MINI VRF DC INVERTER
Technical ManualMini VRF Outdoor Units
8 Kw 10 Kw 12 – 14 15.5–17.5 Kw
20–22.4–26 Kw 40 – 45 Kw
Smar t Energy Saving Green Air Conditioning SolutionsFor Small Scale Residential & Light Commercial Applications
MiracoMiracoMISR REFRIGERATION & AIR CONDITIONING MFG. CO.
improve
buildingsTM
the environmentally sound refrigerant
ww
w.m
iraco
.com
.eg
2
MINI VRF
MINI VRF DC INVERTER Key Features
Variety ofApplications
Residential Light Commercial
( 1 )
AdvancedDesign
Variety of outdoor unit Variety of indoor units
Type & Ranges
( 2 )
WideOutdoor Units
Lineup8 kW to 45 kW
( 3 )
WideIndoor Units
Lineup1.8 kW to 56 kW
( 4 )
WideSelection
Selection software provides flexibility of model selection
( 5 )
WideApplication
Range
( 6 )
( 11 )
Variety ofControls
Individual Controls Wireless Control Wired Control
Central Controls
( 12 )
Variety ofAccessories
EasyInstallation
Service &Maintenance
( 13 ) ( 14 )
HighDurability
( 7 )
SuperQuiet
( 8 )
Enhanced Comfort
High Reliability
( 9 ) ( 10 )
HighEfficiency
( Key Features )14
Rev. (0) - 2016
3
Variety of Applications
Small Scale Residential & Light Commercial Applications
Luxury Apartments
Restaurants
Villas
Offices
Traditional Air Conditioning System
Mini VRFAir Conditioning System
Carrier Mini VRF DC Inverter Systems are Variable Refrigerant Flow R410A Heat Pump Systems.
Carrier Mini VRF DC Inverter Systems are smart energy saving green - air conditioning solutions for small scale residential and light commercial applications for a wide range of environmental conditions and for improvement of bulding appearance.
ww
w.m
iraco
.com
.eg
4
MINI VRF
MINI VRF DC INVERTER Advanced Design
Mini VRF Outdoor Units – Design Layout
Side discharge
2 Pipe system
Outdoor unit includes DC Inverter Compressor + all DC fan motor (s)
Combination Table :
OneOutdoor Unit
Power SupplyV / Ph / Hz
CapacityKw
Maximum Quantityof Indoor Units
220-240 / 1 / 50 8 4
220-240 / 1 / 50 10 5
220-240 / 1 / 50380-415 / 3 / 50 12 6
220-240 / 1 / 50380-415 / 3 / 50 14 6
220-240 / 1 / 50380-415 / 3 / 50 15.5 7
380-415 / 3 / 50 17.5 9
380-415 / 3 / 50 20 10
380-415 / 3 / 50 22.4 11
380-415 / 3 / 50 26 12
380-415 / 3 / 50 40 14
380-415 / 3 / 50 45 15
Rev. (0) - 2016
5
Mini VRF DC Inverter Outdoor Units - Model Identification
Digital No. 1 2 3 4 5 6 7 8 9 10 11 12 13 14Code 3 8 V R 0 0 5 H 1 1 2 0 1 0
1, 2Product Type38 : Outdoor Unit3, 4Product ClassificationVR: MINI VRF DC Inverter5, 6, 7Cooling Capacity003 : 8 kW 004 : 10-12kW005 : 14 kW 006 : 15.5 KW007 : 17.5 - 20 kW 008 : 22.4 kW 010 : 26 kW 014 : 40 kW 016 : 45 kW8Application H : Heat pumpC : Cool Only9Refrigerant 1 : R410A10Market 1 : Egypt & Export11Electrical Characteristics 2 : 220-240V-1PH-50HZ9 : 380-415V-3PH-50HZ12Packing 0 : Standard packing 1 : Crate packing13Model Type 1 : MINI DC Inverter14Model revision code 0 : Side Discharge Type S : Side Discharge Type
8 Kw 10 Kw 12 – 14 15.5–17.5 Kw
20–22.4–26 Kw 40 – 45 Kw
ww
w.m
iraco
.com
.eg
6
MINI VRF
MINI VRF DC INVERTER Advanced Design
Mini VRF DC Inverter Outdoor Units - Technical Specifications
Outdoor Unit Model 38VR003H112010 38VR004H11201S 38VR004H112010
Power Supply V / Ph / Hz 220-240 / 1 / 50 220-240 / 1 / 50 220-240 / 1 / 50
Cooling (1)
Capacity kW 8 10 12Input kW 3.4 3.75 3.95EER kW / kW 2.35 2.67 3.04
Heating (2)
Capacity kW 9 11.5 13.2Input kW 2.8 3.5 3.55COP kW / kW 3.21 3.29 3.72
Max. current A 18.5 22.8 24.4
Connected Indoor UnitsTotal Capacity % 45% ~ 130% 45% ~ 130% 45% ~ 130%Max Quantity 4 5 6
Compressor
Quantity 1 1 1
Type DC InverterTwin Rotary
DC InverterTwin Rotary
DC InverterTwin Rotary
Model TNB220FLHMC TNB220FLHMC TNB306FPGMCCapacity Btu/h 24334 24334 33642
Input W 2200 2200 3010Rated current(RLA) A 9.7 9.7 13.5Crankcase heater W 25 25 25
Refrigerant oil ml FV50S 670ml+200ml FV50S 670ml+200ml FV50S 870ml+630ml
Outdoor Fan Motor
Quantity 1 1 2Type DC Motor DC Motor DC Motor
Model WZDK170-38G-1 WZDK170-38G-1 WZDK100-38GInsulation class E E E
Safe class IPX4 IPX4 IP23Input W 195 195 2*100
Output W 170 170 2*85Rated current A 1.6 1.6 2*0.9
Speed r/min 820 820 800
Outdoor Fan
Material ASG20 ASG20 ASG20Type Axial fan Axial fan Axial fan
Diameter mm 560 560 508Height mm 170 170 170
12 kW10 kW8 kW
Rev. (0) - 2016
7
Wide Outdoor Units Lineup
Mini VRF DC Inverter Outdoor Units - Technical Specifications
Outdoor Unit Model 38VR003H112010 38VR004H11201S 38VR004H112010
Outdoor Coil
Number of rows 1.7 2 2Tube pitch(a) x row pitch(b) mm 22 x 19.05 25.4 x 22 22 x 19.05
Fin spacing mm 1.6 1.6 1.6Fin type (code) Hydrophilic aluminum
Tube outside dia. mm Ф7.94 Ф9.52 Ф7.94Tube type Inner groove tube
Coil length x height mm 890 x 880 880 x 914 1276 x 870Number of circuits 9 5 7
Outdoor Air Flow m3/h 5500 5500 6000Outdoor Sound Pressure Level (3) dB(A) 56 57 57
Outdoor Unit
Dimension(WxHxD) mm 1075 x 966 x 396 1075 x 966 x 396 900 x 1327 x 400Packing (WxHxD) mm 1120 x 1015 x 435 1120x1015x435 1030 x 1456 x 435Net/Gross weight kg 75.5 / 85.5 75.5 / 85.5 95 / 106
RefrigerantType R410A R410A R410A
Factory Charge g 2950 2950 3300Refrigerant Control Electronic Expansion ValveDesign Pressure MPa 4.4 / 2.6 4.4 / 2.6 4.4 / 2.6
Refrigerant Piping Lines (5)
Liquid side mm Ø 9.53 Ø 9.53 Ø 9.53Gas side mm Ø 15.9 Ø 15.9 Ø 15.9
Max. refrigerant pipe length inch 100 100 100
Max. difference in level mm 8 8 8
Electrical Connections
Power Wiring mm2 3 core × 4.0 3 core × 4.0 3 core× 4.0
Control WiringShielded mm2 3 core shielded
wire × 0.753 core shielded
wire × 0.753 core shielded
wire x0.75Notes:
1. Cooling conditions: indoor temp.: 27°C DB / 19°C WB; outdoor temp.: 35°C DB / 24°C WB
2. Heating conditions: indoor temp.: 20°C DB/15°C WB outdoor temp.: 7°C DB / 6°C WB
3. Sound level : is measured in a semi-anechoic chamber conversion value, measured at a position 1 m in front of the unit 0.9m for 8 Kw, 1m for 10 Kw, 1.2m for 12 Kw.
4. Inter connecting refrigerant piping length is 7.5m, level difference is zero.
5. Interconnecting refrigerant piping diameters are based on the condition that the total equivalent liquid line length is less than 90 meter. When the total equivalent liquid line length is more than 90 meter, Please refer to the installation manual to choose interconnecting refrigerant piping diameter.
12 kW10 kW8 kW
ww
w.m
iraco
.com
.eg
8
MINI VRF
MINI VRF DC INVERTER Advanced Design
Outdoor Unit Model 38VR005H112010 38VR006H112010
Power Supply V / Ph / Hz 220-240 / 1 / 50 220-240 / 1 / 50
Cooling (1)
Capacity kW 14 15.5Input kW 4.85 5.65EER kW / kW 2.89 2.74
Heating (2)
Capacity kW 15.4 17Input kW 4.35 5.5COP kW / kW 3.54 3.09
Max. current A 29.8 30
Connected Indoor UnitsTotal Capacity % 45% ~ 130% 45% ~ 130%Max Quantity 6 7
Compressor
Quantity 1 1
TypeDC Inverter Twin Rotary
DC Inverter Twin Rotary
Model TNB306FPGMC LNB42FSCMCCapacity Btu/h 33642 47700
Input W 3010 4240Rated current(RLA) A 13.5 16.1Crankcase heater W 25 25
Refrigerant oil ml FV50S 870ml+630ml FV50S 1400ml+250ml
Outdoor Fan Motor
Quantity 2 2Type DC Motor DC Motor
Model WZDK100-38G WZDK100-38GInsulation class E E
Safe class IP23 IP23Input W 2 x 100 2 x 100
Output W 2 x 85 2 x 85Rated current A 2 x 0.9 2 x 0.9
Speed r/min 800 800
Outdoor Fan
Material ASG20 ASG20Type Axial fan Axial fan
Diameter mm 508 508Height mm 170 170
Mini VRF DC Inverter Outdoor Units - Technical Specifications
14 –15.5 kW
Rev. (0) - 2016
9
Wide Outdoor Units Lineup
Outdoor Unit Model 38VR005H112010 38VR006H112010
Outdoor Coil
Number of rows 2 2Tube pitch(a) x row pitch(b) mm 22 ×19.05 22 ×19.05
Fin spacing mm 1.6 1.6Fin type (code) Hydrophilic aluminum
Tube outside dia. mm Ф 7.94 Ф 7.94Tube type Inner groove tube
Coil length x height mm 1276 × 870 1276 × 870Number of circuits 7 7
Outdoor Air Flowm3/h 6000 6000cfm 57 57
Outdoor Sound Pressure Level (3) dB(A) 57 / 54 57 / 54
Outdoor Unit
Dimension(WxHxD) mm 900 x 1327 x 400 900 x 1327 x 400Packing (WxHxD) mm 1030 x 1456 x 435 1030 x 1456 x 435Net/Gross weight kg 95 / 106 100 / 111
RefrigerantType R410A R410A
Factory Charge g 3900 3900Refrigerant Control Electronic Expansion ValveDesign Pressure MPa 4.4 / 2.6 4.4 / 2.6
Refrigerant Piping
Lines (5)
Liquid side mm Ø 9.53 Ø 9.53Gas side mm Ø 15.9 Ø 15.9
Max. refrigerant pipe length inch 100 100
Max. difference in level mm 8 8
Electrical Connections
Power Wiring mm2 3 core × 4.0 3 core × 4.0Control Wiring
Shieldedmm2 3 core shielded wire × 0.75 3 core shielded wire× 0.75
Notes:
1. Cooling conditions: indoor temp.: 27°C DB / 19°C WB; outdoor temp.: 35°C DB / 24°C WB
2. Heating conditions: indoor temp.: 20°C DB/15°C WB outdoor temp.: 7°C DB / 6°C WB
3. Sound level : is measured in a semi-anechoic chamber conversion value, measured at a position 1 m in front of the unit 0.9m for 8 Kw, 1m for 10 Kw, 1.2m for 12 Kw.
4. Inter connecting refrigerant piping length is 7.5m, level difference is zero.
5. Interconnecting refrigerant piping diameters are based on the condition that the total equivalent liquid line length is less than 90 meter. When the total equivalent liquid line length is more than 90 meter, Please refer to the installation manual to choose interconnecting refrigerant piping diameter.
Mini VRF DC Inverter Outdoor Units - Technical Specifications
14 –15.5 kW
ww
w.m
iraco
.com
.eg
10
MINI VRF
MINI VRF DC INVERTER Advanced Design
Mini VRF DC Inverter Outdoor Units - Technical Specifications
12 –14 –15.5 kW
Outdoor Unit Model 38VR004H119010 38VR005H119010 38VR006H119010
Power Supply V / Ph / Hz 380-415 / 3 / 50 380-415 / 3 / 50 380-415 / 3 / 50
Cooling (1)
Capacity kW 12 14 15.5Input kW 3.9 4.75 5.6EER kW / kW 3.08 2.95 2.77
Heating (2)
Capacity kW 13.2 15.4 17Input kW 3.75 4.55 5.4COP kW / kW 3.52 3.38 3.15
Max. input consumption W 5400 6200 7100Max. current A 10 11 12
Connected Indoor UnitsTotal Capacity % 50% ~ 130% 50% ~ 130% 50% ~ 130%Max Quantity 6 6 7
Compressor
Quantity 1 1 1
TypeDC Inverter Twin Rotary
DC Inverter Twin Rotary
DC Inverter Twin Rotary
Model TNB306FPNMC TNB306FPNMC LNB42FSAMCCapacity Btu/h 33720 33720 47700
Input W 3010 3010 4240Rated current(RLA) A 9.3 9.3 12Crankcase heater W 27 27 25
Refrigerant oil ml FV50S 870+630ml FV50S 870+630ml FV50S 1400ml
Outdoor Fan Motor
Quantity 2 2 2Type DC Motor DC Motor DC Motor
Model WZDK100-38G WZDK100-38G WZDK100-38GInsulation class E E E
Safe class IP23 IP23 IP23Input W 2 x 100 2 x 100 2 x 100
Output W 2 x 85 2 x 85 2 x 85Rated current A 2 x 0.9 2 x 0.9 2 x 0.9
Speed r/min 800 800 800
Outdoor Fan
Material ASG20 ASG20 ASG20Type Axial fan Axial fan Axial fan
Diameter mm 508 508 508Height mm 170 170 170
Rev. (0) - 2016
11
Mini VRF DC Inverter Outdoor Units - Technical Specifications
12 –14 –15.5 kW
Outdoor Unit Model 38VR004H119010 38VR005H119010 38VR006H119010
Outdoor Coil
Number of rows 2 2 2Tube pitch(a)x row pitch(b) mm 22 x 19.05 22 x 19.05 25.4 x 22
Fin spacing mm 1.6 1.6 1.6Tube outside dia. mm Ф7.94 Ф7.94 Ф7.94
Tube type Inner groove tube Inner groove tube Inner groove tubeCoil length x height mm 1276 x 870 1276 x 870 1276 x 870Number of circuits 7 7 7
Outdoor Air Flow m3/h 6000 6000 6000Outdoor Sound Pressure Level (3) dB(A) 57 57 57
Outdoor Unit
Dimension(WxHxD) mm 900 x 1327 x 400 900 x 1327 x 400 900 x 1327 x 400Packing (WxHxD) mm 1030 x 1456 x 435 1030 x 1456 x 435 1030 x 1456 x 435Net/Gross weight kg 95/106 95/106 102/113
RefrigerantType R410A R410A R410A
Factory Charge g 3300 3900 3900Refrigerant Control Electronic Expansion ValveDesign Pressure MPa 4.4 / 2.6 4.4 / 2.6 4.4 / 2.6
Refrigerant Piping Lines (5)
Liquid side mm Ø 9.53 Ø 9.53 Ø 9.53Gas side mm Ø 15.9 Ø 15.9 Ø 19.1
Max. refrigerant pipe length inch 100 100 100
Max. difference in level mm 8 8 8
Electrical Connections
Power Wiring mm2 5 core x2.5 5 core x2.5 5 core x2.5Control Wiring
Shieldedmm2 3 core shielded
wire x 0.753 core shielded
wire x 0.753 core shielded
wire x 0.75Notes:
1. Cooling conditions: indoor temp.: 27°C DB / 19°C WB; outdoor temp.: 35°C DB / 24°C WB
2. Heating conditions: indoor temp.: 20°C DB/15°C WB outdoor temp.: 7°C DB / 6°C WB
3. Sound level : is measured in a semi-anechoic chamber conversion value, measured at a position 1.2 m in front of the unit
4. Inter connecting refrigerant piping length is 7.5m, level difference is zero.
5. Interconnecting refrigerant piping diameters are based on the condition that the total equivalent liquid line length is less than 90 meter. When the total equivalent liquid line length is more than 90 meter, Please refer to the installation manual to choose interconnecting refrigerant piping diameter.
ww
w.m
iraco
.com
.eg
12
MINI VRF
MINI VRF DC INVERTER Advanced Design
Mini VRF DC Inverter Outdoor Units - Technical Specifications
17.5 kW
Outdoor Unit Model 38VR007H11901S
Power Supply V / Ph / Hz 380-415 / 3 / 50
Cooling (1)
Capacity kW 17.5Input kW 5.3EER kW / kW 3.3
Heating (2)
Capacity kW 19Input kW 5COP kW / kW 3.8
Max. input consumption W 7000Max. current A 12.5
Connected Indoor UnitsTotal Capacity % 50% ~ 130%Max Quantity 9
Compressor
Quantity 1
TypeDC Inverter Twin Rotary
Model LNB42FSAMCCapacity Btu/h 47700
Input W 4270Rated current(RLA) A 12Crankcase heater W 25
Refrigerant oil ml FV50S 1400ml
Outdoor Fan Motor
Quantity 2Type DC Motor
Model WZDK100-38GInsulation class E
Safe class IP23Input W 2 x 100
Output W 2 x 85Rated current A 2 x 0.9
Speed r/min 800
Outdoor Fan
Material ASG20Type Axial fan
Diameter mm 508Height mm 170
Rev. (0) - 2016
13
Mini VRF DC Inverter Outdoor Units - Technical Specifications
17.5 kW
Outdoor Unit Model 38VR007H11901S
Outdoor Coil
Number of rows 2.5Tube pitch(a)x row pitch(b) mm 22 x 19.05
Fin spacing mm 1.6Tube outside dia. mm Ф7.94
Tube type Inner groove tubeCoil length x height mm 1276 x 870Number of circuits 12
Outdoor Air Flow m3/h 6800Outdoor Sound Pressure Level (3) dB(A) 59
Outdoor Unit
Dimension(WxHxD) mm 900 x 1327 x 400Packing (WxHxD) mm 1030 x 1456 x 435Net/Gross weight kg 107 / 118
RefrigerantType R410A
Factory Charge g 4500Refrigerant Control Electronic Expansion ValveDesign Pressure MPa 4.4 / 2.6
Refrigerant Piping Lines (5)
Liquid side mm Ø 9.53Gas side mm Ø 19.1
Max. refrigerant pipe length inch 100
Max. difference in level mm 8
Electrical Connections
Power Wiring mm2 5 core x 2.5Control Wiring
Shieldedmm2 3 core shielded wire x 0.75
Notes:
1. Cooling conditions: indoor temp.: 27°C DB / 19°C WB; outdoor temp.: 35°C DB / 24°C WB
2. Heating conditions: indoor temp.: 20°C DB/15°C WB outdoor temp.: 7°C DB / 6°C WB
3. Sound level : is measured in a semi-anechoic chamber conversion value, measured at a position 1.2 m in front of the unit
4. Inter connecting refrigerant piping length is 7.5m, level difference is zero.
5. Interconnecting refrigerant piping diameters are based on the condition that the total equivalent liquid line length is less than 90 meter. When the total equivalent liquid line length is more than 90 meter, Please refer to the installation manual to choose interconnecting refrigerant piping diameter.
ww
w.m
iraco
.com
.eg
14
MINI VRF
MINI VRF DC INVERTER Advanced Design
Mini VRF DC Inverter Outdoor Units - Technical Specifications
20 – 22.4 – 26 kW
Outdoor Unit Model 38VR007H119010 38VR008H11901S 38VR010H11901S
Power Supply V / Ph / Hz 380-415 / 3 / 50 380-415 / 3 / 50 380-415 / 3 / 50
Cooling (1)
Capacity kW 20 22.4 26
Input kW 6.63 7.2 8.4
EER kW / kW 3.02 3.11 3.09
Heating (2)
Capacity kW 22 24.5 28.5
Input kW 5.95 6.7 7.9
COP kW / kW 3.69 3.66 3.6
Connected Indoor UnitsTotal Capacity % 50% ~ 130% 50% ~ 130% 50% ~ 130%
Max Quantity 10 11 12
Compressor
Quantity 1 1 1
TypeDC Inverter Twin Rotary
DC Inverter Twin Rotary
DC Inverter Twin Rotary
Model LNB42FSAMC LNB53FCAMC LNB53FCAMC
Capacity kW 13.98 16.86 16.86
Input kW 4.27 5.2 5.2
Crankcase heater W 25 25 25Refrigerant oil ml 1400+1300 1700+1500 1700+1500
Outdoor Fan Motor
Quantity 2 2 2
Type DC Motor DC Motor DC Motor
Model WZDK170-38G-1 WZDK170-38G-1 WZDK170-38G-1
Insulation class E E E
Safe class IPX4 IPX4 IPX4
Input W 260(up)/200(down) 250(up)/185(down) 250(up)/185(down)
Output W 210(up)/160(down) 200(up)/150(down) 200(up)/150(down)
Rated current A 2.1(up)/1.7(down) 1.7(up)/1.4(down) 1.7(up)/1.4(down)
Outdoor Fan
Quantity 2 2 2
Material ASG20 ASG20 ASG20
Type Axial fan Axial fan Axial fan
Diameter mm 560 560 560
Height mm 170 170 170
Rev. (0) - 2016
15
Mini VRF DC Inverter Outdoor Units - Technical Specifications
20 – 22.4 – 26 kW
Outdoor Unit Model 38VR007H119010 38VR008H11901S 38VR010H11901S
Outdoor Coil
Number of rows 1.6 2 2Tube pitch(a)x row pitch(b) mm 21 x 19.4 21 x 19.4 21 x 19.4
Fin spacing mm 1.5 1.5 1.5Fin type Hydrophilic fin Hydrophilic fin Hydrophilic fin
Tube outside dia. mm Ф7 Ф7 Ф7Tube type Inner groove tube Inner groove tube Inner groove tube
Coil length x height mm 1090 x 756 1080 x 756 1080 x 756Number of circuits 12 18 18
Outdoor Air Flow m3/h 10999 10494 10494Outdoor Sound Pressure Level (3) dB(A) 59 59 60
Outdoor Unit
Dimension(WxHxD) mm 1120 x 1558 x 528 1120 x 1558 x 528 1120 x 1558 x 528Packing (WxHxD) mm 1270 x 1720 x 565 1270 x 1720 x 565 1270 x 1720 x 565Net/Gross weight kg 137 / 153 146.5 / 162.5 147 / 163
RefrigerantType R410A R410A R410A
Factory Charge g 4800 6200 6200Refrigerant Control Electronic Expansion ValveDesign Pressure MPa 4.4 / 2.6
Refrigerant Piping Lines (5)
Gas mm Ф 9.53 Ф 9.53 Ф 9.53Liquid mm Ф 19.1 Ф 19.1 Ф 22.2
Electrical Connections
Power Wiring mm2 5 Wires x 6 mm2 5 Wires x 6 mm2 5 Wires x 6 mm2
Control Wiring
Shieldedmm2 3 Wires x 0.75 mm2 3 Wires x 0.75 mm2 3 Wires x 0.75 mm2
Notes:
1. Cooling conditions: indoor temp.: 27°C DB / 19°C WB; outdoor temp.: 35°C DB / 24°C WB
2. Heating conditions: indoor temp.: 20°C DB/15°C WB outdoor temp.: 7°C DB / 6°C WB
3. Sound level : is measured in a semi-anechoic chamber conversion value, measured at a position 1.2 m in front of the unit
4. Inter connecting refrigerant piping length is 7.5m, level difference is zero.
5. Interconnecting refrigerant piping diameters are based on the condition that the total equivalent liquid line length is less than 90 meter. When the total equivalent liquid line length is more than 90 meter, Please refer to the installation manual to choose interconnecting refrigerant piping diameter.
ww
w.m
iraco
.com
.eg
16
MINI VRF
MINI VRF DC INVERTER Advanced Design
Mini VRF DC Inverter Outdoor Units - Technical Specifications
40 - 45 kW
Outdoor Unit Model 38VR014H119012 38VR016H119012
Power Supply V / Ph / Hz 380-415 / 3 / 50 380-415 / 3 / 50
Cooling (1)
Capacity kW 40 45Input kW 11.9 13.6EER kW / kW 3.35 3.32
Heating (2)
Capacity kW 45 50Input kW 11.1 12.7COP kW / kW 4.05 3.93
Connected Indoor UnitsTotal Capacity % 50% ~ 130% 50% ~ 130%Max Quantity 14 15
Compressor
Quantity 2 2
TypeDC Inverter Twin Rotary
DC Inverter Twin Rotary
Model LNB42FSAMC LNB53FCAMCCapacity kW 13.98 x 2 16.86 x 2
Input kW 4.27 x 2 5.2 x 2Crankcase heater W 25 x 2 25 x 2
Refrigerant oil type FV50S FV50SRefrigerant oil charge ml 1400 x 2 + 2500 1700 x 2 + 3600
Outdoor Fan Motor
Quantity 2Type DC Motor
Model WZDK560-38G(B)Insulation class E
Safe class IP44Input W 580 / 580
Output W 560 / 560Rated current A 3.84 + 3.84
Outdoor Fan
Quantity mm 2Model PlasticType Axial fan
Diameter mm 700Height mm 200
Rev. (0) - 2016
17
Mini VRF DC Inverter Outdoor Units - Technical Specifications
40 - 45 kWOutdoor Unit Model 38VR014H119012 38VR016H119012
Outdoor Coil
Number of rows 2 2.7Tube pitch(a)×row pitch(b) mm 22 x 19.05 22 x 19.05
Fin spacing mm 1.6 1.6Fin type Hydrophilic fin Hydrophilic fin
Tube outside diameter mm Ф 7.94 Ф 7.94Tube type Inner thread tube Inner thread tube
Coil length×height mm ( 1290 + 1260 ) × 792 × 2 ( 1360 x 1390 x 930 ) × 792 × 2Number of circuits 18 24
Outdoor Air Flow m3/h 16575 16575Outdoor Sound Pressure Level (3) dB(A) 62 62
Outdoor Unit
Dimension(WxHxD) mm 1360 x 1650 x 540 1460 x 1650 x 540Packing (WxHxD) mm 1450 x 1785 x 560 1550 x 1785 x 560Net/Gross weight kg 240 / 260 275 / 290
RefrigerantType R410A R410A
Factory Charge g 90 120Refrigerant Control Electronic Expansion ValveDesign Pressure MPa 4.4 / 2.6 4.4 / 2.6Refrigerant Piping Lines (5)
Gas mm Ф 12.7 Ф 12.7Liquid mm Ф 22.2 Ф 25.4
Electrical ConnectionsPower Wiring mm2 4 Wires x 16 mm2 4 Wires x 25 mm2
Control Wiring
Shieldedmm2 3 Wires x 0.75 mm2 3 Wires x 0.75 mm2
Notes:
1. Cooling conditions: indoor temp.: 27°C DB / 19°C WB; outdoor temp.: 35°C DB / 24°C WB
2. Heating conditions: indoor temp.: 20°C DB/15°C WB outdoor temp.: 7°C DB / 6°C WB
3. Sound level : is measured in a semi-anechoic chamber conversion value, measured at a position 1.2 m in front of the unit
4. Inter connecting refrigerant piping length is 7.5m, level difference is zero.
5. Interconnecting refrigerant piping diameters are based on the condition that the total equivalent liquid line length is less than 90 meter. When the total equivalent liquid line length is more than 90 meter, Please refer to the installation manual to choose interconnecting refrigerant piping diameter.
ww
w.m
iraco
.com
.eg
18
MINI VRF
MINI VRF DC INVERTER Advanced Design
Mini VRF DC Inverter Outdoor Units - Dimensions
R: Pipe Connection
Fat Pipe
12 - 14 - 15.5 - 17.5 kW
8 - 10 kW
G
900
600
A
B
H
C D E40
036
0
320
348
1327
F
Dimensions ( mm )
Front Out Pipe Back Out PipeSide Out Pipe Under Surface Out Pipe
SizeModel A B C D E F G H
8 kW 895 590 313 302 355 333 975 86210 kW 990 624 354 336 396 366 1075 966
Rev. (0) - 2016
19
20 - 22.4 - 26 kW
40 - 45 kW
1120
C
668 205.8
1558
1650
414
494
400
528
Dimensions ( mm )
Mini VRF DC Inverter Outdoor Units - Dimensions
505BA
475
500
450
540
SizeModel A B C
40 kW 175 505 136045 kW 225 555 1460
ww
w.m
iraco
.com
.eg
20
MINI VRF
MINI VRF DC INVERTER Advanced Design
Wide VRF Indoor Units Lineup - Types & Range
1.8 - 2.2 - 2.8 - 3.64.5 - 5.6 - 7.1 Kw
1.8 - 2.2 - 2.8 - 3.6 - 4.55.6 - 7.1 Kw
2.2 - 2.8 - 3.6 - 4.5 5.6 - 7.1 Kw
2.2 - 2.8 - 3.6 - 4.5 Kw
2.2 - 2.8 - 3.6- 4.5 -5.6 Kw
2.2 - 2.8 - 3.6- 4.5 -5.6 Kw 2.2 - 2.8 - 3.6 - 4.5 - 5.6 - 7.1 - 8.0 9.0 - 10.0 - 11.2 - 12.5 - 14.0 Kw
2.8 - 3.6 - 4.5 - 5.6 - 7.1 - 8.0 9.0 - 10.0 - 11.2 - 12.5 - 14.0 Kw
3.6 - 4.5 - 5.6 - 7.1 - 8.0 9.0 - 11.2 - 14.0 Kw
2.2 - 2.8 - 3.6 - 4.5 5.6 - 7.1 - 8.0 Kw
12.5 - 14.0 - 20.0 25.0 - 28.0 Kw
2.2 - 2.8 - 3.6 - 4.5 - 5.67.1 - 8.0 Kw
7.1 - 8.0 - 9.0 - 11.2 - 14.0 16.0 - 20.0 - 25.0 - 28.0 Kw
40.0 - 45.0 - 56.0 Kw
Ducted LSP Cassette 1 Way
Ducted MSP
Concealed Floor StandingFresh Air Unit Exposed Floor Standing
Ducted HSP
Ducted Big HSP Floor - Ceiling
High Wall- S
High Wall - C
7.1 - 8.0 - 9.0 Kw
High Wall - R
Cassette 2 Way
Cassette 4 Way
Cassette Compact 4 Way
Rev. (0) - 2016
21
Ducted
Cassette
High Wall Console
Wide VRF Indoor Units Lineup – Applications
ww
w.m
iraco
.com
.eg
22
MINI VRF
MINI VRF DC INVERTER
Carrier selection software provides selection flexibility from wide range of Outdoor and Indoor Units models depending upon load conditions & diversity required for VRF projects.
Carrier selection software is used to design VRF systems which meets the consultants and distributors requirements.
Carrier selection software provides a quick and convenient selection for users, which supports multi-languages. Greatly improving the selection efficiency and simplifying the selection procedures.
Wide Selection
Carrier VRF Selection Software
ReportOutput
Multilanguage Selection
LoadCalculation
AutoCalculating
Drawing Sketch
Rev. (0) - 2016
23
ProjectIt contains project information such as project name, location, etc.Detailed meteorological data’s make the machines selected t for the local environment well.
A/C selectionThere are different types and models of indoor units and all kinds of different power of outdoor units for choosing.
Controller selectionTo select the right central controller for indoor unit and outdoor units; wireless or remote controller for indoor units.
Load calculationIt provides two calculation methods. Directly decide the room load or input the detailed parameters such as room area, estimated cooling / heating load index, heating capacity and cooling capacity.
Piping drawingPiping drawing shows the detailed piping layout of VRF system including outdoor units, indoor units and parameters of piping and branch distributors.
Output reportIt provides a total report of VRF project selection in word or PDF format.
ww
w.m
iraco
.com
.eg
24
MINI VRF
MINI VRF DC INVERTER
Mini VRF units are slimmer and more compact, resulting in significant savings in installation space. In some large residential spaces or some light commercial space, such as villa, restaurant, usually it need more than one indoor unit, so outside the building are also full of outdoor units. Now Carrier can provide an effective solution-Carrier MINI VRF DC Inverter system. Since now the beauty of the building will be back.
Wide Application Range
Wide Stable Operation Range
Space Saving Design Improves Building Appearance
Mini VRFTraditional Air Conditioning
COOLING MODE
HEATING MODE
48°C
27°C
-15°C
-15°C
Outdoor Temperature
Outdoor Temperature
-20 10 40-10 20 500 30 60
Outdoor temp. °C ( D.B )
Rev. (0) - 2016
25
Long Piping Length & Long Height Difference
Piping Installation Data 8 - 10 - 12 - 14 - 15.5 kW 17.5 - 20 - 22.4 - 26 kW 40 - 45 kW
Piping Length
Actual Total Piping Length 100 m 100 m 250 mLongest piping (L) 45 m 60 m 100 mEquivalent Longest Piping Length 50 m 70 m 120 mEquivalent Piping Length ( The farthest IDU to the first Indoor unit branch )
20 m * 20 m * 40 m *
Height Difference
Height Difference Between Indoor and outdoor units
Outdoor Unit Up 30 m 30 m 30 m
Outdoor Unit Down 20 m 20 m 20 m
Height Difference Between Indoor Units 8 m 8 m 8 m
* Total pipe length is equal to all the liquid pipe or all the gas pipe length.
8 m H
eigh
t diff
eren
ce b
etwe
en ID
Us
Heig
ht d
iffer
ence
bet
ween
IDU
and
ODU
ODU
Up 20
m
O
DU D
own
30 m
15 m
The
IDU
to th
e ne
ares
t br
anch
pip
e
20 m
The
firs
t bra
nch
join
t to
the
fart
hest
indo
or u
nit
70 m
Lon
gest
equ
ival
ent p
ipin
g le
ngth
ww
w.m
iraco
.com
.eg
26
MINI VRF
MINI VRF DC INVERTER High Efficiency
High Cooling EER / High Heating COP Values
Mini VRF Outdoor units Series with all high efficiency DC Inverter scroll compressors, all high efficiency, DC motor (s) and high efficiency heat exchanger, achieve top class Cooling Energy Efficiency Ratio EER and Heating Coefficient Of Performance COP.
Cooling EER
Heating COP
8 kW
10.5kW
12kW
17.5kW
26kW
14 kW
20kW
40kW
15.5kW
22.4kW
45kW
2.352.67
3.042.89 2.74
3.303.02 3.11 3.10
3.35 3.32
8 kW
10.5kW
12kW
17.5kW
26kW
14 kW
20kW
40kW
15.5kW
22.4kW
45kW
3.21 3.293.72 3.54
3.09
4.053.703.80 3.66 3.61
3.93
Rev. (0) - 2016
27
High Efficiency MINI VRF DC Inverter Outdoor Unit
High EfficiencyFan Housing
& Outlet Grille
High EfficiencyOutdoor Fan (s)
High EfficiencyOutdoor Coil
High EfficiencyDC Fan Motor
High EfficiencyDC Inverter Twin
Rotary Compressor
Newly DesignedFan Guard
NewDesigned Fan
Air Deflector
PrecoatedAluminum
Fins
InnerGrooveTubes
ww
w.m
iraco
.com
.eg
28
MINI VRF
MINI VRF DC INVERTER High Efficiency
High Efficiency DC Inverter Twin Rotary Compressor Technology
Powerful magnets provide high torque and efficiency and achieve 70% reduction in volume.
Compressor ( Twin Rotary )
structure
Highly Efficient DC Motor: - Creative motor core design. - High density neodymium magnet. - Concentrated type stator. - Wider operating frequency range.
Better balance and Extremely Low Vibration: - Twin eccentric cams. - 2 balance weights.
Highly Stable Moving Parts: - Optimal material matching rollers and vanes - Optimize compressor drive technology. - Highly robust bearings. - Compact structure.
New DC motor-centralized winding
Rotor speed(s-1)20 40 60 80 100
Compressor efficiency
Centralizing winding
Distributing winding
Effic
ienc
y-Ro
tor S
peed
Cur
ve
Common DC motor-distributing winding
Rev. (0) - 2016
29
High Efficiency DC Fan Motor Technology
Fan motor(s) are DC motor type 8 kW and 10 kW outdoor units are equipped with one DC fan motor 12, 14, 15.5, 17.5, 20, 22.4 26, 40, 45 kW outdoor units
are equipped with two DC fan motors According to the running load and pressure, fan speed control
adjusts the speed of DC fan motor to achieve the minimum power consumption. High efficiency DC fan motor saves power up to 50%.
DC fan motor
System pressure
200
400
600
800
1000
Mot
or sp
eed
( RPM
)
DC inverter stepless
adjustmentAC invertermultistep
adjustment
High Efficiency Outdoor Coil Technology
PowerSavingUp To50%
High efficiency inner-threaded pipe, enhance heat transfer.
Carrier design Common design
Hydrophilic film fins + inner-threaded pipes
ww
w.m
iraco
.com
.eg
30
MINI VRF
MINI VRF DC INVERTER Super Quiet
Super Quiet MINI VRF DC Inverter Outdoor Unit
Super QuietFan Housing
& Outlet Grille
Super QuietOutdoor Fan (s)
Super QuietDC Fan Motor
Super QuietDC Inverter Twin
Rotary Compressor
Newly DesignedFan Guard
NewDesigned Fan
Air Deflector
Rev. (0) - 2016
31
Rubber isolators for compressor to absorb vibrations at starting and running.
Optimum design of compressor suction and discharge tubing to absorb vibrations and discharge gas pulsations.
Super Quiet DC Inverter Twin Rotary Compressor Technology
Super Quiet DC Fan Motor Technology
DC fan motor
Compressor ( Twin Rotary )
structure
Newly DesignedFan Guard
New designedfan guard
Newdesigned fan
Air deflector
Super Quiet Fan Housing and Outlet Grille Optimum design of fan housing and outlet grille for minimum airflow
resistance, minimum sound level and minimum vibrations. Efficient Air Management System (AMS) with uniform air circulation over
the complete coil surface at low velocity for minimum sound level.
Super Quiet Outdoor Fan (s)Optimum design of 3-dimensional turbo fanwith patent aerodynamic new profile designof fan blades with sharp edge and little curvebigger diameter for minimum airflowresistance, minimum sound and minimum vibrations.
Totally enclosed motor running with low speeds and minimum vibrations.
ww
w.m
iraco
.com
.eg
32
MINI VRF
MINI VRF DC INVERTER Enhanced Comfort
Smart Soft Start Technology
Soft start function Mini VRF DC inverter compressor reduces strike to the electric network. This kind of high-performance and low sound scroll compressor operates at a faster rate when starting, reducing start-up time. It helps the unit to bring the room temperature up to the set level quickly.
1 2 3 4 5 6 ( Sec )
Starting current( % )
100
200
300
400
500
600Direct startY - ∆ StartStart by Inverter
Comparison of start by inverter and bytraditional methods
Smart Comfort Technology
Quick Warm-up & Cool-down Design and Less Temperature Fluctuation By utilizing the benefits of DC inverter compressor, the system can reach full load quickly and shorten the warm-up and cool-down times to provide an immediate and comfortable air solution.Less temperature fluctuation will create a better living environment.
23 °C
24 °C
25 °C
S-InverterSteady Temperature Fluctuation
Non InverterHigh Temperature Fluctuation
Uncomfortable(Energy Loss)
Uncomfortable(Energy Loss)
Comfortable
Rev. (0) - 2016
33
Smart defrosting program has the following functions :(1) Controls the defrosting time according the system real temperature.(2) Reduces the heating loss by unnecessary defrosting and the indoor unit more comfortable.(3) Shortens the defrosting time to 4 minutes due to the specialized defrosting valve.
Smart Night Super Silent Operation Technology
Smart Night Super Silent Mode is easily set at site on the main board of the outdoor unit. Smart Night Super Silent Mode has the following functions :
(1) Controls peak daytime operation ( X hours ) and non peak night time operation ( Y hours ) as per any one of the following modes : Mode 1 X : 6 hours, Y : 10 hours Mode 2 X : 8 hours, Y : 10 hours Mode 3 X : 6 hours, Y : 12 hours Mode 4 X : 8 hours, Y : 8 hours Smart Night Super Silent Mode is activated X hours after peak day time operation and it goes back to normal operation after Y hours of non peak night operation. (2) Reduces sound level to minimum of 45 dB(A)
Smart Defrosting TechnologyMode 1→ X : 6 hours, Y : 10 hours Mode 2→ X : 8 hours, Y : 10 hoursMode 3→ X : 6 hours, Y : 12 hoursMode 4→ X : 8 hours, Y : 8 hours
Notes: - This function can be activated by setting at site.- Temperature (load) curve shown in the graph is just an example.
Sound
08:00
100
50
14:00 22:00 08:00
Peak value of ambient temp.
Soun
d dB
Load
%C
apac
ity %
8hrs 10hrs
Night silent ModeMax.-10dB(10Hp)
8hrs 10hrs
Night silent ModeMax.-10dB(10Hp)
EndStart EndStart
t min. ∆t
Usual Defrosting
Smart Defrosting
Time
Heat
ing
Capa
city
ww
w.m
iraco
.com
.eg
34
MINI VRF
MINI VRF DC INVERTER High Reliability
Smooth Control During Start-UpBy using inverter-driven compressors, Carrier is able to significantly reduce the electrical and mechanical stresses that are placed on fixed-speed compressors during start-up. Current absorption on an inverter-driven compressor is smoothed out at start-up thus reducing the wear on the electrical and mechanical components and increasing reliability.
Fixed-speed unit: sudden start-up
Inverter: gradual start-up
Start > Drive
CompressorDrive
CompressorCurrent
Fixed-speed unit: 5-7 times drive current
No more thaninverter drive current
Start > Drive
Start > Drive
Fixed-speed unit: c. 3 times normal drive
Inverter: almost sameas during normal drive
Piping Stress
Compressor oil surface
Compressor
Inverter
Fixed-speed unit
After Start-up
Little lowering of oil surface
Temporary fallin oil surface dueto sudden outflowof refrigerant and oil
Before Start-up
Indoor Unit Quantity Monitoring
The quantity of indoor units should be exactly set on the outdoor main board, once some indoor units miscommunication with outdoor units during system running, the outdoor units will stop and display the fault code “H7”. This can prevent compressor from liquid hammer caused by dropped indoor units with EXV unclosed.
Quantity setting switch
ENC3 S12
ON
Rev. (0) - 2016
35
High Durability
High Durability
Anti-rust, weather proof and long life outdoor unit sheet metal parts made of chemically treated and zinc coated ( galvanized ) sheet metal.
Powder painted casing of outdoor unit with prefect adhesion of highly resistant ployester paint 60-80 microns thick, which is electro-statically applied and baked at a temperature of 220°C.
Standard coated aluminum fins of outdoor coil for coastal applications to protect against corrosion.
Compact Design for Effective Use of SpaceEasy installation: No special area is required for outdoor units.Easy transportaion: All outdoor units can be transported by elevator, which greatly simplifies installation and reduces time and labor.Mini VRF indoor and outdoor units are almost as easy to install as residential air conditioning systems, making them ideal for small offices and shops.
Easy Installation, Service and Maintenance
ww
w.m
iraco
.com
.eg
36
MINI VRF
MINI VRF DC INVERTER
Simple Signal Line Connection
Easy Installation, Service and Maintenance
Central control can be connected from indoor side or outdoor side ( X, Y, E terminal ) as you wish ( Reversible communication ).
Only one group of communication wires ( P, Q, E ) can connect outdoor unit, indoor units and network
X Y EP Q E X Y E
Wireless controller can query and modify each indoor unit’s address.
P Q EP Q E P Q E P Q E
Rev. (0) - 2016
37
Auto Addressing of Indoor Units
Through Outdoor UnitOutdoor unit can automatically distribute the addresses to indoor units.
Through Wireless Remote Control Auto addressing of indoor units is done just by pressing button
of wireless remote control. Wireless remote control and wired control can enquire and modify every
indoor unit address.
ww
w.m
iraco
.com
.eg
38
MINI VRF
MINI VRF DC INVERTER Easy Installation, Service and Maintenance
For installation in different types of rooms in small offices and shops,Mini VRF system offers a wide range of indoor and outdoor units. These are almost as easy to install as residential air conditioning systems, making them the ideal choice.
Flexible Four Outlet Locations for Piping & Wiring More convenience in installation
Back Side
Right Side
Front side
Bottom Side
Big pipe
Rev. (0) - 2016
39
Auto-Restart Function
Forced Cooling
Even if an extended power failure occurs, the Mini VRF system automatically restarts with the same settings.
A power failure will not cause any settings to be lost, thus eliminating the need for re-programming.
Forced cooling button makes outdoor unit run in cooling mode at any condition, so it is very easy for installer to charge refrigerant to the system when it need to be done.
The self-diagnosis function detects malfunctions in major locations in the system and displays the type of malfunction and location. This allows service and maintenance to be performed more efficiently.
ww
w.m
iraco
.com
.eg
40
MINI VRF
MINI VRF DC INVERTER Variety of Accessories
Easy Installation Using Branch Joints for refrigerant piping between outdoor and indoor units
Easy Installation Using Branch Box for refrigerant piping between outdoor and indoor units
Branch Joint
Branch Box
Rev. (0) - 2016
41
More convenient piping connector
Easier and safer installation thanks to a branch box that simplifies piping work and the adoption of screw connection.
Both left and right pipe flare connecting from outdoor unit to branch box is reserved, simplified the field installation.
Two sets of pipe size converter are packed with branch box to transfer the pipe size from Φ6.35 to Φ9.53 and from Φ12.7 to 15.9.
Low Sound The branch pipe is linear expansion design which regulates flow of refrigerant and reduces the noise. By locating the branch box in the ceiling or outside ,noise generated by the branch can be kept clear of living spaces, thus maintaining the noise to a minimum.
Brazing-Free Quick Installation All the piping leading to and from the branch box is connected using screw joints, which are easy to use and enable piping installation to be completed quickly.
Indoor Units Installation The branch box can be installed in the ceiling rather than outside. Furthermore , servicing can be complete easily through access to inner components such as the circuit board by simply removing the side and bottom covers.
Universal Indoor Units The same indoor units as R410A DC inverter MINI VRF system.
Branch Joint Branch Box
January 2016
Carrier is committed For continuous improvement of energy saving green products according to national and international standards to ensure the highest quality and reliability standards, and to meet market regulations and requirements.
All specifications subject to change without prior notice according to Carrier policy of continuous development.