r"1 v ' e . r"1 Triconex Product Alert Notice #24-Potential Safety Issue Invensys has reviewed the issue described in this Product Alert Notice and determined that, if no action is taken to resolve the issues described in this notice, there is a potential risk of harm to people, property, and/or the environment. Customers should immediately review and analyze the impact of this issue to their application . If this issue is found to be applicable, remedial actions should be taken to ensure the continued safe operation of their system. Subject: Connecting to a Controller or Emulator in TriStation 1131 v4.6.x May Corrupt an Application Affected Products TriStation™ 1131 Developer's Workbench Software version 4.6.x Problem Description Connecting TriStation 1131 v4.6.x to a controller or the Emulator may corrupt the project's Current Version value, resulting in a project that cannot be safely upgraded to TriStation 1131 v4.7.x or later . Background Connecting TriStation 1131 v4.6.x to a controller or the Emulator may corrupt the project's Current Version value. A project with a corrupted Current Version value cannot be safely upgraded to subsequent releases of the TriStation 1131 software. Performing a Download Changes operation after upgrading the project from TriStation 1131 v4.6.x to v4 .7.x or later may result in unpredictable control program behavior. Operational Restrictions and Recommended Actions The issue described in the Problem Description section only applies to TriStation 1131 v4.6.x . Other versions of the TriStation 1131 software do not exhibit this problem. To ensure that your project's Current Version value is correct, follow the procedure appropriate to your situation: Note: All Download Changes and Download All operations described in this section are to the controller. If your project was last opened in TriStation 1131 v4.6.x, you need to upgrade the project to TriStation 1131 4.7.x or later: Invensys Global Customer Support (GCS) Center http://support.ips .invensys.com Product Alert Notice 24 March 24, 2011 +1 - 866-746-6477 (toil-free, US & Canada) +1-508-549-2424 (worldwide) Part No . 9791010-024, Rev . 0

r1 S·.~ TriconexConnecting TriStation 1131 v4.6.x to a controller or the Emulator may corrupt the project's Current Version value, resulting in a project that cannot be safely upgraded

  • Upload
    others

  • View
    9

  • Download
    0

Embed Size (px)

Citation preview

Page 1: r1 S·.~ TriconexConnecting TriStation 1131 v4.6.x to a controller or the Emulator may corrupt the project's Current Version value, resulting in a project that cannot be safely upgraded

r"1 v ' e . r"1 S·.~ s ·

Triconex

Product Alert Notice #24-Potential Safety Issue

Invensys has reviewed the issue described in this Product Alert Notice and determined that, if no action is taken to resolve the issues described in this notice, there is a potential risk of harm to people, property, and/or the environment. Customers should immediately review and analyze the impact of this issue to their application . If this issue is found to be applicable, remedial actions should be taken to ensure the continued safe operation of their system.

Subject: Connecting to a Controller or Emulator in TriStation 1131 v4.6.x May Corrupt an Application

Affected Products

TriStation™ 1131 Developer's Workbench Software version 4.6.x

Problem Description

Connecting TriStation 1131 v4.6.x to a controller or the Emulator may corrupt the project's Current Version value, resulting in a project that cannot be safely upgraded to TriStation 1131 v4.7.x or later.

Background

Connecting TriStation 1131 v4.6.x to a controller or the Emulator may corrupt the project's Current Version value. A project with a corrupted Current Version value cannot be safely upgraded to subsequent releases of the TriStation 1131 software. Performing a Download Changes operation after upgrading the project from TriStation 1131 v4.6.x to v4 .7.x or later may result in unpredictable control program behavior.

Operational Restrictions and Recommended Actions

The issue described in the Problem Description section only applies to TriStation 1131 v4.6.x . Other versions of the TriStation 1131 software do not exhibit this problem.

To ensure that your project's Current Version value is correct, follow the procedure appropriate to your situation:

Note: All Download Changes and Download All operations described in this section are to the controller.

• If your project was last opened in TriStation 1131 v4.6.x, you need to upgrade the project to TriStation 1131 4.7.x or later:

Invensys Global Customer Support (GCS) Center http ://support.ips.invensys.com

Product Alert Notice 24 March 24, 2011

+1 -866-746-6477 (toil-free, US & Canada) +1-508-549-2424 (worldwide)

Part No . 9791010-024, Rev . 0

Page 2: r1 S·.~ TriconexConnecting TriStation 1131 v4.6.x to a controller or the Emulator may corrupt the project's Current Version value, resulting in a project that cannot be safely upgraded

2 of 4

1. In TriStation 1131 v4.6.x, open the affected project and save any necessary changes.

2. Perform a successful Download Changes operation.

3. Disconnect the project from the controller.

4 . Do not perform any other actions and close TriStation 1131 v4.6.x immediately.

5. Open and upgrade your project in TriStation 1131 v4.7.x or later.

Your project is now safely upgraded and fully-functional in TriStation 1131 v4.7.x and later. If the project was compromised before the upgrade, the issue is now corrected and the project is no longer compromised.

This procedure will not have any adverse effects if performed on a project that is not com prom ised.

Note: See the TriStation 1131 Developer's Guide for detailed instructions on how to upgrade projects.

• If you have already upgraded the project to TriStation 1131 v4.7.x or later and have already performed a Download Changes operation:

1. Check to see if your project is compromised by performing one of the following procedures:

o Select the Controller Panel. If the Programs and Tagnames lists are empty and the tagnames, variables, and other attributes are crossed out in red, then your project is compromised.

This screen shows a project that is compromised:

OC""""","W<mpooo • CJ TIUCON COIlI,oIc<

III!I C""-*'" t.I' Coni'. pbllel ~ Conlr. AIotm T4!<I P ......

~ fnU!lclt Ponel ~ £lnJot« AIotm Test Ponel

Programs and Tagnames

lists missing

Symbols missing

C~Mmit).. ·

own

o From the Project menu, select View Download History. In the Download History dialog box, if you see two entries with the same project name and version then your project is compromised.

Product Alert Notice 24 March 24, 2011 Part No. 9791010-024, Rev . 0

Page 3: r1 S·.~ TriconexConnecting TriStation 1131 v4.6.x to a controller or the Emulator may corrupt the project's Current Version value, resulting in a project that cannot be safely upgraded

This screen shows a project that is compromised:

2. If your project is compromised, do not perform a Download Changes operation.

3. Perform a Download All operation.

4. Verify that your program is no longer compromised by reviewing the Controller Panel or the Download History dialog box.

3 of 4

• If you have already upgraded your project to TriStation 1131 v4.7.x or later but have not yet performed a Download Changes operation, determine if your project's Current Version value is correct by following these steps:

1. Expand the Application tree, open the User Documents node, right-click on Programs, and then create a new program.

2. Add a local variable to the program.

3. Save the program.

4. From the Project menu, select Project Description and look at the Current Version and Downloaded Version values.

o If the current minor version value is the downloaded minor version value plus one, your project is safe and unaffected.

Delete the program created in Step 1. You do not need to continue with this procedure.

This screen shows the Project Description for an unaffected project:

Project Description · EXCOUNTR ~

Project

Filename: C:\Oocurnents and Settings\Al1 Useo-slApprlCalion Data\ T ricooe

. QesCliption: ~111Mi_i5ii~mj,6mi!iU!ll\l!ll_.-------- 1

CUllentVer.ion: 331.1 OownloadedVe .. ion: 331.0

Controller -

Tricon

I 1/4/2011 2:56:28 PM I 6121/200210:05:42 AM

._- .. -.- ---'

OK Cancel I Help I

o If the current minor version value is not the downloaded minor version value plus one, your project is not safe and a Download Changes operation should not be initiated.

Product Alert Notice 24 March 24, 2011 Part No. 9791010-024, Rev. 0

Page 4: r1 S·.~ TriconexConnecting TriStation 1131 v4.6.x to a controller or the Emulator may corrupt the project's Current Version value, resulting in a project that cannot be safely upgraded

4 of 4

Delete the program created in Step 1, and continue to step 5 below.

This screen shows the Project Description for a compromised project:

Project Description · [XCOUNTR ('g) Project -_.- - -. _ . --. _ .

r Filename: C: \Doeument. and Settings\dpau\My Doeument.\Triconex\Tri

Qeseription: 1'.Mmlli!llhllMlii

Current Version: 405.0 Downloaded Veraion: 405.0

Controller -­

Trieon

1/4/20113:24:06PM 1/4/2011 3;24;~ PM

OK I Cancel I ~

5. If your project is affected, do one of the following to recover your project:

o Perform a Download All operation.

o Restore the project from a backup project file according to the following procedure.

i. Open the most recent backup project file in TriStation 1131 v4.6 .x. Be sure that all settings within the project are current and correct for the application.

ii. Perform a successful Download Changes operation in TriStation 1131 v4.6.x.

iii. Disconnect the project from the controller.

iv. Do not perform any other actions and close TriStation 1131 v4.6 .x immediately.

v. Open and upgrade your project in TriStation 1131 v4.7.x or later.

vi . Verify that the upgraded project is no longer compromised by checking that the Current Version value displayed in the Project Description dialog box is correct.

If you have any questions regarding this Product Alert Notice, please contact the Global Customer Support Center, or your local Invensys office.

© 2011 Invensys Systems, Inc. All rights reserved . Invensys, Invensys logo, Triconex, and TriStation are trademarks of Invensys pic, its subsidiaries and affiliates. All other brands may be trademarks of their respective owners .

Product Alert Notice 24 March 24, 2011 Part No. 9791010-024, Rev. 0