16
Use of the AHRI Certified TM Mark indicates a manufacturer’s participation in the program. For verification of certification for individual products, go to www.ahridirectory.org . 426 41 1701 01 08/16/11 PAJ3 Product Specifications 13 SEER, R410A PACKAGE AIR CONDITIONER FOR MANUFACTURED HOUSING, RESIDENTIAL, AND LIGHT COMMERCIAL APPLICATIONS 2 5 TONS Single Phase, 208/230 V, 60 Hz BUILT TO LAST, EASY TO INSTALL AND SERVICE Compact, fully selfcontained, electric cooling unit with horizontal supply and return ducts Light weight, compact construction ideal for manufactured housing and residential applications Environmentally sound R410A refrigerant Vibration isolation provides quiet operation. Compressors have internal over current protection Liquid refrigerant filter driers Hand holds built into the unit base pan Designed to be serviced from both the side and front Accessory electric heaters with single point connections Durable prepainted steel cabinet Norust base pan with integrated drain pan standard on all units Directdrive ECM multispeed, blower motor standard on all models Louvered coil enclosure for protection against vandalism and hail damage Aerodynamic fan blade design reduces the overall sound All models available with optional factory installed tincoated copper evaporator coil. (These models are identified with letters TP in the 11th and 12th positions in the model numbers) LIMITED WARRANTY* 5year parts limited warranty (including compressor and coils) With timely registration, an additional 5 year parts limited warranty (including compressor and coils) *Applies to original purchaser/homeowner, some limitations may apply. See warranty certificate for details. UNIT PERFORMANCE DATA Model Number COOLING Unit Dimensions H x W x D in [mm ] Operating Weight lbs [kg] Capacity BTU/h SEER EER PAJ324000K000A PAJ324000KTP0A 22,800 13.5 11.5 30 [765] x 51 [1295] x 32 [813] 237 [108] PAJ330000K000A PAJ330000KTP0A 28,400 13.2 11.5 30 [765] x 51 [1295] x 32 [813] 249 [113] PAJ336000K000A PAJ336000KTP0A 34,800 13.5 11.5 30 [765] x 51 [1295] x 32 [813] 279 [127] PAJ342000K000A PAJ342000KTP0A 40,500 13.5 11.5 34 [867] x 51 [1295] x 32 [813] 303 [138] PAJ348000K000A PAJ348000KTP0A 46,500 13.2 11.0 34 [867] x 51 [1295] x 32 [813] 305 [139] PAJ360000K000A PAJ360000KTP0A 55,000 13.2 11.0 42 [1070] x 51 [1295] x 32 [813] 352 [160]

Product Specificationsicpindexing.toddsit.com/documents/086477/42641170101.pdfB. SELECT UNIT BASED ON REQUIRED COOLING CAPACITY. Enter Cooling Capacities table at condenser entering

  • Upload
    others

  • View
    5

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Product Specificationsicpindexing.toddsit.com/documents/086477/42641170101.pdfB. SELECT UNIT BASED ON REQUIRED COOLING CAPACITY. Enter Cooling Capacities table at condenser entering

Use of the AHRI Certified TM Mark indicatesa manufacturer’s participation in the program.For verification of certification for individualproducts, go to www.ahridirectory.org .

426 41 1701 01 08/16/11

PAJ3Product Specifications

13 SEER, R−410APACKAGE AIR CONDITIONER FOR MANUFACTURED HOUSING, RESIDENTIAL, AND LIGHT COMMERCIAL APPLICATIONS2 − 5 TONSSingle Phase, 208/230 V, 60 HzBUILT TO LAST, EASY TO INSTALL AND SERVICE• Compact, fully self−contained, electric cooling unit with horizontal supply and return ducts

• Light weight, compact construction ideal for manufactured housing and residential applications

• Environmentally sound R−410A refrigerant

• Vibration isolation provides quiet operation. Compressors have internal over current protection

• Liquid refrigerant filter driers

• Hand holds built into the unit base pan

• Designed to be serviced from both the side and front

• Accessory electric heaters with single point connections

• Durable pre−painted steel cabinet

• No−rust base pan with integrated drain pan standard on all units

• Direct−drive ECM multispeed, blower motor standard on all models

• Louvered coil enclosure for protection against vandalism and hail damage

• Aerodynamic fan blade design reduces the overall sound

• All models available with optional factory installed tin−coated copper evaporator coil. (These models are identified with letters TP in the 11th and 12th positions in the model numbers)

LIMITED WARRANTY*• 5−year parts limited warranty (including compressor and coils)−With timely registration, an additional 5 year parts limited warranty (including compressor and coils)*Applies to original purchaser/homeowner, some limitations may apply. See warranty certificate for details.

UNIT PERFORMANCE DATA

Model Number

COOLING Unit Dimensions H x W x D in [mm ]

OperatingWeight lbs [kg]Capacity BTU/h SEER EER

PAJ324000K000APAJ324000KTP0A 22,800 13.5 11.5 30 [765] x 51 [1295] x 32 [813] 237 [108]

PAJ330000K000APAJ330000KTP0A 28,400 13.2 11.5 30 [765] x 51 [1295] x 32 [813] 249 [113]

PAJ336000K000APAJ336000KTP0A 34,800 13.5 11.5 30 [765] x 51 [1295] x 32 [813] 279 [127]

PAJ342000K000APAJ342000KTP0A 40,500 13.5 11.5 34 [867] x 51 [1295] x 32 [813] 303 [138]

PAJ348000K000APAJ348000KTP0A 46,500 13.2 11.0 34 [867] x 51 [1295] x 32 [813] 305 [139]

PAJ360000K000APAJ360000KTP0A 55,000 13.2 11.0 42 [1070] x 51 [1295] x 32 [813] 352 [160]

Page 2: Product Specificationsicpindexing.toddsit.com/documents/086477/42641170101.pdfB. SELECT UNIT BASED ON REQUIRED COOLING CAPACITY. Enter Cooling Capacities table at condenser entering

2 Specifications subject to change without notice. 426 41 1701 01

MODEL NOMENCLATURE

MODEL SERIES1 2, 3 4 5,6 7,8,9 10 11,12 13 14 15

P AJ 3 36 000 K 00 0 A 1P = Package

AJ = Air Conditioner

3 = 13 SEER24 = 2 Tons30 = 2.5 Tons36 = 3 Tons

42 = 3.5 Tons

48 = 4 Tons60 = 5 Tons NOMINAL COOLING CAPACITY

000 = no factory heat NOMINAL HEATING BTUH (input)

K = 208/230−1−60 VOLTAGE00 = No optionsTP − Tin Plated Evaporator Main Tubes FACTORY INSTALLED OPTIONS

0 = Standard FEATURE CODESales Model Digit

Engineering Digit

Page 3: Product Specificationsicpindexing.toddsit.com/documents/086477/42641170101.pdfB. SELECT UNIT BASED ON REQUIRED COOLING CAPACITY. Enter Cooling Capacities table at condenser entering

3Specifications subject to change without notice.426 41 1701 01

AHRI CAPACITY RATINGS − COOLING CAPACITIES AND EFFICIENCIES

PAJ3 NOMINAL TONS STANDARD CFMNET COOLING CAPACITY

AT 95�F (35�c) (Btuh) EER† SEER**24 2 800 22800 11.5 13.530 2.5 1000 28400 11.5 13.236 3 1200 34800 11.5 13.542 3.5 1400 40500 11.5 13.548 4 1600 46500 11 13.260 5 1750 55000 11 13.2

LEGENDdB−Sound Levels (decibels)db—Dry BulbSEER—Seasonal Energy Efficiency Ratiowb—Wet BulbCOP−Coefficient of Performance* Air Conditioning Heating & Refrigeration Institute† At ”A” conditions−80�F (26.7�C) indoor db/67�F (19.4�C) indoor wb & 95�F (35�C) outdoor db.** Rated in accordance with U.S. Government DOE Department of Energy) test procedures and/or AHRI Standards210/240−08.

Notes:1. Ratings are net values, reflecting the effects of circulating fan heat.Ratings are based on:Cooling Standard: 80�F (26.7�C) db, 67�Fwb (19.4�C) indoor entering−airtemperature and 95�F db (35�C) outdoor entering−air temperature.2. Before purchasing this appliance, read important energy cost andefficiencyinformation available from your retailer.

A−Weighted Sound Power Level (dBA)

PAJ3STANDARD RATING

(dBA)TYPICAL OCTAVE BAND SPECTRUM (dBA without tone adjustment)

125 250 500 1000 2000 4000 800024 72 58 66.5 63.5 64.5 60.5 57.5 51.530 76 62.5 68 64.5 68 67.5 58.5 5336 77 67.5 70 70 70.5 66 60.5 5542 76 65 69 68.5 70 67.5 63 58.548 77 68.5 68 71 70.5 65.5 61.5 5560 80 66.5 70 75.5 75.5 71.5 66.5 58

PHYSICAL DATA − PAJ3UNIT SIZE 24 30 36 42 48 60NOMINAL CAPACITY (ton) 2 2.5 3 3.5 4 5SHIPPING WEIGHT (lb) (kg)

286130

298136

329150

352160

354161

402183

COMPRESSOR TYPE RECIPROCATING SCROLLREFRIGERANT R-410AREFRIGERANT QUANTITY (lb) QUANTITY (kg)

3.31.5

4.01.8

5.32.4

5.92.7

5.02.3

6.22.8

METERING DEVICE ID Piston TXVORIFICE OD (in.) (mm)

0.0591.50

0.0591.50

0.0671.70

0.0731.85

0.0822.08 N/A

OUTDOOR COILROWS...FINS/in.FACE AREA (sq. ft)

1...209.1

1...209.1

2...209.1

2...2010.2

2...2010.2

2...2013.0

OUTDOOR FANNOMINAL AIRFLOW (CFM)DIAMETER (in.)DIAMETER (mm)MOTOR HP (RPM)

240020508

1/8 (800)

240020508

1/8 (800)

270020508

1/4 (1050)

270020508

1/4 (1050)

270020508

1/4 (1050)

300020508

1/3 (1100)INDOOR COILROWS...FINS/in.FACE AREA (sq. ft)

2...124.3

3...124.3

3...124.3

3...124.9

3...124.9

3...126.1

INDOOR BLOWERNOMINAL COOLING AIRFLOW(CFM)NOMINAL SIZE L x D (in.) (mm)MOTOR (HP)

800

10 x 8254 x 203

1/3

100010 x 8

254 x 2031/3

120011 x 9

279 x 2291/2

140011 x 9

279 x 2291/2

160011 x 9

279 x 2293/4

1750

11 x 10279 x 254

1HIGH-PRESSURE SWITCH (psig)CUTOUTRESET (AUTO)

650 +/- 15420 +/- 25

RETURN-AIR FILTERSTHROWAWAY (in.) (mm)

20x20x1

508x508x25

20x24x1

508x610x25

24x30x1

610x762x25

24x36x1

610x914x25*Required filter sizes shown are based on the AHRI (Air Conditioning, Heating and Refrigeration Institute) rated airflow at a velocity of 300 ft/min forthrowaway type or 450 ft/min for high capacity type. Recommended filters are 1−in. (25.4 mm) thick.

Page 4: Product Specificationsicpindexing.toddsit.com/documents/086477/42641170101.pdfB. SELECT UNIT BASED ON REQUIRED COOLING CAPACITY. Enter Cooling Capacities table at condenser entering

4 Specifications subject to change without notice. 426 41 1701 01

PAJ3 ACCESSORIESAccessory Model Number Description Use With

CPLOWAMB001A00 Motormaster� II Low Ambient Control ALLCPHSTART002A00 Compressor Start Kit ALLCPCRKHTR007A00

240V Crankcase Heater24 − 42

NPCRKHTR004A00 48 − 60ELECTRIC HEATERS

Accessory Model Number Nominal Capacity Stages Circuit Breaker Use WithCPHEATER125A00 3.8 / 5.0 1 NO ALLCPHEATER126A00 3.8 / 5.0 1 YES ALLCPHEATER127A00 5.6 / 7.5 2 NO ALLCPHEATER128A00 5.6 / 7.5 2 YES ALLCPHEATER129A00 7.5 / 10.0 2 NO 24 − 48CPHEATER130A00 7.5 / 10.0 2 YES ALLCPHEATER131A00 11.3 / 15.0 2 YES 36 − 60CPHEATER132A00 15.0 / 20.0 2 YES 48 − 60

Note: If installing an accessory heater, the thermostat must have capability to energize ”G” (fan) on a call for ”W” (strip heat).

Multiplication FactorsHEATER kW RATING VOLTAGE DISTRIBUTION MULTIPLICATION FACTOR

240

200 .69208 .75230 .92240 1.00

Example: 15.0 kW (at 240v) heater on 208v = 15.0 (.75 mult factor) = 11.25 capacity at 208v

Page 5: Product Specificationsicpindexing.toddsit.com/documents/086477/42641170101.pdfB. SELECT UNIT BASED ON REQUIRED COOLING CAPACITY. Enter Cooling Capacities table at condenser entering

5Specifications subject to change without notice.426 41 1701 01

UNIT DIMENSIONS − PAJ324−36

PA

J324

PA

J330

PA

J336

Page 6: Product Specificationsicpindexing.toddsit.com/documents/086477/42641170101.pdfB. SELECT UNIT BASED ON REQUIRED COOLING CAPACITY. Enter Cooling Capacities table at condenser entering

6 Specifications subject to change without notice. 426 41 1701 01

UNIT DIMENSIONS − PAJ342−60

PA

J342

PA

J348

PA

J360

Page 7: Product Specificationsicpindexing.toddsit.com/documents/086477/42641170101.pdfB. SELECT UNIT BASED ON REQUIRED COOLING CAPACITY. Enter Cooling Capacities table at condenser entering

7Specifications subject to change without notice.426 41 1701 01

SELECTION PROCEDUREA. DETERMINE COOLING AND HEATING REQUIREMENTS

AT DESIGN CONDITIONS.Given:Required Cooling Capacity (TC) 34,000 Btuh. . . . . . .Sensible Heat Capacity (SHC) 25,000 Btuh. . . . . . . . .Required Heating Capacity 15,000 Btuh. . . . . . . . . . . .Outdoor Entering−Air Temperature 95° F (35° C). . . .Indoor Entering−Air Temperature 80° F edb (26.7° C);

67° F (19.4° C) ewbIndoor−Air Quantity 1200 CFM. . . . . . . . . . . . . . . . . . . .External Static Pressure 0.20 IN. W.C.. . . . . . . . . . . .Electrical Characteristics (V−Ph−Hz) 230−1−60. . . . . .

B. SELECT UNIT BASED ON REQUIRED COOLINGCAPACITY.

Enter Cooling Capacities table at condenser enteringtemperature of 95° F (35° C), indoor air entering at 1200 CFMand 67° F (19.4° C) ewb. The PAJ336 unit provides a totalcooling capacity of 34,500 Btuh and a sensible heat capacity of26,040 Btuh.For indoor−air temperature other than 80° F (26.7° C) edb,calculate sensible heat capacity correction, as required, usingthe formula found following the Cooling Capacities tables.NOTE: Unit ratings are net capacities.

C. SELECT ELECTRIC HEAT.The required heating capacity is 15,000 Btuh (given).Determine the electric heat capacity in kW.

15,000 Btuh

3414 Btuh/kW= 3.8 kW of heat required

Enter the Accessory Electric Heater table on page 4 for 208/230,single−phase, PAJ336 unit. The 5−kW heater at 240v mostclosely satisfies the heating required. To calculate kW at 230 V,multiply the heater kW by multiplication factor 0.92 found in theMultiplication Factors table on page 4.5 kW x 0.92 = 4.6 kW4.6 kW x 3414 Btuh/kW = 15,704 Btuh

D. DETERMINE FAN SPEED AND POWER REQUIREMENTSAT DESIGN CONDITIONS.

Before entering the air delivery tables, calculate the total staticpressure required. From the given, Filter Pressure Drop table,and the Accessory Electric Heat Pressure Drop table find:External static pressure 0.20 IN. W.C.Filter 0.10 IN. W.C.Electric Heat 0.04 IN. W.C.Total static pressure 0.34 IN. W.C.

Enter the table for Dry Coil Air Delivery — Horizontal Discharge.At 0.4 IN. W.C. external static pressure and medium speed, themotor delivers 1236 CFM.

Page 8: Product Specificationsicpindexing.toddsit.com/documents/086477/42641170101.pdfB. SELECT UNIT BASED ON REQUIRED COOLING CAPACITY. Enter Cooling Capacities table at condenser entering

8 426 41 1701 01

PE

RF

OR

MA

NC

E D

ATA

Co

olin

g C

apac

itie

s

PA

J324

EVA

PO

RA

TOR

AIR

CO

ND

EN

SE

R E

NT

ER

ING

AIR

TE

MP

ER

AT

UR

ES

F

(C

)75

(24

)85

(29

)95

(35

)10

5 (4

1)11

5 (4

6)12

5 (5

2)

CF

M /

BF

EW

B F(

C)

Cap

acit

y M

Btu

hTo

tal

Sys

KW

Cap

acit

y M

Btu

hTo

tal

Sys

KW

Cap

acit

y M

Btu

hTo

tal

Sys

KW

Cap

acit

y M

Btu

hTo

tal

Sys

KW

Cap

acit

y M

Btu

hTo

tal

Sys

KW

Cap

acit

y M

Btu

hTo

tal

Sys

KW

Tota

lS

ens

Tota

lS

ens

Tota

lS

ens

Tota

lS

ens

Tota

lS

ens

Tota

lS

ens

700

/0.

08

57 (

14)

21.7

521

.75

1.68

20.4

620

.46

1.79

19.1

119

.11

1.88

17.5

117

.51

1.97

15.7

015

.70

2.05

13.8

513

.85

2.13

62 (

17)

22.9

320

.43

1.69

21.2

319

.61

1.80

19.5

218

.78

1.89

17.5

417

.54

1.97

15.7

315

.73

2.05

13.8

713

.87

2.13

63*

(17)

23.4

816

.83

1.69

21.7

616

.02

1.80

19.9

815

.21

1.90

17.7

914

.23

1.97

15.2

213

.13

2.03

12.6

612

.02

2.09

67 (

19)

25.8

217

.68

1.72

24.0

316

.90

1.84

22.2

016

.11

1.95

20.1

915

.27

2.04

17.4

714

.17

2.10

14.8

013

.11

2.16

72 (

22)

28.8

514

.82

1.72

27.0

614

.10

1.86

25.1

513

.35

1.99

23.2

012

.60

2.11

20.7

011

.65

2.20

17.8

910

.63

2.26

800

/0.

10

57 (

14)

22.8

522

.85

1.70

21.4

921

.49

1.81

20.1

220

.12

1.92

18.4

918

.49

2.01

16.5

716

.57

2.09

14.6

414

.64

2.17

62 (

17)

23.6

121

.88

1.71

21.9

021

.04

1.82

20.2

120

.15

1.92

18.5

218

.52

2.01

16.6

016

.60

2.09

14.6

714

.67

2.17

63*

(17)

24.1

617

.84

1.71

22.3

817

.02

1.83

20.5

316

.20

1.93

18.3

015

.22

2.00

15.6

514

.09

2.06

13.0

712

.94

2.12

67 (

19)

26.5

618

.75

1.73

24.7

017

.97

1.86

22.8

017

.17

1.98

20.7

416

.32

2.07

17.9

615

.21

2.13

15.2

314

.13

2.19

72 (

22)

29.5

315

.47

1.73

27.6

914

.75

1.87

25.7

814

.01

2.01

23.7

413

.26

2.13

21.2

812

.36

2.23

18.3

311

.28

2.29

900

/0.

11

57 (

14)

23.8

223

.82

1.72

22.4

122

.41

1.84

20.9

820

.98

1.95

19.3

619

.36

2.04

17.3

217

.32

2.12

15.3

215

.32

2.21

62 (

17)

24.2

123

.22

1.73

22.5

422

.34

1.84

21.0

121

.01

1.95

19.3

919

.39

2.05

17.3

517

.35

2.12

15.3

415

.34

2.21

63*

(17)

24.7

018

.77

1.73

22.8

717

.94

1.85

20.9

717

.11

1.95

18.7

316

.14

2.02

16.0

314

.99

2.08

13.5

513

.55

2.15

67 (

19)

27.1

319

.72

1.74

25.2

318

.95

1.88

23.2

818

.14

2.00

21.1

517

.29

2.10

18.3

516

.19

2.15

15.6

015

.06

2.21

72 (

22)

30.0

616

.04

1.74

28.1

915

.34

1.89

26.2

314

.59

2.03

24.1

513

.85

2.15

21.7

412

.99

2.25

18.7

211

.91

2.32

See L

eg

en

d a

nd

No

tes o

n p

ag

e 1

0.

PA

J330

EVA

PO

RA

TOR

AIR

CO

ND

EN

SE

R E

NT

ER

ING

AIR

TE

MP

ER

AT

UR

ES

F

(C

)75

(24

)85

(29

)95

(35

)10

5 (4

1)11

5 (4

6)12

5 (5

2)

CF

M /

BF

EW

B F(

C)

Cap

acit

y M

Btu

hTo

tal

Sys

KW

Cap

acit

y M

Btu

hTo

tal

Sys

KW

Cap

acit

y M

Btu

hTo

tal

Sys

KW

Cap

acit

y M

Btu

hTo

tal

Sys

KW

Cap

acit

y M

Btu

hTo

tal

Sys

KW

Cap

acit

y M

Btu

hTo

tal

Sys

KW

Tota

lS

ens

Tota

lS

ens

Tota

lS

ens

Tota

lS

ens

Tota

lS

ens

Tota

lS

ens

875

/0.

08

57 (

14)

27.7

027

.70

2.10

26.0

926

.09

2.24

24.5

424

.54

2.39

22.8

622

.86

2.53

20.9

420

.94

2.68

18.6

718

.67

2.78

62 (

17)

28.8

726

.13

2.11

26.8

725

.20

2.25

24.8

624

.24

2.39

22.9

022

.90

2.53

21.0

121

.01

2.68

18.7

118

.71

2.78

63*

(17)

29.4

321

.34

2.12

27.4

020

.44

2.26

25.3

119

.50

2.40

23.0

918

.54

2.53

20.4

617

.41

2.65

17.3

516

.07

2.71

67 (

19)

31.9

422

.16

2.16

29.9

221

.34

2.31

27.7

920

.47

2.45

25.5

519

.56

2.59

23.1

118

.62

2.73

20.0

017

.41

2.85

72 (

22)

34.8

918

.05

2.22

32.9

217

.29

2.37

30.7

816

.48

2.52

28.4

915

.63

2.66

26.0

814

.75

2.81

23.5

013

.86

2.94

1000

/0.

09

57 (

14)

29.0

429

.04

2.14

27.4

427

.44

2.28

25.7

525

.75

2.43

24.0

224

.02

2.58

22.1

122

.11

2.73

19.7

219

.72

2.86

62 (

17)

29.6

728

.01

2.15

27.7

127

.09

2.29

25.7

925

.79

2.43

24.0

624

.06

2.58

22.1

522

.15

2.73

19.7

519

.75

2.86

63*

(17)

30.1

422

.60

2.16

28.0

721

.72

2.29

25.9

120

.79

2.43

23.6

419

.84

2.57

21.0

718

.77

2.70

17.8

917

.39

2.76

67 (

19)

32.6

223

.42

2.20

30.5

722

.64

2.34

28.4

021

.80

2.49

26.0

920

.91

2.63

23.6

319

.99

2.76

20.5

718

.84

2.89

72 (

22)

35.5

118

.76

2.26

33.5

018

.03

2.41

31.3

017

.23

2.55

28.9

616

.39

2.70

26.4

915

.52

2.84

23.8

714

.64

2.97

1125

/0.

10

57 (

14)

30.1

430

.14

2.18

28.5

128

.51

2.33

26.7

726

.77

2.48

24.9

524

.95

2.63

22.9

822

.98

2.77

20.6

220

.62

2.91

62 (

17)

30.3

829

.71

2.18

28.5

028

.50

2.33

26.8

126

.81

2.48

24.9

924

.99

2.63

23.0

123

.01

2.77

20.6

620

.66

2.92

63*

(17)

30.6

723

.75

2.19

28.5

722

.91

2.33

26.3

622

.00

2.47

24.0

721

.06

2.60

21.5

820

.02

2.74

18.4

218

.42

2.82

67 (

19)

33.1

324

.56

2.23

31.0

423

.83

2.37

28.8

523

.02

2.52

26.4

722

.15

2.66

24.0

221

.25

2.80

21.0

620

.15

2.93

72 (

22)

35.9

619

.38

2.29

33.9

318

.68

2.44

31.6

917

.89

2.59

29.2

917

.07

2.73

26.7

916

.21

2.88

24.1

515

.34

3.01

See L

eg

en

d a

nd

No

tes o

n p

ag

e 1

0.

Page 9: Product Specificationsicpindexing.toddsit.com/documents/086477/42641170101.pdfB. SELECT UNIT BASED ON REQUIRED COOLING CAPACITY. Enter Cooling Capacities table at condenser entering

9426 41 1701 01

CO

OL

ING

CA

PAC

ITIE

S (

CO

NT

)

PA

J336

EVA

PO

RA

TOR

AIR

CO

ND

EN

SE

R E

NT

ER

ING

AIR

TE

MP

ER

AT

UR

ES

F

(C

)75

(24

)85

(29

)95

(35

)10

5 (4

1)11

5 (4

6)12

5 (5

2)

CF

M /

BF

EW

B F(

C)

Cap

acit

y M

Btu

hTo

tal

Sys

KW

Cap

acit

y M

Btu

hTo

tal

Sys

KW

Cap

acit

y M

Btu

hTo

tal

Sys

KW

Cap

acit

y M

Btu

hTo

tal

Sys

KW

Cap

acit

y M

Btu

hTo

tal

Sys

KW

Cap

acit

y M

Btu

hTo

tal

Sys

KW

Tota

lS

ens

Tota

lS

ens

Tota

lS

ens

Tota

lS

ens

Tota

lS

ens

Tota

lS

ens

1050

/0.

07

57 (

14)

33.5

033

.50

2.56

31.6

731

.67

2.73

29.7

929

.79

2.90

27.8

727

.87

3.09

25.5

025

.50

3.24

22.7

422

.74

3.38

62 (

17)

34.8

830

.87

2.59

32.5

229

.76

2.75

30.1

528

.64

2.91

27.8

927

.89

3.08

25.5

525

.55

3.24

22.7

922

.79

3.38

63*

(17)

35.6

625

.30

2.59

33.2

324

.20

2.76

30.7

223

.10

2.93

28.1

822

.01

3.10

24.8

820

.62

3.21

21.1

319

.06

3.31

67 (

19)

38.9

526

.43

2.62

36.5

325

.45

2.81

33.9

624

.41

3.00

31.2

723

.33

3.19

28.2

922

.15

3.35

24.3

420

.62

3.44

72 (

22)

42.8

421

.73

2.66

40.5

620

.88

2.86

38.0

419

.94

3.05

35.3

118

.94

3.25

32.4

317

.90

3.44

29.0

516

.73

3.63

1200

/0.

08

57 (

14)

35.2

135

.21

2.61

33.2

933

.29

2.78

31.3

131

.31

2.96

29.2

829

.28

3.15

26.9

826

.98

3.31

24.0

324

.03

3.45

62 (

17)

35.9

633

.14

2.61

33.6

132

.04

2.79

31.3

431

.34

2.96

29.3

329

.33

3.15

27.0

327

.03

3.32

24.0

724

.07

3.45

63*

(17)

36.6

426

.87

2.62

34.1

525

.80

2.80

31.5

224

.66

2.96

28.8

423

.54

3.13

25.6

322

.20

3.25

21.8

220

.59

3.36

67 (

19)

39.9

128

.02

2.64

37.4

727

.09

2.83

34.8

026

.04

3.03

32.0

324

.96

3.21

29.0

023

.82

3.39

25.0

422

.28

3.49

72 (

22)

43.6

822

.64

2.68

41.3

721

.83

2.88

38.7

920

.91

3.08

36.0

219

.92

3.28

33.0

618

.88

3.47

29.8

017

.78

3.65

1350

/0.

10

57 (

14)

36.6

736

.67

2.63

34.6

934

.69

2.82

32.6

432

.64

3.01

30.5

130

.51

3.21

28.1

728

.17

3.38

25.1

125

.11

3.51

62 (

17)

36.9

635

.26

2.63

34.7

034

.70

2.82

32.6

932

.69

3.02

30.5

630

.56

3.21

28.2

128

.21

3.39

25.1

625

.16

3.51

63*

(17)

37.4

128

.32

2.64

34.8

627

.26

2.82

32.1

826

.14

3.00

29.4

525

.01

3.17

26.2

723

.68

3.29

22.4

722

.36

3.40

67 (

19)

40.6

429

.47

2.66

38.1

628

.58

2.86

35.4

727

.57

3.05

32.6

226

.49

3.24

29.6

025

.37

3.42

25.6

923

.84

3.54

72 (

22)

44.2

823

.43

2.70

41.9

822

.67

2.90

39.3

621

.78

3.10

36.5

420

.81

3.30

33.5

419

.78

3.50

30.2

718

.71

3.68

See L

eg

en

d a

nd

No

tes o

n p

ag

e 1

0.

PA

J342

EVA

PO

RA

TOR

AIR

CO

ND

EN

SE

R E

NT

ER

ING

AIR

TE

MP

ER

AT

UR

ES

F

(C

)75

(24

)85

(29

)95

(35

)10

5 (4

1)11

5 (4

6)12

5 (5

2)

CF

M /

BF

EW

B F(

C)

Cap

acit

y M

Btu

hTo

tal

Sys

KW

Cap

acit

y M

Btu

hTo

tal

Sys

KW

Cap

acit

y M

Btu

hTo

tal

Sys

KW

Cap

acit

y M

Btu

hTo

tal

Sys

KW

Cap

acit

y M

Btu

hTo

tal

Sys

KW

Cap

acit

y M

Btu

hTo

tal

Sys

KW

Tota

lS

ens

Tota

lS

ens

Tota

lS

ens

Tota

lS

ens

Tota

lS

ens

Tota

lS

ens

1225

/0.

11

57 (

14)

39.0

639

.06

2.87

36.9

736

.97

3.13

34.8

834

.88

3.38

32.6

232

.62

3.61

29.5

129

.51

3.81

26.6

026

.60

4.02

62 (

17)

40.6

136

.69

2.89

37.9

435

.42

3.16

35.3

134

.13

3.40

32.6

432

.64

3.61

29.5

729

.57

3.81

26.6

526

.65

4.03

63*

(17)

41.4

729

.95

2.89

38.7

428

.71

3.17

35.9

227

.45

3.41

32.9

126

.13

3.62

28.6

924

.32

3.77

24.7

322

.64

3.93

67 (

19)

45.2

631

.27

2.91

42.5

130

.12

3.20

39.6

328

.95

3.47

36.6

327

.72

3.73

32.6

726

.16

3.95

28.4

724

.50

4.11

72 (

22)

49.8

325

.62

2.94

47.1

424

.58

3.25

44.2

523

.48

3.55

41.1

622

.35

3.82

37.9

821

.16

4.08

33.9

219

.76

4.34

1400

/0.

12

57 (

14)

40.9

840

.98

2.93

38.8

138

.81

3.20

36.6

136

.61

3.46

34.2

634

.26

3.71

31.1

431

.14

3.92

28.0

428

.04

4.13

62 (

17)

41.8

039

.32

2.93

39.1

738

.04

3.20

36.6

236

.62

3.46

34.3

234

.32

3.72

31.2

031

.20

3.92

28.0

728

.07

4.13

63*

(17)

42.5

131

.75

2.93

39.7

030

.51

3.21

36.8

229

.27

3.46

33.7

227

.95

3.70

29.5

026

.16

3.84

25.4

724

.42

4.00

67 (

19)

46.2

933

.08

2.95

43.4

731

.98

3.24

40.5

030

.80

3.52

37.4

329

.59

3.78

33.5

928

.17

4.02

29.2

626

.44

4.19

72 (

22)

50.7

826

.66

2.98

48.0

325

.64

3.30

45.0

624

.55

3.59

41.9

323

.41

3.88

38.6

422

.25

4.14

34.6

920

.95

4.39

1575

/0.

14

57 (

14)

42.5

842

.58

2.96

40.3

440

.34

3.25

38.0

238

.02

3.52

35.6

235

.62

3.78

32.5

232

.52

4.02

29.2

729

.27

4.23

62 (

17)

42.8

941

.73

2.97

40.3

440

.34

3.25

38.0

838

.08

3.52

35.6

835

.68

3.78

32.5

732

.57

4.02

29.3

229

.32

4.23

63*

(17)

43.3

333

.41

2.97

40.4

532

.19

3.25

37.4

830

.93

3.51

34.4

029

.65

3.75

30.1

827

.87

3.91

26.1

825

.96

4.07

67 (

19)

47.0

634

.74

2.98

44.1

933

.68

3.29

41.1

732

.52

3.57

38.0

731

.33

3.83

34.3

530

.00

4.07

29.9

428

.26

4.26

72 (

22)

51.4

727

.57

3.02

48.6

926

.59

3.34

45.6

625

.51

3.64

42.4

724

.38

3.92

39.1

423

.21

4.19

35.2

722

.02

4.44

See L

eg

en

d a

nd

No

tes o

n p

ag

e 1

0

Page 10: Product Specificationsicpindexing.toddsit.com/documents/086477/42641170101.pdfB. SELECT UNIT BASED ON REQUIRED COOLING CAPACITY. Enter Cooling Capacities table at condenser entering

10 426 41 1701 01

CO

OL

ING

CA

PAC

ITIE

S (

CO

NT

)P

AJ3

48E

VAP

OR

ATO

R A

IRC

ON

DE

NS

ER

EN

TE

RIN

G A

IR T

EM

PE

RA

TU

RE

S

F (

C)

75 (

24)

85 (

29)

95 (

35)

105

(41)

115

(46)

125

(52)

CF

M /

BF

EW

B F(

C)

Cap

acit

y M

Btu

hTo

tal

Sys

KW

Cap

acit

y M

Btu

hTo

tal

Sys

KW

Cap

acit

y M

Btu

hTo

tal

Sys

KW

Cap

acit

y M

Btu

hTo

tal

Sys

KW

Cap

acit

y M

Btu

hTo

tal

Sys

KW

Cap

acit

y M

Btu

hTo

tal

Sys

KW

Tota

lS

ens

Tota

lS

ens

Tota

lS

ens

Tota

lS

ens

Tota

lS

ens

Tota

lS

ens

1400

/0.

07

57 (

14)

44.7

244

.72

3.31

42.8

042

.80

3.70

40.3

440

.34

4.07

37.2

937

.29

4.46

34.2

934

.29

4.92

31.1

331

.13

5.43

62 (

17)

46.2

741

.01

3.32

43.8

739

.88

3.71

40.9

538

.51

4.09

37.3

237

.32

4.46

34.3

534

.35

4.92

31.1

831

.18

5.44

63*

(17)

47.1

233

.38

3.32

44.6

732

.29

3.72

41.7

131

.00

4.11

37.6

029

.23

4.46

33.6

127

.56

4.89

29.4

625

.83

5.37

67 (

19)

50.8

834

.65

3.33

48.3

333

.60

3.75

45.6

332

.52

4.17

41.6

430

.97

4.60

37.5

029

.34

5.02

33.2

527

.70

5.51

72 (

22)

55.6

428

.13

3.36

53.0

227

.15

3.79

50.2

826

.13

4.23

47.3

025

.05

4.70

42.9

823

.56

5.21

38.5

721

.98

5.73

1600

/0.

08

57 (

14)

46.6

346

.63

3.36

44.6

044

.60

3.76

42.3

642

.36

4.19

39.0

639

.06

4.56

35.8

735

.87

5.02

32.5

832

.58

5.54

62 (

17)

47.4

243

.87

3.36

45.0

442

.69

3.77

42.3

842

.38

4.19

39.1

239

.12

4.57

35.9

335

.93

5.02

32.6

332

.63

5.54

63*

(17)

48.1

235

.36

3.37

45.5

834

.25

3.77

42.7

533

.07

4.19

38.4

931

.28

4.54

34.3

729

.56

4.96

30.1

427

.76

5.45

67 (

19)

51.8

736

.67

3.38

49.2

635

.66

3.80

46.5

034

.58

4.23

42.5

733

.17

4.68

38.3

331

.52

5.11

33.9

729

.82

5.59

72 (

22)

56.5

929

.32

3.41

53.8

728

.35

3.85

51.0

427

.32

4.29

48.0

526

.26

4.76

43.8

324

.90

5.27

39.2

723

.31

5.81

1750

/0.

09

57 (

14)

47.8

247

.82

3.40

45.7

345

.73

3.80

43.4

843

.48

4.23

40.1

840

.18

4.64

36.8

836

.88

5.09

33.5

133

.51

5.61

62 (

17)

48.1

945

.84

3.40

45.8

745

.51

3.80

43.5

443

.54

4.23

40.2

440

.24

4.64

36.9

336

.93

5.09

33.5

633

.56

5.61

63*

(17)

48.7

136

.72

3.40

46.1

035

.62

3.81

43.2

734

.48

4.23

39.0

232

.73

4.59

34.8

530

.96

5.02

30.6

229

.10

5.50

67 (

19)

52.4

538

.10

3.42

49.7

937

.10

3.84

47.0

036

.04

4.27

43.1

834

.75

4.73

38.8

333

.05

5.16

34.4

431

.30

5.65

72 (

22)

57.1

430

.14

3.45

54.3

729

.18

3.88

51.4

928

.16

4.33

48.4

727

.09

4.80

44.3

425

.84

5.31

39.7

224

.30

5.87

PA

J360

EVA

PO

RA

TOR

AIR

CO

ND

EN

SE

R E

NT

ER

ING

AIR

TE

MP

ER

AT

UR

ES

F

(C

)75

(24

)85

(29

)95

(35

)10

5 (4

1)11

5 (4

6)12

5 (5

2)

CF

M /

BF

EW

BF

(C

)C

apac

ity

MB

tuh

Tot

Sys

KW

Cap

acit

y M

Btu

hTo

tS

ysK

W

Cap

acit

y M

Btu

hTo

tS

ysK

W

Cap

acit

y M

Btu

hTo

tS

ysK

W

Cap

acit

y M

Btu

hTo

tS

ysK

W

Cap

acit

y M

Btu

hTo

tS

ysK

WTo

tal

Sen

sTo

tal

Sen

sTo

tal

Sen

sTo

tal

Sen

sTo

tal

Sen

sTo

tal

Sen

s

1750

/0.

07

57 (

14)

54.4

254

.42

3.99

52.3

652

.36

4.44

50.0

850

.08

4.94

47.4

947

.49

5.49

44.5

544

.55

6.09

41.2

841

.28

6.75

62 (

17)

55.9

249

.50

4.00

53.3

948

.33

4.45

50.6

647

.04

4.94

47.6

545

.52

5.49

44.6

044

.60

6.09

41.3

341

.33

6.75

63*

(17)

56.8

640

.17

4.01

54.2

439

.02

4.46

51.3

837

.78

4.95

48.1

636

.40

5.50

44.5

734

.89

6.09

40.6

733

.27

6.74

67 (

19)

60.9

541

.61

4.04

58.1

440

.47

4.50

55.0

039

.20

5.00

51.5

337

.82

5.55

47.6

736

.31

6.14

43.4

934

.71

6.78

72 (

22)

66.6

233

.65

4.09

63.4

932

.48

4.56

60.0

431

.23

5.07

56.2

429

.86

5.62

52.0

228

.36

6.21

47.4

726

.78

6.85

2000

/0.

08

57 (

14)

56.4

556

.45

4.06

54.2

554

.25

4.51

51.8

151

.81

5.01

49.0

449

.04

5.57

45.9

145

.91

6.17

42.4

642

.46

6.82

62 (

17)

57.1

452

.90

4.06

54.5

651

.64

4.51

51.8

351

.83

5.01

49.1

049

.10

5.57

45.9

645

.96

6.17

42.5

042

.50

6.82

63 (

17)

57.8

842

.52

4.07

55.1

541

.34

4.52

52.1

740

.07

5.02

48.8

338

.67

5.56

45.1

337

.14

6.16

41.1

335

.48

6.81

67 (

19)

62.0

144

.14

4.10

59.0

742

.96

4.56

55.7

941

.67

5.07

52.2

040

.27

5.61

48.2

138

.74

6.20

43.9

437

.10

6.85

72 (

22)

67.7

435

.19

4.16

64.4

634

.01

4.63

60.8

932

.73

5.14

56.9

431

.34

5.69

52.5

829

.82

6.27

47.9

128

.22

6.91

2250 /

0.0

9

57

(1

4)

58

.14

58

.14

4.1

25

5.8

15

5.8

14

.58

53

.21

53

.21

5.0

95

0.3

15

0.3

15

.64

47

.02

47

.02

6.2

44

3.4

04

3.4

06

.89

62

(1

7)

58

.27

57

.81

4.1

35

5.8

75

5.8

74

.58

53

.27

53

.27

5.0

95

0.3

65

0.3

65

.64

47

.07

47

.07

6.2

44

3.4

44

3.4

46

.89

63

(1

7)

58

.65

44

.72

4.1

35

5.8

44

3.5

34

.58

52

.77

42

.26

5.0

84

9.3

44

0.8

45

.63

45

.57

39

.27

6.2

24

1.4

93

7.5

36

.87

67

(1

9)

62

.80

46

.52

4.1

75

9.7

64

5.3

34

.63

56

.39

44

.02

5.1

35

2.7

04

2.6

15

.68

48

.64

41

.05

6.2

74

4.2

83

9.3

46

.91

72

(2

2)

68

.58

36

.65

4.2

26

5.2

13

5.4

54

.70

61

.52

34

.15

5.2

05

7.4

53

2.7

45

.75

52

.99

31

.21

6.3

44

8.2

02

9.5

86

.97

* A

t 75°

F e

nte

rin

g d

ry b

ulb

- T

en

nessee V

alle

y A

uth

ori

ty (

TV

A)

ratin

g c

on

ditio

ns;

all

oth

ers

at

80°

F d

ry b

ulb

.

LE

GE

ND

BF

— B

yp

ass F

acto

rE

wb

— E

nte

rin

g W

et-

Bu

lbkW

— T

ota

l U

nit P

ow

er

Inp

ut

SH

C —

Sen

sib

le H

eat

Cap

acity (

10

00

Btu

h)

TC

— T

ota

l C

ap

acity (

10

00

Btu

h)

(net)

NO

TE

S:

1. D

irect

inte

rpo

latio

n is p

erm

issib

le. D

o n

ot

ext

rap

ola

te.

2.

Th

e f

ollo

win

g f

orm

ula

s m

ay b

e u

sed

:

Sens

ible

cap

acity

(B

tuh)

1.10

x c

fm

t ldb

= t e

db − Wet−

bulb

tem

pera

ture

cor

resp

ondi

ng t

o en

thal

py

air

leav

ing

evap

orat

or c

oil (

h lw

b)t lw

b =

tota

l cap

acity

(B

tuh)

4.5

x cf

mh l

wb

= h

ewb −

Wh

ere

: hew

b =

En

thalp

y o

f air

en

teri

ng

evap

ora

tor

co

il3.

Th

e S

HC

is

based

on

80

° F

(2

6.7

°C)

ed

b t

em

pera

ture

of air

en

teri

ng

in

do

or

co

il.

Belo

w 8

F

(26

.7°C

) ed

b,

su

btr

act

(co

rr facto

r x c

fm)

fro

m S

HC

. A

bo

ve 8

F (

26

.7°C

) ed

b,

ad

d (

co

rr facto

r x c

fm)

to S

HC

. C

orr

ectio

n F

acto

r =

1.1

0 x

(1

- B

F)

x (e

db

- 8

0).

Page 11: Product Specificationsicpindexing.toddsit.com/documents/086477/42641170101.pdfB. SELECT UNIT BASED ON REQUIRED COOLING CAPACITY. Enter Cooling Capacities table at condenser entering

SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE 11426 41 1701 01

Filter Pressure Drop (IN. W.C.)

UNIT SIZEPAJ3

FILTERSIZE in.

(mm) 500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100 2200

2420x20x1(508x508

x25)0.06 0.07 0.08 0.10 0.12 0.13 0.14 0.15 — — — — — — — — — —

3020x24x1(508x610

x25)— — — 0.08 0.09 0.10 0.11 0.13 0.14 0.15 0.16 — — — — — — —

36 − 4224x30x1(610x762

x25)— — — 0.04 0.05 0.06 0.07 0.07 0.08 0.09 0.10 — — — — — — —

48 − 6024x36x1(610x914

x25)— — — — — — — 0.06 0.07 0.07 0.08 0.09 0.09 0.10 0.11 0.12 0.13 0.14

Accessory Electric Heat Pressure Drop (IN. W.C.)

HEATER kW

CFM

800 1000 1200 1400 1600 1800 2000 2200

5−20 0.033 0.037 0.042 0.047 0.052 0.060 0.067 0.075

Wet Coil Delivery*— (Deduct 10% for 208−Volt Operation)UNITPAJ3 SPEED TAP

AIRDELIVERY2

EXTERNAL STATIC PRESSURE (in. W.C.)0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0

241 CFM 965 818 777 731 670 617 563 489 451 3912 CFM 1003 921 890 850 809 756 700 659 597 5393 CFM 1103 1068 1034 996 962 930 892 821 791 742

301 CFM 1052 1018 984 943 914 879 833 795 732 6782 CFM 1141 1107 1069 1036 1006 974 932 899 856 7843 CFM 1246 1213 1181 1144 1108 1078 1043 1015 973 931

361 CFM 1281 1225 1178 1142 1098 1053 1008 935 878 8402 CFM 1359 1321 1278 1236 1201 1160 1109 1068 992 9413 CFM 1476 1441 1403 1366 1323 1289 1245 1201 1159 1117

421 CFM 1453 1408 1373 1337 1295 1255 1215 1177 1134 10682 CFM 1544 1507 1475 1436 1397 1359 1326 1290 1246 12013 CFM 1614 1575 1542 1509 1467 1430 1395 1358 1323 1267

481 CFM 1657 1625 1590 1554 1517 1486 1448 1417 1381 13402 CFM 1707 1673 1644 1614 1586 1549 1515 1479 1449 14073 CFM 1931 1900 1870 1840 1809 1778 1749 1714 1683 1646

601 CFM 1837 1798 1753 1716 1677 1637 1590 1549 1497 14452 CFM 1910 1872 1835 1795 1748 1711 1673 1623 1568 15253 CFM 2098 2065 2032 1996 1956 1917 1877 1839 1798 1753

*Air delivery values are based on operating voltage of 230v, wet coil, without filter or electric heater. Deduct filter and electric heater pressure drops toobtain static pressure available for ducting.NOTES:1. Do not operate the unit at a cooling airflow that is less than 350 cfm for each 12,000 Btuh of rated cooling capacity. Evaporator coil frosting may occurat airflows below this point.2. Standard Cubic Feet per Minute.

Page 12: Product Specificationsicpindexing.toddsit.com/documents/086477/42641170101.pdfB. SELECT UNIT BASED ON REQUIRED COOLING CAPACITY. Enter Cooling Capacities table at condenser entering

SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE12 426 41 1701 01

TYPICAL WIRING SCHEMATIC 208/230−1−60

24 V

olt

The

rmos

tat

Con

nect

ions

24 V

olt

The

rmos

tat

Con

nect

ions

24 V

olt

The

rmos

tat

Con

nect

ions

Page 13: Product Specificationsicpindexing.toddsit.com/documents/086477/42641170101.pdfB. SELECT UNIT BASED ON REQUIRED COOLING CAPACITY. Enter Cooling Capacities table at condenser entering

SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE 13426 41 1701 01

TYPICAL FIELD WIRING

Note: 20 kW shown. Smaller heater have fewer elements and controls. Single-Phase Accessory Electric Heater Wiring

Page 14: Product Specificationsicpindexing.toddsit.com/documents/086477/42641170101.pdfB. SELECT UNIT BASED ON REQUIRED COOLING CAPACITY. Enter Cooling Capacities table at condenser entering

SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE14 426 41 1701 01

Electrical Data

UNITPAJ3 V-PH-HZ

RANGE OFM IFM NOMINAL FLA MCAMOCP **MIN MAX RLA LRA FLA FLA kW * 208 240 208 230

24 208/230-1-60 197 253 8.5 43.0 0.9 2.8

-/- - - 14.3 14.3 203.8/5 18.0 20.8 26.0 29.5 30/30

5.6/7.5 27.0 31.3 37.3 42.6 40/457.5/10 36.1 41.7 48.6 55.6 50/60

30 208/230-1-60 197 253 10.9 54.0 0.9 2.8

-/- - - 17.4 17.4 253.8/5 18.0 20.8 26.0 29.5 30/30

5.6/7.5 27.0 31.3 37.3 42.6 40/457.5/10 36.1 41.7 48.6 55.6 50/60

36 208/230-1-60 197 253 13.1 74.0 1.5 4.1

-/- - - 22.0 22.0 303.8/5 18.0 20.8 27.6 31.1 30/35

5.6/7.5 27.0 31.3 38.9 44.3 40/457.5/10 36.1 41.7 50.3 57.3 60/6011.3/15 54.1 62.5 72.8 83.3 80/90

42 208/230-1-60 197 253 15.7 88.0 1.5 4.1

-/- - - 25.2 25.2 403.8/5 18.0 20.8 27.6 31.1 40

5.6/7.5 27.0 31.3 38.9 44.3 40/457.5/10 36.1 41.7 50.3 57.3 60/6011.3/15 54.1 62.5 72.8 83.3 80/90

48 208/230-1-60 197 253 21.8 117.0 1.5 6.0

-/- - - 34.8 34.8 503.8/5 18.0 20.8 34.8 34.8 50/50

5.6/7.5 27.0 31.3 41.3 46.6 50/507.5/10 36.1 41.7 52.6 59.6 60/6011.3/15 54.1 62.5 75.1 85.6 80/90

15.0/20.0 72.1 83.3 97.6 111.6 100/125

60 208/230-1-60 197 253 27.6 135.0 1.9 7.6

-/- - - 44.0 44.0 603.8/5 18.0 20.8 44.0 44.0 60/60

5.6/7.5 27.0 31.3 43.3 48.6 60/607.5/10 36.1 41.7 54.6 61.6 60/7011.3/15 54.1 62.5 77.1 87.6 80/90

15.0/20.0 72.1 83.3 99.6 113.6 100/125* kW @ 208/240** HACR Type Circuit breakerLEGENDFLA − Full Load AmpsLRA − Locked Rotor AmpsMCA − Minimum Circuit AmpsMOCP − Maximum Overcurrent ProtectionRLA − Rated Load AmpsNOTES:1. In compliance with NEC (National Electrical Code) requirements for multimotor and combination load equipment (refer to NEC Articles 430 and 440), the overcurrentprotective device for the unit shall be Power Supply fuse. The CGA (Canadian Gas Association) units may be fuse or circuit breaker. 2. Minimum wire size is based on 60�C copper wire. If other than 60�C wire is used, or if length exceeds wire length in table, determine size from NEC.

*Heater capacity (kW) based on heater voltage of 208v & 240v. If power distribution voltage to unit varies from rated heater voltage, heater kW will vary accordingly.

OPERATING SEQUENCECooling OperationWith a call for cooling (Y/G), the contactor is energized whichbrings on the compressor and outdoor fan. The indoor fan is alsoenergized. When the cooling demand is met, Y and G arede−energized shutting off the contactor. The indoor fan stops aftera 60 second delay.

Heating OperationWith a call for heating (W2), the auxiliary or electric heat energizesalong with the indoor blower. In case of staged heating, W3 isenergized if the demand is not met. The highest airflow selected isrun while the electric heat is in operation. When heating demand ismet, W3 and W2 sequentially de−energize shutting off the indoorfan and the electric heater.

Continuous FanWith the continuous indoor fan option selected on the thermostat,G is continuously energized keeping the indoor fan running at alltimes.

APPLICATION DATACondensate trap — A 2−in. (51 mm) condensate trap must be fieldsupplied.

1” (25 mm) MIN.

2” (51 mm) MIN.

TRAPOUTLET

A08001

Maximum cooling airflow — To minimize the possibility ofcondensate blow−off from the evaporator, airflow through the unitsshould not exceed 450 CFM/ton.Minimum cooling airflow — The minimum cooling airflow is 350cfm/ton.Minimum cooling operating outdoor air temperature — Allstandard units have a minimum ambient operating temperature of40°F (4.4°C). With accessory low ambient temperature kit, unitscan operate at temperatures down to 0°F (−17.8°C).Maximum operating outdoor air temperature — Maximumoutdoor operating air temperature for cooling is 125°F (51.7°C).

Page 15: Product Specificationsicpindexing.toddsit.com/documents/086477/42641170101.pdfB. SELECT UNIT BASED ON REQUIRED COOLING CAPACITY. Enter Cooling Capacities table at condenser entering

SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE 15426 41 1701 01

TYPICAL INSTALLATION

TOP COVER

INDOORTHERMOSTAT

DISCONNECTPER NEC(UNIT ANDELECTRICHEATER)

FROMPOWERSOURCE

RETURNAIR

POWERENTRY

COMPOSITERUST-PROOFBASEPAN

CONDENSATEDRAINCONNECTION

Power Wiring

Control Wiring

Condenser Airflow

Evaporator Airflow

LOW VOLTAGEENTRY

Page 16: Product Specificationsicpindexing.toddsit.com/documents/086477/42641170101.pdfB. SELECT UNIT BASED ON REQUIRED COOLING CAPACITY. Enter Cooling Capacities table at condenser entering

SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE16 426 41 1701 01

ENGINEERS’ SPECIFICATION GUIDEGENERALFurnish and install outdoor package, electrically controlled, airconditioner utilizing a reciprocating or scroll compressor for coolingduty. Unit shall discharge supply air horizontally as shown oncontract drawings.Nominal unit electrical characteristics shall be ______ v, ______ph, 60 Hz. The unit shall be capable of satisfactory operationwithin voltage limits of ______ v to ______ v. Unit power wiringshall enter unit cabinet at a single location.Separate power supply shall not be required for electric heat.

COOLING CAPACITYTotal cooling capacity of the unit shall be _____ Btuh or greater,and sensible capacity shall be ______ Btuh or greater atconditions of ______ cfm indoor air entering unit at ______�F drybulb, _____�F wet bulb and outdoor entering air of ______�F drybulb. Total design conditions shall be a minimum of ______Btuh/Watt. The unit shall be capable of cooling operation down to40�F (4.4�C) as shipped from the factory.

CABINETUnit cabinet shall be constructed of phosphated, bonderized,zinc−coated, prepainted steel. Basepan shall be made of asingle−piece non−corrosive, composite material.Evaporator−fan compartment interior cabinet surfaces shall beinsulated with a minimum 1/2−in. (12.7 mm) thick, flexiblefiberglass insulation, coated on the air side with aluminum foil.Cabinet panels shall be easily removable for servicing.Outdoor coil shall be protected by metal louvered panels.

COMPRESSORCompressor shall be fully hermetic type with external vibrationisolation.

CONDENSER SECTIONCondenser fan shall be of the direct−driven propeller type blades,riveted to corrosion−resistant spiders, and shall be dynamicallybalanced and discharge air vertically upwards.Condenser coils shall have aluminum−plate fins mechanicallybonded to copper tubes with all joints brazed.Tube sheet openings shall be belled to prevent tube wear.

EVAPORATOR SECTIONFan shall be multi−speed with direct drive motor as shown on theequipment drawings.Fan wheel shall be made from steel, be double−inlet type withforward−curved blades with a corrosion−resistant finish anddynamically balanced.Evaporator coils shall have aluminum−plate fins mechanicallybonded to copper tubes with all joints brazed.Tube sheet openings shall be belled to prevent tube wear.

MOTORSCompressor motors shall be of the refrigerant cooled type with linebreak thermal and current overload protection.All fan motors shall have permanently lubricated bearings, andinherent automatic reset thermal overload protection.Condenser fan motor shall be totally enclosed.

REFRIGERANT SYSTEMRefrigerant system shall include fixed orifice or TXV meteringsystem.

CONTROLSUnit shall be complete with self−contained low voltage controlcircuit.

APPROVALSUnit shall be UL listed as a total package for safety requirements.All wiring shall be in accordance with NEC.Unit shall be rated in accordance with AHRI Standards 210/240.Cabinet insulation shall conform to ASHRAE Standard 62.2Insulation and adhesive shall meet NFPA 90A requirements forflame spread and smoke generation.Unit shall have a sloped drain pan that conforms to ASHRAEStandard 62.2.

ACCESSORIESField−installed accessories shall include solid−state compressorshort−cycle device, outdoor thermostat, room thermostats, electricheaters with single−point connection, crankcase heater, andlow−ambient kit.