PGS1000 kVA

Embed Size (px)

Citation preview

  • 8/10/2019 PGS1000 kVA

    1/6

  • 8/10/2019 PGS1000 kVA

    2/6

    STANDBY 800 ekW 1000 kVA50 Hz 1500 rpm 400 Volts

    FACTORY INSTALLED STANDARD & OPTIONAL EQUIPMENT

    System Standard OptionalAir Inlet Single element canister type air cleaner (with

    pre-cleaners)

    Service indicator

    Dual element & heavy duty air cleaners

    Air inlet adapters & shutoff

    Cooling Radiator with guard (43C)

    Low Profile (frontal area)

    Low Airflow

    Coolant drain line with valve

    Fan and belt guards

    Caterpillar Extended Life Coolant*

    Coolant level sensors*

    Radiator duct flange

    *Not included with packages without radiators

    Radiator with 27C and 50C ambient capability

    Radiant option for 57C ambient with treated water

    Radiator removal

    Heavy duty, harsh environment radiator at 43C and

    50C

    Heat exchanger and expansion tank

    Coolant level switch gauge

    Jacket water heater

    Exhaust Dry exhaust manifold

    Flanged faced outlets

    Mufflers & Silencers

    Stainless steel exhaust flex fittings

    Elbows, flanges, expanders & Y adapters

    Fuel Secondary fuel filters

    Fuel priming pump

    Flexible fuel lines

    Fuel cooler**Not included on packages without radiators

    Water separator

    Duplex fuel filter

    Generator Permanent magnet excited

    Class H insulation

    Class F temperature (105C prime/130C standby)

    Reactive droop

    Digital Voltage Regulator, 3-phase sensing

    Bus bar connections

    Winding temperature detectors

    Anti-condensation space heaters

    Digital Voltage Regulator with KVAR/PF control

    Bearing temperature detectors

    Oversize, premium & self-excited generators

    Cable access box

    European bus bars

    Circuit breakers, UL listed, 3 pole with shunt trip (low

    & medium voltage only)

    Circuit breakers, IEC compliant, 3 pole with shunt trip

    (low & medium voltage only)

    Space heater relay

    Power Termination Bus bar (NEMA and IEC mechanical lug holes)

    -right side standard

    Top and bottom cable entry

    Circuit breakers, UL listed, 3 pole with shunt trip, 80%

    or 100% rated, choice of trip units, manual or

    electrically operated (low voltage only)

    Circuit breakers, IEC compliant, 3 or 4 pole with shunttrip (low voltage only), choice of trip units, manual or

    electrically operted

    Shroud cover for bottom cable entry

    Power terminations can be located on the left and/or

    rear as an option. Also, multiple circuit breakers can

    be ordered. (up to 3)

    Governor Woodward 2301A isochronous Electronic load sharing

    Control Panels User Interface panel (UIP) - rear mount

    EMCP 3.1 Genset Controller

    Speed adjust

    AC&DC customer wiring area (right side)

    CAT digital voltage regulator (CDVR) with KVAR/PF

    control,3-phase sensing

    Reactive droop Emergency Stop Pushbutton

    EMCP3.3

    Option for right or left mount UIP

    Option for rear or left mount Customer wiring area

    Voltage Adjust

    Local and remote annunciator modules

    Load share module

    Discrete I/O module Generator temperature monitoring & protection

    Lube Lubricating oil and filter

    Oil drain line with valves

    Fumes disposal

    Gear type lube oil pump

    Deep sump oil pan

    Electric & air prelube pumps

    Manual prelube with sump pump

    Duplex oil filter

    Oil level regulator

    Mounting Structual Steel Tube

    Anti-vibration mounts (shipped loose)

    Isolator removal

    Spring-tuype, zone 4

    Starting/Charging 24 volt starting motor(s)

    Batteries with rack and cables

    Battery disconnect switch

    Battery chargers (10&20 amp)

    Oversize batteries

    Ether starting aids

    Heavy duty starting motors

    Barring device (manual)

    Air starting motor with control & silencer

    General Crankcase explosion relief valves Automatic transfer switches (ATS)

    EU Certificate of Conformance6 September 2006 1:58 A2

  • 8/10/2019 PGS1000 kVA

    3/6

    STANDBY 800 ekW 1000 kVA50 Hz 1500 rpm 400 Volts

    SPECIFICATIONS

    CAT GENERATOR

    SR4B GeneratorFrame size......................................................................... 692

    Excitation................................................Permanent Magnet

    Pitch.............................................................................. 0.7143

    Number of poles...................................................................4

    Number of bearings......................................................... 002

    Insulation....................... UL 1446 Recognized Class H with

    tropicalization and antiabrasionIP rating..........................................................Drip Proof IP22

    Alignment.....................................................Closed Coupled

    Overspeed capability - % of rated...................................180

    Wave form....................................................................003.00

    Voltage regulation............Less than +/- 1/2% (steady state)Less than +/- 1% (no load to full load)Paralleling kit/Droop transformer.......................... Standard

    Voltage regulator.3 Phase sensing with selectible volts/Hz

    Telephone Influence Factor.............................. Less than 50

    Harmonic distortion......................................... Less than 5%

    CAT DIESEL ENGINE

    3508 TA, 4-stroke-cycle watercooled diesel

    Bore - mm.............................................. 170.00 mm (6.69 in)

    Stroke - mm........................................... 190.00 mm (7.48 in)

    Displacement - L................................... 34.53 L (2107.15 in3

    )Compression ratio........................................................ 13.5:1

    Aspiration........................................................................... TA

    Fuel system............................................Direct unit injection

    Governor type...................................................... Woodward

    CAT EMCP3 CONTROLS

    EMCP3.1 (standard)

    Integral to generator terminal box

    Single location for customer connections

    IP 23 enclosure

    24 Volt DC control

    UL/CSA/CE

    Electrically dead front

    Lockable hinged door

    Run/Auto/Stop control

    True RMS metering, 3-phase

    Speed Adjust (Optional 3.1)

    Digital indications for:

    - RPM

    - Operating hours

    - Oil pressure

    Coolant Temperature

    - System DC volts

    L-L volts, L-N volts, phase amps, Hz

    - ekW, kVA, kVAR, kW-hr, %kW, PF

    Shutdowns with indicating lights for:

    - Low oil pressure

    - Overspeed

    - Emergency stop

    Under and over frequency

    - Reverse powerOvercurrent

    MODBUS isolated data link (RS-485 half-duplex) supports

    seriall communication at data rate up to 115.2 kbaud (*)

    6 September 2006 1:59 A3

  • 8/10/2019 PGS1000 kVA

    4/6

  • 8/10/2019 PGS1000 kVA

    5/6

    STANDBY 800 ekW 1000 kVA50 Hz 1500 rpm 400 Volts

    RATING DEFINITIONS AND CONDITIONS

    Meets or Exceeds International Specifications:AS1359,

    AS2789, CSA, EGSA101P,IEC60034, ISO3046,

    ISO8528,NEMA MG 1-32, UL508, 72/23/EEC, 89/336/EEC,

    98/37/EEC.

    Standby-Output available with varying load for the

    duration of the interruption of the normal source power.

    Standby power in accordance with ISO8528. Fuel stop

    power in accordance with ISO3046, AS2789, and BS5514.

    Standby ambient temperatures shown indicate a coolant

    top tank temperature just below shutdown at 100 percent

    load.

    Ratingsare based on SAE J1995 standard conditions.

    These ratings also apply at ISO3046 standard conditions.

    Fuel Ratesare based on fuel oil of 35 API [16 C (60 F)]

    gravity having an LHV of 42 780 kJ/kg (18,390 Btu/lb)

    when used at 29 C (85 F) and weighing 838.9 g/liter

    (7.001 lbs/U.S. gal.). Additional ratings may be available

    for specific customer requirements. Consult your

    Caterpillar representative for details.

    6 September 2006 1:59 A5

  • 8/10/2019 PGS1000 kVA

    6/6

    STANDBY 800 ekW 1000 kVA50 Hz 1500 rpm 400 Volts

    DIMENSIONS

    Package DimensionsLength 5256.2 mm 206.94 in

    Width 1844.0 mm 72.6 in

    Height 2128.2 mm 83.79 in

    Weight 10 478 kg 23,100 lb

    Note: Do not use for installation design.See general dimension drawings fordetail (Drawing #1532779).

    www.CAT-ElectricPower.co

    2006 CaterpillAll rights reserve

    Materials and specifications are subject to change without noticThe International System of Units (SI) is used in this publication

    CAT, CATERPILLAR, their respective logos and "Caterpillar Yellow," awell as corporate and product identity used herein, are trademarks o

    Caterpillar and may not be used without permissio

    7878757

    Performance No.: TM4514

    Feature Code:: 508DE47

    Source:: European Sourced

    6 September 2006

    6