107
Permit Fairview Municipal Building 55 Anderson Ave.Fairview,NJ Issue December 31,2015 20 00 00-1 VIBRATION ISOLATION, SEISMIC, WIND & FLOOD LOAD RESTRAINTS FOR HVAC, PLUMBING, ELECTRICAL & FIRE PROTECTION COMPONENTS 1 of 33 20 00 00 VIBRATION ISOLATION, SEISMIC, WIND & FLOOD LOAD RESTRAINTS FOR HVAC, PLUMBING, ELECTRICAL & FIRE PROTECTION COMPONENTS SECTION 1 – GENERAL This section specifies required vibration control and seismic restraints for all equipment, where applicable, with the wind load requirements for all equipment in outdoor locations. Additionally, included are provisions for flood control as stated herein. When projects are located in a geographically active seismic, wind or flood location, Section 1.4, General Design and Performance Requirements, will elaborate on those requirements and include specifics pertaining to a facility’s “continued operation.” Para. 1.1, Section C is a partial list of components covered herein. This specification is part of the general conditions for the HVAC, Plumbing, Electrical and Fire Protection contracts. 1.1 SUMMARY DESCRIPTION AND REQUIREMENTS A. This section includes the following: 1. All equipment, piping, ductwork and conduit as noted on the drawing’s schedule or in the specification shall be seismically braced if the building is so classified as listed herein. Vibration control shall apply as described in all cases herein. 2. All outdoor equipment, including roof-mounted components, shall comply with section 1609, Wind Load, IBC-2006. There shall be no decrease of the effects of wind load on a component due to other structures or components acting as blocks or screens. 3. All below, at grade or above grade locations located in a flood hazard area as defined and located herein. 4. Seismic bracing, wind, flood load and isolation materials shall be the certified products of the same manufacturing group and shall be certified by that group. 5. It is the intent of the seismic and wind load portion of this specification to keep all mechanical, electrical, plumbing and fire protection building system components in place during a seismic or high wind event and additionally operational where the occupancy category of the building so requires as listed herein. 6. All such systems must be installed in strict accordance with seismic/wind codes, component manufacturer’s and building construction standards. 7. This specification is considered to be minimum requirements for seismic, wind, flood and vibration control considerations. 8. Any variation, which results in non-compliance with the specification requirements, shall be corrected by the contractor in an approved manner. B. The work in this section includes, but is not limited to, the following: 1. Vibration isolation for piping, ductwork, bus duct, cable tray conduit and equipment, all

PLUMBING, ELECTRICAL & FIRE PROTECTION COMPONENTS … · mechanical, electrical, plumbing and fire protection building system components in place during a seismic or high wind event

  • Upload
    others

  • View
    4

  • Download
    0

Embed Size (px)

Citation preview

Page 1: PLUMBING, ELECTRICAL & FIRE PROTECTION COMPONENTS … · mechanical, electrical, plumbing and fire protection building system components in place during a seismic or high wind event

Permit Fairview Municipal Building 55 Anderson Ave.Fairview,NJ Issue December 31,2015

20 00 00-1 VIBRATION ISOLATION, SEISMIC, WIND & FLOOD LOAD RESTRAINTS FOR HVAC, PLUMBING, ELECTRICAL & FIRE PROTECTION COMPONENTS

1 of 33

20 00 00 VIBRATION ISOLATION, SEISMIC, WIND & FLOOD LOAD RESTRAINTS FOR HVAC, PLUMBING, ELECTRICAL & FIRE PROTECTION COMPONENTS

SECTION 1 – GENERAL This section specifies required vibration control and seismic restraints for all equipment, where applicable, with the wind load requirements for all equipment in outdoor locations. Additionally, included are provisions for flood control as stated herein. When projects are located in a geographically active seismic, wind or flood location, Section 1.4, General Design and Performance Requirements, will elaborate on those requirements and include specifics pertaining to a facility’s “continued operation.” Para. 1.1, Section C is a partial list of components covered herein. This specification is part of the general conditions for the HVAC, Plumbing, Electrical and Fire Protection contracts. 1.1 SUMMARY DESCRIPTION AND REQUIREMENTS

A. This section includes the following:

1. All equipment, piping, ductwork and conduit as noted on the drawing’s schedule or in the specification shall be seismically braced if the building is so classified as listed herein. Vibration control shall apply as described in all cases herein.

2. All outdoor equipment, including roof-mounted components, shall comply with section

1609, Wind Load, IBC-2006. There shall be no decrease of the effects of wind load on a component due to other structures or components acting as blocks or screens.

3. All below, at grade or above grade locations located in a flood hazard area as defined and

located herein.

4. Seismic bracing, wind, flood load and isolation materials shall be the certified products of the same manufacturing group and shall be certified by that group.

5. It is the intent of the seismic and wind load portion of this specification to keep all

mechanical, electrical, plumbing and fire protection building system components in place during a seismic or high wind event and additionally operational where the occupancy category of the building so requires as listed herein.

6. All such systems must be installed in strict accordance with seismic/wind codes,

component manufacturer’s and building construction standards.

7. This specification is considered to be minimum requirements for seismic, wind, flood and vibration control considerations.

8. Any variation, which results in non-compliance with the specification requirements, shall

be corrected by the contractor in an approved manner.

B. The work in this section includes, but is not limited to, the following:

1. Vibration isolation for piping, ductwork, bus duct, cable tray conduit and equipment, all

Page 2: PLUMBING, ELECTRICAL & FIRE PROTECTION COMPONENTS … · mechanical, electrical, plumbing and fire protection building system components in place during a seismic or high wind event

Permit Fairview Municipal Building 55 Anderson Ave.Fairview,NJ Issue December 31,2015

20 00 00-2 VIBRATION ISOLATION, SEISMIC, WIND & FLOOD LOAD RESTRAINTS FOR HVAC, PLUMBING, ELECTRICAL & FIRE PROTECTION COMPONENTS

2 of 33

referred to as components. 2. Component isolation bases. 3. Seismic restraints for isolated components. 4. Seismic restraints for non-isolated components. 5. Wind restraints for isolated components. 6. Wind restraints for non-isolated components. 7. Certification of seismic, wind or flood restraint designs. 8. Installation supervision. 9. Design of attachment of housekeeping pads. 10. All components requiring IBC compliance and certification. 11. All inspection and test procedures for components requiring IBC compliance.

C. All mechanical, electrical, plumbing or fire protection equipment, pipe and ductwork, within,

on or outdoors of the building. Entry of services to the building, up to but not including, the utility connection, is part of this Specification.

D. Components referred to below are typical. (Components not listed are still included in this

specification.) All systems that are part of the building in any way are referred to as components, including:

AC Units Adapter Curb Air Handling Units Boilers Bus Ducts Cabinet Unit Heaters Condensing Units Curbs Ductwork Electrical Panels Equipment Supports Fans (all types) Fan Coil Units

Fire Alarm Panels

Gas Detection Systems Generators Light Fixtures Pipe Pumps (all types) Risers Rooftop Units Supports Switch Gear Tanks (all types) Transformers Unit Heaters Vibration Isolators Water Heaters

1.2 RELATED DOCUMENTS

Drawings and general conditions of the contract, including General Supplementary Conditions and Division 1 Specification Section, apply to this section. In the event that this section conflicts with the isolation or seismic requirements of other sections, the more

Page 3: PLUMBING, ELECTRICAL & FIRE PROTECTION COMPONENTS … · mechanical, electrical, plumbing and fire protection building system components in place during a seismic or high wind event

Permit Fairview Municipal Building 55 Anderson Ave.Fairview,NJ Issue December 31,2015

20 00 00-3 VIBRATION ISOLATION, SEISMIC, WIND & FLOOD LOAD RESTRAINTS FOR HVAC, PLUMBING, ELECTRICAL & FIRE PROTECTION COMPONENTS

3 of 33

stringent criteria stated herein shall apply.

1.3 DEFINITIONS (building and components, all codes)

A. ESSENTIAL FACILITIES

1. Buildings and other structures that are intended to remain operational in the event of extreme environmental loading from flood, wind, snow or earthquakes.

B. LIFE SAFETY AND HIGH HAZARD

1. All systems involved with fire protection, including sprinkler piping, jockey pumps, fire

pumps, control panels, service water supply piping, water tanks, fire dampers, smoke exhaust systems and fire alarm panels. (Life Safety)

2. All mechanical, electrical, plumbing or fire protection systems that support the operation

of, or are connected to, emergency power equipment, including all lighting, generators, transfer switches and transformers. (Life Safety)

3. Automated supply, exhaust, fresh air and relief air systems on emergency control sequence,

including air handlers, duct, dampers, etc., or manually-operated systems used for smoke evacuation, purge or fresh air relief by the fire department. (Life Safety)

4. Heating systems in any facility in Seismic Use Group III, IBC-2000 or Occupancy

Category IV, IBC-2003-2006 where the ambient temperature can fall below 32 degrees Fahrenheit. (Life Safety)

C. GENERAL

Anchor: A device, such as an expansion bolt, for connecting equipment bracing members to the structure of a building. Approved Agency: An established and recognized agency regularly engaged in conducting tests or furnishing analytical or inspection services, when such agency has been approved. Attachment: See Positive Attachment below. Basic Wind Speed: The basic wind speed, in mph, for determination of the wind loads shall be as per Section 1609 (IBC-2006), or local code, if more severe. Local jurisdictions shall determine wind speeds for indicated special wind regions located near gorges or mountainous terrain. Section 6.5.4 of ASCE 7-05 shall be used after determination of basic wind speed by the local jurisdiction. See Section 1609.3 ASCE 7-05 for basic wind speed determination in non-hurricane prone regions. Bracing: Metal channels, cables or hanger angles that prevent components from breaking away from the structure during an earthquake or high winds. See also Longitudinal Bracing and Transverse Bracing. Together, they resist environmental loads from any direction. Certificate of Compliance: A certificate stating that materials and products meet specified

Page 4: PLUMBING, ELECTRICAL & FIRE PROTECTION COMPONENTS … · mechanical, electrical, plumbing and fire protection building system components in place during a seismic or high wind event

Permit Fairview Municipal Building 55 Anderson Ave.Fairview,NJ Issue December 31,2015

20 00 00-4 VIBRATION ISOLATION, SEISMIC, WIND & FLOOD LOAD RESTRAINTS FOR HVAC, PLUMBING, ELECTRICAL & FIRE PROTECTION COMPONENTS

4 of 33

standards or that work was done in compliance with approved construction documents, provided by an approved agency. (Certificate to be supplied by equipment component manufacturer.) Component: A non-structural part or element of an architectural, electrical, mechanical, plumbing or fire protection system within or without of a building system. Component Importance Factor: Factor applied to a component that defines the criticality of that component. This factor can be 1.0 or 1.5. Component, flexible: Component, including its attachments, having a fundamental period greater than 0.06 seconds. Component, rigid: Component, including its attachments, having a fundamental period less than or equal to 0.06 seconds. Consequential Damage: The functional and physical interrelationship of components, their supports and their effect on each other shall be considered so that the failure of an essential or non-essential architectural, mechanical or electrical component shall not cause the failure of an essential architectural, mechanical or electrical component. Equipment: Systems associated with ducts, pipes and conduits also called components. Flood or Flooding: A general and temporary condition or partial and complete inundation of normally dry land from:

1. The overflow of inland or tidal waters.

2. The unusual and rapid accumulation of runoff of surface waters from any source. Flood Hazard Area: The greater of the following of two areas:

1. The area within a flood plain subject to a 1 percent or greater chance of flooding in any year.

2. The area designated as a flood hazard area on a community’s flood hazard map, or otherwise legally designated.

Special Flood Hazard Area Subject to High Velocity Wave Action: Area within the flood hazard area that is subject to high velocity wave action and shown on a Flood Insurance Rate Map (FIRM) or other flood hazard map as zone V, VO, VE or VI-30. Flood Insurance Rate Map (FIRM): An official map of a community on which the Federal Emergency Management Agency (FEMA) has delineated both the special flood hazard areas and the risk premium zones applicable to the community. Gas pipes: For the purposes of this Specification Guide, gas pipe is any pipe that carries fuel, gas, fuel oil, medical gas, or compressed air. Hazardous Contents: A material that is highly toxic or potentially explosive or corrosive and in

Page 5: PLUMBING, ELECTRICAL & FIRE PROTECTION COMPONENTS … · mechanical, electrical, plumbing and fire protection building system components in place during a seismic or high wind event

Permit Fairview Municipal Building 55 Anderson Ave.Fairview,NJ Issue December 31,2015

20 00 00-5 VIBRATION ISOLATION, SEISMIC, WIND & FLOOD LOAD RESTRAINTS FOR HVAC, PLUMBING, ELECTRICAL & FIRE PROTECTION COMPONENTS

5 of 33

sufficient quantity to pose a significant life-safety threat to the general public if an uncontrolled release were to occur. Hurricane Prone Regions: Areas prone to hurricanes include the U.S. Atlantic Ocean, Gulf Coasts, Hawaii, Puerto Rico, Guam, Virgin Islands, and American Samoa where the wind speed is greater than 90 mph. Importance Factor, I: A factor that accounts for the degree of hazard to human life and damage to property. Inspection Certificate: An identification applied on a product by an approved agency containing the name of the manufacturer, the function and performance characteristics, and the name and identification of an approved agency that indicates that the product or material has been inspected and evaluated by an approved agency (see Section 1703.5 and “Label” and “Manufacturer’s Designation” and “Mark”). Label: An identification applied on a product by the manufacturer that contains the name of the manufacturer, the function and performance characteristics, and the name and identification of an approved agency that indicates that the representative sample of the product or material has been tested and evaluated by an approved agency (see Section 1703.5 and “Inspection Certificate,” “Manufacturer’s Designation” and “Mark”). Lateral forces: A force acting on a component in the horizontal plane. This force can be in any direction. Longitudinal bracing: Bracing that prevents a component from moving in the direction of its run. Longitudinal force: An applied force that happens to be in the same direction as the duct or pipe run. Mark: An identification applied on a product by the manufacturer indicating the name of the manufacturer and the function of a product or material (see also “Inspection Certificate,” “Label” and “Manufacturer’s Designation”). Manufacturer’s Designation: An identification applied on a product by the manufacturer indicating that a product or material complies with a specified standard or set of rules (see also “Inspection Certificate,” “Label” and “Mark”.) Occupancy Category: A classification used to determine structural load requirements including those imposed by wind, flood, snow and seismic based on occupancy of the structure. Positive Attachment: A mechanical device, designed to resist seismic forces, which connects a non-structural element, such as a duct, to a structural element, such as a beam. Bolts and welding are examples of positive attachments. Surface glue and friction anchorage do not constitute positive attachment. Examples of positive attachment are epoxy cast in anchors and drill in wedge shaped anchor bolts to concrete and welded or bolted connections directly to the building structure. Double-sided beam clamps, C type are not acceptable as either brace point attachments to the structure or for the support of the component at the bracing location.

Page 6: PLUMBING, ELECTRICAL & FIRE PROTECTION COMPONENTS … · mechanical, electrical, plumbing and fire protection building system components in place during a seismic or high wind event

Permit Fairview Municipal Building 55 Anderson Ave.Fairview,NJ Issue December 31,2015

20 00 00-6 VIBRATION ISOLATION, SEISMIC, WIND & FLOOD LOAD RESTRAINTS FOR HVAC, PLUMBING, ELECTRICAL & FIRE PROTECTION COMPONENTS

6 of 33

Seismic: Related to an earthquake. Seismic loads on a structure are caused by wave movements in the earth during an earthquake. Seismic Design Category: A classification assigned to a structure based on its Seismic Use Group or Occupancy Category and the severity of the design earthquake ground motion at the site. Seismic Forces: The assumed forces prescribed herein, related to the response of the structure to earthquake motions, to be used in the design of the structure and its components. Seismic Use Group, Occupancy Category, IBC-2006: A classification assigned to a building based on its use as defined in Section 1604.516.2. Site Class: A classification assigned to a site based on the types of soils present and their engineering properties as defined in Table 1613.5.2 (IBC-2006). Special Inspection: Inspection as herein required of the materials, installation, fabrication, erection or placement of components and connections requiring special documents and referenced standards (see Section 1704, IBC-2006). Special Inspection, Continuous: The full-time observation of work requiring special inspection by an approved special inspector who is present in the area where the work is being performed. Special Inspection, Periodic: The part-time or intermittent observation of work requiring special inspection by an approved special inspector who is present in the area where the work has been or is being performed and at the completion of the work. Story Drift Ratio: The story drift (Lateral displacement) divided by the story height. Transverse bracing: Bracing that prevents a component from moving from side to side. Wind-Borne Debris Region: Portions of hurricane-prone regions that are within 1 mile of the coastal mean high water line where the basic wind speed is 110 mph or greater, or portions of hurricane-prone regions where the basic wind speed is 120 mph or greater; or Hawaii.

1.4 GENERAL DESIGN AND PERFORMANCE REQUIREMENTS

A. General Design Requirements.

1. SEISMIC CONSIDERATIONS: This project has seismic design requirements as follows:

(a) Occupancy Category I, II & III (Seismic Design Category C) Life Safety Components (Ip = 1.5) High Hazard Components (All Gas Fired Components; Indoor and Outdoor) (Ip = 1.5) Components affected by Consequential Damage (Ip = 1.0)

2. WIND CONSIDERATIONS: This project has wind design requirements as follows:

(a) Wind load in hurricane, tornado and/or wind-borne debris regions (90 plus mph)

Page 7: PLUMBING, ELECTRICAL & FIRE PROTECTION COMPONENTS … · mechanical, electrical, plumbing and fire protection building system components in place during a seismic or high wind event

Permit Fairview Municipal Building 55 Anderson Ave.Fairview,NJ Issue December 31,2015

20 00 00-7 VIBRATION ISOLATION, SEISMIC, WIND & FLOOD LOAD RESTRAINTS FOR HVAC, PLUMBING, ELECTRICAL & FIRE PROTECTION COMPONENTS

7 of 33

having a building height greater than 60 feet. Rooftop structures; Section 6.5.15.1 of ASCE 7-05 design requirements apply)

3. FLOOD CONSIDERATIONS: This project has design requirements in accordance with FEMA and/or FIRM as follows:

(a) None

B. General Design Performance Requirements

1. Seismic and Wind Load Certification and Analysis:

(a) Attachment calculations by the Seismic Restraint Manufacturer’s licensed Engineer substantiating the mounting system, seismic or wind restraints, fasteners or ICC Certified Concrete Anchors shall be submitted for approval along with the shop drawings. Seismic loads shall have their calculations based on seismic loads as established in Specification Section 1.4, Paragraph B, article 5 Design Seismic Loads. Wind loads shall have their calculations based on Section 1.4, Paragraph B, article 6 Design Wind Loads. A registered professional engineer having a PE from the same state as the project, or state of restraint manufacturer shall stamp all analysis, or as required by local building codes.

(b) Unless otherwise specified, all equipment, piping and ductwork shall be restrained to

resist seismic forces. Restraints shall maintain equipment, piping or ductwork in a captive position. Restraint devices shall be designed and selected to meet seismic requirements as defined in the latest issue of:

(i) International Building Code, IBC and ASCE applicable state and local codes (ii) NFPA (fire protection only)

2. Importance Factor, Ip = 1.5 Components:

(a) In addition to all of the above provisions, for components having an Ip greater than

1.0, all trades shall comply with Sections 16 and 17 of the International Building Code using, when available, vendors that comply with the provisions stated herein and submitting the special inspections listed within these specifications. Where compliance is not possible, each contractor shall submit a vendor report (form CVC-1 at end of this specification) clearly indicating that none of the specified, listed or other vendors known to the contractor meets the compliance, testing and certification portions of the IBC specification’s Sections 16 and 17. Special inspections of the component installation shall still be conducted (Section 1.4, Paragraph B, Article 3) even if no vendors meet the following requirements. All non-isolated and isolated equipment (components) shall be secured to the structure in accordance with that code.

3. All component manufacturers shall submit for approval the following as required below:

(a) For all life safety system components noted in this specification: the Approved

Agency’s Certificate of Compliance for the specific equipment on this project when the Seismic Design Category is C through F. Analytical or Shaker Test certification through the component’s load path to structure at its center of gravity shall include

Page 8: PLUMBING, ELECTRICAL & FIRE PROTECTION COMPONENTS … · mechanical, electrical, plumbing and fire protection building system components in place during a seismic or high wind event

Permit Fairview Municipal Building 55 Anderson Ave.Fairview,NJ Issue December 31,2015

20 00 00-8 VIBRATION ISOLATION, SEISMIC, WIND & FLOOD LOAD RESTRAINTS FOR HVAC, PLUMBING, ELECTRICAL & FIRE PROTECTION COMPONENTS

8 of 33

anchorage, structural and on line capability. Use of seismic experience data shall be permitted if evidence confirms that the historical based component has the same construction and weight and accompanying center of gravity as submitted unit and basis of experience claim conforms to loads derived in testing with accompanying accelerations based on AC-156. Seismic qualification by seismic experience data based upon nationally recognized procedures acceptable to the authority having jurisdiction shall be deemed to satisfy the design and evaluation requirements provided that the substantiated seismic capacities equal or exceed the seismic demands determined in accordance with Sections 13.3.1 and 13.3.2 of ASCE 7-05.

(b) In addition, all components needed for the continued operation of the facility in the

above stated categories will have the manufacturer of that component submit the Approved Agency’s Certificate of Compliance for their equipment when the Seismic Design Category is C through F. Analytical or Shaker Test certification through the component’s load path to structure at its center of gravity shall include on line capability. This requirement also pertains to projects that combine an emergency preparedness center within a structure of another Use Group. Where components do not effect the facility’s functional operation but could affect the performance of other components should they dislodge, only anchorage of that component requires compliance. Components needed for continued operation of the building require Analytical or Shaker Test certification through the total component’s load path to structure calculated at its center of gravity. Certification shall prove anchorage, structural and on line capability. For use of seismic experience data, see (a) above.

(c) All components containing hazardous or flammable materials will have the

manufacturer of the component submit the Approved Agency’s Certificate of Compliance for their equipment when used on any project having a minimum Seismic Design Category of C through F. Testing shall be conducted by Analytical or Shaker Test through the total component’s load path to structure at its center of gravity and shall prove anchorage, structural capability and hazardous material containment. Testing shall prove that no internal component will rupture to insure against loss of hazardous or flammable (explosive) material that could support combustion, ignite or contaminate.

(d) All components requiring anchorage compliance only, not listed in the above

categories, shall have the manufacturer of each component submit a PE stamped calculation package stating that their project specific equipment will accept anchorage by calculating its reactions through the component’s load path to structure at its center of gravity at the designated anchorage locations. This requirement is for all projects having a Seismic Design Category of C through F.

4. Seismic Use Group I & II, IBC-2000 & Occupancy Category II & III Structures, IBC-

2003-2006, Ip 1.0, Seismic Design Category C:

(a) Projects in these categories require seismic bracing for all life safety and high hazard components, Paragraph 1.3B sub-paragraphs 1, 2, 5 and 7. In addition, any un-braced component that could adversely affect the performance of a component that must remain functional, Ip 1.5, or could cause the failure or release of hazardous materials (gas or liquid fuel), must be braced or anchored to avoid such failure. This includes

Page 9: PLUMBING, ELECTRICAL & FIRE PROTECTION COMPONENTS … · mechanical, electrical, plumbing and fire protection building system components in place during a seismic or high wind event

Permit Fairview Municipal Building 55 Anderson Ave.Fairview,NJ Issue December 31,2015

20 00 00-9 VIBRATION ISOLATION, SEISMIC, WIND & FLOOD LOAD RESTRAINTS FOR HVAC, PLUMBING, ELECTRICAL & FIRE PROTECTION COMPONENTS

9 of 33

any component that could fall or move laterally. (Consequential Damage, ASCE 7-05, Section 16.2.3.)

5. Design Seismic Loads:

(a) Projects in the United States have a minimum design load of 0.4g for statically

mounted components and 0.5g for resiliently mounted components. Actual loads for both internal and external isolation and/or anchorage of components shall be as above or as calculated for the specific project location but in no event shall it be less than the above.

(b) Exclusions for seismic restraint of piping and duct shall be according to applicable

codes and as stated herein. The minimum horizontal restraint capability shall be 0.4g horizontal and 0.27g vertical (in addition to the gravity load). Life safety equipment defined above shall be designed to withstand a horizontal load of 0.9g and a vertical load of 0.6g.

(c) Analysis for anchorage must indicate calculated dead loads, static seismic loads and

capacity of materials utilized for connections to equipment and structure. Analysis must detail anchoring methods, bolt diameter, embedment depth and/or welded length. All seismic restraint devices shall be designed to accept, without failure, the forces detailed in this section, acting through the equipment center of gravity.

(d) Vertical load shall be calculated at 1/3 the horizontal load as a minimum, or, as

prescribed by the code as 0.2 times Sds.

(e) Internally isolated equipment in lieu of specified isolation and restraint systems must meet all of the requirements of this section, all articles.

(f) A Seismic Design Errors and Omissions Insurance Certificate MUST accompany the

seismic restraint equipment manufacturer’s calculation. Product liability insurance certificates are not acceptable.

(g) Whether the equipment is internally or externally isolated and restrained, the entire

unit assembly must be seismically attached to the structure. Curb or roof rail mounted equipment must not only have seismic or wind attachment of the equipment to the roof but also to the curb or rails. The attachment and certification thereof shall be by this section. Sheet metal screw attachment is acceptable provided that the following five conditions are met and verified.

(i) Calculations support sufficient quantity and size of sheet metal screws to

handle all loads including shear. (ii) Shear and tension allowables are obtained from an accredited third party

source, such as ICC or NDS, not from the screw manufacturer. (iii) Space or gap between the inside overhang of the rooftop unit and the

curb at each of the screw locations is closed with structural material, tapered to contour to both the curb and the components’ inside edge

Page 10: PLUMBING, ELECTRICAL & FIRE PROTECTION COMPONENTS … · mechanical, electrical, plumbing and fire protection building system components in place during a seismic or high wind event

Permit Fairview Municipal Building 55 Anderson Ave.Fairview,NJ Issue December 31,2015

20 00 00-10 VIBRATION ISOLATION, SEISMIC, WIND & FLOOD LOAD RESTRAINTS FOR HVAC, PLUMBING, ELECTRICAL & FIRE PROTECTION COMPONENTS

10 of 33

structure. (iv) Attachment points of the roof-mounted unit to curb and the curb to

structure demonstrates structural load path. (v) The method of attachment does not violate the NRCA rating of the curb

by violating the roof member’s waterproofing.

(h) Failure is defined as the discontinuance of any attachment point or load path between component and structure. Permanent deformation of the component is acceptable as long as the component continues to operate without failure and, if permanent, it is within acceptable manufacturing or structural tolerances.

6. Design Wind Loads:

(a) All outdoor mounted components shall be positively fastened to their supporting

structure as discussed below. Fastening to metal deck is unacceptable.

(i) If component is curb or support mounted, article 5, Design Seismic Loads, paragraph g shall be followed for all roof-mounted components in excess of 9 sq. ft. in cross-sectional area. Curbs shall be as described in Base type B-3 if isolated, Base type B-4 if non-isolated.

(ii) If component is support mounted, article 5, Design Seismic Loads

paragraph g shall be followed for all roof-mounted components requiring waterproofed rail supports. Equipment supports shall be Base type B-5 if isolated, Base type B-6 if non-isolated.

(iii) If equipment is dunnage mounted, positive attachment shall occur through

welding or bolting of equipment to dunnage steel.

(b) Loads and calculations shall be based on IBC-2006, figure 1609 and related sections in ASCE 7-05.

(c) Equivalent basic wind speed shall be based on IBC-2006, Table 1609.3.1.

(d) In no event shall adjacent buildings, structures or screens be considered to diminish

the calculated wind load or its effect on an outdoor component.

7. Design Flood Loads:

(a) Components used for anchorage purposes shall be hot dipped galvanized, cadmium-plated or powder-coated for the purpose of anti-corrosion.

8. Additional Seismic Design Requirements for Fire Protection Components

(a) Fire sprinkler piping system shall be braced to meet the minimum requirements of

NFPA No. 13. Additionally, all branch lines will be braced for structures in Occupancy Category IV, IBC-2003-2006.

Page 11: PLUMBING, ELECTRICAL & FIRE PROTECTION COMPONENTS … · mechanical, electrical, plumbing and fire protection building system components in place during a seismic or high wind event

Permit Fairview Municipal Building 55 Anderson Ave.Fairview,NJ Issue December 31,2015

20 00 00-11 VIBRATION ISOLATION, SEISMIC, WIND & FLOOD LOAD RESTRAINTS FOR HVAC, PLUMBING, ELECTRICAL & FIRE PROTECTION COMPONENTS

11 of 33

(b) All branch lines shall be end tied if not braced (Occupancy Categories II & III).

(c) Standpipe risers shall be provided with a minimum of (1) flexible coupling (Victaulic

Style 77 or equal) to accommodate lateral drift at each floor level.

(d) Vertical pipe risers shall have their weight, where possible, supported above the center of gravity of the riser. Provide lateral guides at the top and bottom of the riser and at intermediate points not to exceed 30’.

(e) Friction connections of any fire protection line to structure are not permissible under

any circumstances. All connections must be positive.

(f) Branch lines shall never act as a brace to mains or cross-mains.

(g) All pipe sleeves through floors shall be designed to accommodate differential movement between the floors.

(h) All pipe sleeves through walls shall be designed to accommodate differential

movement between the structures, when the walls are separations between two independently moving structures.

1.5 SUBMITTAL DATA REQUIREMENTS

A. Refer to Part 1, General.

B. The manufacturer of vibration isolation, seismic, wind and flood restraints shall provide submittals for products as follows:

1. Descriptive Data:

(a) Catalog cuts or data sheets on vibration isolators and specific restraints detailing

compliance with the specification.

(b) Detailed schedules of flexible and rigidly mounted equipment, showing vibration isolators and restraints by referencing numbered descriptive drawings.

2. Shop Drawings:

(a) Submit fabrication details for equipment bases including dimensions, structural

member sizes and support point locations.

(b) Provide all details of suspension and support for ceiling hung equipment.

(c) Where walls, floors, slabs or supplementary steel work are used for restraint locations, details of acceptable attachment methods for ducts and pipe must be included and approved before the condition is accepted for installation. Restraint manufacturer’s submittals must include spacing and maximum seismic/wind loads at the restraint points.

Page 12: PLUMBING, ELECTRICAL & FIRE PROTECTION COMPONENTS … · mechanical, electrical, plumbing and fire protection building system components in place during a seismic or high wind event

Permit Fairview Municipal Building 55 Anderson Ave.Fairview,NJ Issue December 31,2015

20 00 00-12 VIBRATION ISOLATION, SEISMIC, WIND & FLOOD LOAD RESTRAINTS FOR HVAC, PLUMBING, ELECTRICAL & FIRE PROTECTION COMPONENTS

12 of 33

(d) Provide specific details of restraints and anchors, include number, size and locations

for each piece of equipment. Restraint and anchor allowables shall be by structural testing, shake testing, analysis or third party certification.

(e) Calculations shall be submitted as required in Section 1.4, General Design and Performance Requirements.

1.6 RELATED WORK

1. Housekeeping pad structural design, including its attachment to building structure, shall be by the structural engineer of record or as shown on the contract drawings. Attachment of all components and restraints to the pad and size of the pad shall be designed and certified according to this section by the seismic/isolation supplier. Material and labor required for attachment and construction shall be by the concrete section contractor, or by the contractor where specified. Housekeeping pads shall be sized to accommodate a minimum 6” of clearance all around the equipment; or 12 times the outermost anchor bolt diameter, whichever is greater. Where exterior isolators are used, this distance shall be as measured from the outermost holes in the isolator base plate to the edge of the housekeeping pad.

2. The project’s structural engineer shall design all roof and interior steel to support and make

connections to all components, including roof-mounted equipment specified in other sections. Design shall comply with IBC requirements including load path to structure.

3. Roof steel supporting roof-mounted equipment shall be designed for all seismic and wind

forces including, but not limited to, tension, compression and moment loads.

4. Where ceilings are not braced, lay-in lighting fixtures, weighing more than 20 lbs, shall have at least 2 independent corner diagonal wire ties to structure.

5. Lay-in ceilings in compliance with seismic code requirements may use earthquake clips or

other approved means of positive attachment to brace fixtures such as panel lights and diffusers less than 40 lbs to T-bar structures. Local codes dictate fixture support requirements.

1.7 CODE AND STANDARDS REQUIREMENTS

A. Typical Applicable Codes and Standards

1. All City, State and Local Codes (Code)

(1) SMACNA Guidelines for Seismic Restraint of Mechanical Systems, Second Edition (Standard reference, to be used for design purposes only, not code)

(2) NFPA 13 and 14 for Fire Protection System (Standard)

(3) American Society For Testing and Materials (ASTM) (Standard)

(4) International Conference of Building Officials (ICBO) (Standard)

Page 13: PLUMBING, ELECTRICAL & FIRE PROTECTION COMPONENTS … · mechanical, electrical, plumbing and fire protection building system components in place during a seismic or high wind event

Permit Fairview Municipal Building 55 Anderson Ave.Fairview,NJ Issue December 31,2015

20 00 00-13 VIBRATION ISOLATION, SEISMIC, WIND & FLOOD LOAD RESTRAINTS FOR HVAC, PLUMBING, ELECTRICAL & FIRE PROTECTION COMPONENTS

13 of 33

(5) International Building Code (Code)

(6) ASHRAE (Standard reference, to be used for design purposes only, not code).

(7) VISCMA (Vibration Isolation and Seismic Controls Manufacturers Association)

(Standard reference, to be used for design purposes only, not code).

B. In cases where requirements vary, the guideline for the most stringent shall be utilized.

C. Use IBC-2006 as reference code standard unless otherwise designated. 1.8 QUALITY ASSURANCE

A. Manufacturer of vibration isolation, seismic and wind load control equipment or manufacturer’s approved representative shall have the following responsibilities:

1. Determine vibration isolation and restraint sizes and locations.

2. Provide vibration isolation and restraints as scheduled or specified.

3. Provide calculations and materials, if required, for restraint of non-isolated equipment.

4. Provide installation instructions in writing, drawings and trained field supervision, where

necessary, to insure proper installation and performance.

5. Certify correctness of installation upon completion, in writing.

6. All provisions of Section 1.4, General Design and Performance Requirements.

B. All manufacturers of vibration control, seismic, wind or flood restraining systems must provide a Seismic Design Error and Omissions Insurance Certificate for their firm or their design consultant to certify their ability to provide engineering and design as required by this section. This document shall be provided at the time of first submittal from the seismic restraint provider.

C. All manufacturers of any type of equipment including OEM are responsible for Section 1.4.

D. Equipment manufacturer’s substitution of internally or externally isolated and/or restrained

equipment supplied by the equipment vendor, in lieu of the isolation and restraints specified in this section, is acceptable provided all conditions of this section are met. The equipment manufacturer shall provide a letter of guarantee from their engineering department, PE stamped and certified per the section on the Seismic Restraint Design (See Section 1.4B, article 2), stating that the seismic restraints are in full compliance with these specifications. Where used on an Essential or High Hazard Facility, manufacturer’s certification proving on line capability shall be required in addition to all requirements stated in Section 1.4B. Letters from field offices or representatives are unacceptable.

Page 14: PLUMBING, ELECTRICAL & FIRE PROTECTION COMPONENTS … · mechanical, electrical, plumbing and fire protection building system components in place during a seismic or high wind event

Permit Fairview Municipal Building 55 Anderson Ave.Fairview,NJ Issue December 31,2015

20 00 00-14 VIBRATION ISOLATION, SEISMIC, WIND & FLOOD LOAD RESTRAINTS FOR HVAC, PLUMBING, ELECTRICAL & FIRE PROTECTION COMPONENTS

14 of 33

E. All costs for converting to the specified vibration isolation and/or restraints shall be borne by the component vendor in the event of non-compliance with the preceding. Substitution of internal isolation is unacceptable for:

(1) Indoor or outdoor mounted equipment over or adjacent to: (a) Patient or operating areas (b) Theatre space (c) Office locations (d) Assembly areas

Page 15: PLUMBING, ELECTRICAL & FIRE PROTECTION COMPONENTS … · mechanical, electrical, plumbing and fire protection building system components in place during a seismic or high wind event

Permit Fairview Municipal Building 55 Anderson Ave.Fairview,NJ Issue December 31,2015

20 00 00-15 VIBRATION ISOLATION, SEISMIC, WIND & FLOOD LOAD RESTRAINTS FOR HVAC, PLUMBING, ELECTRICAL & FIRE PROTECTION COMPONENTS

15 of 33

SECTION 2 – PRODUCTS 2.1 DESCRIPTION

A. All vibration isolators and seismic restraints described in this Section shall be the product of a single manufacturer. The basis of this specification is The VMC Group, including Vibration Mountings & Controls, Amber/Booth or Korfund Dynamics. Products from other nationally recognized manufacturers are acceptable provided their systems strictly comply with these specifications and have the approval of the specifying engineer. Manufacturer shall be a regular member of VISCMA (Vibration Isolation and Seismic Controls Manufacturers Association). See Form VL-1 listing other manufacturers to be considered for use on this project.

2.2 VIBRATION ISOLATION TYPES

A. Type A: Spring Isolator – Free Standing A*

1. Spring isolators shall be free standing and laterally stable without any housing and complete

with a molded elastomeric cup or ¼” elastomeric acoustical friction pad between the bottom of isolator and the support.

2. All mountings shall have leveling bolts that must be rigidly bolted to the equipment.

3. Spring diameters shall be no less than 0.8” of the compressed height of the spring at rated

load.

4. Springs shall have a minimum additional travel to solid equal to 50% of the operating deflection.

B. Type B: Seismically and Wind Restrained Spring Isolator

MS, MSS, AEQM, ASCM, AMSR

1. Restrained spring mountings shall have a Type A spring isolator within a rigid housing that includes vertical limit stops to prevent spring extension if weight is removed. The housing shall serve as blocking during erection. A maximum clearance of ¼” shall be maintained around restraining bolts and internal elastomeric deceleration bushings. Limit stops shall be out of contact during normal operation. If housings are to be bolted or welded in position there must be an internal isolation pad or elastomeric cup. Housing shall be designed to resist all seismic forces.

C. Type C: Combination Spring/Elastomer Hanger Isolator (30° Type)

HRSA 1. Hangers shall consist of rigid steel frames containing minimum 1 ¼” thick elastomeric

elements at the top and a steel spring with general characteristics as in Type A. The elastomeric element shall have resilient bushings projecting through the steel box.

Page 16: PLUMBING, ELECTRICAL & FIRE PROTECTION COMPONENTS … · mechanical, electrical, plumbing and fire protection building system components in place during a seismic or high wind event

Permit Fairview Municipal Building 55 Anderson Ave.Fairview,NJ Issue December 31,2015

20 00 00-16 VIBRATION ISOLATION, SEISMIC, WIND & FLOOD LOAD RESTRAINTS FOR HVAC, PLUMBING, ELECTRICAL & FIRE PROTECTION COMPONENTS

16 of 33

2. Spring diameters and hanger box lower hole sizes shall be large enough to permit the hanger rod to swing through a 30° arc from side to side before contacting the rod bushing and short-circuiting the spring.

3. Submittals shall include a hanger drawing showing the 30° capability. 4. Hanger locations requiring pre-compression for holding piping at fixed elevation shall be

type pre-compressed or pre-positioning for all manufacturers.

D. Type D: Elastomer Double Deflection Hanger Isolator HR

1. Molded (minimum 1 ¼” thick) elastomeric element with projecting bushing lining the rod

clearance hole. Static deflection at rated load shall be a minimum of 0.35.”

2. Steel retainer box encasing elastomeric mounting capable of supporting equipment up to two times the rated capacity of the element.

E. Type E: Combination Spring/Elastomer Hanger Isolator

HRS

1. Spring and elastomeric elements in a steel retainer box with the features as described for Type C and D isolators.

2. Hanger locations requiring pre-compression for holding piping at fixed elevation shall be

type pre-compressed or pre-positioning for all manufacturers. 3. 30° angularity feature is not required.

F. Type F: Seismically Restrained Elastomer Floor Isolator RSM, MB, RUD

1. Bridge-bearing elastomeric mountings shall have a minimum static deflection of 0.2” and all-

directional seismic capability. The mount shall consist of a ductile iron or aluminum casting containing molded elastomeric elements. The elements shall prevent the central threaded sleeve and attachment bolt from contacting the casting during normal operation. The shock-absorbing elastomeric materials shall be compounded to bridge-bearing or DuruleneTM specifications.

G. Type G: Pad Type Elastomer Isolator (Standard)

Maxiflex

1. One layer of ¾” thick elastomeric pad consisting of 2” square modules for size required.

2. Load distribution plates shall be used as required.

3. Bolting required for seismic compliance. Elastomeric and duck washers and bushings shall be provided to prevent short-circuiting.

Page 17: PLUMBING, ELECTRICAL & FIRE PROTECTION COMPONENTS … · mechanical, electrical, plumbing and fire protection building system components in place during a seismic or high wind event

Permit Fairview Municipal Building 55 Anderson Ave.Fairview,NJ Issue December 31,2015

20 00 00-17 VIBRATION ISOLATION, SEISMIC, WIND & FLOOD LOAD RESTRAINTS FOR HVAC, PLUMBING, ELECTRICAL & FIRE PROTECTION COMPONENTS

17 of 33

H. Type H: Pad Type Elastomer Isolator (High Density)

Fabri-Flex, NDB, NRC

1. Laminated canvas duck and neoprene, maximum loading 1000 psi, minimum ½” thick.

2. Load distribution plate shall be used as required.

3. Bolting required for seismic compliance. Elastomeric and duck washers and bushings shall be provided to prevent short-circuiting.

I. Type I: Thrust Restraints

RSHTR, TRK

1. A spring element similar to Type A isolator shall be combined with steel angles, backup plates, threaded rod, washers and nuts to produce a pair of devices capable of limiting movement of air handling equipment to ¼” due to thrust forces. Contractor shall supply hardware.

2. Thrust restraints shall be installed on all cabinet fan heads, axial or centrifugal fans whose

thrust exceeds 10% of unit weight.

J. Type J: Pipe Anchors MDPA, AG

1. All-directional acoustical pipe anchor, consisting of two sizes of steel tubing or piping

separated by a minimum ½” thick 60 durometer elastomer.

2. Vertical restraint shall be provided by similar material arranged to prevent vertical travel in either direction.

3. Applied loads on the isolation material shall not exceed 500 psi and the design shall be

balanced for equal resistance in any direction.

K. Type K: Pipe Guides PG/AG/SWP/SWX

1. Pipe guides shall consist of a telescopic arrangement of two sizes of steel tubing or piping

separated by a minimum ½” thickness of 60 durometer elastomer.

2. The height of the guides shall be preset with a shear pin to allow vertical motion due to pipe expansion or contraction. Shear pin shall be removable and replaceable to allow for selection of pipe movement.

3. Guides shall be capable of ± 1 5/8” motion, or to meet location requirements.

Page 18: PLUMBING, ELECTRICAL & FIRE PROTECTION COMPONENTS … · mechanical, electrical, plumbing and fire protection building system components in place during a seismic or high wind event

Permit Fairview Municipal Building 55 Anderson Ave.Fairview,NJ Issue December 31,2015

20 00 00-18 VIBRATION ISOLATION, SEISMIC, WIND & FLOOD LOAD RESTRAINTS FOR HVAC, PLUMBING, ELECTRICAL & FIRE PROTECTION COMPONENTS

18 of 33

L. Type L: Isolated Pipe Hanger System CIH, CIR, TIH, PIH

1. Pre-compressed spring and elastomer isolation hanger combined with pipe support into one

assembly. Replaces standard clevis, single or double rod roller, or double rod fixed support.

2. Spring element (same as Type A) with steel lower spring retainer and an upper elastomer retainer cup with an integral bushing to insulate support rod from the isolation hanger.

3. The elastomeric element under the lower steel spring retainer shall have an integral bushing

to insulate the support rod from the steel spring retainer.

4. Hangers shall be designed and constructed to support loads over three times the rated load without failure.

5. Systems shall be pre-compressed to allow for rod insertion and standard leveling.

2.3 SEISMIC RESTRAINT TYPES

A. Type I: Spring Isolator, Restrained MS, MSS, AEQM, ASCM, AMRS

1. Not Used

B. Type II: Seismically Restrained Elastomer Floor Isolator MB, RUD

1. Not Used

C. Type III: All-Directional Seismic Snubber SR, ER

1. Not Used

D. Type IV: Floor or Roof Anchorage Cast-In Plates

1. Rigid attachment to structure utilizing wedge type anchor bolts, anchored plates, machine

screw, bolting or welding. Power shots are unacceptable.

E. Type V: Seismic Cable Restraints SB, LRC

1. Seismic Cable Restraints shall consist of galvanized steel aircraft cables sized to resist

seismic loads with a minimum safety factor of two and arranged to provide all-directional restraint. Cable end connections shall be steel assemblies that swivel to final installation angle and utilize two clamping bolts to provide proper cable engagement. Cables must not be allowed to bend across sharp edges.

Page 19: PLUMBING, ELECTRICAL & FIRE PROTECTION COMPONENTS … · mechanical, electrical, plumbing and fire protection building system components in place during a seismic or high wind event

Permit Fairview Municipal Building 55 Anderson Ave.Fairview,NJ Issue December 31,2015

20 00 00-19 VIBRATION ISOLATION, SEISMIC, WIND & FLOOD LOAD RESTRAINTS FOR HVAC, PLUMBING, ELECTRICAL & FIRE PROTECTION COMPONENTS

19 of 33

F. Type VI: Rigid Arm Brace SAB

1. Not Used

G. Type VII: Internal Clevis Cross Brace ICB

1. Not Used

H. Type VIII: Seismic Waterproof Foundation Wall Sleeve SWFWS

1. Not Used

2.4 EQUIPMENT BASES

A. General 1. All curbs and roof rails are to be bolted or welded to the building steel or anchored to the

concrete deck (minimum thickness shall be 4”) for resisting wind and seismic forces in accordance with the project location. (Fastening to metal deck is unacceptable.)

B. Base Types

1. Type B-1: Integral Structural Steel Base

WFB, SFB, WSB

(a) Rectangular bases are preferred for all equipment.

(b) Centrifugal refrigeration machines and pump bases may be T or L shaped where space is a problem. Pump bases for split case and end suction pumps shall include supports for suction and discharge elbows.

(c) All perimeter members shall be structural steel beams with a minimum depth equal to

1/12 of the longest dimension between isolators.

(d) Base depth need not exceed 12” provided that the deflection and misalignment is kept within acceptable limits as determined by the manufacturer.

(e) Height saving brackets shall be employed in all mounting locations to provide a

minimum base clearance of 2.”

2. Type B-2: Concrete Inertia Base MPF, WPF, CPF

(a) Vibration isolation manufacturer shall furnish rectangular welded or bolted modular steel concrete pouring forms for floating and inertia foundations.

Page 20: PLUMBING, ELECTRICAL & FIRE PROTECTION COMPONENTS … · mechanical, electrical, plumbing and fire protection building system components in place during a seismic or high wind event

Permit Fairview Municipal Building 55 Anderson Ave.Fairview,NJ Issue December 31,2015

20 00 00-20 VIBRATION ISOLATION, SEISMIC, WIND & FLOOD LOAD RESTRAINTS FOR HVAC, PLUMBING, ELECTRICAL & FIRE PROTECTION COMPONENTS

20 of 33

(b) Bases for split case and end suction pumps shall be large enough to provide for suction and discharge elbows.

(c) Bases shall be a minimum of 1/12 of the longest dimension between isolators but not

less than 6.” (d) The base depth need not exceed 12” unless specifically recommended by the base

manufacturer for mass or rigidity. (e) Forms shall include a minimum concrete reinforcing consisting of 3/8” bars welded

in place a maximum of 16” on centers running both ways in a layer 1 to 1½” above the bottom.

(f) Forms shall be furnished with steel templates to hold the component anchor bolts

sleeves and anchors while concrete is being poured.

(g) Height saving brackets shall be employed in all mounting locations to maintain a 2” minimum operational clearance below the base.

3. Type B-3: Seismic Isolation Curb

P6200, P6300 Option: Sound Package 1 & 2 VMC/AB-RPFMA/SRPFMA

(a) Curb-mounted rooftop equipment shown on isolation schedule shall be mounted on

structural seismic spring isolation curbs. The upper frame must provide continuous support for the equipment and must be captive so as to resiliently resist wind and seismic forces. The lower frame must accept point support for both seismic attachment and leveling. The upper frame must be designed with positive fastening provisions (welding or bolting), to anchor the rooftop unit to the curb, which will not violate the National Roofing Contractors Association (NRCA) ratings of the membrane waterproofing. Sheet metal screws are only acceptable if all provisions in Section 1.4, Article B, 7, Design Seismic Loads, are met. Contact points between the rooftop unit, the curb and the building’s structure shall show load path through those locations only.

(b) All-directional elastomeric snubber bushings shall be minimum of ¼” thick. Steel

springs shall be laterally stable and rest on ¼” thick elastomeric acoustical pads or cups.

(c) Hardware must be plated and the springs shall be powder-coated or cadmium-plated. (d) The curb’s waterproofing shall be designed to meet all NRCA requirements.

(e) All spring locations shall have access ports with removable waterproof covers and all

isolators shall be adjustable, removable and interchangeable.

Page 21: PLUMBING, ELECTRICAL & FIRE PROTECTION COMPONENTS … · mechanical, electrical, plumbing and fire protection building system components in place during a seismic or high wind event

Permit Fairview Municipal Building 55 Anderson Ave.Fairview,NJ Issue December 31,2015

20 00 00-21 VIBRATION ISOLATION, SEISMIC, WIND & FLOOD LOAD RESTRAINTS FOR HVAC, PLUMBING, ELECTRICAL & FIRE PROTECTION COMPONENTS

21 of 33

(f) Isolated curbs shall be supplied with a continuous air seal between the upper floating member and the stationary wood nailer.

Option #1 Where sound barrier package is required, curb shall have full size lay in attenuation panels having a minimum STC rating of 60 when combined with the roof deck’s rating. Attenuation system shall add a full sound attenuation structural floor to the curb capable of spanning the curb’s width and designed for live loads of 20 psf. Panels shall not weigh more than 6 psf. The 4” nominal galvanized panel shall be joined to allow for airtight construction and additionally shall have a support system where the panels are used below an outside condenser section. Panels shall be waterproof for both outdoor and indoor application. The space below the curb panels and the roof deck shall have 4” of insulation contractor furnished and installed.

Curb wall construction shall utilize the roofer’s standard insulation where curbs use the TAS open thermal acoustical screening system. Solid wall curbs shall use 2” of the factory duct liner installed by the curb manufacturer. The entire curb shall have a continuous neoprene elastomeric air seal. Type RPFMA shall use an open return system with the roof return opening set as far as possible from the unit’s return opening.

Option # 2 When curb type SRPFMA (Supply Return Plenum Construction) is required, in addition to Option # 1 the walls of the supply section will use 2” sound attenuating panels as well as a continuous inner elastomeric air seal and isolated plenum divider. Both supply and return ducts shall seal directly to curb base floor attenuation panels.

4. Type B-4: Seismic Non-Isolated Curbs

P6000 Option: Sound Package VMC-RPFMA/SRPFMA System

(a) Seismic curbs shall have all provisions as Type B-3 curbs with the exception of

spring isolation.

(b) System shall be designed for positive anchorage or welding of equipment to supports and welding of supports to the building steel, capable of carrying the design seismic loads.

5. Type B-5: Isolated Equipment Supports

R7200/R7300

(a) Continuous structural equipment support rails that combine equipment support and isolation mounting into one unitized roof flashed assembly with all features as described for Type B-3.

(b) System shall be designed for positive anchorage or welding of equipment to supports

and welding of supports to the building steel, capable of carrying the design seismic loads.

6. Type B-6: Non-Isolated Equipment Supports

Page 22: PLUMBING, ELECTRICAL & FIRE PROTECTION COMPONENTS … · mechanical, electrical, plumbing and fire protection building system components in place during a seismic or high wind event

Permit Fairview Municipal Building 55 Anderson Ave.Fairview,NJ Issue December 31,2015

20 00 00-22 VIBRATION ISOLATION, SEISMIC, WIND & FLOOD LOAD RESTRAINTS FOR HVAC, PLUMBING, ELECTRICAL & FIRE PROTECTION COMPONENTS

22 of 33

R7000

(a) This shall have the same provisions as Type B-5 without the spring isolation. 2.5 FLEXIBLE CONNECTORS

A. Type FC-2: Flexible Stainless Steel Hose SS-FP, SS-FW, SS-PM, SS-WE 1. Flexible stainless steel hose shall have stainless steel braid and carbon steel fittings. Sizes 3”

and larger shall be flanged. Smaller sizes shall have male nipples.

B. Type BC-2 connector shall be braided bronze for Freon connections. 1. Minimum lengths shall be as tabulated:

Flanged Male Nipples 3 x 14 10 x 26 ½ x 9 1 ½ x 13 4 x 15 12 x 28 ¾ x 10 2 x 14 5 x 19 14 x 30 1 x 11 2 ½ x 18 6 x 20 16 x 32 1 ¼ x 12 8 x 22

2. Hoses shall be installed on the equipment side of the shut-off valves horizontally and parallel

to the equipment shafts wherever possible.

Page 23: PLUMBING, ELECTRICAL & FIRE PROTECTION COMPONENTS … · mechanical, electrical, plumbing and fire protection building system components in place during a seismic or high wind event

Permit Fairview Municipal Building 55 Anderson Ave.Fairview,NJ Issue December 31,2015

20 00 00-23 VIBRATION ISOLATION, SEISMIC, WIND & FLOOD LOAD RESTRAINTS FOR HVAC, PLUMBING, ELECTRICAL & FIRE PROTECTION COMPONENTS

23 of 33

SECTION 3- EXECUTION 3.1 EXAMINATION

A. All areas that will receive components requiring vibration control, seismic or wind load bracing shall be thoroughly examined for deficiencies that will affect their installation or performance. Such deficiencies shall be corrected prior to the installation of any such system.

B. Examine all “rough ins” including anchors and reinforcing prior to placement. 3.2 COMPONENT INSTALLATION, (General)

A. All vibration isolators and seismic, wind restraint systems must be installed in strict accordance with the manufacturer’s written instructions and all certified submittal data.

B. Installation of vibration isolators and seismic, wind restraints must not cause any change of position of equipment, piping or ductwork resulting in stresses or misalignment.

C. No rigid connections between equipment and the building structure shall be made that degrades the noise and vibration control system specified herein.

D. The contractor shall not install any isolated components in a manner that makes rigid connections with the building unless isolation is not specified. “Building” includes, but is not limited to, slabs, beams, columns, studs and walls.

E. Coordinate work with other trades to avoid rigid contact with the building.

F. Overstressing of the building structure must not occur due to overhead support of equipment. Contractor must submit loads to the structural engineer of record for approval. General bracing may occur from flanges of structural beams, upper truss cords in bar joist construction and cast in place inserts or wedge type drill-in concrete anchors.

G. Seismic cable restraints shall be installed slightly slack to avoid short circuiting the isolated suspended equipment or piping.

H. Seismic cable assemblies are installed taut on non-isolated systems. Seismic rigid braces may be used in place of cables on rigidly attached systems.

I. At locations where seismic cable restraints or seismic single arm braces are located, the support rods must be braced when necessary to accept compressive loads. See Table “E.”

J. At all locations where seismic cable braces and seismic cable restraints are attached to the pipe clevis, the clevis bolt must be reinforced with pipe clevis cross bolt braces or double inside nuts if required by seismic acceleration levels.

K. Vibration isolation manufacturer shall furnish integral structural steel bases as required. Independent steel rails are not permitted.

L. Air handling equipment and centrifugal fans shall be protected against excessive displacement

Page 24: PLUMBING, ELECTRICAL & FIRE PROTECTION COMPONENTS … · mechanical, electrical, plumbing and fire protection building system components in place during a seismic or high wind event

Permit Fairview Municipal Building 55 Anderson Ave.Fairview,NJ Issue December 31,2015

20 00 00-24 VIBRATION ISOLATION, SEISMIC, WIND & FLOOD LOAD RESTRAINTS FOR HVAC, PLUMBING, ELECTRICAL & FIRE PROTECTION COMPONENTS

24 of 33

which results from high air thrust in relation to the equipment weight. Horizontal thrust restraints shall be those described in the specification when horizontal motion exceeds 3/8.”

M. Special and Periodic Inspections for items listed in Section 1.4, Article B shall be conducted and

submitted on a timely basis. 3.3 EQUIPMENT INSTALLATION

A. Equipment shall be isolated and/or restrained as per Tables A-E at the end of this section.

B. Place floor mounted equipment on 4” actual height concrete housekeeping pads properly sized and doweled or expansion shielded to the structural deck to meet acceleration criteria (see Section 1.4). Anchor isolators and/or bases to housekeeping pads. Concrete work is specified under that section of the contract documents.

C. Additional Requirements:

1. The minimum operating clearance under all isolated components bases shall be 2.”

2. All bases shall be placed in position and supported temporarily by blocks or shims, as appropriate, prior to the installation of the equipment, isolators and restraints.

3. All components shall be installed on blocks to the operating height of the isolators. After the

entire installation is complete and under full load including water, the isolators shall be adjusted so that the load is transferred from the blocks to the isolators. Remove all debris from beneath the equipment and verify that there are no short circuits of the isolation. The equipment shall be free to move in all directions, within the limits of the restraints.

4. Ceilings containing diffusers or lighting fixtures must meet seismic requirements by using

earthquake clips of other approved means of positive attachment to secure diffuser and fixtures to T-bar structure.

5. All floor or wall-mounted equipment and tanks shall be restrained with Type V restraints.

3.4 PIPING AND DUCTWORK ISOLATION

A. Vibration Isolation of Piping: 1. HVAC Water Piping: All spring type isolation hangers shall be pre-compressed or pre-

positioned if isolators are installed prior to fluid charge. If installed afterwards, field pre-compressed isolators can be used. All HVAC piping in the machine room shall be isolated as well as pressurized runs in other locations of the building 6” and larger. Type E hangers shall isolate horizontal pressurized runs in all other locations of the building. Floor supported piping shall rest on Type B isolators. Heat exchangers and expansion tanks are considered part of the piping run. The first 3 isolators from the isolated equipment shall have at least the same static deflection as specified for the mountings under the connected equipment. If piping is connected to equipment located in basements and hangs from ceilings under occupied spaces, the first 3 hangers shall have 0.75” nominal deflection or greater for pipe sizes up to and including 3,” 1 3/8” nominal deflection or greater for pipe sizes greater than

Page 25: PLUMBING, ELECTRICAL & FIRE PROTECTION COMPONENTS … · mechanical, electrical, plumbing and fire protection building system components in place during a seismic or high wind event

Permit Fairview Municipal Building 55 Anderson Ave.Fairview,NJ Issue December 31,2015

20 00 00-25 VIBRATION ISOLATION, SEISMIC, WIND & FLOOD LOAD RESTRAINTS FOR HVAC, PLUMBING, ELECTRICAL & FIRE PROTECTION COMPONENTS

25 of 33

3.” Where column spacing exceeds 35’, isolation hanger deflection shall be 2½” for pipes exceeding 3” diameter. Type L hangers may be substituted for the above where isolation hangers are required.

2. Plumbing Water Lines: Plumbing water lines in the machine room shall only be isolated if

connected to isolated equipment. (See Table B.) Isolator type shall be as listed in Article 1, above.

3. Riser Location: All risers shall be supported on Type J or K anchors or guide restraints

positively attached to both the riser and structure. Spiders welded to the pipe can substitute for Type K guides using J Type anchors.

4. Gas lines shall not be isolated.

5. Fire protection lines shall not be isolated.

B. Seismic Restraint of Piping, Conduit, Bus Duct and Cable Tray:

1. All high hazard and life safety pipe regardless of size such as fuel oil piping, fire protection

mains, gas piping, and piping with an Ip=1.5 shall be seismically restrained or braced. Type V seismic cable restraints or resilient single arm braces shall be used if piping is isolated. Type V seismic cable restraints or Type VI single arm braces may be used on non-isolated piping. There are no exclusions for size or distance in this category.

2. Seismically restrain piping, with an Ip = 1.0, located in boiler rooms, mechanical equipment

rooms and refrigeration equipment rooms that is 1¼” I.D. and larger. Type V seismic cable restraints or resilient single arm braces shall be used if piping is isolated. Type V seismic cable restraints or Type VI single arm braces may be used on non-isolated piping.

3. Seismically restrain all other piping 2½” diameter and larger. Type V seismic cable restraints

or resilient single arm braces shall be used if piping is isolated. Type VI seismic cable restraints or single arm braces may be used on non-isolated piping.

4. See Table D for maximum seismic bracing distances. 5. Multiple runs of pipe on the same support shall have distance determined by calculation. 6. Rod braces shall be used for all rod lengths as listed in Table E.

7. Clevis hangers shall have braces placed inside of hanger at seismic brace locations.

8. Where thermal expansion is a consideration, guides and anchors may be used as transverse

and longitudinal restraints provided they have a capacity equal to or greater than the restraint loads in addition to the loads induced by expansion or contraction.

9. For fuel oil and all gas piping, transverse restraints must be at 20’ maximum and longitudinal

restraints at 40’ maximum spacing.

10. Transverse restraint for one pipe section may also act as longitudinal restraint for a pipe

Page 26: PLUMBING, ELECTRICAL & FIRE PROTECTION COMPONENTS … · mechanical, electrical, plumbing and fire protection building system components in place during a seismic or high wind event

Permit Fairview Municipal Building 55 Anderson Ave.Fairview,NJ Issue December 31,2015

20 00 00-26 VIBRATION ISOLATION, SEISMIC, WIND & FLOOD LOAD RESTRAINTS FOR HVAC, PLUMBING, ELECTRICAL & FIRE PROTECTION COMPONENTS

26 of 33

section of the same or smaller size connected perpendicular to it if the restraint is installed within 24” of the centerline of the smaller pipe or combined stresses are within allowable limits at longer distances.

11. Hold down clamps must be used to attach pipe to all trapeze members before applying

restraints. Use Type V or VI restraint, if trapeze is smaller than 48” long.

12. Branch lines may not be used to restrain main lines or cross-mains.

13. All fire protection branch lines shall be end tied.

14. Where pipe passes through a fire-rated, seismic gypsum wall, the wall can act as a lateral/transverse brace for pipe sizes up to and including 6,” provided fire stopping material is tight to the pipe.

15. Where pipe passes through a seismic block or concrete wall, the wall can act as a

lateral/transverse brace.

16. Where horizontal pipe crosses a building’s drift expansion joint, allowance shall be part of the design to accommodate differential motion.

17. Vertical pipe rises between floors shall have their differential movement part of the seismic

design for building drift.

18. For horizontal passage of all underground utilities through building’s foundation wall, all pipes shall pass freely through an oversized opening and waterproofed accordingly to accommodate maximum allowable building drift. (Seismic Restraint Type VIII).

C. Vibration Isolation of Ductwork: Not Required

D. Seismic Restraint of Ductwork:

1. Restrain rectangular ductwork with cross sectional area of 6 square feet or larger. Type V

seismic cable restraints or Type VI single arm braces shall be used on this duct. Duct that serves a life safety function must be braced with no exceptions regardless of size or distance requirements.

2. See Table D for maximum seismic bracing distances. 3. Duct must be reinforced at the restraint locations. Reinforcement shall consist of an

additional angle on top of the ductwork that is attached to the support hanger rods. Ductwork is to be attached to both upper angle and lower trapeze. Additional reinforcing is not required if duct sections are mechanically fastened together with frame bolts and positively fastened to the duct support suspension system.

4. A group of ducts may be combined in a larger frame so that the combined weights and

dimensions of the ducts are less than or equal to the maximum weight and dimensions of the duct for which bracing details are selected.

Page 27: PLUMBING, ELECTRICAL & FIRE PROTECTION COMPONENTS … · mechanical, electrical, plumbing and fire protection building system components in place during a seismic or high wind event

Permit Fairview Municipal Building 55 Anderson Ave.Fairview,NJ Issue December 31,2015

20 00 00-27 VIBRATION ISOLATION, SEISMIC, WIND & FLOOD LOAD RESTRAINTS FOR HVAC, PLUMBING, ELECTRICAL & FIRE PROTECTION COMPONENTS

27 of 33

5. Walls, including gypsum board non-bearing partitions, which have ducts running through them, may replace a typical transverse brace. Provide channel framing around ducts and solid blocking between the duct and frame.

6. If ducts are supported by angles, channels or struts, ducts shall be fastened to it at seismic

brace locations in lieu of duct reinforcement.

EXEMPTIONS

(a) EQUIPMENT:

1. Curb-mounted mushroom, exhaust and vent fans with curb area less than nine square feet are excluded.

2. Floor or curb-mounted equipment weighing less than 400 lbs and not resiliently mounted, where the Importance Factor, Ip = 1.0 and there is no possibility of consequential damage.

3. Equipment weighing less than 20 lbs and distribution systems weighing less than 5 lbs/lineal foot, with an Ip = 1.0 and where flexible connections exist between the component and associated ductwork, piping or conduit.

4. Chain supported lighting fixtures as described in Section 13.6.1 (ASCE 7-05).

(b) DUCT (Applies to Ip = 1.0 only)

1. Rectangular, square, and oval air handling ducts less than six square feet in cross sectional area.

2. Round air handling duct less than 28 inches in diameter. 3. Duct runs supported at locations by two rods less than 12 inches in length

from the structural support to the structural connection to the ductwork. (c) PIPING and CONDUIT

1. All high deformability pipe or conduit 3” or less in diameter suspended by individual hanger rods where Ip = 1.0.

2. High deformability pipe or conduit in Seismic Design Category C, 2” or less in diameter suspended by individual hanger rods where Ip = 1.5.

3. High deformability pipe or conduit in Seismic Design Category D, E or F, 1” or less in diameter suspended by individual hanger rods where Ip = 1.5.

4. All clevis supported pipe or conduit runs installed less than 12” from the top of the pipe to the underside of the support point and trapeze supported pipe suspended by hanger rods having a distance less than 12” in length from the underside of the pipe support to the support point of the structure.

5. Piping systems, including their supports, designed and constructed in accordance with ASME B31.

6. Piping systems, including their supports, designed and constructed in accordance with NFPA, provided they meet the force and displacement requirements of Section 13.3.1 and 13.3.2 (ASCE 7-05).

EXEMPTIONS DO NOT APPLY FOR:

Page 28: PLUMBING, ELECTRICAL & FIRE PROTECTION COMPONENTS … · mechanical, electrical, plumbing and fire protection building system components in place during a seismic or high wind event

Permit Fairview Municipal Building 55 Anderson Ave.Fairview,NJ Issue December 31,2015

20 00 00-28 VIBRATION ISOLATION, SEISMIC, WIND & FLOOD LOAD RESTRAINTS FOR HVAC, PLUMBING, ELECTRICAL & FIRE PROTECTION COMPONENTS

28 of 33

(a) LIFE SAFETY or HIGH HAZARD COMPONENTS 1. Including gas, fire protection, medical gas, fuel oil and compressed air

needed for the continued operation of the facility or whose failure could impair the facility’s continued operation, Occupancy Category IV, IBC-2006 as listed in Section 1.1 C regardless of governing code for HVAC, Plumbing, Electrical piping or equipment. (A partial list is illustrated.) High Hazard is additionally classified as any system handling flammable, combustible or toxic material. Typical systems not excluded are additionally listed below.

(b) ELECTRICAL

1. Includes critical, standby or emergency power components including conduit (1” nominal diameter and larger) cable tray or bus duct, lighting, panels, communication lines involving 911, etc.

(c) PIPING

1. Fuel oil, gasoline, natural gas, medical gas, steam, compressed air or any piping containing hazardous, flammable, combustible, toxic or corrosive materials. Fire protection standpipe, risers and mains. Fire Sprinkler Branch Lines must be end tied.

(d) DUCT

1. Smoke evacuation or pressurization duct or fresh air make up connected to emergency system, emergency generator exhaust, boiler breeching or as used by the fire department on manual override.

(e) EQUIPMENT

1. Previously excluded non life safety duct mounted systems such as fans, variable air volume boxes, heat exchangers and humidifiers having a weight greater than 75 lbs require independent seismic bracing.

3.5 FIELD QUALITY CONTROL, INSPECTION

A. The following systems shall require special inspections conducted by the design professional and employed by this contractor for seismic installation and anchorage during construction.

(a) All smoke control systems require periodic special inspections during erection of ductwork prior to concealment for leakage testing. Additionally, prior to occupancy for pressure differential testing see IBC-2006 1704.14.

(b) All electrical components for standby or emergency power systems. (c) All flammable or combustible piping and their systems.

B. Upon completion of installation of all vibration isolation devices, the manufacturer’s chosen

representative shall inspect the completed project and certify in writing to the Contractor that all systems are installed properly, or list any that require correction. The contractor shall submit a report to the Architect, including the representative’s report, certifying correctness of the installation or detailing corrective work to be done.

Page 29: PLUMBING, ELECTRICAL & FIRE PROTECTION COMPONENTS … · mechanical, electrical, plumbing and fire protection building system components in place during a seismic or high wind event

Permit Fairview Municipal Building 55 Anderson Ave.Fairview,NJ Issue December 31,2015

20 00 00-29 VIBRATION ISOLATION, SEISMIC, WIND & FLOOD LOAD RESTRAINTS FOR HVAC, PLUMBING, ELECTRICAL & FIRE PROTECTION COMPONENTS

29 of 33

4.0 Selection Guide For Vibration Isolation and Seismic Restraint

*See Minimum Deflection Guide for Equipment with Low RPM

TABLE “A” HVAC EQUIPMENT ON GRADE, BASEMENT OR SLAB ON GRADE ABOVE GRADE

EQUIPMENT (See Notes) Size/Type Mtg Isol Nom

Defl* Base Restr Isol Nom Defl* Base Restr

Air Handling Units Indoor

Floor B 0.75 --- IV B 1.5 --- IV Ceiling --- --- --- --- E 0.75 --- V

Outdoor Condensing Units/Condensers Roof --- --- --- IV B 2.50

Minimum B-5 IV

Axial Fans (Inline Type)

Floor B 0.75 --- IV B See Guide --- IV Ceiling --- --- --- --- E See Guide --- V

Base Mounted Pumps To 15 HP Floor B 0.75 B-2 IV B 0.75 B-2 IV >15 HP Floor B 0.75 B-2 IV B 1.50 B-2 IV

Boilers Floor G 0.10 --- IV B 0.75 --- IV

Cabinet Fans & Packaged AHU

Indoor

To 1 HP Floor F 0.20 --- IV B 0.75 --- IV Ceiling --- --- --- --- E 0.75 --- V

>1 HP Floor B 0.75 --- IV B See Guide --- IV Ceiling --- --- --- --- E See Guide --- V

Centrifugal Fans Arr. 1 & 3

Class 1 Floor B 0.75 B-1 IV B See Guide B-1 IV Class 2 &

3 Floor B 0.75 B-2 IV B See Guide B-2 IV

Curb Mtd. Equip. (Non-Isol.) Roof --- --- --- IV --- --- B-6 ---

Rooftop AHU/AC (curb mounted)

< 10 Ton Roof --- --- --- IV B 1.50 B-3 See Notes 5,6 ---

> 10 Ton Roof --- --- --- IV B 2.50 B-3 See Notes 5,6 ---

Page 30: PLUMBING, ELECTRICAL & FIRE PROTECTION COMPONENTS … · mechanical, electrical, plumbing and fire protection building system components in place during a seismic or high wind event

Permit Fairview Municipal Building 55 Anderson Ave.Fairview,NJ Issue December 31,2015

20 00 00-30 VIBRATION ISOLATION, SEISMIC, WIND & FLOOD LOAD RESTRAINTS FOR HVAC, PLUMBING, ELECTRICAL & FIRE PROTECTION COMPONENTS

30 of 33

*Where Component cannot be point supported, Base Type B-1 shall be used. Minimum Deflection Guide for Equipment with Low RPM

Lowest RPM of Rotating Equipment

Minimum Actual Deflection

Less Than 400 3.5” 401 thru 600 2.5” 601 thru 900 1.5” Greater than 900 0.75”

TABLE “B” PLUMBING EQUIPMENT ON GRADE, BASEMENT OR SLAB ON GRADE ABOVE GRADE

EQUIPMENT (See Notes) HP Mtg Isol Defl Base Restr Isol Defl Base Restr

Base Mounted Pumps Up to 15 Floor B 0.75 B-2 IV B 0.75 B-2 IV Over 15 Floor B 0.75 B-2 IV B 1.50 B-2 IV

TABLE “C” ELECTRICAL EQUIPMENT ON GRADE, BASEMENT OR SLAB ON GRADE ABOVE GRADE

EQUIPMENT (See Notes) Size Mtg Isol Defl Base Restr Isol Defl Base Restr

Transformers (Dry Type) All

Floor --- --- --- IV D 0.30 * IV Ceiling --- --- --- V E 0.20 * V

Generators All Floor B 1.0 --- IV B 1.50 * IV

Generators All Over

Occupied Space

--- --- --- --- B 2.50 * IV

Page 31: PLUMBING, ELECTRICAL & FIRE PROTECTION COMPONENTS … · mechanical, electrical, plumbing and fire protection building system components in place during a seismic or high wind event

Permit Fairview Municipal Building 55 Anderson Ave.Fairview,NJ Issue December 31,2015

20 00 00-31 VIBRATION ISOLATION, SEISMIC, WIND & FLOOD LOAD RESTRAINTS FOR HVAC, PLUMBING, ELECTRICAL & FIRE PROTECTION COMPONENTS

31 of 33

General Notes for All Tables: 1. Abbreviations:

(1) Mtg = Mounting (2) Isol = Vibration Isolator Type per Section 2.2, Vibration Isolation Types (3) Defl = Minimum Deflection of Vibration Isolator (4) Base = Base Type per Section 2.4, Equipment Bases (5) Restr = Seismic Restraint Type per Section 2.3 Seismic Restraint Types

2. All deflections indicated are in inches.

3. For equipment with variable speed driven components having driven operating speed below

600 rpm, select isolation deflection from minimum deflection guide.

4. For roof applications, use base Type B-5.

5. Specification Option #1 called out on equipment schedule in curb Type B-3 shall use sound barrier RPFMA when there is no concrete under rooftop units and this option is selected. Curbs can be used for return plenums. (See Option #1 under curb type B-3.)

6. Specification Option #2, called out on equipment schedule in curb Type B-3 shall be used where curbs require supply and return sound attenuation package type SPFMA shall be used. (See Option #2 under curb type B-3.)

7. Units may not be capable of point support. Refer to separate air handling unit specification section. If that section does not provide base and external isolation is required, provide Type B-1 base by this section for entire unit.

8. Static deflection shall be determined based on the deflection guide for Table “A.”

9. Deflections indicated are minimums at actual load and shall be selected for manufacturer’s nominal 5,” 4,” 3,” 2” and 1” deflection spring series; RPM is defined as the lowest operating speed of the equipment.

10. Single stroke compressors may require inertia bases with thicknesses greater than 14” maximum as described for base B-2. Inertia base mass shall be sufficient to maintain double amplitude for 1/8.”

11. Floor mounted fans, substitute base Type B-2 for class 2 or 3 or any fan having static pressure over 5.”

12. Indoor utility sets with wheel diameters less than 24” need not have deflections greater than .75.”

13. Curb-mounted fans with curb area less than 9 square feet are excluded.

14. For equipment with multiple motors, Horsepower classification applies to largest single motor.

Page 32: PLUMBING, ELECTRICAL & FIRE PROTECTION COMPONENTS … · mechanical, electrical, plumbing and fire protection building system components in place during a seismic or high wind event

Permit Fairview Municipal Building 55 Anderson Ave.Fairview,NJ Issue December 31,2015

20 00 00-32 VIBRATION ISOLATION, SEISMIC, WIND & FLOOD LOAD RESTRAINTS FOR HVAC, PLUMBING, ELECTRICAL & FIRE PROTECTION COMPONENTS

32 of 33

15. When either note #s 3 or 4 apply to the project, type RPFMA option #1, or type SPFMA option#2 sound attenuation systems, the use of options #1 or #2 shall appear as a note clearly called out on the equipment schedule for either of these options to apply.

Page 33: PLUMBING, ELECTRICAL & FIRE PROTECTION COMPONENTS … · mechanical, electrical, plumbing and fire protection building system components in place during a seismic or high wind event

Permit Fairview Municipal Building 55 Anderson Ave.Fairview,NJ Issue December 31,2015

20 00 00-33 VIBRATION ISOLATION, SEISMIC, WIND & FLOOD LOAD RESTRAINTS FOR HVAC, PLUMBING, ELECTRICAL & FIRE PROTECTION COMPONENTS

33 of 33

4.1 Spacing Chart For Suspended Components

4.2 Vertical Hanger Rod Bracing Schedule

Table “E” Hanger Rod Bracing Schedule

(Stiffener to be maximum 6” from end of rod) Rod Dia. Clamp Size Maximum

Un-braced Rod Length

Steel Angle Size Clamp Spacing

Min # of Clamps per

Stiffener 3/8" SRBC-1-1/4 19" 1 x 1 x ¼" 16" 2 1/2" SRBC-1-1/4 25" 1 x 1 x ¼" 20" 2 5/8" SRBC-1-1/4 31" 1 x 1 x ¼" 24" 2 3/4" SRBC-1-1/2 37" 1 ½ x 1 ½ x ¼" 28" 2 7/8" SRBC-1-1/2 43" 1 ½ x 1 ½ x ¼" 33" 2 1" SRBC-1-1/2 50" 1 ½ x 1 ½ x ¼" 40" 2

1 1/8" SRBC-1-1/2 62" 1 ½ x 1 ½ x ¼" 50" 2 5.0 Contractor Responsibility

A. This contractor shall follow section 1706 of the 2006 IBC New Jersey Edition. END OF SECTION 20 00 00

Table “D” Seismic Bracing (Maximum Allowable Spacing Shown- Actual Spacing to Be Determined by Calculation)

Equipment

On Center Transverse On Center Longitudinal Change Of Direction

Duct All Sizes 30 Feet 60 Feet 4 Feet Pipe Threaded, Welded, Soldered Or Grooved; Conduit and Conduit Racks To 16” 40 Feet 80 Feet 4 Feet 18” – 28” 30 Feet 60 Feet 4 Feet 30” – 40” 20 Feet 60 Feet 4 Feet 42” & Larger 10 Feet 30 Feet 4 Feet Pipe - No Hub Or Bell And Spigot 2.5” & Larger 10 Feet 20 Feet 4 Feet Boiler Breeching 30 Feet 60 Feet 4 Feet Chimneys & Stacks 30 Feet 60 Feet 4 Feet Conduit 40 Feet 80 Feet 4 Feet Bus Duct 20 Feet 40 Feet 4 Feet Cable Tray 40 Feet 80 Feet 4 Feet

Page 34: PLUMBING, ELECTRICAL & FIRE PROTECTION COMPONENTS … · mechanical, electrical, plumbing and fire protection building system components in place during a seismic or high wind event

Permit Fairview Municipal Building 55 Anderson Ave. Fairview, NJ Issue December 31,2015

21 00 00 - Fire-Suppression Sprinklers

SECTION 21 00 00 - FIRE-SUPPRESSION SPRINKLERS

PART 1 - GENERAL

1.1 RELATED DOCUMENTS

A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to this Section.

1.2 SUMMARY

A. This Section includes fire-suppression sprinklers, piping, and equipment for the following building systems:

1. Wet-pipe, fire-suppression sprinklers, including piping, valves, specialties, and automatic sprinklers.

2. Dry-pipe, fire-suppression sprinklers, including piping, valves, specialties, automatic sprinklers, air compressor, and accessories.

1.3 DEFINITIONS

A. Working Plans: Documents, including drawings, calculations, and material specifications prepared according to NFPA 13 for obtaining approval from authorities having jurisdiction.

1.4 SYSTEM PERFORMANCE REQUIREMENTS

A. Design sprinklers and obtain approval from authorities having jurisdiction.

B. Design sprinkler piping according to the following and obtain approval from authorities having jurisdiction: 1. Include 20 percent margin of safety for available water flow and pressure. 2. Include losses through water-service piping, valves, and backflow preventers. 3. Sprinkler Occupancy Hazard Classifications: As follows:

a. Parking Garage: Ordinary Hazard, Group 1. (Dry) b. Electrical Equipment Rooms: Ordinary Hazard, Group 1. c. Building Service and Storage Areas: Ordinary Hazard, Group 1. d. Mechanical Equipment Rooms: Ordinary Hazard, Group 1. e. Office and Public Areas: Light Hazard. f. Residential Living Areas: Light Hazard. g. Retail: Light Hazard.

4. Minimum Density for Automatic-Sprinkler Piping Design: As follows:

Page 35: PLUMBING, ELECTRICAL & FIRE PROTECTION COMPONENTS … · mechanical, electrical, plumbing and fire protection building system components in place during a seismic or high wind event

Permit Fairview Municipal Building 55 Anderson Ave. Fairview, NJ Issue December 31,2015

21 00 00 - Fire-Suppression Sprinklers

a. Light-Hazard Occupancy: 0.10 gpm over 1500-sq. ft. area. b. Ordinary-Hazard, Group 1 Occupancy: 0.15 gpm over 1500-sq. ft. area.

5. Maximum Protection Area per Sprinkler: As follows:

a. Light Hazard: 225 sq. ft. b. Ordinary Hazard Group 1: 130 sq. ft.

C. Components and Installation: Capable of producing piping systems with 175-psig minimum working-pressure rating, unless otherwise indicated.

1.5 SUBMITTALS

A. Product Data: For the following:

1. Pipe and fitting materials and methods of joining for sprinkler piping. 2. Pipe hangers and supports. 3. Piping seismic restraints. 4. Valves, including specialty valves, accessories, and devices. 5. Alarm devices. Include electrical data. 6. Air compressors. Include electrical data. 7. Fire department connections. Include type; number, size, and arrangement of inlets; caps

and chains; size and direction of outlet; escutcheon and marking; and finish. 8. Sprinklers, escutcheons, and guards. Include sprinkler flow characteristics, mounting,

finish, and other pertinent data.

B. Fire-Hydrant Flow Test Report:

C. Approved Sprinkler Piping Drawings: Working plans, prepared according to NFPA 13, that have been approved by authorities having jurisdiction. Include hydraulic calculations, if applicable.

D. Field Test Reports and Certificates: Indicate and interpret test results for compliance with performance requirements and as described in NFPA 13. Include "Contractor's Material and Test Certificate for Aboveground Piping" and "Contractor's Material and Test Certificate for Underground Piping."

E. Maintenance Data: For each type of sprinkler specialty to include in maintenance manuals specified in Division 1.

1.6 QUALITY ASSURANCE

A. Installer Qualifications: An experienced installer who has designed and installed fire-suppression piping similar to that indicated for this Project and obtained design approval and inspection approval from authorities having jurisdiction.

B. Engineering Responsibility: Preparation of working plans, calculations, and field test reports by a qualified professional engineer hired by the contractor. Base calculations on results of fire-hydrant flow test.

Page 36: PLUMBING, ELECTRICAL & FIRE PROTECTION COMPONENTS … · mechanical, electrical, plumbing and fire protection building system components in place during a seismic or high wind event

Permit Fairview Municipal Building 55 Anderson Ave. Fairview, NJ Issue December 31,2015

21 00 00 - Fire-Suppression Sprinklers

C. Professional Engineer Qualifications: A professional engineer who is legally qualified to practice in jurisdiction where Project is located and who is experienced in providing engineering services of the kind indicated. Engineering services are defined as those performed for installations of fire-suppression piping that are similar to those indicated for this Project in material, design, and extent.

D. Manufacturer Qualifications: Firms whose equipment, specialties, and accessories are listed by product name and manufacturer in UL's "Fire Protection Equipment Directory" and FM's "Fire Protection Approval Guide" and that comply with other requirements indicated.

E. Sprinkler Components: Listing/approval stamp, label, or other marking by a testing agency acceptable to authorities having jurisdiction.

F. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, Article 100, by a testing agency acceptable to authorities having jurisdiction.

G. NFPA Standards: Equipment, specialties, accessories, installation, and testing complying with the following:

1. NFPA 13, "Installation of Sprinkler Systems."

END OF SECTION 21 00 00

Page 37: PLUMBING, ELECTRICAL & FIRE PROTECTION COMPONENTS … · mechanical, electrical, plumbing and fire protection building system components in place during a seismic or high wind event

Permit Fairview Municipal Building 55 Anderson Ave. Fairview, NJ Issue December 31, 2015

21 12 00- Standpipes and Hoses

SECTION 21 12 00 - STANDPIPES AND HOSES

PART 1 - GENERAL

1.1 RELATED DOCUMENTS

A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to this Section.

1.2 SUMMARY

A. This Section includes piping and equipment for the following building systems:

1. Automatic dry-type, Class I standpipes. 2. Automatic wet-type, Class I standpipes.

1.3 DEFINITIONS

A. Hose Connection: Valve with threaded outlet matching fire hose coupling thread for attaching fire hose.

B. Working Plans: Documents, including drawings, calculations, and material specifications prepared according to NFPA 14 for obtaining approval from authorities having jurisdiction.

1.4 SYSTEM PERFORMANCE REQUIREMENTS

A. Design standpipes and obtain approval from authorities having jurisdiction. Include minimum residual pressures at hydraulically remote outlets according to the following:

1. NPS 2-1/2 Hose Connections: 100 psig.

B. Components and Installation: Capable of producing piping systems with 175-psig minimum working-pressure rating, unless otherwise indicated.

1.5 SUBMITTALS

A. Product Data: For the following:

1. Pipe and fitting materials and methods of joining for standpipe piping. 2. Pipe hangers and supports. 3. Piping seismic restraints. 4. Valves, including specialty valves, accessories, and devices.

Page 38: PLUMBING, ELECTRICAL & FIRE PROTECTION COMPONENTS … · mechanical, electrical, plumbing and fire protection building system components in place during a seismic or high wind event

Permit Fairview Municipal Building 55 Anderson Ave. Fairview, NJ Issue December 31, 2015

21 12 00- Standpipes and Hoses

5. Alarm devices. Include electrical data. 6. Air compressors. Include electrical data. 7. Fire department connections. Include type; number, size, and arrangement of inlets; caps

and chains; size and direction of outlet; escutcheon and marking; and finish. 8. Hose connections. Include size, type, and finish.

B. Fire-Hydrant Flow Test Report - Field Test Reports and Certificates: Indicate and interpret test results for compliance with performance requirements and as described in NFPA 14. Include "Contractor's Material and Test Certificate for Aboveground Piping" and "Contractor's Material and Test Certificate for Underground Piping."

C. Maintenance Data: For each type of standpipe specialty to include in maintenance manuals specified in Division 1.

1.6 QUALITY ASSURANCE

A. Installer Qualifications: An experienced installer who has designed and installed fire-suppression piping similar to that indicated for this Project and obtained design approval and inspection approval from authorities having jurisdiction.

B. Engineering Responsibility: Preparation of working plans, calculations, and field test reports by a qualified professional engineer hired by the contractor. Base calculations on results of fire-hydrant flow test.

C. Professional Engineer Qualifications: A professional engineer who is legally qualified to practice in jurisdiction where Project is located and who is experienced in providing engineering services of the kind indicated. Engineering services are defined as those performed for installations of fire-suppression piping that are similar to those indicated for this Project in material, design, and extent.

D. Manufacturer Qualifications: Firms whose equipment, specialties, and accessories are listed by product name and manufacturer in UL's "Fire Protection Equipment Directory" and FM's "Fire Protection Approval Guide" and that comply with other requirements indicated.

E. Standpipe Components: Listing/approval stamp, label, or other marking by a testing agency acceptable to authorities having jurisdiction.

F. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, Article 100, by a testing agency acceptable to authorities having jurisdiction.

G. NFPA Standard: Equipment, specialties, accessories, installation, and testing complying with NFPA 14, "Standpipe and Hose Systems."

END OF SECTION 21 12 00

Page 39: PLUMBING, ELECTRICAL & FIRE PROTECTION COMPONENTS … · mechanical, electrical, plumbing and fire protection building system components in place during a seismic or high wind event

Permit Fairview Municipal Building 55 Anderson Ave. Fairview, NJ Issue December 31, 2015

22 05 00-1 PLUMBING SPECIALTIES 1 of 13

SECTION 22 05 00 PLUMBING SPECIALTIES

PART 1 - GENERAL

1.1 RELATED DOCUMENTS

A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to this Section.

1.2 SUMMARY

A. This Section includes the following plumbing specialties:

1. Backflow preventers. 2. Dishwasher air-gap fittings. 3. Balancing valves. 4. Thermostatic water mixing valves. 5. Strainers. 6. Outlet boxes. 7. Drain valves. 8. Miscellaneous piping specialties. 9. Sleeve penetration systems. 10. Flashing materials. 11. Cleanouts. 12. Floor drains. 13. Trench drains. 14. Roof drains.

B. Related Sections include the following:

1. Division 23 Section "Meters and Gauges" for water meters, thermometers, and pressure gauges.

1.3 DEFINITIONS

A. The following are industry abbreviations for plastic piping materials:

1. ABS: Acrylonitrile-butadiene-styrene plastic. 2. PE: Polyethylene plastic. 3. PUR: Polyurethane plastic. 4. PVC: Polyvinyl chloride plastic.

1.4 PERFORMANCE REQUIREMENTS

Page 40: PLUMBING, ELECTRICAL & FIRE PROTECTION COMPONENTS … · mechanical, electrical, plumbing and fire protection building system components in place during a seismic or high wind event

Permit Fairview Municipal Building 55 Anderson Ave. Fairview, NJ Issue December 31, 2015

22 05 00-2 PLUMBING SPECIALTIES 2 of 13

A. Provide components and installation capable of producing piping systems with following minimum working-pressure ratings, unless otherwise indicated:

1. Domestic Water Piping: 250 psig. 2. Sanitary Waste and Vent Piping: 10-foot head of water. 3. Storm Drainage Piping: 10-foot head of water. 4. Force-Main Piping: 100 psig.

1.5 SUBMITTALS

A. Product Data: Include rated capacities and shipping, installed, and operating weights. Indicate materials, finishes, dimensions, required clearances, and methods of assembly of components; and piping and wiring connections for the following:

1. Backflow preventers and water regulators. 2. Balancing valves and strainers. 3. Thermostatic water mixing valves. 4. Water hammer arresters, air vents. 5. Drain valves. 6. Outlet boxes and washer-supply outlets. 7. Cleanouts, floor drains, open receptors, trench drains, and roof drains. 8. Air-admittance valves, vent caps, vent terminals, and roof flashing assemblies. 9. Sleeve penetration systems.

B. Field test reports.

C. Maintenance Data: For plumbing specialties to include in maintenance manuals. Include the following:

1. Backflow preventers and water regulators. 2. Thermostatic water mixing valves.

1.6 QUALITY ASSURANCE

A. Product Options: Drawings indicate size, profiles, and dimensional requirements of plumbing specialties and are based on the specific system indicated. Refer to Division 1 Section "Product Requirements."

B. Plumbing specialties shall bear label, stamp, or other markings of specified testing agency.

C. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, Article 100, by a testing agency acceptable to authorities having jurisdiction, and marked for intended use.

D. ASME Compliance: Comply with ASME B31.9, "Building Services Piping," for piping materials and installation.

E. NSF Compliance:

Page 41: PLUMBING, ELECTRICAL & FIRE PROTECTION COMPONENTS … · mechanical, electrical, plumbing and fire protection building system components in place during a seismic or high wind event

Permit Fairview Municipal Building 55 Anderson Ave. Fairview, NJ Issue December 31, 2015

22 05 00-3 PLUMBING SPECIALTIES 3 of 13

1. Comply with NSF 14, "Plastics Piping Components and Related Materials," for plastic domestic water piping components. Include marking "NSF-pw" on plastic potable-water piping and "NSF-dwv" on plastic drain, waste, and vent piping.

2. Comply with NSF 61, "Drinking Water System Components--Health Effects, Sections 1 through 9," for potable domestic water plumbing specialties.

1.7 EXTRA MATERIALS

A. Furnish extra materials described below that match products installed and that are packaged with protective covering for storage and identified with labels describing contents.

1. Water Filter Cartridges: Equal to 200 percent of amount installed for each type and size indicated.

2. Operating Key Handles: Equal to 100 percent of amount installed for each key-operated hose bibb and hydrant installed.

PART 2 - PRODUCTS

2.1 MANUFACTURERS

A. In other Part 2 articles where subparagraph titles below introduce lists, the following requirements apply for product selection:

1. Available Manufacturers: Subject to compliance with requirements, manufacturers

offering products that may be incorporated into the Work include, but are not limited to, the manufacturers specified.

2.2 BACKFLOW PREVENTERS

A. Manufacturers:

1. Ames Co., Inc. 2. B & K Industries, Inc. 3. Cla-Val Co. 4. CMB Industries, Inc.; Febco Backflow Preventers. 5. Conbraco Industries, Inc. 6. FLOMATIC Corp. 7. IMI Cash Valve. 8. Mueller Co.; Hersey Meters Div. 9. Sparco, Inc. 10. Watts Industries, Inc.; Water Products Div. 11. Zurn Industries, Inc.; Wilkins Div.

B. General: ASSE standard, backflow preventers.

1. NPS 2 and Smaller: Bronze body with threaded ends.

Page 42: PLUMBING, ELECTRICAL & FIRE PROTECTION COMPONENTS … · mechanical, electrical, plumbing and fire protection building system components in place during a seismic or high wind event

Permit Fairview Municipal Building 55 Anderson Ave. Fairview, NJ Issue December 31, 2015

22 05 00-4 PLUMBING SPECIALTIES 4 of 13

2. NPS 2-1/2 and Larger: Bronze, cast-iron, steel, or stainless-steel body with flanged ends.

a. Interior Lining: AWWA C550 or FDA-approved, epoxy coating for backflow preventers having cast-iron or steel body.

3. Interior Components: Corrosion-resistant materials. 4. Exterior Finish: Polished chrome plate if used in chrome-plated piping system. 5. Strainer: On inlet, if indicated.

C. Reduced-Pressure-Principle Backflow Preventers: ASSE 1013, suitable for continuous pressure application. Include outside screw and yoke gate valves on inlet and outlet, and strainer on inlet; test cocks; and pressure-differential relief valve with ASME A112.1.2 air-gap fitting located between two positive-seating check valves.

1. Pressure Loss: 12 psig maximum, through middle 1/3 of flow range.

D. Double-Check Backflow Prevention Assemblies: ASSE 1015, suitable for continuous pressure application. Include shutoff valves on inlet and outlet, and strainer on inlet; test cocks; and two positive-seating check valves.

1. Pressure Loss: 5 psig maximum, through middle 1/3 of flow range.

E. Reduced-Pressure Detector Assembly Backflow Preventers: ASSE 1047, FM approved or UL listed, and suitable for continuous pressure application. Include outside screw and yoke gate valves on inlet and outlet, and strainer on inlet. Include test cocks; pressure-differential relief valve with ASME A112.1.2 air-gap fitting located between two positive-seating check valves; and bypass with displacement-type water meter, valves, and reduced-pressure backflow preventer.

1. Pressure Loss: 12 psig (83 kPa) maximum, through middle 1/3 of flow range.

F. Double-Check Detector Assembly Backflow Preventers: ASSE 1048, FM approved or UL listed, and suitable for continuous pressure application. Include outside screw and yoke gate valves on inlet and outlet, and strainer on inlet. Include test cocks; two positive-seating check valves; and bypass with displacement-type water meter, valves, and double-check backflow preventer.

1. Pressure Loss: 5 psig (35 kPa) maximum, through middle 1/3 of flow range.

2.3 DISHWASHER AIR-GAP FITTINGS

A. Description: ASSE 1021, fitting suitable for use with domestic dishwashers and for deck mounting; with plastic body, chrome-plated brass cover; and capacity of at least 5 gpm; and inlet pressure of at least 5 psig at temperature of at least 140 deg F (60 deg C). Include 5/8-inch- ID inlet and 7/8-inch- ID outlet hose connections.

B. Hoses: Rubber and suitable for temperature of at least 140 deg F.

1. Inlet Hose: 5/8-inch- ID and 48 inches long. 2. Outlet Hose: 7/8-inch- ID and 48 inches long.

Page 43: PLUMBING, ELECTRICAL & FIRE PROTECTION COMPONENTS … · mechanical, electrical, plumbing and fire protection building system components in place during a seismic or high wind event

Permit Fairview Municipal Building 55 Anderson Ave. Fairview, NJ Issue December 31, 2015

22 05 00-5 PLUMBING SPECIALTIES 5 of 13

2.4 BALANCING VALVES

A. Calibrated Balancing Valves: Adjustable, with two readout ports and memory setting indicator. Include manufacturer's standard hoses, fittings, valves, differential pressure meter, and carrying case.

1. Manufacturers:

a. Amtrol, Inc. b. Armstrong Pumps, Inc. c. Armstrong-Yoshitake, Inc. d. Flow Design, Inc. e. ITT Industries; Bell & Gossett Div. f. ROMAC Industries, Inc.; Hays Fluid Control Div. g. Taco, Inc. h. Tour & Andersson, Inc. i. Watts Industries, Inc.; Water Products Div.

2. NPS 2 and Smaller: Bronze body with brass ball, adjustment knob, calibrated nameplate, and threaded or solder-joint ends.

3. NPS 2-1/2 and Larger: Cast-iron, Y-pattern body with bronze disc and flanged or grooved ends.

B. Memory-Stop Balancing Valves, NPS 2 and Smaller: MSS SP-110, ball valve, rated for 400-psig minimum CWP. Include two-piece, copper-alloy body with standard or full-port, chrome-plated brass ball, replaceable seats and seals, threaded or solder-joint ends, and vinyl-covered steel handle with memory-stop device.

1. Manufacturers:

a. Conbraco Industries, Inc. b. Crane Co.; Crane Valve Group; Crane Valves. c. Crane Co.; Crane Valve Group; Jenkins Valves. d. Crane Co.; Crane Valve Group; Stockham Div. e. Grinnell Corporation. f. Hammond Valve. g. Milwaukee Valve Company. h. NIBCO INC. i. Red-White Valve Corp.

2.5 THERMOSTATIC WATER MIXING VALVES

A. Manufacturers:

1. Lawler Manufacturing Company, Inc. 2. Leonard Valve Company. 3. Mark Controls Corp.; Powers Process Controls. 4. Symmons Industries, Inc.

Page 44: PLUMBING, ELECTRICAL & FIRE PROTECTION COMPONENTS … · mechanical, electrical, plumbing and fire protection building system components in place during a seismic or high wind event

Permit Fairview Municipal Building 55 Anderson Ave. Fairview, NJ Issue December 31, 2015

22 05 00-6 PLUMBING SPECIALTIES 6 of 13

5. T & S Brass and Bronze Works, Inc.

B. General: ASSE 1017, manually adjustable, thermostatic water mixing valve with bronze body. Include check stop and union on hot- and cold-water-supply inlets, adjustable temperature setting, and thermometer.

1. Type: Bimetal thermostat, operation and pressure rating 125 psig (860 kPa) minimum.

2.6 STRAINERS

A. Strainers: Y-pattern, unless otherwise indicated, and full size of connecting piping. Include ASTM A 666, Type 304, stainless-steel screens with 3/64-inch round perforations, unless otherwise indicated.

1. Pressure Rating: 125-psig minimum steam working pressure, unless otherwise indicated. 2. NPS 2 and Smaller: Bronze body, with female threaded ends. 3. NPS 2-1/2 and Larger: Cast-iron body, with interior AWWA C550 or FDA-approved,

epoxy coating and flanged ends. 4. Y-Pattern Strainers: Screwed screen retainer with centered blowdown.

a. Drain: Factory- or field-installed, hose-end drain valve.

2.7 OUTLET BOXES

A. Available Manufacturers:

B. Manufacturers:

1. Acorn Engineering Company. 2. Gray, Guy Manufacturing Co., Inc. 3. IPS Corporation. 4. LSP Products Group. 5. Oatey. 6. Plastic Oddities, Inc. 7. Symmons Industries, Inc. 8. Zurn Industries, Inc.; Jonespec Div.

C. General: Recessed-mounting outlet boxes with supply fittings complying with ASME A112.18.1M. Include box with faceplate, services indicated for equipment connections, and wood-blocking reinforcement.

D. Icemaker Outlet Boxes: With hose connection and the following:

1. Box and Faceplate: Plastic. 2. Shutoff Fitting: Hose bibb. 3. Supply Fitting: NPS 1/2 gate, globe, or ball valve and NPS 1/2 (DN 15) copper, water

tubing.

Page 45: PLUMBING, ELECTRICAL & FIRE PROTECTION COMPONENTS … · mechanical, electrical, plumbing and fire protection building system components in place during a seismic or high wind event

Permit Fairview Municipal Building 55 Anderson Ave. Fairview, NJ Issue December 31, 2015

22 05 00-7 PLUMBING SPECIALTIES 7 of 13

2.8 DRAIN VALVES

A. Hose-End Drain Valves: MSS SP-110, NPS 3/4 ball valve, rated for 400-psig minimum CWP. Include two-piece, copper-alloy body with standard port, chrome-plated brass ball, replaceable seats and seals, blowout-proof stem, and vinyl-covered steel handle.

1. Inlet: Threaded or solder joint. 2. Outlet: Short-threaded nipple with ASME B1.20.7, garden-hose threads and cap.

B. Hose-End Drain Valve: MSS SP-80, gate valve, Class 125, ASTM B 62 bronze body, with NPS 3/4 threaded or solder-joint inlet and ASME B1.20.7, garden-hose threads on outlet and cap. Hose bibbs are prohibited for this application.

C. Stop-and-Waste Drain Valves: MSS SP-110, ball valve, rated for 200-psig minimum CWP or MSS SP-80, Class 125, gate valve; ASTM B 62 bronze body, with NPS 1/8 side drain outlet and cap.

2.9 MISCELLANEOUS PIPING SPECIALTIES

A. Hose Bibbs: Bronze body with replaceable seat disc complying with ASME A112.18.1M for compression-type faucets. Include NPS 1/2 or NPS 3/4 (DN 15 or DN 20) threaded or solder-joint inlet, of design suitable for pressure of at least 125 psig (860 kPa); integral or field-installed, nonremovable, drainable hose-connection vacuum breaker; and garden-hose threads complying with ASME B1.20.7 on outlet.

1. Finish for Equipment Rooms: Rough bronze, or chrome or nickel plated. 2. Finish for Service Areas: Rough bronze. 3. Finish for Finished Rooms: Chrome or nickel plated. 4. Operation for Equipment Rooms: Wheel handle or operating key. 5. Operation for Service Areas: Wheel handle. 6. Operation for Finished Rooms: Wheel handle. 7. Include operating key with each operating-key hose bibb. 8. Include integral wall flange with each chrome- or nickel-plated hose bibb.

B. Air Vents: Float type for automatic air venting.

1. Bolted Construction: Bronze body with replaceable, corrosion-resistant metal float and stainless-steel mechanism and seat; threaded NPS 3/8 (DN 10) minimum inlet; 125-psig (860-kPa) minimum pressure rating at 140 deg F (60 deg C); and threaded vent outlet.

2. Welded Construction: Stainless-steel body with corrosion-resistant metal float, stainless-steel mechanism and seat, threaded NPS 3/8 (DN 10) minimum inlet, 150-psig (1035-kPa) minimum pressure rating, and threaded vent outlet.

C. Roof Flashing Assemblies: Manufactured assembly made of .060 spun Aluminum base with EPDM Cap. Made Weather tite with a grove & bead pressure seal, and lead flashing collar and skirt extending at least 6 inches (150 mm) from pipe with galvanized steel boot reinforcement, and counterflashing fitting.

1. Available Manufacturers: 2. Manufacturers:

Page 46: PLUMBING, ELECTRICAL & FIRE PROTECTION COMPONENTS … · mechanical, electrical, plumbing and fire protection building system components in place during a seismic or high wind event

Permit Fairview Municipal Building 55 Anderson Ave. Fairview, NJ Issue December 31, 2015

22 05 00-8 PLUMBING SPECIALTIES 8 of 13

a. RPS Corporation

b. Portals Plus

D. Deep-Seal Traps: Cast-iron or bronze casting, with inlet and outlet matching connected piping and cleanout trap seal primer valve connection.

1. NPS 2: 4-inch- minimum water seal. 2. NPS 2-1/2 and Larger: 5-inch- minimum water seal.

E. Stack Flashing Fittings: Counterflashing-type, cast-iron fitting, with bottom recess for terminating roof membrane, and with threaded or hub top for extending vent pipe.

F. Vent Terminals: Commercially manufactured, shop- or field-fabricated, frost-proof assembly constructed of galvanized steel, copper, or lead-coated copper. Size to provide 1-inch (25-mm) enclosed air space between outside of pipe and inside of flashing collar extension, with counterflashing.

2.10 SLEEVE PENETRATION SYSTEMS

A. Available Manufacturers:

B. Manufacturers:

1. ProSet Systems, Inc.

2. 3m Fire Protection Products

C. Description: UL 1479, through-penetration firestop assembly consisting of sleeve and stack fitting with firestopping plug.

1. Sleeve: Molded PVC plastic, of length to match slab thickness and with integral nailing flange on one end for installation in cast-in-place concrete slabs.

2. Stack Fitting: ASTM A 48 (ASTM A 48M), gray-iron, hubless-pattern, wye-branch stack fitting with neoprene O-ring at base and gray-iron plug in thermal-release harness in branch. Include PVC protective cap for plug.

a. Special Coating: Include corrosion-resistant interior coating on fittings for plastic chemical waste and vent stacks.

2.11 FLASHING MATERIALS

A. Lead Sheet: ASTM B 749, Type L51121, copper bearing, with the following minimum weights and thicknesses, unless otherwise indicated:

1. General Use: 4-lb/sq. ft., 0.0625-inch thickness. 2. Vent Pipe Flashing: 3-lb/sq. ft., 0.0469-inch thickness. 3. Burning: 6-lb/sq. ft., 0.0938-inch thickness.

Page 47: PLUMBING, ELECTRICAL & FIRE PROTECTION COMPONENTS … · mechanical, electrical, plumbing and fire protection building system components in place during a seismic or high wind event

Permit Fairview Municipal Building 55 Anderson Ave. Fairview, NJ Issue December 31, 2015

22 05 00-9 PLUMBING SPECIALTIES 9 of 13

B. Copper Sheet: ASTM B 152 (ASTM B 152M), of the following minimum weights and thicknesses, unless otherwise indicated:

1. General Applications: 12 oz./sq. ft. 2. Vent Pipe Flashing: 8 oz./sq. ft.

C. Zinc-Coated Steel Sheet: ASTM A 653/A 653M, with 0.20 percent copper content and 0.04-inch minimum thickness, unless otherwise indicated. Include G90 hot-dip galvanized, mill-phosphatized finish for painting if indicated.

D. Elastic Membrane Sheet: ASTM D 4068, flexible, chlorinated polyethylene, 40-mil minimum thickness.

E. Fasteners: Metal compatible with material and substrate being fastened.

F. Metal Accessories: Sheet metal strips, clamps, anchoring devices, and similar accessory units required for installation; matching or compatible with material being installed.

G. Solder: ASTM B 32, lead-free alloy.

H. Bituminous Coating: SSPC-Paint 12, solvent-type, bituminous mastic.

PART 3 - EXECUTION

3.1 INSTALLATION

A. Refer to Division 23 for piping joining materials, joint construction, and basic installation requirements.

B. Install backflow preventers in each water supply to mechanical equipment and systems and to other equipment and water systems that may be sources of contamination. Comply with authorities having jurisdiction.

1. Locate backflow preventers in same room as connected equipment or system. 2. Install drain for backflow preventers with atmospheric-vent drain connection with air-gap

fitting, fixed air-gap fitting, or equivalent positive pipe separation of at least two pipe diameters in drain piping and pipe to floor drain. Locate air-gap device attached to or under backflow preventer. Simple air breaks are not acceptable for this application.

3. Do not install bypass piping around backflow preventers.

C. Install pressure regulators with inlet and outlet shutoff valves and balance valve bypass. Install pressure gages on inlet and outlet.

D. Install strainers on supply side of each control valve, pressure regulator, and solenoid valve.

E. Install cleanouts in aboveground piping and building drain piping according to the following, unless otherwise indicated:

Page 48: PLUMBING, ELECTRICAL & FIRE PROTECTION COMPONENTS … · mechanical, electrical, plumbing and fire protection building system components in place during a seismic or high wind event

Permit Fairview Municipal Building 55 Anderson Ave. Fairview, NJ Issue December 31, 2015

22 05 00-10 PLUMBING SPECIALTIES 10 of 13

1. Size same as drainage piping up to NPS 4. Use NPS 4 for larger drainage piping unless larger cleanout is indicated.

2. Locate at each change in direction of piping greater than 45 degrees. 3. Locate at minimum intervals of 50 feet for piping NPS 4 and smaller and 100 feet for

larger piping. 4. Locate at base of each vertical soil and waste stack.

F. Install cleanout deck plates with top flush with finished floor, for floor cleanouts for piping below floors.

G. Install cleanout wall access covers, of types indicated, with frame and cover flush with finished wall, for cleanouts located in concealed piping.

H. Install flashing flange and clamping device with each stack and cleanout passing through floors with waterproof membrane.

I. Install vent flashing sleeves on stacks passing through roof. Secure over stack flashing according to manufacturer's written instructions.

J. Install frost-proof vent caps on each vent pipe passing through roof. Maintain 1-inch (25-mm) clearance between vent pipe and roof substrate.

K. Install floor drains at low points of surface areas to be drained. Set grates of drains flush with finished floor, unless otherwise indicated.

1. Position floor drains for easy access and maintenance. 2. Set floor drains below elevation of surrounding finished floor to allow floor drainage.

Set with grates depressed according to the following drainage area radii:

a. Radius, 30 Inches or Less: Equivalent to 1 percent slope, but not less than 1/4-inch total depression.

b. Radius, 30 to 60 Inches: Equivalent to 1 percent slope. c. Radius, 60 Inches or Larger: Equivalent to 1 percent slope, but not greater than 1-

inch total depression.

3. Install floor-drain flashing collar or flange so no leakage occurs between drain and adjoining flooring. Maintain integrity of waterproof membranes where penetrated.

4. Install individual traps for floor drains connected to sanitary building drain, unless otherwise indicated.

L. Install roof drains at low points of roof areas according to roof membrane manufacturer's written installation instructions.

1. Install roof-drain flashing collar or flange so no leakage occurs between drain and adjoining roofing. Maintain integrity of waterproof membranes where penetrated.

2. Position roof drains for easy access and maintenance.

M. Fasten wall-hanging plumbing specialties securely to supports attached to building substrate if supports are specified and to building wall construction if no support is indicated.

N. Fasten recessed-type plumbing specialties to reinforcement built into walls.

Page 49: PLUMBING, ELECTRICAL & FIRE PROTECTION COMPONENTS … · mechanical, electrical, plumbing and fire protection building system components in place during a seismic or high wind event

Permit Fairview Municipal Building 55 Anderson Ave. Fairview, NJ Issue December 31, 2015

22 05 00-11 PLUMBING SPECIALTIES 11 of 13

O. Install wood-blocking reinforcement for wall-mounting and recessed-type plumbing specialties.

P. Install individual shutoff valve in each water supply to plumbing specialties. Use ball, gate, or globe valve if specific valve is not indicated. Install shutoff valves in accessible locations. Refer to Division 23 Section "Valves" for general-duty ball, butterfly, check, gate, and globe valves.

Q. Install air vents at piping high points. Include ball, gate, or globe valve in inlet and drain piping from outlet to floor drain.

R. Install traps on plumbing specialty drain outlets. Omit traps on indirect wastes unless trap is indicated.

S. Install escutcheons at wall, floor, and ceiling penetrations in exposed finished locations and within cabinets and millwork. Use deep-pattern escutcheons if required to conceal protruding pipe fittings.

3.2 CONNECTIONS

A. Piping installation requirements are specified in other Division 23 Sections. Drawings indicate general arrangement of piping, fittings, and specialties.

B. Install piping adjacent to equipment to allow service and maintenance.

C. Connect plumbing specialties to piping specified in other Division 22 Sections.

D. Ground equipment.

E. Tighten electrical connectors and terminals according to manufacturer's published torque-tightening values. If manufacturer's torque values are not indicated, use those specified in UL 486A and UL 486B.

F. Connect plumbing specialties and devices that require power according to Division 22 Sections.

3.3 FLASHING INSTALLATION

A. Fabricate flashing from single piece unless large pans, sumps, or other drainage shapes are required. Join flashing according to the following if required:

1. Lead Sheets: Burn joints of lead sheets 6-lb/sq. ft., 0.0938-inch thickness or thicker. Solder joints of lead sheets 4-lb/sq. ft., 0.0625-inch thickness or thinner.

2. Copper Sheets: Solder joints of copper sheets.

B. Install sheet flashing on pipes, sleeves, and specialties passing through or embedded in floors and roofs with waterproof membrane.

1. Pipe Flashing: Sleeve type, matching pipe size, with minimum length of 10 inches, and skirt or flange extending at least 8 inches around pipe.

2. Sleeve Flashing: Flat sheet, with skirt or flange extending at least 8 inches around sleeve.

Page 50: PLUMBING, ELECTRICAL & FIRE PROTECTION COMPONENTS … · mechanical, electrical, plumbing and fire protection building system components in place during a seismic or high wind event

Permit Fairview Municipal Building 55 Anderson Ave. Fairview, NJ Issue December 31, 2015

22 05 00-12 PLUMBING SPECIALTIES 12 of 13

3. Embedded Specialty Flashing: Flat sheet, with skirt or flange extending at least 8 inches around specialty.

C. Set flashing on floors and roofs in solid coating of bituminous cement.

D. Secure flashing into sleeve and specialty clamping ring or device.

E. Install flashing for piping passing through roofs with counterflashing or commercially made flashing fittings, according to Division 23.

F. Extend flashing up vent pipe passing through roofs and turn down into pipe, or secure flashing into cast-iron sleeve having calking recess.

G. Fabricate and install flashing and pans, sumps, and other drainage shapes.

3.4 LABELING AND IDENTIFYING

A. Equipment Nameplates and Signs: Install engraved plastic-laminate equipment nameplate or sign on or near each trap seal primer system.

1. Text: Distinguish among multiple units, inform operator of operational requirements, indicate safety and emergency precautions, and warn of hazards and improper operations, in addition to identifying unit.

2. Refer to Division 23 Section "Basic Mechanical Materials and Methods and “Mechanical Identification" for nameplates and signs.

3.5 FIELD QUALITY CONTROL

A. Manufacturer's Field Service: Engage a factory-authorized service representative to inspect field-assembled trap seal primer systems and grease recovery units and their installation, including piping and electrical connections. Report results in writing.

1. Leak Test: After installation, charge system and test for leaks. Repair leaks and retest until no leaks exist.

2. Operational Test: After electrical circuitry has been energized, start units to confirm proper motor rotation and unit operation. Remove malfunctioning units, replace with new units, and retest.

3. Test and adjust controls and safeties. Replace damaged and malfunctioning controls and equipment.

3.6 PROTECTION

A. Protect drains during remainder of construction period to avoid clogging with dirt and debris and to prevent damage from traffic and construction work.

B. Place plugs in ends of uncompleted piping at end of each day or when work stops.

Page 51: PLUMBING, ELECTRICAL & FIRE PROTECTION COMPONENTS … · mechanical, electrical, plumbing and fire protection building system components in place during a seismic or high wind event

Permit Fairview Municipal Building 55 Anderson Ave. Fairview, NJ Issue December 31, 2015

22 05 00-13 PLUMBING SPECIALTIES 13 of 13

END OF SECTION 22 05 00

Page 52: PLUMBING, ELECTRICAL & FIRE PROTECTION COMPONENTS … · mechanical, electrical, plumbing and fire protection building system components in place during a seismic or high wind event

Permit Fariview Municipal Building 55 Anderson Ave. Fairview, NJ Issue December 31, 2015

22 11 00-1 DOMESTIC WATER PIPING 1 of 9

SECTION 22 11 00 DOMESTIC WATER PIPING

PART 1 - GENERAL

1.1 RELATED DOCUMENTS

A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to this Section.

1.2 SUMMARY

A. This Section includes domestic water piping from locations indicated to fixtures and equipment inside the building.

B. Related Sections include the following:

1. Division 23 Section "Meters and Gages" for thermometers, pressure gages, and fittings. 2. Division 22 Section "Plumbing Specialties" for water distribution piping specialties.

1.3 PERFORMANCE REQUIREMENTS

A. Provide components and installation capable of producing domestic water piping systems with the following minimum working-pressure ratings, unless otherwise indicated: 1. Domestic Water Distribution Piping: Street Pressure 80 psig.

1.4 SUBMITTALS

A. Product Data: For pipe, tube, fittings, and couplings.

B. Water Samples: Specified in "Cleaning" Article in Part 3.

C. Field Test Reports: Indicate and interpret test results for compliance with performance requirements.

1.5 QUALITY ASSURANCE

A. Piping materials shall bear label, stamp, or other markings of specified testing agency.

B. Comply with NSF 61, "Drinking Water System Components-Health Effects; Sections 1 through 9," for potable domestic water piping and components.

PART 2 - PRODUCTS

Page 53: PLUMBING, ELECTRICAL & FIRE PROTECTION COMPONENTS … · mechanical, electrical, plumbing and fire protection building system components in place during a seismic or high wind event

Permit Fariview Municipal Building 55 Anderson Ave. Fairview, NJ Issue December 31, 2015

22 11 00-2 DOMESTIC WATER PIPING 2 of 9

2.1 PIPING MATERIALS

A. Refer to Part 3 "Piping Applications" Article for applications of pipe, tube, fitting, and joining materials.

B. Transition Couplings for Aboveground Pressure Piping: Coupling or other manufactured fitting the same size as, with pressure rating at least equal to and ends compatible with, piping to be joined.

C. Transition Couplings for Underground Pressure Piping: AWWA C219, metal, sleeve-type coupling or other manufactured fitting the same size as, with pressure rating at least equal to and ends compatible with, piping to be joined.

2.2 STEEL PIPING

A. Steel Pipe: ASTM A 53, Grade B, Schedule 40, galvanized. Include ends matching joining method.

1. Steel Pipe Nipples: ASTM A 733, made of ASTM A 53 or ASTM A 106, Schedule 40, galvanized, seamless steel pipe. Include ends matching joining method.

2. Malleable-Iron Unions: ASME B16.39, Class 150, hexagonal-stock body with ball-and-socket, metal-to-metal, bronze seating surface, and female threaded ends.

3. Gray-Iron, Threaded Fittings: ASME B16.4, Class 125, galvanized, standard pattern. 4. Cast-Iron Flanges: ASME B16.1, Class 125. 5. Cast-Iron, Flanged Fittings: ASME B16.1, Class 125, galvanized. 6. Steel-Piping, Grooved-End Fittings: ASTM A 47 (ASTM A 47M), galvanized,

malleable-iron casting; ASTM A 106, galvanized, steel pipe; or ASTM A 536, galvanized, ductile-iron casting; with dimensions matching steel pipe.

a. Steel-Piping, Keyed Couplings: AWWA C606, for steel-pipe dimensions. Include ferrous housing sections, gasket suitable for water, and bolts and nuts.

7. Steel-Piping, Expansion Joints: Compound, galvanized, steel fitting with telescoping body and slip-pipe section. Include packing rings, packing, limit rods, chrome-plated finish on slip-pipe sections, and flanged ends.

8. Steel-Piping, Double Expansion Joints: Compound, galvanized, steel fitting with telescoping body and two slip-pipe sections. Include packing rings, packing, limit rods, chrome-plated finish on slip-pipe sections, and flanged ends.

2.3 DUCTILE-IRON PIPING

A. Piping for fire-suppression applications shall be listed for fire-protection service.

B. Mechanical-Joint, Ductile-Iron Pipe: AWWA C151, with mechanical-joint, bell- and plain-spigot end, unless grooved or flanged ends are indicated.

1. Mechanical-Joint, Ductile-Iron Fittings: AWWA C110, ductile- or gray-iron, standard pattern; or AWWA C153, ductile-iron, compact pattern.

Page 54: PLUMBING, ELECTRICAL & FIRE PROTECTION COMPONENTS … · mechanical, electrical, plumbing and fire protection building system components in place during a seismic or high wind event

Permit Fariview Municipal Building 55 Anderson Ave. Fairview, NJ Issue December 31, 2015

22 11 00-3 DOMESTIC WATER PIPING 3 of 9

a. Glands, Gaskets, and Bolts: AWWA C111, ductile- or gray-iron glands, rubber gaskets, and steel bolts.

2. Ductile-Iron Piping, Grooved-End Fittings: ASTM A 47 (ASTM A 47M), malleable-iron castings or ASTM A 536 ductile-iron castings with dimensions matching pipe.

a. Ductile-Iron-Piping, Keyed Couplings: AWWA C606 for ductile-iron-pipe dimensions. Include ferrous housing sections, gasket suitable for water, and bolts and nuts.

2.4 COPPER TUBING

A. Hard Copper Tube: ASTM B 88, Types K and L (ASTM B 88M, Types A and B), water tube, annealed temper.

1. Copper Pressure Fittings: ASME B16.18, cast-copper-alloy or ASME B16.22, wrought-copper, solder-joint fittings. Furnish wrought-copper fittings if indicated.

2. Bronze Flanges: ASME B16.24, Class 150, with solder-joint end. Furnish Class 300 flanges if required to match piping.

3. Copper Unions: MSS SP-123, cast-copper-alloy, hexagonal-stock body, with ball-and-socket, metal-to-metal seating surfaces and solder-joint or threaded ends.

2.5 VALVES

A. Refer to Division 23 Section "Valves" for bronze and cast-iron, general-duty valves.

B. Refer to Division 22 Section "Plumbing Specialties" for balancing and drain valves.

PART 3 - EXECUTION

3.1 PIPING APPLICATIONS

A. Transition and special fittings with pressure ratings at least equal to piping rating may be used in applications below, unless otherwise indicated.

B. Flanges may be used on aboveground piping, unless otherwise indicated.

C. Grooved joints may be used on aboveground grooved-end piping.

D. Fitting Option: Mechanically formed tee-branch outlets and brazed joints may be used on aboveground copper tubing.

E. Underground Combined Fire-Protection and Domestic Water Service Piping: Provide piping listed for fire-protection service and complying with NSF 61. Use [any of] the following piping materials for each size range:

Page 55: PLUMBING, ELECTRICAL & FIRE PROTECTION COMPONENTS … · mechanical, electrical, plumbing and fire protection building system components in place during a seismic or high wind event

Permit Fariview Municipal Building 55 Anderson Ave. Fairview, NJ Issue December 31, 2015

22 11 00-4 DOMESTIC WATER PIPING 4 of 9

1. Ductile-Iron Piping: mechanical-joint, ductile-iron pipe; mechanical-joint, ductile-iron pipe; mechanical-joint, ductile-iron fittings; and restrained, gasketed joints.

F. Underground Domestic Water Service Piping: Use the following piping materials for each size range:

1. All Sizes: Mechanical-joint, ductile-iron pipe; mechanical-joint, ductile-iron fittings; and

restrained, gasketed joints.

G. Aboveground Domestic Water Piping: Use the following piping materials for each size range:

1. NPS 1-1/2 and Smaller: Hard copper tube, Type L (Type B). 2. NPS 1-1/2 and Smaller: Within residential apartments after manifold: Pex tube, cold

expansion fittings. 3. NPS 2 to NPS 3-1/2: Hard copper tube, Type L (Type B); copper pressure fittings; and

soldered joints. 4. NPS 4 to NPS 8: Vertical Steel pipe schedule 40 ASTM A52, welded fittings. 5. NPS 4 and NPS 8: (Horizontal only where accessible) steel pipe with grooved ends;

steel-piping, grooved-end fittings; steel-piping, keyed couplings; and grooved joints.

3.2 VALVE APPLICATIONS

A. Drawings indicate valve types to be used. Where specific valve types are not indicated, the following requirements apply:

1. Shutoff Duty: Use bronze ball or gate valves for piping NPS 2 and smaller. Use cast-iron butterfly or gate valves with flanged ends for piping NPS 2-1/2 and larger.

2. Throttling Duty: Use bronze ball or globe valves for piping NPS 2 and smaller. 3. Hot-Water-Piping, Balancing Duty: Memory-stop balancing valves. 4. Drain Duty: Hose-end drain valves.

3.3 PIPING INSTALLATION

A. Refer to Division 23 Section "Water Distribution" for site water distribution and service piping.

B. Refer to Division 23 Section "Basic Mechanical Materials and Methods" for basic piping installation.

C. Extend domestic water service piping to exterior water distribution piping in sizes and locations indicated.

D. Install underground ductile-iron piping according to AWWA C600, and AWWA M41, and NFPA 24. Install buried piping inside building between wall and floor penetrations and connection to water service piping outside building with restrained joints. Anchor pipe to wall or floor. Install thrust-block supports at vertical and horizontal offsets.

Page 56: PLUMBING, ELECTRICAL & FIRE PROTECTION COMPONENTS … · mechanical, electrical, plumbing and fire protection building system components in place during a seismic or high wind event

Permit Fariview Municipal Building 55 Anderson Ave. Fairview, NJ Issue December 31, 2015

22 11 00-5 DOMESTIC WATER PIPING 5 of 9

1. Encase piping with polyethylene film according to ASTM A 674 or AWWA C105.

E. Install underground copper tubing according to CDA's "Copper Tube Handbook."

F. Install cast-iron sleeve with water stop and mechanical sleeve seal at each service pipe penetration through foundation wall. Select number of interlocking rubber links required to make installation watertight. Refer to Division 23 Section "Basic Mechanical Materials and Methods" for sleeves and mechanical sleeve seals.

G. Install wall penetration system at each service pipe penetration through foundation wall. Make installation watertight. Refer to Division 23 Section "Basic Mechanical Materials and Methods" for wall penetration systems.

H. Install shutoff valve, hose-end drain valve, strainer, pressure gage, and test tee with valve, inside building at each domestic water service. Refer to Division 23 Section "Meters and Gages" for pressure gages, and to Division 22 Section "Plumbing Specialties" for drain valves and strainers.

I. Install water-pressure regulators downstream from shutoff valves as shown on plans. Refer to Division 22 Section "Plumbing Specialties" for water-pressure regulators.

J. Install aboveground domestic water piping level without pitch and plumb.

K. Fill water piping. Check components to determine that they are not air bound and that piping is full of water.

L. Perform the following steps before operation:

1. Close drain valves, hydrants, and hose bibs. 2. Open shutoff valves to fully open position. 3. Open throttling valves to proper setting. 4. Remove plugs used during testing of piping and plugs used for temporary sealing of

piping during installation. 5. Remove and clean strainer screens. Close drain valves and replace drain plugs. 6. Remove filter cartridges from housings, and verify that cartridges are as specified for

application where used and that cartridges are clean and ready for use.

M. Check plumbing equipment and verify proper settings, adjustments, and operation. Do not operate water heaters before filling with water.

N. Check plumbing specialties and verify proper settings, adjustments, and operation.

1. Water-Pressure Regulators: Set outlet pressure at 80 psig maximum, unless otherwise indicated.

O. Energize pumps and verify proper operation.

3.4 JOINT CONSTRUCTION

Page 57: PLUMBING, ELECTRICAL & FIRE PROTECTION COMPONENTS … · mechanical, electrical, plumbing and fire protection building system components in place during a seismic or high wind event

Permit Fariview Municipal Building 55 Anderson Ave. Fairview, NJ Issue December 31, 2015

22 11 00-6 DOMESTIC WATER PIPING 6 of 9

A. Refer to Division 23 Section "Basic Mechanical Materials and Methods" for basic piping joint construction.

B. Soldered Joints: Use ASTM B 813, water-flushable, lead-free flux; ASTM B 32, lead-free-alloy solder; and ASTM B 828 procedure, unless otherwise indicated.

C. Grooved Joints: Assemble joints with keyed-coupling housing, gasket, lubricant, and bolts according to coupling and fitting manufacturer's written instructions.

D. Mechanically Formed Outlets: Form tee in copper tube according to equipment manufacturer's written instructions. Use tool designed for copper tube; drill pilot hole, form collar for outlet, dimple tube to form seating stop, and braze branch tube into collar.

3.5 VALVE INSTALLATION

A. Install sectional valve close to water main on each branch and riser serving plumbing fixtures or equipment. Use ball or gate valves for piping NPS 2 and smaller. Use butterfly or gate valves for piping NPS 2-1/2 and larger.

B. Install shutoff valve on each water supply to equipment and on each water supply to plumbing fixtures without supply stops. Use ball or gate valves for piping NPS 2 and smaller. Use butterfly or gate valves for piping NPS 2-1/2 and larger.

C. Install drain valves for equipment, at base of each water riser, at low points in horizontal piping, and where required to drain water piping.

1. Install hose-end drain valves at low points in water mains, risers, and branches. 2. Install stop-and-waste drain valves where indicated.

D. Install balancing valve in each hot-water circulation return branch and discharge side of each pump and circulator. Set balancing valves partly open to restrict but not stop flow. Use ball valves for piping NPS 2 and smaller and butterfly valves for piping NPS 2-1/2 and larger. Refer to Division 22 Section "Plumbing Specialties" for balancing valves.

E. Install calibrated balancing valves in each hot-water circulation return branch and discharge side of each pump and circulator. Set calibrated balancing valves partly open to restrict but not stop flow. Refer to Division 22 Section "Plumbing Specialties" for calibrated balancing valves.

3.6 HANGER AND SUPPORT INSTALLATION

A. Refer to Division 20 Section "Vibration Isolation, Seismic, Wind & Flood Load Restraints for HVAC, Plumbing, Electrical & Fire Protection Components".

B. Refer to Division 23 Section "Hangers and Supports" for pipe hanger and support devices. Install the following:

1. Vertical Piping: MSS Type 8 or Type 42, clamps. 2. Individual, Straight, Horizontal Piping Runs: According to the following:

Page 58: PLUMBING, ELECTRICAL & FIRE PROTECTION COMPONENTS … · mechanical, electrical, plumbing and fire protection building system components in place during a seismic or high wind event

Permit Fariview Municipal Building 55 Anderson Ave. Fairview, NJ Issue December 31, 2015

22 11 00-7 DOMESTIC WATER PIPING 7 of 9

a. 100 Feet and Less: MSS Type 1, adjustable, steel clevis hangers. b. Longer Than 100 Feet: MSS Type 43, adjustable roller hangers. c. Longer Than 100 Feet if Indicated: MSS Type 49, spring cushion rolls.

3. Multiple, Straight, Horizontal Piping Runs 100 Feet or Longer: MSS Type 44, pipe rolls. Support pipe rolls on trapeze.

4. Base of Vertical Piping: MSS Type 52, spring hangers.

C. Install supports according to Division 23 Section "Hangers and Supports."

D. Support vertical piping and tubing at base and at each floor.

E. Rod diameter may be reduced 1 size for double-rod hangers, to a minimum of 3/8 inch.

F. Install hangers for steel piping with the following maximum horizontal spacing and minimum rod diameters:

1. NPS 1-1/4 and Smaller: 84 inches with 3/8-inch rod. 2. NPS 1-1/2: 108 inches with 3/8-inch rod. 3. NPS 2: 10 feet with 3/8-inch rod. 4. NPS 2-1/2: 11 feet with 1/2-inch rod. 5. NPS 3 and NPS 3-1/2: 12 feet with 1/2-inch rod. 6. NPS 4 and NPS 5: 12 feet with 5/8-inch rod. 7. NPS 6: 12 feet with 3/4-inch rod. 8. NPS 8 to NPS 12: 12 feet with 7/8-inch rod.

G. Install supports for vertical steel piping every 15 feet.

H. Install hangers for copper tubing with the following maximum horizontal spacing and minimum rod diameters:

1. NPS 3/4 (DN 20) and Smaller: 60 inches (1500 mm) with 3/8-inch (10-mm) rod. 2. NPS 1 and NPS 1-1/4 (DN 25 and DN 32): 72 inches (1800 mm) with 3/8-inch (10-mm)

rod. 3. NPS 1-1/2 and NPS 2 (DN 40 and DN 50): 96 inches (2400 mm) with 3/8-inch (10-mm)

rod. 4. NPS 2-1/2 (DN 65): 108 inches (2700 mm) with 1/2-inch (13-mm) rod. 5. NPS 3 to NPS 5 (DN 80 to DN 125): 10 feet (3 m) with 1/2-inch (13-mm) rod. 6. NPS 6 (DN 150): 10 feet (3 m) with 5/8-inch (16-mm) rod. 7. NPS 8 (DN 200): 10 feet (3 m) with 3/4-inch (19-mm) rod.

I. Install supports for vertical copper tubing every 10 feet (3 m).

3.7 CONNECTIONS

A. Drawings indicate general arrangement of piping, fittings, and specialties.

B. Install piping adjacent to equipment and machines to allow service and maintenance.

Page 59: PLUMBING, ELECTRICAL & FIRE PROTECTION COMPONENTS … · mechanical, electrical, plumbing and fire protection building system components in place during a seismic or high wind event

Permit Fariview Municipal Building 55 Anderson Ave. Fairview, NJ Issue December 31, 2015

22 11 00-8 DOMESTIC WATER PIPING 8 of 9

C. Connect domestic water piping to exterior water service piping. Use transition fitting to join dissimilar piping materials.

D. Connect domestic water piping to service piping with shutoff valve, and extend and connect to the following:

1. Booster Systems: Cold-water suction and discharge piping. 2. Water Heaters: Cold-water supply and hot-water outlet piping in sizes indicated, but not

smaller than sizes of water heater connections. 3. Plumbing Fixtures: Cold- and hot-water supply piping in sizes indicated, but not smaller

than required by plumbing code. Refer to Division 22 Section "Plumbing Fixtures." 4. Equipment: Cold- and hot-water supply piping as indicated, but not smaller than

equipment connections. Provide shutoff valve and union for each connection. Use flanges instead of unions for NPS 2-1/2 (DN 65) and larger.

3.8 FIELD QUALITY CONTROL

A. Inspect domestic water piping as follows:

1. Do not enclose, cover, or put piping into operation until it is inspected and approved by authorities having jurisdiction.

2. During installation, notify authorities having jurisdiction at least 24 hours before inspection must be made. Perform tests specified below in presence of authorities having jurisdiction:

a. Roughing-in Inspection: Arrange for inspection of piping before concealing or closing-in after roughing-in and before setting fixtures.

b. Final Inspection: Arrange for final inspection by authorities having jurisdiction to observe tests specified below and to ensure compliance with requirements.

3. Reinspection: If authorities having jurisdiction find that piping will not pass test or inspection, make required corrections and arrange for reinspection.

4. Reports: Prepare inspection reports and have them signed by authorities having jurisdiction.

B. Test domestic water piping as follows:

1. Test for leaks and defects in new piping and parts of existing piping that have been altered, extended, or repaired. If testing is performed in segments, submit separate report for each test, complete with diagram of portion of piping tested.

2. Leave uncovered and unconcealed new, altered, extended, or replaced domestic water piping until it has been tested and approved. Expose work that was covered or concealed before it was tested.

3. Cap and subject piping to static water pressure of 50 psig (345 kPa) above operating pressure, without exceeding pressure rating of piping system materials. Isolate test source and allow to stand for four hours. Leaks and loss in test pressure constitute defects that must be repaired.

4. Repair leaks and defects with new materials and retest piping or portion thereof until satisfactory results are obtained.

Page 60: PLUMBING, ELECTRICAL & FIRE PROTECTION COMPONENTS … · mechanical, electrical, plumbing and fire protection building system components in place during a seismic or high wind event

Permit Fariview Municipal Building 55 Anderson Ave. Fairview, NJ Issue December 31, 2015

22 11 00-9 DOMESTIC WATER PIPING 9 of 9

5. Prepare reports for tests and required corrective action.

3.9 ADJUSTING

A. Adjust balancing valves in hot-water-circulation return piping to provide adequate flow.

1. Manually adjust ball-type balancing valves in hot-water-circulation return piping to provide flow of hot water in each branch.

2. Adjust calibrated balancing valves to flows indicated.

3.10 CLEANING

A. Clean and disinfect potable and nonpotable domestic water piping as follows:

1. Purge new piping and parts of existing domestic water piping that have been altered, extended, or repaired before using.

2. Use purging and disinfecting procedures prescribed by authorities having jurisdiction or, if methods are not prescribed, procedures described in either AWWA C651 or AWWA C652 or as described below:

a. Flush piping system with clean, potable water until dirty water does not appear at outlets.

b. Fill and isolate system according to either of the following:

1) Fill system or part thereof with water/chlorine solution with at least 50 ppm (50 mg/L) of chlorine. Isolate with valves and allow to stand for 24 hours.

2) Fill system or part thereof with water/chlorine solution with at least 200 ppm (200 mg/L) of chlorine. Isolate and allow to stand for three hours.

c. Flush system with clean, potable water until no chlorine is in water coming from system after the standing time.

d. Submit water samples in sterile bottles to authorities having jurisdiction. Repeat procedures if biological examination shows contamination.

B. Prepare and submit reports of purging and disinfecting activities.

C. Clean interior of domestic water piping system. Remove dirt and debris as work progresses.

END OF SECTION 22 11 00

Page 61: PLUMBING, ELECTRICAL & FIRE PROTECTION COMPONENTS … · mechanical, electrical, plumbing and fire protection building system components in place during a seismic or high wind event

Permit Fairview Municipal Building 55 Anderson Ave. Fairview, NJ Issue December 31, 2015

22 13 00-1 SANITARY WASTE AND VENT PIPING 1 of 10

SECTION 22 13 00 SANITARY WASTE AND VENT PIPING

PART 1 - GENERAL

1.1 RELATED DOCUMENTS

A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to this Section.

1.2 SUMMARY

A. This Section includes soil and waste, sanitary drainage and vent piping inside the building and to locations indicated.

B. Related Sections include the following: 1. Division 22 Section "Plumbing Specialties" for soil, waste, and vent piping systems

specialties.

1.3 DEFINITIONS

A. The following are industry abbreviations for plastic and rubber piping materials: 1. PVC: Polyvinyl chloride plastic.

1.4 PERFORMANCE REQUIREMENTS

A. Provide components and installation capable of producing piping systems with the following minimum working-pressure ratings, unless otherwise indicated:

1. Soil, Waste, and Vent Piping: 10-foot head of water. 2. Sanitary Sewer, Force-Main Piping: 50 psig.

1.5 SUBMITTALS

A. Product Data: For pipe, tube, fittings, and couplings.

B. Shop Drawings: For sovent drainage system, include plans, elevations, sections, and details.

C. Field Test Reports: Indicate and interpret test results for compliance with performance requirements.

1.6 QUALITY ASSURANCE

A. Piping materials shall bear label, stamp, or other markings of specified testing agency.

Page 62: PLUMBING, ELECTRICAL & FIRE PROTECTION COMPONENTS … · mechanical, electrical, plumbing and fire protection building system components in place during a seismic or high wind event

Permit Fairview Municipal Building 55 Anderson Ave. Fairview, NJ Issue December 31, 2015

22 13 00-2 SANITARY WASTE AND VENT PIPING 2 of 10

B. Comply with NSF 14, "Plastics Piping Systems Components and Related Materials," for plastic piping components. Include marking with "NSF-dwv" for plastic drain, waste, and vent piping; "NSF-drain" for plastic drain piping; "NSF-tubular" for plastic continuous waste piping; and "NSF-sewer" for plastic sewer piping.

PART 2 - PRODUCTS

2.1 PIPING MATERIALS

A. Refer to Part 3 "Piping Applications" Article for applications of pipe, tube, fitting, and joining materials.

B. Flexible Transition Couplings for Underground Nonpressure Piping: ASTM C 1173 with elastomeric sleeve. Include ends of same sizes as piping to be joined and include corrosion-resistant metal band on each end.

C. Transition Couplings for Underground Pressure Piping: AWWA C219 metal, sleeve-type coupling or other manufactured fitting same size as, with pressure rating at least equal to and ends compatible with, piping to be joined.

2.2 CAST-IRON SOIL PIPING

A. Hub-and-Spigot Pipe and Fittings: ASTM A 74, Service and Extra-Heavy classes.

1. Gaskets: ASTM C 564, rubber.

B. Hubless Pipe and Fittings: ASTM A 888 or CISPI 301.

1. Couplings: ASTM C 1277 assembly of metal housing, corrosion-resistant fasteners, and ASTM C 564 rubber sleeve with integral, center pipe stop.

a. Heavy-Duty, Type 304, Stainless-Steel Couplings: ASTM A 666, Type 304, stainless-steel shield; stainless-steel bands; and sleeve.

1) NPS 1-1/2 to NPS 4 (DN 40 to DN 100): 3-inch- wide shield with 4 bands. 2) NPS 5 to NPS 12: 4-inch- wide shield with 6 bands.

2.3 STEEL PIPING

A. Steel Pipe: ASTM A 53, Grade B, Schedule 40, galvanized. Include ends matching joining method.

1. Steel Pipe Nipples: ASTM A 733, made of ASTM A 53 or ASTM A 106, Schedule 40, galvanized, seamless steel pipe. Include ends matching joining method.

2. Malleable-Iron Unions: ASME B16.39; Class 150; hexagonal-stock body with ball-and-socket, metal-to-metal, bronze seating surface; and female threaded ends.

Page 63: PLUMBING, ELECTRICAL & FIRE PROTECTION COMPONENTS … · mechanical, electrical, plumbing and fire protection building system components in place during a seismic or high wind event

Permit Fairview Municipal Building 55 Anderson Ave. Fairview, NJ Issue December 31, 2015

22 13 00-3 SANITARY WASTE AND VENT PIPING 3 of 10

3. Cast-Iron, Threaded, Drainage Fittings: ASME B16.12, galvanized. 4. Gray-Iron, Threaded Fittings: ASME B16.4, Class 125, galvanized, standard pattern. 5. Cast-Iron Flanges: ASME B16.1, Class 125. 6. Cast-Iron, Flanged Fittings: ASME B16.1, Class 125, galvanized. 7. Steel-Piping, Grooved-End Fittings: ASTM A 47 (ASTM A 47M), galvanized,

malleable-iron casting; ASTM A 106, galvanized steel pipe; or ASTM A 536, galvanized, ductile-iron casting; with dimensions matching steel pipe.

a. Steel-Piping, Keyed Couplings: AWWA C606, for steel-pipe dimensions. Include ferrous housing sections, gasket suitable for water, and bolts and nuts.

8. Steel-Piping, Expansion Joints: Compound, galvanized steel fitting with telescoping body and slip-pipe section. Include packing rings, packing, limit rods, chrome-plated finish on slip-pipe section, and flanged ends.

9. Steel-Piping, Double Expansion Joints: Compound, galvanized steel fitting with telescoping body and two slip-pipe sections. Include packing rings, packing, limit rods, chrome-plated finish on slip-pipe sections, and flanged ends.

2.4 DUCTILE-IRON PIPING

A. Mechanical-Joint, Ductile-Iron Pipe: AWWA C151, with mechanical-joint bell and plain spigot end, unless grooved or flanged ends are indicated.

1. Mechanical-Joint, Ductile-Iron Fittings: AWWA C110, ductile- or gray-iron standard pattern or AWWA C153, ductile-iron compact pattern.

a. Glands, Gaskets, and Bolts: AWWA C111, ductile- or gray-iron glands, rubber gaskets, and steel bolts.

2. Ductile-Iron Piping, Grooved-End Fittings: ASTM A 47 (ASTM A 47M), malleable-iron castings or ASTM A 536, ductile-iron castings with dimensions matching pipe.

a. Ductile-Iron-Piping, Keyed Couplings: AWWA C606, for ductile-iron-pipe dimensions. Include ferrous housing sections, gasket suitable for water, and bolts and nuts.

2.5 COPPER TUBING

A. Copper DWV Tube: ASTM B 306, drainage tube, drawn temper.

1. Copper Drainage Fittings: ASME B16.23, cast copper or ASME B16.29, wrought copper, solder-joint fittings.

B. Soft Copper Tube: ASTM B 88, Type L (ASTM B 88M, Type B), water tube, annealed temper.

1. Copper Pressure Fittings: ASME B16.18, cast-copper-alloy or ASME B16.22, wrought- copper, solder-joint fittings. Furnish wrought-copper fittings if indicated.

2. Bronze Flanges: ASME B16.24, Class 150, with solder-joint end.

Page 64: PLUMBING, ELECTRICAL & FIRE PROTECTION COMPONENTS … · mechanical, electrical, plumbing and fire protection building system components in place during a seismic or high wind event

Permit Fairview Municipal Building 55 Anderson Ave. Fairview, NJ Issue December 31, 2015

22 13 00-4 SANITARY WASTE AND VENT PIPING 4 of 10

3. Copper Unions: MSS SP-123, cast-copper-alloy, hexagonal-stock body with ball-and-socket, metal-to-metal seating surfaces, and solder-joint or threaded ends.

2.6 PVC PIPING

A. PVC Pipe: ASTM D 2665, solid-wall drain, waste, and vent.

1. PVC Socket Fittings: ASTM D 2665, socket type, made to ASTM D 3311, drain, waste, and vent patterns.

B. PVC Special Fittings: ASTM F 409, drainage-pattern tube and tubular fittings with ends as required for application.

2.7 PE ENCASEMENT

A. PE Encasement for Underground Metal Piping: ASTM A 674 or AWWA C105, PE film, 0.008-inch (0.20-mm) minimum thickness, tube or sheet.

PART 3 - EXECUTION

3.1 PIPING APPLICATIONS

A. Transition and special fittings with pressure ratings at least equal to piping pressure ratings may be used in applications below, unless otherwise indicated.

B. Flanges may be used on aboveground pressure piping, unless otherwise indicated.

C. Aboveground, Soil, Waste, and Vent Piping: Use the following piping materials for each size range: 1. All Sizes: (Within Residential Tower): PVC pipe, PVC socket fittings, and solvent-

cemented joints. 2. All Sizes exposed within parking garage: Hubless, cast-iron soil piping. 3. All Sizes (Indirect Waste): Copper DWV tube, copper drainage fittings, and soldered

joints.

D. Underground, Soil, Waste, and Vent Piping: Use the following piping materials for each size range: 1. All Sizes: Service class, cast-iron soil piping; gaskets; and gasketed joints.

3.2 PIPING INSTALLATION

A. Refer to Division 23 Section "Basic Mechanical Materials and Methods" for basic piping installation.

Page 65: PLUMBING, ELECTRICAL & FIRE PROTECTION COMPONENTS … · mechanical, electrical, plumbing and fire protection building system components in place during a seismic or high wind event

Permit Fairview Municipal Building 55 Anderson Ave. Fairview, NJ Issue December 31, 2015

22 13 00-5 SANITARY WASTE AND VENT PIPING 5 of 10

B. Install cleanouts at grade and extend to where building sanitary drains connect to building sanitary sewers.

C. Install cast-iron sleeve with water stop and mechanical sleeve seal at each service pipe penetration through foundation wall. Select number of interlocking rubber links required to make installation watertight. Refer to Division 23 Section "Basic Mechanical Materials and Methods" for sleeves and mechanical sleeve seals.

D. Install wall penetration system at each service pipe penetration through foundation wall. Make installation watertight. Refer to Division 23 Section "Basic Mechanical Materials and Methods" for wall penetration systems.

E. Install cast-iron soil piping according to CISPI's "Cast Iron Soil Pipe and Fittings Handbook," Chapter IV, "Installation of Cast Iron Soil Pipe and Fittings."

1. Encase underground piping with PE film according to ASTM A 674 or AWWA C105.

F. Make changes in direction for soil and waste drainage and vent piping using appropriate branches, bends, and long-sweep bends. Sanitary tees and short-sweep 1/4 bends may be used on vertical stacks if change in direction of flow is from horizontal to vertical. Use long-turn, double Y-branch and 1/8-bend fittings if 2 fixtures are installed back to back or side by side with common drain pipe. Straight tees, elbows, and crosses may be used on vent lines. Do not change direction of flow more than 90 degrees. Use proper size of standard increasers and reducers if pipes of different sizes are connected. Reducing size of drainage piping in direction of flow is prohibited.

G. Lay buried building drainage piping beginning at low point of each system. Install true to grades and alignment indicated, with unbroken continuity of invert. Place hub ends of piping upstream. Install required gaskets according to manufacturer's written instructions for use of lubricants, cements, and other installation requirements. Maintain swab in piping and pull past each joint as completed.

H. Install soil and waste drainage and vent piping at the following minimum slopes, unless otherwise indicated:

1. Building Sanitary Drain: 2 percent downward in direction of flow for piping NPS 3 and smaller; 1 percent downward in direction of flow for piping NPS 4and larger.

2. Horizontal Sanitary Drainage Piping: 2 percent downward in direction of flow. 3. Vent Piping: 1 percent down toward vertical fixture vent or toward vent stack.

I. Install engineered soil and waste drainage and vent piping systems in locations indicated and as follows:

1. Combination Waste and Vent: Comply with standards of authorities having jurisdiction. 2. Cast-Iron, Sovent, Single Stack: Comply with ASSE 1043 and sovent fitting

manufacturer's written installation instructions. 3. Reduced-Size Venting: Comply with standards of authorities having jurisdiction.

J. Sleeves are not required for cast-iron soil piping passing through concrete slabs-on-grade if slab is without membrane waterproofing.

Page 66: PLUMBING, ELECTRICAL & FIRE PROTECTION COMPONENTS … · mechanical, electrical, plumbing and fire protection building system components in place during a seismic or high wind event

Permit Fairview Municipal Building 55 Anderson Ave. Fairview, NJ Issue December 31, 2015

22 13 00-6 SANITARY WASTE AND VENT PIPING 6 of 10

K. Install PVC soil and waste drainage and vent piping according to ASTM D 2665.

L. Install underground ABS and PVC soil and waste drainage piping according to ASTM D 2321.

M. Do not enclose, cover, or put piping into operation until it is inspected and approved by authorities having jurisdiction.

3.3 JOINT CONSTRUCTION

A. Refer to Division 23 Section "Basic Mechanical Materials and Methods" for basic piping joint construction.

B. Cast-Iron, Soil-Piping Joints: Make joints according to CISPI's "Cast Iron Soil Pipe and Fittings Handbook," Chapter IV, "Installation of Cast Iron Soil Pipe and Fittings."

1. Gasketed Joints: Make with rubber gasket matching class of pipe and fittings. 2. Hubless Joints: Make with rubber gasket and sleeve or clamp.

C. PVC Nonpressure Piping Joints: Join piping according to ASTM D 2665.

3.4 HANGER AND SUPPORT INSTALLATION

A. Refer to Division 20 Section "Vibration Isolation, Seismic, Wind & Flood Load Restraints for HVAC, Plumbing, Electrical & Fire Protection Components" for seismic-restraint devices.

B. Refer to Division 23 Section "Hangers and Supports" for pipe hanger and support devices. Install the following:

1. Vertical Piping: MSS Type 8 or Type 42, clamps. 2. Individual, Straight, Horizontal Piping Runs: According to the following:

a. 100 Feet (30 m) and Less: MSS Type 1, adjustable, steel clevis hangers. b. Longer Than 100 Feet (30 m): MSS Type 43, adjustable roller hangers. c. Longer Than 100 Feet (30 m), if Indicated: MSS Type 49, spring cushion rolls.

3. Multiple, Straight, Horizontal Piping Runs 100 Feet (30 m) or Longer: MSS Type 44, pipe rolls. Support pipe rolls on trapeze.

4. Base of Vertical Piping: MSS Type 52, spring hangers.

C. Install supports according to Division 23 Section "Hangers and Supports."

D. Support vertical piping and tubing at base and at each floor.

E. Rod diameter may be reduced 1 size for double-rod hangers, with 3/8-inch (10-mm) minimum rods.

F. Install hangers for cast-iron soil piping with the following maximum horizontal spacing and minimum rod diameters:

Page 67: PLUMBING, ELECTRICAL & FIRE PROTECTION COMPONENTS … · mechanical, electrical, plumbing and fire protection building system components in place during a seismic or high wind event

Permit Fairview Municipal Building 55 Anderson Ave. Fairview, NJ Issue December 31, 2015

22 13 00-7 SANITARY WASTE AND VENT PIPING 7 of 10

1. NPS 1-1/2 and NPS 2 (DN 40 and DN 50): 60 inches (1500 mm) with 3/8-inch (10-mm) rod.

2. NPS 3 (DN 80): 60 inches (1500 mm) with 1/2-inch (13-mm) rod. 3. NPS 4 and NPS 5 (DN 100 and DN 125): 60 inches (1500 mm) with 5/8-inch (16-mm)

rod. 4. NPS 6 (DN 150): 60 inches (1500 mm) with 3/4-inch (19-mm) rod. 5. NPS 8 to NPS 12 (DN 200 to DN 300): 60 inches (1500 mm) with 7/8-inch (22-mm)

rod. 6. NPS 15 (DN 375): 60 inches (1500 mm) with 1-inch (25-mm) rod. 7. Spacing for 10-foot (3-m) lengths may be increased to 10 feet (3 m). Spacing for fittings

is limited to 60 inches (1500 mm).

G. Install supports for vertical cast-iron soil piping every 15 feet (4.5 m).

H. Install hangers for steel piping with the following maximum horizontal spacing and minimum rod diameters:

1. NPS 1-1/4 (DN 32): 84 inches (2100 mm) with 3/8-inch (10-mm) rod. 2. NPS 1-1/2 (DN 40): 108 inches (2700 mm) with 3/8-inch (10-mm) rod. 3. NPS 2 (DN 50): 10 feet (3 m) with 3/8-inch (10-mm) rod. 4. NPS 2-1/2 (DN 65): 11 feet (3.4 m) with 1/2-inch (13-mm) rod. 5. NPS 3 (DN 80): 12 feet (3.7 m) with 1/2-inch (13-mm) rod. 6. NPS 4 and NPS 5 (DN 100 and DN 125): 12 feet (3.7 m) with 5/8-inch (16-mm) rod. 7. NPS 6 (DN 150): 12 feet (3.7 m) with 3/4-inch (19-mm) rod. 8. NPS 8 to NPS 12 (DN 200 to DN 300): 12 feet (3.7 m) with 7/8-inch (22-mm) rod.

I. Install supports for vertical steel piping every 15 feet (4.5 m).

J. Install hangers for stainless-steel piping with the following maximum horizontal spacing and minimum rod diameters:

1. NPS 2 (DN 50): 84 inches (2100 mm) with 3/8-inch (10-mm) rod. 2. NPS 3 (DN 80): 96 inches (2400 mm) with 1/2-inch (13-mm) rod. 3. NPS 4 (DN 100): 108 inches (2700 mm) with 1/2-inch (13-mm) rod. 4. NPS 6 (DN 150): 10 feet (3 m) with 5/8-inch (16-mm) rod. 5. NPS 8 to NPS 12 (DN 200 to DN 300): 10 feet (3 m) with 7/8-inch (22-mm) rod.

K. Install supports for vertical stainless-steel piping every 10 feet (3 m).

L. Install hangers for copper tubing with the following maximum horizontal spacing and minimum rod diameters:

1. NPS 1-1/4 (DN 32): 72 inches (1800 mm) with 3/8-inch (10-mm) rod. 2. NPS 1-1/2 and NPS 2 (DN 40 and DN 50): 96 inches (2400 mm) with 3/8-inch (10-mm)

rod. 3. NPS 2-1/2 (DN 65): 108 inches (2700 mm) with 1/2-inch (13-mm) rod. 4. NPS 3 to NPS 5 (DN 80 to DN 125): 10 feet (3 m) with 1/2-inch (13-mm) rod. 5. NPS 6 (DN 150): 10 feet (3 m) with 5/8-inch (16-mm) rod. 6. NPS 8 (DN 200): 10 feet (3 m) with 3/4-inch (19-mm) rod.

Page 68: PLUMBING, ELECTRICAL & FIRE PROTECTION COMPONENTS … · mechanical, electrical, plumbing and fire protection building system components in place during a seismic or high wind event

Permit Fairview Municipal Building 55 Anderson Ave. Fairview, NJ Issue December 31, 2015

22 13 00-8 SANITARY WASTE AND VENT PIPING 8 of 10

M. Install supports for vertical copper tubing every 10 feet (3 m).

N. Install hangers for ABS and PVC piping with the following maximum horizontal spacing and minimum rod diameters:

1. NPS 1-1/2 and NPS 2 (DN 40 and DN 50): 48 inches (1200 mm) with 3/8-inch (10-mm) rod.

2. NPS 3 (DN 80): 48 inches (1200 mm) with 1/2-inch (13-mm) rod. 3. NPS 4 and NPS 5 (DN 100 and DN 125): 48 inches (1200 mm) with 5/8-inch (16-mm)

rod. 4. NPS 6 (DN 150): 48 inches (1200 mm) with 3/4-inch (19-mm) rod. 5. NPS 8 to NPS 12 (DN 200 to DN 300): 48 inches (1200 mm) with 7/8-inch (22-mm)

rod.

O. Install supports for vertical ABS and PVC piping every 48 inches (1200 mm).

P. Support piping and tubing not listed above according to MSS SP-69 and manufacturer's written instructions.

3.5 CONNECTIONS

A. Drawings indicate general arrangement of piping, fittings, and specialties.

B. Connect soil and waste piping to exterior sanitary sewerage piping. Use transition fitting to join dissimilar piping materials.

C. Connect drainage and vent piping to the following:

1. Plumbing Fixtures: Connect drainage piping in sizes indicated, but not smaller than required by plumbing code. Refer to Division 22 Section "Plumbing Fixtures."

2. Plumbing Fixtures and Equipment: Connect atmospheric vent piping in sizes indicated, but not smaller than required by authorities having jurisdiction.

3. Plumbing Specialties: Connect drainage and vent piping in sizes indicated, but not smaller than required by plumbing code. Refer to Division 22 Section "Plumbing Specialties."

4. Equipment: Connect drainage piping as indicated. Provide shutoff valve, if indicated, and union for each connection. Use flanges instead of unions for connections NPS 2-1/2 and larger.

3.6 FIELD QUALITY CONTROL

A. During installation, notify authorities having jurisdiction at least 24 hours before inspection must be made. Perform tests specified below in presence of authorities having jurisdiction.

1. Roughing-in Inspection: Arrange for inspection of piping before concealing or closing-in after roughing-in and before setting fixtures.

2. Final Inspection: Arrange for final inspection by authorities having jurisdiction to observe tests specified below and to ensure compliance with requirements.

Page 69: PLUMBING, ELECTRICAL & FIRE PROTECTION COMPONENTS … · mechanical, electrical, plumbing and fire protection building system components in place during a seismic or high wind event

Permit Fairview Municipal Building 55 Anderson Ave. Fairview, NJ Issue December 31, 2015

22 13 00-9 SANITARY WASTE AND VENT PIPING 9 of 10

B. Reinspection: If authorities having jurisdiction find that piping will not pass test or inspection, make required corrections and arrange for reinspection.

C. Reports: Prepare inspection reports and have them signed by authorities having jurisdiction.

D. Test sanitary drainage and vent piping according to procedures of authorities having jurisdiction or, in absence of published procedures, as follows:

1. Test for leaks and defects in new piping and parts of existing piping that have been altered, extended, or repaired. If testing is performed in segments, submit separate report for each test, complete with diagram of portion of piping tested.

2. Leave uncovered and unconcealed new, altered, extended, or replaced drainage and vent piping until it has been tested and approved. Expose work that was covered or concealed before it was tested.

3. Roughing-in Plumbing Test Procedure: Test drainage and vent piping, except outside leaders, on completion of roughing-in. Close openings in piping system and fill with water to point of overflow, but not less than 10-foot head of water (30 kPa). From 15 minutes before inspection starts to completion of inspection, water level must not drop. Inspect joints for leaks.

4. Finished Plumbing Test Procedure: After plumbing fixtures have been set and traps filled with water, test connections and prove they are gastight and watertight. Plug vent-stack openings on roof and building drains where they leave building. Introduce air into piping system equal to pressure of 1-inch wg (250 Pa). Use U-tube or manometer inserted in trap of water closet to measure this pressure. Air pressure must remain constant without introducing additional air throughout period of inspection. Inspect plumbing fixture connections for gas and water leaks.

5. Repair leaks and defects with new materials and retest piping, or portion thereof, until satisfactory results are obtained.

6. Prepare reports for tests and required corrective action.

3.7 CLEANING

A. Clean interior of piping. Remove dirt and debris as work progresses.

B. Protect drains during remainder of construction period to avoid clogging with dirt and debris and to prevent damage from traffic and construction work.

C. Place plugs in ends of uncompleted piping at end of day and when work stops.

3.8 PROTECTION

A. Exposed PVC Piping: Protect plumbing vents exposed to sunlight with two coats of water-based latex paint.

END OF SECTION 22 13 00

Page 70: PLUMBING, ELECTRICAL & FIRE PROTECTION COMPONENTS … · mechanical, electrical, plumbing and fire protection building system components in place during a seismic or high wind event

Permit Fairview Municipal Building 55 Anderson Ave. Fairview, NJ Issue December 31, 2015

22 14 00-1 STORM DRAINAGE PIPING 1 of 8

SECTION 22 14 00 STORM DRAINAGE PIPING

PART 1 - GENERAL

1.1 RELATED DOCUMENTS

A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to this Section.

1.2 SUMMARY

A. This Section includes storm-drainage piping inside the building and to locations indicated.

B. Related Sections include the following:

1. Division 22 Section "Plumbing Specialties" for storm drainage piping system specialties. 2. Division 22 Section "Sump Pumps."

1.3 PERFORMANCE REQUIREMENTS

A. Provide components and installation capable of producing piping systems with the following minimum working-pressure ratings, unless otherwise indicated:

1. Storm Drainage Piping: 10-foot head of water. 2. Storm Drainage, Force-Main Piping: 50 psig.

1.4 SUBMITTALS

A. Product Data: For pipe, tube, fittings, and couplings.

B. Shop Drawings: For controlled-flow storm drainage system, include calculations, plans, and details.

C. Field Test Reports: Indicate and interpret test results for compliance with performance requirements.

1.5 QUALITY ASSURANCE

A. Piping materials shall bear label, stamp, or other markings of specified testing agency.

PART 2 - PRODUCTS

2.1 PIPING MATERIALS

Page 71: PLUMBING, ELECTRICAL & FIRE PROTECTION COMPONENTS … · mechanical, electrical, plumbing and fire protection building system components in place during a seismic or high wind event

Permit Fairview Municipal Building 55 Anderson Ave. Fairview, NJ Issue December 31, 2015

22 14 00-2 STORM DRAINAGE PIPING 2 of 8

A. Refer to Part 3 "Piping Applications" Article for applications of pipe, tube, fitting, and joining materials.

B. Flexible Transition Couplings for Underground Nonpressure Piping: ASTM C 1173 with elastomeric sleeve. Include ends of same sizes as piping to be joined and include corrosion-resistant metal band on each end.

C. Transition Couplings for Underground Pressure Piping: AWWA C219 metal, sleeve-type coupling or other manufactured fitting same size as, with pressure rating at least equal to and ends compatible with, piping to be joined.

2.2 CAST-IRON SOIL PIPING

A. Hub-and-Spigot Pipe and Fittings: ASTM A 74, Service and Extra-Heavy classes.

1. Gaskets: ASTM C 564, rubber.

B. Hubless Pipe and Fittings: ASTM A 888 or CISPI 301.

1. Couplings: ASTM C 1277 assembly of metal housing, corrosion-resistant fasteners, and ASTM C 564 rubber sleeve with integral center pipe stop.

a. Heavy-Duty, Type 304, Stainless-Steel Couplings: ASTM A 666, Type 304, stainless-steel shield; stainless-steel bands; and sleeve.

1) NPS 1-1/2 to NPS 4 (DN 40 to DN 100): 3-inch- (76-mm-) wide shield with 4 bands.

2) NPS 5 to NPS 10 (DN 125 to DN 250): 4-inch- (102-mm-) wide shield with 6 bands.

PART 3 - EXECUTION

3.1 PIPING APPLICATIONS

A. Transition and special fittings with pressure ratings at least equal to piping pressure ratings may be used in applications below, unless otherwise indicated.

B. Flanges may be used on aboveground pressure piping, unless otherwise indicated.

C. Aboveground Storm Drainage Piping: Use the following piping materials for each size range: a. All Sizes: Hubless, cast-iron soil piping, and Couplings: Heavy-duty, FM

approved or cast iron.

D. Underground Storm Drainage Piping: Use the following piping materials for each size range:

1. All Sizes: Service class, cast-iron soil piping; gaskets; and gasketed joints.

Page 72: PLUMBING, ELECTRICAL & FIRE PROTECTION COMPONENTS … · mechanical, electrical, plumbing and fire protection building system components in place during a seismic or high wind event

Permit Fairview Municipal Building 55 Anderson Ave. Fairview, NJ Issue December 31, 2015

22 14 00-3 STORM DRAINAGE PIPING 3 of 8

E. Aboveground Storm Drainage Force Mains: Use the following piping materials for each size range: 1. All Sizes: Galvanized Steel pipe; gray-iron, threaded fittings; and threaded joints.

F. Underground Storm Drainage Force Mains: Use the following piping materials for each size range: 1. All Sizes: Galvanized Steel pipe; gray-iron, threaded fittings; and threaded joints.

3.2 PIPING INSTALLATION

A. Refer to Division 22 Section "Storm Drainage Piping" for Project site storm sewer and drainage piping.

B. Refer to Division 23 Section "Basic Mechanical Materials and Methods" for basic piping installation.

C. Install cleanouts at grade and extend to where building storm drains connect to building storm sewers.

D. Install cleanout fitting with closure plug inside the building in storm drainage force-main piping.

E. Underground, Ductile-Iron, Force-Main Piping: Comply with AWWA C600. Install buried piping inside building between wall and floor penetrations and connection to storm sewer piping outside building with restrained joints. Anchor pipe to wall or floor. Install thrust-block supports at vertical and horizontal offsets.

1. Encase piping with PE film according to ASTM A 674 or AWWA C105.

F. Install cast-iron sleeve with water stop and mechanical sleeve seal at each service pipe penetration through foundation wall. Select number of interlocking rubber links required to make installation watertight. Refer to Division 23 Section "Basic Mechanical Materials and Methods" for sleeves and mechanical sleeve seals.

G. Install wall penetration system at each service pipe penetration through foundation wall. Make installation watertight. Refer to Division 23 Section "Basic Mechanical Materials and Methods" for wall penetration systems.

H. Install cast-iron soil piping according to CISPI's "Cast Iron Soil Pipe and Fittings Handbook," Chapter IV, "Installation of Cast Iron Soil Pipe and Fittings."

1. Encase underground piping with PE film according to ASTM A 674 or AWWA C105.

I. Make changes in direction for storm piping using appropriate branches, bends, and long-sweep bends. Do not change direction of flow more than 90 degrees. Use proper size of standard increasers and reducers if pipes of different sizes are connected. Reducing size of drainage piping in direction of flow is prohibited.

J. Lay buried building drain piping beginning at low point of each system. Install true to grades and alignment indicated, with unbroken continuity of invert. Place hub ends of piping

Page 73: PLUMBING, ELECTRICAL & FIRE PROTECTION COMPONENTS … · mechanical, electrical, plumbing and fire protection building system components in place during a seismic or high wind event

Permit Fairview Municipal Building 55 Anderson Ave. Fairview, NJ Issue December 31, 2015

22 14 00-4 STORM DRAINAGE PIPING 4 of 8

upstream. Install required gaskets according to manufacturer's written instructions for use of lubricants, cements, and other installation requirements. Maintain swab in piping and pull past each joint as completed.

K. Install storm drainage piping at the following minimum slopes, unless otherwise indicated:

1. Building Storm Drain: 1 percent downward in direction of flow for piping NPS 3 (DN 80) and smaller; 1 percent downward in direction of flow for piping NPS 4 (DN 100) and larger.

2. Horizontal Storm-Drainage Piping: 2 percent downward in direction of flow.

L. Install force mains at elevations indicated.

M. Install engineered controlled-flow storm drainage piping in locations indicated.

N. Sleeves are not required for cast-iron soil piping passing through concrete slabs-on-grade if slab is without membrane waterproofing.

O. Do not enclose, cover, or put piping into operation until it is inspected and approved by authorities having jurisdiction.

3.3 JOINT CONSTRUCTION

A. Refer to Division 23 Section "Basic Mechanical Materials and Methods" for basic piping joint construction.

B. Cast-Iron, Soil-Piping Joints: Make joints according to CISPI's "Cast Iron Soil Pipe and Fittings Handbook," Chapter IV, "Installation of Cast Iron Soil Pipe and Fittings."

1. Gasketed Joints: Make with rubber gasket matching class of pipe and fittings. 2. Hubless Joints: Make with rubber gasket and sleeve or clamp.

3.4 VALVE INSTALLATION

A. Refer to Division 23 Section "Valves" for general-duty valves.

B. Shutoff Valves: Install shutoff valve on each sump pump discharge.

1. Use gate or full-port ball valve for piping NPS 2 and smaller. 2. Use gate valve for piping NPS 2-1/2 and larger.

C. Check Valves: Install swing check valve, downstream from shutoff valve, on each sump pump discharge.

3.5 HANGER AND SUPPORT INSTALLATION

A. Refer to Division 20 Section "Vibration Isolation, Seismic, Wind & Flood Load Restraints for HVAC, Plumbing, Electrical & Fire Protection Components" for seismic-restraint devices.

Page 74: PLUMBING, ELECTRICAL & FIRE PROTECTION COMPONENTS … · mechanical, electrical, plumbing and fire protection building system components in place during a seismic or high wind event

Permit Fairview Municipal Building 55 Anderson Ave. Fairview, NJ Issue December 31, 2015

22 14 00-5 STORM DRAINAGE PIPING 5 of 8

B. Refer to Division 23 Section "Hangers and Supports" for pipe hanger and support devices. Install the following:

1. Vertical Piping: MSS Type 8 or Type 42, clamps. 2. Individual, Straight, Horizontal Piping Runs: According to the following:

a. 100 Feet (30 m) and Less: MSS Type 1, adjustable, steel clevis hangers. b. Longer Than 100 Feet (30 m): MSS Type 43, adjustable roller hangers. c. Longer Than 100 Feet (30 m), if Indicated: MSS Type 49, spring cushion rolls.

3. Multiple, Straight, Horizontal Piping Runs 100 Feet (30 m) or Longer: MSS Type 44, pipe rolls. Support pipe rolls on trapeze.

4. Base of Vertical Piping: MSS Type 52, spring hangers.

C. Install supports according to Division 23 Section "Hangers and Supports."

D. Support vertical piping and tubing at base and at each floor.

E. Rod diameter may be reduced 1 size for double-rod hangers, with 3/8-inch (10-mm) minimum rods.

F. Install hangers for cast-iron soil piping with the following maximum horizontal spacing and minimum rod diameters:

1. NPS 1-1/2 and NPS 2 (DN 40 and DN 50): 60 inches (1500 mm) with 3/8-inch (10-mm) rod.

2. NPS 3 (DN 80): 60 inches (1500 mm) with 1/2-inch (13-mm) rod. 3. NPS 4 and NPS 5 (DN 100 and DN 125): 60 inches (1500 mm) with 5/8-inch (16-mm)

rod. 4. NPS 6 (DN 150): 60 inches (1500 mm) with 3/4-inch (19-mm) rod. 5. NPS 8 to NPS 12 (DN 200 to DN 300): 60 inches (1500 mm) with 7/8-inch (22-mm)

rod. 6. NPS 15 (DN 375): 60 inches (1500 mm) with 1-inch (25-mm) rod. 7. Spacing for 10-foot (3-m) lengths may be increased to 10 feet (3 m). Spacing for fittings

is limited to 60 inches (1500 mm).

G. Install supports for vertical cast-iron soil piping every 15 feet (4.5 m).

H. Install hangers for steel piping with the following maximum horizontal spacing and minimum rod diameters:

1. NPS 1-1/4 (DN 32): 84 inches (2100 mm) with 3/8-inch (10-mm) rod. 2. NPS 1-1/2 (DN 40): 108 inches (2700 mm) with 3/8-inch (10-mm) rod. 3. NPS 2 (DN 50): 10 feet (3 m) with 3/8-inch (10-mm) rod. 4. NPS 2-1/2 (DN 65): 11 feet (3.4 m) with 1/2-inch (13-mm) rod. 5. NPS 3 (DN 80): 12 feet (3.7 m) with 1/2-inch (13-mm) rod. 6. NPS 4 and NPS 5 (DN 100 and DN 125): 12 feet (3.7 m) with 5/8-inch (16-mm) rod. 7. NPS 6 (DN 150): 12 feet (3.7 m) with 3/4-inch (19-mm) rod. 8. NPS 8 to NPS 12 (DN 200 to DN 300): 12 feet (3.7 m) with 7/8-inch (22-mm) rod.

I. Install supports for vertical steel piping every 15 feet (4.5 m).

Page 75: PLUMBING, ELECTRICAL & FIRE PROTECTION COMPONENTS … · mechanical, electrical, plumbing and fire protection building system components in place during a seismic or high wind event

Permit Fairview Municipal Building 55 Anderson Ave. Fairview, NJ Issue December 31, 2015

22 14 00-6 STORM DRAINAGE PIPING 6 of 8

J. Install hangers for copper tubing with the following maximum horizontal spacing and minimum rod diameters:

1. NPS 1-1/4 (DN 32): 72 inches (1800 mm) with 3/8-inch (10-mm) rod. 2. NPS 1-1/2 and NPS 2 (DN 40 and DN 50): 96 inches (2400 mm) with 3/8-inch (10-mm)

rod. 3. NPS 2-1/2 (DN 65): 108 inches (2700 mm) with 1/2-inch (13-mm) rod. 4. NPS 3 to NPS 5 (DN 80 to DN 125): 10 feet (3 m) with 1/2-inch (13-mm) rod. 5. NPS 6 (DN 150): 10 feet (3 m) with 5/8-inch (16-mm) rod. 6. NPS 8 (DN 200): 10 feet (3 m) with 3/4-inch (19-mm) rod.

K. Install supports for vertical copper tubing every 10 feet (3 m).

L. Install hangers for ABS and PVC piping with the following maximum horizontal spacing and minimum rod diameters:

1. NPS 1-1/2 and NPS 2 (DN 40 and DN 50): 48 inches (1200 mm) with 3/8-inch (10-mm) rod.

2. NPS 3 (DN 80): 48 inches (1200 mm) with 1/2-inch (13-mm) rod. 3. NPS 4 and NPS 5 (DN 100 and DN 125): 48 inches (1200 mm) with 5/8-inch (16-mm)

rod. 4. NPS 6 (DN 150): 48 inches (1200 mm) with 3/4-inch (19-mm) rod. 5. NPS 8 to NPS 12 (DN 200 to DN 300): 48 inches (1200 mm) with 7/8-inch (22-mm)

rod.

M. Install supports for vertical ABS and PVC piping every 48 inches (1200 mm).

N. Support piping and tubing not listed above according to MSS SP-69 and manufacturer's written instructions.

3.6 CONNECTIONS

A. Drawings indicate general arrangement of piping, fittings, and specialties.

B. Connect interior storm drainage piping to exterior storm drainage piping. Use transition fitting to join dissimilar piping materials.

C. Connect storm drainage piping to roof drains and storm drainage specialties.

D. Connect force-main piping to the following:

1. Storm Sewer: To exterior force main or storm manhole. 2. Sump Pumps: To sump pump discharge.

3.7 FIELD QUALITY CONTROL

A. During installation, notify authorities having jurisdiction at least 24 hours before inspection must be made. Perform tests specified below in presence of authorities having jurisdiction.

Page 76: PLUMBING, ELECTRICAL & FIRE PROTECTION COMPONENTS … · mechanical, electrical, plumbing and fire protection building system components in place during a seismic or high wind event

Permit Fairview Municipal Building 55 Anderson Ave. Fairview, NJ Issue December 31, 2015

22 14 00-7 STORM DRAINAGE PIPING 7 of 8

1. Roughing-in Inspection: Arrange for inspection of piping before concealing or closing-in after roughing-in.

2. Final Inspection: Arrange for final inspection by authorities having jurisdiction to observe tests specified below and to ensure compliance with requirements.

B. Reinspection: If authorities having jurisdiction find that piping will not pass test or inspection, make required corrections and arrange for reinspection.

C. Reports: Prepare inspection reports and have them signed by authorities having jurisdiction.

D. Test storm drainage piping according to procedures of authorities having jurisdiction or, in absence of published procedures, as follows:

1. Test for leaks and defects in new piping and parts of existing piping that have been altered, extended, or repaired. If testing is performed in segments, submit separate report for each test, complete with diagram of portion of piping tested.

2. Leave uncovered and unconcealed new, altered, extended, or replaced storm drainage piping until it has been tested and approved. Expose work that was covered or concealed before it was tested.

3. Test Procedure: Test storm drainage piping, except outside leaders, on completion of roughing-in. Close openings in piping system and fill with water to point of overflow, but not less than 10-foot head of water (30 kPa). From 15 minutes before inspection starts to completion of inspection, water level must not drop. Inspect joints for leaks.

4. Repair leaks and defects with new materials and retest piping, or portion thereof, until satisfactory results are obtained.

5. Prepare reports for tests and required corrective action.

E. Test force-main piping according to procedures of authorities having jurisdiction or, in absence of published procedures, as follows:

1. Leave uncovered and unconcealed new, altered, extended, or replaced force-main piping until it has been tested and approved. Expose work that was covered or concealed before it was tested.

2. Cap and subject piping to static-water pressure of 50 psig (345 kPa) above operating pressure, without exceeding pressure rating of piping system materials. Isolate test source and allow to stand for four hours. Leaks and loss in test pressure constitute defects that must be repaired.

3. Repair leaks and defects with new materials and retest piping, or portion thereof, until satisfactory results are obtained.

4. Prepare reports for tests and required corrective action.

3.8 CLEANING

A. Clean interior of piping. Remove dirt and debris as work progresses.

B. Protect drains during remainder of construction period to avoid clogging with dirt and debris and to prevent damage from traffic and construction work.

C. Place plugs in ends of uncompleted piping at end of day and when work stops.

Page 77: PLUMBING, ELECTRICAL & FIRE PROTECTION COMPONENTS … · mechanical, electrical, plumbing and fire protection building system components in place during a seismic or high wind event

Permit Fairview Municipal Building 55 Anderson Ave. Fairview, NJ Issue December 31, 2015

22 14 00-8 STORM DRAINAGE PIPING 8 of 8

END OF SECTION 22 14 00

Page 78: PLUMBING, ELECTRICAL & FIRE PROTECTION COMPONENTS … · mechanical, electrical, plumbing and fire protection building system components in place during a seismic or high wind event

Permit Fairview Municipal Building 55 Anderson Ave. Fairview, NJ Issue December 31, 2015

22 33 00-1 ELECTRIC, DOMESTIC WATER HEATERS 1 of 6

SECTION 22 33 00 ELECTRIC, DOMESTIC WATER HEATERS

PART 1 - GENERAL

1.1 RELATED DOCUMENTS

A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to this Section.

1.2 SUMMARY

A. This Section includes the following for domestic water systems:

1. Commercial, electric water heaters.

1.3 SUBMITTALS

A. Product Data: For each type and size of water heater. Include rated capacities; shipping, installed, and operating weights; furnished specialties; and accessories.

B. Shop Drawings: Detail water heater assemblies and indicate dimensions, weights, loads, required clearances, method of field assembly, components, and location and size of each field connection.

1. Wiring Diagrams: Power, signal, and control wiring. Differentiate between manufacturer-installed and field-installed wiring.

C. Product Certificates: Signed by manufacturers of water heaters certifying that products furnished comply with requirements.

D. Maintenance Data: For water heaters to include in maintenance manuals specified in Division 1.

E. Warranties: Special warranties specified in this Section.

1.4 QUALITY ASSURANCE

A. Source Limitations: Obtain same type of water heaters through one source from a single manufacturer.

B. Product Options: Drawings indicate size, profiles, and dimensional requirements of water heaters and are based on specific units indicated. Other manufacturers' products complying with requirements may be considered. Refer to Division 1 Section "Substitutions."

Page 79: PLUMBING, ELECTRICAL & FIRE PROTECTION COMPONENTS … · mechanical, electrical, plumbing and fire protection building system components in place during a seismic or high wind event

Permit Fairview Municipal Building 55 Anderson Ave. Fairview, NJ Issue December 31, 2015

22 33 00-2 ELECTRIC, DOMESTIC WATER HEATERS 2 of 6

C. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, Article 100, by testing agency acceptable to authorities having jurisdiction, and marked for intended use.

D. ASME Compliance: Fabricate and label water heater, hot-water storage tanks to comply with ASME Boiler and Pressure Vessel Code: Section VIII, "Pressure Vessels," Division 1.

E. ASHRAE Standards: Comply with performance efficiencies prescribed for the following:

1. ASHRAE 90.1, "Energy Efficient Design of New Buildings except Low-Rise Residential Buildings," for commercial water heaters.

1.5 WARRANTY

A. General Warranty: Special warranty specified in this Article shall not deprive Owner of other rights Owner may have under other provisions of the Contract Documents and shall be in addition to, and run concurrent with, other warranties made by Contractor under requirements of the Contract Documents.

B. Special Warranty: Written warranty, executed by manufacturer agreeing to repair or replace components of water heaters that fail in materials or workmanship within specified warranty period.

1. Failures include heating elements, storage tanks, and heat-pump heat exchangers and compressors.

2. Warranty Period: From date of Substantial Completion:

a. Heating Elements: Five years. b. Storage Tanks: 10 years.

PART 2 - PRODUCTS

2.1 MANUFACTURERS

A. Manufacturers: Subject to compliance with requirements, provide products by one of the following:

1. Commercial, Point-of-Use, Storage, Electric Water Heaters:

a. American Water Heater Co. b. Electric Heater Co. c. GSW Water Heating Co. d. Lochinvar Corp. e. Rheem Manufacturing Co.; Rheem Water Heater Div. f. Rheem Manufacturing Co.; Ruud Water Heater Div. g. Smith: A. O. Smith Water Products Co. h. State Industries.

Page 80: PLUMBING, ELECTRICAL & FIRE PROTECTION COMPONENTS … · mechanical, electrical, plumbing and fire protection building system components in place during a seismic or high wind event

Permit Fairview Municipal Building 55 Anderson Ave. Fairview, NJ Issue December 31, 2015

22 33 00-3 ELECTRIC, DOMESTIC WATER HEATERS 3 of 6

2. Water Heater Stand and Drain Pan Units:

a. Oately

b. Holdrite

3. Compression Tanks:

a. Amtrol, Inc. b. Armstrong Pumps, Inc. c. Myers: F. E. Myers. d. Smith: A. O. Smith; Aqua-Air Div. e. State Industries. f. Taco, Inc. g. Wessels Co. h. Zurn Industries, Inc.; Wilkins Div.

2.2 COMMERCIAL, POINT-OF-USE, STORAGE, ELECTRIC WATER HEATERS

A. Description: Comply with UL 174 or UL 1453, and listed by manufacturer for commercial applications.

B. Storage Tank Construction: ASME-code steel with 150-psig working-pressure rating.

1. Tappings: Factory fabricated of materials compatible with tank for piping connections, relief valve, drain, anode rod, and controls as required. Attach tappings to tank before testing and labeling. Include ASME B1.20.1, pipe thread.

2. Interior Finish: Materials and thicknesses complying with NSF 61, barrier materials for potable-water tank linings. Extend finish into and through tank fittings and outlets.

3. Insulation: Comply with ASHRAE 90.1. Surround entire storage tank except connections and controls.

4. Jacket: Steel, with enameled finish.

C. Heating Elements: Two, unless otherwise indicated; electric, screw-in, immersion type.

1. Temperature Control: Adjustable thermostat.

D. Anode Rod: Factory installed, magnesium.

E. Drain Valve: ASSE 1005, corrosion-resistant metal, factory installed.

F. Special Requirement: NSF 5 construction.

2.3 COMPRESSION TANKS

A. Description: Steel, pressure-rated tank constructed with welded joints and factory-installed, butyl-rubber diaphragm. Include air precharge to minimum system-operating pressure at tank.

Page 81: PLUMBING, ELECTRICAL & FIRE PROTECTION COMPONENTS … · mechanical, electrical, plumbing and fire protection building system components in place during a seismic or high wind event

Permit Fairview Municipal Building 55 Anderson Ave. Fairview, NJ Issue December 31, 2015

22 33 00-4 ELECTRIC, DOMESTIC WATER HEATERS 4 of 6

B. Construction: 150-psig (1035-kPa) working-pressure rating.

C. Tappings: Factory-fabricated steel, welded to tank before testing and labeling. Include ASME B1.20.1, pipe thread.

D. Tank Interior Finish: Materials and thicknesses complying with NSF 61, barrier materials for potable-water tank linings. Extend finish into and through tank fittings and outlets.

E. Tank Exterior Finish: Manufacturer's standard, unless finish is indicated.

F. Air-Charging Valve: Factory installed.

2.4 WATER HEATER ACCESSORIES

A. Combination Temperature and Pressure Relief Valves: ASME rated and stamped and complying with ASME PTC 25.3. Include relieving capacity at least as great as heat input and include pressure setting less than water heater working-pressure rating. Select relief valve with sensing element that extends into tank.

1. Option: Separate temperature and pressure relief valves are acceptable instead of combination relief valve.

2. Exception: Omit combination temperature and pressure relief valve for tankless water heater, and furnish pressure relief valve for installation in piping.

B. Pressure Relief Valves: ASME rated and stamped and complying with ASME PTC 25.3. Include pressure setting less than heat-exchanger working-pressure rating.

C. Water Heater Stands: Water heater manufacturer's factory-fabricated, steel stand for floor mounting and capable of supporting water heater and water. Include dimension that will support bottom of water heater a minimum of 18 inches (457 mm) above the floor.

D. Water Heater Mounting Brackets: Water heater manufacturer's factory-fabricated, steel bracket for wall mounting and capable of supporting water heater and water.

E. Drain Pans: Corrosion-resistant metal with raised edge. Include dimensions not less than base of water heater and include drain outlet not less than 1” PVC.

PART 3 - EXECUTION

3.1 CONCRETE BASES

A. Install concrete bases of dimensions indicated. Refer to Division 23 Section "Basic Mechanical Materials and Methods."

3.2 WATER HEATER INSTALLATION

Page 82: PLUMBING, ELECTRICAL & FIRE PROTECTION COMPONENTS … · mechanical, electrical, plumbing and fire protection building system components in place during a seismic or high wind event

Permit Fairview Municipal Building 55 Anderson Ave. Fairview, NJ Issue December 31, 2015

22 33 00-5 ELECTRIC, DOMESTIC WATER HEATERS 5 of 6

A. Install commercial water heaters on concrete bases.

1. Exception: Omit concrete bases for commercial water heaters if installation on stand, bracket, suspended platform, or direct on floor is indicated.

B. Install water heaters, level and plumb, according to layout drawings, original design, and referenced standards. Maintain manufacturer's recommended clearances. Arrange units so controls and devices needing service are accessible.

C. Anchor water heaters to substrate.

D. Install seismic restraints for water heaters. Anchor to substrate.

E. Install temperature and pressure relief valves in top portion of storage tanks. Use relief valves with sensing elements that extend into tanks. Extend relief valve outlet with water piping in continuous downward pitch and discharge onto closest floor drain.

F. Install pressure relief valves in water piping for water heaters without storage. Extend relief valve outlet with water piping in continuous downward pitch and discharge onto closest floor drain.

G. Install water heater drain piping as indirect waste to spill into open drains or over floor drains. Install hose-end drain valves at low points in water piping for water heaters that do not have tank drains. Refer to Division 22 Section "Plumbing Specialties" for drain valves.

H. Fill water heaters with water.

I. Charge compression tanks with air.

3.3 CONNECTIONS

A. Piping installation requirements are specified in other Division 23 Sections. Drawings indicate general arrangement of piping, fittings, and specialties.

B. Install piping adjacent to machine to allow service and maintenance.

C. Connect hot- and cold-water piping with shutoff valves and unions. Connect hot-water-circulating piping with shutoff valve, check valve, and union.

D. Make connections with dielectric fittings where piping is made of dissimilar metal.

E. Electrical Connections: Power wiring and disconnect switches are specified in Division 26 Sections. Arrange wiring to allow unit service.

F. Ground equipment.

1. Tighten electrical connectors and terminals according to manufacturer's published torque-tightening values. If manufacturer's torque values are not indicated, use those specified in UL 486A and UL 486B.

Page 83: PLUMBING, ELECTRICAL & FIRE PROTECTION COMPONENTS … · mechanical, electrical, plumbing and fire protection building system components in place during a seismic or high wind event

Permit Fairview Municipal Building 55 Anderson Ave. Fairview, NJ Issue December 31, 2015

22 33 00-6 ELECTRIC, DOMESTIC WATER HEATERS 6 of 6

3.4 FIELD QUALITY CONTROL

A. Engage a factory-authorized service representative to perform startup service.

B. In addition to manufacturer's written installation and startup checks, perform the following:

1. Test and adjust controls and safeties. Replace damaged and malfunctioning controls and equipment.

2. Verify that piping system tests are complete. 3. Check for piping connection leaks. 4. Check for clear relief valve inlets, outlets, and drain piping. 5. Check operation of circulators. 6. Test operation of safety controls, relief valves, and devices. 7. Energize electric circuits. 8. Adjust operating controls. 9. Adjust hot-water-outlet temperature settings. Do not set above 140 deg F (60 deg C)

unless piping system application requires higher temperature.

3.5 DEMONSTRATION

A. Engage a factory-authorized service representative to train Owner's maintenance personnel to adjust, operate, and maintain water heaters.

1. Train Owner's maintenance personnel on procedures for starting and stopping, troubleshooting, servicing, and maintaining equipment.

2. Review data in maintenance manuals. Refer to Division 1 Section "Contract Closeout." 3. Review data in maintenance manuals. Refer to Division 1 Section "Operation and

Maintenance Data." 4. Schedule training with Owner, through Architect, with at least seven days' advance

notice.

END OF SECTION 22 33 00

Page 84: PLUMBING, ELECTRICAL & FIRE PROTECTION COMPONENTS … · mechanical, electrical, plumbing and fire protection building system components in place during a seismic or high wind event

Permit Fairview Municipal Building 55 Anderson Ave. Fairview, NJ Issue December 31, 2015

22 33 45-1 SUMP PUMPS 1 of 4

SECTION 22 33 45 SUMP PUMPS

PART 1 - GENERAL

1.1 RELATED DOCUMENTS

A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to this Section.

1.2 SUMMARY

A. This Section includes sump pumps for the building storm drainage systems.

1.3 SUBMITTALS

A. Product Data: Include performance curves, furnished specialties, and accessories for each type and size of pump indicated.

B. Shop Drawings: Show layout and connections for pumps. Include setting drawings with templates, directions for installing foundation and anchor bolts, and other anchorages.

1. Wiring Diagrams: Detail wiring for power, signal, and control systems and differentiate between manufacturer-installed and field-installed wiring.

C. Maintenance Data: For each type and size of pump specified to include in maintenance manuals specified in Division 1.

1.4 QUALITY ASSURANCE

A. Product Options: Drawings indicate size, profiles, connections, and dimensional requirements of pumps and are based on specific manufacturer types and models indicated. Other manufacturers' pumps with equal performance characteristics may be considered. Refer to Division 1 Section "Substitutions."

B. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, Article 100, by a testing agency acceptable to authorities having jurisdiction.

1.5 DELIVERY, STORAGE, AND HANDLING

A. Retain shipping flange protective covers and protective coatings during storage.

B. Protect bearings and couplings against damage.

C. Comply with pump manufacturer's rigging instructions for handling.

Page 85: PLUMBING, ELECTRICAL & FIRE PROTECTION COMPONENTS … · mechanical, electrical, plumbing and fire protection building system components in place during a seismic or high wind event

Permit Fairview Municipal Building 55 Anderson Ave. Fairview, NJ Issue December 31, 2015

22 33 45-2 SUMP PUMPS 2 of 4

PART 2 - PRODUCTS

2.1 MANUFACTURERS

A. Manufacturers: Subject to compliance with requirements, provide products by one of the following:

1. Packaged, Drainage Pump Units:

a. Alyan Pump Co. b. Federal Pump Corp. c. Liberty Pumps. d. Little Giant Pump Co. e. Milton Roy Co.; Hartell Div. f. Myers: F. E. Myers Co. g. Sta-Rite Industries, Inc. h. Zoeller Pump Co.

2.2 SUMP PUMPS, GENERAL

A. Description: Factory-assembled and -tested, single-stage, centrifugal, end-suction sump pump units complying with UL 778. Include motor, operating controls, and construction for permanent installation.

B. Discharge Pipe End Connections NPS 2 and Smaller: Threaded. Pumps available only with flanged-end discharge pipe may be furnished with threaded companion flanges.

C. Discharge Pipe End Connections NPS 2-1/2 and Larger: Flanged.

D. Motors: Single speed, with grease-lubricated ball bearings, and non-overloading through full range of pump performance curves.

E. Finish: Manufacturer's standard paint applied to factory-assembled and -tested units before shipping.

F. Manufacturer's Preparation for Shipping: Clean flanges and exposed machined metal surfaces and treat with anticorrosion compound after assembling and testing. Protect flanges, pipe openings, and nozzles with wooden flange covers or with screwed-in plugs.

2.3 PACKAGED DRAINAGE PUMP UNITS

A. Description: Packaged, automatic-operation, submersible drainage pump; with plastic body, plastic impeller, plastic basin, and motor-mounted float switch with 72-inch- (1830-mm-) minimum power cord and plug.

1. Pump Seals: Mechanical type.

Page 86: PLUMBING, ELECTRICAL & FIRE PROTECTION COMPONENTS … · mechanical, electrical, plumbing and fire protection building system components in place during a seismic or high wind event

Permit Fairview Municipal Building 55 Anderson Ave. Fairview, NJ Issue December 31, 2015

22 33 45-3 SUMP PUMPS 3 of 4

2. Motor: Hermetically sealed, capacitor-start type, with built-in overload protection and three-conductor waterproof power cable of length required, with grounding plug and cable-sealing assembly for connection at pump.

3. Basin: Watertight with inlet pipe connection and gastight cover with vent and pump discharge connections. Plug vent opening if vent piping connection is not required.

4. Controls: Automatic, with mercury-float switches and electrical power cables. 5. Pump Discharge Piping: Manufacturer's standard steel pipe, copper tube, or plastic pipe. 6. Valves: Factory- or field-installed check and shutoff valves on each pump discharge.

PART 3 - EXECUTION

3.1 EXAMINATION

A. Examine roughing-in of plumbing piping systems to verify actual locations of piping connections before pump installation.

3.2 INSTALLATION

A. Install pumps according to manufacturer's written instructions.

B. Install pumps and arrange to provide access for maintenance, including removal of motors, impellers, couplings, and accessories.

C. Support piping so weight of piping is not supported by pumps.

D. Packaged Drainage Pump Units: Install and make direct connections to storm drainage piping.

3.3 CONNECTIONS

A. Storm drainage piping installation requirements are specified in Division 23 Section "Storm Drainage Piping." Drawings indicate general arrangement of piping and specialties. The following are specific connection requirements:

1. Install discharge pipe sizes equal to or greater than diameter of pump nozzles, and connect to storm drainage piping.

2. Install swing check valve and gate or ball valve on each sump pump discharge. Include spring-loaded or weighted-lever check valves for piping NPS 2-1/2 (DN65) and larger.

3. Install swing check valve and gate or ball valve on each automatic, packaged pump discharge.

B. Install electrical connections for power, controls, and devices.

C. Electrical power and control components, wiring, and connections are specified in Division 26 Sections.

D. Ground equipment.

Page 87: PLUMBING, ELECTRICAL & FIRE PROTECTION COMPONENTS … · mechanical, electrical, plumbing and fire protection building system components in place during a seismic or high wind event

Permit Fairview Municipal Building 55 Anderson Ave. Fairview, NJ Issue December 31, 2015

22 33 45-4 SUMP PUMPS 4 of 4

1. Tighten electrical connectors and terminals according to manufacturer's published torque-tightening values. If manufacturer's torque values are not indicated, use those specified in UL 486A and UL 486B

3.4 ADJUSTING

A. Pump Controls: Set pump controls for automatic start, stop, and alarm operation as required for system application.

3.5 COMMISSIONING

A. Final Checks before Starting: Perform the following preventive maintenance operations:

1. Lubricate bearings. 2. Disconnect couplings and check motors for proper direction of rotation. 3. Verify that each pump is free to rotate by hand. Do not operate pump if it is bound or

drags, until cause of trouble is determined and corrected. 4. Verify that pump controls are correct for required application.

B. Starting procedure for pumps with shutoff power not exceeding safe motor power is as follows:

1. Start motors. 2. Open discharge valves slowly. 3. Check general mechanical operation of pumps and motors.

END OF SECTION 22 33 45

Page 88: PLUMBING, ELECTRICAL & FIRE PROTECTION COMPONENTS … · mechanical, electrical, plumbing and fire protection building system components in place during a seismic or high wind event

Permit Fairview Municipal Building 55 Anderson Ave. Fairview, NJ Issue December 31, 2015

22 40 00-1 PLUMBING FIXTURES 1 of 6

SECTION 22 40 00 PLUMBING FIXTURES

PART 1 - GENERAL

1.1 RELATED DOCUMENTS

A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to this Section.

1.2 SUMMARY

A. This Section includes plumbing fixtures and related components.

B. Related Sections include the following:

1. Division 22 Section "Plumbing Specialties" for backflow preventers and specialty

fixtures not in this Section.

1.3 DEFINITIONS

A. Accessible Fixture: Plumbing fixture that can be approached, entered, and used by people with disabilities.

B. Fitting: Device that controls flow of water into or out of plumbing fixture. Fittings specified in this Section include supplies and stops, faucets and spouts, shower heads and tub spouts, drains and tailpieces, and traps and waste pipes. Piping and general-duty valves are included where indicated.

1.4 SUBMITTALS

A. Product Data: Include selected fixture and trim, fittings, accessories, appliances, appurtenances, equipment, and supports and indicate materials and finishes, dimensions, construction details, and flow-control rates for each type of fixture indicated.

B. Shop Drawings: Diagram power, signal, and control wiring and differentiate between manufacturer-installed and field-installed wiring.

C. Maintenance Data: For plumbing fixtures to include in maintenance manuals specified in Division 1.

1.5 QUALITY ASSURANCE

Page 89: PLUMBING, ELECTRICAL & FIRE PROTECTION COMPONENTS … · mechanical, electrical, plumbing and fire protection building system components in place during a seismic or high wind event

Permit Fairview Municipal Building 55 Anderson Ave. Fairview, NJ Issue December 31, 2015

22 40 00-2 PLUMBING FIXTURES 2 of 6

A. Source Limitations: Obtain plumbing fixtures, faucets, and other components of each category through one source from a single manufacturer.

1. Exception: If fixtures, faucets, or other components are not available from a single manufacturer, obtain similar products from other manufacturers specified for that category.

B. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, Article 100, by a testing agency acceptable to authorities having jurisdiction, and marked for intended use.

C. Regulatory Requirements: Comply with requirements in ICC A117.1, "Accessible and Usable Buildings and Facilities"; Public Law 90-480, "Architectural Barriers Act"; and Public Law 101-336, "Americans with Disabilities Act"; about plumbing fixtures for people with disabilities.

D. Regulatory Requirements: Comply with requirements in Public Law 102-486, "Energy Policy Act," about water flow and consumption rates for plumbing fixtures.

E. NSF Standard: Comply with NSF 61, "Drinking Water System Components--Health Effects," for fixture materials that will be in contact with potable water.

F. Select combinations of fixtures and trim, faucets, fittings, and other components that are compatible.

1.6 COORDINATION

A. Coordinate roughing-in and final plumbing fixture locations, and verify that fixtures can be installed to comply with original design and referenced standards.

PART 2 - PRODUCTS

2.1 MANUFACTURERS

A. Fixtures are scheduled on the plumbing drawings.

PART 3 - EXECUTION

3.1 EXAMINATION

A. Examine roughing-in for water soil and for waste piping systems and supports to verify actual locations and sizes of piping connections and that locations and types of supports match those indicated, before plumbing fixture installation. Use manufacturer's roughing-in data if roughing-in data are not indicated.

Page 90: PLUMBING, ELECTRICAL & FIRE PROTECTION COMPONENTS … · mechanical, electrical, plumbing and fire protection building system components in place during a seismic or high wind event

Permit Fairview Municipal Building 55 Anderson Ave. Fairview, NJ Issue December 31, 2015

22 40 00-3 PLUMBING FIXTURES 3 of 6

B. Examine walls, floors, and cabinets for suitable conditions where fixtures are to be installed.

C. Proceed with installation only after unsatisfactory conditions have been corrected.

3.2 FIXTURE INSTALLATION

A. Assemble fixtures, trim, fittings, and other components according to manufacturers' written instructions.

B. For wall-hanging fixtures, install off-floor supports affixed to building substrate.

1. Use carrier supports with waste fitting and seal for back-outlet fixtures. 2. Use chair-type carrier supports with rectangular steel uprights for accessible fixtures.

C. Install back-outlet, wall-hanging fixtures onto waste fitting seals and attach to supports.

D. Install floor-mounting fixtures on closet flanges or other attachments to piping or building substrate.

E. Install wall-hanging fixtures with tubular waste piping attached to supports.

F. Install floor-mounting, back-outlet water closets attached to building floor substrate and wall bracket and onto waste fitting seals.

G. Install counter-mounting fixtures in and attached to casework.

H. Install fixtures level and plumb according to manufacturers' written instructions and roughing-in drawings.

I. Install water-supply piping with stop on each supply to each fixture to be connected to water distribution piping. Attach supplies to supports or substrate within pipe spaces behind fixtures. Install stops in locations where they can be easily reached for operation.

1. Exception: Use ball, gate, or globe valve if stops are not specified with fixture. Refer to Division 23 Section "Valves" for general-duty valves.

J. Install trap and tubular waste piping on drain outlet of each fixture to be directly connected to sanitary drainage system.

K. Install tubular waste piping on drain outlet of each fixture to be indirectly connected to drainage system.

L. Install flushometer valves for accessible water closets and urinals with handle mounted on wide side of compartment. Install other actuators in locations that are easy for people with disabilities to reach.

M. Install tanks for accessible, tank-type water closets with lever handle mounted on wide side of compartment.

Page 91: PLUMBING, ELECTRICAL & FIRE PROTECTION COMPONENTS … · mechanical, electrical, plumbing and fire protection building system components in place during a seismic or high wind event

Permit Fairview Municipal Building 55 Anderson Ave. Fairview, NJ Issue December 31, 2015

22 40 00-4 PLUMBING FIXTURES 4 of 6

N. Install toilet seats on water closets.

O. Install faucet-spout fittings with specified flow rates and patterns in faucet spouts if faucets are not available with required rates and patterns. Include adapters if required.

P. Install water-supply, flow-control fittings with specified flow rates in fixture supplies at stop valves.

Q. Install faucet, flow-control fittings with specified flow rates and patterns in faucet spouts if faucets are not available with required rates and patterns. Include adapters if required.

R. Install shower, flow-control fittings with specified maximum flow rates in shower arms.

S. Install traps on fixture outlets.

1. Exception: Omit trap on fixtures with integral traps. 2. Exception: Omit trap on indirect wastes, unless otherwise indicated.

T. Install disposer in outlet of sinks indicated to have disposer. Install switch where indicated or in wall adjacent to sink if location is not indicated.

U. Install escutcheons at piping wall ceiling penetrations in exposed, finished locations and within cabinets and millwork. Use deep-pattern escutcheons if required to conceal protruding fittings. Refer to Division 23 Section "Basic Mechanical Materials and Methods" for escutcheons.

V. Set bathtubs, shower receptors, and service basins in leveling bed of cement grout. Refer to Division 23 Section "Basic Mechanical Materials and Methods" for grout.

W. Seal joints between fixtures and walls, floors, and counters using sanitary-type, one-part, mildew-resistant, silicone sealant. Match sealant color to fixture color.

3.3 CONNECTIONS

A. Piping installation requirements are specified in other Division 23 Sections. Drawings indicate general arrangement of piping, fittings, and specialties.

B. Connect water supplies from water distribution piping to fixtures.

C. Connect drain piping from fixtures to drainage piping.

D. Supply and Waste Connections to Plumbing Fixtures: Connect fixtures with water supplies, stops, risers, traps, and waste piping. Use size fittings required to match fixtures. Connect to plumbing piping.

E. Supply and Waste Connections to Fixtures and Equipment Specified in Other Sections: Connect fixtures and equipment with water supplies, stops, risers, traps, and waste piping specified. Use size fittings required to match fixtures and equipment. Connect to plumbing piping.

Page 92: PLUMBING, ELECTRICAL & FIRE PROTECTION COMPONENTS … · mechanical, electrical, plumbing and fire protection building system components in place during a seismic or high wind event

Permit Fairview Municipal Building 55 Anderson Ave. Fairview, NJ Issue December 31, 2015

22 40 00-5 PLUMBING FIXTURES 5 of 6

F. Ground equipment.

1. Tighten electrical connectors and terminals according to manufacturer's published torque-tightening values. If manufacturer's torque values are not indicated, use those specified in UL 486A and UL 486B.

3.4 FIELD QUALITY CONTROL

A. Verify that installed fixtures are categories and types specified for locations where installed.

B. Check that fixtures are complete with trim, faucets, fittings, and other specified components.

C. Inspect installed fixtures for damage. Replace damaged fixtures and components.

D. Test installed fixtures after water systems are pressurized for proper operation. Replace malfunctioning fixtures and components, then retest. Repeat procedure until units operate properly.

E. Install fresh batteries in sensor-operated mechanisms.

3.5 ADJUSTING

A. Operate and adjust faucets and controls. Replace damaged and malfunctioning fixtures, fittings, and controls.

B. Operate and adjust disposers, hot-water dispensers, and controls. Replace damaged and malfunctioning units and controls.

C. Adjust water pressure at faucets, shower valves, and flushometer valves to produce proper flow and stream.

D. Replace washers and seals of leaking and dripping faucets and stops.

3.6 CLEANING

A. Clean fixtures, faucets, and other fittings with manufacturers' recommended cleaning methods and materials. Do the following:

1. Remove faucet spouts and strainers, remove sediment and debris, and reinstall strainers and spouts.

2. Remove sediment and debris from drains.

3.7 PROTECTION

A. Provide protective covering for installed fixtures and fittings.

B. Do not allow use of fixtures for temporary facilities unless approved in writing by Owner.

Page 93: PLUMBING, ELECTRICAL & FIRE PROTECTION COMPONENTS … · mechanical, electrical, plumbing and fire protection building system components in place during a seismic or high wind event

Permit Fairview Municipal Building 55 Anderson Ave. Fairview, NJ Issue December 31, 2015

22 40 00-6 PLUMBING FIXTURES 6 of 6

END OF SECTION 22 40 00

Page 94: PLUMBING, ELECTRICAL & FIRE PROTECTION COMPONENTS … · mechanical, electrical, plumbing and fire protection building system components in place during a seismic or high wind event

Permit Fairview Municipal Building 55 Anderson Ave. Fairview, NJ Issue December 31, 2015

22 47 00-1 DRINKING FOUNTAINSAND WATER COOLERS 1 of 4

SECTION 22 47 00 DRINKING FOUNTAINS AND WATER COOLERS

PART 1 - GENERAL

1.1 RELATED DOCUMENTS

A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to this Section.

1.2 SUMMARY

A. This Section includes the following:

1. Drinking fountains. 2. Fixture supports.

1.3 DEFINITIONS

A. Accessible Drinking Fountain and Water Cooler: Fixture that can be approached and used by people with disabilities.

1.4 SUBMITTALS

A. Product Data: Include rated capacities; shipping, installed, and operating weights; furnished specialties; and accessories for each type of fixture indicated.

B. Shop Drawings: Diagram power, signal, and control wiring and differentiate between manufacturer-installed and field-installed wiring.

C. Field Test Reports: Indicate and interpret test results for compliance with performance requirements.

D. Maintenance Data: For fixtures to include in maintenance manuals specified in Division 1.

1.5 QUALITY ASSURANCE

A. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, Article 100, by a testing agency acceptable to authorities having jurisdiction, and marked for intended use.

B. Regulatory Requirements: Comply with requirements in ICC A117.1, "Accessible and Usable Buildings and Facilities"; Public Law 90-480, "Architectural Barriers Act"; and Public Law 101-336, "Americans with Disabilities Act"; about fixtures for people with disabilities.

Page 95: PLUMBING, ELECTRICAL & FIRE PROTECTION COMPONENTS … · mechanical, electrical, plumbing and fire protection building system components in place during a seismic or high wind event

Permit Fairview Municipal Building 55 Anderson Ave. Fairview, NJ Issue December 31, 2015

22 47 00-2 DRINKING FOUNTAINSAND WATER COOLERS 2 of 4

C. NSF Standard: Comply with NSF 61, "Drinking Water System Components--Health Effects," for fixture materials that will be in contact with potable water.

D. ARI Standard: Comply with ARI 1010, "Self-Contained, Mechanically Refrigerated Drinking-Water Coolers," for water coolers and with ARI's "Directory of Certified Drinking Water Coolers" for type and style classifications.

1.6 COORDINATION

A. Coordinate roughing-in and final fixture locations, and verify that fixtures can be installed to comply with original design and referenced standards.

1.7 EXTRA MATERIALS

A. Furnish extra materials described below that match products installed and that are packaged with protective covering for storage and identified with labels describing contents.

1. Filter Cartridges: Equal to 25 percent of amount installed for each type and size indicated, but not less than 5 of each.

PART 2 - PRODUCTS

2.1 MANUFACTURERS

A. For fixture descriptions in other Part 2 articles where the subparagraph titles "Available Products, "introduce a list of manufacturers and their products or manufacturers only, the following requirements apply for product selection: 1. Available Manufacturers: Subject to compliance with requirements, manufacturers

offering products that may be incorporated into the Work include, but are not limited to, the manufacturers specified in other Part 2 articles. A. Elkay B. Halsey Taylor

2.2 FIXTURE SUPPORT

A. Off-Floor, Plumbing Fixture Supports: ASME A112.6.1M, water-cooler carriers. Include vertical, steel uprights with feet and tie rods and bearing plates with mounting studs matching fixture to be supported.

1. Manufacturers:

a. Josam Co. b. Smith, Jay R. Mfg. Co. c. Tyler Pipe; Wade Div. d. Watts Industries, Inc.; Enpoco, Inc. Div. e. Watts Industries, Inc.; Watts Drainage Products Div.

Page 96: PLUMBING, ELECTRICAL & FIRE PROTECTION COMPONENTS … · mechanical, electrical, plumbing and fire protection building system components in place during a seismic or high wind event

Permit Fairview Municipal Building 55 Anderson Ave. Fairview, NJ Issue December 31, 2015

22 47 00-3 DRINKING FOUNTAINSAND WATER COOLERS 3 of 4

f. Zurn Specifications Drainage Operation.

2. Type II: Bilevel, hanger-type carrier with three vertical uprights. 3. Supports for Accessible Fixtures: Include rectangular, vertical, steel uprights instead of

steel pipe uprights.

PART 3 - EXECUTION

3.1 EXAMINATION

A. Examine roughing-in for water and waste piping systems to verify actual locations of piping connections before fixture installation. Verify that sizes and locations of piping and types of supports match those indicated.

B. Examine walls and floors for suitable conditions where fixtures are to be installed.

C. Proceed with installation only after unsatisfactory conditions have been corrected.

3.2 APPLICATIONS

A. Use carrier off-floor supports for wall-hanging fixtures, unless otherwise indicated.

B. Use chrome-plated brass or copper tube, fittings, and valves in locations exposed to view. Plain copper tube, fittings, and valves may be used in concealed locations.

3.3 INSTALLATION

A. Install off-floor supports affixed to building substrate and attach wall-hanging fixtures, unless otherwise indicated.

B. Install fixtures level and plumb.

C. Install water-supply piping with shutoff valve on supply to each fixture to be connected to water distribution piping. Use ball, gate, or globe valve. Install valves in locations where they can be easily reached for operation. Refer to Division 23 Section "Valves" for general-duty valves.

D. Install trap and waste piping on drain outlet of each fixture to be connected to sanitary drainage system.

E. Install pipe escutcheons at wall penetrations in exposed, finished locations. Use deep-pattern escutcheons where required to conceal protruding pipe fittings. Refer to Division 23 Section "Basic Mechanical Materials and Methods" for escutcheons.

F. Seal joints between fixtures and walls and floors using sanitary-type, one-part, mildew-resistant, silicone sealant. Match sealant color to fixture color.

3.4 CONNECTIONS

Page 97: PLUMBING, ELECTRICAL & FIRE PROTECTION COMPONENTS … · mechanical, electrical, plumbing and fire protection building system components in place during a seismic or high wind event

Permit Fairview Municipal Building 55 Anderson Ave. Fairview, NJ Issue December 31, 2015

22 47 00-4 DRINKING FOUNTAINSAND WATER COOLERS 4 of 4

A. Piping installation requirements are specified in other Division 23 Sections. Drawings indicate general arrangement of piping, fittings, and specialties.

B. Connect water supplies from water distribution piping to fixtures.

C. Connect drain piping from fixtures to drainage piping.

D. Ground equipment.

1. Tighten electrical connectors and terminals according to manufacturer's published torque-tightening values. If manufacturer's torque values are not indicated, use those specified in UL 486A and UL 486B.

3.5 FIELD QUALITY CONTROL

A. Water-Cooler Testing: After electrical circuitry has been energized, test for compliance with requirements. Test and adjust controls and safeties.

B. Repair or replace malfunctioning units. Retest as specified above after repairs or replacements are made.

C. Report test results in writing.

3.6 ADJUSTING

A. Adjust fixture flow regulators for proper flow and stream height.

B. Adjust water-cooler temperature settings.

3.7 CLEANING

A. After completing fixture installation, inspect unit. Remove paint splatters and other spots, dirt, and debris. Repair damaged finish to match original finish.

B. Clean fixtures, on completion of installation, according to manufacturer's written instructions.

END OF SECTION 22 47 00

Page 98: PLUMBING, ELECTRICAL & FIRE PROTECTION COMPONENTS … · mechanical, electrical, plumbing and fire protection building system components in place during a seismic or high wind event

Permit Fairview Municipal Building 55 Anderson Ave. Fairview NJ Issue December 31, 2015

26 05 00 - BASIC ELECTRICAL MATERIALS AND METHODS 1 of 10

SECTION 26 05 00 - BASIC ELECTRICAL MATERIALS AND METHODS

PART 1 - GENERAL

1.1 RELATED DOCUMENTS

A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to this Section.

1.2 SUMMARY

A. This Section includes the following:

1. Raceways. 2. Building wire and connectors. 3. Supporting devices for electrical components. 4. Electrical identification. 5. Electricity-metering components. 6. Concrete equipment bases. 7. Electrical demolition. 8. Cutting and patching for electrical construction. 9. Touchup painting.

1.3 DEFINITIONS

A. EMT: Electrical metallic tubing.

B. FMC: Flexible metal conduit.

C. IMC: Intermediate metal conduit.

D. LFMC: Liquidtight flexible metal conduit.

E. RNC: Rigid nonmetallic conduit.

F. MC: Metal Clad Cable

1.4 SUBMITTALS

A. Product Data: For electricity-metering equipment.

B. Shop Drawings: Dimensioned plans and sections or elevation layouts of electricity-metering equipment.

C. Field Test Reports: Indicate and interpret test results for compliance with performance requirements.

Page 99: PLUMBING, ELECTRICAL & FIRE PROTECTION COMPONENTS … · mechanical, electrical, plumbing and fire protection building system components in place during a seismic or high wind event

Permit Fairview Municipal Building 55 Anderson Ave. Fairview NJ Issue December 31, 2015

26 05 00 - BASIC ELECTRICAL MATERIALS AND METHODS 2 of 10

1.5 QUALITY ASSURANCE

A. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, Article 100, by a testing agency acceptable to authorities having jurisdiction, and marked for intended use.

B. Comply with NFPA 70.

1.6 COORDINATION

A. Coordinate chases, slots, inserts, sleeves, and openings with general construction work and arrange in building structure during progress of construction to facilitate the electrical installations that follow.

1. Set inserts and sleeves in poured-in-place concrete, masonry work, and other structural components as they are constructed.

B. Sequence, coordinate, and integrate installing electrical materials and equipment for efficient flow of the Work. Coordinate installing large equipment requiring positioning before closing in the building.

C. Coordinate electrical service connections to components furnished by utility companies.

1. Coordinate installation and connection of exterior underground and overhead utilities and services, including provision for electricity-metering components.

2. Comply with requirements of authorities having jurisdiction and of utility company providing electrical power and other services.

D. Coordinate location of access panels and doors for electrical items that are concealed by finished surfaces.

E. Where electrical identification devices are applied to field-finished surfaces, coordinate installation of identification devices with completion of finished surface.

F. Where electrical identification markings and devices will be concealed by acoustical ceilings and similar finishes, coordinate installation of these items before ceiling installation.

PART 2 - PRODUCTS

2.1 RACEWAYS

A. EMT: ANSI C80.3, zinc-coated steel, with set-screw or compression fittings.

B. FMC: Zinc-coated steel.

C. IMC: ANSI C80.6, zinc-coated steel, with threaded fittings.

D. LFMC: Zinc-coated steel with sunlight-resistant and mineral-oil-resistant plastic jacket.

E. RNC: NEMA TC 2, Schedule 40 PVC, with NEMA TC3 fittings.

F. Raceway Fittings: Specifically designed for the raceway type with which used.

Page 100: PLUMBING, ELECTRICAL & FIRE PROTECTION COMPONENTS … · mechanical, electrical, plumbing and fire protection building system components in place during a seismic or high wind event

Permit Fairview Municipal Building 55 Anderson Ave. Fairview NJ Issue December 31, 2015

26 05 00 - BASIC ELECTRICAL MATERIALS AND METHODS 3 of 10

G. ENT: Electrical Nonmetalic Tubing

2.2 CONDUCTORS

A. Conductors, No. 12 AWG and Smaller: Solid.

B. Conductors, No. 10 AWG and larger: Stranded copper.

C. Insulation: Thermoplastic, rated at 75 deg C minimum.

D. Wire Connectors and Splices: Units of size, ampacity rating, material, type, and class suitable for service indicated.

2.3 SUPPORTING DEVICES

A. Material: Cold-formed steel, with corrosion-resistant coating acceptable to authorities having jurisdiction.

B. Metal Items for Use Outdoors or in Damp Locations: Hot-dip galvanized steel.

C. Slotted-Steel Channel Supports: Flange edges turned toward web, and 9/16-inch diameter slotted holes at a maximum of 2 inches o.c., in webs.

D. Slotted-Steel Channel Supports:

1. Channel Thickness: Selected to suit structural loading. 2. Fittings and Accessories: Products of the same manufacturer as channel supports.

E. Nonmetallic Channel and Angle Systems: Structural-grade, factory-formed, glass-fiber-resin channels and angles with 9/16-inch diameter holes at a maximum of 8 inches o.c., in at least one surface.

1. Fittings and Accessories: Products of the same manufacturer as channels and angles. 2. Fittings and Accessory Materials: Same as channels and angles, except metal items may

be stainless steel.

F. Raceway and Cable Supports: Manufactured clevis hangers, riser clamps, straps, threaded C-clamps with retainers, ceiling trapeze hangers, wall brackets, and spring-steel clamps or click-type hangers.

G. Pipe Sleeves: ASTM A 53, Type E, Grade A, Schedule 40, galvanized steel, plain ends.

H. Cable Supports for Vertical Conduit: Factory-fabricated assembly consisting of threaded body and insulating wedging plug for nonarmored electrical cables in riser conduits. Plugs have number and size of conductor gripping holes as required to suit individual risers. Body constructed of malleable-iron casting with hot-dip galvanized finish.

I. Expansion Anchors: Carbon-steel wedge or sleeve type.

J. Toggle Bolts: All-steel springhead type.

K. Powder-Driven Threaded Studs: Heat-treated steel.

Page 101: PLUMBING, ELECTRICAL & FIRE PROTECTION COMPONENTS … · mechanical, electrical, plumbing and fire protection building system components in place during a seismic or high wind event

Permit Fairview Municipal Building 55 Anderson Ave. Fairview NJ Issue December 31, 2015

26 05 00 - BASIC ELECTRICAL MATERIALS AND METHODS 4 of 10

2.4 ELECTRICAL IDENTIFICATION

A. Identification Devices: A single type of identification product for each application category. Use colors prescribed by ANSI A13.1, NFPA 70, and these Specifications.

B. Colored Adhesive Marking Tape for Raceways, Wires, and Cables: Self-adhesive vinyl tape, not less than 1 inch wide by 3 mils thick.

C. Underground Warning Tape: Permanent, bright-colored, continuous-printed, vinyl tape with the following features:

1. Not less than 6 inches wide by 4 mils thick. 2. Compounded for permanent direct-burial service. 3. Embedded continuous metallic strip or core. 4. Printed legend that indicates type of underground line.

D. Tape Markers for Wire: Vinyl or vinyl-cloth, self-adhesive, wraparound type with preprinted numbers and letters.

E. Color-Coding Cable Ties: Type 6/6 nylon, self-locking type. Colors to suit coding scheme.

F. Engraved-Plastic Labels, Signs, and Instruction Plates: Engraving stock, melamine plastic laminate punched or drilled for mechanical fasteners 1/16-inch minimum thickness for signs up to 20 sq. in. and 1/8-inch minimum thickness for larger sizes. Engraved legend in black letters on white background.

G. Interior Warning and Caution Signs: Comply with 29 CFR, Chapter XVII, Part 1910.145. Preprinted, aluminum, baked-enamel-finish signs, punched or drilled for mechanical fasteners, with colors, legend, and size appropriate to the application.

H. Exterior Warning and Caution Signs: Comply with 29 CFR, Chapter XVII, Part 1910.145. Weather-resistant, nonfading, preprinted, cellulose-acetate butyrate signs with 0.0396-inch, galvanized-steel backing, with colors, legend, and size appropriate to the application. 1/4-inch grommets in corners for mounting.

I. Fasteners for Nameplates and Signs: Self-tapping, stainless-steel screws or No. 10/32 stainless-steel machine screws with nuts and flat and lock washers.

2.5 EQUIPMENT FOR UTILITY COMPANY'S ELECTRICITY METERING

A. Current-Transformer Cabinets: Comply with requirements of electrical power utility company.

B. Meter Sockets: Comply with requirements of electrical power utility company.

C. Modular Meter Centers: Factory-coordinated assembly of a main meter center circuit-breaker unit with wireways, tenant meter socket modules, and tenant branch circuit breakers arranged in adjacent vertical sections, complete with interconnecting buses.

1. Housing: NEMA 250, Type 1 enclosure. 2. Tenant Branch Circuit Breakers: Series combination rated to protect circuit breakers in

downstream panelboards that have 10,000-A interrupting capacity, minimum.

2.6 CONCRETE BASES

Page 102: PLUMBING, ELECTRICAL & FIRE PROTECTION COMPONENTS … · mechanical, electrical, plumbing and fire protection building system components in place during a seismic or high wind event

Permit Fairview Municipal Building 55 Anderson Ave. Fairview NJ Issue December 31, 2015

26 05 00 - BASIC ELECTRICAL MATERIALS AND METHODS 5 of 10

A. Concrete Forms and Reinforcement Materials:

B. Concrete: 3000-psi, 28-day compressive strength.

2.7 TOUCHUP PAINT

A. For Equipment: Equipment manufacturer's paint selected to match installed equipment finish.

B. Galvanized Surfaces: Zinc-rich paint recommended by item manufacturer.

PART 3 - EXECUTION

3.1 ELECTRICAL EQUIPMENT INSTALLATION

A. Headroom Maintenance: If mounting heights or other location criteria are not indicated, arrange and install components and equipment to provide the maximum possible headroom.

B. Materials and Components: Install level, plumb, and parallel and perpendicular to other building systems and components, unless otherwise indicated.

C. Equipment: Install to facilitate service, maintenance, and repair or replacement of components. Connect for ease of disconnecting, with minimum interference with other installations.

D. Right of Way: Give to raceways and piping systems installed at a required slope.

3.2 RACEWAY APPLICATION

A. Use the following raceways for outdoor installations:

1. Exposed: IMC. 2. Concealed: IMC. 3. Underground, Single Run: PVC. 4. Underground, Grouped: PVC. 5. Connection to Vibrating Equipment: LFMC. 6. Boxes and Enclosures: NEMA 250, Type 3R or Type 4.

B. Use the following raceways for indoor installations:

1. Exposed: EMT. 2. Concealed: EMT. 3. Connection to Vibrating Equipment: FMC; except in wet or damp locations, use LFMC. 4. Damp or Wet Locations: IMC. 5. Boxes and Enclosures: NEMA 250, Type 1, unless otherwise indicated.

3.3 RACEWAY AND CABLE INSTALLATION

A. Conceal raceways and cables, unless otherwise indicated, within finished walls, ceilings, and floors.

Page 103: PLUMBING, ELECTRICAL & FIRE PROTECTION COMPONENTS … · mechanical, electrical, plumbing and fire protection building system components in place during a seismic or high wind event

Permit Fairview Municipal Building 55 Anderson Ave. Fairview NJ Issue December 31, 2015

26 05 00 - BASIC ELECTRICAL MATERIALS AND METHODS 6 of 10

B. Install raceways and cables at least 6 inches away from parallel runs of flues and steam or hot-water pipes. Locate horizontal raceway runs above water and steam piping.

C. Use temporary raceway caps to prevent foreign matter from entering.

D. Make conduit bends and offsets so ID is not reduced. Keep legs of bends in the same plane and straight legs of offsets parallel, unless otherwise indicated.

E. Use raceway and cable fittings compatible with raceways and cables and suitable for use and location.

F. Install raceways embedded in slabs in middle third of slab thickness where practical, and leave at least 1-inch concrete cover.

1. Secure raceways to reinforcing rods to prevent sagging or shifting during concrete placement.

2. Space raceways laterally to prevent voids in concrete. 3. Install conduit larger than 1-inch trade size parallel to or at right angles to main

reinforcement. Where conduit is at right angles to reinforcement, place conduit close to slab support.

4. Transition from nonmetallic tubing to Schedule 80 nonmetallic conduit, rigid steel conduit, or IMC before rising above floor.

5. Make bends in exposed parallel or banked runs from same centerline to make bends parallel. Use factory elbows only where elbows can be installed parallel; otherwise, provide field bends for exposed parallel raceways.

G. Install pull wires in empty raceways. Use No. 14 AWG zinc-coated steel or monofilament plastic line with not less than 200-lb tensile strength. Leave at least 12 inches of slack at each end of the pull wire.

H. Install telephone and signal system raceways, 2-inch trade size and smaller, in maximum lengths of 150 feet and with a maximum of two 90-degree bends or equivalent. Separate lengths with pull or junction boxes where necessary to comply with these requirements, in addition to requirements above.

I. Connect motors and equipment subject to vibration, noise transmission, or movement with a maximum of 72-inch flexible conduit. Install LFMC in wet or damp locations. Install separate ground conductor across flexible connections.

J. Set floor boxes level and trim after installation to fit flush to finished floor surface.

3.4 WIRING METHODS FOR POWER, LIGHTING, AND CONTROL CIRCUITS

A. Feeders: Type THHN/THWN insulated conductors in raceway.

B. Underground Feeders and Branch Circuits: Type THWN or single-wire, Type UF insulated conductors in raceway.

C. Branch Circuits: Type THW or THHN/THWN insulated conductors in raceway where exposed. Metal-clad cable where concealed in ceilings and gypsum board partitions.

D. Remote-Control Signaling and Power-Limited Circuits: Type THHN/THWN insulated conductors in raceway for Classes 1, 2, and 3, unless otherwise indicated.

Page 104: PLUMBING, ELECTRICAL & FIRE PROTECTION COMPONENTS … · mechanical, electrical, plumbing and fire protection building system components in place during a seismic or high wind event

Permit Fairview Municipal Building 55 Anderson Ave. Fairview NJ Issue December 31, 2015

26 05 00 - BASIC ELECTRICAL MATERIALS AND METHODS 7 of 10

3.5 WIRING INSTALLATION

A. Install splices and taps that are compatible with conductor material and that possess equivalent or better mechanical strength and insulation ratings than unspliced conductors.

B. Install wiring at outlets with at least 12 inches of slack conductor at each outlet.

C. Connect outlet and component connections to wiring systems and to ground. Tighten electrical connectors and terminals, according to manufacturer's published torque-tightening values. If manufacturer's torque values are not indicated, use those specified in UL 486A.

3.6 ELECTRICAL SUPPORTING DEVICE APPLICATION

A. Damp Locations and Outdoors: Hot-dip galvanized materials or nonmetallic, U-channel system components.

B. Dry Locations: Steel materials.

C. Support Clamps for PVC Raceways: Click-type clamp system.

D. Selection of Supports: Comply with manufacturer's written instructions.

E. Strength of Supports: Adequate to carry present and future loads, times a safety factor of at least four; minimum of 200-lb design load.

3.7 SUPPORT INSTALLATION

A. Install support devices to securely and permanently fasten and support electrical components.

B. Install individual and multiple raceway hangers and riser clamps to support raceways. Provide U-bolts, clamps, attachments, and other hardware necessary for hanger assemblies and for securing hanger rods and conduits.

C. Support parallel runs of horizontal raceways together on trapeze- or bracket-type hangers.

D. Size supports for multiple raceway installations so capacity can be increased by a 25 percent minimum in the future.

E. Support individual horizontal raceways with separate, malleable-iron pipe hangers or clamps.

F. Install 1/4-inch diameter or larger threaded steel hanger rods, unless otherwise indicated.

G. Spring-steel fasteners specifically designed for supporting single conduits or tubing may be used instead of malleable-iron hangers for 1-1/2-inch and smaller raceways serving lighting and receptacle branch circuits above suspended ceilings and for fastening raceways to slotted channel and angle supports.

H. Arrange supports in vertical runs so the weight of raceways and enclosed conductors is carried entirely by raceway supports, with no weight load on raceway terminals.

I. Simultaneously install vertical conductor supports with conductors.

Page 105: PLUMBING, ELECTRICAL & FIRE PROTECTION COMPONENTS … · mechanical, electrical, plumbing and fire protection building system components in place during a seismic or high wind event

Permit Fairview Municipal Building 55 Anderson Ave. Fairview NJ Issue December 31, 2015

26 05 00 - BASIC ELECTRICAL MATERIALS AND METHODS 8 of 10

J. Separately support cast boxes that are threaded to raceways and used for fixture support. Support sheet-metal boxes directly from the building structure or by bar hangers. If bar hangers are used, attach bar to raceways on opposite sides of the box and support the raceway with an approved fastener not more than 24 inches from the box.

K. Install metal channel racks for mounting cabinets, panelboards, disconnect switches, control enclosures, pull and junction boxes, transformers, and other devices unless components are mounted directly to structural elements of adequate strength.

L. Install sleeves for cable and raceway penetrations of concrete slabs and walls unless core-drilled holes are used. Install sleeves for cable and raceway penetrations of masonry and fire-rated gypsum walls and of all other fire-rated floor and wall assemblies. Install sleeves during erection of concrete and masonry walls.

M. Securely fasten electrical items and their supports to the building structure, unless otherwise indicated. Perform fastening according to the following unless other fastening methods are indicated:

1. Wood: Fasten with wood screws or screw-type nails. 2. Masonry: Toggle bolts on hollow masonry units and expansion bolts on solid masonry units. 3. New Concrete: Concrete inserts with machine screws and bolts. 4. Existing Concrete: Expansion bolts. 5. Instead of expansion bolts, threaded studs driven by a powder charge and provided with

lock washers may be used in existing concrete. 6. Steel: Welded threaded studs or spring-tension clamps on steel.

a. Field Welding: Comply with AWS D1.1.

7. Welding to steel structure may be used only for threaded studs, not for conduits, pipe straps, or other items.

8. Light Steel: Sheet-metal screws. 9. Fasteners: Select so the load applied to each fastener does not exceed 25 percent of its

proof-test load.

3.8 IDENTIFICATION MATERIALS AND DEVICES

A. Install at locations for most convenient viewing without interference with operation and maintenance of equipment.

B. Coordinate names, abbreviations, colors, and other designations used for electrical identification with corresponding designations indicated in the Contract Documents or required by codes and standards. Use consistent designations throughout Project.

C. Self-Adhesive Identification Products: Clean surfaces before applying.

D. Tag and label circuits designated to be extended in the future. Identify source and circuit numbers in each cabinet, pull and junction box, and outlet box. Color-coding may be used for voltage and phase identification.

E. Install continuous underground plastic markers during trench backfilling, for exterior underground power, control, signal, and communication lines located directly above power and communication lines. Locate 6 to 8 inches below finished grade. If width of multiple lines installed in a common trench or concrete envelope does not exceed 16 inches, overall, use a single line marker.

Page 106: PLUMBING, ELECTRICAL & FIRE PROTECTION COMPONENTS … · mechanical, electrical, plumbing and fire protection building system components in place during a seismic or high wind event

Permit Fairview Municipal Building 55 Anderson Ave. Fairview NJ Issue December 31, 2015

26 05 00 - BASIC ELECTRICAL MATERIALS AND METHODS 9 of 10

F. Color-code 208/120-V system secondary service, feeder, and branch-circuit conductors throughout the secondary electrical system as follows:

1. Phase A: Black. 2. Phase B: Red. 3. Phase C: Blue.

G. Color-code 480/277-V system secondary service, feeder, and branch-circuit conductors throughout the secondary electrical system as follows:

1. Phase A: Brown. 2. Phase B: Orange. 3. Phase C: Yellow.

H. Install warning, caution, and instruction signs where required to comply with 29 CFR, Chapter XVII, Part 1910.145, and where needed to ensure safe operation and maintenance of electrical systems and of items to which they connect. Install engraved plastic-laminated instruction signs with approved legend where instructions are needed for system or equipment operation. Install metal-backed butyrate signs for outdoor items.

I. Install engraved-laminated emergency-operating signs with white letters on red background with minimum 3/8-inch high lettering for emergency instructions on power transfer, load shedding, and other emergency operations.

3.9 UTILITY COMPANY ELECTRICITY-METERING EQUIPMENT

A. Install equipment according to utility company's written requirements. Provide grounding and empty conduits as required by utility company.

3.10 FIRESTOPPING

A. Apply firestopping to cable and raceway penetrations of fire-rated floor and wall assemblies to achieve fire-resistance rating of the assembly. Firestopping materials and installation requirements.

3.11 CONCRETE BASES

A. Construct concrete bases shall be provided for all floor mounted electrical equipment, sized not less than 4 inches larger, in both directions, than supported unit. Follow supported equipment manufacturer's anchorage recommendations and setting templates for anchor-bolt and tie locations, unless otherwise indicated. Use 3000-psi, 28-day compressive-strength concrete and reinforcement.

3.12 CUTTING AND PATCHING

A. Cut, channel, chase, and drill floors, walls, partitions, ceilings, and other surfaces required to permit electrical installations. Perform cutting by skilled mechanics of trades involved.

B. Repair and refinish disturbed finish materials and other surfaces to match adjacent undisturbed surfaces. Install new fireproofing where existing firestopping has been disturbed. Repair and refinish materials and other surfaces by skilled mechanics of trades involved.

Page 107: PLUMBING, ELECTRICAL & FIRE PROTECTION COMPONENTS … · mechanical, electrical, plumbing and fire protection building system components in place during a seismic or high wind event

Permit Fairview Municipal Building 55 Anderson Ave. Fairview NJ Issue December 31, 2015

26 05 00 - BASIC ELECTRICAL MATERIALS AND METHODS 10 of 10

3.13 FIELD QUALITY CONTROL

A. Inspect installed components for damage and faulty work, including the following:

1. Raceways. 2. Building wire and connectors. 3. Supporting devices for electrical components. 4. Electrical identification. 5. Electricity-metering components. 6. Concrete bases. 7. Electrical demolition. 8. Cutting and patching for electrical construction. 9. Touchup painting.

3.14 REFINISHING AND TOUCHUP PAINTING

A. Refinish and touch up paint.

1. Clean damaged and disturbed areas and apply primer, intermediate, and finish coats to suit the degree of damage at each location.

2. Follow paint manufacturer's written instructions for surface preparation and for timing and application of successive coats.

3. Repair damage to galvanized finishes with zinc-rich paint recommended by manufacturer. 4. Repair damage to PVC or paint finishes with matching touchup coating recommended by

manufacturer.

3.15 CLEANING AND PROTECTION

A. On completion of installation, including outlets, fittings, and devices, inspect exposed finish. Remove burrs, dirt, paint spots, and construction debris.

B. Protect equipment and installations and maintain conditions to ensure that coatings, finishes, and cabinets are without damage or deterioration at time of Substantial Completion.

END OF SECTION 26 05 00