SWIMMING POOL HEAT PUMP UNIT

Installation & Instruction Manual

Page 2: powerpack user … · Web view8. Make sure that there is circuit breaker for the unit, lack of circuit breaker can lead to electrical shock or fire. 9. The heat pump located inside
Page 3: powerpack user … · Web view8. Make sure that there is circuit breaker for the unit, lack of circuit breaker can lead to electrical shock or fire. 9. The heat pump located inside

CONTENTS1. Preface

2. Specifications

2.1 Performance Data of Swimming Pool Heat Pump Unit

2.2 Dimensions for Swimming Pool Heat Pump Unit

3. Installation and Connection

3.1 Installation of System

3.2 Swimming Pool Heat Pumps Location

3.3 How Close to Your Pool?

3.4 Swimming Pool Heat Pumps Plumbing

3.5 Swimming Pool Heat Pumps Electrical Wiring

3.6 Initial Start-up of the Unit

4. Usage and Operation

4.1 Parameter table

4.2 The Functions of the LED Controller

4.3 How to Set Operation Parameter

4.4 How To Choose Mode

4.5 How to know the Current Status

5. Maintenance and Inspection

5.1 Maintenance

5.2 Trouble Shooting Guide

6. Appendix

6.1 Connection of PCB Illustration

6.2 Connections Explanation

6.3 Caution & Warning

6.4 Cable specification

1

2

2

3

4

4

5

5

6

7

7

8

8

9

9

10

11

12

12

12

13

13

13

14

15

Page 4: powerpack user … · Web view8. Make sure that there is circuit breaker for the unit, lack of circuit breaker can lead to electrical shock or fire. 9. The heat pump located inside

1. PREFACE

In order to provide our customers with quality, reliability and versatility, this product hasbeen made to strict production standards. This manual includes all the necessaryinformation about installation, debugging, discharging and maintenance. Please read thismanual carefully before you open or maintain the unit. The manufacture of this product willnot be held responsible if someone is injured or the unit is damaged, as a result of improperinstallation, debugging, or unnecessary maintenance. It is vital that the instructions withinthis manual are adhered to at all times. The unit must be installed by qualified personnel.

The unit can only be repaired by qualified installer centre , personnel or an authoriseddealer.

Maintenance and operation must be carried out according to the recommended time andfrequency, as stated in this manual.

Use genuine standard spare parts only.Failure to comply with these recommendations will invalidate the warranty.

Swimming Pool Heat Pump Unit heats the swimming pool water and keeps the temperatureconstant. For split type unit, The indoor unit can be Discretely hidden or semi-hidden tosuit a luxury house.

Our heat pump has following characteristics:

1 DurableThe heat exchanger is made of PVC & Copper Nickle tube which can withstand

prolonged exposure to swimming pool water.2 Installation flexibility

The unit can be installed outdoors or indoors.3 Quiet operation

The unit comprises an efficient rotary/ scroll compressor and a low-noise fan motor,which guarantees its quiet operation.4 Advanced controlling

The unit includes micro-computer controlling, allowing all operation parameters to beset. Operation status can be displayed on the LED wire controller. Remote controller can bechosen as future option.

1

Page 5: powerpack user … · Web view8. Make sure that there is circuit breaker for the unit, lack of circuit breaker can lead to electrical shock or fire. 9. The heat pump located inside

UNIT Model PASRW015 PASRW020Heating Capacity kW 6.8 9.2

Btu/h 23200 31400Heating Power Input kW 1.15 1.65Running Current A 5.23 7.50Power Supply 230V /50Hz 230V /50Hz

Compressor Quantity 1 1Compressor Rotary Rotary

Fan Quantity 1 1Fan Power Input W 120 120Fan Rotate Speed RPM 850 850Fan Direction Horizontal HorizontalNoise dB(A) 47 51Water Connection mm 50 50Water Flow Volume 3

m /h 2.2 3.0Water Pressure Drop (max) kPa 8 10Unit Net Dimensions (L/W/H) mm See the drawing of the unitsUnite Shipping Dimensions (L/W/H) mm See package labelNet Weight/Shipping Weight kg See nameplate/See package label

2.SPECIFICATION

2.1 Performance data of Swimming Pool Heat Pump Unit

*** REFRIGERANT : R410A

2

Page 6: powerpack user … · Web view8. Make sure that there is circuit breaker for the unit, lack of circuit breaker can lead to electrical shock or fire. 9. The heat pump located inside

TYPESIZE

PASRW015/020

A 650B 1005C 590D 405E 340

2.SPECIFICATION

2.2 The dimensions for Swimming Pool Heat Pump Unit

Models PASRW015/020unit mm

Water Inlet

AWater Outlet

Drainage

Horizontal vision

D E

CB

Vertical vision

3

Page 7: powerpack user … · Web view8. Make sure that there is circuit breaker for the unit, lack of circuit breaker can lead to electrical shock or fire. 9. The heat pump located inside

3.INSTALLATION AND CONNECTION

3.1 Installation illustration

Chlorinator cell

Water inlet Sand filter

Water outlet

Water pump

Pool

Valve

Water supply

(or other type filter)

Installation items:

The factory only provides the main unit and the water unit; the other items in the illustrationare necessary spare parts for the water system ,that provided by users or the installer.

Attention:

Please follow these steps when using for the first time1.Open valve and charge water.2.Make sure that the pump and the water-in pipe have been filled with water.3.Close the valve and start the unit.ATTN: It is necessary that the water-in pipe is higher than the pool surface.

4

Page 8: powerpack user … · Web view8. Make sure that there is circuit breaker for the unit, lack of circuit breaker can lead to electrical shock or fire. 9. The heat pump located inside

500m

2000

mm

3.INSTALLATION AND CONNECTION

3.2 Swimming Pool Heat Pumps Location

The unit will perform well in any outdoor location provided that the following three factors are

presented:

1. Fresh Air - 2. Electricity - 3. Pool filter piping

The unit may be installed virtually anywhere outdoors. For indoor pools please consult the

supplier. Unlike a gas heater, it has no draft or pilot light problem in a windy area.

DO NOT place the unit in an enclosed area with a limited air volume, where the units

discharge air will be re-circulated.DO NOT place the unit to shrubs which can block air inlet. These locations deny the unit of acontinuous source of fresh air which reduces it efficiency and may prevent adequate heatdelivery.

Air inlet

Air outlet

700m m

3 00

mm800mm

1000mm

Air outlet

2500m

m

700m m

Air inlet

3.3 How Close To Your Pool?

Normally, the pool heat pump is installed within 7.5 metres of the pool. The longer thedistance from the pool, the greater the heat loss from the piping. For the most part ,the pipingis buried. Therefore, the heat loss is minimal for runs of up to15 meters(15 meters to and fromthe pump = 30 meters total), unless the ground is wet or the water table is high. A very roughestimate of heat loss per 30 meters is 0.6 kW-hour,(2000BTU) for every 5 difference intemperature between the pool water and the ground surrounding the pipe, which translates toabout 3% to 5% increase in run time.

5

Page 9: powerpack user … · Web view8. Make sure that there is circuit breaker for the unit, lack of circuit breaker can lead to electrical shock or fire. 9. The heat pump located inside

3.INSTALLATION AND CONNECTION

3.4 Swimming Pool Heat Pumps PlumbingThe Swimming Pool Heat Pumps exclusive rated flow titanium heat exchanger requires no

special plumbing arrangements except bypass(please set the flow rate according to thenameplate). The water pressure drop is less than 10kPa at max. Flow rate. Since there is noresidual heat or flame Temperatures, The unit does not need copper heat sink piping. PVCpipe can be run straight into the unit.

Location: Connect the unit in the pool pump discharge (return) line downstream of all filterand pool pumps, and upstream of any chlorinators, ozonators or chemical pumps.

Standard model have slip glue fittings which accept 32mm or 50 mm PVC pipe forconnection to the pool or spa filtration piping. By using a 50 NB to 40NB you can plumb 40NB

Give serious consideration to adding a quick coupler fitting at the unit inlet and outlet to alloweasy draining of unit for winterizing and to provide easier access should servicing berequired.

From pump

PVC COUPLERRECOMMENDED(Provided)

To pool

CONDENSATIONDRAINBARB FTG

Condensation: Since the Heat pump cools down the air about 4 -5 , water may condense onthe fins of the horseshoe shaped evaporator. If the relative humidity is very high, this couldbe as much as several litres an hour. The water will run down the fins into the basepan anddrain out through the barbed plastic condensation drain fitting on the side of the basepan.This fitting is designed to accept 20mm clear vinyl tubing which can be pushed on by handand run to a suitable drain. It is easy to mistake the condensation for a water leak inside theunit.

NB: A quick way to verify that the water is condensation is to shut off the unit and keep thepool pump running. If the water stops running out of the basepan, it is condensation. ANEVEN QUICKER WAY IS to TEST THE DRAIN WATER FOR CHLORINE - if the is no chlorinepresent, then it's condensation.

6

Page 10: powerpack user … · Web view8. Make sure that there is circuit breaker for the unit, lack of circuit breaker can lead to electrical shock or fire. 9. The heat pump located inside

3.INSTALLATION AND CONNECTION

3.5 Swimming Pool Heat Pumps Electrical Wiring

NOTE: Although the unit heat exchanger is electrically isolated from the rest of the unit, it

simply prevents the flow of electricity to or from the pool water. Grounding the unit is stillrequired to protect you against short circuits inside the unit. Bonding is also required.

The unit has a separate molded-in junction box with a standard electrical conduit nipple

already in place. Just remove the screws and the front panel, feed your supply lines inthrough the conduit nipple and wire-nut the electric supply wires to the three connectionsalready in the junction box (four connections if three phase). To complete electrical hookup,connect Heat Pump by electrical conduit, UF cable or other suitable means as specified (aspermitted by local electrical authorities) to a dedicated AC power supply branch circuitequipped with the proper circuit breaker, disconnect or time delay fuse protection.

Disconnect - A disconnect means (circuit breaker , fused or un-fused switch) should belocated within sight of and readily accessible from the unit, This is common practice oncommercial and residential air conditioners and heat pumps. It prevents remotely-energizingunattended equipment and permits turning off power at the unit while the unit is beingserviced.

3.6 Initial startup of the Unit

NOTE- In order for the unit to heat the pool or spa, the filter pump must be running to

circulate water through the heat exchanger.

Start up Procedure - After installation is completed, you should follow these steps:1. Turn on your filter pump. Check for water leaks and verify flow to and from the pool.2. Turn on the electrical power supply to the unit, then press the key ON/OFF of wirecontroller, It should start in several seconds.3. After running a few minutes make sure the air leaving the top(side) of the unit iscooler(Between 5-10 )4. With the unit operating turn the filter pump off. The unit should also turn off automatically,5. Allow the unit and pool pump to run 24 hours per day until desired pool water emperature isreached. When the water-in temperature reach setting, The unit just shuts off. The unit willnow automatically restart (as long as your pool pump is running)when the pool temperaturedrops more than 2 below set temperature.

Time Delay- The unit is equipped with a 3 minute built-in solid state restart delay included toprotect control circuit components and to eliminate restart cycling and contactor chatter. Thistime delay will automatically restart the unit approximately 3 minutes after each controlcircuit interruption. Even a brief power interruption will activate the solid state 3 minuterestart delay and prevent the unit from starting until the 5 minute countdown is completed.Power interruptions during the delay period will have no effect on the 3 minute countdown.

7

Page 11: powerpack user … · Web view8. Make sure that there is circuit breaker for the unit, lack of circuit breaker can lead to electrical shock or fire. 9. The heat pump located inside

Digit meaning default Adjust(yes/no)

0 Return water temp.Setting(cooling mode)

27 yes

1 Return water temp.Setting(heating mode)

27 yes

2 Turnround of dehumidifyingunder heating mode frost

45MIN yes

3 Defrosting start temperature -7 yes

4Terms of exit defrostunder heating model

13 yes

5 time of exit defrostunder heating mode

8MIN yes

6 Electric-valve adjust 1 yes

7 Automatic restarting 0 yes

8 Model(cooling only/heat pump/auxiliary electrical heating/hot water

3 yes

9 Water pump model 0 yes

10 Fan mode 1 yes

11 Target over-heat degree / disable

12 Electric-expansive valveinitialization

/ disable

13 Fan type 1 yes

4. USAGE AND OPERATION4.1 Parameter table

*Remark:Parameter 07:

01

the unit can not restart automaticallythe unit can restart automatically

Parameter 08:

0123

the mode of the unit is cooling onlythe mode of the unit is heat pumpthe mode of the unit is auxiliary electrical heating;the mode of the unit is heating only.

Parameter 09:0: always open.1: 60 seconds start before compressors starting.

30 seconds stop after compressors stopping.Parameter10:

01

low fan speedhigh fan speed

2

34

automatic fan speed(high speed when air temperature is below 10when air temperature is above 15

);low fan speed during 9PM~8AM,high speed at other time;automatic running according to above condition 2and 3.

8

,low speed

Page 12: powerpack user … · Web view8. Make sure that there is circuit breaker for the unit, lack of circuit breaker can lead to electrical shock or fire. 9. The heat pump located inside

but data can t be changed.

Parameter 0parameter 1

to parameter 01waterset the entering compressor after frosting

3MODE

parameter 01parameter 4 parameter 015parameter

CLOCK TIMER ON 13 OFF TIMER CLOCK TIMER ON TIMER OFF

HEAT

4. USAGE AND OPERATION4.2 The Functions of the LED Controller

LED srceen

DEFROSTPress to set and checkthe operation data.

HEATCOOL

CLOCK TIMER ON TIMER OFF

MODE Press` MODE` to change therunning mode

Press to turn on andturn off the units.

Press `CLOCK` to setthe time Press the key to setthe

time to turn on theunitPress the key to setthetime to turn off theunit

4.3 How to set operation parameterStandby status-presssetting interface.

button to enter operation parameter

Under parameter setting, pressparameter from 00-12,

or to select data for

Press MODE to start setting(parameter from 00-12, seeOperation Parameter Table).No press in 5s, the LED will display water-in/water-out temp-erature(under running)or current time (unit stops).Whilst running, you can press

,to check current parameter,

DEF RO STHEAT

to set the entering water COOLtemp. under cooling modedefault setting: 27

CLOCK TIMER ON TIMER OFF

MODEDEFROSTHEAT

COOL

temp. under heating modedefault setting:27

CLOCK TIMER ON TIMER OFF

MODEparameter 2 EHEAT

Total working time of HEAT MODECOOL

CLOCK TIMER ON TIMER OFF

parameterEHEAT

Terms of Entry DefrostingFunction COOLdefault setting: -7

CLOCK TIMER ON TIMER OFF

DEFROSTHEAT

COOL

Terms of Exit DefrostingFunctiondefault setting:

MODEDEFROSTHEAT

COOL

Max. Time of defrosting

Default setting: 8min.

MODE

9

Page 13: powerpack user … · Web view8. Make sure that there is circuit breaker for the unit, lack of circuit breaker can lead to electrical shock or fire. 9. The heat pump located inside

Mode: 0(cooling only)1(cooling&heating)2(auxiliary elec.heating)

CLOCK TIMER ON TIMER OFF

Pump: 0 (always open)

compressors starting.30seconds stop after compressors

initialization

4. USAGE AND OPERATION

parameter 01parameter 6

DEFROSTHEAT

COOLMODE

parameter 7Can save settingafter power off or not1 (yes) 0 (No)

D EF R OS THEAT

COOLMODE

Parameter 8

3(heating only)

DEFROSTHEAT

COOLMODE

Electric-valve adjust CLOCK TIMER ON TIMER OFF CLOCK TIMER ON TIMER OFF

parameter 9 Parameter 10 Parameter 11

1 (60 seconds start before EHEATHEAT

COOLMODE

Can select fan modeDEFROST

HEATCOOL

MODEtarget over heat degree

DEFROSTHEAT

COOLMODE

stopping)

CLOCK TIMER ON TIMER OFF

Parameter12

Electric-expansive valveDEFROST

HEATCOOL

MODE

CLOCK TIMER ON TIMER OFF CLOCK TIMER ON TIMER OFF

CLOCK TIMER ON TIMER OFF

4.4 How to choose Mode

Heating mode Defrost Show

DEFROST

HEATCOOL

Cooling mode

MODEDEFROST

HEATCOOL

MODEDEFROST

HEATCOOL

MODE

CLOCK TIMER ON TIMER OFF CLOCK TIMER ON TIMER OFF CLOCK TIMER ON TIMER OFF

Press MODE to choose mode(mode can be changed under running)Press to power on unit. Under running, the LED displays the water-intemp, water-out temp and current mode.Elec. Heating -NOT APPLICABLE FOR THESE MODELS.

10

Page 14: powerpack user … · Web view8. Make sure that there is circuit breaker for the unit, lack of circuit breaker can lead to electrical shock or fire. 9. The heat pump located inside

4. USAGE AND OPERATION4.5 How to know the current status?

Water temp.Of inlet

Water temp.Of outlet

Evaperater temp.

DEFROSTHEAT

COOLMODE

DEFROSTHEAT

COOLMODE

DEFROSTHEAT

COOLMODE

CLOCK TIMER ON TIMER OFF

Condenser temp.

CLOCK TIMER ON TIMER OFF

Ambient temp.

CLOCK TIMER ON TIMER OFF

DEFROSTHEAT

COOL

CLOCK TIMER ON TIMER OFF

MODEDEFROST

HEATCOOL

CLOCK TIMER ON TIMER OFF

MODE

11

Page 15: powerpack user … · Web view8. Make sure that there is circuit breaker for the unit, lack of circuit breaker can lead to electrical shock or fire. 9. The heat pump located inside

5. MAINTENANCE AND INSPECTION

5.1 MaintenanceCheck the water supply device and the release often. You should avoid the condition of no water or air enteringinto system, as this will influence unit's performance and reliability. You should clear the pool/spa filter regularlyto avoid damage to the unit as a result of the dirty of clogged filter.The area around the unit should be dry, clean and well ventilated. Clean the side heating exchangerregularly to maintain good heat exchange as conserve energy .

The operation pressure of the refrigerant system should only be serviced by a certified technician .

Check the power supply and cable connection often,.Should the unit begin to operate abnormally,switch it off and contact your certified Pollrite technician.Discharge all water in the water pump and water system ,so that freezing of the water in the pump or watersystem does not occur. You should discharge the water at the bottom of water pump if the unit will not beused for an extended period of time. You should check the unit thoroughly and fill the system with waterfully before using it for the first time after a prolonged period of no usage.

5.2 Trouble Shooting Guide

Malfunction

Water inlet temp.Sensor failure

Water outlet temp.Sensor failure

Coil1 sensor1failureCoil2 sensor2failure

Ambient sensor failure

Temp. differential betweenwater-in and water-outis too large

Anti freezingunder cooling mode

The first time freezingprotection in winter

The second time freezingprotection in winter

LEDController

PP1

PP2

PP3

PP4

PP5

PP6

PP7

PP7

PP7

Reason

The sensor is openor short circuit

The sensor is openor short circuit

The sensor is openor short circuitThe sensor is openor short circuitThe sensor is openor short circuitWater flow volume notenough,water pressuredifference is too low

Outlet water is too low

Ambient or inlet watertemp. is too low

Ambient or inlet watertemp. is too lower

Resolution

Check or change the sensor

Check or change the sensor

Check or change the sensor

Check or change the sensor

Check or change the sensor

Check the water flow volume,or system obstruction.

Check the water flow volumeor outlet water temp. sensor

High pressure protect

Low pressure protect

EE1

EE2

Too much refrigerant orpoor heat spread

Refrigerate not sufficient,the

filter or the capillary locked

1

2

1

2

To discharge the over-refrigerant

To clean the heating spreader and improvethe condensing device

To check the system's leakage and fillof refrigerantTo change the capillary or filter

Flow switch failure

3times water-in andwater-out temp.differece

EE3

EE5

No water/little waterin water system.

Water flow rate notenough

Check the water flow volume,water pump is failure or not

Check the water flow rate, orwater system is jammed or not

protectionin 30 minutes

Defrosting Defrost Code Display

Communication failure EE8 LED controller and ThePCB connection failure

Check the wire connection

12

Page 16: powerpack user … · Web view8. Make sure that there is circuit breaker for the unit, lack of circuit breaker can lead to electrical shock or fire. 9. The heat pump located inside

No. symbol meaning

K1 COMP Compressor 220-230VAC

K4 PUMP Water pump 220-230VAC

K3 FAN Fan motor 220-230VAC

K2 4VAL 4way valve 220-230VAC

L AC-L Live wire

12V ~12V,~12V Control power input

1,2,3 GND 12V NET Wire controller

4 INTWT Water in temp.(input)

5 OUTWT Water out temp.(input)

6 PIPE Temp. Of coil1( input)

7 EVAP. Temp. Of coil1( input)

8 EXT. External temp.(input)

9,10 GND KYIN On/Off Switch(input)(no use)

11 MDIN Model(input)(no use)

12 WATER Flow switch (input)( normal close)

13 HP High pressure protect (input)

14,15 LP GND Low pressure protect (input)

FAN2

4VAL

OUWT

INWT

WATER

EVAP.

MDIN

~12V

~12V

+12V

KYIN

PIPE

GND

GND

GND

EXT.

NET

HP

LP

PUMP

COMP

FAN1

AC-L

6. APPENDIX

6.1 Connection of PCB illustration

PC2000

6.2 Connections explanation

13

Page 17: powerpack user … · Web view8. Make sure that there is circuit breaker for the unit, lack of circuit breaker can lead to electrical shock or fire. 9. The heat pump located inside

6. APPENDIX

6.3 Caution & Warning1. The unit can only be repaired by qualified installer centre personnel or an authorised

dealer. for Europe market2. This appliance is not intended for use by persons (including children) with reduced physical

sensory or mental capabilities, or lack of experience and knowledge, unless they have beengiven supervision or instruction concerning use of the appliance by a person responsible fortheir safety. for Europe marketChildren should be supervised to ensure that they do not play with the appliance.

3. Please make sure that the unit and power connection have good earthing, otherwise maycause electrical shock.

4. If the supply cord is damaged, it must be replaced by the manufacturer or our service agentor similarly qualified person in order to avoid a hazard.

5. Directive 2002/96/EC (WEEE):The symbol depicting a crossed-out waste bin that is underneath the appliance indicatesthat this product, at the end of its useful life, must be handled separately from domesticwaste, must be taken to a recycling centre for electric and electronic devices or handedback to the dealer when purchasing an equivalent appliance.

6. Directive 2002/95/EC (RoHs): This product is compliant with directive 2002/95/EC (RoHs)concerning restrictions for the use of harmful substances in electric and electronic devices.

7. The unit CANNOT be installed near the flammable gas. Once there is any leakage of the gas, fire can be occur.

8. Make sure that there is circuit breaker for the unit, lack of circuit breaker can lead toelectrical shock or fire.

9. The heat pump located inside the unit is equipped with an over-load protection system. Itdoes not allow for the unit to start for at least 3 minutes from a previous stoppage.

10. The unit can only be repaired by the qualified personnel of an installer center or anauthorized dealer. for North America market

11. Installation must be performed in accordance with the NEC/CEC by authorized person only.for North America market

12. USE SUPPLY WIRES SUITABLE FOR 75 .13. Caution: Single wall heat exchanger, not suitable for potable water connection.

14

Page 18: powerpack user … · Web view8. Make sure that there is circuit breaker for the unit, lack of circuit breaker can lead to electrical shock or fire. 9. The heat pump located inside

Nameplatemaximumcurrent

Phase line Neutral line Earth line MCB Creepage protector Signal line

No morethan 13A 2

3¡Á1.5mm2

1.5mm2

1.5mm 20A 30mA less than 0.1 sec

2n¡Á0.5mm

13~25A 23¡Á4mm 24mm 24mm 40A 30mA less than 0.1 sec

25~30A 23¡Á6mm24mm 26mm 40A 30mA less than 0.1 sec

30~40A 23¡Á10mm24mm 210mm 63A 30mA less than 0.1 sec

40~55A 23¡Á16mm24mm 216mm 80A 30mA less than 0.1 sec

55~70A 23¡Á25mm24mm 225mm 100A 30mA less than 0.1 sec

Nameplatemaximumcurrent

Phase line Earth line MCB Creepage protector Signal line

No morethan 13A 2

2¡Á1.5mm2

1.5mm 20A 30mA less than 0.1 sec

2n¡Á0.5mm

13~25A 22¡Á4mm 24mm 40A 30mA less than 0.1 sec

25~30A 22¡Á6mm26mm 40A 30mA less than 0.1 sec

30~40A 22¡Á10mm 10 2mm 63A 30mA less than 0.1 sec

40~55A 22¡Á16mm216 mm 80A 30mA less than 0.1 sec

55~70A 22¡Á25mm225 mm 100A 30mA less than 0.1 sec

6. APPENDIX

6.4 Cable specification1. Single phase unit

2. Three phase unit

When the unit will be installed at outdoor, please use the cable which can against UV.

15