NYC Department of Education
Building Condition Assessment Survey 2018-2019
R050Architectural Inspection
Inspection Type Last EditedTime InInspectionId
P.S. 50 - STATEN ISLAND, 200 ADELAIDE AVENUE, STATEN ISLAND, NY, 10306School:
3211 2019-03-21 09:09AM 2019-03-25 03:05PMARCHITECTURAL - SENIOR
3212 2019-03-21 10:50AM 2019-03-26 09:09PMARCHITECTURAL - ASSOCIATE
Asset DataQuestion Answer
Was the Building Fully Accessible for Inspection? Yes
Principal(s) Information
Principal Name Joseph Santello
Principal Organization P.S. 50 - Staten Island
Meeting with Principal? No
Principal Feedback The Principal questionnaire was returned with no comments on
the physical building condition at this time.
Custodian Dennis Maestrallis
Fireman Lou Desiano
Building Square Footage 83,000
Comments on the Area (Square Feet) N/A
Comments on the Stories (Floors) plus Basements 2+B
Comments on the Year Built 1957
Comments on the Student Population 774
Comments on the Staff Population 104
Comments on the Number of Classrooms 37
Weather Heavy Rain
Facade Photo
Adelaide Avenue - Southwest view
Main Entrance Photo
Facade A - Adelaide Avenue
Page 1 of 29 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
R050Architectural InspectionRoof Photo
Roof 1 - East View
Have any Systems/Major Building Components been upgraded? Systems: Windows/Guards, Exterior Door replacement (full),
Parapet, Exterior Walls repairs, repointing (partial )
Years: 2007
Systems: Cafeteria Flooring replacement
Years: 2010
Systems: Areaway Grating replacement
Years: 2013
Systems: Chimney repairs
Years: 2014
Systems: Roofing, Bulkhead (Stair B) repairs, Library upgrade
Years: 2016
1968 (13000 SF)Have there been any New Building Additions?
Tandem No Tandem
Leased Space? No
Priority ConditionExist
Last Year?
Priority
Category
Condition
Description
Component
Affected
Location
Description
Person(s)
Notified
Person(s)
Title
Photo
Image
No condition recorded
Structural Engineer Required
Structural
Condition Type
Condition
Description
Component
Affected
Location
Description
Person(s)
Notified
Person(s)
Title
Photo
Image
No condition recorded
Accessibility
Accessibility Status Question Response
Physical Breakdown Structure Exists Complies Required Deficiency
FUNCTIONAL ACCESSIBILITY
Exterior Routes
NoExterior Entrances & Exits
SADDLE HEIGHT > 1/2"
NoNoExterior H/C Lifts
NoNoExterior Ramps and Railings
Interior Routes
NoNoCorridor and Lobby H/C Lifts
NoYesInterior Corridor Doors And Hardware
YesInterior Corridors & Lobbies
NoInterior Elevators
YesInterior Lobby Doors And Hardware
Page 2 of 29 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
R050Architectural Inspection
Physical Breakdown Structure Exists Complies Required Deficiency
NoInterior Ramps
Rooms & Spaces
Art Rooms
Yes NoRoom 224
NOT ON ACCESSIBLE ROUTE
Auditorium
Yes Yes1st Floor
Cafeteria
Yes NoBasement
NOT ON ACCESSIBLE ROUTE
Classrooms
Yes NoNone on Accessible Route
NOT ON ACCESSIBLE ROUTE
NoComputer Rooms
Gymnasium
Yes No1st Floor
NOT ON ACCESSIBLE ROUTE
Library
Yes NoRoom 209
NOT ON ACCESSIBLE ROUTE
Main Office
Yes NoRoom 115
NOT ON ACCESSIBLE ROUTE
NoMulti-purpose Room
Nurse's Office
Yes NoRoom 113
NOT ON ACCESSIBLE ROUTE
NoPool
NoScience Lab
Toilet Rooms (boys)
Yes NoNone on Accessible Route
NOT ON ACCESSIBLE ROUTE
Toilet Rooms (girls)
Yes NoNone on Accessible Route
NOT ON ACCESSIBLE ROUTE
Toilet Rooms (staff)
Yes NoNone on Accessible Route
NOT ON ACCESSIBLE ROUTE
Page 3 of 29 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
R050Architectural Inspection
Building Template
Inspection
Question Response
Architectural
ATHLETIC FIELDS Does not exist
EXTERIOR Inspected
InspectedAREAWAY
Instance on Facade A - AW1,2 ; Facade E - AW3,4 Inspected
3- FairInstance Condition
Instance Quantity 4
Instance Quantity Uom EACH
AREAWAY SLAB:CRACKS AND SPALLINGDeficiency
Deficiency Location/Instance
30Deficiency Quantity
Quantity Uom S.F.
Potential Action REPAIR
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Facade E
Violations No violations recorded
InspectedAWNINGS AND CANOPIES
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
Page 4 of 29 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
R050Architectural Inspection
Question Response
EXTERIOR
InspectedCHIMNEY
MasonryMaterial Type(s)
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedCOPING
Condition 3- Fair
CAST STONE:DETERIORATED FLASHINGDeficiency
Deficiency Location/Instance
150Deficiency Quantity
Quantity Uom L.F.
Potential Action REPAIR
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Facade E
Violations No violations recorded
Does not existCORNICE
InspectedDOORS
InspectedDOOR HARDWARE
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedDOORS AND FRAMES
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedLINTELS
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedTRANSOM/SIDE LIGHT
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedEXTERIOR SOFFITS
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedEXTERIOR WALLS
MasonryMaterial Type(s)
30,000Replacement Quantity
Replacement Uom S.F.
Instance on All Facades Inspected
3- FairInstance Condition
Instance Quantity 30,000
Instance Quantity Uom S.F.
Page 5 of 29 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
R050Architectural Inspection
Question Response
EXTERIOR
EXTERIOR WALLS
BRICK:DETERIORATED MASONRY SILLSDeficiency
Roof Plan Reference
Elevation
Elevation Reference Facades A, D, E
30Deficiency Quantity
Quantity Uom L.F.
Potential Action REMOVE AND REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Facade E
Violations No violations recorded
BRICK:OPEN JOINTSDeficiency
Roof Plan Reference
Elevation
Elevation Reference All Facades
400Deficiency Quantity
Quantity Uom S.F.
Potential Action REPOINT
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Page 6 of 29 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
R050Architectural Inspection
Question Response
EXTERIOR
EXTERIOR WALLS
Deficiency Photo 1
Facade F
Deficiency Photo 2
Facade D
Violations No violations recorded
BRICK:WATER INFILTRATION IN INSTRUCTIONAL SPACEDeficiency
Roof Plan Reference
Elevation
Elevation Reference Facade A
30Deficiency Quantity
Quantity Uom S.F.
Potential Action REPAIR
PRIORITY 5Urgency of Action
LEVEL 4Purpose of Action
Deficiency Photo 1
Room 239
Violations 35271419L
Does not existLOADING DOCK
InspectedLOUVER
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
Page 7 of 29 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
R050Architectural Inspection
Question Response
EXTERIOR
InspectedPARAPETS
MasonryMaterial Type(s)
7,000Replacement Quantity
Replacement Uom C.F.
Instance on Allow Facades Inspected
3- FairInstance Condition
Instance Quantity 7,000
Instance Quantity Uom CF
BRICK:OPEN JOINTSDeficiency
Deficiency Location/Instance
200Deficiency Quantity
Quantity Uom S.F.
Potential Action REPOINT
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Facade A
Violations No violations recorded
Does not existPLAZA DECK
InspectedROOF
InspectedROOFING
Replacement Quantity 35,000
Replacement Uom S.F.
InspectedLEADERS, GUTTERS, DOWNSPOUTS, SCUPPERS
2- Between Good and FairCondition
No deficiencies recordedDeficiency
InspectedROOF BARRIER
2- Between Good and FairCondition
No deficiencies recordedDeficiency
Does not existROOF CAGE
Does not existROOF FENCE
Does not existROOF HATCH/SMOKE HATCH
InspectedROOFING
Instance on Built-Up:Roofs 1, 2 Inspected
3- FairInstance Condition
Instance Quantity 35,000
Instance Quantity Uom S.F.
“Does the roof have major mechanical equipment sitting on Dunnage
Steel less than 18" above the Roofing?"
No
Installation Year 1997
Source of Installation Year Custodial Staff
Page 8 of 29 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
R050Architectural Inspection
Question Response
EXTERIOR
ROOF
ROOFING
ROOFING
BUILT-UP:FLASHING:CAP FLASHING MISSINGDeficiency
Deficiency Location/Instance
100Deficiency Quantity
Quantity Uom L.F.
Potential Action INSTALL NEW
PRIORITY 4Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Facade A
Violations No violations recorded
BUILT-UP:ROOFING:LOSS OF GRAVELDeficiency
Deficiency Location/Instance
1,000Deficiency Quantity
Quantity Uom S.F.
Potential Action INSTALL NEW GRAVEL
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Roof 1
Violations No violations recorded
BUILT-UP:ROOFING:MAJOR ACTIVE ROOF LEAKS IN
INSTRUCTIONAL SPACE
Deficiency
Page 9 of 29 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
R050Architectural Inspection
Question Response
EXTERIOR
ROOF
ROOFING
ROOFING
Deficiency Location/Instance
100Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE ROOFING WITHOUT MAJOR EQUIPMENT
REMOVAL
PRIORITY 5Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Staircase A Shown, also Room 203 and Corridor near Room 240
similar .
Violations No violations recorded
BUILT-UP:ROOFING:BEYOND USEFUL LIFEDeficiency
Built-Up:Roofs 1, 2Deficiency Location/Instance
35,000Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 1Urgency of Action
LEVEL 2Purpose of Action
Violations No violations recorded
InspectedROOFING DRAINS
2- Between Good and FairCondition
No deficiencies recordedDeficiency
InspectedSPECIALTIES
InspectedBULKHEAD/PENTHOUSE
3- FairCondition
BULKHEAD/PENTHOUSE CEILING:PLASTER
DAMAGED/DETERIORATED
Deficiency
Deficiency Location/Instance
40Deficiency Quantity
Quantity Uom S.F.
Potential Action MAINTENANCE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Page 10 of 29 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
R050Architectural Inspection
Question Response
EXTERIOR
ROOF
SPECIALTIES
BULKHEAD/PENTHOUSE
Deficiency Photo 1
Bulkhead 4
Violations No violations recorded
BULKHEAD/PENTHOUSE WALLS/INTERIOR:CMU
CRACKS/SPALLING
Deficiency
Deficiency Location/Instance
30Deficiency Quantity
Quantity Uom S.F.
Potential Action MAINTENANCE
PRIORITY 2Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Bulkhead 2
Violations No violations recorded
Does not existCUPOLA/ SPIRES/ TOWERS
Does not existDORMER
Does not existDUNNAGE STEEL
Does not existROOF/GRAVITY TANK
InspectedSKYLIGHT/ROOF VENT
Material Type(s) Glass
3- FairCondition
BROKEN FRAMINGDeficiency
Deficiency Location/Instance
10Deficiency Quantity
Quantity Uom L.F.
Potential Action MAINTENANCE
Page 11 of 29 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
R050Architectural Inspection
Question Response
EXTERIOR
ROOF
SPECIALTIES
SKYLIGHT/ROOF VENT
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Skylight/Roof Vent
Violations No violations recorded
DAMAGED FLASHINGDeficiency
Deficiency Location/Instance
10Deficiency Quantity
Quantity Uom L.F.
Potential Action MAINTENANCE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Skylight/Roof Vent
Violations No violations recorded
InspectedSTAIRS/RAMPS: EXTERIOR
InspectedBUILDING CHEEK/FLANK WALLS
Condition 4- Between Fair and Poor
STONE:OPEN JOINTSDeficiency
Deficiency Location/Instance
20Deficiency Quantity
Quantity Uom S.F.
Potential Action REPOINT
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Page 12 of 29 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
R050Architectural Inspection
Question Response
EXTERIOR
STAIRS/RAMPS: EXTERIOR
BUILDING CHEEK/FLANK WALLS
Deficiency Photo 1
Facade E
Violations No violations recorded
STONE:CRACKS/SPALLING - MINORDeficiency
Deficiency Location/Instance
10Deficiency Quantity
Quantity Uom S.F.
Potential Action REPAIR
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Facade E
Violations No violations recorded
InspectedRAILINGS
Condition 4- Between Fair and Poor
RUST - MINORDeficiency
Deficiency Location/Instance
20Deficiency Quantity
Quantity Uom L.F.
Potential Action MAINTENANCE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Page 13 of 29 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
R050Architectural Inspection
Question Response
EXTERIOR
STAIRS/RAMPS: EXTERIOR
RAILINGS
Deficiency Photo 1
Facade E
Violations No violations recorded
InspectedSTAIRS/RAMPS
Condition 4- Between Fair and Poor
STONE:OPEN JOINTSDeficiency
Deficiency Location/Instance
10Deficiency Quantity
Quantity Uom L.F.
Potential Action REPOINT
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Facade E
Violations No violations recorded
STONE:DETERIORATED SUBSTRATEDeficiency
Deficiency Location/Instance
10Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE SUBSTRATE AND RESET
PRIORITY 4Urgency of Action
LEVEL 2Purpose of Action
Page 14 of 29 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
R050Architectural Inspection
Question Response
EXTERIOR
STAIRS/RAMPS: EXTERIOR
STAIRS/RAMPS
Deficiency Photo 1
Facade E
Violations No violations recorded
InspectedWINDOWS
10,000Replacement Quantity
Replacement Uom S.F.
InspectedEXTERIOR GUARDS
Condition 3- Fair
RUST - MINORDeficiency
Roof Plan Reference
Elevation
50Deficiency Quantity
Quantity Uom S.F.
Potential Action MAINTENANCE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Facade C
Violations No violations recorded
InspectedLINTELS
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedWINDOWS
Material Type(s) Aluminum
Instance on Aluminum - Other:All Facades Inspected
2- Between Good and FairInstance Condition
Instance Quantity 10,000
Page 15 of 29 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
R050Architectural Inspection
Question Response
EXTERIOR
WINDOWS
WINDOWS
Instance Quantity Uom S.F.
Installation Year 2007
Source of Installation Year Documented
No deficiencies recordedDeficiency
INTERIOR Inspected
AUDITORIUM
Instance on 1st Floor (456 Seats) Inspected
Ceiling
Instance on 1st Floor (456 Seats) Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Door(s)
Instance on 1st Floor (456 Seats) Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Fixed H/C Lift
Instance on 1st Floor (456 Seats) Does not exist
Fixed Seating
Instance on 1st Floor (456 Seats) Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Floor Finish
Instance on 1st Floor (456 Seats) Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Sliding-folding Partition
Instance on 1st Floor (456 Seats) Does not exist
Stage
Instance on 1st Floor (456 Seats) Inspected
Stage
Instance on 1st Floor (456 Seats) Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Stage Curtain Rigging
Instance on 1st Floor (456 Seats) Inspected
5- PoorInstance Condition
INOPERABLEDeficiency
Left Side of StageDeficiency Location/Instance
1Deficiency Quantity
Quantity Uom EACH
Potential Action MAINTENANCE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Violations No violations recorded
Stage Curtains
Instance on 1st Floor (456 Seats) Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Walls
Instance on 1st Floor (456 Seats) Inspected
2- Between Good and FairInstance Condition
Page 16 of 29 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
R050Architectural Inspection
Question Response
INTERIOR
AUDITORIUM
Walls
No deficiencies recordedDeficiency
Window Curtains/Shades/Blinds
Instance on 1st Floor (456 Seats) Inspected
1- GoodInstance Condition
No deficiencies recordedDeficiency
CAFETERIA
Instance on Basement Inspected
Ceiling
Instance on Basement Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Door(s)
Instance on Basement Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Fixed Equipment
Instance on Basement Does not exist
Floor Finish
Instance on Basement Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Sliding-folding Partition
Instance on Basement Does not exist
Stage
Instance on Basement Does not exist
Walls
Instance on Basement Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Window Curtains/Shades/Blinds
Instance on Basement Does not exist
InspectedCLASSROOMS/CORRIDORS/ADMIN SPACES
InspectedCeiling
Condition 2- Between Good and Fair
ACOUSTIC TILES ON PLASTER:DAMAGED/MISSING -
ACTIVE LEAK
Deficiency
Corridor near Room 240Deficiency Location/Instance
10Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 5Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Corridor near Room 240
Page 17 of 29 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
R050Architectural Inspection
Question Response
INTERIOR
CLASSROOMS/CORRIDORS/ADMIN SPACES
Ceiling
Violations No violations recorded
PLASTER:CRACKS/SPALLING - ACTIVE LEAKDeficiency
Corridor near Room 203Deficiency Location/Instance
10Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 5Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Corridor near Room 203
Violations No violations recorded
InspectedDoor(s)
Condition 3- Fair
WOOD:DETERIORATED DOORDeficiency
Rooms 101, 104Deficiency Location/Instance
2Deficiency Quantity
Quantity Uom EACH
Potential Action MAINTENANCE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Room 104
Violations No violations recorded
InspectedFloor Finish
Condition 2- Between Good and Fair
TERRAZZO:CRACKSDeficiency
Main Entrance LobbyDeficiency Location/Instance
120Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Page 18 of 29 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
R050Architectural Inspection
Question Response
INTERIOR
CLASSROOMS/CORRIDORS/ADMIN SPACES
Floor Finish
Deficiency Photo 1
Main Entrance Lobby
Violations No violations recorded
VINYL TILES:BROKEN/DETERIORATED/MISSING TILESDeficiency
Corridor near Stair A/1Deficiency Location/Instance
10Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Corridor near Stair A/1
Violations No violations recorded
Does not existSpecialties
InspectedWalls
Condition 2- Between Good and Fair
PLASTER:CRACKS/SPALLING - ACTIVE LEAKDeficiency
Rooms 239, 240Deficiency Location/Instance
20Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 5Urgency of Action
LEVEL 4Purpose of Action
Deficiency Photo 1
Room 239
Violations 35271419L
GYMNASIUM
Instance on 1st Floor Inspected
Ceiling
Instance on 1st Floor Inspected
2- Between Good and FairInstance Condition
Page 19 of 29 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
R050Architectural Inspection
Question Response
INTERIOR
GYMNASIUM
Ceiling
No deficiencies recordedDeficiency
Door(s)
Instance on 1st Floor Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Fixed Equipment
Instance on 1st Floor Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Floor Finish
Instance on 1st Floor Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Seating
Instance on 1st Floor Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Sliding-folding Partition
Instance on 1st Floor Does not exist
Stage
Instance on 1st Floor Does not exist
Walls
Instance on 1st Floor Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Window Curtains/Shades/Blinds
Instance on 1st Floor Does not exist
InspectedINTERIOR DOOR HARDWARE
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedINTERIOR GUARDS
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
KITCHEN
Instance on Basement Inspected
Ceiling
Instance on Basement Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Door(s)
Instance on Basement Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Floor Finish
Instance on Basement Inspected
3- FairInstance Condition
CERAMIC TILE:BROKEN/MISSING TILESDeficiency
Near SinksDeficiency Location/Instance
20Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
Page 20 of 29 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
R050Architectural Inspection
Question Response
INTERIOR
KITCHEN
Floor Finish
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Near Sinks
Violations No violations recorded
Walls
Instance on Basement Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
LIBRARY
Instance on Room 209 Inspected
Built-in Furnishing
Instance on Room 209 Does not exist
Ceiling
Instance on Room 209 Inspected
1- GoodInstance Condition
No deficiencies recordedDeficiency
Door(s)
Instance on Room 209 Inspected
1- GoodInstance Condition
No deficiencies recordedDeficiency
Floor Finish
Instance on Room 209 Inspected
1- GoodInstance Condition
No deficiencies recordedDeficiency
Walls
Instance on Room 209 Inspected
1- GoodInstance Condition
No deficiencies recordedDeficiency
LOCKER ROOM
Instance on 1st Floor - Boys Inspected
YesAlternative Use
Instance on 2nd Floor - Girls Inspected
YesAlternative Use
Ceiling
Instance on 1st Floor - Boys Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Instance on 2nd Floor - Girls Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Door(s)
Instance on 1st Floor - Boys Inspected
3- FairInstance Condition
Page 21 of 29 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
R050Architectural Inspection
Question Response
INTERIOR
LOCKER ROOM
Door(s)
WOOD:DETERIORATED DOORDeficiency
EntranceDeficiency Location/Instance
1Deficiency Quantity
Quantity Uom EACH
Potential Action MAINTENANCE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Entrance
Violations No violations recorded
Instance on 2nd Floor - Girls Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Floor Finish
Instance on 1st Floor - Boys Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Instance on 2nd Floor - Girls Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Locker Room Lockers
Instance on 1st Floor - Boys Does not exist
Instance on 2nd Floor - Girls Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Walls
Instance on 1st Floor - Boys Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Instance on 2nd Floor - Girls Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Does not existMULTI-PURPOSE ROOM
Does not existPOOLS
SCIENCE DEMO ROOM
Instance on Room 205 Inspected
NoAlternative Use
Fixed Equipment
Instance on Room 205 Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Does not existSCIENCE LAB
Does not existSCIENCE PREP ROOM
SHOWER ROOM
Page 22 of 29 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
R050Architectural Inspection
Question Response
INTERIOR
SHOWER ROOM
Instance on 1st Floor - Boys Inspected
YesAlternative Use
Instance on 2nd Floor - Girls Inspected
YesAlternative Use
Ceiling
Instance on 1st Floor - Boys Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Instance on 2nd Floor - Girls Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Door(s)
Instance on 1st Floor - Boys Does not exist
Instance on 2nd Floor - Girls Does not exist
Floor Finish
Instance on 1st Floor - Boys Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Instance on 2nd Floor - Girls Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Walls
Instance on 1st Floor - Boys Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Instance on 2nd Floor - Girls Inspected
2- Between Good and FairInstance Condition
GLAZED BLOCK:CRACKS/SPALLINGDeficiency
EntranceDeficiency Location/Instance
10Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Entrance
Violations No violations recorded
InspectedSTAIRS/RAMPS: INTERIOR
Do Letter Stair Signs Exist? 0
InspectedCeiling
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedDoor(s)
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
Page 23 of 29 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
R050Architectural Inspection
Question Response
INTERIOR
STAIRS/RAMPS: INTERIOR
Does not existPartition
InspectedRailings
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedStairs and Landings
Condition 2- Between Good and Fair
TERRAZZO:CRACKSDeficiency
Main Entrance VestibuleDeficiency Location/Instance
10Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Main Entrance Vestibule
Violations No violations recorded
InspectedWalls
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedSTRUCTURAL
InspectedCOLUMNS/BEAMS/BEARING WALLS
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedFLOOR STRUCTURE
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedFOUNDATION WALLS
Material Type(s) Concrete
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedROOF STRUCTURE
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedVAULTS-BUNKERS
InspectedFoundation Walls
2- Between Good and FairCondition
No deficiencies recordedDeficiency
InspectedSlab Structure
2- Between Good and FairCondition
No deficiencies recordedDeficiency
Does not existVault/Ash Hoist Doors and Framing
InspectedTOILET ROOMS - STAFF
InspectedCeiling
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
Page 24 of 29 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
R050Architectural Inspection
Question Response
INTERIOR
TOILET ROOMS - STAFF
InspectedDoor(s)
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedFloor Finish
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedStalls
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedWalls
Condition 2- Between Good and Fair
CERAMIC TILE:BROKEN/ MISSINGDeficiency
1st Floor MenDeficiency Location/Instance
10Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
1st Floor Men
Violations No violations recorded
InspectedTOILET ROOMS - STUDENTS
InspectedCeiling
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedDoor(s)
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedFloor Finish
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedStalls
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedWalls
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
LIFE SAFETY Inspected
Does not existF.D. HOLDING AREA
Does not existSTEEL STAIRS
SITE Inspected
Does not existCONTAINERIZATION
InspectedDRAINAGE SYSTEM FOR ASPHALT
InspectedCatch Basins/Manhole - Surrounded by Asphalt
Condition 2- Between Good and Fair
Page 25 of 29 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
R050Architectural Inspection
Question Response
SITE
DRAINAGE SYSTEM FOR ASPHALT
Catch Basins/Manhole - Surrounded by Asphalt
No deficiencies recordedDeficiency
Does not existCulverts - Asphalt Covering
InspectedDRAINAGE SYSTEM FOR CONCRETE
InspectedCatch Basins/Manhole - Surrounded by Concrete
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
Does not existCulverts - Concrete Covering
Does not existDRAINAGE SYSTEM FOR SOIL
Does not existDRINKING FOUNTAINS
InspectedFENCES
Condition 3- Fair
WROUGHT IRON:DAMAGED/DETERIORATEDDeficiency
Along Adelaide AvenueDeficiency Location/Instance
80Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Along Adelaide Avenue
Violations No violations recorded
Does not existIRRIGATION SYSTEM
InspectedPAVING
InspectedDOT Sidewalk
Does not existAsphalt
InspectedConcrete
4- Between Fair and PoorCondition
DAMAGED/DETERIORATED/MISSING SECTIONSDeficiency
Along Adelaide Avenue, Platt StreetDeficiency Location/Instance
800Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 4Urgency of Action
LEVEL 4Purpose of Action
Deficiency Photo 1
Along Adelaide Avenue
Violations 6830
HEAVINGDeficiency
Page 26 of 29 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
R050Architectural Inspection
Question Response
SITE
PAVING
DOT Sidewalk
Concrete
Along Adelaide Avenue, Platt StreetDeficiency Location/Instance
250Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 4Urgency of Action
LEVEL 4Purpose of Action
Deficiency Photo 1
Along Adelaide Avenue
Violations 6830
Does not existPavers
InspectedSite Sidewalks & Walkways
InspectedAsphalt
3- FairCondition
CRACKS - MAJORDeficiency
South of SchoolDeficiency Location/Instance
550Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
South of School
Violations No violations recorded
InspectedConcrete
3- FairCondition
DAMAGED/DETERIORATED/MISSING SECTIONSDeficiency
Along Adelaide Avenue, Platt StreetDeficiency Location/Instance
100Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Page 27 of 29 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
R050Architectural Inspection
Question Response
SITE
PAVING
Site Sidewalks & Walkways
Concrete
Deficiency Photo 1
Along Adelaide Avenue
Violations No violations recorded
Does not existPavers
InspectedStudent Non-Use
Gravel Exists? No
InspectedAsphalt
2- Between Good and FairCondition
No deficiencies recordedDeficiency
InspectedConcrete
2- Between Good and FairCondition
No deficiencies recordedDeficiency
Does not existPavers
InspectedStudent Use
Gravel Exists? No
InspectedAsphalt
2- Between Good and FairCondition
No deficiencies recordedDeficiency
Does not existConcrete
Does not existPavers
InspectedPLAYGROUNDS
South of SchoolInstance
Benches
Instance on South of School Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Fence
Instance on South of School Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Pavement
Instance on South of School Does not exist
Play Equipment
Instance on South of School Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Safety Surfacing
Instance on South of School Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Unpaved Area
Instance on South of School Does not exist
Does not existPLAYING SURFACE
Page 28 of 29 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
R050Architectural Inspection
Question Response
SITE
InspectedRETAINING WALLS
Condition 3- Fair
Are there any Retaining Walls 6' OR higher facing public street/sidewalk? No
CAST IN PLACE CONCRETE:CRACKS/SPALLING - MAJORDeficiency
South Side of SchoolDeficiency Location/Instance
40Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
South Side of School
Violations No violations recorded
InspectedSEATING
InspectedBenches
Does not existConcrete
InspectedMetal/Wood/Plastic
2- Between Good and FairCondition
No deficiencies recordedDeficiency
Does not existBleachers
Does not existSITE WALLS (NOT RETAINING WALLS)
InspectedSTAIRS/RAMPS: EXTERIOR
InspectedRailings
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedSite Cheek/flank Walls
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedStairs/ramps
Condition 2- Between Good and Fair
CAST IN PLACE CONCRETE:CRACKS/SPALLING - MAJORDeficiency
South Side of SchoolDeficiency Location/Instance
20Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
South Side of School
Violations No violations recorded
Page 29 of 29 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)