    1. Updates on Fire Safety Requirements

    in Public Housing.

    2. Findings from processing of submissions.

  • 7/27/2019 PDMS Fire Safety Reqmts for 2 Dec10

    2/26

    Updates on Fire Safety Requirements

    a) PROVISION OF FIRE LIFT FOR HDB PROJECTS

    Relaxation of provision of fire lift for HDB projects within

    a distance of not more than 9 m from the exit staircase.

    Background

    Changes

    FSSD informed HDB that the relaxation will cease with effectfrom 15th

    July 2009

    Henceforth, fire lift for HDB projects shall be adjacent andaccessible to an exit staircase and be approached by a firefighting lobby at each storey.

    [Fire Code Ref. clause 6.6.3 (b)]

  • 7/27/2019 PDMS Fire Safety Reqmts for 2 Dec10

    3/26

    X

    Updates on Fire Safety Requirements

  • 7/27/2019 PDMS Fire Safety Reqmts for 2 Dec10

    4/26

    Updates on Fire Safety Requirements

  • 7/27/2019 PDMS Fire Safety Reqmts for 2 Dec10

    5/26

    Updates on Fire Safety Requirements

    b) PROVISION OF DRY/WET RISER SYSTEM FOR HDB PROJECTS

    Background

    In most of the design, riser system is sited at central part of the

    building to maximize the serving coverage.This design concept has achieved cost efficiency.

    Fire Safety Requirements

    Fire Code clause 6.2.2 (b) states that position of rising main andlanding valve shall be immediately outside the door of the exitstaircase.

  • 7/27/2019 PDMS Fire Safety Reqmts for 2 Dec10

    6/26

    X

    Updates on Fire Safety Requirements

  • 7/27/2019 PDMS Fire Safety Reqmts for 2 Dec10

    7/26

    Updates on Fire Safety Requirements

  • 7/27/2019 PDMS Fire Safety Reqmts for 2 Dec10

    8/26

    c) Effective width of main gate for residential unit can be

    less than 850mm

    proposal accepted by FSSD

    Updates on Fire Safety Requirements

    The effective width of 850mm is only applicable to exit dooras stated in Fire Code.

  • 7/27/2019 PDMS Fire Safety Reqmts for 2 Dec10

    9/26

    d) Selfclosing device to be provided to fire rated services duct door

    as required in Fire CodeFor projects under construction/awarded without selfclosing device,status quo. No RVO required.

    Updates on Fire Safety Requirements

  • 7/27/2019 PDMS Fire Safety Reqmts for 2 Dec10

    10/26

    e) Provision of Fire Hose Reel to services rooms e.g.Consumer Switch Room, Telecom Equipment room,

    Utility Room, Domestic/Riser Pump Room, BulkyRefuse Room, MDF Room & Lift Motor Room etc

    For Public Housing, provision of Fire Hose Reel canbe excluded, however Fire Extinguisher

    shall be

    provided.

    Updates on Fire Safety Requirements

  • 7/27/2019 PDMS Fire Safety Reqmts for 2 Dec10

    11/26

    f) Provision of Fire Extinguisher & Fire Hose Reelto Precinct Pavilion (Open sided)

    Fire Extinguisher is required, it could be kept by Town Councilwhen pavilion is not used for any function.

    Fire Hose Reel shall be provided if area exceeding 200 sq mIf pavilion is located within the serving range of 36m of any FireHose Reel installed in adjacent building, dedicated Fire HoseReel need not be provided.

    Updates on Fire Safety Requirements

  • 7/27/2019 PDMS Fire Safety Reqmts for 2 Dec10

    12/26

    g) Provision of Exit Sign to Services Rooms e.g.Consumer Switch Room, Telecom Equipment room,

    Utility Room, Domestic/Riser Pump Room, BulkyRefuse Room, MDF Room & Lift Motor Room etc

    Provision of Exit Sign is not required to room withonly

    single exit.

    Updates on Fire Safety Requirements

  • 7/27/2019 PDMS Fire Safety Reqmts for 2 Dec10

    13/26

    Provision of Exit Sign is not required.

    Updates on Fire Safety Requirements

  • 7/27/2019 PDMS Fire Safety Reqmts for 2 Dec10

    14/26

    Exit doornear external

    Exit doornear external

    h) Provision of fire rated door to side of exit staircase is not

    required@ 1st storey if it is a void deck space and door isnear to exterior open space.

    Updates on Fire Safety Requirements

  • 7/27/2019 PDMS Fire Safety Reqmts for 2 Dec10

    15/26

    Dischargeto external

    Dischargeto external

    i) Provision of fire rated door to discharge of exit staircase is notrequired @ 1st storey which is directly facing exterior open space.

    Updates on Fire Safety Requirements

  • 7/27/2019 PDMS Fire Safety Reqmts for 2 Dec10

    16/26

    j) EXEMPTION OF FIRE

    ALARM SYSTEM &FIRE EXTINGUISHERTO HDB MULTI

    STOREY CARPARKAND MARKET BY FSSDON 29TH

    JULY2000

    Updates on Fire Safety Requirements

  • 7/27/2019 PDMS Fire Safety Reqmts for 2 Dec10

    17/26

    Updates on Fire Safety Requirements

    Residential block

    k) Door to exit staircase and services ducts only need

    to comply with

    hr fire rating.

    Doors to services rooms at 1st

    storey are as follow:

    1.

    Facing external directly needs not be fire rated.

    2.

    Facing nonoccupied space to have

    hr fire rating.

    3.

    Facing occupied space or escape route to have

    Same fire rating of element of structure.

  • 7/27/2019 PDMS Fire Safety Reqmts for 2 Dec10

    18/26

    Updates on Fire Safety Requirements

    MSCP

    l) Doors to exit staircase and services ducts onlyneed to have

    hr fire rating,

    If 50% unobstructed facade openings is achieved.

  • 7/27/2019 PDMS Fire Safety Reqmts for 2 Dec10

    19/26

    1st Storey

    Excessive circulation atstaircase can be avoided.

    Findings from processing of submissions

  • 7/27/2019 PDMS Fire Safety Reqmts for 2 Dec10

    20/26

    Excessive circulation atstaircase can be avoided.

    Typical Storey

    Findings from processing of submissions

  • 7/27/2019 PDMS Fire Safety Reqmts for 2 Dec10

    21/26

    Habitable Height 10.050m from access road level

    Provision of Dry Riser to MSCP

    Findings from processing of submissions

  • 7/27/2019 PDMS Fire Safety Reqmts for 2 Dec10

    22/26

    Before After

    Riser piping housed within

    protected staircase

    Riser piping runningthru car park area

    Findings from processing of submissions

  • 7/27/2019 PDMS Fire Safety Reqmts for 2 Dec10

    23/26

    Before After

    Position not appropriate, itshould house within protectedstaircase to avoid unnecessary

    ducting to dry riser.

    CorrectPosition

    Findings from processing of submissions

  • 7/27/2019 PDMS Fire Safety Reqmts for 2 Dec10

    24/26

    MSCP

    min. 50% UNOBSTRUCTED OPEING TO FACADE

    Findings from processing of submissions

  • 7/27/2019 PDMS Fire Safety Reqmts for 2 Dec10

    25/26

    MSCP

    min. 50% UNOBSTRUCTED OPEING TO FACADE

    Findings from processing of submissions

  • 7/27/2019 PDMS Fire Safety Reqmts for 2 Dec10

    26/26

    Thank you