International Electrical Engineering Journal (IEEJ) Vol. 4 (2013) No. 1, pp. 899-906 ISSN 2078-2365 899 Performance Analysis of DFIG Based Wind Power Generation under Unbalanced Conditions Performance Analysis of DFIG Based Wind Power Generation under Unbalanced Conditions ANJU. M 1 R. RAJASEKARAN 2 1 , Department of EEE, SNS College of Technology, Coimbatore. 2 , Department of EEE, SNS College of Technology, Coimbatore. 1 [email protected] 2 [email protected] Abstract - This paper proposes a detailed study about the performance analysis of Doubly Fed Induction Generator (DFIG). The Wind Energy Conversion System (WECS) mainly focus with three main electrical aspects: 1) Wind Turbine Generators (WTGs) 2) Power Electronics Conversion Systems (PECS) 3) grid-connection issues. The topology of DFIG driven by a variable speed wind turbine through a multi-stage gearbox. The stator of the DFIG is connected directly to the grid, while the wound rotor is connected through a partial-scale frequency converter. DFIGs are typically more expensive and less robust than FSIG (Fixed Speed Induction Generator). Permanent Magnet Synchronous Generator (PMSG) runs at a constant speed and its excitation from a constant power source external or independent of the load or transmission network, they are equipped with a separate DC source or permanent magnet excitation system (rotating or static) associated with a voltage regulator to control the output voltage before the generator is connected to the grid. Design of DFIG is analysed by means of MATLAB/SIMULINK block set. Index terms Fault Ride Through Capability, Voltage Dip, Wind Turbine Generators, Power Electronic Converters, Grid- Connection issues. I. INTRODUCTION In recent years more attention has been focused on induction machines for low and medium power application because they have attractive advantages over conventional generators such as low unit cost, less maintenance robust construction etc. Doubly-Fed Induction Generators (DFIG) are particularly suitable for isolated operation like hydro and wind developments. [1]. Power utilities have compiled Low-Voltage Ride-Through (LVRT) grid code standards to the wind farms which demanding additional services for network reliability and security enhancement. LVRT grid code standards specify a minimum voltage profile to a wind farm should be able to ride-through. Consequently wind farms are required to stay beyond the defined voltage profile stipulated in published grid codes [2]. The wind generation includes fixed-speed system as well as variable-speed system. The variable- speed wind power generation is mostly used in wind power generation development because it can operate on the maximum power point of the machine. This system include synchronous and asynchronous generator [3]. PMSG generate the output voltage without a constant frequency. The AC-DC-AC converter is responsible to controlling the frequency and to make the voltage constant at the dc link. The PMSG does not need the gearbox and has a light mass and high efficiency. The whole power generated need to pass through the

Performance Analysis of DFIG Based Wind Power Generation under Unbalanced …ieejournal.com/Vol_4_No_1/Performance Analysis of DFI… ·  · 2013-05-24Performance Analysis of DFIG

Embed Size (px)

Citation preview

Page 1: Performance Analysis of DFIG Based Wind Power Generation under Unbalanced …ieejournal.com/Vol_4_No_1/Performance Analysis of DFI… ·  · 2013-05-24Performance Analysis of DFIG

International Electrical Engineering Journal (IEEJ) Vol. 4 (2013) No. 1, pp. 899-906 ISSN 2078-2365

899 Performance Analysis of DFIG Based Wind Power Generation under Unbalanced Conditions

Performance Analysis of DFIG Based Wind Power

Generation under Unbalanced Conditions

ANJU. M1 R. RAJASEKARAN

2

1 , Department of EEE, SNS College of Technology, Coimbatore. 2 , Department of EEE, SNS College of Technology, Coimbatore.

1 [email protected]

[email protected]

Abstract - This paper proposes a detailed study about the

performance analysis of Doubly Fed Induction Generator

(DFIG). The Wind Energy Conversion System (WECS) mainly

focus with three main electrical aspects: 1) Wind Turbine

Generators (WTGs) 2) Power Electronics Conversion Systems

(PECS) 3) grid-connection issues. The topology of DFIG

driven by a variable speed wind turbine through a multi-stage

gearbox. The stator of the DFIG is connected directly to the

grid, while the wound rotor is connected through a partial-scale

frequency converter. DFIGs are typically more expensive and

less robust than FSIG (Fixed Speed Induction Generator).

Permanent Magnet Synchronous Generator (PMSG) runs at a

constant speed and its excitation from a constant power source

external or independent of the load or transmission network,

they are equipped with a separate DC source or permanent

magnet excitation system (rotating or static) associated with a

voltage regulator to control the output voltage before the

generator is connected to the grid. Design of DFIG is analysed

by means of MATLAB/SIMULINK block set.

Index terms – Fault Ride Through Capability, Voltage Dip,

Wind Turbine Generators, Power Electronic Converters, Grid-

Connection issues.

I. INTRODUCTION

In recent years more attention has been focused

on induction machines for low and medium power

application because they have attractive advantages over

conventional generators such as low unit cost, less

maintenance robust construction etc. Doubly-Fed

Induction Generators (DFIG) are particularly suitable for

isolated operation like hydro and wind developments.

[1].

Power utilities have compiled Low-Voltage

Ride-Through (LVRT) grid code standards to the wind

farms which demanding additional services for network

reliability and security enhancement. LVRT grid code

standards specify a minimum voltage profile to a wind

farm should be able to ride-through. Consequently wind

farms are required to stay beyond the defined voltage

profile stipulated in published grid codes [2].

The wind generation includes fixed-speed

system as well as variable-speed system. The variable-

speed wind power generation is mostly used in wind

power generation development because it can operate on

the maximum power point of the machine. This system

include synchronous and asynchronous generator [3].

PMSG generate the output voltage without a constant

frequency. The AC-DC-AC converter is responsible to

controlling the frequency and to make the voltage

constant at the dc link. The PMSG does not need the

gearbox and has a light mass and high efficiency. The

whole power generated need to pass through the

Page 2: Performance Analysis of DFIG Based Wind Power Generation under Unbalanced …ieejournal.com/Vol_4_No_1/Performance Analysis of DFI… ·  · 2013-05-24Performance Analysis of DFIG

International Electrical Engineering Journal (IEEJ) Vol. 4 (2013) No. 1, pp. 899-906 ISSN 2078-2365

900 Performance Analysis of DFIG Based Wind Power Generation under Unbalanced Conditions

converter, so, the rated power of the converter must to be

the same rated power of the generator [4].

In wind turbines based on DFIG, the stator is

directly connected to the grid and the rotor is excited by

three phase converter which can regulate both active and

reactive power of stator machine through control of dq-

axis rotor currents. The rated power of the back-to-back

converter is smaller than the generator rated power, this

converter must be specified by the slip power, which is

approximately 25% of the rated power of the generator.

The DFIG is heavier than the PMSG and needs the

gearbox, which causes the whole system heaviest [6].

II. OPERATION OF DFIG

The majority of wind turbines are equipped with

Doubly Fed Induction Generators (DFIGs). The wound

rotor induction generator have stator directly connected

to the grid and rotor mains via a partially rated variable

frequency AC/DC/AC converter (VFC). This have the

ability to handle a fraction (25%-30%) of the total power

to achieve full control of the generator. The Variable

Frequency Controller consists of a Rotor side Converter

(RSC) and a Grid-Side Converter (GSC) connected back-

to-back by a dc-link capacitor in order to meet power

factor requirement (e.g. −0.95 to 0.95) at the point of

connection. In order to get a complete control of entire

transmission line, voltage across the dc link capacitor

must be double the value of grid voltage. Most wind

farms are equipped with switched shunt capacitors for

conventional reactive power compensation. Moreover,

because many wind farms are connected to weak power

system networks which are characterized by low short

circuit ratios and under-voltage conditions.

Fig. 1.Wind turbine model

One of the important issues related to the wind

farms equipped with DFIGs is the grid fault or low

voltage ride through capability and system stability. One

technique of blocking the RSC is short circuiting the

rotor circuit by a crow-bar circuit to protect the converter

from over current. WTGs continue their operation to

produce some active power and the GSCs can be set to

control the reactive power and voltage.

Fig.2. Equivalent circuit of DFIG

The rotor leakage reactance, Lr and the rotor

resistance Rr. In addition, the rotor circuit will generated

the mechanical power by including an additional rotor

resistance component, Rr(1–s)/s. Note that the rotor and

stator circuits are linked via a transformer whose turns

ratio depends on the actual turns ratio between the stator

and rotor (1:k) and also the slip „s‟ of the machine. That‟s

why induction machine are also called rotating

transformer.

In an induction machine the slip is defined as

S=(Ns-Nr)/Ns-----------------------------(1)

where „Ns’ and „Nr’ are the synchronous speed and

speed of the rotor respectively. The synchronous speed is

given by

Ns=(120*fe)/p rpm ------------------------------(2)

Page 3: Performance Analysis of DFIG Based Wind Power Generation under Unbalanced …ieejournal.com/Vol_4_No_1/Performance Analysis of DFI… ·  · 2013-05-24Performance Analysis of DFIG

International Electrical Engineering Journal (IEEJ) Vol. 4 (2013) No. 1, pp. 899-906 ISSN 2078-2365

901 Performance Analysis of DFIG Based Wind Power Generation under Unbalanced Conditions

Where p is the number of pole pairs and fe is the

electrical frequency of the applied stator voltage.

III. CONTROL DESIGN OF DFIG

Control design of DFIG consist of RSC (Rotor

side Converter) and GSC (Grid Side Converter)

A. The Rotor-Side Converter (RSC)

The Rotor-Side Converter (RSC) applies the voltage

to the rotor windings of the Doubly-Fed Induction

Generator. The purpose of the rotor-side converter is to

control the rotor currents such that the rotor flux position

is optimally oriented with respect to the stator flux in

order that the desired torque is developed at the shaft of

the machine. The rotor-side converter uses a torque

controller to regulate the wind turbine power output and

the voltage or reactive power measured at the machine

stator terminals. The power is controlled in order to

follow a pre-defined turbine power-speed characteristic

to track the maximum power point. The actual electrical

output power from the generator terminals added to the

total power losses (mechanical and electrical) is

compared with the reference power obtained from the

wind turbine characteristic. In order to reduce the power

error or rotor speed error to zero a Proportional-Integral

(PI) regulator is used at the outer control loop. The

output of this regulator is the reference rotor current irqref

that must be injected in the rotor winding by rotor-side

converter. This q-axis component controls the

electromagnetic torque Te. The actual irq component of

rotor current is compared with irqref and the error is

minimized to zero by a current PI regulator at inner

control loop. The output of this current controller loop is

the voltage vrq, which is generated by rotor-side converter

with another similarly regulated ird and vrd component the

required 3-phase voltages applied to the rotor winding

are obtained.

To describe the control scheme, the general Park‟s

model of an induction machine is introduced. Stator-

oriented reference frame without saturation the voltage

vector equations are

Vs=is*Rs +dα/dt--------------------(3)

Vr=ir*Rr+ dα/dt--------------------(4)

where „Vs’ is the stator voltage imposed by the grid. The

rotor voltage „Vr’ is controlled by the rotor-side

converter and used to perform generator control. The flux

vector equations are

αs = Ls*is + Lm*ir------------------(5)

αr = Lm*is + Lr *ir---------------(6)

The stator and rotor self-inductances are „Ls’ and „Lr’ :

Ls = Lm + Lls , Lr = Lm + Llr-----------(7)

Defining leakage factor,

σ=1-Lm2/Lr*Ls----------------(8)

L0=Lm2/Ls------------------(9)

Vrd=ird*Rr+ σLr*dird/dt-wslip* σLr*irq-----------------(10)

Vrq=irq*Rr+ σLr*dirq/dt-wslip (σLr*ird+L0*ims)-------(11)

wslip=ws-wr----------------------------(12)

The stator flux angle is calculated from

αst= ∫(Vst-is*Rs)dt----------------(13)

αsb= ∫(Vsb-is*Rs)dt----------------------------(14)

θs=tan-1(αst / αsb)----------------------------------(15)

The control scheme for the rotor-side converter

is organized in a generic way with two PI-controllers.

Fig. 3 shows a schematic block diagram for the rotor-side

converter control. The outer speed control loop or a

reference torque imposed on the machine is used for the

reference q-axis rotor current irq. These two options may

be termed as speed-control mode or torque-control mode

for the generator, instead of regulating the active power

directly. For speed-control mode one outer PI controller

is to control the speed error signal in terms of maximum

Page 4: Performance Analysis of DFIG Based Wind Power Generation under Unbalanced …ieejournal.com/Vol_4_No_1/Performance Analysis of DFI… ·  · 2013-05-24Performance Analysis of DFIG

International Electrical Engineering Journal (IEEJ) Vol. 4 (2013) No. 1, pp. 899-906 ISSN 2078-2365

902 Performance Analysis of DFIG Based Wind Power Generation under Unbalanced Conditions

power point tracking. Furthermore, another PI controller

is added to produce the reference signal of the d-axis

rotor current component to control the reactive power

required from the generator. Assuming that all reactive

power to the machine is supplied by the stator the

reference value ird may set to zero. The switching

dynamics of the IGBT-switches of the rotor converter are

neglected and it is assumed that the rotor converter is

able to follow demand values at any time.

Fig .3 The Rotor-Side Converter (RSC)

B. The Grid-Side Converter (GSC)

The grid-side converter aims to regulate the

voltage of the dc capacitor link. Moreover, it is allowed

to generate or absorb reactive power for voltage support

requirements. The function is realized with two internal

control loops as well an outer regulation loop. The output

of the dc voltage regulator is the reference current icdref

for the current regulator. The inner current regulation

loop consists of a current regulator to control the

magnitude and phase of the voltage generated by

converter. The icdref produced by the dc voltage regulator

and specified q-axis icqref reference is shown in Fig.4.

Fig .4 The Grid-Side Converter (GSC)

D. DC-LINK Model

In order to keep the DC-link voltage constant,

GSC plays a major role. Therefore all the voltages and

currents are transferred to a specific reference frame

which rotates at the speed of terminal voltage phasor.

E. TORQUE CONTROL

The turbine model is based on the steady-state

power characteristics of the turbine. The friction factor

and the inertia of the turbine are combined with those of

the generator coupled to the turbine. The output

mechanical power of the turbine is given by:

Pm = 0.5*ρ*A*Cp*vw3------------------ (16)

Where Pm is the mechanical output power of the

turbine,

ρ is the air density (Kg/m3) and A is the turbine swept

area.

A=π*R2---------------------------(17)

„R’ is the blade radius (length), „Cp’ is the performance

coefficient of the turbine, and „vw’ is the wind speed

(m/s).

The power coefficient is defined as the power output of

the wind turbine which is available. This coefficient

Page 5: Performance Analysis of DFIG Based Wind Power Generation under Unbalanced …ieejournal.com/Vol_4_No_1/Performance Analysis of DFI… ·  · 2013-05-24Performance Analysis of DFIG

International Electrical Engineering Journal (IEEJ) Vol. 4 (2013) No. 1, pp. 899-906 ISSN 2078-2365

903 Performance Analysis of DFIG Based Wind Power Generation under Unbalanced Conditions

determines the “maximum power” the wind turbine can

absorb from the available wind power at a given wind

speed. It is a function of the tip-speed ratio „λ‟ and the

blade pitch angle „β‟. The blade pitch angle can be

controlled by using a “pitch-controller” and the Tip-

Speed Ratio (TSR) is given as

λ=w*R/V-------------------------(18)

where „w‟ is the rotational speed of the generator and „R‟

is radius of the rotor blades. Hence, the TSR can be

controlled by controlling the rotational speed of the

generator. For a given wind speed, there is only one

rotational speed of the generator which gives a maximum

value of „Cp‟ at a given . This is the major principle

behind the Maximum-Power Point Tracking (MPPT) and

a wind turbine needs to be designed keeping this strategy

in mind.

Fig.5. wind turbine Cp curves

IV. SIMULATION RESULTS AND DISCUSSION

Fig.6. Torque Generation

Fig.7.Grid Side Converter

Fig.8.Rotor Side Converter

a) Operation of DFIG under normal conditions

Fig.9. Modelling of DFIG based wind power generation

Page 6: Performance Analysis of DFIG Based Wind Power Generation under Unbalanced …ieejournal.com/Vol_4_No_1/Performance Analysis of DFI… ·  · 2013-05-24Performance Analysis of DFIG

International Electrical Engineering Journal (IEEJ) Vol. 4 (2013) No. 1, pp. 899-906 ISSN 2078-2365

904 Performance Analysis of DFIG Based Wind Power Generation under Unbalanced Conditions

Fig.10. Grid Voltage and Current

Fig.11. Stator Voltage and Current

Fig.12. Rotor Voltage and Current

Fig.13. Capacitor Voltage

Fig.14. Electromagnetic Torque

b) Operation of DFIG under unbalanced

condition

Fig.15. Stator Voltage and Current

Fig.16. Rotor Voltage and Current

V.APPENDIX

TABLE I

WIND TURBINE SYSTEM SIMULATION

PARAMETERS

TABLE II TWO-MASS MODEL PARAMETERS

Page 7: Performance Analysis of DFIG Based Wind Power Generation under Unbalanced …ieejournal.com/Vol_4_No_1/Performance Analysis of DFI… ·  · 2013-05-24Performance Analysis of DFIG

International Electrical Engineering Journal (IEEJ) Vol. 4 (2013) No. 1, pp. 899-906 ISSN 2078-2365

905 Performance Analysis of DFIG Based Wind Power Generation under Unbalanced Conditions

TABLE IV-VS-PCS

VI. CONCLUSION

This paper provides a control design of DFIG

based wind power systems. DFIG is a typical

variable speed wind generation systems. That have

a capability to operate in a variable speed with

optimal tip speed ratio. Control design of Rotor side

converter and grid side converter are performed.

Electromagnetic Torque generation is done by

means of measuring speed and pitch angle. Rotor

side converter design is done by measuring real and

reactive power. Grid side converter design is done

by measuring DC link voltage. Operation of DFIG

is analysed in a unbalanced condition and obtained

the results.

VII.REFERENCES

[1] M. Anju and R Rajasekaran, “Co-Ordination Of SMES With

STATCOM For Mitigating SSR And Damping Power System

Oscillations In A Series Compensated Wind Power System”

IEEE 2013 International Conference on Computer

Communication and Informatics (ICCCI -2013), Jan. 09 – 11,

2013.

[2] J. Morren and S. W. H. de Haan, “Ride through of wind turbines

with doubly-fed induction generator during a voltage dip,” IEEE

Trans. Energy Convers., vol. 20, no. 2, pp. 707–710, Jun. 2005.

[3] L. Peng, B. Francois, and Y. Li, “Improved crowbar control

strategy of DFIG based wind turbines for grid fault ride-

through,” in Proc. IEEE Appl. Power Electron. Conf., 2009, pp.

1932–1938.

[4] J. Niiranen, “Voltage dip ride through of a doubly fed generator

equippedwith active crowbar,” presented at the NordicWind

Power Conf., Gothenburg, Sweden, 2004.

[5] P. S. Flannery and G. Venkataramanan, “A grid fault tolerant

doubly fed induction generator wind turbine via series connected

grid side converter,” presented at the WINDPOWER Conf.,

Pittsburgh, PA, Jun. 2006.

[6] P. S. Flannery and G. Venkataramanan, “Evaluation of voltage

sag ride through of a doubly fed induction generator wind turbine

with series grid side converter,” 38th Annu. IEEE Power

Electron. Spec. Conf., Jun. 2007, pp. 1839–1845.

[7] P. S. Flannery and G. Venkataramanan, “A fault tolerant doubly

fed induction generator wind turbine using a parallel grid side

rectifier and series grid side converter,” IEEE Trans. Power

Electron., vol. 23, no. 3, pp. 1126–1135, May 2008.

[8] P. S. Flannery and G. Venkataramanan, “Unbalanced voltage sag

ride through of a doubly fed induction generator wind turbine

with series grid side converter,” IEEE Trans. Ind. Appl., vol. 45,

no. 5, pp. 1879–1887, Sep./Oct. 2009.

[9] O. Abdel-Baqi and A. Nasiri, “A dynamic LVRT solution for

doubly fed induction generators,” IEEE Transaction for Power

Electronics., vol. 25, no. 1, pp. 193–196, Jan. 2010.

[10] W. Gao, G.Wang, and J. Ning, “Development of low voltage

ride-through control strategy for wind power generation using

real time digital simulator,” in Proc. IEEE Power Syst. Conf.

Expo., 2009, pp. 1–6.

[11] M. Rahimi and M. Parniani, “Coordinated control approaches for

lowvoltage ride-through enhancement in wind turbines with

doubly fed induction generators,” IEEE Trans. Energy Convers.,

vol. 25, no. 3, pp. 873– 883, Sep. 2010.

Page 8: Performance Analysis of DFIG Based Wind Power Generation under Unbalanced …ieejournal.com/Vol_4_No_1/Performance Analysis of DFI… ·  · 2013-05-24Performance Analysis of DFIG

International Electrical Engineering Journal (IEEJ) Vol. 4 (2013) No. 1, pp. 899-906 ISSN 2078-2365

906 Performance Analysis of DFIG Based Wind Power Generation under Unbalanced Conditions

[12] X.Yan, G.Venkataramanan,Y.Wang, Q. Dong, and B. Zhang,

“Grid-fault tolerant operation of DFIG wind turbine generator

using a passive resistance network,” IEEE Trans. Power

Electron., vol. 26, no. 10, pp. 2896– 2905, Oct. 2011.

[13] C. Abbey, W. Li, L. Owatta, and G. Joos, “Power electronic

converter control techniques for improved low voltage ride

through performance in WTGs,” in Proc. IEEE Power Electron.

Spec. Conf., 2006, pp. 1–6.