2
PowerSkid SYSTEMS BI-DIRECTIONAL AC TO DC INVERTER/CONVERTERS For 5 kVAC, 15 kVAC, and 34.5 kVAC class grid connected battery energy storage applications, Dynapower Corporation offers it’s PowerSkid System line of utility grade, bi-directional, true four-quadrant, Digital Signal Processor (DSP) controlled inverter/converters. Dynapower’s efficient, flexible and highly modular PowerSkid System optimizes the transfer of energy between a DC energy storage system and a 3 phase medium voltage grid. is integrated package combines a medium voltage step up transformer, system cooling, controls and a full complement of switchgear and protection - including an AC circuit breaker, AC contactors, AC & DC Fusing, DC load break contactors and a DC manual isolation switch - into a single, heavy duty industrial enclosure. is integrated solution yields substantial reduction in Engineering, Procurement, Construction, and Management (EPCM) costs to the customer. e PowerSkid™ provides power conditioning (voltage and frequency support) for intermittent loads and renewable generation. PowerSkid MODES OF OPERATION e PowerSkid™ provides two modes of operation; Grid-Tied (PQ mode) and Stand-Alone (UF mode). In the Grid -Tied mode, the PowerSkidcontrols the AC output real power (P) and reactive power (Q). In Stand- Alone mode, the PowerSkid™ controls the AC output voltage (U) and frequency (F). e system can be started in either mode and the transfer between modes is done dynamically. Advanced control schemes for multi- unit autonomous and micro-grid applications are available. PowerSkidSystems AC Voltage 5 kVAC - 34.5 kVAC DC Voltage 750VDC – 1,250 VDC Power 1,000 kVA – 6,000 kVA Higher Power Systems Available Compliance UL 1741, IEEE 1547, & IEEE 519 Transformer Integrated Cast Coil or VPI Transformer Cooling • Liquid-cooled inverter modules and filters • Variety of Heat Exchange Options Available Features • True Four Quadrant Operation (Real and Reactive Power) • Local or Remote Operation • Zero Voltage Ride rough • Anti-Islanding Protection • Modular Redundancy • Sub-cycle System Response • RS232, RS485 and Ethernet communication available WWW.DYNAPOWER.COM T: 802 860 7200 6.0 MVA PowerSkidSystem with Integrated ULTRACAST™ Cast Coil Transformer, System Cooling, Controls and a Full Complement of AC & DC Switchgear

PowerSkid SyStemS - Energy · Dynapower Corporate Headquarters - South Burlington, Vermont 4.5 MVA PowerSkid™ System with Integrated ULTRACAST™ Cast Coil Transformer, System Cooling,

  • Upload
    others

  • View
    1

  • Download
    0

Embed Size (px)

Citation preview

Page 1: PowerSkid SyStemS - Energy · Dynapower Corporate Headquarters - South Burlington, Vermont 4.5 MVA PowerSkid™ System with Integrated ULTRACAST™ Cast Coil Transformer, System Cooling,

PowerSkid™ SyStemSBi-D irect ional ac to Dc inverter/converterS

For 5 kVAC, 15 kVAC, and 34.5 kVAC class grid connected

battery energy storage applications, Dynapower Corporation

offers it’s PowerSkid™ System line of utility grade, bi-directional,

true four-quadrant, Digital Signal Processor (DSP) controlled

inverter/converters. Dynapower’s efficient, flexible and highly

modular PowerSkid™ System optimizes the transfer of energy

between a DC energy storage system and a 3 phase medium

voltage grid.

This integrated package combines a medium voltage step up transformer, system cooling, controls and a full complement of switchgear and protection - including an AC circuit breaker, AC contactors, AC & DC Fusing, DC load break contactors and a DC manual isolation switch - into a single, heavy duty industrial enclosure. This integrated solution yields substantial reduction in Engineering, Procurement, Construction, and Management (EPCM) costs to the customer. The PowerSkid™ provides power conditioning (voltage and frequency support) for intermittent loads and renewable generation.

PowerSkid™ MODES OF OPERATION

The PowerSkid™ provides two modes of operation; Grid-Tied (PQ mode) and Stand-Alone (UF mode). In the Grid -Tied mode, the PowerSkid™ controls the AC output real power (P) and reactive power (Q). In Stand-Alone mode, the PowerSkid™ controls the AC output voltage (U) and frequency (F). The system can be started in either mode and the transfer between modes is done dynamically. Advanced control schemes for multi-unit autonomous and micro-grid applications are available.

PowerSkid™ Systems

AC Voltage 5 kVAC - 34.5 kVAC

DC Voltage 750VDC – 1,250 VDC

Power 1,000 kVA – 6,000 kVA Higher Power Systems Available

Compliance UL 1741, IEEE 1547, & IEEE 519

Transformer Integrated Cast Coil or VPI Transformer

Cooling • Liquid-cooledinvertermodulesand filters

• VarietyofHeatExchangeOptionsAvailable

Features • TrueFourQuadrantOperation(Real and Reactive Power)

• LocalorRemoteOperation

• ZeroVoltageRideThrough

•Anti-IslandingProtection

•ModularRedundancy

• Sub-cycleSystemResponse

• RS232,RS485andEthernetcommunication available

www.Dynapower.comt: 802 860 7200

6.0 MVA PowerSkid™ System with Integrated ULTRACAST™ Cast Coil Transformer, System Cooling, Controls and a Full Complement of AC & DC Switchgear

Page 2: PowerSkid SyStemS - Energy · Dynapower Corporate Headquarters - South Burlington, Vermont 4.5 MVA PowerSkid™ System with Integrated ULTRACAST™ Cast Coil Transformer, System Cooling,

85 Meadowland DriveSouth Burlington, VT 05403

© 2011 Dynapower Corporation

www.dynapower.com

ISO9001

PowerSkid™ SyStemS - B i -D irect ional ac to Dc inverter/converterS

SYSTEM CONTROL

Dynapower’s state of the art control and monitoring platform provides operators with both local and remote operation of the system. In the remote operating mode, a communication link provides autonomous operator control via Ethernet, RS232, orRS485.Forlocalcontrol,DynapowerprovidesanOperatorInterfaceTerminal(OIT)forerrorsetcommandsandfullsystem display status.

SYSTEM MONITORINGThe PowerSkid™ provides full system status information including AC output real & reactive power, AC output voltage & frequency, DC battery voltage and DC current readings to the remote operator through feedback signals or through the communication link (via an RTU or PLC). The PowerSkid™ has an on-board monitoring and diagnostics of all subsystems, including cooling, control, safety, interlocks, etc with error history and grid fault data capture. System operating informationisaccessibleontheOITbothlocallyandremotelythrough the communication port.

Visit our Website for additional information

T: 802 860 7200

Dynapower Corporate Headquarters - South Burlington, Vermont

4.5 MVA PowerSkid™ System with Integrated ULTRACAST™ Cast Coil Transformer, System Cooling, Controls and a Full Complement of AC & DC Switchgear

Contact Our Battery Application Engineering Group