Page 1: POWER SYSTEM ANALYSIS TADP 641

POWER SYSTEM ANALYSIS

TADP 641

Case Example

SHORT CIRCUIT

CALCULATION

Juan Manuel Gers, PhD

Page 2: POWER SYSTEM ANALYSIS TADP 641

Example

Page 3: POWER SYSTEM ANALYSIS TADP 641

Example

Calculate the short circuit current for a three phase fault at busbar D.

Consider that the Hydro Power Station is under maintenance and therefore all the breakers associated are open.

Let base MVA = 75 MVA

Let base kV on 132 kV nominal part of system = 132 kV

The base kV on other parts of the system is obtained by referring this voltage through the interconnecting transformers.

Page 4: POWER SYSTEM ANALYSIS TADP 641

Example Solution

SUPPLYGRID

G3

G4

G5

G6

E'

T9

T10

T17

T18

T16

T15

E

D6

T20

T21

T13T11

D4B

D4A

T12

F'

F

D5

DT7

T8

D'

D2

C C'

Page 5: POWER SYSTEM ANALYSIS TADP 641

Positive Secuence Diagram for Fault at Busbar D

NEUTRAL BUS ' N '

E

G6

G5

G4

G3

T18

T17

T16

T15

FI

F

D5

D4B

D4A

D6

E

T10

T9

E'

SZ

D

Page 6: POWER SYSTEM ANALYSIS TADP 641

Positive Sequence Network

P.U.1E

FI

EE'

Z

F

E

I

AZ

D

ZB

FI

E

A

D

ZC

Page 7: POWER SYSTEM ANALYSIS TADP 641

Equivalent Impedances

The resulting positive sequence diagram is shown below:

..0712.04

285.0

4

151.0134.0upZ A

..0897.00327.0047.001.01768.0

1335.00433.0

2

094.001.0 up

xZ B

..0397.01607.0

0897.00712.0upZC

..19.250397.0

1up

Z

EI

c

F

Axx

xupcurrentBase 328

101323

1075.).1(

3

6

Page 8: POWER SYSTEM ANALYSIS TADP 641

Fault Current Calculation

Page 9: POWER SYSTEM ANALYSIS TADP 641

Solution of Example with Software

Page 10: POWER SYSTEM ANALYSIS TADP 641