Phasors in New Zealand NASPI February 2013 Transpower: Victor Lo, Richard Sherry OSIsoft: Ann Moore

Phasors in New Zealand - naspi. · PDF fileJoined by HVDC (1200MW). Long and skinny, ... • MATLAB link . 1. PI (OSIsoft) ... Monitoring SVC performance during grid faults -100.000

Embed Size (px)

Citation preview

Page 1: Phasors in New Zealand - naspi. · PDF fileJoined by HVDC (1200MW). Long and skinny, ... • MATLAB link . 1. PI (OSIsoft) ... Monitoring SVC performance during grid faults -100.000

Phasors in New Zealand

NASPI February 2013

Transpower: Victor Lo, Richard Sherry OSIsoft: Ann Moore

Page 2: Phasors in New Zealand - naspi. · PDF fileJoined by HVDC (1200MW). Long and skinny, ... • MATLAB link . 1. PI (OSIsoft) ... Monitoring SVC performance during grid faults -100.000

New Zealand Grid

Two 50Hz asynchronous systems - North and South Island Joined by HVDC (1200MW). Long and skinny, high impedance, 220kV, 110kV, 66kV

South: Hydro, Wind

North: Hydro, Thermal, Wind

4500MW

2200MW

Page 3: Phasors in New Zealand - naspi. · PDF fileJoined by HVDC (1200MW). Long and skinny, ... • MATLAB link . 1. PI (OSIsoft) ... Monitoring SVC performance during grid faults -100.000

Why Phasors?

• Situational awareness

• Early warning on emerging stability issues

• Monitor equipment performance

• Validate power system models

Page 4: Phasors in New Zealand - naspi. · PDF fileJoined by HVDC (1200MW). Long and skinny, ... • MATLAB link . 1. PI (OSIsoft) ... Monitoring SVC performance during grid faults -100.000

PMU Locations (14) North Island

1. Otahuhu (Gen & Load) 2. Huntly (Gen) 3. Whakamaru (Gen) 4. Stratford (Gen) 5. Bunnythorpe 6. Haywards (HVDC terminal) 7. Westwind (Windfarm)

South Island 1. Kikiwa (STATCOM) 2. Islington (SVC & Load) 3. Twizel (Gen) 4. Benmore (HVDC terminal) 5. Roxburgh (Gen) 6. Tiwai (Smelter) 7. North Makarewa

Page 5: Phasors in New Zealand - naspi. · PDF fileJoined by HVDC (1200MW). Long and skinny, ... • MATLAB link . 1. PI (OSIsoft) ... Monitoring SVC performance during grid faults -100.000

Phasor measurements • Synchronised recording of phasor data – time

stamped by GPS clock

• Real Time measurement of 3 phase Voltage & Current – both magnitude and phase angle

• Sampled 50 times per second (50 Hz is nominal system frequency)

• Phasors are extracted from our protection relays

Page 6: Phasors in New Zealand - naspi. · PDF fileJoined by HVDC (1200MW). Long and skinny, ... • MATLAB link . 1. PI (OSIsoft) ... Monitoring SVC performance during grid faults -100.000

Data access 1. PI (OSIsoft) – Main data source

SCADA, PMUs, protection logs, system logs, etc.

2. Psymetrix – Phasor-only data source

Real-time monitoring and alarms Oscillation frequency, damping (stability) Locus plots Monthly system stability reports

Page 7: Phasors in New Zealand - naspi. · PDF fileJoined by HVDC (1200MW). Long and skinny, ... • MATLAB link . 1. PI (OSIsoft) ... Monitoring SVC performance during grid faults -100.000

1. PI (OSIsoft) data access • Main data source with SCADA, PMU, logs, etc.

• Screens • EXCEL link • MATLAB link

Page 8: Phasors in New Zealand - naspi. · PDF fileJoined by HVDC (1200MW). Long and skinny, ... • MATLAB link . 1. PI (OSIsoft) ... Monitoring SVC performance during grid faults -100.000

1. PI (OSIsoft) data access

Page 9: Phasors in New Zealand - naspi. · PDF fileJoined by HVDC (1200MW). Long and skinny, ... • MATLAB link . 1. PI (OSIsoft) ... Monitoring SVC performance during grid faults -100.000

1. PI (OSIsoft) data access

Custom screens are relatively easy to make

Page 10: Phasors in New Zealand - naspi. · PDF fileJoined by HVDC (1200MW). Long and skinny, ... • MATLAB link . 1. PI (OSIsoft) ... Monitoring SVC performance during grid faults -100.000

2. Psymetrix data access • More specialized phasor applications.

• Real time monitoring, eg alarms • Oscillations (freq and decay), locus plots

Alarms

Page 11: Phasors in New Zealand - naspi. · PDF fileJoined by HVDC (1200MW). Long and skinny, ... • MATLAB link . 1. PI (OSIsoft) ... Monitoring SVC performance during grid faults -100.000

PMU Usage • An investigation tool (not used in real time

operations) • Event analysis • Power system model validation • Monitoring oscillations (Psymetrix)

Page 12: Phasors in New Zealand - naspi. · PDF fileJoined by HVDC (1200MW). Long and skinny, ... • MATLAB link . 1. PI (OSIsoft) ... Monitoring SVC performance during grid faults -100.000

System Under-frequency event

6.5Hz oscillation “Generator Pole

slipping”

Page 13: Phasors in New Zealand - naspi. · PDF fileJoined by HVDC (1200MW). Long and skinny, ... • MATLAB link . 1. PI (OSIsoft) ... Monitoring SVC performance during grid faults -100.000

Monitoring SVC performance during grid faults

-100.000

-50.000

0.000

50.000

100.000

150.000

200.000

200.000

205.000

210.000

215.000

220.000

225.000

230.000

235.000

240.000

245.000

250.000

36:0

9 AM

36:0

9 AM

36:0

9 AM

36:0

9 AM

36:0

9 AM

36:1

0 AM

36:1

0 AM

36:1

0 AM

36:1

0 AM

SVC

(M

var)

Islin

gton

220

kV

bus

volta

ge (k

V)

Page 14: Phasors in New Zealand - naspi. · PDF fileJoined by HVDC (1200MW). Long and skinny, ... • MATLAB link . 1. PI (OSIsoft) ... Monitoring SVC performance during grid faults -100.000

Undampped Oscillation in South Island (with mainly Hydro)

15MW

1.5Hz

Page 15: Phasors in New Zealand - naspi. · PDF fileJoined by HVDC (1200MW). Long and skinny, ... • MATLAB link . 1. PI (OSIsoft) ... Monitoring SVC performance during grid faults -100.000

Phasors, to finish… • 14 PMU sites give good grid coverage • Plans to add 2 new sites at top of North Island • Used for investigations:

• Fault analysis, oscillation monitoring • Model validation • Equipment monitoring

• Storage / Data processing with PI & Psymetrix • Developing more uses as time goes on, e.g.

Anti-islanding detection