Power Plus High Efficiency Condensing Boilers

BERETTA POWER PLUS INTELLIGENT DESIGN

Stand alone

and cascade

installations

(from 50 to

400 kW)

for light

commercial

heating

solutions

Page 2: Power Plus High Efficiency Condensing Boilers€¦ · - Kit for conversion from natural gas to LPG - Assembly template. b The Installation and operation manual is an integral part

Maximum efficiency...

Beretta Power Plus has been designed specifically for cascade applications. By automatically controlling the number of boilers in operation, the system can optimise the heat supply according to demand at any particular time. For instance in spring and autumn when the heat request is lower, or in buildings such as hotels and restaurants where the heat request is not constant, the system can switch on and off individual boilers thereby ensuring maximum efficiency.

Power Plus cascade installations can be tailored to meet the space requirements of the customer. There are three different configuration possibilities for the cascade, wallhung installation, free standing side by side installation or free standing back to back installation. Thanks to its modular nature the cascade system offers a versatile solution for large domestic or light commercial buildings.

Maximum flexibility...

Warranty Guide2 years parts and labour, 5 years heat exchanger

TYPICAL INSTALLATIONS

UK Sales, General Enquiries: 0844 391 0999 Vokèra Ireland: 056 7755057 [email protected] www.vokera.co.uk www.vokera.ie

CONDEXAPROLight commercial wall hung boiler

50 kW1 CondexaPRO 50M

100 kW1 CondexaPRO 100M

150 kW1 CondexaPRO 50M1 CondexaPRO 100S

200 kW1 CondexaPRO 100M1 CondexaPRO 100S

250 kW1 CondexaPRO 50M2 CondexaPRO 100S

300 kW1 CondexaPRO 100M2 CondexaPRO 100S

350 kW1 CondexaPRO 50M3 CondexaPRO 100S

400 kW1 CondexaPRO 100M3 CondexaPRO 100S

Typical installations

CondexaPRO50M

CondexaPRO100MSPECIFICATIONS CondexaPRO

100SHeat output at 80/60˚C 44.2 kW 88.3 kW 88.3 kWHeat output at 50/30˚C 48.5 kW 96.8 kW 96.8 kWFlow rate at 20˚C 33.0 l/min 66.7 l/min 66.7 l/minWaterside pressure

drop at 20˚C 700 mbar 700 mbar 700mbarMaximum water pressure 6.0 bar 6.0 bar 6.0 barMinimum water pressure 0.5 bar 0.5 bar 0.5 barMaximum water

temperature (flow) 80˚C 80˚C 80˚CFlue connection 1 x 50mm 2 x 50mm 2 x 50mmPower supply 230v 1PH 230v 1PH 230v 1PH

50Hz 50Hz 50HzStart current 0.8A 1.6A 1.6ARun current 0.74A 1.45A 1.45AWidth 600mm 600mm 600mmDepth 380mm 380mm 380mmHeight 1000mm 1000mm 1000mmDry weight 60kg 90kg 90kg

CONDEXAPRO 100M

M=Master Unit S=Slave Unit

UK Sales, General Enquiries: 0844 391 0999 Vokèra Ireland: 056 7755057 [email protected] www.vokera.co.uk www.vokera.ie

CONDEXAPROLight commercial wall hung boiler

50 kW1 CondexaPRO 50M

100 kW1 CondexaPRO 100M

150 kW1 CondexaPRO 50M1 CondexaPRO 100S

200 kW1 CondexaPRO 100M1 CondexaPRO 100S

250 kW1 CondexaPRO 50M2 CondexaPRO 100S

300 kW1 CondexaPRO 100M2 CondexaPRO 100S

350 kW1 CondexaPRO 50M3 CondexaPRO 100S

400 kW1 CondexaPRO 100M3 CondexaPRO 100S

Typical installations

CondexaPRO50M

CondexaPRO100MSPECIFICATIONS CondexaPRO

100SHeat output at 80/60˚C 44.2 kW 88.3 kW 88.3 kWHeat output at 50/30˚C 48.5 kW 96.8 kW 96.8 kWFlow rate at 20˚C 33.0 l/min 66.7 l/min 66.7 l/minWaterside pressure

drop at 20˚C 700 mbar 700 mbar 700mbarMaximum water pressure 6.0 bar 6.0 bar 6.0 barMinimum water pressure 0.5 bar 0.5 bar 0.5 barMaximum water

temperature (flow) 80˚C 80˚C 80˚CFlue connection 1 x 50mm 2 x 50mm 2 x 50mmPower supply 230v 1PH 230v 1PH 230v 1PH

50Hz 50Hz 50HzStart current 0.8A 1.6A 1.6ARun current 0.74A 1.45A 1.45AWidth 600mm 600mm 600mmDepth 380mm 380mm 380mmHeight 1000mm 1000mm 1000mmDry weight 60kg 90kg 90kg

CONDEXAPRO 100M

M=Master Unit S=Slave Unit

Power Plus

Power Plus

1 Power Plus1 Power Plus

1 Power Plus1 Power Plus

1 Power Plus2 Power Plus

1 Power Plus2 Power Plus

1 Power Plus3 Power Plus

1 Power Plus3 Power Plus

Pre-mix combustion group, consisting of a modulating gas valve integrated with a high total head fan, guaranteeing the system a constant calibrated gas and air mix, thereby ensuring the highest efficiency under any running conditions.

High efficiency 50 kW heat exchanger consisting of a continuous bimetal corrugated helical tube (copper on the water side and AISI 316 stainless steel on the flue side). The micro flame steel burner is located in the upper part of the heat exchanger with single spark ignition.

The Master/Slave control system is located behind the front panel. It is made up of a master board that manages one or more slave boards (according to the number of slave boilers in the installation). The master board, besides allowing the cascade installation of more slave boilers, can also manage the following:

A high temperature circuit.A low temperature circuit.A DHW tank.The temperature control function and the remote control panel.

A Power Plus module can contain one or two 50 kW boiler units, connected to the water and gas system in parallel. Each unit is made up as follows:

The architecture of Power Plus

2

Page 3: Power Plus High Efficiency Condensing Boilers€¦ · - Kit for conversion from natural gas to LPG - Assembly template. b The Installation and operation manual is an integral part

PERFORMANCE DATAMaximum flexibility...

the powerto changefor thebetter

The architecture of Power Plus

Power Plus

naturally better

Data UnitPower Plus

50Power Plus

100MPower Plus

100S

Max. heating capacity HHV KW 50 100 100 (Q)

Min. heating capacity HHV KW 16.3 16.3 16.3 (Q)

Max. heat output in heating (80/60°C) KW 44.2 88.3 88.3 (P)

Min. heat output in heating (80/60°C) KW 14.8 14.8 14.8 (P)

Max. heat output in heating (50/30°C) KW 48.8 96.8 96.8

Min. heat output in heating (50/30°C) KW 16.3 16.3 16.3

Efficiency ref. NHV (80/60°C) % 98.2

Efficiency at 30% ref. NHV (80/60°C) % 98.7

Efficiency ref. NHV (50/30°C) % 107.7

Efficiency at 30% ref. NHV (50/30°C) % 108.7

CO2 at minimum - maximum NG % 9,0 - 9,0

CO2 at minimum - maximum ULPG % 10,4 - 10,4

Gas supply pressure NG KPa 1.13

Max. gas comsumption NG Mj/h 179.9 278.96 359.85

Min. gas delivery NG Mj/h 57.4 57.4 57.4

Gas supply pressure ULPG KPa 2.75

Max. gas delivery ULPG G30 Mj/h 183.45 284.25 366.91

Min. gas delivery ULPG G30 Mj/h 58.46 58.46 58.46

Max. gas delivery ULPG G31 Mj/h 165.4 256.72 330.86

Min. gas delivery ULPG G31 Mj/h 52.82 52.82 52.82

NOx emission class - 5 Nm3/h

Max. working pressure in heating bar 6 (PMS)

Min. working pressure in heating bar 0.5

Range of boiler water temperature settings °C 20 - 80

Heating water content litres 5 10 10

Protection rating IP X0D

Power supply voltage V/Hz 230V/50Hz

Electrical power input W 80 160 160

Empty weight kg 60 90 90

Noise level at max/min heat output dBA 58 / 49 58 / 49 58 / 49

Heating water content litres 5.1

3

(**) Measurements taken at 1m from the appliance, at height of 1.5m with background noise of 36.5 dDB

+ _ 3 °C)(

G30 - G31 ULPG fuels

Page 4: Power Plus High Efficiency Condensing Boilers€¦ · - Kit for conversion from natural gas to LPG - Assembly template. b The Installation and operation manual is an integral part

BERETTA: THE SPECIALISTS IN HOME HEATING TECHNOLOGY

Melbourne: 03 9554 2275 Sydney: 02 9853 2100 Brisbane: 07 3308 5400 Gold Coast: 07 5552 2600

Townsville: 07 4750 3100 Adelaide: 08 8152 7600 Perth: 08 9350 2600

[email protected]

BERETTA FOCUS ON TECHNOLOGY

25

The Vokera CondexaPRO Boiler is supplied in a single package protected by a cardboard box.

The following material is supplied with the boiler:

- Installation and operation manual- Warranty certificate- Water pressure test certificate- Spare parts catalogue- Outside probe- Kit for conversion from natural gas to LPG- Assembly template.

b The Installation and operation manual is an integral part of the appliance and must be read and kept with care.

1

2

H

L P

W 600 mmD 380 mmH 1000 mmNet weight ~ 60 ~ 90 kgWeight with packaging ~ 65 ~ 95 kg

Description 50 M 100 M - 100 S

RECEIVING THE PRODUCT

DIMENSIONS AND WEIGHT

PowerP

lus

Vokera CondexaPROBeretta PowerPlus

25

The Vokera CondexaPRO Boiler is supplied in a single package protected by a cardboard box.

The following material is supplied with the boiler:

- Installation and operation manual- Warranty certificate- Water pressure test certificate- Spare parts catalogue- Outside probe- Kit for conversion from natural gas to LPG- Assembly template.

b The Installation and operation manual is an integral part of the appliance and must be read and kept with care.

1

2

H

L P

W 600 mmD 380 mmH 1000 mmNet weight ~ 60 ~ 90 kgWeight with packaging ~ 65 ~ 95 kg

Description 50 M 100 M - 100 S

RECEIVING THE PRODUCT

DIMENSIONS AND WEIGHT

PowerP

lus

Vokera CondexaPROBeretta PowerPlus

DIMENSIONS AND WEIGHT

V1051114

DW