Pumped Refrigerant Economization and Title 24

[email protected]

1

Page 2: Pumped Refrigerant Economization and Title 24 - CFRT · Pumped Refrigerant Economization and Title 24 fred.rebarber@emerson.com 1 . Agenda Fundamentals and the Operation of the Pumped

Agenda Fundamentals and the Operation of the Pumped

Refrigerant Economizer System

Design Considerations and Optimization

Data From the Field

The Title 24 Approval Process, Method and Documentation

2

Page 3: Pumped Refrigerant Economization and Title 24 - CFRT · Pumped Refrigerant Economization and Title 24 fred.rebarber@emerson.com 1 . Agenda Fundamentals and the Operation of the Pumped

3

Liebert DSE Indoor Unit

Next generation data

center cooling system

Liebert EconoPhase

First ever pumped

refrigerant economizer Liebert MC

Intelligent, high

efficiency condensers

iCOM Thermal System

Manager

System Overview

Page 4: Pumped Refrigerant Economization and Title 24 - CFRT · Pumped Refrigerant Economization and Title 24 fred.rebarber@emerson.com 1 . Agenda Fundamentals and the Operation of the Pumped

Fix

ed

Dig

ital

Fix

ed

Dig

ital

Digital scroll compressors match cooling to IT load

Staged evaporator coil reduces compressor power and optimizes economizer performance

Electronic expansion valve for part-load and low ambient efficiency

EC plug fans match airflow to server needs

Reduced compressor power

through iCOM optimization

4

System Components

Page 5: Pumped Refrigerant Economization and Title 24 - CFRT · Pumped Refrigerant Economization and Title 24 fred.rebarber@emerson.com 1 . Agenda Fundamentals and the Operation of the Pumped

5

Variable

speed fans Fin/Tube Liebert MC +/-

Efficiency (COP)

31 47 + 52%

Sound Power (dBA)

77.3 73 - 4.3 dBA

Refrigerant Charge (lb)

22 6 - 73%

Footprint (ft2)

39.8 33.6 - 15%

Weight (lb)

670 400 - 40%

Liebert iCOM Control CAN bus communication with

indoor unit to maximize efficiency

High-Efficiency Air-Cooled Condensers

Page 6: Pumped Refrigerant Economization and Title 24 - CFRT · Pumped Refrigerant Economization and Title 24 fred.rebarber@emerson.com 1 . Agenda Fundamentals and the Operation of the Pumped

6

Liebert DSE Indoor Unit

Liebert MC Condensers

Liebert EconoPhase Module

EconoPhase module is installed in series with the compressor circuit, with no need for additional coils or heat exchangers.

EconoPhase Pumped Refrigerant Economizer

Page 7: Pumped Refrigerant Economization and Title 24 - CFRT · Pumped Refrigerant Economization and Title 24 fred.rebarber@emerson.com 1 . Agenda Fundamentals and the Operation of the Pumped

7

DX Operation Mode

Cooling

Mode

Outdoor

Temp

Cooling

PUE

Full

Compressor 95 1.28

Compressor Evaporator

Electronic

expansion valve

Refrigerant

Pump Condenser

Evaporator: 3.2 kW

Condenser: 3.9 kW

Pump 1: 0 kW Pump 2: 0 kW

Compressor 2: 8.5 kW Compressor 1: 8.5 kW

Page 8: Pumped Refrigerant Economization and Title 24 - CFRT · Pumped Refrigerant Economization and Title 24 fred.rebarber@emerson.com 1 . Agenda Fundamentals and the Operation of the Pumped

Compressor 2: 8.5 kW 8

Full and Partial Economization

Cooling

Mode

Outdoor

Temp

Cooling

PUE

Full

Compressor 95 1.28

Partial

EconoPhase 65 1.17

Compressor Evaporator

Electronic

expansion valve

Refrigerant

Pump Condenser

Evaporator: 3.2 kW

Condenser: 3.9 kW

Compressor 1: 0 kW

Pump 2: 0 kW Pump 1: 0.6 kW

Page 9: Pumped Refrigerant Economization and Title 24 - CFRT · Pumped Refrigerant Economization and Title 24 fred.rebarber@emerson.com 1 . Agenda Fundamentals and the Operation of the Pumped

9

Full and Partial Economization

Cooling

Mode

Outdoor

Temp

Cooling

PUE

Full

Compressor 95 1.28

Partial

EconoPhase 65 1.17

Full

EconoPhase 45 1.09

Compressor Evaporator

Electronic

expansion valve

Refrigerant

Pump Condenser

Evaporator: 3.2 kW

Condenser: 3.9 kW

PUE as low as 1.05 Full Economizer Mode

Compressor 2: 0 kW Compressor 1: 0 kW

Pump 1: 0.6 kW Pump 2: 0.6 kW

Page 10: Pumped Refrigerant Economization and Title 24 - CFRT · Pumped Refrigerant Economization and Title 24 fred.rebarber@emerson.com 1 . Agenda Fundamentals and the Operation of the Pumped

10

Annual free-cooling hours increase at higher return air conditions and lower unit loads:

At 70% load and 85°F, full

economization is

available at 50°F outdoor

EconoPhase 100% Free-Cooling Capability

Percentage of Annual Hours with 100% Free-Cooling Available

Location 85°F Return Air 95°F Return Air

San Francisco, CA 42% 70%

Chicago, IL 55% 62%

Charlotte, NC 36% 45%

Page 11: Pumped Refrigerant Economization and Title 24 - CFRT · Pumped Refrigerant Economization and Title 24 fred.rebarber@emerson.com 1 . Agenda Fundamentals and the Operation of the Pumped

Economization Hours in San Francisco DSE 125 at 90ºF RAT, 70% Unit Load

11

Page 12: Pumped Refrigerant Economization and Title 24 - CFRT · Pumped Refrigerant Economization and Title 24 fred.rebarber@emerson.com 1 . Agenda Fundamentals and the Operation of the Pumped

Liebert DSE Indoor Unit

Liebert MC Condenser

Liebert EconoPhase

12

Liebert

iCOM

Liebert DSE with iCOM Benefits:

– Maximizes free-cooling hours

through automatic

economizer transition control

– Minimizes power

consumption by optimizing

component operation for

lowest total system power

– Provides built-in diagnostics

to ensure proper system

operation

– Provides interface to Liebert

data center management

systems

End-to-End Thermal Management Solution

Pump

Speed

Refrigerant

Temperature

Pump

Head

EconoPhase

Unit Status

Condenser

Fan Speed

Ambient

Temperature Head

Pressure

Liebert MC

Unit Status

Unit

Capacity

Room

Temperature

Evaporator

Fan Speed

Room

Humidity

Page 13: Pumped Refrigerant Economization and Title 24 - CFRT · Pumped Refrigerant Economization and Title 24 fred.rebarber@emerson.com 1 . Agenda Fundamentals and the Operation of the Pumped

13

Integrated economizer control with automatic diagnostics

– iCOM monitoring of pump operation

– Automatic changeover on loss of free cooling

– Pump unit serviceable without loss of mechanical cooling

EconoPhase Automatic Diagnostics

Page 14: Pumped Refrigerant Economization and Title 24 - CFRT · Pumped Refrigerant Economization and Title 24 fred.rebarber@emerson.com 1 . Agenda Fundamentals and the Operation of the Pumped

MC Condenser and PRE Skid

14

Page 15: Pumped Refrigerant Economization and Title 24 - CFRT · Pumped Refrigerant Economization and Title 24 fred.rebarber@emerson.com 1 . Agenda Fundamentals and the Operation of the Pumped

Liebert DSE Models Technical Data

Model

DA080 (1) DA085 (1) DA125 DA150 DA165

95°F DB, 52.3 DP

Total Capacity kW (net) 88 100 146 170 181

Sensible Capacity kW (net) 84 94 146 170 181

Full-load SCOP @ 95°F ambient 3.2 3.1 3.8 3.2 3.1

SCOP @ 35°F ambient (kW/kW)* 10.5 10.1 17.5 13.0 12.8

85°F DB, 52.3 DP

Total Capacity kW (net) 85 92 130 153 163

Sensible Capacity kW (net) 77 83 130 153 163

Full-load SCOP @ 95°F ambient 3.0 2.7 3.4 2.9 2.8

SCOP @ 35°F ambient (kW/kW)* 9.1 8.7 12.2 12.0 11.7

*Economizer mode operating at 100% DX capacity

Note: Capacity data is rated and factory-certified per ASHRAE 127-2012 with a 5% tolerance

(1) Available in UPFLOW units as well as downflow

Basic Dimensions - Downflow Units

Model Length (A) Width (B) Height (C)

DA080 100" 35" 76"

DA085 100" 35" 76"

DA125 144" 47" 76"

DA150 144" 47" 76"

DA165 144" 47" 76"

*Add minimum 18" height for separate filter plenum, plus floorstand height

Page 16: Pumped Refrigerant Economization and Title 24 - CFRT · Pumped Refrigerant Economization and Title 24 fred.rebarber@emerson.com 1 . Agenda Fundamentals and the Operation of the Pumped

FIELD SUPPLIED DATA

Page 17: Pumped Refrigerant Economization and Title 24 - CFRT · Pumped Refrigerant Economization and Title 24 fred.rebarber@emerson.com 1 . Agenda Fundamentals and the Operation of the Pumped

Real World Data Compared to Predicted

Page 18: Pumped Refrigerant Economization and Title 24 - CFRT · Pumped Refrigerant Economization and Title 24 fred.rebarber@emerson.com 1 . Agenda Fundamentals and the Operation of the Pumped

18

Partial Economization Begins at 70°F

Page 19: Pumped Refrigerant Economization and Title 24 - CFRT · Pumped Refrigerant Economization and Title 24 fred.rebarber@emerson.com 1 . Agenda Fundamentals and the Operation of the Pumped

0

100

200

300

400

500

600

700

800

Sep Oct Nov Dec Jan Feb Mar Apr May Jun Jul Aug Sep Oct

DSE Economizer Monthly Run Hours 2012-2013

Unit #1 Econ Hrs

Unit #2 Econ Hrs

2012 Temperatures

5,354Hrs

Liebert DSE Beta Test Upstate NY

2013 Temperatures

4,018Hrs

Page 20: Pumped Refrigerant Economization and Title 24 - CFRT · Pumped Refrigerant Economization and Title 24 fred.rebarber@emerson.com 1 . Agenda Fundamentals and the Operation of the Pumped

Liebert DSE Cooled Data Center Performance

1.00

1.05

1.10

1.15

1.20

1.25

1.30

1.35

1.40

0

50

100

150

200

250

300

350

400

29-Aug-12 18-Oct-12 7-Dec-12 26-Jan-13 17-Mar-13 6-May-13 25-Jun-13 14-Aug-13 3-Oct-13 22-Nov-13 11-Jan-14

C

oo

lin

g P

UE

K

W

Power History

Data Center Total Avg. KW

UPS Total Avg. KW

Actual Avg. Cooling KW

Avg O/A Temp

Cooling PUE

Page 21: Pumped Refrigerant Economization and Title 24 - CFRT · Pumped Refrigerant Economization and Title 24 fred.rebarber@emerson.com 1 . Agenda Fundamentals and the Operation of the Pumped

21

Driver – Improved PUE

Initial Interest - ASHRAE Allowable Conditions (20% RH to 62.6° F. Dew Point)

Reality - Most Customers prefer ASHRAE Recommended Conditions (41.9° F. Dew Point to 60% RH)

DSE is an indirect system and not sensitive to tight inside humidity tolerances.

Page 22: Pumped Refrigerant Economization and Title 24 - CFRT · Pumped Refrigerant Economization and Title 24 fred.rebarber@emerson.com 1 . Agenda Fundamentals and the Operation of the Pumped

THE ROAD TO TITLE 24 APPROVAL

22

Page 23: Pumped Refrigerant Economization and Title 24 - CFRT · Pumped Refrigerant Economization and Title 24 fred.rebarber@emerson.com 1 . Agenda Fundamentals and the Operation of the Pumped

Executive Summary CEC Submission Report

At the time the Energy Code was written, the refrigerant economization method was just being released into the market place to meet high efficiency needs

Since 2012, over 1500 of the Liebert DSE systems have been installed throughout North America, South America, Europe and Australia

52 systems are installed in California data centers.

23

Page 24: Pumped Refrigerant Economization and Title 24 - CFRT · Pumped Refrigerant Economization and Title 24 fred.rebarber@emerson.com 1 . Agenda Fundamentals and the Operation of the Pumped

CEC Economization Requirements

The Energy Code requires all Data Centers to meet the efficiency requirement of either one of two prescriptive economization methods (outside air economization or water economization). This now includes pumped refrigerant economization.

Or demonstrate through the Exceptional Design Compliance method the proposed solution meets or exceeds the energy efficiency of the prescriptive methods.

24

Page 25: Pumped Refrigerant Economization and Title 24 - CFRT · Pumped Refrigerant Economization and Title 24 fred.rebarber@emerson.com 1 . Agenda Fundamentals and the Operation of the Pumped

Title 24 – Section 140.9 (a)– Prescriptive Requirements for Computer Rooms

Economizers

– (A) air-side with full capacity at 55F DB outdoor temp

– (B) water-side with full capacity at 40F DB outdoor temp

– Exceptions

• Room under 5 tons

• 50 tons of new equipment in an existing room in existing bldg

• 20 tons of new equipment in a new room in existing bldg

25

Page 26: Pumped Refrigerant Economization and Title 24 - CFRT · Pumped Refrigerant Economization and Title 24 fred.rebarber@emerson.com 1 . Agenda Fundamentals and the Operation of the Pumped

Title 24 Time Dependant Valuation

26

“…TDV is quite simple. It holds the total cost of energy constant at forecasted retail price levels but gives more weight to on‐peak hours and less weight to off‐peak hours. This means that energy efficiency measures that perform better on‐peak will be valued more highly than measures that do not.”

Source:

http://www.energy.ca.gov/title24/2013standards/prerulemaking/document

s/general_cec_documents/Title24_2013_TDV_Methodology_Report_23F

eb2011.pdf

Page 27: Pumped Refrigerant Economization and Title 24 - CFRT · Pumped Refrigerant Economization and Title 24 fred.rebarber@emerson.com 1 . Agenda Fundamentals and the Operation of the Pumped

The Path To Approval

Baseline energy budget created using the Energy Commission’s public domain software CBECC-Com (Build 717).

The proposed Liebert DSE model was created using the CBECC-Com software, by extracting the IDF model (IDF is a format used by EnergyPlus) and then adding custom curves for the Liebert DSE equipment.

The custom curves were developed from a regression analysis of Liebert pumped refrigerant system data, following the AHRI 1360 standard used for determining the efficiency rating.

We then simulated the proposed model. Once both models were created and simulated, the results were extracted to the Exceptional Design Compliance - End-Use Summary Comparison spreadsheet.

27

Page 29: Pumped Refrigerant Economization and Title 24 - CFRT · Pumped Refrigerant Economization and Title 24 fred.rebarber@emerson.com 1 . Agenda Fundamentals and the Operation of the Pumped

Pumped Refrigerant Approved in 14 of 16 Climate Zones

29

Page 30: Pumped Refrigerant Economization and Title 24 - CFRT · Pumped Refrigerant Economization and Title 24 fred.rebarber@emerson.com 1 . Agenda Fundamentals and the Operation of the Pumped

Energy and Water Savings

A cooling system with a water economizer uses an average of 4.2 million gallons of water per year for a data center with an IT load of 1.2 MW.

The Liebert DSE pump refrigerant economization system utilizes less energy based on the TDV calculation methods for 14 of these 16 climate zones

30

Page 31: Pumped Refrigerant Economization and Title 24 - CFRT · Pumped Refrigerant Economization and Title 24 fred.rebarber@emerson.com 1 . Agenda Fundamentals and the Operation of the Pumped

Water Reduction in All Climate Zones

31

Page 32: Pumped Refrigerant Economization and Title 24 - CFRT · Pumped Refrigerant Economization and Title 24 fred.rebarber@emerson.com 1 . Agenda Fundamentals and the Operation of the Pumped

Project Approval Process

The CEC approved the inclusion of the Liebert EconoPhase pumped refrigerant economizer as a prescriptive option on September 9, 2015, as shown in the CEC’s Blueprint newsletter, Issue 111.

“The approval to use pumped refrigerant economizers is an alternative to the use of water-side economizers per Section 140.9(a)1B, and is specific to pumped refrigerant economizers installed in climate zones 1-9, 11-14, and 16.”

The Liebert EconoPhase economizer system is not yet accounted for in the CEC’s performance software, so engineers and others wanting to use the Liebert DSE with Econophase pumped refrigerant economizer in California should follow this guideline:

– If the project is complying using the performance approach, then the cooling system serving the computer room should be specified as a basic, efficient chilled water plant, with an integrated water economizer. The compliance documents can be used to show local government jurisdictions that the efficiency of the Liebert DSE is equivalent or better than the chilled water system and acceptable as a prescriptive alternative.

32

Source: http://www.energy.ca.gov/2015publications/CEC-400-

2015-031/CEC-400-2015-031.pdf

Page 34: Pumped Refrigerant Economization and Title 24 - CFRT · Pumped Refrigerant Economization and Title 24 fred.rebarber@emerson.com 1 . Agenda Fundamentals and the Operation of the Pumped

34