Pipe Friction Factor Calculation http://www.pipeflow.com/pipe-pressure-drop-calculations/pipe-friction-factors#Colebrook_White[4/13/2015 12:12:32 PM] Friction Factor Calculations The Darcy-Weisbach equation, for calculating the friction loss in a pipe, uses a dimensionless value known as the friction factor (also known as the Darcy-Weisbach friction factor or the Moody friction factor) and it is four times larger than the Fanning friction factor. Friction Factor Chart / Moody Chart Friction Factor for Laminar Flow Critical Flow Condition Pipe Flow Software » Pipe Pressure Drop Calculations (0 items) Monday 13th April 2015 Search The friction factor or Moody chart is the plot of the relative roughness (e/D) of a pipe against the Reynold's number. The blue lines plot the friction factor for flow in the wholly turbulent region of the chart, while the straight black line plots the friction factor for flow in the wholly laminar region of the chart. In 1944, LF Moody plotted the data from the Colebrook equation and the resulting chart became known as The Moody Chart or sometimes the Friction Factor Chart. It was this chart which first enabled the user to obtain a reasonably accurate friction factor for turbulent flow conditions, based on the Reynolds number and the Relative Roughness of the pipe. The friction factor for laminar flow is calculated by dividing 64 by the Reynold's number. Friction factor (for laminar flow) = 64 / Re When flow occurs between the Laminar and Turbulent flow conditions (Re 2300 to Re

Pipe Friction Factor Calculation2

Embed Size (px)

DESCRIPTION

Pipe Friction Factor

Citation preview

Page 1: Pipe Friction Factor Calculation2

Pipe Friction Factor Calculation

http://www.pipeflow.com/pipe-pressure-drop-calculations/pipe-friction-factors#Colebrook_White[4/13/2015 12:12:32 PM]

Friction Factor Calculations The Darcy-Weisbach equation, for calculating the friction loss in a pipe, uses a dimensionless value known as the friction factor (also known as the Darcy-Weisbach friction factor or the Moody friction factor) and it is four times larger than the Fanning friction factor.

Friction Factor Chart / Moody Chart

Friction Factor for Laminar Flow

Critical Flow Condition

Pipe Flow Software » Pipe Pressure Drop Calculations » Friction Factors

(0 items)

Monday 13th April 2015

Search

The friction factor or Moody chart is the plot of the relative roughness (e/D) of a pipe against the Reynold's number. The blue lines plot the friction factor for flow in the wholly turbulent region of the chart, while the straight black line plots the friction factor for flow in the wholly laminar region of the chart.

In 1944, LF Moody plotted the data from the Colebrook equation and the resulting chart became known as The Moody Chart or sometimes the Friction Factor Chart. It was this chart which first enabled the user to obtain a reasonably accurate friction factor for turbulent flow conditions, based on the Reynolds number and the Relative Roughness of the pipe.

The friction factor for laminar flow is calculated by dividing 64 by the Reynold's number.

Friction factor (for laminar flow) = 64 / Re

When flow occurs between the Laminar and Turbulent flow conditions (Re 2300 to Re

Page 2: Pipe Friction Factor Calculation2

Pipe Friction Factor Calculation

http://www.pipeflow.com/pipe-pressure-drop-calculations/pipe-friction-factors#Colebrook_White[4/13/2015 12:12:32 PM]

Friction Factor for Turbulent Flow

Colebrook-White Equation

Pipe Flow Software Pipe Flow Expert Software Pipe Flow Wizard Software Pipe Flow Advisor Software

Convert 123 Software

Customer Testimonials

Common FAQs

Who Uses Our Software

Software Downloads

How to Buy Software Online Get Software License Code

Software Videos

Technical Documents

Pipe Pressure Drop Calculations

Fluid Density Fluid Viscosity Laminar & Turbulent Flow Pipe Roughness

Reynold's Numbers Friction Factors Pipe Friction Loss Pipe Fitting Losses

Component Losses Elevation Changes

News & Press Releases

About Pipe Flow Software

Contact Us

4000) the flow condition is known as critical and is difficult to predict. Here the flow is neither wholly laminar nor wholly turbulent. It is a combination of the two flow conditions.

The friction factor for turbulent flow is calculated using the Colebrook-White equation:

Due to the implicit formation of the Colebrook-White equation, calculation of the friction factor requires an iterative solution via numerical methods.

The friction factor is then used in the Darcy-Weisbach formula to calculate the fluid frictional loss in a pipe.

Secure Online Payments

Page 3: Pipe Friction Factor Calculation2

Pipe Friction Factor Calculation

http://www.pipeflow.com/pipe-pressure-drop-calculations/pipe-friction-factors#Colebrook_White[4/13/2015 12:12:32 PM]

About Pipe FlowPipeFlow.comWho Uses Our SoftwareCustomer TestimonialsHow To Buy OnlinePipe Pressure Drop Calculations TheorySite Map

Pipe Flow ExpertPipe Flow ExpertPipe Design CalculationsSoftware ScreenshotsExample SystemsSoftware DocumentationSoftware Videos

Pipe Flow WizardPipe Flow WizardPressure Drop CalculatorFlow Rate CalculatorPipe Diameter CalculatorPipe Length Calculator

Pipe Flow AdvisorPipe Flow AdvisorChannel Flow CalculatorWeir Flow CalculatorTank Emptying TimeTank Volume Calculator

Pipe Flow Software: Piping design, Pressure drop calculator, Flow rate calculator, Pump head calculations, Pump selection software. Copyright © Pipe Flow Software 2015