Accessing the web page of a KE2 Evaporator Efficiency controller reveals a great deal of information about the system performance, setpoints and allows for quick adjustments. While this information is also available using the user interface of the controller, when networked, the controller’s information can be accessed, reviewed, and changed from anywhere there is network access.
KE2 MasterViewOverview
KE2 EvaporatorEfficiency
TM
thermsolutions
ENTER
BACK
22
MODIFY STATUS
KE2 Therm Evaporator Efficiency
IP Address: 10.10.50.51 Location: Walk-in FreezerMac Address: 00.04.A3.12.07.87
ABC Contracting(888)555-3358
All Clear
TM
thermsolutions
ALARM
Home SetpointsNetworkSettings Graphs Login
CompressorRelay On
System ModeCool
Evaporator FanRelay On
Room Temp-5.2 F
Coil Temp-11.6 F
Sat Temp-19.0 F
Superheat4.4 F
Valve Position26.7%
Suct Pressure17.9 psig
Suct Temp-14.6 F
System System On
DefrostRelay Off
Monitor71.1 F
Door SwClosed
Door SwClosed
Q.1.19 September 2012
© Copyright 2012 KE2 Therm Solutions, Inc., Washington, Missouri 63090
MODIFY STATUS
KE2 Therm Evaporator Efficiency
IP Address: 10.10.50.51 Location: Walk-in FreezerMac Address: 00.04.A3.12.07.87
ABC Contracting(888)555-3358
All Clear
TM
thermsolutions
ALARM
Home SetpointsNetworkSettings Graphs Login
CompressorRelay On
System ModeCool
Evaporator FanRelay On
Room Temp-5.2 F
Coil Temp-11.6 F
Sat Temp-19.0 F
Superheat4.4 F
Valve Position26.7%
Suct Pressure17.9 psig
Suct Temp-14.6 F
System System On
DefrostRelay Off
Monitor71.1 F
Door SwClosed
Door SwClosed
See page 3 See page 5 & 6
See page 4 See page 7
Required to make changes to the Settings, Network Setup, and Setpoints pages
First line is functionSecond line is the current system performance
For each parameter:
Home PageWhat the screen shows: Displays real time system information, and shows the interaction of multiple system conditions This screen looks at the system conditions, and can help with diagnostics, system performance, or just offer peace of mind
that the system is running properly.
Q.1.19 September 2012, Page 2
Q.1.19 September 2012, Page 3Settings
What the screen shows: The Settings page contains controller configuration for email and web access. It also allows installers to customize the MasterView with their company information. The Settings page includes the buttons
to update the controller, reset power to the controller, send a test e-mail, clear data collected, and clear alarms. If the optional Data key was purchased, it is activated on this screen.
MODIFY STATUS
Settings(Set Location)MAC:00:04:A3:13:A2:3F
Network Logout
Business Name Phone Number Location
ActivateSettingsHome Login
Email Server Log Key ActivationCurrent Key: RFCC-88DE-XNAHTime Remaining: 999 Days 999 Hours
Firmware
User Name
Controller
PasswordDHCP Options Test Email
Email Address for AlertsWeb Server Port
Email SubjectEmail Options
Reset
Bootloader
Clear Logs
Clear Alarms
v02.028
Submit
Note: Advanced - requires IT Support
Basic (Port 25) Advanced (Port 465)
KE2 Therm Solutions (888) 337 3358 (Set Location)
OffDHCP ClientDHCP Server
For help in setting up an email account see bulletin Q.5.3 Establishing Gmail
For Bootloader information refer to Q.5.6 KE2 Bootloader Guide
Clicking Activate starts the data logging key
Customer may input their company information
User defines controller location for future access and alarm notifications
Required to gain control of Settings page
Prevents unauthor-ized access
Returns user to Home Page
Remotely cycles power to the controller
Use to verify proper email configuration
Removes all data stored by the controller
Resets controller’s alarms and alarm conditions
Customer may input their company information
© Copyright 2012 KE2 Therm Solutions, Inc., Washington, Missouri 63090
Q.1.19 September 2012, Page 4Network Setup
What the screen shows: Enables the user to Bond the KE2 Evap for multiple evaporator applications, and provides setup for adding controllers to an existing network.
MODIFY STATUS
Network Setup
Board Name 3 MAC ADDRESS IP ADDRESS Board Name 7 MAC ADDRESS IP ADDRESS
Board Name 2 MAC ADDRESS IP ADDRESS Board Name 6 MAC ADDRESS IP ADDRESS
Board Name 1 MAC ADDRESS IP ADDRESS Board Name 5 MAC ADDRESS IP ADDRESS
Board Name 4 MAC ADDRESS IP ADDRESS Board Name 8 MAC ADDRESS IP ADDRESS
00:04:A3:14:E0:F5
00:00:00:00:00:00
00:00:00:00:00:00
00:00:00:00:00:00
00:00:00:00:00:00
00:00:00:00:00:00
00:00:00:00:00:00
00:00:00:00:00:00
10.10.50.130
0.0.0.0
0.0.0.0
0.0.0.0
0.0.0.0
0.0.0.0
0.0.0.0
0.0.0.0
Prevents unauthorized access to the controller. User must enter password to make changes to the Network Setup page.
Discover finds all of the KE2 Evap controllers located on the network. The information from the connected controllers populates the appropriate spaces on the page.
Once discovered, Bond creates a link between controllers that coordinates the refrigeration and defrost cycles. When bonding, user should review Multi-evap Setpoints.
Evaporator
Bond
Business Name Phone Number Location
Discover
Home
LoginClear Page
Current Values
NetworkSettings
Step 1: Step 2:
Multi-Controller Environment
Subnet Mask Primary DNSGateway Secondary DNS
255.255.0.0 10.10.255.254 10.10.255.254 8.8.8.8
Q.1.19 September 2012, Page 5
MODIFY STATUS
Setpoints Page1Location:(Set Location)
Home RestoreNetworkSettings Page 2Login
ROOM TEMP DEFROST TYPE VALVE TYPE
Page 1
Refrigerant Defrost per Day Defr Pmp Dwn TimeDefrost Mode Superheat
Air Temp Diff First Defrost Delay HI Temp Alrm OffsetDefrost Term Temp Max Operating Press
Refrig Fan Mode Defrost Fan State Lo Temp Alrm OffsetDefrost Parameter Max Valve Steps
Max Comp Runtime Elec Defrost Mode HI Temp Alrm DelayDrain Time Motor Step Rate
Min Comp Runtime Max Fan Delay Time Lo Temp Alrm DelayFan Delay Temp Motor Type
R-404A
1.0 F 10.0 F50.0 F
On w/Compressor Off 4.0 F
5 min Pulse 60 min2 min
2 min 2 min 10 min20.0 F
On w/CompressorPermanentCycle
DemandScheduleRuntime
OffOn
Pulse Permanent
BipolarUnipolar
MechanicalKE2SER/SEI 1- 20SER B - LSEI30SEI50SEHETS 12 - 50ETS 100ETS 250/400KVCarelCustom
ElectricAirHot Gas - Comp OnHot Gas - Comp Off
R-404AR-507R-407AR-407CR-422AR-422DR-134aR-22R-717R-438AR-408AR-409AR-407FR-410AR-744
0 minDemand
-10 F Electric Mechanical
Values shown in illustration are default values.
Three setpoints needed for the controller to begin controlling
Setpoints - Page 1What the screen shows: Allows the user to setup the controller, and to customize the controller to meet specific application needs. The three primary setpoints – Room Temp, Defrost Type and Valve Type are in the gold boxes at the top. Only these three are
necessary for the controller to begin normal operation.
© Copyright 2012 KE2 Therm Solutions, Inc., Washington, Missouri 63090
Q.1.19 September 2012, Page 6
MODIFY STATUS
Setpoints Page 2Location:(Set Location)
Home RestoreNetworkSettings Login
ROOM TEMP DEFROST TYPE Refrigerate
Page 1 Page 2
Next Mode
Dig In1 Mode Aux Temp Mode Temp UnitsDigital In1 State Multi Evap Cool
Dig In2 Mode Aux Relay Mode Door Alarm DelayDigital In2 State Multi Evap Defrost
Dig In3 Mode 2nd Room Temp Multi Air Temp CtrlDigital In3 State Multi Evap Sensor
Air Temp Offset Suct Press Offset Suct Temp OffsetCoil Temp Offset Aux Temp Offset
Proportional Derivative Comp Run TimeIntegral
Door Disabled
Disabled 30 minClosed Synchronized
Disabled -50.0 F Warmest AirClosed Shared
0.0 F 0.0 0.0 F0.0 F 0.0 F
Disabled2nd Room TempDoor SwitchExt AlarmDefrost Interlock*Defrost Lockout*System OffLight Switch**Camera Switch**
* (DI2 only)**(DI3 only)
OpenClosed
Alarm Relay2nd Comp Relay2nd Fan Relay2nd Defr Relay2 Speed Fan CtlLights RelayCamera Relay
SynchronizedIndependent
DisabledMonitor2nd Room Temp2nd Coil Temp
FahrenheitClosed
Electric
Values shown in illustration are default values.FahrenheitCelsius
Warmest AirAverage Air
SynchronizedIndependent
SharedNot Shared
Synchronized
This feature allows you to manually change the controller’s operating state, i.e. put the controller into manual defrost
Setpoints - Page 2What the screen shows: See and adjust the group of setpoints that control the various Digital Inputs. There are three primary inputs as well as a fourth Auxiliary input. Additionally this screen is where you set the controllers that
are bonded
Weekly SnapshotWhat the screen shows: The System Snapshot shows the past five days of Room Temp and Coil Temp readings, as well as the number and
duration of defrost cycles. It is an essential tool for system analysis and troubleshooting. The experts at KE2 Technical Support can help troubleshoot your system using this information.
MODIFY STATUS
Weekly SnapshotLocation:(Set Location)
Number of Defrost Cycles: 3 Note: Each grid mark represents
approximately 2 hours
Home Refresh
100F
-50F
50F
25F
0F
-25F
75F
100F
-50F
50F
25F
0F
-25F
75F
T-1day
T=0 T-5days
T-4days
T-2days
T-3days
RoomTemp
CoilTemp
Electric
Defrost cycle Defrost cycle Defrost cycle
Q.1.19 September 2012, Page 7