    Daikin Water Chillers are of the self-contained type. This means that they are assembled, internally wired and

    charged with refrigerant at the factory for easy installation, only requiring external wiring and plumbing on site.

    They are compatible with Daikin's Air Handling and/or Fan Coil Units.

    All rights reservedPrinted in Japan 11/06/005 SW.HP.AD

    c

    DealerHead Office:

    Umeda Center Bldg., 2-4-12, Nakazaki-Nishi,

    Kita-ku, Osaka, 530-8323 Japan

    Tokyo Office:

    JR Shinagawa East Bldg., 2-18-1, Konan,

    Minato-ku, Tokyo, 108-0075 Japan

    http://www.daikin.com/global/

    1. Air conditioners should not be installed in areas where corrosive gases, such as acid gas or alkaline gas, are produced.2. If the outdoor unit is to be installed close to the sea shore, direct exposure to the sea breeze should be avoided and choose an

    outdoor unit with anti-corrosion treatment.

    Cautions on product corrosion

    Warning Daikin Industries, Ltd.s products are manufactured for export to numerous countries throughout the

    world. Daikin Industries, Ltd. does not have control over which products are exported to and used in a

    particular country. Prior to purchase, please therefore confirm with your local authorised importer,

    distributor and/or retailer whether this product conforms to the applicable standards, and is suitable for

    use, in the region where the product will be used. This statement does not purport to exclude, restrict

    or modify the application of any local legislation.

    Ask a qualified installer or contractor to install this product. Do not try to install the product yourself.

    Improper installation can result in water or refrigerant leakage, electrical shock, fire or explosion.

    Use only those parts and accessories supplied or specified by Daikin. Ask a qualified installer or

    contractor to install those parts and accessories. Use of unauthorised parts and accessories or

    improper installation of parts and accessories can result in water or refrigerant leakage, electrical

    shock, fire or explosion.Read the User's Manual carefully before using this product. The User's Manual provides important

    safety instructions and warnings. Be sure to follow these instructions and warnings.

    If you have any enquiries, please contact your local importer, distributor and/or retailer.

    Printed on 100% recycled paper with soy ink.Specifications, designs and other content appearing in this brochure are current as of November 2006 but subject to change without notice.

    ISO 14001 is the standarddefined by theInternational Organization forStandardization (ISO) relating to environmental management systems. Our grouphas been acknowledged by an internationally accredited compliance organisationas having an appropriate programme of environmental protection procedures andactivities to meet therequirements of ISO 14001.

    AboutI SO14001

    ISO 9001 is a plant certification system defined by theInternationalOrganization for Standardization (ISO) relating to quality assurance. ISO9001 certification covers quality assurance aspects relatedto the design,development, manufacture, installation, and supplementary service ofproducts manufactured at the plant.

    AboutI SO9001

    JMI-0107 EC99J2044

  • 8/2/2019 PCU0610A - Chiller [Small]

    2/16

    2

    H i g h -p e r f or m a n c e D a i k i n W a t e r C h i l l e r s a r e A v a i l a b l e i n

    a B r o a d R a n g e o f M o de l s t o S u i t D i v e r s e A p p l ic a t i o ns .

    List of Daikin Water Chiller Models

    1 2

    Air Cooled Water Chillers: UWAP Series / UWAXP Series

    : UWA Series / ( For High Outdoor Temperature Use )

    Dedicated water chillers are able to operate year

    round because they can accommodate a wide range

    of outdoor temperatures. The high-performance models

    with capacities of over 40 HP can deliver between

    10% (12%) and 100% of their capacities. They are

    able to withstand the demanding conditions typical ofindustrial applications.

    Air Cooled Water Chillers - Heat Pump Type

    Water Cooled Water Chillers

    Air cooled heat pump system units are an ideal

    way to provide a reliable supply of hot and cold

    water. Of compact size because no cooling tower

    is required, they are also suitable for office

    building air conditioning. These high-end models

    provide an answer to a variety of air conditioning

    requirements.

    Water cooled units provide a stable supply of

    chilled water year round and are unaffected by

    changes in the outdoor temperature. In addition

    to air conditioning applications, they are also a

    highly reliable industrial process cooling solution

    thanks to their stability and wide temperature

    control range.

    Air Cooled Water Chillers

    AirCooled

    WaterChillers

    20 40 60 80 100 150 200 250 300 350 450 500 600 700 800 900 1000 1 200 1 400 Page

    11

    12 13

    14

    14 15

    17

    18

    21

    21 22

    23

    27

    27

    2829

    9 10

    9

    Capacity Range (kW)

    Air CooledWater Chillers - Heat PumpType

    Water Cooled Water Chiller s

    Standard Unit

    Standard Unit

    Standard Unit

    Brine Cooling Unit

    Standard Unit

    ForHigh Outdoor Temperature Use

    Standard Unit

    Inverter Cooling Unit

    Brine Cooling Unit

    Year - Round Cooling Only Unit

    Standard Unit

    Air Cooled Water Chillers

    20 40 60 80 100 150 200 250 300 350 450 500 600 700 800 900 1000 1 200 1 400 Page

    12

    13

    15

    18

    21

    22

    24

    27

    28

    29

    10

    9

    Capacity Range (kW)

    Air CooledWater Chillers - Heat PumpType

    Water Cooled Water Chiller s

    Standard Unit

    Standard Unit

    Standard Unit

    Brine Cooling Unit

    Standard Unit

    ForHigh Outdoor Temperature Use

    Standard Unit

    Brine Cooling Unit

    Year - Round Cooling Only Unit

    Standard Unit

    WaterCooled

    WaterChillers

    AirCooledWaterChillers

    -HeatPumpType

    : UWYP Series

    : UWY Series

    : UWP Series

    : UWD Series ZUW Series

    50Hz

    60Hz

    106 1260 UWAP-BY1

    106 1260 UWAP-BY1K

    12.5 75

    11.2 67

    106 1260 UWA-AY1

    106 1260 UWYP-BY1

    106 1260 UWY-AY1

    8 80

    118 355 UWD-DY1

    UWAXP-AY1

    108.4 319.2 UWA-JAY1

    351.6 791 UWA-JY1

    UWP-AY3

    6.7 67 UWAP-AY3

    68 808 UWAP-BY1Z

    UWYP-AY3

    367 1450ZUW-AY1

    190 715 ZUW-AY1Z

    118 355 UWAP-BYB

    118 355 UWAP-BYBK

    118 355 UWYP-BYB

    118 355 UWY-AYB

    9 90 UWP-AY3

    79 370 UWA-JATJ

    7.5 75 UWAP-AY3

    79 242

    118 355 UWA-AYB

    UWYP-AY312.5 75

    441 1040 ZUW-AYB

    233 555 ZUW-AYBZ

    UWAP-BYBZ

    Daikin chilling units employ advanced technology that provides highly

    accurate temperature control to within 0.5 . They are widely used in

    applications ranging from air conditioning to industrial equipment.

    Recent changes have introduced new models with substantially

    increased capacities of up to 480 HP and various model series,

    including advanced inverter type units, year-round cooling type units,

    and units with brine-resistant specifications. By providing a full lineup

    of heat source series choices, Daikin offers an even more flexible

    array of solutions for a wide range of heat source applications.

  • 8/2/2019 PCU0610A - Chiller [Small]

    3/16

    Equipped with an Efficient, Durable

    Semi-hermetically Sealed Screw Compressor.

    60,000Sales volume

    Gate Rotor

    ScrewRotor

    SuctionPressure

    SuctionPressure

    Discharge Pressure

    Discharge Pressure

    Equipped with a Newly Developed,

    Highly Efficient Compact C ompressor.Optimization of the unit enhances efficient operation. A newlydeveloped denture mold enabled the production of a compactmodel with reduced volume and weight.

    High Operational Efficiency R educes E nergy Loss.In addition to efficient operation afforded by a 12-compression single cycle, the single screw constructioneliminates blow-by from high to low pressure sections toreduce energy loss. Daikin water chillers are equipped with atightly sealed gate rotor to reduce refrigerant loss fromleakage. Our compressors are designed for efficient operation

    High Accuracy and High Durability.

    Careful construction features gate rotors positioned to theright and left of the screw to eliminate eccentric loadproduced by pressure differential. The orthogonal rotor shaftuses high-precision ball and roller bearings, which extends itslife compared to conventional types. In addition, powertransmission between rotors is reduced, thus eliminatingfriction wear and maintaining stable operating performanceover an extended period of time.

    Low Vibration and Sound Levels.

    Daikin water chillers use gate rotors made of high-performance engineering plastic for smooth meshing with thescrew rotor, thereby reducing shock and vibration. whilemaintaining stable operation. The gate rotors are wellbalanced to equalize pressure, which reduces noise and

    Lightweight Compact Design Save Space.In addition to the simple single rotor construction, thecompact, lightweight design eliminates the need for an oilcooler while incorporating the oil separator into a single partto reduce the space required for setup.

    Durable Construction Increases InspectionIntervals thereby De creasing M aintenance.

    Durability of the equipment increases the maintenance intervalto approximately 40,000 hours (or about seven years). Thesimplified lubrication system, including a high/low pressuredifferential lubrication system and ball and roller bearings,reduces the factors that can contribute to problems. Alongwith increasing the maintenance and inspection interval, thecareful construction of Daikin water chillers enhancesreliability.

    CasingScrew rotor

    Slide valve

    Ball bearingMotor

    Gate rotor

    High efficient oil separatorHigh-low pressure

    differential lubricating mechanism

    Be aring lubricating oil formodels using new refrigerant

    Re frigerant inlet

    Re frigerant outlet

    1

    2

    3

    4

    5

    6

    7

    8

    9

    10

    11

    12

    4

    5

    63

    8

    9

    7

    10

    11

    High Function Microcomputer Control Panel and

    Multifunctional R emote Controller R ealise E fficient

    Operation Control.

    Simple key operation displays re quired operating andsettings data. Displays a complete of operating data foreasy comprehension.

    Up to eight units can be group controlled by a single remote controller.

    Equipped with simultaneous defrost prevention control foravoiding radical water temperature change when operatingmultiple units.*Simultaneous defrost can be carried out for up to two units when five or moreunits are connected.

    Note : Custom orders ma y take more time for delivery.

    Rotation control

    Microcomputer Control Panel Ma kes Operation

    Control Easy.

    Multi-display

    Controls Multiple Units Effectively

    A Multifunctional Liquid Crystal Remote

    Controller for Effective G roup Control.

    Function for Equal Controlusing Microcomputer Control Panel

    Enables different types of remote control, such as controlby commands from the host computer, the DaikinBuilding Air-Conditioning Control System (D-B ACS ), or themultifunctional remote controller.

    Remote Control by Remote Command

    On/Off remote control

    Remote s etting of water temperature

    Setting for heat storage operationYou can switch settings from normal operation to either

    temperature setting for heat storage or control by the external

    Lower noise operation for during nighttimeYou can reduce the operating noise by stopping half the fan.

    Note that the capacity control of the chiller should be limited to

    less than 70%.

    Forced fan operation control*You can force fan operation even when the unit is stopped,

    which is convenient for removing the snow collected on the fan.

    *This function is designed for in areas where snow rarely falls.

    An optional snow hood should be used in areas prone to snow.

    Demand control(1) You can have Three demand controls are possible thermostat

    Off, less than 40% or less than 70%. (Factory set:70%)

    (2)Demand control may also be ac hieved by setting the operating

    current of the compressor.

    *Demand control is available on all models, with the exception of

    those listed below.

    UWAP75 750AY3, UWAXP125 750AY1, UWA37 109JAY1,

    UWA120 270JY1, UWA27 122JATJ, UWYP125 750AY3,

    UWP90 900AY3

    Outdoor temperature

    Inlet/Outlet temperature

    Discharge gas temperature

    Displays operating data for easy comprehension ofsystem status.

    High and low pressure

    Water temperature setting

    Malfunction code

    *For details, refer to the Operation Manual of each model.

    On/Off control

    Water temperature setting

    Switching of operating

    mode

    Defrost cycle setting*

    Heat storage operation

    Enables different types of remote control.

    Low noise operation during

    nighttime

    Forced fan operation

    Demand control*

    Rotation control

    Inspection/Test operation

    Memorizes the number of stops for each unit (therefore noteffective for systems in continuous operation), and smoothsoperation by starting in order from the unit with the leastnumber of starts and stops to increase the life time of allapparatus in the system.

    B R C307 (Option)

    *Applies to a ll models, with the exc eption of those listed below.

    UWA37 109JAY1, UWA120 270JY1,

    UWA27 122JATJ, UWP90 900AY3

    *Demand control is not availablewith

    *Applies to heat-pump type only.

    Outdoor temp.

    Discharge gas temp.

    Water temp. setting

    Inlet/outlet water temp.

    H/L pressure of refrigerant

    Centralized control

    Malfunction code display

    3 4

  • 8/2/2019 PCU0610A - Chiller [Small]

    4/16

    Daikin's C ontrol System for C entral Air C onditioning

    S ystem Offers Appropriate C ontrol for Us e

    and S ize of Building.

    Daikin's intelligent control solution for the whole air

    conditioning system.

    Daikin's Control System for

    Central Air Conditioning.

    Daikin introduces its "C ontrol System for Central Air Conditioning" The sys tem letsyou freely combine a number of optional controllers for centralized control toconstruct the air conditioning control system that is appropriate for your needs. Thesystem executes total central control of chillers and air conditioners, to save

    management labour while realizing ideal central air conditioning performance.

    Different Control Apparatus C ombinations Enable a Multipurpose S ystem.Daikin offers a lineup of centralcontrollers equipped with a variety offunctions. The unified ON/OFF controllerlets you turn equipment on and offindividually or in groups. The scheduletimer lets you program the time forconnected equipment to be turned onand off for each week. Controlapparatus with different functions canbe freely combined, and up to 64groups can be centrally controlled.

    *Number of units that can be

    Note:The system shown above is applicable only to Series UWAJ-G, UWYJ-B, UWAP-G and UWYP-G.Note:Air handling and Fan coil units can be connected by custom orders.

    Centra l remote controller Unif ied ON/OFF controller Schedule timer

    Model

    Stop-running command

    Cooling/heating mode setting

    Temp. setting

    Schedule function

    Interlock setting

    Power proportion limitation

    Stop-running

    Cooling/heating mode

    Temperature set

    Room temp. (suction inlet)

    Water temp. (inlet/outlet)

    Abnormal

    Abnormal signal

    Filter signal

    Continuous running period

    Temp. upper/lower limit

    Standard connection

    Air-cooling Unit

    UWAP,UWYP,UWA,UWY

    Water-cooling Unit

    ZUW

    AIRNET

    DioUnit

    Commodity from other companies

    Pump, Refrigerating Unit, Cooling Tower

    (Note1)

    System Structure(VRV+central conditioning)

    Cool/warm water pump 1Cooling tower 1

    iPU(Reservedfor VRV)

    Ethemet

    VRV(4 ports)

    256 indoor units

    Dio Unit Dio Unit

    Wiring adaptor is required for connecting Dio unit to Airnet

    1. C entral air-conditioning sys tem can be c ontrolledtogether with VRV.

    2. Operating interface is based on the windowsinterface, which is easy to use.

    3. 1024 units (groups) of indoor unit or watercooled chiller can be connected.

    4. Power distribution in proportions, calc ulation thepower rate and other AC-related costs of user.

    5. C an be connected with Air Conditioning NetworkService System

    6. Ordinary 2-core cable is used for wiring, the fieldwiring work is very simple.

    Features of I-Manager

    ( realised function irrespective item only data information, can't be achieved up till now)

    Note1: Can realize partial function of Air Conditioning Network Service System.

    * Please contact Daikin for detaileddata for connection of Fan coiland AC(terminal products)

    Remote controller(units No. control)

    Cool/warm water pump 3

    Monitoring

    function

    Controlling

    function

    Function

    Remote monitorcenter

    Max. 4 iPUsare

    iPU(Reserved for central

    air-conditioningsystem)

    Equipment~pump of othercompany, cooling tower(1

    port)Pump 4 units

    Note: It is not possible to connect a high outdoor temperature specification unit and the UWAP75 750.

    D -NET

    I-Manager

    D -NET

    D -NET

    wiring adaptor

    Water cooled chiller (1 port)Air-cooling 240HP 2 units

    Water-cooling 400US RT 1 unit

    Unified ON/OFF controller

    Chilling unit

    Possible to link withhost computer

    Schedule timer

    SkyAir series

    VRV system

    Central remote controller

    Possible to have a forcedshut-down input

    Enables control of other air conditioning systemssuch as VRV, SkyAir or HRV.

    Enables individual control from chillers to air conditioners by using a single line.

    Enables group control by remote controllers of both chillers and air conditioners.

    Lets you develop a system that doesn't use individual remote controllers.(Central remote controller required)

    Air handling unit Air handling unit Fan coil unit Possiblewireless remote controller

    System configuration

    D adaptorI-Manager option

    Control Function List of I-Manager

    I-Manager Control heat resources system by using I-Manager

    New VersionNew Version

    5 6

  • 8/2/2019 PCU0610A - Chiller [Small]

    5/16

    Model Lineup

    50Hz

    60Hz

    50Hz

    60Hz

    50Hz

    60Hz

    50Hz

    60Hz

    R-407C

    R-22

    Standard Unit

    Year - Round Cooling

    Only Unit

    Brine Cooling Unit

    Standard Unit

    Refrigerant Uni ts ser ie s Mod el No.

    UWAPBY1

    UWAPBYB

    UWAPBY1K

    UWAPBYBK

    UWAPBY1Z

    UWAPBYBZ

    UWAAY1

    UWAAYB

    Capacity (kW)

    9, 10

    10

    11

    12

    12, 13

    13

    14, 15

    15

    page315

    120

    120

    120

    120

    120

    120

    120

    120

    370

    140

    140

    140

    140

    420

    160

    160

    160

    160

    480

    180

    180

    180

    180

    530

    200

    200

    200

    200

    580

    220

    220

    220

    220

    630

    240

    240

    240

    240

    740

    280

    280

    280

    280

    840

    320

    320

    320

    320

    960

    360

    360

    360

    360

    1060

    400

    400

    400

    400

    1160

    440

    440

    440

    440

    1260

    480

    480

    480

    480

    50/60Hz

    50Hz

    60Hz

    50Hz

    60Hz

    50Hz

    60Hz

    50Hz

    50Hz

    60Hz

    Refrigerant

    R-407C

    R-22

    Units series

    Standard Unit

    Year - Round Cooling

    Only Unit

    Brine Cooling Unit

    Inverter Cooling Unit

    Standard Unit

    Model No.

    UWAPAY3*

    UWAPBY1

    UWAPBYB

    UWAPBY1K

    UWAPBYBK

    UWAPBY1Z

    UWAPBYBZ

    UWAXPAY1

    UWAAY1

    UWAAYB

    Capacity (kW)

    6.7/7.5

    75

    11.2/12.5

    125

    125

    17/19

    190

    190

    22.4/25

    250

    250

    33.5/37.5

    375

    375

    45/50

    500

    500

    56/63

    630

    630

    67/75

    750

    750

    106

    40

    40

    40

    40

    40

    40

    40

    40

    132

    50

    50

    50

    50

    50

    50

    50

    50

    160

    60

    60

    60

    60

    60

    60

    60

    60

    212

    80

    80

    80

    80

    265

    100

    100

    100

    100

    100

    100

    100

    100

    9

    9, 10

    10

    11

    12

    12, 13

    13

    14

    14, 15

    15

    page

    Note: Capacity figures are provided for reference and assume a power supply frequency of 60 Hz.

    Employs the new refrigerant R-407C.

    UWAP75 750AY3UWAXP125 750AY1UWAP40 480BY1(K)(Z)UWAP40 120BYB (K)(Z)

    New Refrigerant Efficient and Reliable Compressors

    To improve their operationa l reliability, 5 -- 30HP modelsemploy scroll compressors, while 40 -- 480HP models areequipped with semi-hermetic single screw compressors.

    Refrigerant inlet

    Refrigerant outlet

    Semi-hermetic singlescrew compressor

    The user can select to give priority to either precision orreduced power consumption.

    Continues ope ration to levelsas low as 10(12)% of totalcapacity to provide stablewater temperature controleven during low-load peri-ods.

    This mode can be used to re-duce power consumption ifhighly precise water temperature control is not necessary dur-ing low-load periods. It shutsdown the compressor when theload drops below 40%.

    High-P recis ion Mode Low-P ower Mode

    Note: Switching between the above modes is accomplished using a control on

    the outdoor unit.

    Multiple Operating Modes

    RefrigerantInlet

    RefrigerantOutlet

    WaterOutlet

    WaterInlet

    Heat Exchanger withStainless Steel Plates

    Stainless s teel heat ex-changer plates prevent rust,thereby improving their dura-bility and the system's op-

    Reliability

    Applies to All Models

    The compact design of these units significantly reduces thespace required for installation.

    The horizontal linkup design increases installation flexibility.

    In the outdoor unit, component parts of a small size have been used wherever

    possible to reduced its size and correspondingly reduce how much space it re-

    quires. Furthermore, replacing the 2-way refrigerant inlets with 4-way inlets has

    reduced the amount of space the outdoor unit needs even further.

    This design provides the installation does not protrude so far, making it possible

    to install water chillers along a wall or under a roof overhang.

    Note: Water supply piping must be purchased separately.

    (UWAP375AY3 750AY3)

    UWAP40 480BY1 (K)(Z)UWAP40 120BYB (K)(Z)

    Easy Installation

    UWAP125AY3 750AY3

    High load compliance and highly efficient inverter control provide highly precise

    adjustment of the water temperature, making it possible to reduce the size of

    the peripheral equipment.

    UWAXP125 750AY1

    Compressor duty cycling control together with emergencyoperation and power-interruption auto-restart functions pro-vide enhanced air conditioning system reliability.

    UWA40 480AY1UWA40 120AYB

    A choice of three control system is available.

    UWA40 480AY1

    Outflow water temperature control

    Provides precise control of the water temprerature.

    (UWAP40 160BY1, UWA40 160AY1)

    Compressor count control

    Controls the number of compressors operating depending on the load.

    (UWAP40 480BY1, UWA40 480AY1)

    In flow water temperature control

    Performs duty cycling control.

    (UWAP40 480BY1, UWA40 480AY1)

    Reduced Energy Wastage

    Continuous c apacity control with a range from 10% to100% helps to reduce energy wastage during low-load

    UWAP40 160BY1 (K)(Z)UWAP40 120BYB (K)(Z)

    UWAP40 160BY1 (K)(Z)UWAP40 120BYB (K)(Z)

    UWA40 160AY1UWA40 120AYB

    UWA40 480AY1UWAP40 120AYB

    UWAP40 480BY1 (Z)UWAP40 120BYB (Z)

    UWAP40 480BY1

    CapacityWater Temperature Control Range

    Models Employing R-407C Models Employing R-22

    3 30

    40 480

    5 to 16

    4 to 25 (Inver Cooling Unit)

    4 to 25-10 to 0 (Brine Cooling Unit)

    4 to 16

    Wide Water Temperature Control Range

    The wide water temperature control range providescompatibility with a variety of heat source requirements.

    A variety of brine-resistant specification models are availablethat provide stable cooling operation at brine outflowtemperatures down to -10 .

    Applies to All Models

    Applies to All Models

    UWAP120BY1KUWAXP 750AY1 UWAP 180B Y 1

    Wide Operation Range

    A variety of year-round cooling type models are availablethat provide stable operation at outdoor temperatures down

    The wide outdoor air temperature range ensures a stablesupply of chilled water year round.

    Applies to All Models

    CapacityOutdoor Air Temperature Range where Cooling Possible

    Models Employing R-407C Models Employing R-22

    3 30

    40 480

    -15 to 43

    -5 to 43

    -15 to 43

    ( Y ear-Round Cooling Only Unit )

    0 to 43 ( Brine Cool ing Unit )

    -5 to 43

    High Precision

    10

    9

    8

    7

    Upper Limit Signal

    Water T e mp. ( )

    Example of Outlet Water Temperature Control

    If outlet water temperature rises above the upper limit signal,the load starts to increase in 10% inc rements

    As the temperaturefalls below the upperlimit signal, the loadincrease incrementsare reduced to 5%.

    As the temperaturefalls below the setvalue, the loadincrease incrementsre main at 5%.

    When changes inoutlet watertemperature become1 or less, thethermostat is turned off.

    Value Set

    The outlet water temperature is precisely controlled to within0.5(with a stable load) through the use of electric expansion

    UWAXP125 750AY1

    UWAP40 160BY1 (K)(Z)UWAP40 120BYB (K)(Z)

    UWA40 160AY1UWA40 120AYB

    Inverter control with high load compliance achieves highlyaccura te outflow water temperature control to within 0.5

    Note: In systems with one compressor installed and where the load factor is 30%

    or more, and in systems with two or more compressors installed and where the

    load factor is 30% or more, control to within 0.5 is possible.

    AirCooled

    WaterChillers

    AirCooled

    WaterChillers

    Air Cool

    ed Water Chillers

    : UWAP S eries UWAXP Series

    : UWA Series

    7 8

  • 8/2/2019 PCU0610A - Chiller [Small]

    6/16

    10

    AirCooled

    WaterChillers

    AirCooled

    WaterChillers

    Notes:*1 Cooling capacity is based on the following conditions : Leaving chilled water temp.7 (44.5 F), entering chilled water temp.12 (53.6 F), and outdoor air temp. 35 DB(95 FDB).*2 The following safety devices are equipped as standard. High pressure protector. Low pressure protector. Compressor thermal protector. Fusible plug. Reverse-phaseprotector.

    Overheat protection of discharge gas. Overcurrent relay(compressor). Freeze-up protection thermostat. Overcurrent relay(fan). Safety valve.*3 The unit is equipped with standard water filt er.*4 This product is manufactured in China.

    Specifications

    kW

    Btu/h

    USRT

    /min

    %

    kW

    m3/min

    cfm

    kW

    mm

    kg

    kg

    Model

    Cooling capacity

    Power supply

    Chilled water flow rate

    Capacity steps

    Compressor

    Evaporator type

    Condenser type

    Condenser

    fan

    Refrigerant

    Pipe connections water

    inlet/outlet

    Dimensions(H W D)

    Weight

    Operating weight

    Operation range

    Type

    Motor output

    Type

    Drive

    Air flow rate

    Motor output

    118 355kW class

    UWAP40 120BYBStandard Unit

    60Hz

    UWAP40BYB

    (40 )

    UWAP50BYB

    (50 )

    UWAP60BYB

    (60 )

    UWAP100BYB

    (100 )

    UWAP120BYB

    (120 )

    118

    403,000

    34

    3 phase, 60 Hz 400/440 V, 4 wires s ystem

    338

    100~10-0

    Semi-hermetic sealed single-screw type

    30 1

    Brazing Plate type

    Cross fin coil

    Propeller

    Direct drive

    810

    28,593

    0.5 4

    R-407C

    3B Flange (80A HG20593-97)

    2,456 2,200 2,000

    1,690

    1,723

    0 to 43

    150

    512,000

    43

    430

    37 1

    1,010

    35,653

    1.0 4

    1,810

    1,846

    180

    614,000

    51

    516

    45 1

    1,870

    1,910

    300

    1,024,000

    85

    860

    37

    2

    2,020

    71,306

    1.0 8

    4B Flange (100A HG20593-97)

    2,456 4,400 2,000

    3,500

    3,551

    355

    1,212,000

    101

    1,018

    45 2

    3,605

    3,662

    Notes:*1 Cooling capacity is based on the following conditions : Leaving chilled water temp.7 (44.5 F), entering chilled water temp.12 (53.6 F), and outdoor air temp. 35 DB(95 FDB).*2 The following safety devices are equipped as standard. High pressure protector. Low pressure protector. Compressor thermal protector. Fusible plug. Reverse-phaseprotector.

    Overheat protection of discharge gas. Overcurrent relay(compressor). Freeze-up protection thermostat. Overcurrent relay(fan). Safety valve.*3 The unit is equipped with standard water filt er.*4 This product is manufactured in China.

    530 1,260kW class

    UWAP200 480BY1Standard Unit

    50Hz

    Specifications

    kW

    Btu/h

    USRT

    /min

    %

    kW

    m3/min

    cfm

    kW

    mm

    kg

    kg

    Type

    Motor output

    Type

    Drive

    Air flow rate

    Motor output

    UWAP200BY1

    (200 )UWAP220BY1

    (220 )UWAP240BY1

    (240 )UWAP280BY1

    (280 )UWAP320BY1

    (320 )

    UWAP360BY1

    (360 )UWAP480BY1

    (460 )

    530

    1,809,000

    151

    3 phase, 50 Hz 380/400/415 V, 4 wires s ystem

    1,519

    100~10-0

    Semi-hermetic sealed single-screw type

    45 2+60

    Brazing Plate type

    Cross fin coil

    Propeller

    Direct drive

    3,010

    106,253

    1.0 14

    R-407C

    5B Flange (125A HG20593-97)

    2,456 7,050

    2,000

    6,000

    6,198

    0 to 43

    UWAP400BY1

    (400 )UWAP440BY1

    (440 )Model

    Cooling capacity

    Power Supply

    Chilled Water Flow Rate

    Capacity Steps

    Compressor

    Evaporetor type

    Comdenser type

    Condenser

    fan

    Refrigerant

    Pipe connections water

    inlet/outlet

    Dimensions(H W D)

    Weight

    Operation weight

    Operation range

    580

    1,979,000

    165

    1,663

    45+60 2

    3,440

    121,432

    1.0 16

    2,456 7,500

    2,000

    6,500

    6,719

    630

    2,150,000

    179

    1,806

    60 3

    3,870

    136,611

    1.0 18

    2,456 7,950

    2,000

    7,005

    7,245

    740

    2,525,000

    210

    2,121

    (45+60) 2

    4,300

    151,790

    (1.0 10) 2

    4B Flange

    (100A HG20593-97)

    (2,456 4,850

    2,000) 2

    4,125 2

    4,196 2

    840

    2,867,000

    239

    2,408

    (60 2) 2

    5,160

    182,148

    (1.0 12) 2

    (2,456 5,300

    2,000) 2

    4,590 2

    4,661 2

    960

    3,276,000

    273

    2,752

    (45 3) 2

    5B Flange (125A HG20593-97)

    (2,456 6,600

    2,000) 2

    5,500 2

    5,691 2

    1,060

    3,617,000

    301

    3,039

    (45 2+60) 2

    6,020

    212,506

    (1.0 14) 2

    (2,456 7,050

    2,000) 2

    6,000 2

    6,198 2

    1,160

    3,959,000

    330

    3,325

    (45+60 2) 2

    6,880

    242,864

    (1.0 16) 2

    (2,456 7,500

    2,000) 2

    6,500 2

    6,719 2

    1,260

    4,300,000

    358

    3,612

    (60 3) 2

    7,740

    273,222

    (1.0 18) 2

    (2,456 7,950

    2,000) 2

    7,005 2

    7,245 2

    Notes:*1 Cooling capacity is based on the following conditions : Leaving chilled water temp.7 (44.5 F), entering chilled water temp.12 (53.6 F), and outdoor air temp. 35 DB(95 FDB).*2 The following safety devices are equipped as st andard. High pressure protector. Low pressure protector. Compressor thermal protector. Fusible plug. Reverse-phaseprotector.

    Overheat protection of discharge gas. Overcurrent relay(compressor). Freeze-up protection thermostat. Overcurrent relay(fan). Safety valve.*3 The unit is equipped with standard water filter.*4 This product is manufactured in China.

    Specifications

    kW

    Btu/h

    USRT

    /min

    %

    kW

    m3/min

    cfm

    kW

    mm

    kg

    kg

    Type

    Motor output

    Type

    Drive

    Air flow rate

    Motor output

    UWAP40BY1

    (40 )UWAP50BY1

    (50 )UWAP60BY1

    (60 )UWAP80BY1

    (80 )UWAP100BY1

    (100 )

    UWAP120BY1

    (120 )UWAP180BY1

    (180 )

    106

    362,000

    30

    3 phase, 50 Hz 380/400/415 V, 4 wires s ystem

    304

    100~10-0

    Semi-hermetic sealed single-screw type

    30 1

    Brazing Plate type

    Cross fin coil

    Propeller

    Direct drive

    780

    27,534

    0.5 4

    R-407C

    3B Flange (80A HG20593-97)

    2,456 2,200 2,000

    1,690

    1,723

    0 to 43

    UWAP140BY1

    (140 )UWAP160BY1

    (160 )

    106 480kW class

    UWAP40 180BY1Standard Unit

    50Hz

    Model

    Cooling capacity

    Power Supply

    Chilled Water Flow Rate

    Capacity Steps

    Compressor

    Evaporetor type

    Comdenser type

    Condenser

    fan

    Refrigerant

    Pipe connections water

    inlet/outlet

    Dimensions(H W D)

    Weight

    Operation weight

    Operation range

    132

    450,000

    38

    378

    37 1

    860

    30,358

    1.0 4

    1,810

    1,846

    160

    546,000

    46

    459

    45 1

    1,870

    1,910

    210

    717,000

    60

    602

    60 1

    1,290

    45,537

    1.0 6

    2,456 2,650

    2,000

    2,375

    2,422

    265

    904,000

    75

    760

    37 2

    1,600

    56,480

    1.0 8

    4B Flange (100A HG20593-97)

    2,456 4,400 2,000

    3,500

    3,551

    320

    1,092,000

    91

    917

    45

    2

    1,720

    60,716

    3,605

    3,662

    370

    1,263,000

    105

    1,061

    45+60

    2,150

    75,895

    1.0 10

    2,456 4,850

    2,000

    4,125

    4,196

    420

    1,433,000

    119

    1,204

    60 2

    2,580

    91,074

    1.0 12

    2,456 5,300

    2,000

    4,590

    4,661

    480

    1,638,000

    137

    1,376

    45 3

    5BFlange

    (125AHG20593-97 )

    2,456 6,600

    2,000

    5,500

    5,691

    Notes:*1 Cooling capacity is based on the following conditions : Leaving chilled water temp.7 (44.5 F), entering chilled water temp.12 (53.6 F), and outdoor air temp. 35 DB(95 FDB).*2 The following safety devices are equipped as standard. High pressure switch. Reverse-phase protector. Fusible plug. Freeze up thermostat. Overcurrent relay for compressor

    and fan motor. Overheat protection for discharge gas. fan thermal protector.*3 This product is manufactured in Japan.

    Specifications

    kW

    Btu/h

    USRT

    /min

    %

    kW

    m3/min

    cfm

    kW

    mm

    kg

    kg

    Model

    Cooling capacity

    (50/60 Hz)

    Power supply

    Chilled water flow rate

    (50/60 Hz)

    Capacity steps

    Compressor

    Evaporator type

    Condenser type

    Condenser

    fan

    Refrigerant

    Pipe connections water

    inlet/outlet

    Dimensions (H W D)

    Weight

    Operating weight

    Operation range

    Type

    Motor output

    Type

    Drive

    Air flow rate

    (50/60 Hz)

    Motor output

    UWAP75AY3

    (3 )

    UWAP125AY3

    (5 )

    UWAP190AY3

    (8 )UWAP250AY3

    (10 )

    UWAP375AY3

    (15 )UWAP750AY3

    (30 )

    6.7/7.5

    22,900/25,600

    1.91/2.13

    3 phase, 50 Hz 380/400/415 V, 60 Hz 400/440 V, 3 w ires system

    19/22

    100-0

    Hermetically sealed scroll type

    2.2 1

    Brazed plate heat exchanger

    Cross fin coil

    Propeller

    Direct drive

    75/85

    2,650/3,000

    0.14 1

    R-407C

    1B Flange (JIS10K)(25A) 2

    1,450 635(839) 690

    136

    138

    -15 to 43

    11.2/12.5

    38,200/42,700

    3.19/3.55

    32/36

    3.75 1

    90/95

    3,180/3,350

    0.20 1

    140

    142

    17.0/19.0

    58,000/64,900

    4.83/5.40

    49/54

    5.5 1

    140/160

    4,940/5,650

    0.215+0.14

    1 1/2B Flange (JIS10K)(40A) 2

    1,450 1,280 690

    248

    253

    22.4/25.0

    76,500/85,400

    6.37/7.11

    64/72

    7.5 1

    175/185

    6,180/6,530

    0.215+0.22

    260

    264

    33.5/37.5

    114,000/128,000

    9.53/10.7

    96/108

    100-67-34-0

    7.5+3.75

    265/280

    9,350/9,880

    (0.215+0.22)+0.2

    1B Flange (JIS10K)

    (25A) 2+11/2BFlange

    (JIS10K)(40A) 2

    1,500 1,925 690

    400

    407

    45.0/50.0

    154,000/171,000

    12.8/14.2

    129/143

    100-50-0

    7.5 2

    350/370

    12,400/13,100

    (0.215+0.22) 2

    1 1/2B Flange

    (JIS10K)(40A) 4

    1,500 2,570 690

    515

    525

    56.0/63.0

    191,000/215,000

    15.9/17.9

    161/181

    100-80-60-40-20-0

    7.5 2+3.75

    440/465

    15,500/16,400

    (0.215+0.22) 2+0.2

    1B Flange (JIS10K)

    (25A) 2+11/2BFlange

    (JIS10K)(40A) 4

    1,550 3,230 758

    680

    695

    67.0/75.0

    229,000/256,000

    19.1/21.3

    192/215

    100-67-34-0

    7.5 3

    525/555

    18,500/19,600

    (0.215+0.22) 3

    1 1/2B Flange

    (JIS10K)(40A) 6

    1,550 3,870 758

    800

    820

    UWAP500AY3

    (20 )

    UWAP630AY3

    (25 )

    *1

    6.7/7.5 67/75kW class

    UWAP75 750AY3Standard Unit

    50/60Hz

    9

    Air Cooled Water Chillers

  • 8/2/2019 PCU0610A - Chiller [Small]

    7/16

  • 8/2/2019 PCU0610A - Chiller [Small]

    8/16

  • 8/2/2019 PCU0610A - Chiller [Small]

    9/16

    UWAP40BY1

    UWAP40BYB

    UWAP50BY1

    UWAP50BYB

    UWAP60BY1

    UWAP60BYBUWAP80BY1

    UWAP100BY1

    UWAP100BYB

    UWAP120BY1

    UWAP120BYBUWAP140BY1 UWAP160BY1 UWAP180BY1

    Model

    Remote controller

    Communication I/F P.C. board

    Communication I/F P.C. B storage box

    Transmission wire

    Central remote controller

    Unified ON/OFF controller

    Schedule timer

    BRC307C50

    BRP66B3 1

    BRP66A97 1(external)

    BER66A5 1

    DCS302CA61

    DCS301BA61

    DST301BA61

    BRP66A100 1(internal)

    BER66A7 1

    Not required (S.Box installed)

    UWAP75AY3 UWAP125AY3 UWAP190AY3 UWAP250AY3 UWAP375AY3 UWAP500AY3 UWAP630AY3 UWAP750AY3

    *1

    *1

    *1

    *1

    Model

    Remote controller

    Chillingwatersupplyinterruptingrelay

    Waterhigh pressure (1.6 MPa)upgrader

    IPU

    Dio unit

    D Air unit

    Interface for use in L ONWORKS

    Interface for use in BACnet

    Central remote controller

    Unified ON/OFF controller

    Schedule timer

    BRC307D503

    GWEL-UWYP40B

    GWP-UWYP40B

    DAM602A5

    DEC102A

    DAM101A

    DMS504B51

    DMS502A51

    DCS302CA61

    DCS301BA61

    DST301BA61

    GWP-UWYP80B

    GWEL-UWYP100B

    GWP-UWYP100B

    GWEL-UWYP180B

    GWP-UWYP180B

    UWAP200BY1 UWAP220BY1 UWAP240BY1 UWAP280BY1 UWAP320BY1 UWAP360BY1 UWAP400BY1 UWAP440BY1 UWAP480BY1Model

    Remote controller

    Chillingwatersupplyinterruptingrelay

    Waterhigh pressure (1.6 MPa)upgrader

    IPU

    Dio unit

    D Air unit

    Interface for use in LONWORKS

    Interface for use in BACnet

    Central remote controller

    Unified ON/OFF controller

    Schedule timer

    BRC307D503

    GWEL-UWYP180B

    GWP-UWYP180B

    DAM602A5

    DEC102A

    DAM101A

    DMS504B51

    DMS502A51

    DCS302CA61

    DCS301BA61

    DST301BA61

    GWEL-UWYP280B

    GWP-UWYP280B

    GWEL-UWYP360B

    GWP-UWYP360B

    Notes:*1 Communication I/F P.C. board, Communication I/F P.C. B storage box and Transmission w ire are also required.

    Model

    Remote controller *1

    Communication I/F P.C. board

    Communication I/F P.C. B storage box

    Transmission wire

    UWAXP125AY1

    UWA40AY1

    UWA40AYB

    UWA50AY1

    UWA50AYB

    UWA60AY1

    UWA60AYBUWA80AY1

    UWA100AY1

    UWA100AYB

    UWA120AY1

    UWA120AYBUWA140AY1 UWA160AY1 UWA180AY1

    UWAXP190AY1 UWAXP250AY1 UWAXP375AY1 UWAXP500AY1 UWAXP630AY1 UWAXP750AY1

    BRC307C50

    BRP66B3 1

    BER66A5

    BPR66A97

    BER66A6

    BER66A7

    BRP66B3 2

    BRP66A96

    BER66A8

    Model

    Remote controller

    Chillingwatersupplyinterruptingrelay

    Waterhigh pressure (1.6 MPa)upgrader

    IPU

    Dio unit

    D Air unit

    Interface for use in LONWORKS

    Interface for use in BACnet

    Central remote controller

    Unified ON/OFF controller

    Schedule timer

    Model

    Remote controller

    Chillingwatersupplyinterruptingrelay

    Waterhigh pressure (1.6 MPa)upgrader

    IPU

    Dio unit

    D Air unit

    Interface for use in LONWORKS

    Interface for use in BACnet

    Central remote controller

    Unified ON/OFF controller

    Schedule timer

    UWA200AY1 UWA220AY1 UWA240AY1 UWA280AY1 UWA320AY1 UWA360AY1 UWA400AY1 UWA440AY1 UWA480AY1

    BRC307D503

    GWEL-UWY40A

    GWP-UWY40A

    DAM602A5

    DEC102A

    DAM101A

    DMS504B51

    DMS502A51

    DCS302CA61

    DCS301BA61

    DST301BA61

    BRC307D503

    GWEL-UWY180A

    GWP-UWY180A

    DAM602A5

    DEC102A

    DAM101A

    DMS504B51

    DMS502A51

    DCS302CA61

    DCS301BA61

    DST301BA61

    GWEL-UWY80A

    GWP-UWY80A GWP-UWY100A

    GWEL-UWY180A

    GWP-UWY180A

    GWEL-UWY280A

    GWEL-UWY281A

    GWEL-UWY360A

    GWP-UWY360A

    Notes:*1 Communication I/F P.C. board, Communication I/F P.C. B storage box and Transmission waire are also required.

    Option List

    Specifications

    kW

    Btu/h

    USRT

    /min

    %

    kW

    m3/min

    cfm

    kW

    mm

    kg

    kg

    Model

    Cooling capacity

    Power supply

    Chilled water flow rate

    Capacity steps

    Compressor

    Evaporator type

    Condenser type

    Condenser

    fan

    Refrigerant

    Pipe connections water

    inlet/outlet

    Dimensions (H W D)

    Weight

    Operating weight

    Operation range

    Type

    Motor output

    Type

    Drive

    Air flow rate

    Motor output

    Notes:*1 Cooling capacity is based on the following conditions : Leaving chilled water temp.7 (44.5 F), entering chilled water temp.12 (53.6 F), and outdoor air temp. 35 DB(95 FDB).*2 The following safety devices are equipped as standard. High pressure protector. Low pressure protector. Compressor thermal protector. Fusible plug. Reverse-phaseprotector.

    Overheat protection of discharge gas. Overcurrent relay(compressor). Freeze-up protection thermostat. Overcurrent relay(fan). Safety valve.*3 The unit is equipped with standard water filt er.*4 The limited length of wire represents its max. length when the pressure is lower than 2%.*5 This product is manufactured in China.

    *1

    118 355kW class

    UWA40 120AYBStandard Unit

    60Hz

    UWA120AYB

    (120 )

    UWA100AYB

    (100 )

    UWA60AYB

    (60 )UWA50AYB

    (50 )

    UWA40AYB

    (40 )

    118

    403,000

    34

    3 phase, 60 Hz 400/440 V, 4 wires s ystem

    338

    100~10-0 (continuous capacity control)

    Semi-hermetic sealed single-screw type

    30 1

    Blazing Plate type

    Cross fin coil

    Propeller

    Direct drive

    800

    28,240

    0.5 4

    R-22

    3B Flange (80A)

    2,395 2,200 2,000

    1,500

    1,517

    -5 to 43

    150

    512,000

    43

    430

    37 1

    810

    28,593

    0.8 4

    1,650

    1,670

    180

    614,000

    51

    516

    45 1

    940

    33,182

    1.2 4

    1,750

    1,773

    300

    1,024,000

    85

    860

    37 2

    1,620

    57,186

    0.8 8

    4B Flange (100A)

    2,395 4,400 2,000

    3,300

    3,336

    355

    1,212,000

    101

    1,018

    45 2

    1,880

    66,364

    1.2 8

    3,500

    3,542

    Specifications

    kW

    Btu/h

    USRT

    /min

    %

    kW

    m3/min

    cfm

    kW

    mm

    kg

    kg

    Model

    Cooling capacity

    Power supply

    Chilled water flow rate

    Capacity steps

    Compressor

    Evaporator type

    Condenser type

    Condenser

    fan

    Refrigerant

    Pipe connections water

    inlet/outlet

    Dimensions(H W D)

    Weight

    Operating weight

    Operation range

    Type

    Motor output

    Type

    Drive

    Air flow rate

    Motor output

    UWA200AY1

    (200 )UWA220AY1

    (220 )UWA240AY1

    (240 )UWA280AY1

    (280 )UWA320AY1

    (320 )UWA360AY1

    (360 )UWA480AY1

    (480 )

    530

    1,809,000

    151

    3 phase, 50 Hz 380/400/415 V, 4 wires system

    1,519

    100~10-0 (continuous capacity control)

    Semi-hermetic sealed single-screw type

    45 2+60

    Blazing Plate type

    Cross fin coil

    Propeller

    Direct drive

    2,620

    92,486

    1.2 12

    R-22

    5B Flange (125A HG20593-97)

    2,460 6,600 2,000

    5,660

    5,737

    -5 to 43

    580

    1,979,000

    165

    1,663

    45+60 2

    2,720

    96,016

    5,695

    5,782

    630

    2,150,000

    179

    1,806

    60 3

    2,820

    99,546

    5,750

    5,850

    840

    2,867,000

    239

    2,408

    (60 2) 2

    3.760

    132,728

    3,640 2

    3,704 2

    960

    3,276,000

    273

    2,752

    (45 3) 2

    5,040

    177,912

    (1.2 12) 2

    5B Flange (125A HG20593-97)

    (2,460 6,600 2,000) 2

    5,605 2

    5,670 2

    1,060

    3,617,000

    301

    3,039

    (45 2+60) 2

    5,240

    184,972

    5,660 2

    5,737 2

    1,160

    3,959,000

    330

    3,325

    (45+60 2) 2

    5,440

    192,032

    5,695 2

    5,782 2

    1,260

    4,300,000

    358

    3,612

    (60 3) 2

    5,640

    199,092

    5,750 2

    5,850 2

    UWA400AY1

    (400 )UWA440AY1

    (440 )

    Notes:*1 Cooling capacity is based on the following conditions : Leaving chilled water temp.7 (44.5 F), entering chilled water temp.12 (53.6 F), and outdoor air temp. 35 DB(95 FDB).*2 The following safety devices are equipped as standard. High pressure protector. Low pressure protector. Compressor thermal protector. Fusible plug. Reverse-phaseprotector.

    Overheat protection of discharge gas. Overcurrent relay(compressor). Freeze-up protection thermostat. Overcurrent relay(fan). Safety valve.*3 Standard for the max. chilled water pressure is 0.7MPa, but1.6MPa is available if required.*4 Installation/operating weight includes the weight of refrigerant and refrigerant oil(charged before delivery).

    740

    2,525,000

    210

    2,121

    (45+60) 2

    3,560

    125,668

    (1.2 8) 2

    4B Flange (100A HG20593-97)

    (2,395 4,400 2,000) 2

    3,620 2

    3,684 2

    *1

    530 1,260kW class

    UWA200 480AY1Standard Unit

    50Hz

    AirCooled

    WaterChillers

    AirCooled

    WaterChillers

    15 16

    Air Cooled Water Chillers

  • 8/2/2019 PCU0610A - Chiller [Small]

    10/16

    For High Outdoor Temperature Use

    Specifications

    Model

    Cooling capacity

    Power supply

    Chilled water flow rate

    Cooling capacity

    Chilled water flow rate

    Capacity steps

    Compressor

    Evaporator type

    Condenser type

    Condenser

    fan

    Refrigerant

    Pipe connections water inlet/outlet

    Dimensions (H W D)

    Weight

    Operating weight

    Operation range

    kW

    Btu/h

    USRT

    kW

    Btu/h

    USRT

    %

    kW

    m3/min

    cfm

    kW

    mm

    kg

    kg

    Type

    Motor output

    Type

    Drive

    Air flow rate

    Motor output

    UWA27JATJ

    (25 )

    79.0

    269,800

    22.4

    3 phase, 60 Hz, 208/230 V, 3 wires system

    206

    71.0

    242,000

    20.1

    185

    100-50-0

    Semi-hermetically sealed reciprocating

    22

    Dry expansion shell and Hi-X tube

    Cross fin coil (Waffle louver fins and Hi-X tubes)

    Propeller

    Direct drive

    580

    20,480

    1.7ea. 2

    R-22

    FPT2 (50A)

    1,765 2,025

    1,065

    750

    790

    15 to 49

    UWA32JATJ

    (30 )UWA43JATJ

    (40 )UWA53JATJ

    (50 )UWA62JATJ

    (60 )UWA70JATJ

    (70 )UWA80JATJ

    (80 )UWA90JATJ

    (90 )UWA108JATJ

    (100 )UWA122JATJ

    (120 )

    94.3

    320,600

    26.7

    245

    82.0

    280,900

    23.4

    215

    100-66-33-0

    480

    16,950

    1.0ea. 2

    1,915 2,025

    1,065

    900

    970

    125.0

    426,600

    35.5

    326

    111.0

    378,900

    31.5

    289

    30

    1,160

    40,960

    1.0ea. 4

    FPT2 1/2 (65A)

    1,890 2,005 2,000

    1,300

    1,370

    5 to 49

    162.0

    553,500

    46.1

    423

    145.0

    494,000

    41.0

    377

    100-75-50-25-0

    37

    1.7ea. 4

    1,540

    1,630

    185.0

    632,100

    52.6

    483

    171.0

    584,100

    48.6

    466

    45

    1,400

    49,430

    2.5ea. 4

    FPT3 (80A)

    1,610

    1,700

    212.0

    722,200

    60.0

    552

    191.0

    653,100

    54.2

    497

    100-83-66-50-33-0

    26 2

    1,920

    67,800

    1.0ea. 8

    4B Flange (JIS16K)(100A)

    1,745 2,005

    4,000

    2,500

    2,600

    15 to 49

    253.0

    865,000

    72.0

    661

    219.0

    746,400

    62.1

    570

    30 2

    1,915 2,005 4,000

    2,600

    2,730

    274.0

    936,400

    78.0

    715

    248.0

    845,200

    70.4

    645

    100-88-75-63-50-25-0

    2,850

    2,980

    324.0

    1,107,000

    92.2

    845

    285.0

    972,200

    81.0

    742

    37 2

    2,320

    81,920

    1.7ea. 8

    5B Flange (JIS16K)(125A)

    2,870

    3,000

    370.0

    1,262,000

    105.0

    964

    335.0

    1,145,000

    95.3

    873

    45 2

    2,800

    98,870

    2.5ea. 8

    3,050

    3,210

    Notes:*1 Cooling capacity is based on the following conditions : Leaving chilled water temp.6.7 (44 F), entering chilled water temp.12.2 (54 F), and outdoor air temp. 35 DB(95 FDB).*2 Cooling capacity is based on the following conditions : Leaving chilled water temp.6.7 (44 F), entering chilled water temp.12.2 (54 F), and outdoor air temp. 46 DB(115 FDB).*3 The following safety devices are equipped as st andard. High/low pressure switch. Oil pressure control switch. Compressor thermal protector. Recycling guard timer.

    Crankcase heater. 3-element overcurrent relay for compressors and fan motors. Freeze-up protection thermostat. Fusible plug. Safety valve(for UWA53, 62, 90, 108,122JATJ).

    *4 This product is manufactured in Japan.

    *1

    *2

    79 370kW class

    UWA27 122JATJFor High Outdoor Temperature Use

    60Hz

    Specifications

    Model

    Cooling capacity

    Power supply

    Chilled water flow rate

    Compressor

    Evaporator type

    Condenser type

    Condenser

    fan

    Refrigerant

    Pipe connections water inlet/outlet

    Dimensions (H W D)

    Weight

    Operation range

    Type

    Motor output

    Type

    Drive

    Air flow rate

    Motor output

    kW

    Btu/h

    USRT

    kW

    m3/min

    cfm

    kW

    mm

    kg

    351.6

    1,201,500

    99.9

    3 phase, 50 Hz 380/400/415 V, 4 wires system

    100-83-67-50-33-17-0

    Semi-hermetic sealed reciprocating

    30 3

    Dry expansion shell and Hi-X tubes

    Cross fin coil (Waffle louver fins and Hi-X tubes)

    Propeller

    Direct drive

    2,580

    91,100

    0.9ea. 12

    R-22

    5B Flange (JIS16K)(125A)

    2,095 2,005 5,700

    4,360

    5 to 49

    404.4

    1,380,800

    115.0

    37 3

    3,000

    105,900

    4,470

    474.7

    1,620,600

    135.0

    45 3

    3,720

    131,400

    1.5ea. 12

    4,660

    562.8

    1,921,500

    160.0

    100-88-75-63-50-25-0

    37 4

    Dry expansion shell and corrugated tubes

    4,000

    141,300

    0.9ea. 16

    2,075 2,005 8,000

    6,110

    667.9

    2,280,400

    189.9

    45 4

    4,960

    175,200

    1.5ea. 16

    6,340

    791.0

    2,700,800

    224.7

    100-83-67-50-33-17-0

    37 6

    Dry expansion shell

    and Hi-X tubes

    6,000

    211,900

    0.9ea. 24

    2,095 2,005 11,400

    8,940

    UWA270JY1(300 )UWA228JY1(240 )UWA192JY1(200 )UWA162JY1(180 )UWA138JY1(150 )UWA120JY1(130 )

    Notes:*1 Cooling capacity is based on the following conditions : Leaving chilled water temp.6.7 (44 F), entering chilled water temp.12.2 (54 F), and outdoor air temp. 35 DB(95 FDB).*2 The following safety devices are equipped as standard. High pressure switch. Low pressure switch. Oil pressure control switch. Compressor thermal protector. Recycling

    guard timer. Crankcase heater. 3-element overcurrent relay (Compressor, Fan motors). Freeze-up protection thermostat. Fusible plug. Safety valve (except for UWA120JY1).*3 This product is manufactured in Japan.

    *1

    351.6 791kW class

    UWA120 270JY1For High Outdoor Temperature Use

    50Hz

    Specifications

    Model

    Cooling capacity

    Power supply

    Chilled water flow rate

    Cooling capacity

    Chilled water flow rate

    Capacity steps

    Compressor

    Evaporator type

    Condenser type

    Condenser

    fan

    Refrigerant

    Pipe connections water

    inlet/outlet

    Dimensions (H W D)

    Weight

    Operating weight

    Operation range

    Type

    Motor output

    Type

    Drive

    Air flow rate

    Motor output

    108.4

    369,800

    30.8

    3 phase, 50 Hz 380/400/415 V, 4 wires s ystem

    282

    97.4

    332,500

    27.7

    279

    100-66-33-0

    Semi-hermetically sealed reciprocating

    30

    Dry expansion shell and Hi-X tube

    Cross fin coil (Waffle louver fins and Hi-X tubes)

    Propeller

    Direct drive

    860

    30,370

    0.9ea. 4

    R-22

    FPT2 1/2 (65A)

    1,720 2,005 2,000

    1,230

    1,300

    5 to 52

    137.2

    468,200

    39.0

    358

    124.8

    425,800

    35.4

    325

    100-75-50-25-0

    37

    1,000

    35,310

    1,890 2,005 2,000

    1,420

    1,490

    161.3

    550,400

    45.8

    420

    149.9

    511,500

    42.6

    391

    45

    1,240

    43,790

    1.5ea. 4

    FPT3 (80A)

    1,520

    1,610

    186.0

    634,900

    52.9

    485

    167.4

    571,400

    47.6

    436

    100-83-66-50-33-0

    1,720

    60,730

    0.9ea. 8

    1,745 2,005 4,000

    2,500

    2,600

    219.1

    747,600

    62.3

    571

    197.1

    672,600

    56.0

    514

    30 2

    4B Flange (JIS16K)(100A)

    2,600

    2,730

    250.6

    855,100

    71.2

    653

    225.5

    769,400

    64.1

    588

    100-88-75-63-50-25-0

    2,000

    70,620

    1,915 2,005 4,000

    2,850

    2,980

    272.7

    930,500

    77.5

    711

    250.8

    855,900

    71.3

    654

    37 2

    2,870

    3,000

    319.2

    1,089,200

    90.7

    832

    290.5

    991,200

    82.6

    757

    45 2

    2,480

    87,580

    1.5ea. 8

    5B Flange

    (JIS16K)(125A)

    3,050

    3,210

    Notes:*1 Cooling capacity is based on the following conditions : Leaving chilled water temp.6.7 (44 F), entering chilled water temp.12.2 (54 F), and outdoor air temp. 35 DB(95 FDB).*2 Cooling capacity is based on the following conditions : Leaving chilled water temp.6.7 (44 F), entering chilled water temp.12.2 (54 F), and outdoor air temp. 46 DB(115 FDB).*3 The following safety devices are equipped as st andard. High/low pressure switch. Oil pressure control switch. Compressor thermal protector. Recycling guard timer.

    Crankcase heater. 3-element overcurrent relay for compressors and fan motors. Freeze-up prorection thermostat. Fusible plug. Safety valve(for UWA47, 55, 93, 109JAY1).*4 This product is manufactured in Japan.

    UWA37JAY1

    (40 )UWA47JAY1

    (50 )UWA55JAY1

    (60 )UWA63JAY1

    (70 )UWA75JAY1

    (80 )UWA80JAY1

    (90 )UWA93JAY1

    (100 )

    *1

    *2

    kW

    Btu/h

    USRT

    kW

    Btu/h

    USRT

    %

    kW

    m3/min

    cfm

    kW

    mm

    kg

    kg

    UWA109JAY1

    (120 )

    108.4 319.2kW class

    UWA37 109JAY1For High Outdoor Temperature Use

    50Hz

    UWA55JAY1 UWA138JY1 UWA80JATJ

    Provides a stable supply of chilled water even when the outdoor temperature is ashigh as 49 .

    Capacity can be controlled in multiple steps of between 3 and7 for efficient energy use.

    Full Lineup Includes Models withCapacities Ranging from 79 791kW.

    Equipped with a Compact andPowerful Semi-hermetically SealedReciprocating Compressor.

    : UWA Series

    UWA37JAY1 109JAY1UWA120JY1 270JY1U W A 2 7J A T J / 3 2 J A T J , 7 0J A T J 1 2 2J A T JUWA43JATJ 62JATJ

    5 to 525 to 49

    15 to 495 to 49

    Wide Operating Range

    Temperature range by model.

    Wide Capacity Range

    UWA37JAY1 109JAY1UWA43JATJ 122JATJUWA120JY1 270JY1

    A selector switch makes it possible to operate only one refrig-erant circuit while the other is under repair.

    Two Independent Refrigerant Circuits

    UWA63JAY1 109JAY1UWA70JATJ 122JATJU WA12 0 JY 1 2 70 JY 1

    Air Cooled Water Chillers

    AirCooled

    WaterChillers

    AirCooled

    WaterChillers

    17

    18

  • 8/2/2019 PCU0610A - Chiller [Small]

    11/1619 20

    AirCooledWaterChillers

    -HeatPumpType

    AirCooledWaterChillers

    -HeatPumpType

    Low Power Consumption

    Continuous capacity control with a range from 10(12)% to100% helps to reduce energy wastage during low-load

    UWYP 40 160BY1 UWYP 40 120BYBUWY40 120AY1 UWY40 120AYB

    UWYP40 160BY1UWYP40 120BYB

    UWA40 160AY1UWA40 120AYB

    High Precision

    10

    9

    8

    7

    Upper Limit Signal

    W a te r T e mp . ( )

    Example of Outlet Water Temperature Control

    If outlet water temperature rises above the upper limit signal,the load starts to increase in 10% inc rements

    As the temperaturefalls below the upperlimit signal, the loadincrease incrementsare reduced to 5%.

    As the temperaturefalls below the setvalue, the loadincrease incrementsre main at 5%.

    When changes in outletwater temperaturebecome 1 or less,the thermostat is turnedoff.

    Value Set

    The outlet water temperature is precisely controlled to within0.5

    (with a stable load) through the use of electric expansion

    : UWYP Series

    : UWY Series

    New Refrigerant

    UWYP125 750AY3UWYP40 480BY1UWYP40 120BYB

    Employs the new refrigerant R-407C.

    Efficient and Reliable Compressors

    To improve their operational reliability, 40 -- 480HP modelsare equipped with semi-hermetic single screw compressors.

    Applies to All Models

    Re frigerant inlet

    Re frigerant outlet

    Semi-hermetic singlescrew compressor

    UWYP40 160BY1UWYP40 120BYB

    UWY40 160AY1UWY40 120AYB

    UWYP100 480BY1UWYP100 120BYB

    Duty cycling control equalizes the operating time of the

    UWY100 480AY1

    UWY40 160AY1

    A choice of three control systems is available.

    Outflow water temperature control

    Provides precise control of the water temperature.

    Compressor count control

    Controls the number of compressors operating depending on the load.

    Inflow water temperature control

    Performs duty cycling control.

    UWY100 120AYB

    UWYP40 160BY1UWY40 480AYBUWYP40 120BYB

    Continues ope ration to levelsas low as 12% of total ca-pacity to provide stable wa-ter temperature control evenduring low-load periods.

    This mode can be used toreduce power consumption ifhighly precise water tempera-ture control is not necessaryduring low-load periods. Itshuts down the compressorwhen the load drops below40%.

    High-P recision Mode Low-Power Mode

    Multiple Operating Modes

    The user can select to give priority to either precision or reduced

    power consumption.

    Capacity Control Mode

    The maximum current level of the compressor can be specified

    in order to control demand for power. Since this func tion allows

    setting of the upper limit current value, comfortable operation is

    maintained while effectively controlling demand. In contrast to

    conventional capacity control step limit systems, maximum

    capacity is maintained at the desired demand value.

    Current Demand Function

    Demand Mode

    Users can select the operating mode that best matches theheat source application.

    Note: Switching between the above modes is accomplished using a control on

    the outdoor unit.

    Note: Water supply piping must be purchased separately.

    (UWYP375AY3 750AY3)

    UWYP40 480BY1UWYP40 120BYB

    UWY40 120AY1UWY40 120AYB

    Wide Operation Range

    Note: Measures to protect against drain water freezing are necessary in cold re-gions where the highest temperature stays below 0 on several consecutive

    days.

    A new defrosting system makes possible heating operationeven when the outdoor temperature is as low as -15 .

    CapacityOutdoor Air Temperature Range where Cooling Possible

    Models Employing R-407C Models Employing R-22

    5 3 0

    40 480

    -15 to 43

    -5 to 43 -5 to 43

    UWYP40 480BY1UWYP40 120BYB

    UWY40 480AY1UWY40 120AYB

    UWYP40 480BY1UWYP40 120BYB

    UWY40 480AY1UWY40 120AYB

    Applies to All Models

    RefrigerantInlet

    RefrigerantOutlet

    WaterOutlet

    Heat Exchanger with

    Stainless Steel Plates

    Stainless steel heat ex-changer plates prevent rust,thereby improving their du-rability and the system'soperational reliability.

    Reliability

    Applies to All Models

    Easy Installation

    Defrosting is performed under computer control as part ofcontinuous capacity control, resulting in stable heatingperformance.

    The system detects ice formation by constantly monitoring the outdoor tempera-

    ture, the pressures of the high- and low-pressure components, and the timers. In

    addition, continuous capacity control allows smooth control of capacity even af-

    ter a rise in the pressure of the high-pressure components. Remaining ice is

    melted a little at a time, and stable heating performance is maintained.

    The compact design of these units significantly reduces thespace required for installation.

    In the outdoor unit, component parts of a small size have been used whereverpossible to reduced its size and correspondingly reduce how much space it re-

    quires. Furthermore, replacing the 2-way refrigerant inlets with 4-way inlets has

    reduced the amount of space the outdoor unit needs even further.

    UWYP125 750AY3 The horizontal linkup design increases installation flexibility.

    This design ensures the installation does not protrude so far, making it possible

    to install water chillers along a wall or under a roof overhang.

    Air heat exchangers employ fins with acrylic coating forsuperior durability.

    50/60Hz

    50Hz

    60Hz

    50Hz

    60Hz

    R-407C

    R-22

    Standard Unit

    Standard Unit

    Refrigerant Uni ts ser ie s Mod el No.

    UWYPAY3

    UWYPBY1

    UWYPBYB

    UWYAY1

    UWYAYB

    Capacity (kW)

    21

    21, 22

    22

    23

    24

    page6.7/7.5

    11.2/12.5

    125

    17/19

    190

    22.4/25

    250

    33.5/37.5

    375

    45/50

    500

    56/63

    630

    67/75

    750

    106

    40

    40

    40

    40

    132

    50

    50

    50

    50

    160

    60

    60

    60

    60

    212

    80

    80

    80

    265

    100

    100

    100

    100

    50Hz

    60Hz

    50Hz

    60Hz

    R-407C

    R-22

    Standard Unit

    Standard Unit

    Refrigerant Uni ts ser ie s Mod el No.

    UWYPBY1

    UWYPBYB

    UWYAY1

    UWYAYB

    Capacity (kW)

    21, 22

    22

    23

    24

    page315

    120

    120

    120

    120

    370

    140

    140

    420

    160

    160

    480

    180

    180

    530

    200

    200

    580

    220

    220

    630

    240

    240

    740

    280

    280

    840

    320

    320

    960

    360

    360

    1060

    400

    400

    1160

    440

    440

    1260

    480

    480

    Model Lineup

    UWY P750AY3 UWYP 120B Y 1 UWY P180B Y 1

    Air Cooled Water Chillers -Heat PumpType

  • 8/2/2019 PCU0610A - Chiller [Small]

    12/16

  • 8/2/2019 PCU0610A - Chiller [Small]

    13/16

    AirCooledWaterChillers

    -HeatPumpType

    AirCooledWaterChillers

    -HeatPumpType

    UWYP40AY1

    UWYP50AY1

    UWYP60AY1

    UWYP 80AY1 UWYP 100AY 1

    UWYP120AY1

    UWYP140AY1

    UWYP160AY1

    UWYP180AY1

    UWYP200AY1

    UWYP220AY1

    UWYP240AY1

    UWYP280AY1

    UWYP320AY1

    UWYP380AY1

    UWYP400AY1

    UWYP440AY1

    UWYP480AY1

    Model

    Remote controller

    Chilling watersupply interrupting relay

    Waterhigh pressure (1.6 MPa)upgrader

    IPU

    Dio unit

    D Air unit

    Interface for use in L ONWORKS

    Interface for use in BACnet

    Central remote controller

    Unified ON/OFF controller

    Schedule timer

    BRC307D503

    GWEL-UWYP40B

    GWP-UWYP40B

    DAM602A5

    DEC102A

    DAM101A

    DMS504B51

    DMS502A51

    DCS302CA61

    DCS301BA61

    DST301BA61

    GWP-UWYP80B

    GWEL-UWYP100B

    GWP-UWYP100B

    GWEL-UWYP180B

    GWP-UWYP180B

    GWEL-UWYP280B

    GWP-UWYP280B

    GWEL-UWYP360B

    GWP-UWYP360B

    Option List

    UWYP40BY1

    UWYP50BY1

    UWYP60BY1

    UWYP40BYB

    UWYP50BYB

    UWYP60BYB

    UWYP80BY1 UWYP100BY1

    UWYP120BY1

    UWYP140BY1

    UWYP160BY1

    UWYP100BYB

    UWYP120BYB

    UWYP180BY1

    UWYP200BY1

    UWYP220BY1

    UWYP240BY1

    UWYP280BY1

    UWYP320BY1

    UWYP360BY1

    UWYP400BY1

    UWYP440BY1

    UWYP480BY1

    Model

    Remote controller

    Chilling watersupply interrupting relay

    Waterhigh pressure (1.6 MPa)upgrader

    IPU

    Dio unit

    D Air unit

    Interface for use in LONWORKS

    Interface for use in BACnet

    Central remote controller

    Unified ON/OFF controller

    Schedule timer

    BRC307D503

    GWEL-UWYP40B

    GWP-UWYP40B

    DAM602A5

    DEC102A

    DAM101A

    DMS504B51

    DMS502A51

    DCS302CA61

    DCS301BA61

    DST301BA61

    GWP-UWYP80B

    GWEL-UWYP100B

    GWP-UWYP100B

    GWEL-UWYP180B

    GWP-UWYP180B

    GWEL-UWYP280B

    GWP-UWYP280B

    GWEL-UWYP360B

    GWP-UWYP360B

    UWYP125AY3 UWYP190AY3 UWYP250AY3 UWYP375AY3 UWYP500AY3 UWYP630AY3 UWYP750AY3

    Notes:

    *1 Communication I/F P.C. board, Communication I/F P.C. B s torage box and Transmission waire are also required.

    Remote controller *1

    Communication I/F P.C. board

    Communication I/F P.C. B storage box

    Transmission wire

    Model

    BRC307C50

    BRP66B3

    BPR66A97

    BER66A5

    BPR66A100

    BER66A7

    Notes:*1 Cooling capacity is based on the following conditions : Leaving chilled water temp.7 (44.5 F), entering chilled water temp.12 (53.6 F), and outdoor air temp. 35 DB(95 FDB).*2 Heating capacity is based on the following conditions : Leaving hot water temp.45 (113 F), entering hot water temp.40 (104 F), and outdoor air temp. 7 DB(44.5 FDB),and

    6 WB(43 FWB).

    *3 The following safety devices are equipped as standard. High pressure protector. Low pressure protector. Compressor thermal protector. Fusible plug. Reverse-phaseprotector. Overheat protection of discharge gas. Overcurrent relay(compressor). Freeze-up protection thermostat. Overcurrent relay(fan). Safety valve.

    *4 The unit is equipped with standard water filter. *5 The limited length of wire represents its max. length when the pressure is lower than 2%. *6 This product is manufactured in China.

    Specifications

    Type

    Motor output

    Type

    Drive

    Air flow rate

    Motor output

    *1

    Model

    Cooling capacity

    Chilled water flow rate

    Heating capacity

    Power supply

    Hot water flow rate

    Capacity steps

    Compressor

    Evaporator type

    Condenser type

    Condenser

    fan

    Refrigerant

    Pipe connections

    water inlet/outlet

    Dimensions(H W D)

    Weight

    Operating weight

    Operation range

    kW

    Btu/h

    USRT

    /min

    kW

    Btu/h

    USRT

    /min

    %

    kW

    m3/min

    cfm

    kW

    mm

    kg

    kg

    *2

    118 355kW class

    UWY40 120AYBStandard Unit

    60Hz

    UWY40AYB

    (40 )UWY50AYB

    (50 )

    UWY60AYB

    (60 )

    UWY100AYB

    (100 )

    UWY120AYB

    (120 )

    118

    403,000

    34

    338

    132

    450,000

    38

    3 phase, 60 Hz 400/440 V, 3 wires syst em

    378

    100~10-0

    Semi-hermetic sealed single-screw type

    30 1

    Blazing Plate type

    Cross fin coil

    Propeller

    Direct drive

    800

    28,240

    0.5 4

    R-22

    3B Flange (80A HG20593-97)

    2,395 2,200 2,000

    1,700

    1,717

    cooling -5 to 43, heating -20 to 21

    150

    512,000

    43

    430

    170

    580,000

    48

    487

    37 1

    810

    28,593

    0.8 4

    1,800

    1,820

    180

    614,000

    51

    516

    200

    683,000

    57

    573

    45 1

    940

    33,182

    1.2 4

    1,950

    1,973

    300

    1,024,000

    85

    860

    335

    1,143,000

    95

    960

    37 2

    1,620

    57,186

    0.8 8

    4B Flange (100A HG20593-97)

    2,395 4,400 2,000

    3,600

    3,636

    355

    1,212,000

    101

    1,018

    400

    1,365,000

    114

    1,147

    45 2

    1,880

    66,364

    1.2 8

    3,900

    3,942

    Notes:*1 Cooling capacity is based on the following conditions : Leaving chilled water temp.7 (44.5 F), entering chilled water temp.12 (53.6 F), and outdoor air temp. 35 DB(95 FDB).*2 Heating capacity is based on the following conditions : Leaving hot water temp.45 (113 F), entering hot water temp.40 (104 F), and outdoor air temp. 7 DB(44.5 FDB),and

    6 WB(43 FWB).*3 The following safety devices are equipped as standard. High pressure protector. Low pressure protector. Compressor thermal protector. Fusible plug. Reverse-phase

    protector. Overheat protection of discharge gas. Overcurrent relay(compressor). Freeze-up protection thermostat. Overcurrent relay(fan). Safety valve.

    *4 Standard for the max. chilled water pressure is 0.7MPa, but1.6MPa is available if required. *5 Installation/operating weight includes the weight of refrigerant and refrigerant oil(charged before delivery).

    Specifications

    Type

    Motor output

    Type

    Drive

    Air flow rate

    Motor output

    UWY200AY1

    (200 )UWY220AY1

    (220 )UWY240AY1

    (240 )UWY280AY1

    (280 )UWY320AY1

    (320 )UWY360AY1

    (360 )UWY480AY1

    (480 )UWY400AY1

    (400 )UWY420AY1

    (420 )

    *1

    Model

    Cooling capacity

    Chilled water flow rate

    Heating capacity

    Power supply

    Hot water flow rate

    Capacity steps

    Compressor

    Evaporator type

    Condenser type

    Condenser

    fan

    Refrigerant

    Pipe connections Water inlet/outlet

    Dimensions (H W D)

    Weight

    Operating weight

    Operation range

    kW

    Btu/h

    USRT

    /min

    kW

    Btu/h

    USRT

    /min

    %

    kW

    m3/min

    cfm

    kW

    mm

    kg

    kg

    630

    2,150,000

    179

    1,806

    720

    2,457,000

    205

    2,064

    60 3

    2,820

    99,546

    6,350

    6,450

    740

    2,525,000

    210

    2,121

    840

    2,867,000

    239

    2,408

    (45+60) 2

    3,560

    125,668

    (1.2 8) 2

    4B Flange (100A HG20593-97)

    (2,395 4,400 2,000) 2

    4,020 2

    4,084 2

    530

    1,809,000

    151

    1,519

    600

    2,048,000

    171

    3 phase, 50 Hz 380/400/415 V, 4 wires sys tem

    1,720

    100~10-0 (continuous capacity control)

    Semi-hermetic sealed single-screw type

    45 2+60

    Blazing plate type

    Cross fin coil

    Propeller

    Direct drive

    2,620

    92,486

    1.2 12

    R-22

    5B Flange (125A HG20593-97)

    (2,460 6,600 2,000) 2

    6,260

    6,337

    cooling -5 to 43, heating -20 to 21

    *2

    580

    1,979,000

    165

    1,663

    660

    2,252,000

    188

    1,892

    45+60 2

    2,720

    96,016

    6,295

    6,382

    840

    2,867,000

    239

    2,408

    960

    3,276,000

    273

    2,752

    (60 2) 2

    3,760

    132,728

    4,040 2

    4,104 2

    960

    3,276,000

    273

    2,752

    1,080

    3,686,000

    307

    3,096

    (45 3) 2

    5,040

    177,912

    (1.2 12) 2

    5B Flange (125A H G20593-97)

    (2,460 6,600 2,000) 2

    6,205 2

    6,270 2

    1,060

    3,617,000

    301

    3,039

    1,200

    4,095,000

    341

    3,440

    (45 2+60) 2

    5,240

    184,972

    6,260 2

    6,337 2

    1,260

    4,300,000

    358

    3,612

    1,440

    4,914,000

    410

    4,128

    (60 3) 2

    5,640

    199,092

    6,350 2

    6,450 2

    1,160

    3,959,000

    330

    3,325

    1,320

    4,505,000

    375

    3,784

    (45+60 2) 2

    5,440

    192,032

    6,295 2

    6,382 2

    530 1,260kW class

    UWY200 480AY1Standard Unit

    50Hz

    Notes:*1 Cooling capacity is based on the following conditions : Leaving chilled water temp.7 (44.5 F), entering chilled water temp.12 (53.6 F), and outdoor air temp. 35 DB(95 FDB).*2 Heatinging capacity is based on the following conditions : Leaving hot water temp.45 (113 F), entering hot water temp.40 (104 F), and outdoor air temp. 7 DB(44.5 FDB),and

    6 WB(43 FWB).

    *3 The following safety devices are equipped as standard. High pressure protector. Low pressure protector. Compressor thermal protector. Fusible plug. Reverse-phaseprotector.

    Overheat protection of discharge gas. Overcurrent relay(compressor). Freeze-up protection thermostat. Overcurrent relay(fan). Safety valve.*4 Standard for the max. chilled water pressure is 0.7MPa, but1.6MPa is available if required. *5 Installation/operating weight includes the weight of refrigerant and refrigerant oil(charged before delivery).*6 This product is manufactured in China.

    Specifications

    Type

    Motor output

    Type

    Drive

    Air flow rate

    Motor output

    UWY40AY1

    (40 )

    UWY50AY1

    (50 )

    UWY60AY1

    (60 )

    UWY80AYAY1

    (80 )

    UWY100AY1

    (100 )UWY120AY1

    (120 )UWY180AY1

    (180 )UWY140AY1

    (140 )UWY160AY1

    (160 )

    *1

    Model

    Cooling capacity

    Chilled water flow rate

    Heating capacity

    Power supply

    Hot water flow rate

    Capacity steps

    Compressor

    Evaporator type

    Condenser type

    Condenser

    fan

    Refrigerant

    Pipe connections water inlet/outlet

    Dimensions (H W D)

    Weight

    Operating weight

    Operation range

    kW

    Btu/h

    USRT

    /min

    kW

    Btu/h

    USRT

    /min

    %

    kW

    m3/min

    cfm

    kW

    mm

    kg

    kg

    160

    546,000

    46

    459

    180

    614,000

    51

    516

    45 1

    840

    29,652

    1.2 4

    1,950

    1,973

    210

    717,000

    60

    602

    240

    819,000

    68

    688

    60 1

    940

    33,182

    2,020

    2,052

    106

    362,000

    30

    304

    118

    403,000

    34

    3 phase, 50 Hz 380/400/415 V, 4 wires sys tem

    338

    100~10-0 (continuous capacity control)

    Semi-hermetic sealed single-screw type

    30 1

    Brazed plate type

    Cross fin coil

    Propeller

    Direct drive

    700

    24,710

    0.5 4

    R-22

    3B Flange (80A HG20593-97)

    2,395 2,200 2,000

    1,700

    1,717

    cooling -5 to 43, heating -20 to 21

    *2

    132

    450,000

    38

    378

    150

    512,000

    43

    430

    37 1

    710

    25,063

    0.8 4

    1,800

    1,820

    265

    904,000

    75

    760

    300

    1,024,000

    85

    860

    37 2

    1,420

    50,126

    0.8 8

    4B Flange (100A HG20593-97)

    2,395 4,400 2,000

    3,600

    3,636

    320

    1,092,000

    91

    917

    355

    1,212,000

    101

    1,018

    45 2

    1,680

    59,304

    1.2 8

    3,900

    3,942

    370

    1,263,000

    105

    1,061

    420

    1,433,000

    119

    1,204

    45+60

    1,780

    62,834

    4,020

    4,084

    480

    1,638,000

    137

    1,376

    540

    1,843,000

    154

    1,548

    45 3

    2,520

    88,956

    1.2 12

    5B Flange (125AHG20593-97)

    2,460 6,600

    2,000

    6,205

    6,270

    420

    1,433,000

    119

    1,204

    480

    1,638,000

    137

    1,376

    60 2

    1,880

    66,364

    4,040

    4,104

    106 480kW class

    UWY40 180AY1Standard Unit

    50Hz

    Air CooledWater Chillers -Heat PumpType

    23 24

  • 8/2/2019 PCU0610A - Chiller [Small]

    14/16

    A single built-in control box simplifies operation and control.

    Provides a stable supply of chilled water throughout the

    Since the heat exchanger employs water, operation of the unit is not affected by

    changes in the outdoor temperature. A stable water temperature is maintained

    year round.

    All controls and indicators are centralized in a single control box, making it possi-

    ble to control the system using fewer personnel. Installation is simplified by inte-

    gration of the control box with the main unit.

    The water temperature setting can be set to any valuebetween 4 and 25 .

    The 10 HP model has a footprint measuring only 0.32square meters.

    8 to 30 HP models have a modular design that enables u nits with different capaci-

    ties to be used together in a single system and simplifies increasing system ca-

    pacity later on 3 5 HP models have a similar configuration and are designed

    for compactness.

    The starter panel is built into the control panel, simplifying

    Easy Installation

    UWP90AY3 900AY3

    All models are fitted with a pressure gauge as standard.

    Performance characteristics under partial load are efficient.

    Reliability

    Efficient Performance

    Well Appointed

    The new double-pipe heat exchanger design reduces clogging, significantly in-

    creasing resistance to dirty cooling water.

    The double-pipe heat exchanger and an individual error

    indication function help reduce the manpower required for

    Maintenance

    UWP90AY3 900AY3UWD1320DY1 4000DY1

    Year Round Cooling Operation

    Applies to All Models

    Wide Water Temperature Control Range

    RangeUWP90AY3 900AY3

    Simple Operation and Control

    UWD1320DY1 4000DY1

    UWD1320DY1UWP900AY3

    Model Lineup

    Refrigerant Uni ts ser ie s Mod el No.Capacity (kW)

    page

    50/60Hz

    50Hz

    R-407C

    R-134a

    Standard Unit

    Standard Unit

    UWPAY3

    UWDDY1

    8/9

    90

    13.2/15

    150

    20/22.4

    224

    26.5/30

    300

    40/45

    450

    53/60

    600

    67/75

    750

    80/90

    900

    118

    1320

    150

    1700

    180

    2000

    236

    2650

    300

    3350

    355

    4000

    27

    27

    Refrigerant Uni ts ser ie s Mod el No.

    50Hz

    60Hz

    50Hz

    60Hz

    R-134a

    Standard Unit

    Brine Cooling Unit

    ZUWAY1

    ZUWAYB

    ZUWAY1Z

    ZUWAYBZ

    Capacity

    100RT

    100

    100

    120RT

    120

    120

    120

    120

    150RT

    150

    150

    150

    150

    175RT

    175

    175

    175

    175

    200RT

    200

    200

    200

    200

    240RT

    240

    240

    240

    240

    280RT

    280

    280

    280

    300RT

    300

    300

    300

    350RT

    350

    350

    400RT

    400

    400

    28

    28

    29

    29

    page

    : UWP Series

    : UWD S eries ZUW Series

    Employs the new refrigerants R-407C and R-134a.

    New Refrigerant

    UWP90 900AY3

    UWD1320 40000DY1ZUW 100 400AY(1)(B)ZUW 100 400AY(1)(B)Z

    To improve their operational reliability, 5 -- 30HP modelsemploy scroll compressors, while 40 -- 120HP models areequipped with semi-hermetic single screw compressors.

    Refrigerant inlet

    Refrigerant outlet

    Semi-hermetic singlescrew compressor

    Efficient and Reliable Compressors

    Applies to All Models

    WaterCoole

    d

    WaterChille

    rs

    WaterCoole

    d

    WaterChille

    rs

    ZUW175AY1

    1 compressoris operating

    2compressors

    100

    50

    0 25 50 100

    Powerconsumptionratio(%)

    Cooling capacity ratio (%)

    Increased characteristicunder partial load

    Water Cooled Water Chillers

    25 26

  • 8/2/2019 PCU0610A - Chiller [Small]

    15/16

    Specifications

    UWP90AY3

    (3 )UWP150AY3

    (5 )UWP224AY3

    (8 )UWP300AY3

    (10 )UWP450AY3

    (15 )UWP600AY3

    (20 )UWP750AY3

    (25 )UWP900AY3

    (30 )Model

    Cooling capacity

    (50/60 Hz)

    Power supply

    Chilled water flow rate

    (50/60 Hz)

    Capacity steps

    Compressor

    Evaporator type

    Condenser type

    Refrigerant

    Pipe

    connections

    Dimensions (H W D)

    Weight

    Operating weight

    Type

    Motor output

    Condenserwater inlet/outlet

    Chilled water inlet/outlet

    Drain outlet

    kW

    Btu/h

    USRT

    /min

    %

    kW

    mm

    kg

    kg

    8.0/9.0

    27,300/30,700

    2.28/2.56

    3 phase, 50 Hz 380/400/415 V, 60 Hz 400/440 V, 3 wi res system

    23/26

    100-0

    Hermetically sealed scroll type

    3.0 1

    Brazed plate heat exchanger

    Double pipe condenser

    R-407C

    FPT1 (25A)

    FPT1 (25A)

    FPT3/4 (20A)

    1,280 405 690

    100

    102

    13.2/15.0

    45,100/51,200

    3.75/4.27

    38/43

    3.75 1

    110

    112

    20.0/22.4

    68,300/76,500

    5.69/6.37

    57/64

    5.5 1

    FPT1 1/2 (40A)

    FPT1 1/2 (40A)

    1,280 405 790

    150

    154

    26.5/30.0

    90,500/102,000

    7.54/8.53

    76/86

    7.5 1

    160

    165

    40.0/45.0

    137,000/154,000

    11.4/12.8

    115/129

    100-50-0

    5.5 2

    FPT1 1/2 2 (40A)

    FPT1 1/2 2 (40A)

    1,280 808 790

    305

    313

    53.0/60.0

    181,000/205,000

    15.1/17.1

    152/172

    7.5 2

    325

    335

    67.0/75.0

    229,000/256,000

    19.1/21.3

    192/215

    100-60-0

    7.5+5.5 2

    FPT1 1/2 3 (40A)

    FPT1 1/2 3 (40A)

    1,280 1,211 790

    465

    478

    80.0/90.0

    273,000/307,000

    22.8/25.6

    229/258

    100-67-0

    7.5 3

    485

    500

    Notes:*1 Cooling capacity is based on the following conditions : Leaving chilled water temp.7 (44.5 F), entering chilled water temp.12 (53.6 F), leaving condenser water temp. 35 (95 F), entering

    condenser water temp.30 (86 F).*2 The following safety devices are equipped as standard. High/low pressure switch. Freeze-up protection thermostat. Overcurrent relay for compressors. Reverse-phase protector. Discharge gas overheat protector. Fusible plug. Safety valve.

    *3 This product is manufactured in Japan.

    *1

    8 / 9 80 / 90kW class

    UWP90 900AY3Standard Unit

    50/60Hz

    SpecificationsUWD1320DY1

    (40 )UWD1700DY1

    (50 )UWD2000DY1

    (60 )UWD2650DY1

    (80 )UWD3350DY1

    (100 )UWD4000DY1

    (120 )Model

    Cooling capacity

    Power supply

    Chilled water flow rate

    Condenser water flow rate

    Compressor

    Evaporator type

    Condenser type

    Refrigerant

    Pipe

    connections

    Dimensions (H W D)

    Weight (Approx.)

    Operating weight (Approx.)

    Type

    Motor output

    Capacitycontrol

    Condenserwater inlet/outlet

    Chilledwater inlet/outlet

    Chilledwaterdrain outlet

    Condenserwaterdrain outlet

    kW

    Btu/h

    USRT

    /min

    /min

    kW

    %

    mm

    kg

    kg

    118

    403,000

    33.6

    3 phase, 50 Hz 380/400/415 V, 3 wires sy stem

    338

    420

    Semi-hermetic sealed single screw type

    30 1

    100-70-40-0

    Shell and Hi-X tube type

    Shell and cross fin tube type

    R-134a

    FPT3 (80A)

    FPT3 (80A)

    FPT3/4

    FPT1/4

    1,600 2,320 759

    1,100

    1,220

    150

    512,000

    42.7

    430

    534

    37 1

    1,702 2,600 759

    1,250

    1,390

    180

    615,000

    51.2

    516

    640

    45 1

    FPT4 (100A)

    4B Flange (JIS10K)(100A)

    FPT1

    1,280

    1,420

    236

    806,000

    67.1

    677

    837

    30 2

    100-70-40-20-0

    FPT3 (80A)

    1,623 3,330 994

    1,800

    1,980

    300

    1,020,000

    85.3

    860

    1,068

    37 2

    1,745 3,338 1,050

    2,200

    2,420

    355

    1,210,000

    101

    1,018

    1,263

    45 2

    FPT4 (100A)