PRF - PV - Technical Note on Solar Grid Integeration Ver 1 0

Embed Size (px)

Citation preview

  • 8/11/2019 PRF - PV - Technical Note on Solar Grid Integeration Ver 1 0

    1/17

    TECHNICAL NOTE

    Solar Grid Integration

    Nov 2012

  • 8/11/2019 PRF - PV - Technical Note on Solar Grid Integeration Ver 1 0

    2/17

  • 8/11/2019 PRF - PV - Technical Note on Solar Grid Integeration Ver 1 0

    3/17

    3 | P a g e

    TABLE OF CONTENTS

    1 Executive Summary 4

    2 Introduction 4

    3Grid Interconnection

    Standards5

    3.1 Safety Standards 6

    3.1.1 Fire Safety 6

    3.1.2 Islanding 6

    3.1.3 Over/Under voltage 7

    3.1.4 Grounding 8

    3.1.5 Over/Under Frequency 8

    3.1.6 Manual Disconnect Switch 9

    3.1.7 Short Circuit Capacity 9

    3.2 Quality Standards 10

    3.2.1 Harmonics 10

    3.2.2 Power Factor 11

    3.2.3 Flicker 12

    3.2.4 Voltage Imbalance 12

    3.2.5 DC Injection 13

    Appendix 14-16

  • 8/11/2019 PRF - PV - Technical Note on Solar Grid Integeration Ver 1 0

    4/17

    4 | P a g e

    1.Executive Summary

    The note summarizes the technical guidelines that need to be followed for integrating a PVsystem to grid, problems accompanied with higher penetration of PV system and possible

    solutions to overcome it. With the increased Levelized cost of electricity from conventional

    energy sources such as coal, petroleum etc, its evident that solar energy would achieve grid

    parity sooner. The best part of PV systems is that they can be installed on every roof top that

    has minimum shading. So the penetration level of solar in supplying power to the grid is huge.

    It offers several advantages such as reduction in transmission losses; reduction in carbon foot-

    print and uninterrupted power supply.

    With the advancement in inverter technologies many more things are to come such as

    power factor control, voltage stabilization and remote energy management system. With such a

    kind of opportunity available, one must plan the distribution network in order to account for this

    increased penetration. The document discuss the precautions one need to take for connecting

    PV to grid, based on current standards and so the user has to be aware of the change in

    standards with time and region. The document assumes that the reader is fully aware of the

    technical concepts related to grid infrastructure and its protective equipments. Moreover a

    basic knowledge of electrical engineering is a must.

    2. Introduction

    The concept of synchronization is a recent trend evolved in 19thcentury when large sized

    Diesel Generators were added to the grid by many industries in Europe and America.

    The conditions for grid synchronization are that the

    1) The phase angle of voltage source must be within 15 with that of the grid voltage.

    2) The frequency of the sources must exactly match.

    3) In case of three phase synchronization the phase sequences must also match.

    The modern technical standards for grid connection are based on the above ground rules

    and other power quality issues. Each region either follow their own standards (like

  • 8/11/2019 PRF - PV - Technical Note on Solar Grid Integeration Ver 1 0

    5/17

    5 | P a g e

    Australia) or they specify the either of the three such as IEEE, NEC or UL standards to be

    followed.

    The basic structure for grid tied solar photovoltaic system is shown in Figure 1.

    The system comprises of an inverter which usually is a grid tie inverter. These inverters

    should have automatic synchronizing mechanisms and should be able to provide islanding

    protection. There are a lot of technical and safety standards that a grid tied inverter must

    satisfy to be employed in this kind of system.

    3. Grid Integration Standards

    The grid integration requires some safety and power quality standards to be met. The

    following section outlines the standards that the user has to be aware of before installing a

    grid connected PV systems.

    Figure [1]

  • 8/11/2019 PRF - PV - Technical Note on Solar Grid Integeration Ver 1 0

    6/17

    6 | P a g e

    3.1 SAFETY STANDARDS

    3.1.1 Fire Safety

    The potential of fire hazard is greater for DC than AC because a DC arc is harder to

    extinguish than an AC. The absence of a zero crossing in DC makes it more difficult for the arc to

    extinguish. DC voltages greater than 300V are bound have fire protection systems according to

    UL1741.

    3.1.2 Islanding

    Islanding is a phenomenon where a portion of utility system that contains both the

    load and generation source is isolated from the remainder of the utility system but

    remains energized. The principal concern with Islanding is the safety of line

    workers who come in contact with the line that is unexpectedly energized. Even

    when these people are trained to test the safety of a line before working the

    chances of accidents may remain high. The other concerns are damage to the

    utility equipments from a DG system working outside of specifications, and

    interface with automated distribution system protection function such as reclosing.

    Therefore the phenomenon of islanding happens to be two ways- Intentional and

    Unintentional.

    Intentional Islanding can occur at customer level such as hospital uses its

    emergency generators during a utility level. Potential safety concerns occur when

    DG system that is not specifically and approved for intentional islanding fails to

    detect the loss of utility power and continues to energize an isolated section of the

    utility line. Grid Tied inverters certified with UL1741 standard are recommended for

    this purpose.

    In order to avoid unintentional islanding inverters use active methods such as

    frequency shift, frequency instability, Power variation, Current Injection etc.

    Sometimes over/under voltage and over/under frequency protection schemes gives

    protection against unintentional islanding. IEEE 1547 standard specifies inverter to

    automatically trip if the RMS voltage at the point of coupling is above 10% or 12%

    below the nominal value or if the frequency is not between 1 Hz of the nominal

    value. With static inverters there is range of loads which are called Non-Detection

    Zone (NDZ) for which these methods of detection of islanding becomes difficult.

  • 8/11/2019 PRF - PV - Technical Note on Solar Grid Integeration Ver 1 0

    7/17

    7 | P a g e

    Modern technologies with greater penetration want PV system to ride through such

    voltage or frequency disturbances. But with incorporation such stringent conditions

    the penetration of PV system would lead to grid instability.

    3.1.3 Over/Under Voltage Protection

    The inverter has to operate at higher voltage compared to the grid in order to inject

    power into the grid. Considering the grid to be infinite and the level of penetration

    of PV to be low, the increase in voltage is very less. However due to faulty

    operation there is chance of increase in the terminal voltage at the point of coupling

    to the grid. Overvoltage may reduce the life time of the equipment and under-

    voltage may cause equipments to operate at lesser efficiency. International

    standards1have posed limitation. The situation becomes worse with higher

    penetration of PV into the system leading to unstable grid. If the power produced

    by the PV at a point is higher than the power consumed at that point, the surplus

    energy will flow into the grid. The reverse power flow causes the voltage to rise as

    it goes to other end. However this not issue with urban grid with high impedance

    network. In case of rural grid with low impedance and increase penetration of PV

    could cause the voltage to rise beyond the limits. This issue is called Over-Voltage.

    It is possible to minimize this effect by tap changing transformers but the lines near

    to the transformers may face under-voltage. Over-Voltages and under-voltages

    both have a negative impact on Generation side and distribution side. Over-voltage

    1Refer appendix 1A for IEEE 1547 and IEC6127 standards on Voltage Constraints.

  • 8/11/2019 PRF - PV - Technical Note on Solar Grid Integeration Ver 1 0

    8/17

    8 | P a g e

    may reduce the life time of the equipment and under-voltage may cause the

    equipments to operate less efficiently.

    There is a significant problem of voltage rise or fall when there is a large

    penetration of PV in to the distributed system. The problem can be lessened andthe upper limit on penetration of PV can be subsequently increased by the

    following ways.

    Decrease in the utility impedance. Increase use of transformers, use of multiple

    conductors and transformers with large de-rating factors results in lesser utility

    impedance and would decrease the effect of voltage with PV penetration. But this can

    be achieved with increase in cost and short circuit current which results in the redesign

    of over current protection equipments.

    Use of energy storage devices to store the excess power and deliver power whenthere is a shortfall would obviously reduce the impact of voltage rise or fall.

    Using PV inverters to supply or absorb reactive power to the grid would be a cost-

    effective solution for the voltage rise or fall. This in some cases results in under-

    utilization of available energy from the PV system.

    Energy Management systems (EMS) which are another technology coming into picture

    esp. for micro grids where a central system manages loads shedding accordingly to

    manage the problem of over/under voltage. Thus a careful disintegration of critical and

    non critical loads are to be done and the EMS should be managed based on that.

    3.1.4 Grounding

    There is no standard specification on the grounding but it always makes sense to

    protect your devices from lightning and shock. The grounding system is based on

    the specifications made by the inverter manufacture and the panel manufacturer. It

    is always good to have a surge arrester installed near the switchboard where the

    inverter terminal wires are connected. This will prevent loss of costly equipments

    due to lightning and surges.

    3.1.5 Under/Over Frequency Protection

    The disruption of balance between supply and demand leads to frequency

    fluctuations. The effect becomes more noticeable with higher penetration of PV

    system into the grid. There is a wide variety of impact on the quality of goods

  • 8/11/2019 PRF - PV - Technical Note on Solar Grid Integeration Ver 1 0

    9/17

    9 | P a g e

    produced from industries due to frequency fluctuations. It also stated that the

    resonance from frequency fluctuations may damage small generators and a chain

    reaction may lead to outage. International standards2require inverter to get tripped

    in the event of frequency disturbances occurring either in its output or the gridfrequency.

    The rapid variation in the output power of the PV due to cloud transient has a

    significant impact on the frequency of the system. This is because the variation is

    directly linked with the ramp rate and response time of the other generating plant.

    Battery storage systems are the best solutions for controlling the frequency

    disturbance due to load mismatch. Excess energy generated can be stored during

    normal operation and when there is an imbalance the stored power can be

    injected

    3

    .

    3.1.6 Manual Disconnect Switch

    Grid Connected PV systems are mandated in some parts of world to provide a

    lockable manual disconnect switch which the grid operator may use to ensure that

    there is no unintentional islanding. This ensures the 100% safety of the operators

    working on the line. But IEEE 929-2000 standards say that the utility systems may

    relax the requirement of a manual disconnect if the inverter is non islanding one.

    The cost of this switch when compared to cost of entire system is negligible butwhen they are compared with returns of the system they are relatively expensive.

    This device needs to be placed near the point of connection to the grid at an

    accessible height. In the UL 741 standards the provision of the utility disconnection

    switch is made mandatory.

    3.1.7 Short Circuit Capacity

    Short circuit capacity is amount of current that flows out of the system when a short

    circuit fault occurs in the network (Figure 2). If the short circuit current rating is high

    than the breaker capacity then the breaker will not be able to isolate the fault and

    the result would be the damage of equipments. PV inverters which are certified

    according to international standards have generally lower magnitude of fault

    2Refer appendix 1B for IEEE 1547 and IEC6127 standards on Frequency Constraints.

    3Refer appendix 3A for Battery sizing based on PV plant size.

  • 8/11/2019 PRF - PV - Technical Note on Solar Grid Integeration Ver 1 0

    10/17

    10 | P a g e

    current of the order 1-1.5 times the rated capacity. But there is a problem with

    upstream protection devices when there is a large penetration of the PV systems

    the fault current from the upstream would be low enough for the devices to act and

    hence leads to very dangerous situation of continuous flow of fault current.

    Figure [2]

    3.2 QUALITY STANDARDS

    3.2.1 Harmonics

    Harmonics is generally caused by non linear loads and generally viewed as

    pollution to the electrical network. The power electronic converters used with the

    Distributed generation systems are also a source of harmonics. Due to the

    capacitive coupling between the ground and the point of interconnection with the

    grid, the converter injects a capacitive ground current due to its switching action

    which can cause a high EMI. Square wave and Quasi square wave inverters are

    known to be major sources of harmonics. But majority of the latest technology

    inverters use Sinusoidal pulse width modulation techniques and digital active

    harmonic filters to reduce the production of harmonics at the output. The effect of

    harmonics not limited to be overloading of capacitors, resonance with the system

    leading to overstressing, overheating of magnetic cores of transformers and other

    rotating machines. If the disturbance happens in the 3rd5thand 7thharmonic then

    there would a large magnitude of current flow in the neutral wire which may have

  • 8/11/2019 PRF - PV - Technical Note on Solar Grid Integeration Ver 1 0

    11/17

    11 | P a g e

    been rated for less current carrying in which case will lead to burning of cables.

    Harmonics create problems of interference with telephone lines, broadcasting

    instruments. Electronic devices such a series reactor or static capacitors are

    installed in the distribution station to reduce the level of harmonics.

    IEEE 519 Section 11.54recommends that the voltage distortion limits, as a

    percentage of nominal fundamental frequency voltage in the utility service, should

    not exceed 5% of the total voltage harmonic distortion and 3% of any individual

    harmonic. Spectrum analyzers are devices used for measuring the harmonics

    produced by source. Standards require the measurement to be made with the

    instruments which has good response up to 25thharmonic. The tests on the

    inverter should be carried out under clear sky conditions. Certified inverters are

    exempted from testing it on site.

    3.2.2 Power Factor

    Power factor is the ratio of the real power delivered to the apparent power. PV

    inverters when operated at unity power factor impose the grid to supply all the

    greater proposition of reactive power and hence reducing the power factor at the

    distribution station. But it has an added advantage of reducing the transmission

    losses since there is no or lesser real power transmission along the line. (Figure: 3)

    The inverter should operate between 0.8 leading and 0.95 lagging for outputs

    ranging from 20% to 100% of the rated VA. IEC 6127 requires the inverter system

    to have a lagging power factor of 0.9 when the power is greater that of 50% of

    rated power. The basic criterion for islanding is that the PV should supply the real

    and reactive power of the load. The other reason to impose restriction on power

    factor is to prevent islanding.

    4Refer Appendix 2A for IEEE 519 on Harmonic Restrictions.

  • 8/11/2019 PRF - PV - Technical Note on Solar Grid Integeration Ver 1 0

    12/17

    12 | P a g e

    Figure 3

    3.2.3 Flicker

    Increase or decrease in voltage for a short period of time is called flicker. There are

    no standards defining flicker in numerical terms. The effect is based on the comfort

    level of the user. It is considered objectionable when it causes the modulation of

    lighting level sufficient to cause irritation to human eyes

    The term flicker is very subjective and depends on the magnitude of voltage and

    frequency. The lesser the frequency of flicker greater is its effect. A potential

    source of flicker from PV systems is during startup and shutdown of the system.

    The IEEE 1547-2003 allows 5% voltage fluctuations during the synchronization

    part of the DG (Distributed Generation) system. There is a general concern that the

    fluctuation in PV output would be a major cause for flicker in the output.

    3.2.4 Voltage Imbalance

    Voltage imbalance is a condition in which the amplitude of each phase voltage is

    different in a three phase system or the phase difference is not exactly 120.

    Voltage imbalance will generate current with twice the frequency and a backward

    magnetic field in three-phase synchronous machines, and will have a negative

    impact on generators, such as temperature rise of rotors, noise, and vibration. It

    will also have an impact on induction machines and power electronic devices.

    Generally for 33KV the voltage imbalance shall not exceed 3%. The phase current

  • 8/11/2019 PRF - PV - Technical Note on Solar Grid Integeration Ver 1 0

    13/17

    13 | P a g e

    imbalance according to IEEE929-2000 should be less than 5% measured at 50%

    and 100% of the rated current.

    3.2.5 DC Injection

    Transformer-less inverter inject DC current at the output of the AC terminal. IEEE

    1547 insists that the injected DC current must be lesser 0.5% of the rated capacity

    at the point of delivery. For a three phase inverter the injected DC current

    measured between phase to phase must not exceed 0.5% or 5 milli-amperes,

    whichever is greater. The limits is based on the harmonic standards and the limit of

    the distribution transformers which can tolerate about 0.5% of the dc current

    without its core getting saturated and the residual current devices (RCD) used forprotection (25 mA). When a number of inverters are connected to the grid in

    parallel then their combined value should be less than 0.5% of the distribution

    transformer used.

    IEC 61727 insists that the dc injection shall not be greater than 1% of the rated

    inverter current when the inverter is operating at the maximum power point.

  • 8/11/2019 PRF - PV - Technical Note on Solar Grid Integeration Ver 1 0

    14/17

    14 | P a g e

    Appendix 1

    A. Voltage Constraints for Grid Connected PV Inverters

    The IEC 6127 guidelines values are to be satisfied when the inverter is running at 50% of therated power.

    Voltage Condition

    (% Nominal Voltage)

    Maximum time to Disconnect

    (IEC 6127)

    V < 50% 0.1 Sec

    50% V < 85% 2 Sec

    85% V 110% Continuous Operation

    110% V 135% 2 Sec

    V > 135% 0.1 Sec

    Voltage Condition

    (% Nominal Voltage)

    Maximum time to Disconnect

    (IEEE 1547)

    V < 50% 0.16 Sec ( 8 Cycles)

    50% < V< 88% 2 Sec (100 Cycles)

    110% < V < 120% 1 Sec ( 50 Cycles)

    V > 120% 0.16 Sec (8 Cycles)

  • 8/11/2019 PRF - PV - Technical Note on Solar Grid Integeration Ver 1 0

    15/17

    15 | P a g e

    Appendix 1

    B. Frequency constraints for Grid Connected PV Inverters

    Frequency Range

    Maximum Clearance Time(IEEE1547)

    F > 60.5 Hz0.16

    F < 57.05

    0.16

    59.8 < F < 57.06

    Adjustable ( 0.16 and 300)

    559.3 if DER 30 kW.

    6For DER > 30 kW

  • 8/11/2019 PRF - PV - Technical Note on Solar Grid Integeration Ver 1 0

    16/17

    16 | P a g e

    Appendix 2

    A. Harmonic Content Limitat ions on Grid Connected PV Inverters

    IEEE 519 Sec 11.5

    Total harmonic distortion : 5.0%

    Maximum Distortion

    Harmonic Number Even Harmonics Odd Harmonics

    h < 11 1.0% 4.0%

    10 < h < 17 0.5% 2.0%

    18 < h 35 0.1 % 0.3%

  • 8/11/2019 PRF - PV - Technical Note on Solar Grid Integeration Ver 1 0

    17/17

    17 | P a g e

    Appendix 3

    A. Battery Sizing fo r Resolving Clou d Transient Issues.