Upload
others
View
7
Download
0
Embed Size (px)
Citation preview
NA60 - flayer - 08 - 2006
ApplicationThe relay type NA60 can be typically used in radial or meshed MV and LV networks as feeder or power transformer protection:
on radial, ring and parallel feeders of any length in solidly grounded, ungrounded, Petersen coil and/or resistance grounded systems,on parallel connected generators on the same busbar.
Moreover undervoltage and overvoltage functions are provided as protections or voltage controls.
Protective functions27 Undervoltage49 Thermal image50/51 Phase overcurrent50N/51N Residual overcurrent59 Overvoltage59N Residual overvoltage67 Directional overcurrent67N Directional ground faultBf Circuit breaker failure
•
•
Measuring inputsThree phase current inputs and one residual current input, with nominal currents independently selectable at 1A or 5A through DIP-switches.Three phase voltage inputs with programmable nominal voltag-es within range 50...130 V (UR=100V) or 200...520 V (UR=400V) and one residual voltage input, with programmable nominal voltage within range 50...130 V (UER=100V).
ConstructionAccording to the hardware configurations, the NA60 protection relay can be shipped in various case styles depending on the required mounting options (flush, projecting mounting, rack or with separate operator panel).
•
•
phase & res idual overcurrent, phase & G round d irect ional , t h e r m a l i m a G e , u n d e r / o v e r v o lta G e p r o t e c t i o n r e l ay
50N 51N
49 50 51 74CT
52
74TCS BF
67N
METERING- IL1..IL3,IθL1..,IE,UE,ϕE..- Oscillography
COMMUNICATION- RS232- Modbus RS485- Modbus TCP/IP- IEC 870-5-103
Control functions & Logic selectivity
NA60
59N
67
74VT5927
NA60 - flayer - 08 - 2006 2
Control and monitoringSeveral predefined functions are implemented:
Activation of two set point profilesPhase CTs monitoring (74CT)Phase VTs monitoring (74VT)Logic selectivityCold load pickup (CLP) with block or setting changeTrip circuit supervision (74TCS)Second harmonic restraint (inrush)Remote trippingSynchronizationCB commands and diagnostic
Firmware updatingThe use of flash memory units allows on-site firmware updating.
MeteringNA60 provides metering values for phase and residual currents and residual voltage, making them available for reading on a dis-play or to communication interfaces.Input signals are sampled 24 times per period and the RMS value of the fundamental component is measured using the DfT (Dis-crete fourier Transform) algorithm and digital filtering.With DfT the RMS value of 2nd, 3rd, 4th and 5th harmonic of phase current are also measured.On the base of the direct measurements of the phase currents, the minimum-peak-fixed-rolling demand, mean-minimum-maxi-mum absolute phase currents are processed.The measured signals can be displayed with reference to nomi-nal values or directly expressed in Ampères and Volts.
Setting safetyTwo session level (User or Administrator) with password for sen-sible data access.
Logic selectivityWith the aim of providing a selective protection system, some protective functions may be blocked (pilot wire accelerated log-ic). To guarantee maximum fail-safety, the relay performs a run time monitoring for pilot wire continuity and pilot wire shorting. for long distances, when high insulation and high EMC immunity is essential, a suitable pilot wire to fiber optic converter (BfO) is available.
••••••••••
Modular designIn order to extend I/O capability, the NA60 hardware can be cus-tomized through external auxiliary modules:
output relays and LEDsbinary inputsblocking signals (logic selectivity)4...20 mA converters.
Fault recording (Oscillography)Upon trigger of tripping/starting of each function or external signals, the relay records in COMTRADE format more than 300 events with 1 ms acquisition rate and 0.5 s recording time (0.25 pre fault time).
CommunicationMultiple communication interfaces are implemented:
a RS232 local communication front-end interface, used for protection management, viewing and changing the relay pro-gramming, obtaining readings of the logic states, the chrono-logical events, measuring, and for relay testing and resetting commands;two back-end interfaces for communication with remote moni-toring and control systems by:- RS485 using ModBus® RTU or IEC 60870-5-103 protocol,- Ethernet port (RJ45 or optical fiber) using ModBus/TCP protocol.
••••
•
•
BLOUTS1
S3
S2
BLIN(S3)
BLIN(S2)
NA10
NA60 NA60 NA60 NA60NA60NA60
NA60 NA60
NA60
NA10NA10
Ring main logic selectivity
NA60 - flayer - 08 - 2006 3
MMI (Man Machine Interface)The user interface comprises a membrane keyboard, a backlight LCD alphanumeric display and eight LEDs.The green ON LED indicates auxiliary power supply and self di-agnostics, two LEDs are dedicated to the Start and Trip (yellow for Start, red for Trip) and five red LEDs are user assignable.
Binary inputsTwo binary inputs are available with programmable active state (active-ON/active-Off) and programmable timer (active to Off/ON or ON/Off transitions).Several presettable functions can be associated to each input.
Cold Load Pickup (CLP)To prevent unwanted tripping of the protective functions on tem-porary overcurrent (i.e. load startings), the CLP function can be used with two different operating modes:
each threshold can be blocked for a programmable timeeach threshold can be changed for a programmable time.
Programming and settingsAll relay programming and adjustment operations may be per-formed through MMI (Keyboard and display) or using a Personal Computer with the aid of the ThySetter software.
••
Output relaysSix output relays are available (two changeover and four make contacts); each relay may be individually programmed as nor-mal state (normally energized, de-energized or pulse) and reset mode (manual or automatic). A programmable timer is provided for each relay (minimum ac-tivation time).The user may program the function of each final relay in accor-dance with a matrix (tripping matrix) structure.
Circuit BreakerSeveral diagnostic, monitoring and control functions are provided:
health thresholds can be set; when the accumulated duty (SI or SI2) or the number of opening operations exceeds the threshold an alarm is activatedtrip time (mechanism); if the trip time is too long, a diagnostic alarm is issuedposition; if a 52a-52b discrepancy is detected, the relative alarm goes ONbreaker failure (Bf); breaker status is monitored by means 52a-52b and/or through line current measurementsbreaker control; opening and closing commands can be car-ried out locally or remotelytrip circuit supervision (74TCS).
Second harmonic restraintTo prevent unwanted tripping of the protective functions on transformer inrush current, the protective elements can be blocked when the ratio between the second harmonic current and the relative fundamental current is larger than a setting threshold.The function can be programmed to switch an output relay so as to cause a blocking protection relays lacking in second har-monic restraint.
Self diagnosticsAll hardware and software functions are repeatedly checked and any anomalies reported via display messages, communica-tion interfaces, LEDs and output relays. Anomalies may refer to:
hw faults (auxiliary power supply, output relay coil interrup-tions, MMI board...)sw faults (boot and run time tests for data base, EEPROM memory checksum failure, data BUS,...)
• pilot wire faults (break or short in the wire)• Circuit breaker faults.
•
•
•
•
•
•
•
•
ThySetter
NA60 - flayer - 08 - 2006 4
S P E C I f I C A T I O N S GENERAL
Mechanical dataMounting: flush, projecting, rack or separated operator panelMass (flush mounting case) 2.0 kg Insulation testsReference standards EN60255-5High voltage test 50Hz 2 kV 60s Impulse voltage withstand (1.2/50 ms) 5 kVInsulation resistance >100 MW Voltage dip and interruptionReference standards EN61000-4-29 EMC tests for interference immunity1 MHz damped oscillatory wave EN60255-22-1 1 kV-2.5 kVHigh energy pulse EN61000-4-5 2 kV-400 ADamped oscillatory wave EN61000-4-12 2.5 kVRing wave EN61000-4-12 2 kVfast transient burst (5/50 ns) EN60255-22-4 4 kVConducted common mode EN61000-4-16 30 VElectrostatic discharge EN60255-22-2 8 kVMagnetic field 50 Hz EN61000-4-8 1 kA/mConducted radio-frequency fields EN60255-22-6 10 VRadiated radio-frequency fields EN60255-4-3 10 V/m EmissionReference standards EN61000-6-4 (ex EN50081-2)Conducted emission 0.15...30 MHz Class ARadiated emission 30...1000 MHz Class A Climatic testsReference standards IEC60068-x, ENEL R CLI 01, CEI 50 Mechanical testsReference standards EN60255-21-1, 21-2, 21-3
Safety requirementsReference standards EN61010-1Pollution degree 3Reference voltage 250 VOvervoltage IIIPulse voltage 5 kVReference standards EN60529Protection degree: - front side IP51 - rear side, connection terminals IP20
Environmental conditions Ambient temperature -25...+55 °CStorage temperature -40...+85 °CRelative umidity 10...95 %Atmospheric pressure 70...110 kPa
CertificationsCE conformity- Product standard for measuring relays EN50263 EMC Directive 89/336/EEC Low Voltage Directive 73/23/EEC
- Type tests IEC 60255-6
INPuT CIRCuITS
Auxiliary power supply uauxNominal value 24...48 Vac/dc 115...230 Vac/110...220 VdcRange (each one of the above nominal values) 19...60 Vac/dc 85...265 Vac/75...300 VdcPower consumption: - maximum (energized relays, Ethernet TX) 10 W (20 VA) - maximum (energized relays, Ethernet fX) 15 W (25 VA) Phase current inputsNominal current I N 1 A or 5 A selectable by DIP SwitchesPermanent overload 20 AThermal overload (1s) 500 ARated consumption (for any phase) ≤ 0.2 VA
Residual current inputNominal current I EN 1 A or 5 A selectable by DIP SwitchPermanent overload 25 AThermal overload (1s) 500 ARated consumption ≤ 0.2 VA Voltage inputsReference voltage U R 100 V or 400 V selectable on orderNominal voltage U N 50...130 V or 200...520 V selectable by swPermanent overload 2 U R1s overload 2 URRated consumption (for any phase) ≤ 0.5 VA Residual voltage inputReference voltage U ER 100 VNominal voltage U EN 50...130 V selectable by swPermanent overload 2 U ER1s overload 2 U ERRated consumption ≤ 0.5 VA
Binary inputsQuantity 2 Type wet inputsMax permissible voltage 19...265 Vac/19...300 VdcMax consumption, energized 3 mA
Block input (Logic selectivity)Quantity 1Type dry inputs (powered by internal isolated supply) Max consumption, energized 5 mA
OuTPuT CIRCuITS
Output relays K1...K6 Quantity 6- type of contacts K1, K2 changeover (SPDT, type C) - type of contacts K3, K4, K5 make (SPST-NO, type A) - type of contacts K6 break (SPST-NC, type B)Nominal current 5 ANominal voltage 250 VBreaking capacity:- direct current (L/R = 40 ms) 30 VA - alternating current (l = 0,4) 40 W Make 1000 W/VAShort duration current (0,5 s) 15 A Block output (Logic selectivity)Quantity 1Type optocoupler
LEDsQuantity 8- ON/fail (green) 1- Start (yellow) 1- Trip (red) 1- Allocatable (red) 5
NA60 - flayer - 08 - 2006 5
COMMuNICATION INTERFACES
Local PC RS232 19200 bps Network: - RS485 1200...57600 bps - Ethernet 100BaseT 100 Mbps Protocol ModBus® RTU-TCP/IP IEC 60870-5-103
GENERAL SETTINGS
Nominal valuesPhase nominal current I N 1A, 5APhase CTs nominal primary current I NP 1A...10 kAResidual nominal current I EN 1A, 5AResidual CT nominal primary current I ENP 1A...10 kANominal voltage U N 50...130V or 200...520VPhase VTs nominal primary voltage U NP 50V...500 kVResidual nominal voltage U EN 50...130VResidual VT nominal primary voltage U ENP 50V...500 kVNominal frequency f N 50, 60 Hz
CB diagnosticOperation counts 0...10000Contact interrupting duty SI 0...5000 INTrip time (SI2t evaluation) 0.050...1.000 sContact interrupting duty SI2t 0...5000 (IN)2.sCB discrepancy time 0.010...10.000 sTrip time (mechanism) 0.050...1.000 s
CLP (Cold Load Pickup)CB trip delay time t CBCLP 0.000...1.000 s
Binary input timersBinary inputs ON delay time t IN1ON, t IN2ON 0.00...100.0 sBinary inputs Off delay time t IN1Off, t IN2Off 0.00...100.0 s
Output relay timersK1...K6 minimum activation time t TR1... t TR6 0.00...500.0 s
FuNCTIONS
undervoltage (27)Pickup U< (definite-time characteristic) 0.30...1.20 UNTime delay tU< (definite-time characteristic) 0.05...200 s Overvoltage (59)Pickup U>, U>> (definite-time characteristic) 0.60...1.20 UNTime delays tU>, tU>> (definite-time characteristic) 0.05...200 s Thermal image (49)Base current IB 0.10...2.00 INPickup Dq> 1.2 DqBAlarm Pickup DqAL1 0.3...1.0 DqBAlarm Pickup DqAL2 0.3...1.0 DqBInitial thermal imageDqIN 0.0...1.0 DqBOverload coefficient at starting KINR 1.0...3.0Thermal time constant t 1...200 min
Phase overcurrent (50/51)Pickup I> (definite-time characteristic) 0.100...10.00 INTime delay t > (definite-time characteristic) 0.03...200 sPickup I> (IEC A,B,C,I2t inverse-time) 0.100...10.00 INTime delay t > (IEC A,B,C,I2t inverse-time) 0.10...60.0 sPickup I>CLP 0.100...10.00 INTime delay t >CLP 0.03...100 sPickup I>> (definite-time characteristic) 0.100...40.0 IN Time delay t >> (definite-time characteristic) 0.03...10.00 sPickup I>> (I2t inverse-time characteristic) 0.100...20.0 INTime delay t >> (I2t inverse-time characteristic) 0.03...10.00 sPickup I>>CLP 0.100...40.0 INTime delay t >>CLP 0.03...100 sPickup I>>> (definite-time characteristic) 0.100...40.0 INTime delay t >>> (definite-time characteristic) 0.03...10.00 sPickup I>CLP 0.100...40.0 INTime delay t >>>CLP 0.03...100 s
Residual overcurrent (50N/51N)Pickup IE> (definite-time characteristic) 0.002...2.00 IENTime delay tE> (definite-time characteristic) 0.03...200 sPickup IE> (IEC A,B,C inverse-time) 0.002...2.00 IENTime delay tE> (IEC A,B,C inverse-time) 0.10...60.0 sPickup IE>CLP 0.002...2.00 IENTime delay tE>CLP 0.03...100 sPickup IE>> (definite-time characteristic) 0.002...8.00 IENTime delay tE>> (definite-time characteristic) 0.03...10.0 sPickup IE>>CLP 0.002...8.00 IENTime delay tE>>CLP 0.03...100 sPickup IE>>> (definite-time characteristic) 0.002...8.00 IENTime delay tE>> (definite-time characteristic) 0.03...10.0 sPickup IE>>>CLP 0.002...8.00 IENTime delay tE>>>CLP 0.03...100 s Residual overvoltage (59N)Pickup UE>, UE>> (definite-time characteristic) 0.01...0.20 UENTime delays tUE>, tUE> (definite-time characteristic) 0.05...200 s
Directional phase overcurrent (67)Characteristic angle q 0...90°Pickup Iq> (definite-time characteristic) 0.100...10.00 I NTime delay tq> (definite-time characteristic) 0.05...200 sPickup Iq> (IEC A,B,C,I2t inverse-time) 0.100...10.00 I NTime delay tq> (IEC A,B,C,I2t inverse-time)) 0.10...60.0 sPickup Iq>CLP 0.100...10.00 INTime delay tq> CLP 0.03...100 sPickup Iq>> 0.100...40.00 I NTime delay tq>> (definite-time characteristic) 0.03...10.0 sPickup Iq>>CLP 0.100...40.0 INTime delay tq>>CLP 0.03...100 sPickup Iq>>> 0.100...40.00 I NTime delay tq>>> (definite-time characteristic) 0.03...10.0 sPickup Iq>>CLP 0.100...40.0 INTime delay tq>>CLP 0.03...100 s Directional earth fault overcurrent (67N)Pickup I ED> (definite-time characteristic) 0.002...10.00 IENTime delay tED> (definite-time characteristic) 0.03...200 sPickup I ED> (IEC A,B,C inverse-time) 0.002...10.00 I ENTime delay tED> (inverse-time characteristic) 0.10...60.0 sPickup U ED> 0.004...0.500 U ENCharacteristic angle qE> 0...359 °Maximum deviation from the characteristic angle b> 0...180°Pickup I ED>> 0.002...10.00 IENTime delay tED>> (definite-time characteristic) 0.05...200 sPickup U ED>> 0.004...0.500 U ENCharacteristic angle qE>> 0...359 °Maximum deviation from the characteristic angle b>> 0...180°Pickup I ED>>> 0.002...10.00 IENTime delay tED>>> (definite-time characteristic) 0.05...200 sPickup U ED>>> 0.004...0.500 U ENCharacteristic angle qE>>> 0...359 °Maximum deviation from the characteristic angle b>>> 0...180°
Breaker failure (BF)Pickup IBf> 0.05...1.00 INPickup IEBf> 0.002..2.00 IENTime delay t Bf (definite-time characteristic) 0.01...10.00 s52a/52b mode 52a or 52b
CT monitoring (74CT)Pickup S< (ILMIN/ ILMAX) 0.10...0.95Pickup I*> 0.10..1.00 INTime delay t S (definite-time characteristic) 0.03...200 s
VT monitoring (74VT)Pickup U2VT> 0.05..0.50 UNPickup I2VT> 0.05..0.50 INPickup U VT< 0.05..0.50 UNPickup U VT> 0.05..0.50 UNPickup D IVT< 0.05..0.50 INPickup IVT> 0.10..40.0 INTime delay t VT-AL (definite-time characteristic) 0.0...10.0 s
NA60 - flayer - 08 - 2006 6
Logic selectivity50/51 block out drop-out time delay tfI> 0.00...1.00 s50N/51N block out drop-out time delay tfI E> 0.00...1.00 s50/51 block in drop-out time delay tBI> 0.10...10.00 s50N/51N block in drop-out time delay tBI E> 0.10...10.00 sOutput pulse repetition period 0.05-0,1-1-10-30 sInput pulse window 0.05-0,1-1-10-30 s
Second harmonic restraintI2NDH> (I2nd /IL) 0.10...0.50
METERING
Measured parametersPhase currents:
fundamental RMS values IL1, IL2, IL3 2nd harmonic components IL1-2nd, IL2-2nd, IL3-2nd3rd harmonic components IL1-3rd, IL2-3rd, IL3-3rd4th harmonic components IL1-4th, IL2-4th, IL3-4th5th harmonic components IL1-5th, IL2-5th, IL3-5thEquivalent thermal current IthPositive and negative sequence values I1, I2Directional components of input currents IqL1, IqL2 IqL3Thermal image DqPeak demand RMS values IL1MAX, IL2MAX, IL3MAXMinimum demand RMS values IL1MIN, IL2MIN, IL3MINfixed demand RMS values IL1fIX, IL2fIX, IL3fIXRolling demand RMS values IL1ROL, IL2ROL, IL3ROLMean (IL1+IL2+IL3)/3 ILMax RMS value ILMAXMin RMS value ILMIN
Residual currentfundamental RMS value IE3rd harmonic component IE-3rdphase displacement between residual voltage and current jE
Voltages:fundamental phase-to-earth RMS values UL1, UL2, UL3 fundamental phase-to-phase RMS values U12, U23, U31fundamental residual RMS value UENegative sequence value U2
frequency f
••••••••••••••••
•••
••••
Oscillographyfile format COMTRADERecords >300 [1]Recording mode linearSampling rate <1 msTrigger setup:
source binary input communication (ThySetter) outputs (K1...K6)
pre-trigger time 0.05...1.00 spost-trigger time 0.05...60.00 s
Data recorded on sampled channels: instantaneous currents iL1, iL2, iL3, iEinstantaneous voltages uL1, uL2, uL3, uE
Data recorded on analog channels: frequency fRMS currents IL1, IL2, IL3, IE, I1,I2, IqL1, IqL2 IqL3second harmonic RMS currents IL1-2nd, IL2-2nd, IL3-2ndRMS voltages UL1, UL2, UL3, U12, U23, U31, UE, U2
Data recorded on digital channels: output relays K1...K6binary inputs IN1, IN2
Note 1: pre-trigger time 0.25 spost-trigger time 0.25 sTotal recording time 0.5 s
•
••
••
••••
••
•••
Fault recording
NA60 - flayer - 08 - 2006 7
Connection diagram example
NA60
OUTP
UT R
ELAY
S
NA60-SCH.ai
UAUXA1 ≅
A2
A9
A10
A11A12
A13
A14
E1
THYB
US
D1
ETHE
RNET
A3A4A5A6A7A8
K2
K3
K4
K5
K6
K1
RS23
2 FRONTPANEL
RS48
5
F1F2F3F4F5A+
B-
BLOC
K OU
T
A15BLOUT-
BLOUT+ A16
UE
UL1
UL2
UL3
BIN
ARY
INPU
TSA19IN1
IN2
A20A21A22
VOLT
AGE
INPU
TS
R (*)
(*) ANTIFERRORESONANCE
da
dn
n
a
N
A
L1L2L3
67, 6
7NOP
ERAT
ION
BLOC
K INA17
A18
C1IL1
IL2
IL3
IE
CURR
ENT
INPU
TS
P1S1S2
P2
P1S1S2
P2
C2C3
C4C5
C6
C7
C8
B7
B8
B5
B6
B3
B4
B1
B2
Headquarters: 20139 Milano - Piazza Mistral, 7 - Tel. +39 02 574 957 01 ra - fax +39 02 574 037 63Factory: 35127 Padova - Z.I. Sud - Via dell’Artigianato, 48 - Tel. +39 049 894 770 1 ra - fax +39 049 870 139 0
www.thytronic.it - [email protected] - www.pro-n.it
D I M E N S I O N S
FRONT VIEWS
FLUSH MOUNTING PANEL CUTOUT
N.4 HOLES ø 3,5
REAR VIEWS
SIDE VIEWS
FLUSH MOUNTING PROJECTING MOUNTING PROJECTING MOUNTING
PROJECTING MOUNTING
FLUSH MOUNTING(Separate operator panel)
PROJECTING MOUNTING(Separate operator panel) (Stand alone)
SEPARATE OPERATOR PANELFLUSH MOUNTING
212.5 275
ON 321 54
TRIP
START
120
ON 41 32 5
TRIP
START
107
177
205
149
F1
D1
RX
TX
F2F3F4F5
A1A2
A3A4A5
A6A7A8
A9A10A11
A12A13A14
A15A16
A17A18
A19A20
A21A22
B1B2B3B4B5B6B7B8
C1 C2
C4C3
C5 C6
C7 C8
E1
101
171
8031
F1
D1
RX
TX
F2F3F4F5
A1A2
A3A4A5
A6A7A8
A9A10A11
A12A13A14
A15A16
A17A18
A19A20
A21A22
B1B2B3B4B5B6B7B8
C1 C2
C4C3
C5 C6
C7 C8
E1
128.5110
200
168
20
3030 5 10370
161
154
170