53
Department of Civil and Structural Engineering Plastic Design of Portal frame to Eurocode 3 Supporting Notes University of Sheffield

Plastic Design of Portal frame to Eurocode 3 · PDF filePlastic Design of Portal frame to Eurocode 3. Supporting Notes. ... EC3 requires that the second order effects are explicitly

Embed Size (px)

Citation preview

Page 1: Plastic Design of Portal frame to Eurocode 3 · PDF filePlastic Design of Portal frame to Eurocode 3. Supporting Notes. ... EC3 requires that the second order effects are explicitly

Department of Civil and

Structural Engineering

Plastic Design of Portal

frame to Eurocode 3 Supporting Notes

University of

Sheffield

Page 2: Plastic Design of Portal frame to Eurocode 3 · PDF filePlastic Design of Portal frame to Eurocode 3. Supporting Notes. ... EC3 requires that the second order effects are explicitly

2

CONTENTS

CONTENTS ............................................................................................................................... 2

List of Figures ............................................................................................................................ 5

1 Introduction ........................................................................................................................ 1

1.1 Outline of Portal Frames ............................................................................................ 1

1.2 Pitched Roof characteristics and parts ....................................................................... 2

2 Plastic analysis of portal frames ......................................................................................... 3

2.1 Plastic Design of Portal Frames ................................................................................. 3

2.2 Elastic vs. plastic analysis .......................................................................................... 3

3 Differnces Between EC3 and BS5950 ............................................................................... 4

3.1 Load Combinations .................................................................................................... 4

3.2 Consideration of second-order effects, ....................................................................... 4

3.3 Base fixity .................................................................................................................. 4

3.4 Separate checks for cross-section and buckling, ........................................................ 4

4 Worked example ................................................................................................................ 5

5 Material .............................................................................................................................. 7

5.1 Scopes ......................................................................................................................... 7

5.2 Design values of material coefficient ......................................................................... 8

6 Ultimate Limit State ........................................................................................................... 8

6.1 Outline ........................................................................................................................ 8

6.2 Design main concept .................................................................................................. 8

6.3 Partial Safety factors .................................................................................................. 9

6.3.1 Partial Safety factor of resistance ........................................................................... 9

6.3.2 Partial Safety factor for loads ................................................................................. 9

6.4 Load combination ..................................................................................................... 10

7 Ultimate limit state Analysis (First Order Vs Second Order) .......................................... 11

7.1 P.Ξ΄ effects ................................................................................................................. 11

7.2 P. Ξ” effects ............................................................................................................... 12

7.3 How EC3 account for Second Order effects ............................................................ 13

7.3.1 Checking if second order affects significance ...................................................... 13

7.3.2 Determination of Ξ±cr ............................................................................................. 13

7.3.3 Accounting second order effects .......................................................................... 16

Page 3: Plastic Design of Portal frame to Eurocode 3 · PDF filePlastic Design of Portal frame to Eurocode 3. Supporting Notes. ... EC3 requires that the second order effects are explicitly

3

8 Serviceability limit state ................................................................................................... 18

8.1 Outlines .................................................................................................................... 18

8.2 Load Combinations .................................................................................................. 18

8.3 Deflections limiting values: ..................................................................................... 18

8.4 Procedures ................................................................................................................ 19

9 Frame Imperfections ........................................................................................................ 20

10 Connection of members ................................................................................................... 22

10.1 Eaves and apex connections ..................................................................................... 22

10.2 Lateral restraint to portal frames .............................................................................. 23

10.3 Bracing to compression flanges of rafters ................................................................ 23

10.4 Purlins ....................................................................................................................... 24

10.5 Column base ............................................................................................................. 24

11 Bracing ............................................................................................................................. 25

11.1 Overall column bracing ............................................................................................ 25

11.1.1 Portal bracing ................................................................................................... 25

11.2 Bracing to inner flanges ........................................................................................... 26

11.3 Bracing at the plastic hinge ...................................................................................... 27

12 Cross section resistance .................................................................................................... 28

12.1 The classification of cross-section ........................................................................... 28

12.2 Bending moment ...................................................................................................... 29

12.3 Shear ......................................................................................................................... 29

12.3.1 For low shear (see EN 1993-1-1 Section 6.2.8), .............................................. 30

12.3.2 For high shear ................................................................................................... 30

12.4 Axial force ................................................................................................................ 30

12.4.1 For low axial force ........................................................................................... 30

12.4.2 For high axial force .......................................................................................... 31

13 Stability checks, ............................................................................................................... 31

13.1 Restraint of plastic hinge .......................................................................................... 31

13.2 Rafter Stability ......................................................................................................... 32

13.3 Stability of haunch ................................................................................................... 33

13.4 Stability of the column ............................................................................................. 34

14 Fire Boundary Condition .................................................................................................. 35

14.1 Outline ...................................................................................................................... 35

Page 4: Plastic Design of Portal frame to Eurocode 3 · PDF filePlastic Design of Portal frame to Eurocode 3. Supporting Notes. ... EC3 requires that the second order effects are explicitly

4

14.2 Building Regulation requirements in UK................................................................. 35

14.3 Alternative approaches to boundary fire .................................................................. 35

14.4 Effects of fire on Portal frames ................................................................................ 36

14.5 Mathematical Model ................................................................................................ 37

15 Appendix .......................................................................................................................... 39

16 Reference .......................................................................................................................... 47

Page 5: Plastic Design of Portal frame to Eurocode 3 · PDF filePlastic Design of Portal frame to Eurocode 3. Supporting Notes. ... EC3 requires that the second order effects are explicitly

5

LIST OF FIGURES

1 multiple span frames

2 Single-span symmetrical portal frame (Malik SN051a-EN-EU)

3 Side Cladding (Malik SN051a-EN-EU)

4- P.Ξ΄ effects

5- Magnification of sway displacements

6- Snap-through failure

7- Parameters required

8- Examples of Category A

9- Definition of horizontal displacements

10- Frame imperfections as column slopes

11- Force equivalent to frame imperfections

12- Apex and Eaves Connections

13- Stabilising of the column

14- Braces to rafter bottom flange

15- Braced portals

16- Effects of purlin flexibility on bracing

17- Bracing to inner flanges

18- Typical stiff torsional restraint

19- Bracing at plastic hinge

20- Bending moment diagram for uniform temperature rise

21- Probable positions of fire hinges in portal frame

22- Rafter collapse to eaves level

23- Moment Ratios

24- Dimensions defining taper factor

25- Value of Bt

26 Forces and moments acting on the column and rafters

Page 6: Plastic Design of Portal frame to Eurocode 3 · PDF filePlastic Design of Portal frame to Eurocode 3. Supporting Notes. ... EC3 requires that the second order effects are explicitly

1

1 INTRODUCTION

1.1 Outline of Portal Frames

Portal frame construction is a method of building and designing simple structures, primarily

using steel. The connections between the columns and the rafters are designed to be moment-

resistant, i.e. they can carry bending forces. Because of these very strong and rigid joints

some of the bending moment in the rafters is transferred to the columns. This means that the

size of the rafters can be reduced or the span can be increased for the same size rafters. This

makes portal frames a very efficient construction technique especially in steel being able to

make use of plastic methods. Portal frames construction is popular due to the following

reasons;

1) It provides large clear floor areas offering maximization of the site for

example in; retail stores, distribution warehouse, manufacturing

facilities, and leisure centers.

2) They are capable of being extended in the future if this is accounted

within design.

3) Multiple bays are possible where internal column can be eliminated

where required by using valley beam as shown if figure .1.

Figure 1 multiple span frames

Portal frames can be clad with all sorts of material but the most popular solution, for reasons

of economy and speed, is some form of lightweight insulated metal cladding with cavity

masonry work to the bottom 2m of the wall to provide security and impact resistance (Morris,

1981). The lightweight cladding would be carried on sheeting rails spanning between the

columns of the portal frames.

Page 7: Plastic Design of Portal frame to Eurocode 3 · PDF filePlastic Design of Portal frame to Eurocode 3. Supporting Notes. ... EC3 requires that the second order effects are explicitly

2

1.2 Pitched Roof characteristics and parts

Figure 2 Single-span symmetrical portal frame (Malik SN051a-EN-EU)

A single-span pitched roof portal frame (figure2) will typically have (Malik SN051a-EN-EU):

1) Span between 15 meters to 50 meters.

2) Eaves 5 meters to 10 meters.

3) A roof pitched between 5 degrees and 10 degrees. (6 degrees is commonly

adopted).

4) A frame spacing between 5 meters and 8 meters (the greater the spacing being

associated with the longer span portal frames).

5) Haunches in the rafters at the eaves and apex used to reduce the depth of the rafter

and achieve efficient moment connection at these points.

6) The portal frame supports side cladding by means of cold formed purlins and

sheeting.

Figure 3 Side Cladding (Malik SN051a-EN-EU)

Most of these characteristics are prescribed by the economics of portal frames relative to other

forms of constructions.

Page 8: Plastic Design of Portal frame to Eurocode 3 · PDF filePlastic Design of Portal frame to Eurocode 3. Supporting Notes. ... EC3 requires that the second order effects are explicitly

3

2 PLASTIC ANALYSIS OF PORTAL FRAMES

2.1 Plastic Design of Portal Frames

Plastic theory has been used in the UK for the basis of the design of low-rise frames,

particularly portal frames, since its use was first allowed in BS449 in 1948. In many

countries the use of plastic theory is permitted by their own national codes. But plastic

methods of analysis are mainly used to allow engineers to more easily do the analysis

and more economical design portal frames than typical elastic methods. The concept

of plastic analysis method is to calculate the loads that can be applied to cause the

frame to fail as a failure mechanism occur e.g. enough plastic hinges occur (Morris,

1981).

2.2 Elastic vs. plastic analysis

The methods of analysis fall into either elastic analysis or plastic analysis. Elastic

analysis often produces less economical structures because it does not allow large-

scale plastic redistribution of bending moments, although these will occur in an

adequately braced structure and will enable the structure to carry higher loads than

calculated by elastic analysis. Generally, plastic analysis results in more economical

structures because plastic redistribution allows slightly smaller members to carry the

same loads. On the other hand in some cases elastic analysis can be more economical

as plastic analysis depends on bracing system, because plastic redistribution imposes

extra requirements on bracing of members. The overall economy of the frame might

therefore depend on the ease with which the frame can be braced.

Page 9: Plastic Design of Portal frame to Eurocode 3 · PDF filePlastic Design of Portal frame to Eurocode 3. Supporting Notes. ... EC3 requires that the second order effects are explicitly

4

3 DIFFERNCES BETWEEN EC3 AND BS5950

There are a number of differences between EC3 and previous UK practice, which need to be

clearly understood by the designers that used to BS5950 but intend to use EC3. The main

differences affecting the portal frame designing noted below (King, Technical Report P164).

3.1 Load Combinations

BS5950 uses one set of load factors for a combination of (dead + live) loads, but a

lower load factor for (dead + live + wind) loads. In principal, EC3 requires that all

variable actions (live loads, wind loads, ect.) are considered in the same load

combination, but includes a reduction factor on all variable actions, except the most

unfavorable.

3.2 Consideration of second-order effects,

EC3 requires that the second order effects are explicitly considered in analysis, either

by second-order analysis or by modifications to classic first-order analysis. For single-

storey portal frame design, the sway check method in BS 5950 uses deflection checks

to assess the stiffness. If the stiffness is too low, it has to be increased. If the stiffness

is above a certain value, second order can be ignored.

3.3 Base fixity

It is common practice in the UK to assume that column bases are truly pinned for

ultimate limit state bending moment diagrams, where they are actually nominally

connected. EC3 requires consideration of the actual flexibility. In the case of

nominally pinned bases, the assumption of a truly pinned base is conservative, so it is

acceptable. However, for fixed bases the actual flexibility must be considered.

3.4 Separate checks for cross-section and buckling,

EC3 has entirely separate checks for the cross-section resistance and buckling

resistance. This is unfamiliar, but very helpful for checking elements of varying

sections along the fram

Page 10: Plastic Design of Portal frame to Eurocode 3 · PDF filePlastic Design of Portal frame to Eurocode 3. Supporting Notes. ... EC3 requires that the second order effects are explicitly

5

4 WORKED EXAMPLE

The worked example is aimed to provide guidance on method of designing a portal frame to

Eurocode for maximum vertical load combination; which is been used due to the fact that

most portal frame design is governed by gravity (dead + snow) loading. The required

designing steps where identified from (EN2005-1-1) and the following procedure where

developed for the worked example (see Appendix A for the flow chart);

(1) Define frame geometry.

(2) Calculate the Loading on the portal frame accurately based on the initial sizing of the

sections as follow (Gravity Load);

Snow loading.

Gravity loading.

(3) Choose a trial sections and a trial haunch length by selecting universal beam section that

have plastic modules as given by Weller’s charts (The institutionof Structural Engineers,

TP/08/43 EC3/08/16). The haunch length should be chosen to optimize the overall portal

structure. A length of L/10 from the column face is a reasonable initial choice, but the

proportions of the haunch generally depend of the characteristics of each individual

building. A haunch length of L/10 will normally place the first hinge in the top of the

column.

(4) Calculate frame imperfection equivalent forces, referring to section 5.3.2 of EN1993-1-

1:2005.

(5) Perform plastic analysis of the frame, assuming no reduction in plastic moment of

resistance from coexistent axial and shear force. This approach may need modifying,

where axial load are high.

(6) Determine sensitivity of portal frame to sway, by calculating Ξ±cr, s, EST.

Page 11: Plastic Design of Portal frame to Eurocode 3 · PDF filePlastic Design of Portal frame to Eurocode 3. Supporting Notes. ... EC3 requires that the second order effects are explicitly

6

(7) Determine sensitivity of portal frame to snap-through rafter buckling, by calculating

Ξ±cr,s,est.

(8) Determine Ξ±cr,est = min (Ξ±cr,s,est , Ξ±cr,s,est).

(9) If Ξ±cr,est < 15 the member design forces is calculated due to second order effects; this is

done by using amplified partial load factors method (section 5.3.2 of EN1993-1-1:2005).

(10) For the column check the following:

(A) The classification is Class 1 or Class 2.

(B) The cross-section resistance is adequate, and checks if axial and shear force has

effect on plastic resistance of section (section 5.5.2 of EN1993-1-1:2005).

(C) The resistance of the member to minor axis buckling between lateral restraints

is adequate; this might be between plastic hinge and lateral restraint or between

two lateral restraints. To prevent this spacing is limited below Lm (section

BB.3.1.1of EN1993-1-1:2005).

(D) The resistance of member to minor axis buckling between torsional restraints is

adequate, it checked for by same criteria as lateral restraint where maximum

spacing between torsional restraint are limited to ( Lk , Ls ,Ls ) (section

BB.3.2.2of EN1993-1-1:2005).

(11) For the rafter check that,

(A) The classification is Class 1 and Class 2 as step 7A.

(B) The cross-section resistance is adequate, as a step 7B

(C) The resistance of the member to minor axis buckling between lateral restraints is

adequate as step 7C.

(D) The resistance of the member to minor axis buckling between torsional restraints

is adequate as step 7D.

Page 12: Plastic Design of Portal frame to Eurocode 3 · PDF filePlastic Design of Portal frame to Eurocode 3. Supporting Notes. ... EC3 requires that the second order effects are explicitly

7

(12) For the Haunches check that:

(A) T he classification is Class 1 and Class 2 as step 7A.

(B) The cross-sectional resistance is adequate, as step 7B above, but checking at

several cross-sections within the length of the haunch (ends, quarter, and mid-

span and three quarter points).

(C) The resistance of the member to minor axis buckling between lateral restraints is

adequate as step 7C.

5 MATERIAL

5.1 Scopes

EC3 covers design in steel to BSEN 10025 (grades Fe430 Fe510 only). For members, the

hunches, the end plates, the base-plated and any stiffeners an S275 steel to EN10025 with

yield 275N/mm2 and ultimate strength of 430N/mm2 is adopted

Table 1-Nominal values of yield Strength and ultimate tensile Strength (Baddoo, 1993 )

Page 13: Plastic Design of Portal frame to Eurocode 3 · PDF filePlastic Design of Portal frame to Eurocode 3. Supporting Notes. ... EC3 requires that the second order effects are explicitly

8

5.2 Design values of material coefficient (BS EN 1993-1-1:2005)

Modulus of elasticity (E) = 210 000 N/mm2.

Shear modulus (G) = E/2(1+v) = 81 000N/mm2.

Poisson’s ratio (v) = 0.3.

Coefficient of linear thermal expansion (Ξ±) = 12 x10-6 per Co.

Density (ρ) = 7 850 kg/m3.

6 ULTIMATE LIMIT STATE

6.1 Outline

According to EC3 all actions that could occur at the same time are considered together, so

frame imperfection equivalent forces (which are discussed in section 9) as well as wind loads

should be considered as additives to permanent actions and other imposed loads with an

appropriate combination factor applied to them. Although several combinations exist, only the

least favourable combination of loads should be considered. Most general example is wind

load can act on both sides of portal frame but only combination need to be considered is the

least favourable direction with respect to each load combination.

6.2 Design main concept

A structure must have adequate resistance to internal forces and bending moments, known as

structural resistance. In addition it must exist in a state of static equilibrium under the action

of the applied loads, i.e. it must have adequate resistance to overturning, uplift ECT. Due to

fact that static equilibrium is rarely critical for portal framed buildings, so not considered in

details. The following are cases where static equilibrium might be critical:

1. In high wind speed areas.

2. In high but narrow buildings, result in overturning.

3. Where there is large opening allowing generation of high positive wind pressure inside

the building at the same time as high suction over the roof.

Page 14: Plastic Design of Portal frame to Eurocode 3 · PDF filePlastic Design of Portal frame to Eurocode 3. Supporting Notes. ... EC3 requires that the second order effects are explicitly

9

6.3 Partial Safety factors

EC3 uses partial safety factor format for checking ULS, in which the partial safety factors

obtain a considerable safety margin against uncertainties of load on structure and resistance of

the material. So that it reduces the resistance of the material and increase the applied load on

the structure.

οΏ½π‘π‘β„Žπ‘Žπ‘Žπ‘Žπ‘Žπ‘Žπ‘Žπ‘π‘π‘Žπ‘Žπ‘Žπ‘Žπ‘Žπ‘Žπ‘Žπ‘Žπ‘Žπ‘Žπ‘Žπ‘Žπ‘Žπ‘Žπ‘π‘ π‘Žπ‘Žπ‘Žπ‘Žπ‘Žπ‘Žπ‘Žπ‘Žπ‘Žπ‘Žπ‘Žπ‘Žπ‘Žπ‘Žπ‘Ÿπ‘Ÿπ‘π‘π‘Žπ‘Ž

𝛾𝛾𝑀𝑀� > π‘Žπ‘Žπ‘’π‘’π‘’π‘’π‘Žπ‘Žπ‘π‘π‘Žπ‘Ž π‘œπ‘œπ‘’π‘’ βˆ‘(π‘π‘β„Žπ‘Žπ‘Žπ‘Žπ‘Žπ‘Žπ‘Žπ‘π‘π‘Žπ‘Žπ‘Žπ‘Žπ‘Žπ‘Žπ‘Žπ‘Žπ‘Žπ‘Žπ‘Žπ‘Žπ‘Žπ‘Žπ‘π‘ π‘Žπ‘Žπ‘π‘π‘Žπ‘Žπ‘Žπ‘Žπ‘œπ‘œπ‘Ÿπ‘Ÿ) Γ— 𝛾𝛾𝐹𝐹

6.3.1 Partial Safety factor of resistance

π›Ύπ›Ύπ‘€π‘€π‘œπ‘œ 1.1 For the resistance of the cross-section

𝛾𝛾𝑀𝑀1 1.1 For the resistance buckling of the member

𝛾𝛾𝑀𝑀𝑐𝑐 1.25 For the resistance of the net sections

𝛾𝛾𝑀𝑀𝑀𝑀 1.25 For the resistance of the bolts

𝛾𝛾𝑀𝑀𝑀𝑀 1.25 For the resistance of welds

Table 2- Partial Safety Factors of Steel Resistance (BS EN 1993-1-1:2005)

6.3.2 Partial Safety factor for loads

Partial factors for actions are either

β€’ Permanent action dead load 𝛾𝛾𝐺𝐺

β€’ Variable action live load 𝛾𝛾𝑄𝑄

Those will have different values depending on wither the action is favourable or

unfavourable for the structure stability.

Table 3-Partial safety factors for actions in building structure (Baddoo, 1993 )

Page 15: Plastic Design of Portal frame to Eurocode 3 · PDF filePlastic Design of Portal frame to Eurocode 3. Supporting Notes. ... EC3 requires that the second order effects are explicitly

10

6.4 Load combination

EC3 normally consider all possible coincident actions but with the less unfavourable variable

action reduced by combination reduction factor (ψ). The β€œcombination factor” reduces the

intensity of loading, when several variable loads are considered to be acting together. There is

only low probability of all variable action occurring at full intensity at the same time, so the

combination factor is used.

All ULS load combinations must include the effect if any of imperfection forces (horizontal

forces) from any direction particularly in frame analysis. The Single expression for ULS load

combination is as follow (Baddoo, 1993 )

Note that there are different ψ factors for different types of variable actions. The table below

from EN1990:2002 shows different factors.

Table 4- Recommended Values of ψ for buildings (Baddoo, 1993 )

Characteristic value of the permanent action (πΊπΊπ‘˜π‘˜ 𝑗𝑗 ) X 𝛾𝛾𝐺𝐺

+ Full characteristic value of the most unfavorable variable action (π‘„π‘„π‘˜π‘˜ 1) X 𝛾𝛾𝑄𝑄 1

+ Reduced values of all other unfavorable variable action (π‘„π‘„π‘˜π‘˜ ,π‘Žπ‘Ž Γ— ψ0,π‘Žπ‘Ž) X 𝛾𝛾𝑄𝑄,π‘Žπ‘Ž

Page 16: Plastic Design of Portal frame to Eurocode 3 · PDF filePlastic Design of Portal frame to Eurocode 3. Supporting Notes. ... EC3 requires that the second order effects are explicitly

11

7 ULTIMATE LIMIT STATE ANALYSIS (FIRST ORDER VS SECOND ORDER)

Normally first-order analysis is acceptable unless when the frame or frame member is

exceedingly slender. The limitations are given below; where structures exceed these

limitations second order analysis must be used.

7.1 P.Ξ΄ effects

P.Ξ΄ effects are the effects on member behaviour due to displacements at right-angles to the

axial force in the member. These displacements may be enforced (by external load or

moments), most notably in the case of axial loading along a member with initial bow, or

maybe the result of the natural tendency to buckle under pure axial load. The displacements

are the sum if the initial deformation of the member and deflection due loading. The result of

such deflections is to reduce the effective stiffness when axial load is compressive, due to

increased bending moment see below figure 4. Conversely, when axial load is tensile, it

increases the effective stiffness, though the effect will generally be minimal in common single

storey portal frames.

Figure 4- P.Ξ΄ effects (King, Technical Report P164)

Page 17: Plastic Design of Portal frame to Eurocode 3 · PDF filePlastic Design of Portal frame to Eurocode 3. Supporting Notes. ... EC3 requires that the second order effects are explicitly

12

7.2 P. Ξ” effects

P. Ξ” effects are the effects on overall frame behaviour due to the displacement at right-angles

to the applied forces, directly due to those same forces. The displacements are the sum of the

initial deformation of the frame and deflection due loading. For pitched roof portals, the prime

example is the effect of gravity loads on sway deflections. The effect is to magnify the sway

deflection due to overall inclination of the column which produces a reduction in effective

stiffness, see the figure 5,

Figure 5- Magnification of sway displacements (King, Technical Report P164)

Another possible mode of failure which is sensitive to P. Ξ” effects is β€œarching failure” or

β€œsnap-through” of pair of rafters (see fig below). This has to be checked because it is possible

to design portals of 3 spans or more with stiff outer bays that provide horizontal support to the

rafters of the inner spans. Then the rafters of the inner spans can act as arches with the

horizontal reaction provided by the outer bays. Where this arching action works, the rafters

will support more vertical load than if they were acting only as beams. This check is used to

ensure that the rafters are not so flexible that they Β΄snap throughΒ΄.

Figure 6- Snap-through failure (King, Technical Report P147)

Page 18: Plastic Design of Portal frame to Eurocode 3 · PDF filePlastic Design of Portal frame to Eurocode 3. Supporting Notes. ... EC3 requires that the second order effects are explicitly

13

7.3 How EC3 account for Second Order effects

7.3.1 Checking if second order affects significance

First order analysis may be used for the structure where the increase of the relevant internal

forces or moments or any other change of structural behaviour caused by deformations can be

neglected. This condition may be assumed to be fulfilled, if the following criterion is satisfied

(BS EN 1993-1-1:2005):

β€’ Ξ±cr β‰₯ 10 for elastic analysis

β€’ Ξ±cr β‰₯ 15for plastic analysis

- Where:

Ξ±cr Is the factor by which the design loading would have to be increased to

cause elastic instability in a global mode.

7.3.2 Determination of Ξ±cr

For frames with pitched rafters,

Ξ±cr,est= min (Ξ±cr,r,est , Ξ±cr,s,est)

- Where

Ξ±cr,s,est is the estimate of Ξ±cr for sway buckling mode (see Section 3.3.1)

Ξ±cr,r,est is the estimate of Ξ±cr for rafter snap-through buckling mode

(see Section 3.3.2)

Page 19: Plastic Design of Portal frame to Eurocode 3 · PDF filePlastic Design of Portal frame to Eurocode 3. Supporting Notes. ... EC3 requires that the second order effects are explicitly

14

7.3.2.1 Sway buckling load factor (Oppe, SN033a-EN-EU)

The parameters required to calculate Ξ±cr,s,est, for portal frames are shown in Figure 7 . As

can be seen, Ξ΄HEF is the lateral deflection at the top of each column when subjected to an

arbitrary lateral load HEHF. (The magnitude of the total lateral load is arbitrary, as it is simply

used to calculate the sway stiffness HEHF/Ξ΄EHF.) The horizontal load applied at the top of each

column should be proportional to the vertical reaction. Thus, for an individual column:

𝐻𝐻𝐸𝐸𝐻𝐻𝐹𝐹 ,π‘Žπ‘Ž

π‘‰π‘‰π‘ˆπ‘ˆπ‘ˆπ‘ˆπ‘ˆπ‘ˆ ,π‘Žπ‘Ž=π»π»πΈπΈπ»π»πΉπΉπ‘‰π‘‰π‘ˆπ‘ˆπ‘ˆπ‘ˆπ‘ˆπ‘ˆ

- Where

HEHF is the sum of all the equivalent horizontal forces at column tops

(see figure 7)

VULS is the sum of all factored vertical reactions at ULS calculated from

first-order plastic analysis

HEHFi is equivalent horizontal force at top of column i (there are two

columns in a single-span portal, three in a two-span portal, etc.)

VULS,i is factored vertical reaction at ULS at column i, calculated from first-

order plastic analysis

Figure 7- Parameters required to estimate alpha critical

for sway mode failure (J.B.P.Lim, November 2005)

Page 20: Plastic Design of Portal frame to Eurocode 3 · PDF filePlastic Design of Portal frame to Eurocode 3. Supporting Notes. ... EC3 requires that the second order effects are explicitly

15

An estimate of Ξ±cr can then be obtained from

Ξ±cr,s,est = 0.8 οΏ½1 βˆ’ �𝑁𝑁𝑅𝑅 ,π‘ˆπ‘ˆπ‘ˆπ‘ˆπ‘ˆπ‘ˆπ‘π‘π‘…π‘… ,π‘π‘π‘Žπ‘Ž

οΏ½π‘šπ‘šπ‘Žπ‘Žπ‘šπ‘šοΏ½ οΏ½οΏ½ β„Žπ‘Žπ‘Žπ‘‰π‘‰π‘ˆπ‘ˆπ‘ˆπ‘ˆπ‘ˆπ‘ˆ ,π‘Žπ‘Ž

οΏ½ �𝐻𝐻𝐸𝐸𝐻𝐻𝐹𝐹 ,π‘Žπ‘Žπ›Ώπ›ΏπΈπΈπ»π»πΉπΉ ,π‘Žπ‘Ž

οΏ½π‘šπ‘šπ‘Žπ‘Žπ‘Ÿπ‘ŸοΏ½

Where:

�𝑁𝑁𝑅𝑅 ,π‘ˆπ‘ˆπ‘ˆπ‘ˆπ‘ˆπ‘ˆπ‘π‘π‘…π‘… ,π‘π‘π‘Žπ‘Ž

οΏ½π‘šπ‘šπ‘Žπ‘Žπ‘šπ‘š Is the maximum ratio in any rafter.

𝑁𝑁𝑅𝑅,π‘ˆπ‘ˆπ‘ˆπ‘ˆπ‘ˆπ‘ˆ Is the axial force in rafter (see figure 7 (b)).

𝑁𝑁𝑅𝑅,π‘π‘π‘Žπ‘Ž = πœ‹πœ‹2 𝐸𝐸 πΌπΌπ‘Žπ‘Žπ‘ˆπ‘ˆ2 Is the Euler load of the rafter on full span (assumed pinned)

Ir Is the in-plane second moment of area of rafter

Ξ΄EHF,i Is the horizontal deflection of column top (see figure 7 (c))

οΏ½ β„Žπ‘Žπ‘Žπ‘‰π‘‰π‘ˆπ‘ˆπ‘ˆπ‘ˆπ‘ˆπ‘ˆ ,π‘Žπ‘Ž

οΏ½ �𝐻𝐻𝐸𝐸𝐻𝐻𝐹𝐹 ,π‘Žπ‘Žπ›Ώπ›ΏπΈπΈπ»π»πΉπΉ ,π‘Žπ‘Ž

οΏ½π‘šπ‘šπ‘Žπ‘Žπ‘Ÿπ‘Ÿ Is the minimum value for columns 1 to n (n = the number of columns)

7.3.2.2 Rafter Snap-through buckling load factor (Oppe, SN033a-EN-EU)

For frames with rafter slopes not steeper than 1:2 (26Β°), Ξ±cr,r may be taken as:

Ξ±cr,r,est = οΏ½π·π·π‘ˆπ‘ˆοΏ½ οΏ½

55.7οΏ½4+π‘ˆπ‘ˆβ„ŽοΏ½

π›Ίπ›Ίβˆ’1��𝐼𝐼𝑐𝑐+πΌπΌπ‘Žπ‘Ž

πΌπΌπ‘Žπ‘ŽοΏ½ οΏ½275

π‘’π‘’π‘¦π‘¦π‘Žπ‘ŽοΏ½ tan 2πœƒπœƒπ‘Žπ‘Ž

D cross-section depth of rafter

L span of the bay

h means height of the column

𝐼𝐼𝑐𝑐 in-plane second moment of area of column

πΌπΌπ‘Žπ‘Ž in-plane second moment of area of rafter

π‘’π‘’π‘¦π‘¦π‘Žπ‘Ž nominal yield strength of the rafter

πœƒπœƒπ‘Žπ‘Ž roof slope if roof is symmetrical

𝛺𝛺 Fr/Fo the ratio of the arching effect of the frame where

Fr= factored vertical load on the rafter

F0 = maximum uniformly distributed load for plastic failure of the rafter treated as a

fixed end beam of span L οΏ½πΉπΉπ‘œπ‘œ = 16 π‘Šπ‘Šπ‘π‘π‘π‘ ,𝑦𝑦 ,𝑅𝑅 π‘’π‘’π‘¦π‘¦π‘ˆπ‘ˆ

οΏ½

But where Ξ© ≀ 1, Ξ±cr,r = ∞

Page 21: Plastic Design of Portal frame to Eurocode 3 · PDF filePlastic Design of Portal frame to Eurocode 3. Supporting Notes. ... EC3 requires that the second order effects are explicitly

16

7.3.3 Accounting second order effects (J.B.P.Lim, November 2005)

Eurocode account to second order effects in the absence of elastic-plastic second order

analysis software by deriving loads that are amplified to account for the effects of deformed

geometry (second order effects). Application of these amplified loads through first order

analysis gives bending moment, axial forces and shear forces that include the second-order

effects approximately. The magnification factor is calculated by method called Merchant-

Rankin method, which is as following:

7.3.3.1 Category A: Regular, symmetric and asymmetric pitched and mono-pitched frames

Regular, symmetrical and mono pitched frames are either single-span or multi span frames in

which there is only a small variation in height (h) or span (L) between different spans;

variation in height and span of the order of 10% may be considered sufficiently small. 1

1 βˆ’ οΏ½ 1π›Όπ›Όπ‘π‘π‘Žπ‘Ž

οΏ½

Provided that π›Όπ›Όπ‘π‘π‘Žπ‘Ž β‰₯3

Where π›Όπ›Όπ‘π‘π‘Žπ‘Ž can be calculated as shown above in section 7.3.2

Figure 8- Examples of Category A (Oppe, SN033a-EN-EU)

Page 22: Plastic Design of Portal frame to Eurocode 3 · PDF filePlastic Design of Portal frame to Eurocode 3. Supporting Notes. ... EC3 requires that the second order effects are explicitly

17

7.3.3.2 Category B: Frames that fall outside of Category A and excluding tied portals

Frames that are outside of category A and excluding tied portals 1.1

1 βˆ’ οΏ½ 1π›Όπ›Όπ‘π‘π‘Žπ‘Ž

οΏ½

7.3.3.3 Procedure of Plastic analysis

The method, as currently given in EN 1993-1-1, implies the following procedure:

(i) Choose initial portal sections. (ii) Calculate Ξ±cr factor by which the design loading would have to be increased to

cause elastic instability in a global mode (iii) Comply with Merchant Rankin by multiplying the partial safety factors by the

following magnification factor;

1

1 βˆ’ οΏ½ 1π›Όπ›Όπ‘π‘π‘Žπ‘Ž

οΏ½

(iv) Perform the rigid plastic analysis of portal frame using the Partial safety factors in step (iii).

(v) Check that collapse load factor of step (iv) analysis is greater one (πΆπΆπ‘œπ‘œπ‘π‘π‘π‘π‘Žπ‘Žπ‘π‘π‘Žπ‘Žπ‘Žπ‘Ž π‘π‘π‘œπ‘œπ‘Žπ‘Žπ‘™π‘™ π‘’π‘’π‘Žπ‘Žπ‘π‘π‘Žπ‘Žπ‘œπ‘œπ‘Žπ‘Ž β‰₯1.0) where,

πΆπΆπ‘œπ‘œπ‘π‘π‘π‘π‘Žπ‘Žπ‘π‘π‘Žπ‘Žπ‘Žπ‘Ž π‘π‘π‘œπ‘œπ‘Žπ‘Žπ‘™π‘™ π‘’π‘’π‘Žπ‘Žπ‘π‘π‘Žπ‘Žπ‘œπ‘œπ‘Žπ‘Ž =πΆπΆπ‘œπ‘œπ‘π‘π‘π‘π‘Žπ‘Žπ‘π‘π‘Žπ‘Žπ‘Žπ‘Ž π‘π‘π‘œπ‘œπ‘Žπ‘Žπ‘™π‘™π‘ˆπ‘ˆπ‘ˆπ‘ˆπ‘ˆπ‘ˆ π‘π‘π‘œπ‘œπ‘Žπ‘Žπ‘™π‘™

(vi) If the Collapse load factor in step (v) is less than one then increase the section size and re-check if the increased section size can withstand second-order effects.

Page 23: Plastic Design of Portal frame to Eurocode 3 · PDF filePlastic Design of Portal frame to Eurocode 3. Supporting Notes. ... EC3 requires that the second order effects are explicitly

18

8 SERVICEABILITY LIMIT STATE

8.1 Outlines

The serviceability limit state (SLS) analysis should be performed using SLS load cases

mentioned below, to ensure that deflections are within acceptable limit at characteristic

loading. This is normally first-order analysis, where plasticity occurs under SLS loads, the

deflections from plastic deformations should be included in the analysis.

It is important to ensure that the deflections etc. are acceptable for the cladding and use of the

building, for example for brittle cladding such as brickwork, the limit of h/150 on horizontal

deflection may be unsuitable.

8.2 Load Combinations

Structural imperfections should not normally be considered. No partial safety factors

applied to actions for the SLS. The load combination as follow (BS EN 1991-1-3:2003):

Note that there are different ψ factors for different types of variable actions, see section ULS

8.3 Deflections limiting values (BUREAU, SN035a-EN-EU):

No specific deflection limits are set in Eurocode 1993-1-1 [1]. According to EN 1993-1-1, Β§

7.2 and EN 1990 – Annex A1.4 [2], deflection limits should be specified for each project and

agreed with the client. The National Annex to EN 1993-1-1 may specify limits for application

in individual countries. Where limits are specified they have to be satisfied. Where limits are

not specified, the following might be helpful when deciding relevant deflection limits.

Characteristic values of permanent actions (βˆ‘Gk j)

+Full characteristic value of the most unfavorable variable action Qk,1

+Reduced values of all other unfavorable variable actions ψ0,i Qk,i

Page 24: Plastic Design of Portal frame to Eurocode 3 · PDF filePlastic Design of Portal frame to Eurocode 3. Supporting Notes. ... EC3 requires that the second order effects are explicitly

19

β€’ Portal frames without gantry cranes h/150 β€’ Other single storey buildings h/300

Figure 9- Definition of horizontal displacements (BUREAU, SN035a-EN-EU)

8.4 Suggested Procedure to check serviceability limit state

1) Determine SLS load combinations and ψ factors.

2) Perform first order analysis.

3) Check that Ξ±cr β‰₯ 15 to allow for second-order effects to be ignored

4) If Ξ±cr ≀ 15to, re-analyze including magnification factor described in section (7.3.3)

5) Check that the deflections do not impair the function of the building, including the

cladding.

Page 25: Plastic Design of Portal frame to Eurocode 3 · PDF filePlastic Design of Portal frame to Eurocode 3. Supporting Notes. ... EC3 requires that the second order effects are explicitly

20

9 FRAME IMPERFECTIONS

Frame imperfections are assumed in EC3 as a slope of the columns and can be induced in

the analysis model as shown below;

Figure 10- Frame imperfections as column slopes (BS EN 1993-1-1:2005)

EC3 allows the use of the equivalent horizontal forces, which are probably easier to use on

sloping roof structures such as portals. These forces may be calculated from the column axial

force using β€˜β€™simply supported’’ assumptions as below (BS EN 1993-1-1:2005);

Ο† = Ο†o Ξ±h Ξ±m

- With Ο†o for single storey frame it is 1/200

Ξ±h is the reduction factor for the height h applicable to columns:

Ξ±β„Ž = 2βˆšβ„Ž

But 23≀ Ξ±h ≀ 1.0

h is the height if the structure in meters.

Ξ±m is the reduction factor for the number of columns in the row

Ξ±π‘šπ‘š = οΏ½0.5(1 + 1π‘šπ‘š

)

m is the number of columns in a row.

Columns which carry a vertical load NEd of less than 50% of the mean value of the

vertical load per column in the plane considered shall not be considered in m.

Page 26: Plastic Design of Portal frame to Eurocode 3 · PDF filePlastic Design of Portal frame to Eurocode 3. Supporting Notes. ... EC3 requires that the second order effects are explicitly

21

Frame imperfections induce internal forces and moments that will increase or

decrease the effect of other actions depending on the direction. Therefore if the frame

imperfections is to be induced in geometry model of EC3 (discussed earlier) it is

require two versions to be considered; from each side, but are only considered in one

direction at a time.

It must be remembered that the horizontal forces due imperfections do not increase the

total horizontal load on the building as shown if figure below,

Figure 11- Force equivalent to frame imperfections (BS EN 1993-1-1:2005)

The following simplified approach to frame imperfection can be used for regular portal frame;

1) Calculate total axial load on structure, NEd.

2) Calculate Π€ NEd

3) Divide this Π€ NEd into series of equal horizontal forces applies at top of each column.

Frame imperfections induce internal forces and moments that will increase or decrease the

effects of actions, depending on the direction.

Page 27: Plastic Design of Portal frame to Eurocode 3 · PDF filePlastic Design of Portal frame to Eurocode 3. Supporting Notes. ... EC3 requires that the second order effects are explicitly

22

10 CONNECTION OF MEMBERS

The rafter and columns of I-section portal frames consist of rolled I-sections, with rafter end

being haunched and sit-bolted to the columns. The column section is heavier than the rafter

section, so that the relative column-haunch rafter strengths roughly follow the shape of the

bending moment diagram up the column and across the rafter. As a scope of plastic analysis,

moments referred to are plastic moments under gravity loading, with plastic hinges

developing either in the column top or in the rafter at the haunch and in the rafter near apex

(Position of maximum bending moments).

10.1 Eaves and apex connections

The types of eaves and apex haunches shown in figure 12 are the ones almost universally

used because of their relative simplicity and the ease with which the frame can be erected.

The critical design condition is usually gravity loading with the rafter-to-column connection

having to sustain a high negative moment and apex connection smaller positive moment. The

moment at the eaves produces a high tensile force in the upper flange of the rafter that is

transmitted through the upper tension bolts and the end plate to the inner flange of the

column. The compressive force in the lower flange of the haunch is transferred in bearing

through the end plate onto the column flange and into the web.

Figure 12- Apex and Eaves Connections ( The Southern African Institute of Steel

Construction,)

Page 28: Plastic Design of Portal frame to Eurocode 3 · PDF filePlastic Design of Portal frame to Eurocode 3. Supporting Notes. ... EC3 requires that the second order effects are explicitly

23

The transfer of moment at the apex is similar, except that here the moment is positive so the

forces are reversed. The haunch and apex regions are vitally important parts of the frame and

must be carefully proportioned. It is possible to achieve economy through simplification of

the connections, but only when every aspect of the transfer of direct, moment and shear forces

has been carefully considered.

10.2 Lateral restraint to portal frames

As there are high bending moments at the column-to-rafter junction it is necessary to provide

adequate lateral-torsional restraint in this region. This may be done by means of a strut

connected into the column web within the depth of the rafter haunch. A typical detail is

shown in figure 13, where a circular hollow section with an end plate is used. This section is

light, as well as strong in both tension and compression; because of the butt-welded end plate

it is also able to offer torsional restraint to the column in this highly stressed area.

Figure 13- Stabilising of the column ( The Southern African Institute of Steel

Construction,)

10.3 Bracing to compression flanges of rafters

Where the lower flanges of the rafters are in compression, either near the columns when under

gravity loading or further up the slope when under wind uplift loading, they require to be

restrained laterally to prevent buckling. This is usually done by fitting angle braces to the

purlins, as shown in figure 14.

Page 29: Plastic Design of Portal frame to Eurocode 3 · PDF filePlastic Design of Portal frame to Eurocode 3. Supporting Notes. ... EC3 requires that the second order effects are explicitly

24

Figure 14- Braces to rafter bottom flange (King, Technical Report P164)

10.4 Purlins (Chaffotec, SS049a-EN-EU)

In a typical portal-frame building the main structural components are the portal frames

themselves and the purlins. The principal function of roofing purlins is to transfer the forces

on the roof of a building to its main structure. The wall rails perform the same role on the

facades. Purlins and wall rails are important components in the secondary structure of a

building. The purlin structure of a building is designed in accordance with the type of roofing

to be used. The nature of the roofing, in particular, directly influences the spacing between

purlins; to achieve maximum economy it is necessary to optimize the combined cost of these

two items by choosing the correct spacing for the frames. Various spanning arrangements can

be used for the purlins, e.g. single, double or multi-span or Z-sections overlapped over the

rafters.

10.5 Column base (King, Technical Report P147)

The great majority of portal frames are designed with nominally pinned bases. This is for

reasons of economy and simple design. Not only are fixed bases more expensive because of

the need for thicker and larger base plates and the stiffening that is necessary, but the

foundations require being much larger to resist the base moments. Only in cases of large

lateral deflection, or possibly where brick walls are built into the columns, is it necessary to

resort to fixed bases. These should be kept as simple as possible.

Page 30: Plastic Design of Portal frame to Eurocode 3 · PDF filePlastic Design of Portal frame to Eurocode 3. Supporting Notes. ... EC3 requires that the second order effects are explicitly

25

11 BRACING

Bracing is required to resist lateral loads, principally wind loads, and the destabilising effects

of the imperfections defined in Section 5.2.3 of EN 1993-1-1:2005. This bracing must be

correctly positioned and have adequate strength and stiffness to justify the assumptions made

in the analysis and member checks.

EN 1993-1-1:2005 Section 5.2.3 of allows the imperfections to be described either as

geometrical imperfections or as equivalent horizontal forces. The equivalent horizontal forces,

which cause the forces in the bracing, do not increase the total load on the whole structure,

because they form a self equilibrating load case.

11.1 Overall column bracing (King, Technical Report P164)

Bracing must be provided to hold the columns upright and resist loads, such as wind loading,

occurring at right angles to the frame. Columns are assumed to be built slightly out of

vertical, and the simplest method to account for this effect is by means of the equivalent

horizontal forces shown in Figure imperfection section. These forces can occur in any

direction, but are considered to act in one direction at a time.

The bracing is designed to resist wind loads plus equivalent horizontal forces, which amounts

to approximately [wind forces 0.5% vertical forces causing axial compression]. Care must be

taken when detailing the bracing, as details that reduce the stiffness (e.g. by deflection from

local bending of plates, rings or angles) might increase the imperfection loads due to second-

order effects. If the columns carry a net tensile force, as in an uplift load case due to wind,

then this loading does not destabilise the structure, so may be neglected.

11.1.1 Portal bracing

The term β€œportal bracing” is commonly used to describe a system of bracing comprising

portals instead of cross-bracing to provide the restraint normal to the main frames. An

example of portal bracing is shown in Figure 15. It is frequently used to provide lateral

stability to the top of the internal columns, because the use of cross-bracing would result in an

unacceptable restriction to freedom of use. It is also used at exterior walls, where cross-

bracing might obstruct windows, doors, etc.

Page 31: Plastic Design of Portal frame to Eurocode 3 · PDF filePlastic Design of Portal frame to Eurocode 3. Supporting Notes. ... EC3 requires that the second order effects are explicitly

26

Figure 15- Braced portals (King, Technical Report P147)

The bracing portals are designed to resist the total equivalent horizontal forces from all the

columns that rely on those portals for stability, plus the relevant wind load.

11.2 Bracing to inner flanges

Bracing to the inner flanges is often most conveniently formed by diagonal struts from the

purlins or sheeting rails or sheeting rails to gluts welded to the inner flange and web, as shown

in figure 17. The effectiveness of such bracing depends on the stiffness of the system,

especially the stiffness of the purlins. The effect of purlins flexibility on the bracing is shown

in figure 16.

Figure 16- Effects of purlin flexibility on bracing (King, Technical Report P164)

Figure 17- Bracing to inner flanges (King, Technical Report P147)

The compression flange of eaves and valley haunches must be braced at the column-haunches

connection, unless stability analysis test data prove it to be unnecessary. This restraint is

needed, because the haunch stability checks are based on full torsional restraint at this point.

Page 32: Plastic Design of Portal frame to Eurocode 3 · PDF filePlastic Design of Portal frame to Eurocode 3. Supporting Notes. ... EC3 requires that the second order effects are explicitly

27

11.3 Bracing at the plastic hinge (King, Technical Report P164)

Due to the fact that at plastic hinges, all material of the cross-section is at yield; this result in

cross-section unable to resist any twisting action. Hence it is recommended by EN1993-1-

1:2005 that a restraint should be provided at plastic hinge position in order to resist against

lateral torsion buckling.

Figure 18- Typical stiff torsional restraint (King, Technical Report P164)

Section 6.3.5.2 of EN 1993-1-1:2005 recommends that bracing should be provided to both

tension and compression flanges at or within 0.5h of the calculated plastic hinges, where h is

the depth of the member (see fig below)

Figure 19- Bracing at plastic hinge (King, Technical Report P147)

At each rotated plastic hinge location the cross section should have an effective lateral and

torsional restraint with appropriate resistance to lateral forces and torsion induced by local

plastic deformations of the member at this location. At each plastic hinge location, the

connection (e.g. bolts) of the compression flange to the resisting element at that point (e.g.

purlin), and any intermediate element (e.g. diagonal brace) should be designed to in its plane

and perpendicular to the web plane, without any combination with other loads.

Page 33: Plastic Design of Portal frame to Eurocode 3 · PDF filePlastic Design of Portal frame to Eurocode 3. Supporting Notes. ... EC3 requires that the second order effects are explicitly

28

12 CROSS SECTION RESISTANCE

12.1 The classification of cross-section

EC3 (BS EN 1993-1-1:2005) defines four classes of cross section. The class into which a

particular cross section falls depends upon the slenderness of each element (defined by a

width-to-thickness ratio) and the compressive stress distribution i.e. uniform or linear. The

classes are defined in terms of performance requirements for resistance of bending moments:

1) Class 1 cross-sections are those which can form a plastic hinge with the required

rotational capacity for plastic analysis.

2) Class 2 cross-sections are those which, although able to develop a plastic moment,

have limited rotational capacity and are therefore unsuitable for structures designed by

plastic analysis.

3) Class 3 cross-sections are those in which the calculated stress in the extreme

compression fibre can reach yield but local buckling prevents the development of the

plastic moment resistance.

4) Class 4 cross-sections are those in which local buckling limits the moment resistance

(or compression resistance for axially loaded members). Explicit allowance for the

effects of local buckling is necessary.

The Eurocode classifications according to slenderness of flange or web elements is given in

EN 1993-1-1:2005 (E) Table 5.2.In portal frame designed by plastic methods, the columns

and rafters must be Class 1 or Class 2. These two classes have the same rule for checking

resistance. The only element which may be different is the haunch web, which may be Class

3, according to EN1993-1-1:2005 (E).

Page 34: Plastic Design of Portal frame to Eurocode 3 · PDF filePlastic Design of Portal frame to Eurocode 3. Supporting Notes. ... EC3 requires that the second order effects are explicitly

29

12.2 Bending moment (BS EN 1993-1-1:2005)

The design value of the bending moments MEd at each cross-section shall satisfy: 𝑀𝑀𝐸𝐸𝑙𝑙

𝑀𝑀𝑐𝑐 ,𝑅𝑅𝑙𝑙 ≀ 1.0

Where Mc, Rd is determined considering fastener holes (see EN 1993-1-1:2005

Section 6.2.5.)

The design resistance for bending about one principal axis of a cross-section is determined as

follow:

𝑀𝑀𝑐𝑐 ,𝑅𝑅𝑙𝑙 = 𝑀𝑀𝑝𝑝𝑝𝑝 ,𝑅𝑅𝑙𝑙 = π‘Šπ‘Šπ‘π‘π‘π‘ π‘’π‘’π‘¦π‘¦π›Ύπ›Ύπ‘€π‘€π‘œπ‘œ

for class 1 and 2 cross-section.

𝑀𝑀𝑐𝑐 ,𝑅𝑅𝑙𝑙 = π‘€π‘€π‘Žπ‘Žπ‘π‘ ,𝑅𝑅𝑙𝑙 = π‘Šπ‘Šπ‘Žπ‘Žπ‘π‘ ,π‘šπ‘šπ‘Žπ‘Žπ‘Ÿπ‘Ÿ π‘’π‘’π‘¦π‘¦π›Ύπ›Ύπ‘€π‘€π‘œπ‘œ

for class 3 cross-section.

𝑀𝑀𝑐𝑐 ,𝑅𝑅𝑙𝑙 = π‘Šπ‘Šπ‘Žπ‘Žπ‘’π‘’π‘’π‘’ ,π‘šπ‘šπ‘Žπ‘Žπ‘Ÿπ‘Ÿ π‘’π‘’π‘¦π‘¦π›Ύπ›Ύπ‘€π‘€π‘œπ‘œ

for class 4 cross-section.

12.3 Shear (BS EN 1993-1-1:2005)

The design value of the shear force 𝑉𝑉𝐸𝐸𝑙𝑙 at each cross section shall satisfy:

𝑉𝑉𝐸𝐸𝑙𝑙𝑉𝑉𝑐𝑐,𝑅𝑅𝑙𝑙

≀ 1.0

- Where 𝑉𝑉𝑐𝑐 ,𝑅𝑅𝑙𝑙 is the design shear resistance.

For plastic design 𝑉𝑉𝑐𝑐 ,𝑅𝑅𝑙𝑙 is the design plastic shear resistance 𝑉𝑉𝑝𝑝𝑝𝑝 ,𝑅𝑅𝑙𝑙 which is given by;

𝑉𝑉𝑝𝑝𝑝𝑝 ,𝑅𝑅𝑙𝑙 = 𝐴𝐴𝑣𝑣 (𝑒𝑒𝑦𝑦 /√3)𝛾𝛾𝑀𝑀0

- Where 𝐴𝐴𝑣𝑣 is the shear area which is for rolled I and H sections given by;

Av = Aβˆ’2bπ‘Žπ‘Žπ‘Žπ‘Ž + (π‘Žπ‘Žπ‘€π‘€ + 2π‘Žπ‘Ž)π‘Žπ‘Žπ‘’π‘’

Where

A is the cross-sectional area

b is the overall breadth

tf is the flange thickness

r is the root radius

Where the shear force is present allowance should be made for it, effects on the moment resistance are as following.

Page 35: Plastic Design of Portal frame to Eurocode 3 · PDF filePlastic Design of Portal frame to Eurocode 3. Supporting Notes. ... EC3 requires that the second order effects are explicitly

30

12.3.1 For low shear (see EN 1993-1-1 Section 6.2.8),

Where the shear force is less than the half the plastic shear resistance its effect on the

moment resistance may be neglected.

VEd <0.5 Vpl.Rd

12.3.2 For high shear

Where high shear force exists reduced moment resistance should be taken as the design

resistance of the cross-section, calculated using reduced yield strength

VEd > 0.5 Vpl.Rd

(1 βˆ’ 𝜌𝜌)𝑒𝑒𝑦𝑦

𝜌𝜌 = οΏ½οΏ½2𝑉𝑉𝐸𝐸𝑙𝑙𝑉𝑉𝑝𝑝𝑝𝑝 ,𝑅𝑅𝑙𝑙

οΏ½ βˆ’ 1οΏ½ 2

12.4 Axial force (BS EN 1993-1-1:2005)

Where axial force is present, allowance should be made for its effects on the plastic moment

resistance of the cross-section. For doubly symmetrical I and H sections or other flanged

sections,

12.4.1 For low axial force

Allowance need to not be made for the effect of the axial force on the plastic resistance

moment about y-y axis when both the following criteria a satisfied:

𝑁𝑁𝐸𝐸𝑙𝑙 ≀ 0.25 𝑁𝑁𝑝𝑝𝑝𝑝 ,𝑅𝑅𝑙𝑙 and

𝑁𝑁𝐸𝐸𝑙𝑙 ≀ (0.5 β„Žπ‘€π‘€π‘Žπ‘Žπ‘€π‘€π‘’π‘’π‘¦π‘¦)/π›Ύπ›Ύπ‘šπ‘šπ‘œπ‘œ

Provided that the design value of shear force VEd does not exceed 50% of the design plastic

shear resistance Vpl,Rd no reduction of the resistance defined for bending and axial force need

to be made.

Page 36: Plastic Design of Portal frame to Eurocode 3 · PDF filePlastic Design of Portal frame to Eurocode 3. Supporting Notes. ... EC3 requires that the second order effects are explicitly

31

12.4.2 For high axial force

Where VEd exceeds 50% of Vpl,Rd the design resistance of the cross-section to combinations of

moment and axial force should be calculated using reduced yield strength.

(1 βˆ’ 𝜌𝜌)𝑒𝑒𝑦𝑦

𝜌𝜌 = οΏ½οΏ½2𝑉𝑉𝐸𝐸𝑙𝑙𝑉𝑉𝑝𝑝𝑝𝑝 ,𝑅𝑅𝑙𝑙

οΏ½ βˆ’ 1οΏ½ 2

13 STABILITY CHECKS,

The following stability checks should be carried out

β€’ Restraint of plastic hinge β€’ Stability of the rafter β€’ Stability of haunch β€’ Stability of columns

13.1 Restraint of plastic hinge

At a plastic hinge location both flanges should location both flanges should be provided with

lateral and torsional restraint by means of diagonal stays. If is not practical to provide such

restraint at actual hinge location, it is permissible to provide it within a distance along the

member equal to h/2. (See section 11.3) (King, Technical Report P147)

At the location of plastic hinges, all of the material of the cross-section is at yield. It is

therefore unable to resist any twisting action and therefore the restraint against lateral torsion

buckling is reduced. It is thus necessary to impose a more stringent limitation on the distance

to the next restraint than would otherwise be the case.

For members with restraints to the compression flange but without intermediate restraints to

the tension flange, the maximum distance to the next compression flange restraint Lm may be

found using either a conservative method based on the uniform moment equal to the most

Page 37: Plastic Design of Portal frame to Eurocode 3 · PDF filePlastic Design of Portal frame to Eurocode 3. Supporting Notes. ... EC3 requires that the second order effects are explicitly

32

adverse moment in the segment or using a method which takes some account of moment

gradient.

Lm, the distance from a plastic hinge to the next lateral restraint may conservatively be

calculated using the expression (BS EN 1993-1-1:2005)

Lm =38iz

157.4

NEd

A

+

1756C1

2

W pl,y2

AIt

fy

235

2

In this equation

NEd is the design value of the compression force in the member

A is the cross section area (mm2) of the member

Wpl is the plastic section modulus of the member

fy is the yield strength of the material (N/mm2 )

It is the torsion constant of the member

C1 is a factor which depends on moment distribution and can safely be taken as 1.

If the member is restrained on the flange then the maximum distance to then the

maximum distance to the nearest restraint to both flanges should not be greater than Lk

(assuming constant uniform moment) or it may be taken as Ls calculated as for the

stability of the haunch but with taper factor of 1.0 ( see clause 8.8.3).

13.2 Rafter Stability (The institutionof Structural Engineers, TP/08/43

EC3/08/16)

The rafter should be checked to ensure that the stability is maintained in all load cases.

Unless there is wind uplift, the following checks should be made;

a) At the plastic hinge location near the ridge both flanges should be laterally restraint in

order to provide torsional restraint.

b) A purlin or other restraint is needed on compression flange at a distance determined in

the same way as mentioned above for plastic hinge (Spacing restraint < Lm).

Page 38: Plastic Design of Portal frame to Eurocode 3 · PDF filePlastic Design of Portal frame to Eurocode 3. Supporting Notes. ... EC3 requires that the second order effects are explicitly

33

c) In areas where there is a compression on the bottom flange the procedure given for

haunches in section 13.3 should be applied using constants applicable to haunch/depth

= 1

13.3 Stability of haunch

Provided that the tension flange of the haunch is restrained, then the maximum length

between restraints to the compression flange of the haunch should be limited to Ls

obtained as shown below, provide that;

a) The rafter is a UB section

b) The haunch flange is not smaller than the rafter flange.

c) The depth of the haunch (hh) is not greater than twice the depth of the rafter

allowing for its slope (hh)

d) Adjacent to plastic hinge locations the spacing of the tension restraint complies

with Lm.

Where Ls is given by;

1) For three flanged haunches (BS EN 1993-1-1:2005)

π‘ˆπ‘ˆπ‘Žπ‘Ž =οΏ½οΏ½πΆπΆπ‘Ÿπ‘Ÿ π‘ˆπ‘ˆπ‘˜π‘˜οΏ½

𝑐𝑐

2) For two flanged hunches (BS EN 1993-1-1:2005)

π‘ˆπ‘ˆπ‘Žπ‘Ž =οΏ½οΏ½πΆπΆπ‘Ÿπ‘Ÿ π‘ˆπ‘ˆπ‘˜π‘˜οΏ½

𝑐𝑐

Where

- C is the taper factor to take account of the haunch shape

- Cn is a non-linear moment gradient factor given as below;

- Lk is the length derived for a uniform member with a cross-section equal to the shallowest section

Page 39: Plastic Design of Portal frame to Eurocode 3 · PDF filePlastic Design of Portal frame to Eurocode 3. Supporting Notes. ... EC3 requires that the second order effects are explicitly

34

14.5

6004.5

2

βˆ’

+

=

f

y

zf

y

k

th

Ef

ith

Ef

L

13.4 Stability of the column

Near the top of the column a restraint should be provided at the location of the plastic hinge,

together with a further restraint at a distance below the position of the hinge restraint, based

on that given for the spacing of restraints at plastic hinges (Lm). If the column is restrained on

the tension flange then the distance to the nearest restraint on the compression flange may be

taken as, (The institutionof Structural Engineers, TP/08/43 EC3/08/16)

+=

EdRkyN

Rkyplkms aNM

MLCL

,,

,,

Where

Cm is the modification factor for linear moment gradient.

a is the distance between the centroid of the member with the plastic hinge

and the centroid of the restraint members.

Mpl,y,Rk is the characteristic plastic moment of resistance in the strong direction.

MN,y,Rk is the characteristic plastic moment of resistance in the strong direction

allowing for the effects of axial load.

Page 40: Plastic Design of Portal frame to Eurocode 3 · PDF filePlastic Design of Portal frame to Eurocode 3. Supporting Notes. ... EC3 requires that the second order effects are explicitly

35

14 FIRE BOUNDARY CONDITION

14.1 Outline

If the building is constructed close to the site boundary, the external wall of the building

will require a degree of fire resistance. It is generally accepted that the structural members

that support these wall will also require fire resistance to ensure that the walls remain stable

for a reasonable period during fire.

14.2 Building Regulation requirements in UK (Newman, Technical Report P313)

The requirement for external walls to have fire resistance has resulted in portal framed

building being treated as a special case. The argument put forward by building authorities was

that columns and rafters of portal frames are designed as a single continuous element thus;

this means that the whole elements of the portal frames requires same level if fire resistance.

As a result of providing this fire protection to rafter and columns as well, represented a

significant increase in the cost and therefore an alternative solutions where investigated to

keep portal frames building economical.

14.3 Alternative approaches to boundary fire (Newman, Technical Report P313)

Following a study (Constrado 1979) of portal frames behavior in actual fire it was

concluded that the most viable alternative to fire protecting rafters is to ensure that, even if the

roof collapsed, the stability of the external walls would be maintained. Guidance on how to

achieve this conclusion was initially published in 1979 by Constrado. The guide was later

published by SCI, as a second edition the behavior of steel portal frames in boundary

conditions (P087). That publication has been referenced in Approved documents B for a

number of years. The designing of boundary walls to resist the forces and moments as

recommended in SCI P087, is generally a more economical solution than fire protecting the

whole portal frame. This engineering solution is considered to meet the β€œreasonableness” test

of the Building Regulations.

Page 41: Plastic Design of Portal frame to Eurocode 3 · PDF filePlastic Design of Portal frame to Eurocode 3. Supporting Notes. ... EC3 requires that the second order effects are explicitly

36

14.4 Effects of fire on Portal frames

In the early stages of fire, the portal rafter starts to heat up and expands which results in a

small outward deflection of the eaves and small upward deflection of the apex. As fire

continues to burn, the rafter temperature continues to raise the deflection and moments due to

thermal expansion increase. The bending moments induced by thermal expansion are shown

in figure 20.

Figure 20- Bending moment diagram for uniform temperature rise (Newman, Technical

Report P313)

The temperature raising causes a reduction in the yield strength of the steel and although the

loading is constant, the reduction in moment capacity causes the formation of plastic hinge at

a high temperature. Plastic hinges starts to form at in the rafter where the term β€˜fire hinge’ is

used to distinguish this type of plastic hinge from plastic hinges which can form at normal

temperatures. The moment resistance of fire hinge is slightly less corresponding value at

normal temperature, so the fire hinges tends to forms at the end of hunches and near to the

ridge see figure below.

Figure 21- Probable positions of fire hinges in portal frame (Newman, Technical Report

P313)

Page 42: Plastic Design of Portal frame to Eurocode 3 · PDF filePlastic Design of Portal frame to Eurocode 3. Supporting Notes. ... EC3 requires that the second order effects are explicitly

37

At this stage, the frame maintains its basic shape where the loading on the frame is it’s self-

weight and purlins but with only proportion of the weight of cladding. The rafter continues to

collapse and falls to the eaves level but remains reasonably straight between fire hinges.

Torsion stability may occur as the purlins lose their strength. The rafter is acting partially as

centenary, creating a tension load, which pulls on the top of the column. The columns are still

upright and shows sign of distress.

The rafter continues to collapse as it loses stiffness and the section may rotate so that it sags

with the web horizontal. The moment at the end of the hunch still withstand an applicable

value. As the rafter further losses strength; it continue to sag to below eaves level and begin to

pull inward the tops of columns.

Figure 22- Rafter collapse to eaves level (Newman, Technical Report P313)

The mathematical model of the rafter collapse mechanism at this stage is given in Appendix.

It is the forces and moments at this stage that are used to determine the overturning moment.

14.5 Mathematical Model (Newman, Technical Report P313)

A full mathematical model of the collapse mechanism for symmetrical pitched portal frames

has been developed and presented in Appendix. The use of the full model is tedious to hand

calculations. Thus a more simplified version was recommended in SCI P087 which applies to

symmetrical pitched rafter of single or multi-bay. Also the columns on the boundary should

be adequately restrained in longitudinal direction. The requirement is for fire protection of

columns and requirement to resist the calculated forces and moments on the column bases are

applicable only to columns that support protected area of boundary wall. Columns which do

not support protected areas will not require fire protection or moment resisting column bases.

Page 43: Plastic Design of Portal frame to Eurocode 3 · PDF filePlastic Design of Portal frame to Eurocode 3. Supporting Notes. ... EC3 requires that the second order effects are explicitly

38

So the foundations, columns and column beams base should be designed to resist the

following moment s and reactions.

Vertical Reaction

𝑉𝑉𝑅𝑅 =12

𝑀𝑀𝑒𝑒 Γ— π‘ˆπ‘ˆ Γ— π‘ˆπ‘ˆ + π‘Šπ‘Šπ·π·

Horizontal Reaction

𝐻𝐻𝑅𝑅 = 𝐾𝐾 οΏ½π‘€π‘€π‘’π‘’π‘ˆπ‘ˆ 𝐺𝐺 𝐴𝐴 βˆ’πΆπΆ 𝑀𝑀𝑝𝑝

𝐺𝐺� π‘€π‘€π‘π‘π‘Žπ‘Ž π‘Ÿπ‘Ÿπ‘œπ‘œπ‘Žπ‘Ž π‘π‘π‘Žπ‘Žπ‘Žπ‘Žπ‘Žπ‘Ž π‘Žπ‘Žβ„Žπ‘Žπ‘Žπ‘Ÿπ‘Ÿ

𝑀𝑀𝑐𝑐

10π‘Œπ‘Œ

Overturning moment:

𝑂𝑂𝑂𝑂𝑀𝑀 = 𝐾𝐾 οΏ½π‘€π‘€π‘’π‘’π‘ˆπ‘ˆ 𝐺𝐺 π‘Œπ‘Œ �𝐴𝐴 +π΅π΅π‘Œπ‘ŒοΏ½ βˆ’π‘€π‘€π‘π‘ οΏ½

πΆπΆπ‘Œπ‘ŒπΊπΊβˆ’ 0.065οΏ½οΏ½ π‘€π‘€π‘π‘π‘Žπ‘Ž π‘Ÿπ‘Ÿπ‘œπ‘œπ‘Žπ‘Ž π‘π‘π‘Žπ‘Žπ‘Žπ‘Žπ‘Žπ‘Ž π‘Žπ‘Žβ„Žπ‘Žπ‘Žπ‘Ÿπ‘Ÿ

𝑀𝑀𝑐𝑐

10

In which

β€’ 𝐡𝐡 = π‘ˆπ‘ˆ2βˆ’πΊπΊ2

8𝐺𝐺

Where

β€’ Wf is the load at the time of collapse (KN/m2) given in table 7 in appendix.

β€’ WD is the dead load of the wall cladding (KN).

β€’ S is the distance between frame centers (m).

β€’ G is the distance between ends of hunches (m).

β€’ Y is the vertical height of the end of hunch (m).

β€’ Mp is the plastic moment of resistance of the rafter (KNm).

β€’ Mc is the plastic moment of resistance of column (KNm).

β€’ K =1 for single bay frames or is taken from table 5

β€’ L is the span (m).

β€’ A and C are the frame geometry parameters, given in appendix table 6.

Page 44: Plastic Design of Portal frame to Eurocode 3 · PDF filePlastic Design of Portal frame to Eurocode 3. Supporting Notes. ... EC3 requires that the second order effects are explicitly

39

15 APPENDIX

A)

Calculation of non-linear moment factor

Cn = 12[R1 + 3R2 + 4R3 + 3R4 + R5 + 2(Rsβˆ’Re)]

- In which the values of R are given by R = (My,Ed + a NEd ) fy Wy,pl

- Where a is the distance between the centroid of the member and the centroid of the

restraining members, such as purlin restraining rafter. - R1 to R5 are the values at the ends quarter points and centre numbered sequentially

along the member. Only positive values should be included.

- In addition, only positive values of (Rs-RE) should be included, where

β€’ RE is the greater value of R1 and R5

β€’ RS is the maximum numeric value of R anywhere along the length being

considered.

Figure 23- Moment Ratios (BS EN 1993-1-1:2005)

Page 45: Plastic Design of Portal frame to Eurocode 3 · PDF filePlastic Design of Portal frame to Eurocode 3. Supporting Notes. ... EC3 requires that the second order effects are explicitly

40

B)

For a non-uniform member with constant flanges, provided that h β‰₯ 1,2b and h /tf β‰₯ 20 then

for haunched members or segments,

Calculation of taper factor,

c =1+3

ht f

βˆ’ 9

hmax

hmin

βˆ’1

2 / 3

Where

hh is the additional depth of the haunch or taper

hmax is the maximum depth of the cross-section within the length Ly

hmin is the minimum depth of the cross-section within the length Ly

hs is the vertical depth of the unhaunched section

Lh is the length of the haunch within the length Ly

Ly is the length between points at which the compression flange is laterally

Restrained

Figure 24- Dimensions defining taper factor (BS EN 1993-1-1:2005)

Page 46: Plastic Design of Portal frame to Eurocode 3 · PDF filePlastic Design of Portal frame to Eurocode 3. Supporting Notes. ... EC3 requires that the second order effects are explicitly

41

C)

πΆπΆπ‘šπ‘š =1

𝐡𝐡0 + 𝐡𝐡1π›½π›½π‘Žπ‘Ž + 𝐡𝐡2π›½π›½π‘Žπ‘Ž2

Calculation of (Cm) modification factor for linear moment gradient.

- In which

𝐡𝐡0 = 1+10πœ‚πœ‚1+20πœ‚πœ‚

𝐡𝐡1 = 5οΏ½πœ‚πœ‚πœ‹πœ‹+10οΏ½πœ‚πœ‚

𝐡𝐡2 = 0.51+πœ‹πœ‹οΏ½πœ‚πœ‚

βˆ’ 0.51+20πœ‚πœ‚

- Where:

a) πœ‚πœ‚ = π‘π‘π‘π‘π‘Žπ‘ŽπΈπΈπ‘π‘π‘π‘π‘Žπ‘Žπ‘‚π‘‚

β€’ π‘π‘π‘π‘π‘Žπ‘ŽπΈπΈ = πœ‹πœ‹2πΈπΈπΌπΌπ‘§π‘§π‘ˆπ‘ˆπ‘Žπ‘Ž2

β€’ π‘ˆπ‘ˆπ‘Žπ‘Ž is the distance between the torsional restraints

β€’ π‘π‘π‘π‘π‘Žπ‘Žπ‘‚π‘‚ is the elastic critical torsional buckling force for an I-section between restraint of both flanges at spacing π‘ˆπ‘ˆπ‘Žπ‘Ž with intermediate lateral restraint to the tension flange.

π‘π‘π‘π‘π‘Žπ‘Žπ‘‚π‘‚ = οΏ½ 1π‘Žπ‘Žπ‘Žπ‘Ž

2οΏ½ οΏ½πœ‹πœ‹2πΈπΈπΌπΌπ‘§π‘§π‘Žπ‘Ž2

π‘ˆπ‘ˆπ‘Žπ‘Ž2 + πœ‹πœ‹2πΈπΈπΌπΌπ‘€π‘€π‘ˆπ‘ˆπ‘Žπ‘Ž2 + πΊπΊπΌπΌπ‘Žπ‘ŽοΏ½

π‘Žπ‘Žπ‘Žπ‘Ž2 = π‘Žπ‘Žπ‘Žπ‘Ž2 + π‘Žπ‘Žπ‘Žπ‘Ž2 + π‘Žπ‘Ž2

β€’ A is the distance between the centroid of the member and the centroid of the restraining members, such as purlin restraining rafter

b) π›½π›½π‘Žπ‘Ž

It is the ratio of the algebraically smaller end moment to the larger end moment.

moments that produce compression in the non-restrained flange should be taken

ms positive. If the ratio is less than -1.0 the value of π›½π›½π‘Žπ‘Ž should be taken as -1.0

see figure

Page 47: Plastic Design of Portal frame to Eurocode 3 · PDF filePlastic Design of Portal frame to Eurocode 3. Supporting Notes. ... EC3 requires that the second order effects are explicitly

42

Figure 25- Value of Bt (BS EN 1993-1-1:2005)

Page 48: Plastic Design of Portal frame to Eurocode 3 · PDF filePlastic Design of Portal frame to Eurocode 3. Supporting Notes. ... EC3 requires that the second order effects are explicitly

43

D)

D1) Derivation of overturning moments (Newman, Technical Report P313):

The model assumes a worst-case scenario in which the rafter is inverted and acts like a

centenary. However, a small allowance is made for the residual bending resistance of the

rafter. The geometry and the forces acting on the collapsing rafter are shown in figure 26.

Fire boundary

Figure 26 Forces and moments acting on the column and rafters (Newman, Technical

Report P313)

Considering vertical equilibrium, the vertical reaction on the base of column base is given as

follow:

VR=F1+F2

Considering rafter equilibrium, taking moments about apex:

𝑀𝑀𝑃𝑃1 + 𝑀𝑀𝑃𝑃2 + 𝐻𝐻𝑅𝑅1 sinπœƒπœƒ +𝐹𝐹1𝑅𝑅1 cos πœƒπœƒ

2= 𝐹𝐹1𝑅𝑅1 cos πœƒπœƒ

Giving:

𝐻𝐻 =𝐹𝐹1𝑅𝑅1 cos πœƒπœƒ βˆ’ 2(𝑀𝑀𝑃𝑃1 + 𝑀𝑀𝑃𝑃2)

2𝑅𝑅1 sinπœƒπœƒ

And

𝐻𝐻𝑅𝑅 = 𝐻𝐻

Page 49: Plastic Design of Portal frame to Eurocode 3 · PDF filePlastic Design of Portal frame to Eurocode 3. Supporting Notes. ... EC3 requires that the second order effects are explicitly

44

For the column equilibrium, the base overturning moment given by:

𝑂𝑂𝑂𝑂𝑀𝑀 = π»π»π‘Œπ‘Œ + 𝐹𝐹1𝑋𝑋1 + 𝐻𝐻1𝑋𝑋1 + 𝑀𝑀𝑝𝑝1

Where:

R1 is the rafter length from end of hunch to apex including allowance for elongation R2 is the haunch length from center line of column. Y is the height of end of haunch

𝐸𝐸 cos𝛼𝛼 + 𝑅𝑅2 sin(πœƒπœƒπ‘œπ‘œ βˆ’ 𝛼𝛼) L is the span. E is the column height. πœƒπœƒπ‘œπ‘œ Is the initial rafter angle. X1 is the horizontal distance from column base to end of haunch

𝐸𝐸 sin𝛼𝛼 + 𝑅𝑅2 cosπœƒπœƒπ‘œπ‘œ βˆ’ 𝛼𝛼 X2 is the horizontal distance from the column base to the end of haunch

𝐸𝐸 sin𝛼𝛼 + 12𝑅𝑅2 cosπœƒπœƒπ‘œπ‘œ βˆ’ 𝛼𝛼.

Ξ‘ is the column deflection angle. Θ is rafter sag angle

cosβˆ’1 οΏ½π‘ˆπ‘ˆβˆ’2𝑋𝑋12𝑅𝑅1

οΏ½ For single bay frames

cosβˆ’1 οΏ½π‘ˆπ‘ˆβˆ’2𝑋𝑋1+𝐸𝐸 sin 𝛼𝛼2𝑅𝑅1

οΏ½ For multi bay frames

F1 is the vertical load on the rafter length R1 F2 is the vertical load on the rafter length R2 VR is the vertical reaction on the column base. HR is the horizontal reaction on column base. H is the resultant horizontal load in rafter. MP1 is the fire hinge moment at end of haunch. MP2 is the fire hinge moment at apex

Page 50: Plastic Design of Portal frame to Eurocode 3 · PDF filePlastic Design of Portal frame to Eurocode 3. Supporting Notes. ... EC3 requires that the second order effects are explicitly

45

D2) Tables

Table 5- Multiplication factors for multi-bay frame (BS EN 1993-1-1:2005)

Table 6- Frame geometry parameters A and C (Newman, Technical Report P313)

Page 51: Plastic Design of Portal frame to Eurocode 3 · PDF filePlastic Design of Portal frame to Eurocode 3. Supporting Notes. ... EC3 requires that the second order effects are explicitly

46

Table 7- Percentage dead weight of roof cladding systems remaining at the time of the

rafter collapse (Newman, Technical Report P313)

Page 52: Plastic Design of Portal frame to Eurocode 3 · PDF filePlastic Design of Portal frame to Eurocode 3. Supporting Notes. ... EC3 requires that the second order effects are explicitly

47

16 REFERENCE

The Southern African Institute of Steel Construction, Economics of Steel Structures. -

[s.l.] : The Southern African Institute of Steel Construction. - Vol. First Edition 2001.

Baddoo Nancy R. C EC3 - concise Eurocode 3 for the design of steel buildings in the United

Kingdom [Book]. - [s.l.] : Ascot : Steel Construction Institute, 1993 .

BS EN 1991-1-3:2003 Eurocode 1 β€” Actions on structures Part 1-3: General actions β€”

Snow loads [Book]. - 389 Chiswick High Road, London, W4 4AL : Standards, Institution

British.

BS EN 1993-1-1:2005 Eurocode 3: Design of steel structures BS EN 1993-1-1:2005 [Book]. -

389 Chiswick High Road, London, W4 4AL : Standards, Institution British.

BUREAU Alain Practical deflection limits for single storey buildings [Online] //

www.access-steel.com. - Access Steel, SN035a-EN-EU. - 15 October 2008.

Chaffotec P. Le Scheme development: Purlin structure design [Online] // www.access-

steel.com. - Access Steel, SS049a-EN-EU. - 15 November 2008.

Eur.Ing Eur Ing Structural Steel Design e-Learning Portal [Online] // http://www.n-

aktive.co.uk/. - Eur Ing Structural Steel Design e-Learning Portal. - 10 November 2008.

J.B.P.Lim C.M.King , A.J.Rathbone , J.M.Davies , V.Edmondson Eurocode 3 and the in-

plane stability of portal frames [Journal]. - [s.l.] : The Structure Engineering Journal,

November 2005. - p 43-49.

King C M Design of Steel Portal for Europe [Book]. - [s.l.] : The steel construction Institute,

Techhnnical Report P164.

King C M Plastic Design of Simgle-Storey Pitced-Roof Portal Frames to Eurocode 3

[Book]. - [s.l.] : The steel construction Institute, Techhnnical Report P147.

King Charles Flow chart: Plastic analysis of a portal frame [Online] // www.access-

steel.com. - Access Steel, SF019a-EN-EU. - 15 October 2008.

Malik SN051a-EN-EU A S, Scheme development: Details for portal frames using rolled

sections [Online] // www.access-steel.com. - Access Steel. - 20 October 2008.

Morris M.R. Horne and L.J. Plastic design of low-rise frames [Book]. - [s.l.] : London :

Granada, 1981.

Newman W I Simms and G M Single storey steel framed buildings in fire boundary

conditions [Book]. - [s.l.] : The steel construction Institute,, Thechnical Report P313.

Oppe Matthias Simple methods for second order effects in portal frames [Online] //

www.access-steel.com. - Access Steel, SN033a-EN-EU. - 15 October 2008.

Page 53: Plastic Design of Portal frame to Eurocode 3 · PDF filePlastic Design of Portal frame to Eurocode 3. Supporting Notes. ... EC3 requires that the second order effects are explicitly

48

Plum L J Morris & D R Structural Steelwrok Design to BS5950 2nd Edition [Book]. - [s.l.] :

Harlow : Longman, 1996.

The institutionof Structural Engineers Manual for the design of steelwork building

structures to Eurcode 3 [Book]. - TP/08/43 EC3/08/16.

Weare Alan Hayward and Frank Steel detailer's manual [Book]. - [s.l.] : Oxford : BSP

Professional, 1989.