61
1 SESSION 3 Short Circuit Calculations, Unsymmetrical Faults Leonard Bohmann, Michigan State University Elham Makram, Clemson University

Lecture Notes EEE 360 - Michigan Technological … Circuit Calculations, Unsymmetrical Faults Leonard Bohmann, Michigan State University Elham Makram, Clemson University. 2 ... Lecture

  • Upload
    vomien

  • View
    222

  • Download
    2

Embed Size (px)

Citation preview

Page 1: Lecture Notes EEE 360 - Michigan Technological … Circuit Calculations, Unsymmetrical Faults Leonard Bohmann, Michigan State University Elham Makram, Clemson University. 2 ... Lecture

1

SESSION 3

Short Circuit Calculations, Unsymmetrical Faults

Leonard Bohmann, Michigan State University

Elham Makram, Clemson University

Page 2: Lecture Notes EEE 360 - Michigan Technological … Circuit Calculations, Unsymmetrical Faults Leonard Bohmann, Michigan State University Elham Makram, Clemson University. 2 ... Lecture

2

Short Circuit CalculationsLeonard Bohmann

Michigan State University

Page 3: Lecture Notes EEE 360 - Michigan Technological … Circuit Calculations, Unsymmetrical Faults Leonard Bohmann, Michigan State University Elham Makram, Clemson University. 2 ... Lecture

3

Line to Ground Short

2003 IEEE T & D CONFERENCE

Page 4: Lecture Notes EEE 360 - Michigan Technological … Circuit Calculations, Unsymmetrical Faults Leonard Bohmann, Michigan State University Elham Makram, Clemson University. 2 ... Lecture

42003 IEEE T & D CONFERENCE

-3

-2

-1

0

1

2

3

4

5

6

7

0 0.05 0.1 0.15 0.2tA

mp

s(k

A)

Short Circuit Fault Currents

high frequency transient

dc offset decaying sinusoid

Page 5: Lecture Notes EEE 360 - Michigan Technological … Circuit Calculations, Unsymmetrical Faults Leonard Bohmann, Michigan State University Elham Makram, Clemson University. 2 ... Lecture

52003 IEEE T & D CONFERENCE

Short Circuit Fault Currents (continued)

v(t)

X(t) R

]e)tcos(

)t[cos()t(Z

V)t(i

then

)t(jXR)t(Z

)tcos(V)t(v

if

)t(XtR

0

m

m

ω−θ−α+ω−

θ−α+ω=

+=θ∠α+ω=

-3

-2

-1

0

1

2

3

4

5

0 0.05 0.1 0.15 0.2

Page 6: Lecture Notes EEE 360 - Michigan Technological … Circuit Calculations, Unsymmetrical Faults Leonard Bohmann, Michigan State University Elham Makram, Clemson University. 2 ... Lecture

6

dc offset

-3

-2

-1

0

1

2

3

4

5

0 0.05 0.1 0.15 0.2

θ−α+ω−θ−α+ω=

ω− XtR

0m e)tcos()tcos(

Z

V)t(i

2003 IEEE T & D CONFERENCE

Page 7: Lecture Notes EEE 360 - Michigan Technological … Circuit Calculations, Unsymmetrical Faults Leonard Bohmann, Michigan State University Elham Makram, Clemson University. 2 ... Lecture

7

Variable magnitude

-6

-4

-2

0

2

4

6

0 0.01 0.02 0.03 0.04 0.05 0.06 0.07 0.08 0.09 0.1

t

2003 IEEE T & D CONFERENCE

)tcos()t(Z

V)t(i m θ−α+ω=

Page 8: Lecture Notes EEE 360 - Michigan Technological … Circuit Calculations, Unsymmetrical Faults Leonard Bohmann, Michigan State University Elham Makram, Clemson University. 2 ... Lecture

8

Reactance of Synchronous Machine

00.1

0.20.3

0.40.5

0.60.7

0.80.9

1

0 0.2 0.4 0.6 0.8 1 1.2 1.4

t

reac

tan

ce(p

u)

X'd

X"d

Xd

2003 IEEE T & D CONFERENCE

Page 9: Lecture Notes EEE 360 - Michigan Technological … Circuit Calculations, Unsymmetrical Faults Leonard Bohmann, Michigan State University Elham Makram, Clemson University. 2 ... Lecture

9

• Use sub-transient reactance to calculatefault currents– worst case for when CB is opening

• Do not calculate dc offset directly– use X/R to approximate offset

(asymmetry ratio) at opening time– X/R is the time constant of the decay in

cycles

2003 IEEE T & D CONFERENCE

Page 10: Lecture Notes EEE 360 - Michigan Technological … Circuit Calculations, Unsymmetrical Faults Leonard Bohmann, Michigan State University Elham Makram, Clemson University. 2 ... Lecture

10

How do youcalculate the

fault current (If)at bus 3?

ZT12

ZT35

1 2

3

4

ZG1

ZG4

ZT15

ZL5

5

ZL2

If

ZT23

ZT34

2003 IEEE T & D CONFERENCE

Page 11: Lecture Notes EEE 360 - Michigan Technological … Circuit Calculations, Unsymmetrical Faults Leonard Bohmann, Michigan State University Elham Makram, Clemson University. 2 ... Lecture

11

Use Thevenin equivalent

VTh

ZTh

3

If

• VTh: open circuitvoltage

– also called the pre-fault voltage, Vf

– often use 1∠ 0°

2003 IEEE T & D CONFERENCE

Page 12: Lecture Notes EEE 360 - Michigan Technological … Circuit Calculations, Unsymmetrical Faults Leonard Bohmann, Michigan State University Elham Makram, Clemson University. 2 ... Lecture

122003 IEEE T & D CONFERENCE

Use for:

• symmetrical faults

– single phase networks

– three phase faults in three phasenetworks (per phase equivalent)

• concept for solving all faults

Page 13: Lecture Notes EEE 360 - Michigan Technological … Circuit Calculations, Unsymmetrical Faults Leonard Bohmann, Michigan State University Elham Makram, Clemson University. 2 ... Lecture

132003 IEEE T & D CONFERENCE

• This method calculates the currentgoing into the fault

• Often want the current elsewherein the network (through a circuitbreaker, in bus bars, in other lines,etc.)

Page 14: Lecture Notes EEE 360 - Michigan Technological … Circuit Calculations, Unsymmetrical Faults Leonard Bohmann, Michigan State University Elham Makram, Clemson University. 2 ... Lecture

14

A current source, with the magnitude ofthe fault current, placed at the fault, hasthe same effect on the rest of the circuitas the short circuit.

Vf

ZTh

3

If

Vf

ZTh

3

If

2003 IEEE T & D CONFERENCE

Page 15: Lecture Notes EEE 360 - Michigan Technological … Circuit Calculations, Unsymmetrical Faults Leonard Bohmann, Michigan State University Elham Makram, Clemson University. 2 ... Lecture

15

Adding a current source tothe original circuit hasthe same electricaleffect as adding it tothe equivalent circuit

2003 IEEE T & D CONFERENCE

Vf

ZTh

3

If

ZT12

ZT35

1 2

3

4

ZG1

ZG4

ZT23ZT15

ZL5

5

ZL2

ZT34

If

Page 16: Lecture Notes EEE 360 - Michigan Technological … Circuit Calculations, Unsymmetrical Faults Leonard Bohmann, Michigan State University Elham Makram, Clemson University. 2 ... Lecture

16

All the voltages and allthe currents can be foundusing the new circuit.

2003 IEEE T & D CONFERENCE

ZT12

ZT35

1 2

3

4

ZG1

ZG4

ZT23ZT15

ZL5

5

ZL2

ZT34

If

Use superposition:– Use the original sources

(or assume currents are 0and voltages are 1∠ 0°)

– Use just the currentsource, gives changesdue to the fault

Page 17: Lecture Notes EEE 360 - Michigan Technological … Circuit Calculations, Unsymmetrical Faults Leonard Bohmann, Michigan State University Elham Makram, Clemson University. 2 ... Lecture

17

Calculation detailsBus Admittance Matrix: Ybus

2003 IEEE T & D CONFERENCE

I = Ybus V

vector of currentinjections

vector of busvoltages

ZT12

ZT35

1 2

3

4

ZG1

ZG4

ZT23ZT15

ZL5

5

ZL2

ZT34

If

Page 18: Lecture Notes EEE 360 - Michigan Technological … Circuit Calculations, Unsymmetrical Faults Leonard Bohmann, Michigan State University Elham Makram, Clemson University. 2 ... Lecture

182003 IEEE T & D CONFERENCE

ZT12

ZT35

1 2

3

4

ZG1

ZG4

ZT23ZT15

ZL5

5

ZL2

ZT34

If

=

555351

4443

35343332

232221

151211

bus

00

000

0

00

00

Y

YYY

YY

YYYY

YYY

YYY

Diagonals:Σ of Y connected at nodeY22 = 1/ZT12 + 1/ZL2 + 1/ZT23

Off diagonals:- of Y connected between nodesY53 = -1/ZT35

Page 19: Lecture Notes EEE 360 - Michigan Technological … Circuit Calculations, Unsymmetrical Faults Leonard Bohmann, Michigan State University Elham Makram, Clemson University. 2 ... Lecture

192003 IEEE T & D CONFERENCE

Ybus is sparse (lots of zero)

– small size

– easy to build

– quick algorithms to manipulate

Page 20: Lecture Notes EEE 360 - Michigan Technological … Circuit Calculations, Unsymmetrical Faults Leonard Bohmann, Michigan State University Elham Makram, Clemson University. 2 ... Lecture

20

Bus Impedance Matrix: Zbus

2003 IEEE T & D CONFERENCE

V = Zbus I

vector of currentinjections

vector of busvoltages ZT12

ZT35

1 2

3

4

ZG1

ZG4

ZT23ZT15

ZL5

5

ZL2

ZT34

If

Zbus = Ybus-1

Page 21: Lecture Notes EEE 360 - Michigan Technological … Circuit Calculations, Unsymmetrical Faults Leonard Bohmann, Michigan State University Elham Makram, Clemson University. 2 ... Lecture

21

=

5554535251

4544434241

3534333231

2524232221

1514131211

busZ

ZZZZZ

ZZZZZ

ZZZZZ

ZZZZZ

ZZZZZ

2003 IEEE T & D CONFERENCE

Zbus is a full matrix– slow to invert– slow to manipulate– avoid using if

possible

Diagonal element is the TheveninImpedance at that bus– Z33 is the Thevenin Impedance at bus 3

Page 22: Lecture Notes EEE 360 - Michigan Technological … Circuit Calculations, Unsymmetrical Faults Leonard Bohmann, Michigan State University Elham Makram, Clemson University. 2 ... Lecture

222003 IEEE T & D CONFERENCE

To find the change in voltages due tothe fault current at bus 3:

=

∆∆∆∆∆

0

0

I-

0

0

V

V

V

V

V

f

5554535251

4544434241

3534333231

2524232221

1514131211

5

4

3

2

1

ZZZZZ

ZZZZZ

ZZZZZ

ZZZZZ

ZZZZZ

Page 23: Lecture Notes EEE 360 - Michigan Technological … Circuit Calculations, Unsymmetrical Faults Leonard Bohmann, Michigan State University Elham Makram, Clemson University. 2 ... Lecture

23

To calculate current in line 2-3:

2003 IEEE T & D CONFERENCE

23T

32f23 Z

VVI

∆−∆=∆

1 2

3

4

ZT23

5 If

∆I23f

Page 24: Lecture Notes EEE 360 - Michigan Technological … Circuit Calculations, Unsymmetrical Faults Leonard Bohmann, Michigan State University Elham Makram, Clemson University. 2 ... Lecture

24

Asymmetry ratio: S

• Method calculates the RMS worst caseof the 60 Hz component– this is needed to set protective relays

• For circuit breaker selection, need toknow the total RMS current (60 Hzand dc offset)– Circuit breakers are rated on symmetrical

fault current, assuming an X/R ratio of 152003 IEEE T & D CONFERENCE

Page 25: Lecture Notes EEE 360 - Michigan Technological … Circuit Calculations, Unsymmetrical Faults Leonard Bohmann, Michigan State University Elham Makram, Clemson University. 2 ... Lecture

252003 IEEE T & D CONFERENCE

( ) RXt2

ac

RMS

RXt2

acRMS

2RX

t

ac2acRMS

2dc

2acRMS

21isS(t)wheretSI

I

21II

I2II

III

ω−

ω−

ω−

⋅+=

⋅+=

+=

+=

e

e

e

Asymmetry ratio

Page 26: Lecture Notes EEE 360 - Michigan Technological … Circuit Calculations, Unsymmetrical Faults Leonard Bohmann, Michigan State University Elham Makram, Clemson University. 2 ... Lecture

26

Calculating X/R• Equations presented are

for a single order system• For higher order systems,

– ignore R and findequivalent X,

– ignore X, and findequivalent R

• Actual decay is typicallyquicker than thisapproximation

ZT12

ZT35

1 2

3

4

ZG1

ZG4

ZT23ZT15

ZL5

5

ZL2

ZT34

If

2003 IEEE T & D CONFERENCE

Page 27: Lecture Notes EEE 360 - Michigan Technological … Circuit Calculations, Unsymmetrical Faults Leonard Bohmann, Michigan State University Elham Makram, Clemson University. 2 ... Lecture

27

Algorithm

2003 IEEE T & D CONFERENCE

• Calculate Thevenin Impedance• Calculate current into fault• Find the needed elements of Zbus (not all

of them)• Find the needed changes in bus voltages• Find the line currents of of interest• Find the dc offset

Page 28: Lecture Notes EEE 360 - Michigan Technological … Circuit Calculations, Unsymmetrical Faults Leonard Bohmann, Michigan State University Elham Makram, Clemson University. 2 ... Lecture

28

Example• The oneline drawing of a system, along with Zbus

are shown below.

j 0.08 pu

j0.03 pu

1 2

3

4

j0.1pu

j0.1 pu

j0.025 puj0.05 pu

j15pu

5

j10 pu

If

j0.05 pu

2003 IEEE T & D CONFERENCE

puj

=

0799004290064400623005590

0429006580048700450003340

0644004870073100675005020

0623004500067500831005380

0559003340050200538006560

Zbus

.....

.....

.....

.....

.....

i) Calculate the fault current for athree phase solid fault at bus 3.

ii) Calculate the voltages at bus 1,2, and 3 during this fault.

iii) Calculate the current flowingfrom bus 2 to bus 3.

Page 29: Lecture Notes EEE 360 - Michigan Technological … Circuit Calculations, Unsymmetrical Faults Leonard Bohmann, Michigan State University Elham Makram, Clemson University. 2 ... Lecture

29

Part (i): Calculate the fault current for a threephase solid fault at bus 3.

• Assume all initial busvoltages are 1∠ 0°– therefore all initial

currents are 0

• Use the 3,3 elementof Zbus for theThevenin impedance.

1∠ 0°

j0.731

3

If

2003 IEEE T & D CONFERENCE

puj

j

6813I

07310

1I

f

f

.

.

−=

=

Page 30: Lecture Notes EEE 360 - Michigan Technological … Circuit Calculations, Unsymmetrical Faults Leonard Bohmann, Michigan State University Elham Makram, Clemson University. 2 ... Lecture

30

Multiply the negative of the fault current by elements inthe 3rd column to get the change in voltages

2003 IEEE T & D CONFERENCE

Part (ii): Calculate the voltages at bus 2, 3, and4 during this fault.

=

∆∆−

−−

0

0

13.68--

0

0

0799004290064400623005590

0429006580048700450003340

0644004870073100675005020

0623004500067500831005380

0559003340050200538006560

V

V

1

9230

6870

5

4

jj

.....

.....

.....

.....

.....

.

.

Page 31: Lecture Notes EEE 360 - Michigan Technological … Circuit Calculations, Unsymmetrical Faults Leonard Bohmann, Michigan State University Elham Makram, Clemson University. 2 ... Lecture

312003 IEEE T & D CONFERENCE

Part (ii): Calculate the voltages at bus 2, 3, and4 during this fault. (continued)

pu

pu

pu

0101VVV

07660923001VVV

3130687001VVV

33i3f

22i2f

11i1f

=−°∠=∆−==−°∠=∆−==−°∠=∆−=

..

..

The voltages during the fault are the initial voltagesminus the changes in the voltages

Page 32: Lecture Notes EEE 360 - Michigan Technological … Circuit Calculations, Unsymmetrical Faults Leonard Bohmann, Michigan State University Elham Makram, Clemson University. 2 ... Lecture

322003 IEEE T & D CONFERENCE

Part (iii): Calculate the current flowing from bus 2to bus 3.

The current is the differencebetween the voltagesdivided by the impedance

pujj

8630250

007660I

Z

VVI

23f

T23

3f2f23f

..

. −=−=

−=

1 2

3

4

5-j13.68 pu

-j3.86 pu

Page 33: Lecture Notes EEE 360 - Michigan Technological … Circuit Calculations, Unsymmetrical Faults Leonard Bohmann, Michigan State University Elham Makram, Clemson University. 2 ... Lecture

33

Problem

1 2

3

4

j0.1 puj0.1 pu

j0.1 pu

j0.025 puj0.05 pu

j0.05 pu

j 0.08

2003 IEEE T & D CONFERENCE

A small power system is sketched below along with Zbus.

a) What is the fault current for a three-phase fault toground at bus 3?

b) What are the voltages at busses 2, 3, and 4?c) What is the current due to the fault from bus 4 to 3 and

from 2 to 3?

puj 2bus 10

4045106342221742

1063658463432613

4222634353440443

1742261304437834

Z −×

=

....

....

....

....

Page 34: Lecture Notes EEE 360 - Michigan Technological … Circuit Calculations, Unsymmetrical Faults Leonard Bohmann, Michigan State University Elham Makram, Clemson University. 2 ... Lecture

12003 IEEE T & D CONFERENCE

Unsymmetrical FaultsElham Makram

Clemson University

Page 35: Lecture Notes EEE 360 - Michigan Technological … Circuit Calculations, Unsymmetrical Faults Leonard Bohmann, Michigan State University Elham Makram, Clemson University. 2 ... Lecture
Page 36: Lecture Notes EEE 360 - Michigan Technological … Circuit Calculations, Unsymmetrical Faults Leonard Bohmann, Michigan State University Elham Makram, Clemson University. 2 ... Lecture
Page 37: Lecture Notes EEE 360 - Michigan Technological … Circuit Calculations, Unsymmetrical Faults Leonard Bohmann, Michigan State University Elham Makram, Clemson University. 2 ... Lecture
Page 38: Lecture Notes EEE 360 - Michigan Technological … Circuit Calculations, Unsymmetrical Faults Leonard Bohmann, Michigan State University Elham Makram, Clemson University. 2 ... Lecture
Page 39: Lecture Notes EEE 360 - Michigan Technological … Circuit Calculations, Unsymmetrical Faults Leonard Bohmann, Michigan State University Elham Makram, Clemson University. 2 ... Lecture
Page 40: Lecture Notes EEE 360 - Michigan Technological … Circuit Calculations, Unsymmetrical Faults Leonard Bohmann, Michigan State University Elham Makram, Clemson University. 2 ... Lecture
Page 41: Lecture Notes EEE 360 - Michigan Technological … Circuit Calculations, Unsymmetrical Faults Leonard Bohmann, Michigan State University Elham Makram, Clemson University. 2 ... Lecture
Page 42: Lecture Notes EEE 360 - Michigan Technological … Circuit Calculations, Unsymmetrical Faults Leonard Bohmann, Michigan State University Elham Makram, Clemson University. 2 ... Lecture

1

SINGLE LINE TO GROUND FAULT

Fig.1. Single line to ground fault on phase A

2003 IEEE T & D CONFERENCE

Zf

Ibf IcfIaf

a

b

c

n

0f210

affa

210

12

0

21

22

12

22

10212

0

afff

cfbf

3I*ZVVVOr,

I*ZVNow

III

0Ia)a(IThus

II

a)I–(aa)I–(a

0IaaIIaIIaI

equations,currenttheFrom

I*ZV

0II

locationfaultatConditionsBoundary

=++=

===++

==

=++=++

===

Page 43: Lecture Notes EEE 360 - Michigan Technological … Circuit Calculations, Unsymmetrical Faults Leonard Bohmann, Michigan State University Elham Makram, Clemson University. 2 ... Lecture

22003 IEEE T & D CONFERENCE

SINGLE LINE TO GROUND FAULT (CONTD.)

Fig.2. Sequence connection for A-G fault

I0

To satisfy the voltage and current boundary conditions, the sequence networks should beconnected in series as shown in Fig. 2.

3Zf

ZeroSequenceNetwork

ZeroSequenceNetwork

ZeroSequenceNetwork

I1

I2

V0

+

-

+V1-

V2-

+

Page 44: Lecture Notes EEE 360 - Michigan Technological … Circuit Calculations, Unsymmetrical Faults Leonard Bohmann, Michigan State University Elham Makram, Clemson University. 2 ... Lecture

32003 IEEE T & D CONFERENCE

LINE TO LINE FAULT

Fig.3. Line to line fault

a

Zf

Ibf IcfIaf

b

c

n

Vaf

+

Vbf Vcf

1f21

22

f12

12

22

10

212

0f212

0

bffcfbf

21

22

12

22

1212

0

cfbf

af

IZVV

a)V-(aZa)I-(aa)V-(a

toleadsThis

VaaVV

)aIIa(IZaVVaV

IZVV

conditionsboundaryVoltage

I-I

a)I(a-a)I(a

0IaaIaIIa

0I

Thus,

I-I

0I

ConditionsboundaryCurrent

+=+=

+++

++=++

+=

=+=+

=+++

=

==

Page 45: Lecture Notes EEE 360 - Michigan Technological … Circuit Calculations, Unsymmetrical Faults Leonard Bohmann, Michigan State University Elham Makram, Clemson University. 2 ... Lecture

42003 IEEE T & D CONFERENCE

Fig.4. Connection of sequence network for BC fault

To satisfy the voltage and current boundary conditions, the sequence networks shouldbe connected as shown in Fig. 4.

LINE TO LINE FAULT (CONTD.)

Zf

PositiveSequenceNetwork

NegativeSequenceNetwork

I1

I2

+V1-

V2-

+

Page 46: Lecture Notes EEE 360 - Michigan Technological … Circuit Calculations, Unsymmetrical Faults Leonard Bohmann, Michigan State University Elham Makram, Clemson University. 2 ... Lecture

52003 IEEE T & D CONFERENCE

DOUBLE LINE TO GROUND FAULT

Fig.5. Double line to ground fault

0f10

f22

12

12

0212

0

21

22

10212

0

cfbf

fcfbfbf

210

af

I3ZV-VThus

Z)IaaIaI

Ia2I(aVVaV

Also,

VVThus

VaaVVaVVaV

Thus,

VV

and,

)ZI(IV

conditionsboundaryVoltage

0III

Thus,

0I

location,faultat the

ConditionsboundaryCurrent

=++

++=++

=++=++

=

+=

=++

=

Zf

a

b

c

n

+

Ibf IcfIaf

Vaf Vbf Vcf

Page 47: Lecture Notes EEE 360 - Michigan Technological … Circuit Calculations, Unsymmetrical Faults Leonard Bohmann, Michigan State University Elham Makram, Clemson University. 2 ... Lecture

62003 IEEE T & D CONFERENCE

DOUBLE LINE TO GROUND FAULT (CONTD.)

Fig.6. Sequence network connection for doubleline to ground fault

Considering the voltage and current boundary conditions, the sequence networks areconnected as shown in Fig. 6.

3Zf

I0

ZeroSequenceNetwork

PositiveSequenceNetwork

NegativeSequenceNetwork

I1

I2

V0

+

-

+V1-

V2-

+

Page 48: Lecture Notes EEE 360 - Michigan Technological … Circuit Calculations, Unsymmetrical Faults Leonard Bohmann, Michigan State University Elham Makram, Clemson University. 2 ... Lecture

72003 IEEE T & D CONFERENCE

Example 1

Consider the power system shown in Fig. 7.

Ratings

G1 and G2: 100 MVA, 20 kV

X1 = X2 = 0.3 pu

X0 = 0.04 pu

T1 and T2: 100 MVA, 345/20 kV

XT1 = XT2 =0.08 pu

T. L. X1 = X2 = 0.15 pu

X0 = 0.5 pu

Find the voltages at Bus 1 and thecurrents from T1 to P due to

(i) Single line to ground fault at P

(ii) Line to line fault at P

(iii) Double line to ground fault at P

Fig. 7. Example 1

G1 G2

T1 T21 2P T. L.

Page 49: Lecture Notes EEE 360 - Michigan Technological … Circuit Calculations, Unsymmetrical Faults Leonard Bohmann, Michigan State University Elham Makram, Clemson University. 2 ... Lecture

82003 IEEE T & D CONFERENCE

Positive sequence network

Negative sequence network Zero sequence network

Z0th = j0.08

j0.2213

Pj0.08 j0.5Z1th = j0.2213

P

j0.3 j0.3

j0.08 j0.15 j0.08

1

P

2 j0.53j0.38

P

j0.2213

P

j0.2213j0.15)j0.08(j0.3||j0.8)(0.3Z

01VEEIf

th

21

=+++=°∠===

Page 50: Lecture Notes EEE 360 - Michigan Technological … Circuit Calculations, Unsymmetrical Faults Leonard Bohmann, Michigan State University Elham Makram, Clemson University. 2 ... Lecture

92003 IEEE T & D CONFERENCE

(i) Single line to ground fault

P--T1fromcomponentsphasecurrentThe

0.15304-(j0.8)j1.913-ZI-V

0.42332-(j0.38)(j1.114)-ZI-V

0.57668j0.38)(-j1.114)(–1.0ZI-EV

:arelocationfaultat thecomponentsvoltagesequenceThe

j1.9134-I

j1.114-I

114.10.38)(0.53

0.53*II

P--T1fromcomponentscurrentsequencethearefollowingThe

j1.9134-j0.08)j0.2213(j0.2213

01

)ZZ(Z

EIII

000

222

1111

0

2

11

2th1th0th021

>===

======

==

−=+

=

>

=++

°∠++

===

j

=

a2

a1

a0

2

2

c

b

a

I

I

I

*

1

1

111

I

I

I

aa

aa

Page 51: Lecture Notes EEE 360 - Michigan Technological … Circuit Calculations, Unsymmetrical Faults Leonard Bohmann, Michigan State University Elham Makram, Clemson University. 2 ... Lecture

102003 IEEE T & D CONFERENCE

-j0.799c

-j0.799b

-j3.027

c-j5.739= 3 I0

-j2.712

j0.799-j1.913–(-j1.114)aa(-j1.114)I

j0.799-j1.913–a(-j1.114)(-j1.114)aI

j3.027-j1.913-j1.114--j1.114I

2c

2b

a

=+=

=+=

==

j0.866-0.2297

))(-0.42332240(1)(0.57668)120(10.15304-VaaVVV

j0.866--0.2297

))(-0.42332120(1)(0.57668)240(10.15304-aVVaVV

00.42332–0.576680.15304-VVVV

:arelocationfaultat thevoltagesphaseThe

22

10c

212

0b

210a

+=°∠+°∠+=++=

=°∠+°∠+=++=

=+=++=

Page 52: Lecture Notes EEE 360 - Michigan Technological … Circuit Calculations, Unsymmetrical Faults Leonard Bohmann, Michigan State University Elham Makram, Clemson University. 2 ... Lecture

112003 IEEE T & D CONFERENCE

(ii) Line to line fault

°∠=°∠=

°∠===

==−=

=+=

=+=

==>

−=+

−=>

−=+

°∠=+

=−=

00.5V

0-0.5V

01V

5.0ZI-V

0.5j0.38)(-j1.316)(-1.0ZIEV

:Voltages

2.279(j1.316)a(-j1.316)aI

2.279a(j1.316)(-j1.316)aI

0I

316.1jP)--1T(I

316.1j)0.53(0.38

0.5326.2jP)--1T(I

26.2j0.2213)(j0.2213

01

)Z(Z

EII

:Currents

c

b

a

2a2a2

1a1a1

2c

2b

a

2

1

2th1th21 j

Page 53: Lecture Notes EEE 360 - Michigan Technological … Circuit Calculations, Unsymmetrical Faults Leonard Bohmann, Michigan State University Elham Makram, Clemson University. 2 ... Lecture

122003 IEEE T & D CONFERENCE

SEQUENCE PHASE SHIFT THROUGH WYE/DELTA TRANSFORMER BANK

•Positive and negative sequence impedance is independent of connection

•These networks ignore phase shift

•When current and voltages are transformed from one side to the other phase shift must

be considered.

•Standard ANSI connection has been shown in figs. 8 (a) and 8 (b).

Fig. 8 (a) Wye/Delta Fig. 8 (b) Delta/Wye

High side Low sideIA

IB

IC

Ia

Ib

Ic

A

B

C

a

b

c

nIA

nIB

nIC

IA

IB

IC

n:1

BC

A

bc

a

High side Low side

Ia

Ib

Ic

IA

IB

IC

a

b

c

A

B

C

Ia/n

Ib/n

Ic/n

n:1

BC

A

bc

a

Page 54: Lecture Notes EEE 360 - Michigan Technological … Circuit Calculations, Unsymmetrical Faults Leonard Bohmann, Michigan State University Elham Makram, Clemson University. 2 ... Lecture

132003 IEEE T & D CONFERENCE

30VV

unitperInor

30V3na)-(1nV)aV-n(V)V-n(VV

:voltagesequenceNegative

30II

unitperInor

30I3n)a-(1nI)Ia-n(I)I-n(II

:currentsequenceNegative

30VV

unit,perinor

30V3n)a-(1nV)Va-n(VV

:volatgesequencePositive

30II

unit,perIn

30-I3na)-(1nI)aI-n(I)I-n(II

:currentsequencePositive

8(a)fig.Refer to

a2A2

a2a2a2a2b2a2A2

a2A2

A22

A2A22

A2C2A22a

a1A1

a12

aa12

a1A1

a1A1

A1A1A1A1C1A11a

°−∠=

°−∠====

°−∠=

°∠====

°∠=

°∠===

°∠=

°∠====

Page 55: Lecture Notes EEE 360 - Michigan Technological … Circuit Calculations, Unsymmetrical Faults Leonard Bohmann, Michigan State University Elham Makram, Clemson University. 2 ... Lecture

142003 IEEE T & D CONFERENCE

°−∠=

°−∠=

°−∠==

°∠=

°−∠==

°∠=

°∠===

30VV

voltagesequenceNegative

30II

unitperInor

30In

3)aI-(I

n

1I

:currentsequenceNegative

30VV

unit,perinor,

30Vn

3)aV-(V

n

1V

:voltagesequencePostitive

30II

unit,perinor,

30In

3)Ia-(I

n

1)I-(I

n

1I

:currentsequencePostitive

(b)8fig.Refer to

a2A2

a2A2

a2a2a2A2

a1A1

A1A1A1a1

a1A1

a1a12

a1b1a1A1

Page 56: Lecture Notes EEE 360 - Michigan Technological … Circuit Calculations, Unsymmetrical Faults Leonard Bohmann, Michigan State University Elham Makram, Clemson University. 2 ... Lecture

152003 IEEE T & D CONFERENCE

°∠=°+∠=

∆∆

30-voltageLowsequenceNegativegeHigh voltasequenceNegative(ii)

30voltageLowsequencePositivegeHigh voltasequencePositive(i)

:sconnectionY-or-Yingeneral,In

Page 57: Lecture Notes EEE 360 - Michigan Technological … Circuit Calculations, Unsymmetrical Faults Leonard Bohmann, Michigan State University Elham Makram, Clemson University. 2 ... Lecture

162003 IEEE T & D CONFERENCE

Example 2

Find the currents and voltages at G1 of Example 1, due to single line to ground fault at P.

0I

j1.9295)60(1.114)120(1.114

)60-(1.1141201)120-(1.1142401aIIaI

j1.9295-60-j1.114120-j1.114-III

0I

60-j1.11430j1.114-I

120-j1.114-30-j1.114-I

:Currents(i)

cg

ag2ag12

bg

ag21agag

ag0

ag2

1ag

==°∠+°∠=

°∠°∠+°∠°∠=+=

=°∠+°∠=+=

=

°∠=°+∠=

°∠=°∠=

Page 58: Lecture Notes EEE 360 - Michigan Technological … Circuit Calculations, Unsymmetrical Faults Leonard Bohmann, Michigan State University Elham Makram, Clemson University. 2 ... Lecture

172003 IEEE T & D CONFERENCE

°∠°∠

°−∠=

=

°∠=+=

°∠=

°∠°∠=+=

°−∠=°∠°∠=+=

°∠=

°∠==

==

==

901

12.240577.0

60577.0

V

V

V

*

1

1

111

V

V

V

901.0VaaVV

240.120.577

1500.334-2100.666aVVaV

60577.0300.334-30-0.666VVV

300.334-V

30-0.666V

shift)phaseneglectingNetworksequence(from0.3342-

ZI–V

shift)phaseneglectingNetworksequence(from0.666

j0.3)(-j1.114)(-1.0ZI–EV

:Voltages(ii)

ag2

ag1

ag0

2

2

cg

bg

ag

ag22

ag1cg

ag2ag12

bg

ag2ag1ag

ag2

ag1

g2a2ag2

g1a1ag1

aa

aa

Example 2 ( contd.)

Page 59: Lecture Notes EEE 360 - Michigan Technological … Circuit Calculations, Unsymmetrical Faults Leonard Bohmann, Michigan State University Elham Makram, Clemson University. 2 ... Lecture

182003 IEEE T & D CONFERENCE

PROBLEM #1

For the system shown below, find the currents in the transformer and generator windings inper unit and amperes for a single-line-to-ground fault at

(i) P

(ii) R

G1

15/115 kVP

G1R

G: 100 MVA, 15 kV

X1=X2= 0.1,

X0 = 0.05

Transformer:

100 MVA, 15/115 kV

X = 0.1

PROBLEMS

Page 60: Lecture Notes EEE 360 - Michigan Technological … Circuit Calculations, Unsymmetrical Faults Leonard Bohmann, Michigan State University Elham Makram, Clemson University. 2 ... Lecture

19

PROBLEM #2

Solve examples 1 and 2 for a double-line-to-ground fault at P.

PROBLEMS

2003 IEEE T & D CONFERENCE

Page 61: Lecture Notes EEE 360 - Michigan Technological … Circuit Calculations, Unsymmetrical Faults Leonard Bohmann, Michigan State University Elham Makram, Clemson University. 2 ... Lecture

202003 IEEE T & D CONFERENCE

PROBLEM #3

Solve examples 1 and 2 for a line-line fault at P.

PROBLEMS