRF system will keep stable performance.
Left side
Upper side
Back side
3214-4-22-40-58-76
-61.24 -55.3 -15.12
R410A DC Inverter VRF 28R410A DC Inverter VRF27
The Mini VRF provides the max. piping length possibility of 328ft., The height difference between outdoor unit and indoor unit can be up to a maximum of 66ft. The height difference between indoors unit can be up to a maximum of 26ft. These generous allowances facilitate an extensive variety of system designs.
Flexible piping design Space saving design
Easy installation
Comfortable temperature
Autorestart function
Easy maintenance
Even if there is an extended power failure, the A/C system will automatically restart operation. A power failure will not cause any settings to be lost, thus eliminating the need for re-programming.
No need special room for the outdoor units. Easy installation: all the outdoor units can be transported by elevator. This makes installation dramatically easy, and effectively reduces time and labor.So the Mini VRF system indoor and outdoor units are almost as easy to install as residential air conditioning systems, making them ideal for small offices and shops.
The inverter Mini VRF can quickly reach the desired temperature. After reaching the set temperature, it finely adjusts to cope with any changes. This means less temperature fluctuation and assures you greater comfort that can be achieved in minutes.
82 F
78.7 F
75.5 F
Comfortable
S-InverterSteady Temperature Fluctuation
Non InverterHigh Temperature Fluctuation
Uncomfortable(Energy Loss)
Uncomfortable(Energy Loss)
The Mini VRF units are slimmer and more compact, resulting in significant savings in installation space. In some large residential spaces or some light commercial space, such as villa, restaurant, usually it need more than one indoor unit, so outside the building are also full of outdoor units. Now Midea can provide an effective solution-Midea MINI VRF system. Since now the beauty of the building will be back.
Forced cooling button makes outdoor unit run in cooling mode at any condition, so it is very easy for you to charge refrigerant to the system when it need to be done.
The self-diagnosis function detects malfunctions in major locations in the system and displays the type of malfunction and location. This allows service and maintenance to be performed more efficiently.
The longest pipinglength : 230ft.(Equivalent Length)
Height differencesbetween indoor &
outdoor units : 98ft.*
The first branch joint to the farthest indoor unit : 66ft.
(one-way piping size up : 132ft.)Height difference between indoor units : 26ft.
The longest piping length : 230ft. (Equivalent Length)Total piping length: 328ft.From the first branch joint to the farthest indoor unit : 132ft. (one-way piping size up)
Summary
Easy to transport
*when outdoor unit up height difference is 98ft.,when outdoor unit down height difference is 66ft.
R410A DC Inverter VRF 30R410A DC Inverter VRF 29
More convenient piping connector - branch box
New piping connection design
Easier and safer installation thanks to a branch box that simplifies piping work and the adoption of screw connection.
Both left and right pipe screw connection from outdoor unit to branch box is reserved, simplified the field installation.
Two sets of pipe size converter are packed with branch box to transfer the pipe size from Φ1/4in. to Φ3/8in. and fromΦ1/2in. to 5/8in.
The branch pipe is linear expansion design which regu-lates the flow of refrigerant and reduces the noise. By locating the branch box in the ceiling or outside ,noise generated by the branch box can be kept clear of living spaces, thus maintaining the noise level to a minimum.
All the piping leading to and from the branch box is connected using screw joints,which are easy to use and enable piping installation to be completed quickly.
Brazing-free quick installation
Indoor installation
Universal indoor units
The branch box can be installed in the ceiling rather than outside. Furthermore, servicing can be complete easily through access to inner components such as the circuit board by simply removing the side and bottom covers.
The same indoor units as R410a DC inverter mini VRF system.
Low noise
OUTDOOR UNITS LINEUP - Mini VRFCapacity 36000Btu/h(3Ton),47500Btu/h(4Ton)
Notes: 1. The cooling conditions: indoor temp.: 80.6°FDB, 60°FWB outdoor temp.: 95°FDB equivalent pipe length: 16.4ft. drop length: 0ft. 2. The heating conditions: indoor temp.: 68°FDB, 44.6°FWB outdoor temp.: 42.8°FDB equivalent pipe length: 16.4ft. drop length: 0ft. 3. Sound level: Anechoic chamber conversion value, measured at a point 3.28ft. in front of the unit at a height of 3.94ft. above the floor. During actual operation. These values are normally somewhat higher as a result of ambient conditions. 4. The above data may be changed without any notice for future improvement on quality and performance.
NEWFashionDesign
Model MDV-V105W/DVN1 MDV-V140W/DVN1
Power supply 208~230V,60Hz,1-Phase
Cooling capacity
Heating capacity
Efficiency
Airflow rate(H/M/L)
Sound level
Refrigerant Type
Net dimension(W×H×D)
Packing dimension(W×H×D)
Net/Gross weight
Maximum No. of indoor units
Connection ratio
Vertical pipe length
Actual pipe length
Equivalent pipe length
Total pipe length
Liquid side
Gas side
SEER
HSPF
Btu/h
Btu/h
Btu/(h·W)
Btu/(h·W)
CFM
dB(A)
in.
in.
lbs.
ft.
ft.
ft.
ft.
in.
in.
36,000
40,000
15.1
8.4
4100
57.0
5
47,500
52,500
14.5
8.8
4100
57.0
45%-110%
98
197
230
328
Ф3/8
Ф5/8
Connectable indoor unit
Piping connections
Specifications
R410A
35-7/16×52-1/4×12-5/8
40-9/16×57-5/16×17-1/8
209/234
7
R410A DC Inverter VRF 32R410A DC Inverter VRF31
INDOOR UNIT LINEUPFour-way Cassette
Model
Capacity
28
9000Btu/h
36
12000Btu/h
45
15000Btu/h
56
19000Btu/h
71
24000Btu/h
Model
Capacity
80
27000Btu/h
90
30000Btu/h
100
34000Btu/h
112
38000Btu/h
140
48000Btu/h
MDV-D XX Q4/VN1-D
Ceiling & Floor
Model
Capacity
36
12200Btu/h
Model
Capacity
80
27300Btu/h
45
15300Btu/h
90
30700Btu/h
56
19100Btu/h
112
38200Btu/h
71
24200Btu/h
140
47800Btu/h
MDV-D XX DL/VN1-C
Concealed Duct Unit (A5 Type)
Model
Capacity
22
7500Btu/h
28
9000Btu/h
36
12000Btu/h
45
15000Btu/h
56
19000Btu/h
Model
Capacity
71
24000Btu/h
80
27000Btu/h
90
30000Btu/h
112
38000Btu/h
140
48000Btu/h
MDV-D XX T2/VN1-CA5
Wall-mounted Type
MDV-D XX G/N1-S
Model
Capacity
22
7500Btu/h
28
9500Btu/h
36
12200Btu/h
45
15300Btu/h
56
19100Btu/h
High Static Pressure Duct
Model
Capacity
71
24200Btu/h
80
27300Btu/h
90
30700Btu/h
112
38200Btu/h
140
47800Btu/h
160
54600Btu/h
MDV-D XX T1/VN1-B
Four-way Cassette
Concealed Duct Unit (A5 Type)
High Static Pressure Duct
Ceiling & Floor Type
Wall-mounted S Type
Indoor Units Lineup
Indoor Units
R410A DC Inverter VRF 34R410A DC Inverter VRF33
1. Nominal cooling capacities are based on the following conditions: return air temp. : 80.6°FDB,66.2°FWB,and outdoor temp.: 95°FDB,equivalent ref. piping: 26.25ft. (horizontal) 2. Nominal heating capacities are based on the following conditions: return air temp.: 68°FDB,outdoor temp.: 44.6°FDB,42.8°FWB, and equivalent ref. Piping: 26.25ft. (horizontal)3. Sound Level is measured 4.59ft. below the unit.
Notes:
Model
Power supply 208~230V,60Hz,1-Phase
Cooling capacity
Heating capacity
Power input
Airflow rate(H/M/L)
Sound level
Refrigerant
Body
Panel
Piping connections
Rated current
Cooling
Heating
Cooling
Heating
Type
Control method
Btu/h
Btu/h
W
W
A
A
CFM
dB(A)
in.
in.
lbs.
in.
in.
lbs.
in.
in.
in.
MDV-D28Q/VN1-D MDV-D36Q/VN1-D MDV-D45Q/VN1-D MDV-D56Q/VN1-D MDV-D71Q/VN1-D
9,000
10,900
65
65
0.3
0.3
514/454/384
42/38/35
53 /66.2
13.2/19.9
Ф1/4
Ф1/2
12,000
13,600
65
65
0.3
0.3
514/454/384
42/38/35
53 /66.2
13.2/19.9
Ф1/4
Ф1/2
15,000
17,100
75
75
0.34
0.34
526/463/390
42/38/35
53 /66.2
13.2/19.9
Ф1/4
Ф1/2
19,000
20,700
75
75
0.34
0.34
526/463/390
42/38/35
57.4/70.6
13.2/19.9
Ф3/8
Ф5/8
24,000
27,300
100
100
0.46
0.46
671/576/444
45/42/39
57.4/70.6
13.2/19.9
Ф3/8
Ф5/8
Net dimension(W×H×D)
Packing dimension(W×H×D)
Net/Gross weight
Net dimension(W×H×D)
Packing dimension(W×H×D)
Packing dimension(W×H×D)
Liquid side
Gas side
Drain piping Ф1-1/4
Wireless remote controller (RM05/BG(T)E-A)
R410A
EXV
33-1/16 × 9-1/16×33-1/16
37-19/32 × 9-23/32 × 37-19/32
37-13/32 ×1-13/16 ×37-13/32
40-3/4 × 3-17/32 × 40-3/4
Standard controller
Model
Power supply 208~230V,60Hz,1-Phase
Cooling capacity
Heating capacity
Power input
Airflow rate(H/M/L)
Sound level
Refrigerant
Body
Panel
Piping connections
Rated current
Cooling
Heating
Cooling
Heating
Type
Control method
Btu/h
Btu/h
W
W
A
A
CFM
dB(A)
in.
in.
lbs.
in.
in.
lbs.
in.
in.
in.
MDV-D80Q/VN1-D MDV-D90Q/VN1-D MDV-D100Q/VN1-D MDV-D112Q/VN1-D MDV-D140Q/VN1-D
27,000
30,600
100
100
0.46
0.46
691/598/465
45/42/39
33-1/16 × 9-1/16×33-1/16
37-19/32 × 9-23/32 × 37-19/32
57.4/70.6
13.2/19.9
Ф3/8
Ф5/8
30,000
34,100
165
165
0.75
0.75
936/765/642
48/45/43
70.6/86
13.2/19.9
Ф3/8
Ф5/8
34,000
37,500
165
165
0.75
0.75
936/765/642
48/45/43
70.6/86
13.2/19.9
Ф3/8
Ф5/8
38,000
42,700
165
165
0.75
0.75
936/765/642
48/45/43
70.6/86
13.2/19.9
Ф3/8
Ф5/8
48,000
51,200
200
200
0.92
0.92
988/799/656
50/47/44
70.6/86
13.2/19.9
Ф3/8
Ф5/8
Net dimension(W×H×D)
Packing dimension(W×H×D)
Net/Gross weight
Net dimension(W×H×D)
Packing dimension(W×H×D)
Packing dimension(W×H×D)
Liquid side
Gas side
Drain piping Ф1-1/4
Wireless remote controller (RM05/BG(T)E-A)
33-1/16 ×1-13/16 × 33-1/16
37-19/32×12-15/32 ×37-19/32
R410A
EXV
37-13/32 ×1-13/16 ×37-13/32
40-3/4 × 3-17/32 × 40-3/4
Standard controller
Quiet operation, soft air supply
Uniform air flow of four ways Four kinds of colors panel available
Easy trouble shooting Reserved multi-function ports
High lift pump
Four Way Cassette
■ Streamline plate ensures quietness■ Advanced 3-D spiral fan design reduces the air resistance and operation noise.
By adding digital tube displayer on the display board, the Error Codes can be displayed directly on it which helps to find and shoot the trouble.
Drain pump can take up the condenser water to 29-17/32in. which helps to make easier installation of the drain piping system.
Ultra-thin machine body for easy installation and maintenance, min. 9-1/16in. in height.
The four air discharge port provides strong
circulating air flow to cool or heat every corner of the
room and realizes even temperature distribution; by
choosing high airflow mode, high ceiling application
over 1/8in. can get equal comfort.
To another room
Fresh Air Intake
(White) Standard
(Gray) Optional
(Black) Optional
(Blue) Optional
For ductconnecting
9-1/16in.29-17/32in.
Four-way Airflow(4-stage fan speed)
Diffuser
3-D spiral fan blade
R410A DC Inverter VRF 36R410A DC Inverter VRF35
Compact size
Two external static pressure settings for added flexibility
Convenient installation
Flexible control and convenient for maintenance
The capacity ranges from 7000Btu/h to 48000Btu/h, totally 10 models.
Only 8-9/32in. (22~56 models) or 10-5/8in. (71 to 140 model) in height.The EXV is built-in design of the indoor unit, main body without an extra throttle kit box.
The EXV is fixed inside of the indoor unit.Standard filter placed in an aluminum frame, which is removable downward from bottom.Suction chamber is included as standard equipment.Fresh air hole, air inlet/outlet flange are standard for easy duct connection.Air inlet from back is standard and from bottom as optional with the same connectable duct.
Standard Wired remote controller KJR-10B/DP(T)-E. The display board is connected with the E-box in factory, easier trouble-shooting by LED display.The Electrical control box can be removed 3.3ft. away from the unit, easy to access when needs maintenance.(Should be required by client in advance and done by Midea CAC in factory).Standard functional port such as Remote On/Off Dry contact switch and Alarm signal output (220V).
Four speed fan motor (Super high speed as an optional)Change the wiring connection from 'Hi' to 'SH' to change the ESP.
Wide capacity range
Concealed Duct Unit (A5 Type)
Air intake from belowAir intake from back
8-9/32in or 10-5/8in
Min.3/16in.
Drop-Ceiling
Drain pump is equipped as standard accessory with 29-17/32in.(750mm) pumphead.
MANUAL OPERATION TIMER DEF./FAN ALARM
29-17/32in.
ceiling
Notes: 1. Nominal cooling capacities are based on the following conditions: return air temp. : 80.6°FDB,66.2°FWB,and outdoor temp.: 95°FDB,equivalent ref. piping: 26.25ft. (horizontal) 2. Nominal heating capacities are based on the following conditions: return air temp.: 68°FDB,outdoor temp.: 44.6°FDB,42.8°FWB, and equivalent ref. Piping: 26.25ft. (horizontal)3. Sound Level is measured 4.59ft. below the unit.* external static pressure are based on high speed indoor air flow.* Specifications are subject to change without prior notice for product improvement.
MANUAL
RUN TIMER DEF ALARM
22~56 model 71~140 model
Model
Power supply 208~230V,60Hz,1-Phase
Cooling capacity
Heating capacity
Power input
Airflow rate(H/M/L)
External static pressure
Sound level
Refrigerant
Piping connections
Rated current
Cooling
Heating
Cooling
Heating
Type
Control method
Btu/h
Btu/h
W
W
A
A
CFM
in.WG
dB(A)
in.
in.
lbs.
in.
in.
in.
MDV-D22T2/VN1-CA5 MDV-D28T2/VN1-CA5 MDV-D36T2/VN1-CA5 MDV-D45T2/VN1-CA5 MDV-D56T2/VN1-CA5
7,000
8,900
55
55
0.25
0.25
(340)310/240/190
38/35/32
47.4/57.3
Ф1/4
Ф1/2
9,000
10,900
55
55
0.25
0.25
(340)310/240/190
38/35/32
47.4/57.3
Ф1/4
Ф1/2
12,000
13,600
63
63
0.28
0.28
(340)310/240/190
40/38/36
48.5/58.4
Ф1/4
Ф1/2
15,000
17,100
100
100
0.46
0.46
(560)500/390/340
41/39/36
59.5/70.5
Ф1/4
Ф1/2
19,000
21,500
100
100
0.46
0.46
(560)500/390/340
41/39/36
59.5/70.5
Ф3/8
Ф5/8
Net dimension(W×H×D)
Packing dimension(W×H×D)
Net/Gross weight
Liquid side
Gas side
Drain piping Ф1-1/4
Wired controller KJR-10B/DP(T)-E
0.04(0.04~0.12)
27-9/16×8-1/4×25
36-1/32×11-13/32×25-25/32
R410A
EXV
36-7/32×8-1/4×25
44-1/32×11-13/32×25-25/32
Standard controller
Model
Power supply 208~230V,60Hz,1-Phase
Cooling capacity
Heating capacity
Power input
Airflow rate(H/M/L)
External static pressure
Sound level
Refrigerant
Piping connections
Rated current
Cooling
Heating
Cooling
Heating
Type
Control method
Btu/h
Btu/h
W
W
A
A
CFM
in.WG
dB(A)
in.
in.
lbs.
in.
in.
in.
MDV-D71T2/VN1-CA5 MDV-D80T2/VN1-CA5 MDV-D90T2/VN1-CA5 MDV-D112T2/VN1-CA5 MDV-D140T2/VN1-CA5
24,000
27,300
160
160
0.73
0.73
(710)620/530/480
0.04(0.04~0.12)
43/40/36
36-7/32×8-1/4×25
44-1/32×13-25/32×25-25/32
68.3/79.4
Ф3/8
Ф5/8
27,000
30,700
132
132
0.61
0.61
(920)790/690/610
45/40/37
88.2/106.9
Ф3/8
Ф5/8
30,000
34,100
132
132
0.61
0.61
(920)790/690/610
45/40/37
92.6/110.2
Ф3/8
Ф5/8
38,000
42,700
370
370
1.7
1.7
(1200)1060/920/820
0.16(0.04~0.32)
48/42/38
92.6/110.2
Ф3/8
Ф5/8
48,000
52,900
335
335
1.53
1.53
(1260)1120/970/830
0.16(0.04~0.4)
48/43/39
47-1/4×11-13/16×34-1/16
54-17/32×14-3/4×36-7/32
110.2/131.2
Ф3/8
Ф5/8
Net dimension(W×H×D)
Packing dimension(W×H×D)
Net/Gross weight
Liquid side
Gas side
Drain piping Ф1-1/4
Wired controller KJR-10B/DP(T)-E
0.08(0.04~0.2)
44-7/8×10-5/8×30-1/2
53-11/32×13-25/32×31-5/16
R410A
EXV
Standard controller
R410A DC Inverter VRF 38R410A DC Inverter VRF37
High Static Pressure Duct
Wide capacity range
Flexible duct design
Convenient installation
Flexible control and convenient for maintenance
Option:
Four speed fan motor (medium high speed as an option). External static pressure can be up to 0.77in.WG.
The EXV is fixed inside the indoor unit, no need extra connection. Standard filter placed in an aluminum frame, which is removable downward from bottom.Flange for air in/outlet duct connection is standard.
16-17/32in.17-23/32in.
Min.
INDOOR UNIT
Standard Wired remote controller KJR-10B/DP(T)-E, and wireless remote controller RM05/BG(T)E-A is as an option.The display board is connected with the E-box in factory, easier trouble-shooting by LED display.Easy access filters both in rear & bottom. Standard functional port such as remote on/off dry contact.
The max distance of air supply is about 45.9ft. while the height of air supply is about 21.3ft.With 16-17/32in thickness body, the minimum distance above the ceiling is 17-23/32in.
Optional drain pumps with 29-17/32in. pumphead.
the longest distanceof air supply is 46ft.
The height of airsupply is 21ft.
INDOOR UNIT
Fresh air in take
The capacity ranges from 24200Btu/h to 54600Btu/h, totally six models.
Air supply Air return
29-17/32in.
ceiling
Model
Power supply 208~230V,60Hz,1-Phase
Cooling capacity
Heating capacity
Power input
Airflow rate(H/M/L)
External static pressure
Sound level
Refrigerant
Piping
connections
Rated current
Cooling
Heating
Cooling
Heating
Type
Control method
Btu/h
Btu/h
W
W
A
A
CFM
in.WG
dB(A)
in.
in.
lbs.
in.
in.
in.
MDV-D71T1/VN1-B MDV-D80T1/VN1-B MDV-D90T1/VN1-B MDV-D112T1/VN1-B MDV-D140T1/VN1-B MDV-D160T1/VN1-B
24,200
27,300
263
263
1.1
1.1
1034/923/790
0.16(0.12~0.78)
48/46/44
102.5/114.6
Ф3/8
Ф5/8
Ф1-1/4
27,300
30,700
263
263
1.1
1.1
943/879/766
0.16(0.12~0.78)
48/46/44.5
102.5/114.6
Ф3/8
Ф5/8
Ф1-1/4
30,700
34,100
423
423
1.8
1.8
1324/1189/939
0.16(0.12~0.78)
52/49/47
110/124.5
Ф3/8
Ф5/8
Ф1-1/4
38,200
42,600
524
524
2.3
2.3
1324/1189/939
0.20(0.12~0.78)
52/49/47
111.6/123.6
Ф3/8
Ф5/8
Ф1-1/4
47,800
54,600
627
627
2.7
2.7
1783/1595/1465
0.20(0.12~0.78)
53/50/48
154.5/171
Ф3/8
Ф5/8
Ф1-1/4
54,600
61,400
832
832
3.6
3.6
1783/1595/1465
0.20(0.12~0.78)
54/52/50
154.5/171
Ф3/8
Ф5/8
Ф1-1/4
Net dimension(W×H×D)
Packing dimension(W×H×D)
Net/Gross weight
Liquid side
Gas side
Drain piping
Wired controller KJR-10B/DP(T)-E
37-1/2×16-9/16×27-3/16
43-3/8×17-3/4×30-1/4
R410A
EXV
47-1/4×15-3/4×23-5/8
56-5/16×17-3/4×30-1/4
Standard controller
Notes: 1. Nominal cooling capacities are based on the following conditions: return air temp. : 80.6°FDB,66.2°FWB,and outdoor temp.: 95°FDB,equivalent ref. piping: 26.25ft. (horizontal) 2. Nominal heating capacities are based on the following conditions: return air temp.: 68°FDB,outdoor temp.: 44.6°FDB,42.8°FWB, and equivalent ref. Piping: 26.25ft. (horizontal)3. Sound Level is measured 4.59ft. below the unit.* Specifications are subject to change without prior notice for product improvement.
R410A DC Inverter VRF 40R410A DC Inverter VRF39
Ceiling & floor
Panel with LED display
Convenient for installation
Low noise, creates quiet and comfortable environment.
Auto swing and wide angle air flow
The front panel and display panel have different colors for choose: white and brown for big panel, blue and brown for small panel, and the other colors can be customized according to the customers’ demands.
1.The unit has auto horizontal swing and auto vertical swing function, which supplies more even and comfortable airflow.
2.Three air flow speed: high/middle/low, double air guides.3.Adoption of the electronic expansion valve, ensure precise flow
control, as well lower modulation noise when EXV operating.4.Smoother airflow with less turbulence. Owing to the multiple-blade
fan and the air guide design, the airflow is getting smoother and more comfortable.
The ceiling type can be easily installed into a corner of the ceiling even if the ceiling is very narrowIt is especially useful when installation of an air conditioner in the center of the ceiling is impossible due to a structure such as one lighting
Slim and sleek design starting at just 66lbs. in weight means quick,easy & neat installation.Low noise operation, lowest to 36 dB(A)
Auto Swing & Wide-angle Airflow
>13/16in.
7-13/16in.
Drop ceiling
Air Outlet
The unit can be installed either horizontally on the ceiling or vertically against the wall.
Notes: 1. Nominal cooling capacities are based on the following conditions: return air temp. : 80.6°FDB,66.2°FWB,and outdoor temp.: 95°FDB,equivalent ref. piping: 26.25ft. (horizontal) 2. Nominal heating capacities are based on the following conditions: return air temp.: 68°FDB,outdoor temp.: 44.6°FDB,42.8°FWB, and equivalent ref. Piping: 26.25ft. (horizontal)3. Floor standing :Sound level is measured 3.28ft. from air-outlet in horizontal distance, 3.28ft. above the floor in vertical distance. Ceiling mounted:Sound level is measured 3.28ft. from air-outlet in horizontal distance,3.28ft.from air-outlet in vertical distance.
* Specifications are subject to change without prior notice for product improvement.
Model
Power supply 208~230V,60Hz,1-Phase
Cooling capacity
Heating capacity
Power input
Airflow rate(H/M/L)
Sound level
Refrigerant
Piping connections
Rated current
Cooling
Heating
Cooling
Heating
Type
Control method
Btu/h
Btu/h
W
W
A
A
CFM
dB(A)
in.
in.
lbs.
in.
in.
in.
MDV-D36DL/VN1-C MDV-D45DL/VN1-C MDV-D56DL/VN1-C MDV-D71DL/VN1-C
12,200
13,600
49
49
0.55
0.55
353/283/235
40/38/36
57.3/70.5
Ф1/4
Ф1/2
15,300
17,100
147
147
0.55
0.55
441/383/324
43/41/38
61.7/75
Ф1/4
Ф1/2
19,100
20,700
147
147
0.55
0.55
441/383/324
43/41/38
61.7/75
Ф3/8
Ф5/8
24,200
27,300
147
147
0.57
0.57
441/383/324
43/41/38
61.7/75
Ф3/8
Ф5/8
Net dimension(W×H×D)
Packing dimension(W×H×D)
Net/Gross weight
Liquid side
Gas side
Drain piping Ф5/8
Wireless remote controller RM05/BG(T)E-AStandard controller
R410A
EXV
38-31/32×25-31/32×8-1/8
42-7/8×29-9/32×11-21/32
Model
Power supply 208~230V,60Hz,1-Phase
Cooling capacity
Heating capacity
Power input
Airflow rate(H/M/L)
Sound level
Refrigerant
Piping connections
Rated current
Cooling
Heating
Cooling
Heating
Type
Control method
Btu/h
Btu/h
W
W
A
A
CFM
dB(A)
in.
in.
lbs.
in.
in.
in.
MDV-D80DL/VN1-C MDV-D90DL/VN1-C MDV-D112DL/VN1-C MDV-D140DL/VN1-C
27,300
30,600
185
185
0.6
0.6
706/530/412
45/43/40
76.1/90.4
Ф3/8
Ф5/8
30,700
34,100
185
185
0.6
0.6
706/530/412
45/43/40
76.1/90.4
Ф3/8
Ф5/8
38,200
42,700
241
241
0.83
0.83
1165/1095/1018
47/45/42
119/130.1
Ф3/8
Ф5/8
47,800
51,200
241
241
0.83
0.83
1165/1095/1018
47/45/42
119/130.1
Ф3/8
Ф5/8
Net dimension(W×H×D)
Packing dimension(W×H×D)
Net/Gross weight
Liquid side
Gas side
Drain piping Ф5/8
Wireless remote controller RM05/BG(T)E-AStandard controller
R410A
EXV
50-13/32 × 25-31/32×8-1/8
54-9/32 × 29-9/32 × 11-21/32
65-3/4 ×26-25/32 × 9-19/32
69-29/64×29-59/64 ×12-61/64
R410A DC Inverter VRF 42R410A DC Inverter VRF41
Wall mounted(S type panel)
Panel with LED display
Convenient for installation
Auto swing louver Easy maintenanceEasy maintenance has been realized as the front panel can removed for easy access.
The front panel and display panel have different colors for choose: white and brown for big panel, blue and brown for small panel, and the other colors can be customized according to the customers’ demands.
Multi-refrigerant outlet pipe method: left\right\rear, more flexible for installation.The EXV is built-in the indoor unit, compact size, Longer the connection pipe, Gas pipe: 18-27/64in./Liquid pipe: 21-21/32in., more flexible for the installation Adopts new type fixing plate, easy for installation and stable.
Open panel
The Auto Swing Louver function ensures that the air direction corresponds to the mode selected.
Rear
Left Right
1
2
3
4
Step
Swing Notes: 1. Nominal cooling capacities are based on the following conditions: return air temp. : 80.6°FDB,66.2°FWB,and outdoor temp.: 95°FDB,equivalent ref. piping: 26.25ft. (horizontal) 2. Nominal heating capacities are based on the following conditions: return air temp.: 68°FDB,outdoor temp.: 44.6°FDB,42.8°FWB, and equivalent ref. Piping: 26.25ft. (horizontal)
3. Sound level is measured 3.28ft. below the air out-let both in horizontal and vertical distance.
* Specifications are subject to change without prior notice for product improvement.
Model
Power supply 208~230V,60Hz,1-Phase
Cooling capacity
Heating capacity
Power input
Airflow rate(H/M/L)
Sound level
Refrigerant
Piping
connections
Rated current
Cooling
Heating
Cooling
Heating
Type
Control method
Btu/h
Btu/h
W
W
A
A
CFM
dB(A)
in.
in.
lbs.
in.
in.
in.
MDV-D22G/VN1-S MDV-D28G/VN1-S MDV-D36G/VN1-S MDV-D45G/VN1-S MDV-D56G/VN1-S
7,500
8,200
28
28
0.14
0.14
309/283/253
35/32/29
28.7/36.4
Ф3/8
Ф5/8
Ф5/8
9,500
10,900
28
28
0.14
0.14
309/283/253
35/32/29
28.7/36.4
Ф3/8
Ф5/8
Ф5/8
12,200
13,600
28
28
0.14
0.14
347/306/283
35/32/29
R410A
EXV
28.7/36.4
Ф3/8
Ф5/8
Ф5/8
15,300
17,000
51
51
0.2
0.2
506/444/371
40/38/34
33.4/41.5
Ф3/8
Ф5/8
Ф5/8
19,100
21,500
51
51
0.2
0.2
544/506/444
40/38/34
33.4/41.5
Ф3/8
Ф5/8
Ф5/8
Net dimension(W×H×D)
Packing dimension(W×H×D)
Net/Gross weight
Liquid side
Gas side
Drain piping
Wireless remote controller RM05/BG(T)E-A
36-1/32×11-13/32×9-1/16
40-5/32×15-11/32×12-13/32
42-7/32×12-13/32×9-1/16
46-15/32×16-11/32×12-13/32
Standard controller
R410A DC Inverter VRF 44R410A DC Inverter VRF43
Weekly Schedule Centralized Controller
MD-CCM03
MD-CCM02
MD-CCM09
Outdoor Centralized Controller
Network MonitoringController
Web Monitoring Tool
MD-CCM07
MD-CCM08
Midea Router
Midea Remote Service Centre
User’s Monitoring System
Indoor Centralized Controller
MD-NIM01
Note: The wires in the diagram show the signal flows only,while not represent the actual connecting ways.
Individual controlCentralized Control
Connectable tovarious sized BMS/BAS
Accessories
KJR-10BKJR-12B
RM05
Card-key Interface
Infared Sensor
Remote controller
Wire controller
MD-NIM05
MD-NIM09
485A-I
MD-CCM08
Outdoor units
Building Management System
Control Systems
R410A DC Inverter VRF 46R410A DC Inverter VRF45
Portable device
Background light
Wireless remote controller is a portable control device. It provides a convenient way for users to control the AC everywhere within a range up to 36ft.
Explicit user interfaceUsers can synchronize the air conditioners’ parameter with the display panel of the wireless remote controller. It’s the very way to make the room environment precisely work at the user’s will.
Background light allows user operate the device in the dark room freely. The device lights whenever the keys are pressed and last during the whole operating procedure.
Built-in timerBuilt-in daily timer offers the convenience of automatically starting and turning down the air conditioners according to the set time.
Addressing settingBesides the machine’s auto assigning addresses function, users can set the indoor unit’s address via the wireless remote controller.
Functions
WIRELESS REMOTE CONTROLLER
Dimensions
Power
Model
1.5V(LR03/AAA)×2
RM05
5-29/32in.×2-9/16in.×25/32in.
Specifications
Temp
ON/OFF
Time ON/OFF
Fan speed
Transmitting display
Lock
Running mode
Economic operation
1
2
4
7
8
3
6
9
Time5
ON OFF
0 3 6 9 12 15 18 21
75.2°F
Time
RM05
ON OFF
The inddor unit is set to work at automode from 8:00 to 20:00
On/Off
Operation mode setting
Heating mode
Fan speed setting
Room temp. setting
Vertical swing
Horizontal swing
Economic mode
Group setting
Key lock
Backlight
Current time
RC prohibition
Address
Error code
Period
On/Off per day
On/Off per week
On/Off timer
FOLLOW ME
Emergent stop
Emergent start
Address setting
BMS access
Control via internet
MAX. controllable IDU 1 1 16/64 1024
Model name RM05MD-CCM03MD-CCM09
KJR-90BMDV-WLJKXTKJR-10B
KJR-12B
Item Remote Wired Controller3rd-generation
Monitoring SystemCentralized Controller
AC control function
Display
Timer
Control
: Each of this kind of controller has the corresponding functions. : This function is optional. : This function is not available through the corresponding controller.
/Week
/4
/28
Comparison of Controllers
R410A DC Inverter VRF 48R410A DC Inverter VRF47
Built-in timer
Functions
Follow me
Easy connection
With the FOLLOW ME function, the wired controller can detect the air temperature at the user’s altitude instead that of the ceiling or the floor. This helps making the room environment comfortable and the temperature accurate.
Built-in daily timer offers the convenience of automatically starting and turning down the air conditioners according to the set time.
Wired controller conveniently connects to the indoor unit’s display panel with the appropriative connecting wire.
Easy installationThe wired controller allows to be installed into the wall by fixing the bottom directly or fixing the device to a mounting cabinet.
Wired Controller
Dimensions
Power
Model 10B
4-3/4in.×4-3/4in.×19/32in.
Power from the display panel. Extra power is unnecessary.
12B
4-3/4in.×4-3/4in.×19/32in.
Specifications
0 3 6 9 12 15 18 21
75.2°F
Time
Sensor part
FOLLOW ME Button
KJR-10B KJR-12B
ON OFF
KJR-10B Wire controller
Indoor main board
Display panel
The inddor unit is set to work at automode from 8:00 to 20:00
(1.6)
Error code or protection code
Connectingstatus matrix
GROUP QUERY RUN SET
SET.TEMPROOM.TEMP
#GROUPALLINLINE ON OFF
Hr HrON
T3 OFFT2AT2B
ERRORPROTECT
MODE
FAN
AUTO
OPR.UNSUCCESS
00+
01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16
16+
32+
48+
#
Functions
Centralized control Three lock modes
Single/unified control mode
MD-CCM03 is a multifunctional device which is able to control up to 64 indoor units. And the connection length can be up to 3,937ft. With the newly designed machines, this device connects to the master outdoor unit, making the centralized wiring quite simple.The 2 ways of connecting is as follows:
Centralized controller MD-CCM03 provides a superior way to manage the indoor units. Users are able to make their own choice from locking the wireless controller, locking the running mode or lock the MD-CCM03’s keyboard, as they wish.
The control object can be either single or all, making the controlling operation convenient and easy. With the operation signal feedback, users ensure their machines work at the precise working mode.
Indoor unit working status displayMD-CCM03 displays both the indoor units working status and the error codes. Via checking the error codes table in the user manual, users can easily find out the malfunction and call the repairman.
Access to network monitoringMD-CCM03 is able to bridge up to 64 indoor units to the network monitoring system and the building management system.
INDOOR CENTRALIZED CONTROLLER Centralized Controller
Dimensions(H×W×D)
Power
6-11/16in.×4-5/16in.×2-3/4in.
198-242V(50/60Hz)
Model MD-CCM03
Specifications
MD-CCM03
Locking
Running
Mode
Locking
Remote
Controller
Locking
Keyboard
Centralized
Controller
MD-CCM03
MAX.64
OPR.UNSUCCESS
X,Y,E
X,Y,E X,Y,E X,Y,E X,Y,E
P,Q,E P,Q,E P,Q,E
R410A DC Inverter VRF 50R410A DC Inverter VRF49
Single/unified control modeThe control object can be either single or all, making the controlling operation convenient and easy. With the operation signal feedback, users ensure their machines work at the precise working mode.
Functions
Weekly schedule
Three lock modes
MD-CCM09 allows up to 64 indoor units making the weekly schedule. Users can set up to 4 periods per day and select the desired running mode and room temperature. The operating object could be any indoor unit or all the indoor units.
Centralized controller MD-CCM03 provides a superior way to manage the indoor units. Users are able to make their own choice from locking the wireless controller, locking the running mode or lock the MD-CCM03’s keyboard, as they wish.
Indoor unit working status display
MD-CCM03 displays both the indoor units working status and the error codes. Via checking the error codes table in the user manual, users can easily find out the malfunction and call the repairman.
WEEKLY SCHEDULE CENTRALIZED CONTROLLER
Centralized Controller
Dimensions(H×W×D)
Power
6-11/16in.×4-5/16in.×2-3/4in.
198-242V(50/60Hz)
Model MD-NIM09
Specifications
MD-CCM09
Locking
Running
Mode
Locking
Remote
Controller
Locking
Keyboard
Centralized
Controller
Sun
Mon
Tue
Wed
Thu
Fri
Sat
71.6°F
71.6°F
off
8:00 16:00 23:5982.4°F
78.8°F
78.8°F
78.8°F
78.8°F
78.8°F
82.4°F
71.6°F
71.6°F
71.6°F
17°F
17°F
17°F
73.4°F
73.4°F
73.4°F
78.8°F
78.8°F
75.2°F
71.6°F 75.2°F
OPR.UNSUCCESS
(1.6)
Error code or protection code
Connectingstatus matrix
GROUP QUERY RUN SET
SET.TEMPROOM.TEMP
#GROUPALLINLINE ON OFF
Hr HrON
T3 OFFT2AT2B
ERRORPROTECT
MODE
FAN
AUTO
OPR.UNSUCCESS
00+
01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16
16+
32+
48+
#
UNIFIED ON/OFF CONTROLLER
Functions
Unified control
Centralized control
KJR-90B only offers the on/off and heating/cooling choice for the indoor unit. And the running temperature is set to be comfortable previously. By this way, the indoor environment is quite convenient to manage.
KJR-90B centralized control up to 16 indoor units.
Light indicatorThe lights of the KJR-90B indicate the indoor unit’s running mode. This helps discovering the abnormal indoor unit. After the operations, the lights will fade to save energy and avoid disturbance. The indications are as follows:
Easy installationKJR-90B can be easily mounted on the built-in cabinet:
Unified controller designed with graceful appearance and explicit panel.
Centralized Controller
Single On/Off key
Unified On/Off key
Light Blue
Cooling/Fan
Red
Heating
Flash
IDU Error
EEPROM Error
Dimensions(H×W×D)
Power
3-9/16in.×3-3/8in.×5/16in.
Powered from display panel. Extra power unnecessary.
Model KJR-90B
Specifications
KJR-90B
68°Fcooling
82°Fheating
Max.16
R410A DC Inverter VRF 52R410A DC Inverter VRF51
Friendly user interface3rd generation monitoring system offers a simple and explicit user interface to allow realize its functions simply.3rd generations monitoring system is able to control up 1024 indoor units and 512 outdoor units.
Group definition 3rd
3RD GENERATION MONITORING SYSTEM
Central Control Software
Functions
The layout drawing of the floor makes it easy to select the desired unit. Click the unit to operateThe structure of the building
Multiple functions
Running parameter display
3rd generation system is able to realize the remote control of indoor units. The command of indoor unit can be both the normal ones, such as changing the running modes, adjusting the temp., timer functions, and the higher class command, such as excluding the other controllers to realize unique PC control.
3rd generation system can synchronize both the indoor and outdoor units’ running status and parameters, to realize the visual control of the refrigerant system. Moreover, the 3rd generation system records the running status and error information of the refrigerant system, which helps the maintenance accurate and easy.
Electricity charge apportionment
The principle of the electricity distribution
With the appropriate devices, 3rd generation system can record the total electricity consumption and the on/off time of the outdoor units. And with the indoor units’ actual cooling power, the software intelligently distributes the power consumption to each indoor unit. Moreover, the software can generate the electricity charge bills and the bill of the indoor units’ on/off time, which is a basis of the power consumption.
Normal
Funtions
Group
Settings
3rd generation
monitoring
system
Unique
PC Control
Running
status
Reports
0%
10.2% 10.2%
20%
35% 35%35.3%
35.1%
19.4%
Room01 Room02 Room03 Room04
Actual Usage Rate
Displayed Rate
10%
20%
30%
40%
power distributionRoom02(120kWh)
Room01(60kWh)
Room04(210kWh)
Room03(210kWh)
Room 01 electric powerconsumption
Demand capacityof Room01 Total power
consumptionTotal demand capacityof indoor units
R410A DC Inverter VRF 54R410A DC Inverter VRF53
Network example
Monitoring units via local web
Wide compatibility
Contains 4 groups of RS-485 communication ports and be able to connect up to 256 indoor units or 128 outdoor units to the BMS.Be free to connect to the BMS or not.Be compatible with 3rd generation monitoring software Firebird.Monitor machines via local network.
MD-CCM08 allows users explore the units via local network, simply using the Internet Explorer. Moreover, users can not only check the units running conditions, but also change the running parameter of the units, which is quite convenient for users to control.
BACNET® BMS GATEWAY Accessories
CCM08 has a wonderful adaptability to the BMS.
Company BMS software
1
2
3
4
5
SIMENS
TRANE
Honeywell
Schneider
Johnson
Brand
APOGEE
Tracer Summit
Alerton
Andover
METASYS
MD-CCM08
BMS
Outdoor units
Outdoor units
Indoor units
BACnet/IP protocol
APOGEEA N Y W H E R E
TM
TRACER SUMMT
CCM03
CCM03
TCP/IP
MD-CCM08
RS485
CCM02
Monitoring system
HUB
Indoor units
Network example
Cooperate with the 3rd generation monitoring software.Enables centralized control of up to 1024 indoor units and 512 outdoor units to the LonWorks BMS.Easily connects to the BMS system.Ideal for scattered units of large projects, such as high office buildings, etc.
LONWORKS® BMS GATEWAY Accessories
UPS is recommended only, not necessary.
PC should be field supplied. 3-core shield twisted pair lines should be applied to the network.
Recommended config
Packing list
Operating system
Packing list MD-CCM07 and power converter
WIN2000/WIN XP SP4
CPU
HDD
Interface port
Software
Database
Electricity meter
Pentium 4 2G or above
40G free space
2 RS-232 terminals and 3 USB ports
3rd generation monitoring software kit
Microsoft SQL Sever 2000 personal edition
Chint DTS634 or corresponding model
MD-CCM07
Outdoor side
MD-CCMO7gateway
Indoor sideUPS
R410A DC Inverter VRF 56R410A DC Inverter VRF55
Indications and installation
Low power consumption
Calculate the power consumption.Do not need adjustment after working for long periods.One outdoor unit corresponds one digital power meter.
The digital power meter works at low consumption. The working power is as follows:Voltage circuit: less than 2W/10VACurrent circuit: less than 2.5VA
DIGITAL POWER METER DTS634
19/32in. long crack
7-29
/32i
n.
9-1/
16in
.5-5/32in.5-23/32in.
A phaseB phaseC phase
LCD
2-27/32in.
Impulse
Installation example Electrical wiring
Cooperate with the wired controller to realized humanistic automatic control. High voltage power is unnecessary, making the device safe and steady.Auto-restart function inside.
Automatically adjust the room environment.Automatically extend the shutting down time, avoiding frequent ON/OFF.Graceful appearance accommodates itself to the different buildings.
HOTEL CARD KEY INTERFACE MODULE
INFRARED SENSOR CONTROLLER
Accessories
Wired controller is necessary in this card-key system.
220V
CN
2
CN
1
Installation example Electrical wiring
MD-NIM09 works together with the wired controller.
Dimensions(H×W×D)
Power
3-3/8in.×2-7/8in.×5/8in.
Powered from display panel. Extra power unnecessary.
Model MD-NIM05
Dimensions(H×W×D)
Power
Senor part: 1-13/16in.×1-3/16in.×1in., Control box: 3-3/8in.×2-7/8in.×5/8in.
Powered from display panel. Extra power unnecessary.
Model MD-NIM09
Specifications
Specifications
MD-NIM05
MD-NIM09
S1
Infra-red inductive controller
Infra-red sensor
Infra-red inductive control box
KJR-10B Wire controller
Indoor main board
Display panel
CN3CN2CN1MD-NIM09/E
KJR-10B
KJR-10B
Card key
MD-NIM05MD-NIM05
Card keyAC contactor
KM
KJR-10BKJR-10B
MD-NIM09 MD-NIM09
The digital power meter is checked to be up to standard after it is manufactured, so it's able to work at once on the project site. The lights indications and the installation are as the left.
R410A DC Inverter VRF 58R410A DC Inverter VRF57
It contains project information such as project name, nation, location, etc. Detailed meteorologic datas make the machines selected fit for the local environment well.
Midea has developed a new program to design V4+ systems which meets the consultants’ and distributors’ requirements. The software provides a quick and convenient selection for users, which supports multi-languages. Greatly improving the selection efficiency and simplifying the procedure.
Selection software
ProjectIt provides two calculation methods. Directly decide the room load or input the detailed parameters such as room area, estimated cooling/heating load index, heating capacity and cooling capacity.
Load calculation
There are 5 types and 39 models of indoor units and 29 models of outdoor units for choosing.
A/C selectionPiping drawing shows the detailed layout of an A/C system and parameters of piping and branch distributors.
Piping drawing
To select the right central controller for indoor units and outdoor units; wireless or remote controller for indoor units.
Controller selectionOutput a total report of selection project in word or PDF format.
Report output
Accessories
R410A DC Inverter VRF 60R410A DC Inverter VRF59
FQZHN-01C
FQZHN-02C
FQZHN-03C
FQZHN-04C
FQZHN-05C
OD
:1/2
ID:1
/4
ID:3
/8
OD
:1/2
OD
:1/2
ID:1
/2
ID:3
/8
ID:1
/2
ID:1
/4
ID:3
/8
ID:5
/8
OD
:5/8
ID:3
/4(ID:1
/2)
OD
:5/8
ID:3
/8
ID:5
/8
(ID:1
/2)
OD
:5/8
ID:3
/8
ID:1
/4
ID:1
-3/8
ID:1
-5/8
ID:1
-3/8
ID:1
-5/8
ID:1
-5/8
ID:1
-3/4
ID:1
-3/4
OD:
1-5/
8
ID:1
-1/8
ID:1
-1/4
OD
:1-1
/8
ID:1
-1/8
ID:3
/4ID
:7/8
OD
:1-1
/8
ID:3
/4
ID:7
/8
OD
:1-1
/8
ID:5
/8
ID:5
/8
(ID:3
/4)
OD
:7/8
ID:7
/8
OD
:7/8
ID:7
/8
ID:1
ID:5
/8
(ID:3
/4)
OD
:7/8
ID:1
/2
ID:5
/8
(ID:3
/4)
OD
:7/8
ID:7
/8
OD
:7/8
ID:7
/8
ID:1
ID:5
/8
(ID:3
/4)
OD
:7/8
ID:1
/2
ID:1
/2
(ID:5
/8)
OD
:3/4
ID:3
/4
OD
:3/4
ID:3
/4
ID:7
/8ID:1
/2
(ID:5
/8)
OD
:3/4
ID:3
/8
ID:1
/2
(ID:5
/8)
OD
:3/4
ID:3
/4
OD
:3/4
ID:3
/4
ID:5
/8ID:1
/2
(ID:5
/8)
OD
:3/4
ID:3
/4
ID:7
/8
ID:1
-1/8
OD:
1-3/
8
ID:1
-3/8
OD:
1-3/
8
ID:1
-1/2ID
:7/8
ID:1
-1/8
OD:
1-3/
8
ID:1
-3/8
OD
:1/2
ID:3
/8
ID:3
/8
ID:1
/4
OD
:3/8
ID:1
/4
OD
:3/8
ID:3
/8
Name Gas side joints Liquid Side Joints
Refrigerant DistributorsIndoor branch drawing
Accessories Model Feature Model name Description
FQZHW-02N1C For two outdoor units connection
For two outdoor units connectionFQZHW-03N1C
FQZHW-04N1C For four outdoor units connection
SBH-01
SBH-03
SBH-04
For high static pressure duct and A5 duct
type indoor units(Option)
FQZHN-01C
FQZHN-02C
FQZHN-03C
FQZHN-04C
FQZHN-05C
A*<56.6MBH
56.6MBH≤A*<112.6MBH
112.6MBH≤A*<225.2MBH
225.2MBH≤A*<313.9MBH
313.9MBH≤A*
Branch joint for 410A
outdoor unit
(Not for Mini VRF)
Branch joint for R410A
indoor unit
Drain pump kit
A*:The total capacity of indoor units following this branch joint
R410A DC Inverter VRF 62R410A DC Inverter VRF61
Outdoor branch FQZHW-02N1C FQZHW-03N1C FQZHW-04N1C
Gas side
Liquid side
Oil balance pipe
0D:3/4
ID:7/8
ID:3/4
Y3
ID:5/8
ID:3/4
ID:5/8
ID:5/8
0D:5/8ID:1/2
ID:1/2
0D:5/8
Y1
Y6Y2
ID:3/4ID:7/8
ID:5/8
0D:5/8ID:5/8
ID:1/2
Y1
Y7
ID:3/4ID:7/8
ID:5/8
0D:5/8ID:5/8
ID:1/2
Y1
Y7
ID:1ID:1
ID:5/8
0D:5/8ID:5/8
ID:1/2
Y1
Y8
0D:1
ID:7/8Y5
0D:7/8
ID:3/4
Y4
ID:5/8
ID:5/8
ID:3/4
ID:5/8
0D:5/8ID:1/2
ID:1/2
0D:5/8
Y1
Y6Y2
ID:5/8
ID:3/4
ID:5/8
ID:5/8
0D:5/8ID:1/2
ID:1/2
0D:5/8
Y1
Y6Y2
0D:1-3/8
ID:1-1/2
ID:1-3/8
Q3
ID:1-3/8
ID:1-1/4
ID:1-1/4
Q4
0D:1-1/4
ID:1
0D:1-1/4
ID:1-1/4
ID:1
Q1
Q2 ID:1-1/4
0D:1-3/8
ID:1-1/4ID:1-1/2
ID:1-3/80D:1-1/4
ID:1
0D:1-1/4
ID:1-1/4
ID:1
Q1
Q2Q7
ID:1-1/4
0D:1-3/8
ID:1-1/4ID:1-1/2
ID:1-3/80D:1-1/4
ID:1
0D:1-1/4
ID:1-1/4
ID:1
Q1
Q2Q7
ID:1-1/2
ID:1-5/8
ID:1-1/4
0D:1-1/4ID:1-1/4
ID:1
Q1
Q5
ID:1-1/2
ID:1-5/8
ID:1-1/4
0D:1-1/4ID:1-1/4
ID:1
Q1
Q5ID:1-5/8
ID:1-3/4
ID:1-1/4
0D:1-1/4ID:1-1/4
ID:1
Q1
Q6
Outdoor branch drawing
ID:1/4
P(Two)P
ID:1/4
Memo