Daikin Water Chillers are of the self-contained type. This means that they are assembled, internally wired and
charged with refrigerant at the factory for easy installation, only requiring external wiring and plumbing on site.
They are compatible with Daikin's Air Handling and/or Fan Coil Units.
All rights reservedPrinted in Japan 11/06/005 SW.HP.AD
c
DealerHead Office:
Umeda Center Bldg., 2-4-12, Nakazaki-Nishi,
Kita-ku, Osaka, 530-8323 Japan
Tokyo Office:
JR Shinagawa East Bldg., 2-18-1, Konan,
Minato-ku, Tokyo, 108-0075 Japan
http://www.daikin.com/global/
1. Air conditioners should not be installed in areas where corrosive gases, such as acid gas or alkaline gas, are produced.2. If the outdoor unit is to be installed close to the sea shore, direct exposure to the sea breeze should be avoided and choose an
outdoor unit with anti-corrosion treatment.
Cautions on product corrosion
Warning Daikin Industries, Ltd.s products are manufactured for export to numerous countries throughout the
world. Daikin Industries, Ltd. does not have control over which products are exported to and used in a
particular country. Prior to purchase, please therefore confirm with your local authorised importer,
distributor and/or retailer whether this product conforms to the applicable standards, and is suitable for
use, in the region where the product will be used. This statement does not purport to exclude, restrict
or modify the application of any local legislation.
Ask a qualified installer or contractor to install this product. Do not try to install the product yourself.
Improper installation can result in water or refrigerant leakage, electrical shock, fire or explosion.
Use only those parts and accessories supplied or specified by Daikin. Ask a qualified installer or
contractor to install those parts and accessories. Use of unauthorised parts and accessories or
improper installation of parts and accessories can result in water or refrigerant leakage, electrical
shock, fire or explosion.Read the User's Manual carefully before using this product. The User's Manual provides important
safety instructions and warnings. Be sure to follow these instructions and warnings.
If you have any enquiries, please contact your local importer, distributor and/or retailer.
Printed on 100% recycled paper with soy ink.Specifications, designs and other content appearing in this brochure are current as of November 2006 but subject to change without notice.
ISO 14001 is the standarddefined by theInternational Organization forStandardization (ISO) relating to environmental management systems. Our grouphas been acknowledged by an internationally accredited compliance organisationas having an appropriate programme of environmental protection procedures andactivities to meet therequirements of ISO 14001.
AboutI SO14001
ISO 9001 is a plant certification system defined by theInternationalOrganization for Standardization (ISO) relating to quality assurance. ISO9001 certification covers quality assurance aspects relatedto the design,development, manufacture, installation, and supplementary service ofproducts manufactured at the plant.
AboutI SO9001
JMI-0107 EC99J2044
8/2/2019 PCU0610A - Chiller [Small]
2/16
2
H i g h -p e r f or m a n c e D a i k i n W a t e r C h i l l e r s a r e A v a i l a b l e i n
a B r o a d R a n g e o f M o de l s t o S u i t D i v e r s e A p p l ic a t i o ns .
List of Daikin Water Chiller Models
1 2
Air Cooled Water Chillers: UWAP Series / UWAXP Series
: UWA Series / ( For High Outdoor Temperature Use )
Dedicated water chillers are able to operate year
round because they can accommodate a wide range
of outdoor temperatures. The high-performance models
with capacities of over 40 HP can deliver between
10% (12%) and 100% of their capacities. They are
able to withstand the demanding conditions typical ofindustrial applications.
Air Cooled Water Chillers - Heat Pump Type
Water Cooled Water Chillers
Air cooled heat pump system units are an ideal
way to provide a reliable supply of hot and cold
water. Of compact size because no cooling tower
is required, they are also suitable for office
building air conditioning. These high-end models
provide an answer to a variety of air conditioning
requirements.
Water cooled units provide a stable supply of
chilled water year round and are unaffected by
changes in the outdoor temperature. In addition
to air conditioning applications, they are also a
highly reliable industrial process cooling solution
thanks to their stability and wide temperature
control range.
Air Cooled Water Chillers
AirCooled
WaterChillers
20 40 60 80 100 150 200 250 300 350 450 500 600 700 800 900 1000 1 200 1 400 Page
11
12 13
14
14 15
17
18
21
21 22
23
27
27
2829
9 10
9
Capacity Range (kW)
Air CooledWater Chillers - Heat PumpType
Water Cooled Water Chiller s
Standard Unit
Standard Unit
Standard Unit
Brine Cooling Unit
Standard Unit
ForHigh Outdoor Temperature Use
Standard Unit
Inverter Cooling Unit
Brine Cooling Unit
Year - Round Cooling Only Unit
Standard Unit
Air Cooled Water Chillers
20 40 60 80 100 150 200 250 300 350 450 500 600 700 800 900 1000 1 200 1 400 Page
12
13
15
18
21
22
24
27
28
29
10
9
Capacity Range (kW)
Air CooledWater Chillers - Heat PumpType
Water Cooled Water Chiller s
Standard Unit
Standard Unit
Standard Unit
Brine Cooling Unit
Standard Unit
ForHigh Outdoor Temperature Use
Standard Unit
Brine Cooling Unit
Year - Round Cooling Only Unit
Standard Unit
WaterCooled
WaterChillers
AirCooledWaterChillers
-HeatPumpType
: UWYP Series
: UWY Series
: UWP Series
: UWD Series ZUW Series
50Hz
60Hz
106 1260 UWAP-BY1
106 1260 UWAP-BY1K
12.5 75
11.2 67
106 1260 UWA-AY1
106 1260 UWYP-BY1
106 1260 UWY-AY1
8 80
118 355 UWD-DY1
UWAXP-AY1
108.4 319.2 UWA-JAY1
351.6 791 UWA-JY1
UWP-AY3
6.7 67 UWAP-AY3
68 808 UWAP-BY1Z
UWYP-AY3
367 1450ZUW-AY1
190 715 ZUW-AY1Z
118 355 UWAP-BYB
118 355 UWAP-BYBK
118 355 UWYP-BYB
118 355 UWY-AYB
9 90 UWP-AY3
79 370 UWA-JATJ
7.5 75 UWAP-AY3
79 242
118 355 UWA-AYB
UWYP-AY312.5 75
441 1040 ZUW-AYB
233 555 ZUW-AYBZ
UWAP-BYBZ
Daikin chilling units employ advanced technology that provides highly
accurate temperature control to within 0.5 . They are widely used in
applications ranging from air conditioning to industrial equipment.
Recent changes have introduced new models with substantially
increased capacities of up to 480 HP and various model series,
including advanced inverter type units, year-round cooling type units,
and units with brine-resistant specifications. By providing a full lineup
of heat source series choices, Daikin offers an even more flexible
array of solutions for a wide range of heat source applications.
8/2/2019 PCU0610A - Chiller [Small]
3/16
Equipped with an Efficient, Durable
Semi-hermetically Sealed Screw Compressor.
60,000Sales volume
Gate Rotor
ScrewRotor
SuctionPressure
SuctionPressure
Discharge Pressure
Discharge Pressure
Equipped with a Newly Developed,
Highly Efficient Compact C ompressor.Optimization of the unit enhances efficient operation. A newlydeveloped denture mold enabled the production of a compactmodel with reduced volume and weight.
High Operational Efficiency R educes E nergy Loss.In addition to efficient operation afforded by a 12-compression single cycle, the single screw constructioneliminates blow-by from high to low pressure sections toreduce energy loss. Daikin water chillers are equipped with atightly sealed gate rotor to reduce refrigerant loss fromleakage. Our compressors are designed for efficient operation
High Accuracy and High Durability.
Careful construction features gate rotors positioned to theright and left of the screw to eliminate eccentric loadproduced by pressure differential. The orthogonal rotor shaftuses high-precision ball and roller bearings, which extends itslife compared to conventional types. In addition, powertransmission between rotors is reduced, thus eliminatingfriction wear and maintaining stable operating performanceover an extended period of time.
Low Vibration and Sound Levels.
Daikin water chillers use gate rotors made of high-performance engineering plastic for smooth meshing with thescrew rotor, thereby reducing shock and vibration. whilemaintaining stable operation. The gate rotors are wellbalanced to equalize pressure, which reduces noise and
Lightweight Compact Design Save Space.In addition to the simple single rotor construction, thecompact, lightweight design eliminates the need for an oilcooler while incorporating the oil separator into a single partto reduce the space required for setup.
Durable Construction Increases InspectionIntervals thereby De creasing M aintenance.
Durability of the equipment increases the maintenance intervalto approximately 40,000 hours (or about seven years). Thesimplified lubrication system, including a high/low pressuredifferential lubrication system and ball and roller bearings,reduces the factors that can contribute to problems. Alongwith increasing the maintenance and inspection interval, thecareful construction of Daikin water chillers enhancesreliability.
CasingScrew rotor
Slide valve
Ball bearingMotor
Gate rotor
High efficient oil separatorHigh-low pressure
differential lubricating mechanism
Be aring lubricating oil formodels using new refrigerant
Re frigerant inlet
Re frigerant outlet
1
2
3
4
5
6
7
8
9
10
11
12
4
5
63
8
9
7
10
11
High Function Microcomputer Control Panel and
Multifunctional R emote Controller R ealise E fficient
Operation Control.
Simple key operation displays re quired operating andsettings data. Displays a complete of operating data foreasy comprehension.
Up to eight units can be group controlled by a single remote controller.
Equipped with simultaneous defrost prevention control foravoiding radical water temperature change when operatingmultiple units.*Simultaneous defrost can be carried out for up to two units when five or moreunits are connected.
Note : Custom orders ma y take more time for delivery.
Rotation control
Microcomputer Control Panel Ma kes Operation
Control Easy.
Multi-display
Controls Multiple Units Effectively
A Multifunctional Liquid Crystal Remote
Controller for Effective G roup Control.
Function for Equal Controlusing Microcomputer Control Panel
Enables different types of remote control, such as controlby commands from the host computer, the DaikinBuilding Air-Conditioning Control System (D-B ACS ), or themultifunctional remote controller.
Remote Control by Remote Command
On/Off remote control
Remote s etting of water temperature
Setting for heat storage operationYou can switch settings from normal operation to either
temperature setting for heat storage or control by the external
Lower noise operation for during nighttimeYou can reduce the operating noise by stopping half the fan.
Note that the capacity control of the chiller should be limited to
less than 70%.
Forced fan operation control*You can force fan operation even when the unit is stopped,
which is convenient for removing the snow collected on the fan.
*This function is designed for in areas where snow rarely falls.
An optional snow hood should be used in areas prone to snow.
Demand control(1) You can have Three demand controls are possible thermostat
Off, less than 40% or less than 70%. (Factory set:70%)
(2)Demand control may also be ac hieved by setting the operating
current of the compressor.
*Demand control is available on all models, with the exception of
those listed below.
UWAP75 750AY3, UWAXP125 750AY1, UWA37 109JAY1,
UWA120 270JY1, UWA27 122JATJ, UWYP125 750AY3,
UWP90 900AY3
Outdoor temperature
Inlet/Outlet temperature
Discharge gas temperature
Displays operating data for easy comprehension ofsystem status.
High and low pressure
Water temperature setting
Malfunction code
*For details, refer to the Operation Manual of each model.
On/Off control
Water temperature setting
Switching of operating
mode
Defrost cycle setting*
Heat storage operation
Enables different types of remote control.
Low noise operation during
nighttime
Forced fan operation
Demand control*
Rotation control
Inspection/Test operation
Memorizes the number of stops for each unit (therefore noteffective for systems in continuous operation), and smoothsoperation by starting in order from the unit with the leastnumber of starts and stops to increase the life time of allapparatus in the system.
B R C307 (Option)
*Applies to a ll models, with the exc eption of those listed below.
UWA37 109JAY1, UWA120 270JY1,
UWA27 122JATJ, UWP90 900AY3
*Demand control is not availablewith
*Applies to heat-pump type only.
Outdoor temp.
Discharge gas temp.
Water temp. setting
Inlet/outlet water temp.
H/L pressure of refrigerant
Centralized control
Malfunction code display
3 4
8/2/2019 PCU0610A - Chiller [Small]
4/16
Daikin's C ontrol System for C entral Air C onditioning
S ystem Offers Appropriate C ontrol for Us e
and S ize of Building.
Daikin's intelligent control solution for the whole air
conditioning system.
Daikin's Control System for
Central Air Conditioning.
Daikin introduces its "C ontrol System for Central Air Conditioning" The sys tem letsyou freely combine a number of optional controllers for centralized control toconstruct the air conditioning control system that is appropriate for your needs. Thesystem executes total central control of chillers and air conditioners, to save
management labour while realizing ideal central air conditioning performance.
Different Control Apparatus C ombinations Enable a Multipurpose S ystem.Daikin offers a lineup of centralcontrollers equipped with a variety offunctions. The unified ON/OFF controllerlets you turn equipment on and offindividually or in groups. The scheduletimer lets you program the time forconnected equipment to be turned onand off for each week. Controlapparatus with different functions canbe freely combined, and up to 64groups can be centrally controlled.
*Number of units that can be
Note:The system shown above is applicable only to Series UWAJ-G, UWYJ-B, UWAP-G and UWYP-G.Note:Air handling and Fan coil units can be connected by custom orders.
Centra l remote controller Unif ied ON/OFF controller Schedule timer
Model
Stop-running command
Cooling/heating mode setting
Temp. setting
Schedule function
Interlock setting
Power proportion limitation
Stop-running
Cooling/heating mode
Temperature set
Room temp. (suction inlet)
Water temp. (inlet/outlet)
Abnormal
Abnormal signal
Filter signal
Continuous running period
Temp. upper/lower limit
Standard connection
Air-cooling Unit
UWAP,UWYP,UWA,UWY
Water-cooling Unit
ZUW
AIRNET
DioUnit
Commodity from other companies
Pump, Refrigerating Unit, Cooling Tower
(Note1)
System Structure(VRV+central conditioning)
Cool/warm water pump 1Cooling tower 1
iPU(Reservedfor VRV)
Ethemet
VRV(4 ports)
256 indoor units
Dio Unit Dio Unit
Wiring adaptor is required for connecting Dio unit to Airnet
1. C entral air-conditioning sys tem can be c ontrolledtogether with VRV.
2. Operating interface is based on the windowsinterface, which is easy to use.
3. 1024 units (groups) of indoor unit or watercooled chiller can be connected.
4. Power distribution in proportions, calc ulation thepower rate and other AC-related costs of user.
5. C an be connected with Air Conditioning NetworkService System
6. Ordinary 2-core cable is used for wiring, the fieldwiring work is very simple.
Features of I-Manager
( realised function irrespective item only data information, can't be achieved up till now)
Note1: Can realize partial function of Air Conditioning Network Service System.
* Please contact Daikin for detaileddata for connection of Fan coiland AC(terminal products)
Remote controller(units No. control)
Cool/warm water pump 3
Monitoring
function
Controlling
function
Function
Remote monitorcenter
Max. 4 iPUsare
iPU(Reserved for central
air-conditioningsystem)
Equipment~pump of othercompany, cooling tower(1
port)Pump 4 units
Note: It is not possible to connect a high outdoor temperature specification unit and the UWAP75 750.
D -NET
I-Manager
D -NET
D -NET
wiring adaptor
Water cooled chiller (1 port)Air-cooling 240HP 2 units
Water-cooling 400US RT 1 unit
Unified ON/OFF controller
Chilling unit
Possible to link withhost computer
Schedule timer
SkyAir series
VRV system
Central remote controller
Possible to have a forcedshut-down input
Enables control of other air conditioning systemssuch as VRV, SkyAir or HRV.
Enables individual control from chillers to air conditioners by using a single line.
Enables group control by remote controllers of both chillers and air conditioners.
Lets you develop a system that doesn't use individual remote controllers.(Central remote controller required)
Air handling unit Air handling unit Fan coil unit Possiblewireless remote controller
System configuration
D adaptorI-Manager option
Control Function List of I-Manager
I-Manager Control heat resources system by using I-Manager
New VersionNew Version
5 6
8/2/2019 PCU0610A - Chiller [Small]
5/16
Model Lineup
50Hz
60Hz
50Hz
60Hz
50Hz
60Hz
50Hz
60Hz
R-407C
R-22
Standard Unit
Year - Round Cooling
Only Unit
Brine Cooling Unit
Standard Unit
Refrigerant Uni ts ser ie s Mod el No.
UWAPBY1
UWAPBYB
UWAPBY1K
UWAPBYBK
UWAPBY1Z
UWAPBYBZ
UWAAY1
UWAAYB
Capacity (kW)
9, 10
10
11
12
12, 13
13
14, 15
15
page315
120
120
120
120
120
120
120
120
370
140
140
140
140
420
160
160
160
160
480
180
180
180
180
530
200
200
200
200
580
220
220
220
220
630
240
240
240
240
740
280
280
280
280
840
320
320
320
320
960
360
360
360
360
1060
400
400
400
400
1160
440
440
440
440
1260
480
480
480
480
50/60Hz
50Hz
60Hz
50Hz
60Hz
50Hz
60Hz
50Hz
50Hz
60Hz
Refrigerant
R-407C
R-22
Units series
Standard Unit
Year - Round Cooling
Only Unit
Brine Cooling Unit
Inverter Cooling Unit
Standard Unit
Model No.
UWAPAY3*
UWAPBY1
UWAPBYB
UWAPBY1K
UWAPBYBK
UWAPBY1Z
UWAPBYBZ
UWAXPAY1
UWAAY1
UWAAYB
Capacity (kW)
6.7/7.5
75
11.2/12.5
125
125
17/19
190
190
22.4/25
250
250
33.5/37.5
375
375
45/50
500
500
56/63
630
630
67/75
750
750
106
40
40
40
40
40
40
40
40
132
50
50
50
50
50
50
50
50
160
60
60
60
60
60
60
60
60
212
80
80
80
80
265
100
100
100
100
100
100
100
100
9
9, 10
10
11
12
12, 13
13
14
14, 15
15
page
Note: Capacity figures are provided for reference and assume a power supply frequency of 60 Hz.
Employs the new refrigerant R-407C.
UWAP75 750AY3UWAXP125 750AY1UWAP40 480BY1(K)(Z)UWAP40 120BYB (K)(Z)
New Refrigerant Efficient and Reliable Compressors
To improve their operationa l reliability, 5 -- 30HP modelsemploy scroll compressors, while 40 -- 480HP models areequipped with semi-hermetic single screw compressors.
Refrigerant inlet
Refrigerant outlet
Semi-hermetic singlescrew compressor
The user can select to give priority to either precision orreduced power consumption.
Continues ope ration to levelsas low as 10(12)% of totalcapacity to provide stablewater temperature controleven during low-load peri-ods.
This mode can be used to re-duce power consumption ifhighly precise water temperature control is not necessary dur-ing low-load periods. It shutsdown the compressor when theload drops below 40%.
High-P recis ion Mode Low-P ower Mode
Note: Switching between the above modes is accomplished using a control on
the outdoor unit.
Multiple Operating Modes
RefrigerantInlet
RefrigerantOutlet
WaterOutlet
WaterInlet
Heat Exchanger withStainless Steel Plates
Stainless s teel heat ex-changer plates prevent rust,thereby improving their dura-bility and the system's op-
Reliability
Applies to All Models
The compact design of these units significantly reduces thespace required for installation.
The horizontal linkup design increases installation flexibility.
In the outdoor unit, component parts of a small size have been used wherever
possible to reduced its size and correspondingly reduce how much space it re-
quires. Furthermore, replacing the 2-way refrigerant inlets with 4-way inlets has
reduced the amount of space the outdoor unit needs even further.
This design provides the installation does not protrude so far, making it possible
to install water chillers along a wall or under a roof overhang.
Note: Water supply piping must be purchased separately.
(UWAP375AY3 750AY3)
UWAP40 480BY1 (K)(Z)UWAP40 120BYB (K)(Z)
Easy Installation
UWAP125AY3 750AY3
High load compliance and highly efficient inverter control provide highly precise
adjustment of the water temperature, making it possible to reduce the size of
the peripheral equipment.
UWAXP125 750AY1
Compressor duty cycling control together with emergencyoperation and power-interruption auto-restart functions pro-vide enhanced air conditioning system reliability.
UWA40 480AY1UWA40 120AYB
A choice of three control system is available.
UWA40 480AY1
Outflow water temperature control
Provides precise control of the water temprerature.
(UWAP40 160BY1, UWA40 160AY1)
Compressor count control
Controls the number of compressors operating depending on the load.
(UWAP40 480BY1, UWA40 480AY1)
In flow water temperature control
Performs duty cycling control.
(UWAP40 480BY1, UWA40 480AY1)
Reduced Energy Wastage
Continuous c apacity control with a range from 10% to100% helps to reduce energy wastage during low-load
UWAP40 160BY1 (K)(Z)UWAP40 120BYB (K)(Z)
UWAP40 160BY1 (K)(Z)UWAP40 120BYB (K)(Z)
UWA40 160AY1UWA40 120AYB
UWA40 480AY1UWAP40 120AYB
UWAP40 480BY1 (Z)UWAP40 120BYB (Z)
UWAP40 480BY1
CapacityWater Temperature Control Range
Models Employing R-407C Models Employing R-22
3 30
40 480
5 to 16
4 to 25 (Inver Cooling Unit)
4 to 25-10 to 0 (Brine Cooling Unit)
4 to 16
Wide Water Temperature Control Range
The wide water temperature control range providescompatibility with a variety of heat source requirements.
A variety of brine-resistant specification models are availablethat provide stable cooling operation at brine outflowtemperatures down to -10 .
Applies to All Models
Applies to All Models
UWAP120BY1KUWAXP 750AY1 UWAP 180B Y 1
Wide Operation Range
A variety of year-round cooling type models are availablethat provide stable operation at outdoor temperatures down
The wide outdoor air temperature range ensures a stablesupply of chilled water year round.
Applies to All Models
CapacityOutdoor Air Temperature Range where Cooling Possible
Models Employing R-407C Models Employing R-22
3 30
40 480
-15 to 43
-5 to 43
-15 to 43
( Y ear-Round Cooling Only Unit )
0 to 43 ( Brine Cool ing Unit )
-5 to 43
High Precision
10
9
8
7
Upper Limit Signal
Water T e mp. ( )
Example of Outlet Water Temperature Control
If outlet water temperature rises above the upper limit signal,the load starts to increase in 10% inc rements
As the temperaturefalls below the upperlimit signal, the loadincrease incrementsare reduced to 5%.
As the temperaturefalls below the setvalue, the loadincrease incrementsre main at 5%.
When changes inoutlet watertemperature become1 or less, thethermostat is turned off.
Value Set
The outlet water temperature is precisely controlled to within0.5(with a stable load) through the use of electric expansion
UWAXP125 750AY1
UWAP40 160BY1 (K)(Z)UWAP40 120BYB (K)(Z)
UWA40 160AY1UWA40 120AYB
Inverter control with high load compliance achieves highlyaccura te outflow water temperature control to within 0.5
Note: In systems with one compressor installed and where the load factor is 30%
or more, and in systems with two or more compressors installed and where the
load factor is 30% or more, control to within 0.5 is possible.
AirCooled
WaterChillers
AirCooled
WaterChillers
Air Cool
ed Water Chillers
: UWAP S eries UWAXP Series
: UWA Series
7 8
8/2/2019 PCU0610A - Chiller [Small]
6/16
10
AirCooled
WaterChillers
AirCooled
WaterChillers
Notes:*1 Cooling capacity is based on the following conditions : Leaving chilled water temp.7 (44.5 F), entering chilled water temp.12 (53.6 F), and outdoor air temp. 35 DB(95 FDB).*2 The following safety devices are equipped as standard. High pressure protector. Low pressure protector. Compressor thermal protector. Fusible plug. Reverse-phaseprotector.
Overheat protection of discharge gas. Overcurrent relay(compressor). Freeze-up protection thermostat. Overcurrent relay(fan). Safety valve.*3 The unit is equipped with standard water filt er.*4 This product is manufactured in China.
Specifications
kW
Btu/h
USRT
/min
%
kW
m3/min
cfm
kW
mm
kg
kg
Model
Cooling capacity
Power supply
Chilled water flow rate
Capacity steps
Compressor
Evaporator type
Condenser type
Condenser
fan
Refrigerant
Pipe connections water
inlet/outlet
Dimensions(H W D)
Weight
Operating weight
Operation range
Type
Motor output
Type
Drive
Air flow rate
Motor output
118 355kW class
UWAP40 120BYBStandard Unit
60Hz
UWAP40BYB
(40 )
UWAP50BYB
(50 )
UWAP60BYB
(60 )
UWAP100BYB
(100 )
UWAP120BYB
(120 )
118
403,000
34
3 phase, 60 Hz 400/440 V, 4 wires s ystem
338
100~10-0
Semi-hermetic sealed single-screw type
30 1
Brazing Plate type
Cross fin coil
Propeller
Direct drive
810
28,593
0.5 4
R-407C
3B Flange (80A HG20593-97)
2,456 2,200 2,000
1,690
1,723
0 to 43
150
512,000
43
430
37 1
1,010
35,653
1.0 4
1,810
1,846
180
614,000
51
516
45 1
1,870
1,910
300
1,024,000
85
860
37
2
2,020
71,306
1.0 8
4B Flange (100A HG20593-97)
2,456 4,400 2,000
3,500
3,551
355
1,212,000
101
1,018
45 2
3,605
3,662
Notes:*1 Cooling capacity is based on the following conditions : Leaving chilled water temp.7 (44.5 F), entering chilled water temp.12 (53.6 F), and outdoor air temp. 35 DB(95 FDB).*2 The following safety devices are equipped as standard. High pressure protector. Low pressure protector. Compressor thermal protector. Fusible plug. Reverse-phaseprotector.
Overheat protection of discharge gas. Overcurrent relay(compressor). Freeze-up protection thermostat. Overcurrent relay(fan). Safety valve.*3 The unit is equipped with standard water filt er.*4 This product is manufactured in China.
530 1,260kW class
UWAP200 480BY1Standard Unit
50Hz
Specifications
kW
Btu/h
USRT
/min
%
kW
m3/min
cfm
kW
mm
kg
kg
Type
Motor output
Type
Drive
Air flow rate
Motor output
UWAP200BY1
(200 )UWAP220BY1
(220 )UWAP240BY1
(240 )UWAP280BY1
(280 )UWAP320BY1
(320 )
UWAP360BY1
(360 )UWAP480BY1
(460 )
530
1,809,000
151
3 phase, 50 Hz 380/400/415 V, 4 wires s ystem
1,519
100~10-0
Semi-hermetic sealed single-screw type
45 2+60
Brazing Plate type
Cross fin coil
Propeller
Direct drive
3,010
106,253
1.0 14
R-407C
5B Flange (125A HG20593-97)
2,456 7,050
2,000
6,000
6,198
0 to 43
UWAP400BY1
(400 )UWAP440BY1
(440 )Model
Cooling capacity
Power Supply
Chilled Water Flow Rate
Capacity Steps
Compressor
Evaporetor type
Comdenser type
Condenser
fan
Refrigerant
Pipe connections water
inlet/outlet
Dimensions(H W D)
Weight
Operation weight
Operation range
580
1,979,000
165
1,663
45+60 2
3,440
121,432
1.0 16
2,456 7,500
2,000
6,500
6,719
630
2,150,000
179
1,806
60 3
3,870
136,611
1.0 18
2,456 7,950
2,000
7,005
7,245
740
2,525,000
210
2,121
(45+60) 2
4,300
151,790
(1.0 10) 2
4B Flange
(100A HG20593-97)
(2,456 4,850
2,000) 2
4,125 2
4,196 2
840
2,867,000
239
2,408
(60 2) 2
5,160
182,148
(1.0 12) 2
(2,456 5,300
2,000) 2
4,590 2
4,661 2
960
3,276,000
273
2,752
(45 3) 2
5B Flange (125A HG20593-97)
(2,456 6,600
2,000) 2
5,500 2
5,691 2
1,060
3,617,000
301
3,039
(45 2+60) 2
6,020
212,506
(1.0 14) 2
(2,456 7,050
2,000) 2
6,000 2
6,198 2
1,160
3,959,000
330
3,325
(45+60 2) 2
6,880
242,864
(1.0 16) 2
(2,456 7,500
2,000) 2
6,500 2
6,719 2
1,260
4,300,000
358
3,612
(60 3) 2
7,740
273,222
(1.0 18) 2
(2,456 7,950
2,000) 2
7,005 2
7,245 2
Notes:*1 Cooling capacity is based on the following conditions : Leaving chilled water temp.7 (44.5 F), entering chilled water temp.12 (53.6 F), and outdoor air temp. 35 DB(95 FDB).*2 The following safety devices are equipped as st andard. High pressure protector. Low pressure protector. Compressor thermal protector. Fusible plug. Reverse-phaseprotector.
Overheat protection of discharge gas. Overcurrent relay(compressor). Freeze-up protection thermostat. Overcurrent relay(fan). Safety valve.*3 The unit is equipped with standard water filter.*4 This product is manufactured in China.
Specifications
kW
Btu/h
USRT
/min
%
kW
m3/min
cfm
kW
mm
kg
kg
Type
Motor output
Type
Drive
Air flow rate
Motor output
UWAP40BY1
(40 )UWAP50BY1
(50 )UWAP60BY1
(60 )UWAP80BY1
(80 )UWAP100BY1
(100 )
UWAP120BY1
(120 )UWAP180BY1
(180 )
106
362,000
30
3 phase, 50 Hz 380/400/415 V, 4 wires s ystem
304
100~10-0
Semi-hermetic sealed single-screw type
30 1
Brazing Plate type
Cross fin coil
Propeller
Direct drive
780
27,534
0.5 4
R-407C
3B Flange (80A HG20593-97)
2,456 2,200 2,000
1,690
1,723
0 to 43
UWAP140BY1
(140 )UWAP160BY1
(160 )
106 480kW class
UWAP40 180BY1Standard Unit
50Hz
Model
Cooling capacity
Power Supply
Chilled Water Flow Rate
Capacity Steps
Compressor
Evaporetor type
Comdenser type
Condenser
fan
Refrigerant
Pipe connections water
inlet/outlet
Dimensions(H W D)
Weight
Operation weight
Operation range
132
450,000
38
378
37 1
860
30,358
1.0 4
1,810
1,846
160
546,000
46
459
45 1
1,870
1,910
210
717,000
60
602
60 1
1,290
45,537
1.0 6
2,456 2,650
2,000
2,375
2,422
265
904,000
75
760
37 2
1,600
56,480
1.0 8
4B Flange (100A HG20593-97)
2,456 4,400 2,000
3,500
3,551
320
1,092,000
91
917
45
2
1,720
60,716
3,605
3,662
370
1,263,000
105
1,061
45+60
2,150
75,895
1.0 10
2,456 4,850
2,000
4,125
4,196
420
1,433,000
119
1,204
60 2
2,580
91,074
1.0 12
2,456 5,300
2,000
4,590
4,661
480
1,638,000
137
1,376
45 3
5BFlange
(125AHG20593-97 )
2,456 6,600
2,000
5,500
5,691
Notes:*1 Cooling capacity is based on the following conditions : Leaving chilled water temp.7 (44.5 F), entering chilled water temp.12 (53.6 F), and outdoor air temp. 35 DB(95 FDB).*2 The following safety devices are equipped as standard. High pressure switch. Reverse-phase protector. Fusible plug. Freeze up thermostat. Overcurrent relay for compressor
and fan motor. Overheat protection for discharge gas. fan thermal protector.*3 This product is manufactured in Japan.
Specifications
kW
Btu/h
USRT
/min
%
kW
m3/min
cfm
kW
mm
kg
kg
Model
Cooling capacity
(50/60 Hz)
Power supply
Chilled water flow rate
(50/60 Hz)
Capacity steps
Compressor
Evaporator type
Condenser type
Condenser
fan
Refrigerant
Pipe connections water
inlet/outlet
Dimensions (H W D)
Weight
Operating weight
Operation range
Type
Motor output
Type
Drive
Air flow rate
(50/60 Hz)
Motor output
UWAP75AY3
(3 )
UWAP125AY3
(5 )
UWAP190AY3
(8 )UWAP250AY3
(10 )
UWAP375AY3
(15 )UWAP750AY3
(30 )
6.7/7.5
22,900/25,600
1.91/2.13
3 phase, 50 Hz 380/400/415 V, 60 Hz 400/440 V, 3 w ires system
19/22
100-0
Hermetically sealed scroll type
2.2 1
Brazed plate heat exchanger
Cross fin coil
Propeller
Direct drive
75/85
2,650/3,000
0.14 1
R-407C
1B Flange (JIS10K)(25A) 2
1,450 635(839) 690
136
138
-15 to 43
11.2/12.5
38,200/42,700
3.19/3.55
32/36
3.75 1
90/95
3,180/3,350
0.20 1
140
142
17.0/19.0
58,000/64,900
4.83/5.40
49/54
5.5 1
140/160
4,940/5,650
0.215+0.14
1 1/2B Flange (JIS10K)(40A) 2
1,450 1,280 690
248
253
22.4/25.0
76,500/85,400
6.37/7.11
64/72
7.5 1
175/185
6,180/6,530
0.215+0.22
260
264
33.5/37.5
114,000/128,000
9.53/10.7
96/108
100-67-34-0
7.5+3.75
265/280
9,350/9,880
(0.215+0.22)+0.2
1B Flange (JIS10K)
(25A) 2+11/2BFlange
(JIS10K)(40A) 2
1,500 1,925 690
400
407
45.0/50.0
154,000/171,000
12.8/14.2
129/143
100-50-0
7.5 2
350/370
12,400/13,100
(0.215+0.22) 2
1 1/2B Flange
(JIS10K)(40A) 4
1,500 2,570 690
515
525
56.0/63.0
191,000/215,000
15.9/17.9
161/181
100-80-60-40-20-0
7.5 2+3.75
440/465
15,500/16,400
(0.215+0.22) 2+0.2
1B Flange (JIS10K)
(25A) 2+11/2BFlange
(JIS10K)(40A) 4
1,550 3,230 758
680
695
67.0/75.0
229,000/256,000
19.1/21.3
192/215
100-67-34-0
7.5 3
525/555
18,500/19,600
(0.215+0.22) 3
1 1/2B Flange
(JIS10K)(40A) 6
1,550 3,870 758
800
820
UWAP500AY3
(20 )
UWAP630AY3
(25 )
*1
6.7/7.5 67/75kW class
UWAP75 750AY3Standard Unit
50/60Hz
9
Air Cooled Water Chillers
8/2/2019 PCU0610A - Chiller [Small]
7/16
8/2/2019 PCU0610A - Chiller [Small]
8/16
8/2/2019 PCU0610A - Chiller [Small]
9/16
UWAP40BY1
UWAP40BYB
UWAP50BY1
UWAP50BYB
UWAP60BY1
UWAP60BYBUWAP80BY1
UWAP100BY1
UWAP100BYB
UWAP120BY1
UWAP120BYBUWAP140BY1 UWAP160BY1 UWAP180BY1
Model
Remote controller
Communication I/F P.C. board
Communication I/F P.C. B storage box
Transmission wire
Central remote controller
Unified ON/OFF controller
Schedule timer
BRC307C50
BRP66B3 1
BRP66A97 1(external)
BER66A5 1
DCS302CA61
DCS301BA61
DST301BA61
BRP66A100 1(internal)
BER66A7 1
Not required (S.Box installed)
UWAP75AY3 UWAP125AY3 UWAP190AY3 UWAP250AY3 UWAP375AY3 UWAP500AY3 UWAP630AY3 UWAP750AY3
*1
*1
*1
*1
Model
Remote controller
Chillingwatersupplyinterruptingrelay
Waterhigh pressure (1.6 MPa)upgrader
IPU
Dio unit
D Air unit
Interface for use in L ONWORKS
Interface for use in BACnet
Central remote controller
Unified ON/OFF controller
Schedule timer
BRC307D503
GWEL-UWYP40B
GWP-UWYP40B
DAM602A5
DEC102A
DAM101A
DMS504B51
DMS502A51
DCS302CA61
DCS301BA61
DST301BA61
GWP-UWYP80B
GWEL-UWYP100B
GWP-UWYP100B
GWEL-UWYP180B
GWP-UWYP180B
UWAP200BY1 UWAP220BY1 UWAP240BY1 UWAP280BY1 UWAP320BY1 UWAP360BY1 UWAP400BY1 UWAP440BY1 UWAP480BY1Model
Remote controller
Chillingwatersupplyinterruptingrelay
Waterhigh pressure (1.6 MPa)upgrader
IPU
Dio unit
D Air unit
Interface for use in LONWORKS
Interface for use in BACnet
Central remote controller
Unified ON/OFF controller
Schedule timer
BRC307D503
GWEL-UWYP180B
GWP-UWYP180B
DAM602A5
DEC102A
DAM101A
DMS504B51
DMS502A51
DCS302CA61
DCS301BA61
DST301BA61
GWEL-UWYP280B
GWP-UWYP280B
GWEL-UWYP360B
GWP-UWYP360B
Notes:*1 Communication I/F P.C. board, Communication I/F P.C. B storage box and Transmission w ire are also required.
Model
Remote controller *1
Communication I/F P.C. board
Communication I/F P.C. B storage box
Transmission wire
UWAXP125AY1
UWA40AY1
UWA40AYB
UWA50AY1
UWA50AYB
UWA60AY1
UWA60AYBUWA80AY1
UWA100AY1
UWA100AYB
UWA120AY1
UWA120AYBUWA140AY1 UWA160AY1 UWA180AY1
UWAXP190AY1 UWAXP250AY1 UWAXP375AY1 UWAXP500AY1 UWAXP630AY1 UWAXP750AY1
BRC307C50
BRP66B3 1
BER66A5
BPR66A97
BER66A6
BER66A7
BRP66B3 2
BRP66A96
BER66A8
Model
Remote controller
Chillingwatersupplyinterruptingrelay
Waterhigh pressure (1.6 MPa)upgrader
IPU
Dio unit
D Air unit
Interface for use in LONWORKS
Interface for use in BACnet
Central remote controller
Unified ON/OFF controller
Schedule timer
Model
Remote controller
Chillingwatersupplyinterruptingrelay
Waterhigh pressure (1.6 MPa)upgrader
IPU
Dio unit
D Air unit
Interface for use in LONWORKS
Interface for use in BACnet
Central remote controller
Unified ON/OFF controller
Schedule timer
UWA200AY1 UWA220AY1 UWA240AY1 UWA280AY1 UWA320AY1 UWA360AY1 UWA400AY1 UWA440AY1 UWA480AY1
BRC307D503
GWEL-UWY40A
GWP-UWY40A
DAM602A5
DEC102A
DAM101A
DMS504B51
DMS502A51
DCS302CA61
DCS301BA61
DST301BA61
BRC307D503
GWEL-UWY180A
GWP-UWY180A
DAM602A5
DEC102A
DAM101A
DMS504B51
DMS502A51
DCS302CA61
DCS301BA61
DST301BA61
GWEL-UWY80A
GWP-UWY80A GWP-UWY100A
GWEL-UWY180A
GWP-UWY180A
GWEL-UWY280A
GWEL-UWY281A
GWEL-UWY360A
GWP-UWY360A
Notes:*1 Communication I/F P.C. board, Communication I/F P.C. B storage box and Transmission waire are also required.
Option List
Specifications
kW
Btu/h
USRT
/min
%
kW
m3/min
cfm
kW
mm
kg
kg
Model
Cooling capacity
Power supply
Chilled water flow rate
Capacity steps
Compressor
Evaporator type
Condenser type
Condenser
fan
Refrigerant
Pipe connections water
inlet/outlet
Dimensions (H W D)
Weight
Operating weight
Operation range
Type
Motor output
Type
Drive
Air flow rate
Motor output
Notes:*1 Cooling capacity is based on the following conditions : Leaving chilled water temp.7 (44.5 F), entering chilled water temp.12 (53.6 F), and outdoor air temp. 35 DB(95 FDB).*2 The following safety devices are equipped as standard. High pressure protector. Low pressure protector. Compressor thermal protector. Fusible plug. Reverse-phaseprotector.
Overheat protection of discharge gas. Overcurrent relay(compressor). Freeze-up protection thermostat. Overcurrent relay(fan). Safety valve.*3 The unit is equipped with standard water filt er.*4 The limited length of wire represents its max. length when the pressure is lower than 2%.*5 This product is manufactured in China.
*1
118 355kW class
UWA40 120AYBStandard Unit
60Hz
UWA120AYB
(120 )
UWA100AYB
(100 )
UWA60AYB
(60 )UWA50AYB
(50 )
UWA40AYB
(40 )
118
403,000
34
3 phase, 60 Hz 400/440 V, 4 wires s ystem
338
100~10-0 (continuous capacity control)
Semi-hermetic sealed single-screw type
30 1
Blazing Plate type
Cross fin coil
Propeller
Direct drive
800
28,240
0.5 4
R-22
3B Flange (80A)
2,395 2,200 2,000
1,500
1,517
-5 to 43
150
512,000
43
430
37 1
810
28,593
0.8 4
1,650
1,670
180
614,000
51
516
45 1
940
33,182
1.2 4
1,750
1,773
300
1,024,000
85
860
37 2
1,620
57,186
0.8 8
4B Flange (100A)
2,395 4,400 2,000
3,300
3,336
355
1,212,000
101
1,018
45 2
1,880
66,364
1.2 8
3,500
3,542
Specifications
kW
Btu/h
USRT
/min
%
kW
m3/min
cfm
kW
mm
kg
kg
Model
Cooling capacity
Power supply
Chilled water flow rate
Capacity steps
Compressor
Evaporator type
Condenser type
Condenser
fan
Refrigerant
Pipe connections water
inlet/outlet
Dimensions(H W D)
Weight
Operating weight
Operation range
Type
Motor output
Type
Drive
Air flow rate
Motor output
UWA200AY1
(200 )UWA220AY1
(220 )UWA240AY1
(240 )UWA280AY1
(280 )UWA320AY1
(320 )UWA360AY1
(360 )UWA480AY1
(480 )
530
1,809,000
151
3 phase, 50 Hz 380/400/415 V, 4 wires system
1,519
100~10-0 (continuous capacity control)
Semi-hermetic sealed single-screw type
45 2+60
Blazing Plate type
Cross fin coil
Propeller
Direct drive
2,620
92,486
1.2 12
R-22
5B Flange (125A HG20593-97)
2,460 6,600 2,000
5,660
5,737
-5 to 43
580
1,979,000
165
1,663
45+60 2
2,720
96,016
5,695
5,782
630
2,150,000
179
1,806
60 3
2,820
99,546
5,750
5,850
840
2,867,000
239
2,408
(60 2) 2
3.760
132,728
3,640 2
3,704 2
960
3,276,000
273
2,752
(45 3) 2
5,040
177,912
(1.2 12) 2
5B Flange (125A HG20593-97)
(2,460 6,600 2,000) 2
5,605 2
5,670 2
1,060
3,617,000
301
3,039
(45 2+60) 2
5,240
184,972
5,660 2
5,737 2
1,160
3,959,000
330
3,325
(45+60 2) 2
5,440
192,032
5,695 2
5,782 2
1,260
4,300,000
358
3,612
(60 3) 2
5,640
199,092
5,750 2
5,850 2
UWA400AY1
(400 )UWA440AY1
(440 )
Notes:*1 Cooling capacity is based on the following conditions : Leaving chilled water temp.7 (44.5 F), entering chilled water temp.12 (53.6 F), and outdoor air temp. 35 DB(95 FDB).*2 The following safety devices are equipped as standard. High pressure protector. Low pressure protector. Compressor thermal protector. Fusible plug. Reverse-phaseprotector.
Overheat protection of discharge gas. Overcurrent relay(compressor). Freeze-up protection thermostat. Overcurrent relay(fan). Safety valve.*3 Standard for the max. chilled water pressure is 0.7MPa, but1.6MPa is available if required.*4 Installation/operating weight includes the weight of refrigerant and refrigerant oil(charged before delivery).
740
2,525,000
210
2,121
(45+60) 2
3,560
125,668
(1.2 8) 2
4B Flange (100A HG20593-97)
(2,395 4,400 2,000) 2
3,620 2
3,684 2
*1
530 1,260kW class
UWA200 480AY1Standard Unit
50Hz
AirCooled
WaterChillers
AirCooled
WaterChillers
15 16
Air Cooled Water Chillers
8/2/2019 PCU0610A - Chiller [Small]
10/16
For High Outdoor Temperature Use
Specifications
Model
Cooling capacity
Power supply
Chilled water flow rate
Cooling capacity
Chilled water flow rate
Capacity steps
Compressor
Evaporator type
Condenser type
Condenser
fan
Refrigerant
Pipe connections water inlet/outlet
Dimensions (H W D)
Weight
Operating weight
Operation range
kW
Btu/h
USRT
kW
Btu/h
USRT
%
kW
m3/min
cfm
kW
mm
kg
kg
Type
Motor output
Type
Drive
Air flow rate
Motor output
UWA27JATJ
(25 )
79.0
269,800
22.4
3 phase, 60 Hz, 208/230 V, 3 wires system
206
71.0
242,000
20.1
185
100-50-0
Semi-hermetically sealed reciprocating
22
Dry expansion shell and Hi-X tube
Cross fin coil (Waffle louver fins and Hi-X tubes)
Propeller
Direct drive
580
20,480
1.7ea. 2
R-22
FPT2 (50A)
1,765 2,025
1,065
750
790
15 to 49
UWA32JATJ
(30 )UWA43JATJ
(40 )UWA53JATJ
(50 )UWA62JATJ
(60 )UWA70JATJ
(70 )UWA80JATJ
(80 )UWA90JATJ
(90 )UWA108JATJ
(100 )UWA122JATJ
(120 )
94.3
320,600
26.7
245
82.0
280,900
23.4
215
100-66-33-0
480
16,950
1.0ea. 2
1,915 2,025
1,065
900
970
125.0
426,600
35.5
326
111.0
378,900
31.5
289
30
1,160
40,960
1.0ea. 4
FPT2 1/2 (65A)
1,890 2,005 2,000
1,300
1,370
5 to 49
162.0
553,500
46.1
423
145.0
494,000
41.0
377
100-75-50-25-0
37
1.7ea. 4
1,540
1,630
185.0
632,100
52.6
483
171.0
584,100
48.6
466
45
1,400
49,430
2.5ea. 4
FPT3 (80A)
1,610
1,700
212.0
722,200
60.0
552
191.0
653,100
54.2
497
100-83-66-50-33-0
26 2
1,920
67,800
1.0ea. 8
4B Flange (JIS16K)(100A)
1,745 2,005
4,000
2,500
2,600
15 to 49
253.0
865,000
72.0
661
219.0
746,400
62.1
570
30 2
1,915 2,005 4,000
2,600
2,730
274.0
936,400
78.0
715
248.0
845,200
70.4
645
100-88-75-63-50-25-0
2,850
2,980
324.0
1,107,000
92.2
845
285.0
972,200
81.0
742
37 2
2,320
81,920
1.7ea. 8
5B Flange (JIS16K)(125A)
2,870
3,000
370.0
1,262,000
105.0
964
335.0
1,145,000
95.3
873
45 2
2,800
98,870
2.5ea. 8
3,050
3,210
Notes:*1 Cooling capacity is based on the following conditions : Leaving chilled water temp.6.7 (44 F), entering chilled water temp.12.2 (54 F), and outdoor air temp. 35 DB(95 FDB).*2 Cooling capacity is based on the following conditions : Leaving chilled water temp.6.7 (44 F), entering chilled water temp.12.2 (54 F), and outdoor air temp. 46 DB(115 FDB).*3 The following safety devices are equipped as st andard. High/low pressure switch. Oil pressure control switch. Compressor thermal protector. Recycling guard timer.
Crankcase heater. 3-element overcurrent relay for compressors and fan motors. Freeze-up protection thermostat. Fusible plug. Safety valve(for UWA53, 62, 90, 108,122JATJ).
*4 This product is manufactured in Japan.
*1
*2
79 370kW class
UWA27 122JATJFor High Outdoor Temperature Use
60Hz
Specifications
Model
Cooling capacity
Power supply
Chilled water flow rate
Compressor
Evaporator type
Condenser type
Condenser
fan
Refrigerant
Pipe connections water inlet/outlet
Dimensions (H W D)
Weight
Operation range
Type
Motor output
Type
Drive
Air flow rate
Motor output
kW
Btu/h
USRT
kW
m3/min
cfm
kW
mm
kg
351.6
1,201,500
99.9
3 phase, 50 Hz 380/400/415 V, 4 wires system
100-83-67-50-33-17-0
Semi-hermetic sealed reciprocating
30 3
Dry expansion shell and Hi-X tubes
Cross fin coil (Waffle louver fins and Hi-X tubes)
Propeller
Direct drive
2,580
91,100
0.9ea. 12
R-22
5B Flange (JIS16K)(125A)
2,095 2,005 5,700
4,360
5 to 49
404.4
1,380,800
115.0
37 3
3,000
105,900
4,470
474.7
1,620,600
135.0
45 3
3,720
131,400
1.5ea. 12
4,660
562.8
1,921,500
160.0
100-88-75-63-50-25-0
37 4
Dry expansion shell and corrugated tubes
4,000
141,300
0.9ea. 16
2,075 2,005 8,000
6,110
667.9
2,280,400
189.9
45 4
4,960
175,200
1.5ea. 16
6,340
791.0
2,700,800
224.7
100-83-67-50-33-17-0
37 6
Dry expansion shell
and Hi-X tubes
6,000
211,900
0.9ea. 24
2,095 2,005 11,400
8,940
UWA270JY1(300 )UWA228JY1(240 )UWA192JY1(200 )UWA162JY1(180 )UWA138JY1(150 )UWA120JY1(130 )
Notes:*1 Cooling capacity is based on the following conditions : Leaving chilled water temp.6.7 (44 F), entering chilled water temp.12.2 (54 F), and outdoor air temp. 35 DB(95 FDB).*2 The following safety devices are equipped as standard. High pressure switch. Low pressure switch. Oil pressure control switch. Compressor thermal protector. Recycling
guard timer. Crankcase heater. 3-element overcurrent relay (Compressor, Fan motors). Freeze-up protection thermostat. Fusible plug. Safety valve (except for UWA120JY1).*3 This product is manufactured in Japan.
*1
351.6 791kW class
UWA120 270JY1For High Outdoor Temperature Use
50Hz
Specifications
Model
Cooling capacity
Power supply
Chilled water flow rate
Cooling capacity
Chilled water flow rate
Capacity steps
Compressor
Evaporator type
Condenser type
Condenser
fan
Refrigerant
Pipe connections water
inlet/outlet
Dimensions (H W D)
Weight
Operating weight
Operation range
Type
Motor output
Type
Drive
Air flow rate
Motor output
108.4
369,800
30.8
3 phase, 50 Hz 380/400/415 V, 4 wires s ystem
282
97.4
332,500
27.7
279
100-66-33-0
Semi-hermetically sealed reciprocating
30
Dry expansion shell and Hi-X tube
Cross fin coil (Waffle louver fins and Hi-X tubes)
Propeller
Direct drive
860
30,370
0.9ea. 4
R-22
FPT2 1/2 (65A)
1,720 2,005 2,000
1,230
1,300
5 to 52
137.2
468,200
39.0
358
124.8
425,800
35.4
325
100-75-50-25-0
37
1,000
35,310
1,890 2,005 2,000
1,420
1,490
161.3
550,400
45.8
420
149.9
511,500
42.6
391
45
1,240
43,790
1.5ea. 4
FPT3 (80A)
1,520
1,610
186.0
634,900
52.9
485
167.4
571,400
47.6
436
100-83-66-50-33-0
1,720
60,730
0.9ea. 8
1,745 2,005 4,000
2,500
2,600
219.1
747,600
62.3
571
197.1
672,600
56.0
514
30 2
4B Flange (JIS16K)(100A)
2,600
2,730
250.6
855,100
71.2
653
225.5
769,400
64.1
588
100-88-75-63-50-25-0
2,000
70,620
1,915 2,005 4,000
2,850
2,980
272.7
930,500
77.5
711
250.8
855,900
71.3
654
37 2
2,870
3,000
319.2
1,089,200
90.7
832
290.5
991,200
82.6
757
45 2
2,480
87,580
1.5ea. 8
5B Flange
(JIS16K)(125A)
3,050
3,210
Notes:*1 Cooling capacity is based on the following conditions : Leaving chilled water temp.6.7 (44 F), entering chilled water temp.12.2 (54 F), and outdoor air temp. 35 DB(95 FDB).*2 Cooling capacity is based on the following conditions : Leaving chilled water temp.6.7 (44 F), entering chilled water temp.12.2 (54 F), and outdoor air temp. 46 DB(115 FDB).*3 The following safety devices are equipped as st andard. High/low pressure switch. Oil pressure control switch. Compressor thermal protector. Recycling guard timer.
Crankcase heater. 3-element overcurrent relay for compressors and fan motors. Freeze-up prorection thermostat. Fusible plug. Safety valve(for UWA47, 55, 93, 109JAY1).*4 This product is manufactured in Japan.
UWA37JAY1
(40 )UWA47JAY1
(50 )UWA55JAY1
(60 )UWA63JAY1
(70 )UWA75JAY1
(80 )UWA80JAY1
(90 )UWA93JAY1
(100 )
*1
*2
kW
Btu/h
USRT
kW
Btu/h
USRT
%
kW
m3/min
cfm
kW
mm
kg
kg
UWA109JAY1
(120 )
108.4 319.2kW class
UWA37 109JAY1For High Outdoor Temperature Use
50Hz
UWA55JAY1 UWA138JY1 UWA80JATJ
Provides a stable supply of chilled water even when the outdoor temperature is ashigh as 49 .
Capacity can be controlled in multiple steps of between 3 and7 for efficient energy use.
Full Lineup Includes Models withCapacities Ranging from 79 791kW.
Equipped with a Compact andPowerful Semi-hermetically SealedReciprocating Compressor.
: UWA Series
UWA37JAY1 109JAY1UWA120JY1 270JY1U W A 2 7J A T J / 3 2 J A T J , 7 0J A T J 1 2 2J A T JUWA43JATJ 62JATJ
5 to 525 to 49
15 to 495 to 49
Wide Operating Range
Temperature range by model.
Wide Capacity Range
UWA37JAY1 109JAY1UWA43JATJ 122JATJUWA120JY1 270JY1
A selector switch makes it possible to operate only one refrig-erant circuit while the other is under repair.
Two Independent Refrigerant Circuits
UWA63JAY1 109JAY1UWA70JATJ 122JATJU WA12 0 JY 1 2 70 JY 1
Air Cooled Water Chillers
AirCooled
WaterChillers
AirCooled
WaterChillers
17
18
8/2/2019 PCU0610A - Chiller [Small]
11/1619 20
AirCooledWaterChillers
-HeatPumpType
AirCooledWaterChillers
-HeatPumpType
Low Power Consumption
Continuous capacity control with a range from 10(12)% to100% helps to reduce energy wastage during low-load
UWYP 40 160BY1 UWYP 40 120BYBUWY40 120AY1 UWY40 120AYB
UWYP40 160BY1UWYP40 120BYB
UWA40 160AY1UWA40 120AYB
High Precision
10
9
8
7
Upper Limit Signal
W a te r T e mp . ( )
Example of Outlet Water Temperature Control
If outlet water temperature rises above the upper limit signal,the load starts to increase in 10% inc rements
As the temperaturefalls below the upperlimit signal, the loadincrease incrementsare reduced to 5%.
As the temperaturefalls below the setvalue, the loadincrease incrementsre main at 5%.
When changes in outletwater temperaturebecome 1 or less,the thermostat is turnedoff.
Value Set
The outlet water temperature is precisely controlled to within0.5
(with a stable load) through the use of electric expansion
: UWYP Series
: UWY Series
New Refrigerant
UWYP125 750AY3UWYP40 480BY1UWYP40 120BYB
Employs the new refrigerant R-407C.
Efficient and Reliable Compressors
To improve their operational reliability, 40 -- 480HP modelsare equipped with semi-hermetic single screw compressors.
Applies to All Models
Re frigerant inlet
Re frigerant outlet
Semi-hermetic singlescrew compressor
UWYP40 160BY1UWYP40 120BYB
UWY40 160AY1UWY40 120AYB
UWYP100 480BY1UWYP100 120BYB
Duty cycling control equalizes the operating time of the
UWY100 480AY1
UWY40 160AY1
A choice of three control systems is available.
Outflow water temperature control
Provides precise control of the water temperature.
Compressor count control
Controls the number of compressors operating depending on the load.
Inflow water temperature control
Performs duty cycling control.
UWY100 120AYB
UWYP40 160BY1UWY40 480AYBUWYP40 120BYB
Continues ope ration to levelsas low as 12% of total ca-pacity to provide stable wa-ter temperature control evenduring low-load periods.
This mode can be used toreduce power consumption ifhighly precise water tempera-ture control is not necessaryduring low-load periods. Itshuts down the compressorwhen the load drops below40%.
High-P recision Mode Low-Power Mode
Multiple Operating Modes
The user can select to give priority to either precision or reduced
power consumption.
Capacity Control Mode
The maximum current level of the compressor can be specified
in order to control demand for power. Since this func tion allows
setting of the upper limit current value, comfortable operation is
maintained while effectively controlling demand. In contrast to
conventional capacity control step limit systems, maximum
capacity is maintained at the desired demand value.
Current Demand Function
Demand Mode
Users can select the operating mode that best matches theheat source application.
Note: Switching between the above modes is accomplished using a control on
the outdoor unit.
Note: Water supply piping must be purchased separately.
(UWYP375AY3 750AY3)
UWYP40 480BY1UWYP40 120BYB
UWY40 120AY1UWY40 120AYB
Wide Operation Range
Note: Measures to protect against drain water freezing are necessary in cold re-gions where the highest temperature stays below 0 on several consecutive
days.
A new defrosting system makes possible heating operationeven when the outdoor temperature is as low as -15 .
CapacityOutdoor Air Temperature Range where Cooling Possible
Models Employing R-407C Models Employing R-22
5 3 0
40 480
-15 to 43
-5 to 43 -5 to 43
UWYP40 480BY1UWYP40 120BYB
UWY40 480AY1UWY40 120AYB
UWYP40 480BY1UWYP40 120BYB
UWY40 480AY1UWY40 120AYB
Applies to All Models
RefrigerantInlet
RefrigerantOutlet
WaterOutlet
Heat Exchanger with
Stainless Steel Plates
Stainless steel heat ex-changer plates prevent rust,thereby improving their du-rability and the system'soperational reliability.
Reliability
Applies to All Models
Easy Installation
Defrosting is performed under computer control as part ofcontinuous capacity control, resulting in stable heatingperformance.
The system detects ice formation by constantly monitoring the outdoor tempera-
ture, the pressures of the high- and low-pressure components, and the timers. In
addition, continuous capacity control allows smooth control of capacity even af-
ter a rise in the pressure of the high-pressure components. Remaining ice is
melted a little at a time, and stable heating performance is maintained.
The compact design of these units significantly reduces thespace required for installation.
In the outdoor unit, component parts of a small size have been used whereverpossible to reduced its size and correspondingly reduce how much space it re-
quires. Furthermore, replacing the 2-way refrigerant inlets with 4-way inlets has
reduced the amount of space the outdoor unit needs even further.
UWYP125 750AY3 The horizontal linkup design increases installation flexibility.
This design ensures the installation does not protrude so far, making it possible
to install water chillers along a wall or under a roof overhang.
Air heat exchangers employ fins with acrylic coating forsuperior durability.
50/60Hz
50Hz
60Hz
50Hz
60Hz
R-407C
R-22
Standard Unit
Standard Unit
Refrigerant Uni ts ser ie s Mod el No.
UWYPAY3
UWYPBY1
UWYPBYB
UWYAY1
UWYAYB
Capacity (kW)
21
21, 22
22
23
24
page6.7/7.5
11.2/12.5
125
17/19
190
22.4/25
250
33.5/37.5
375
45/50
500
56/63
630
67/75
750
106
40
40
40
40
132
50
50
50
50
160
60
60
60
60
212
80
80
80
265
100
100
100
100
50Hz
60Hz
50Hz
60Hz
R-407C
R-22
Standard Unit
Standard Unit
Refrigerant Uni ts ser ie s Mod el No.
UWYPBY1
UWYPBYB
UWYAY1
UWYAYB
Capacity (kW)
21, 22
22
23
24
page315
120
120
120
120
370
140
140
420
160
160
480
180
180
530
200
200
580
220
220
630
240
240
740
280
280
840
320
320
960
360
360
1060
400
400
1160
440
440
1260
480
480
Model Lineup
UWY P750AY3 UWYP 120B Y 1 UWY P180B Y 1
Air Cooled Water Chillers -Heat PumpType
8/2/2019 PCU0610A - Chiller [Small]
12/16
8/2/2019 PCU0610A - Chiller [Small]
13/16
AirCooledWaterChillers
-HeatPumpType
AirCooledWaterChillers
-HeatPumpType
UWYP40AY1
UWYP50AY1
UWYP60AY1
UWYP 80AY1 UWYP 100AY 1
UWYP120AY1
UWYP140AY1
UWYP160AY1
UWYP180AY1
UWYP200AY1
UWYP220AY1
UWYP240AY1
UWYP280AY1
UWYP320AY1
UWYP380AY1
UWYP400AY1
UWYP440AY1
UWYP480AY1
Model
Remote controller
Chilling watersupply interrupting relay
Waterhigh pressure (1.6 MPa)upgrader
IPU
Dio unit
D Air unit
Interface for use in L ONWORKS
Interface for use in BACnet
Central remote controller
Unified ON/OFF controller
Schedule timer
BRC307D503
GWEL-UWYP40B
GWP-UWYP40B
DAM602A5
DEC102A
DAM101A
DMS504B51
DMS502A51
DCS302CA61
DCS301BA61
DST301BA61
GWP-UWYP80B
GWEL-UWYP100B
GWP-UWYP100B
GWEL-UWYP180B
GWP-UWYP180B
GWEL-UWYP280B
GWP-UWYP280B
GWEL-UWYP360B
GWP-UWYP360B
Option List
UWYP40BY1
UWYP50BY1
UWYP60BY1
UWYP40BYB
UWYP50BYB
UWYP60BYB
UWYP80BY1 UWYP100BY1
UWYP120BY1
UWYP140BY1
UWYP160BY1
UWYP100BYB
UWYP120BYB
UWYP180BY1
UWYP200BY1
UWYP220BY1
UWYP240BY1
UWYP280BY1
UWYP320BY1
UWYP360BY1
UWYP400BY1
UWYP440BY1
UWYP480BY1
Model
Remote controller
Chilling watersupply interrupting relay
Waterhigh pressure (1.6 MPa)upgrader
IPU
Dio unit
D Air unit
Interface for use in LONWORKS
Interface for use in BACnet
Central remote controller
Unified ON/OFF controller
Schedule timer
BRC307D503
GWEL-UWYP40B
GWP-UWYP40B
DAM602A5
DEC102A
DAM101A
DMS504B51
DMS502A51
DCS302CA61
DCS301BA61
DST301BA61
GWP-UWYP80B
GWEL-UWYP100B
GWP-UWYP100B
GWEL-UWYP180B
GWP-UWYP180B
GWEL-UWYP280B
GWP-UWYP280B
GWEL-UWYP360B
GWP-UWYP360B
UWYP125AY3 UWYP190AY3 UWYP250AY3 UWYP375AY3 UWYP500AY3 UWYP630AY3 UWYP750AY3
Notes:
*1 Communication I/F P.C. board, Communication I/F P.C. B s torage box and Transmission waire are also required.
Remote controller *1
Communication I/F P.C. board
Communication I/F P.C. B storage box
Transmission wire
Model
BRC307C50
BRP66B3
BPR66A97
BER66A5
BPR66A100
BER66A7
Notes:*1 Cooling capacity is based on the following conditions : Leaving chilled water temp.7 (44.5 F), entering chilled water temp.12 (53.6 F), and outdoor air temp. 35 DB(95 FDB).*2 Heating capacity is based on the following conditions : Leaving hot water temp.45 (113 F), entering hot water temp.40 (104 F), and outdoor air temp. 7 DB(44.5 FDB),and
6 WB(43 FWB).
*3 The following safety devices are equipped as standard. High pressure protector. Low pressure protector. Compressor thermal protector. Fusible plug. Reverse-phaseprotector. Overheat protection of discharge gas. Overcurrent relay(compressor). Freeze-up protection thermostat. Overcurrent relay(fan). Safety valve.
*4 The unit is equipped with standard water filter. *5 The limited length of wire represents its max. length when the pressure is lower than 2%. *6 This product is manufactured in China.
Specifications
Type
Motor output
Type
Drive
Air flow rate
Motor output
*1
Model
Cooling capacity
Chilled water flow rate
Heating capacity
Power supply
Hot water flow rate
Capacity steps
Compressor
Evaporator type
Condenser type
Condenser
fan
Refrigerant
Pipe connections
water inlet/outlet
Dimensions(H W D)
Weight
Operating weight
Operation range
kW
Btu/h
USRT
/min
kW
Btu/h
USRT
/min
%
kW
m3/min
cfm
kW
mm
kg
kg
*2
118 355kW class
UWY40 120AYBStandard Unit
60Hz
UWY40AYB
(40 )UWY50AYB
(50 )
UWY60AYB
(60 )
UWY100AYB
(100 )
UWY120AYB
(120 )
118
403,000
34
338
132
450,000
38
3 phase, 60 Hz 400/440 V, 3 wires syst em
378
100~10-0
Semi-hermetic sealed single-screw type
30 1
Blazing Plate type
Cross fin coil
Propeller
Direct drive
800
28,240
0.5 4
R-22
3B Flange (80A HG20593-97)
2,395 2,200 2,000
1,700
1,717
cooling -5 to 43, heating -20 to 21
150
512,000
43
430
170
580,000
48
487
37 1
810
28,593
0.8 4
1,800
1,820
180
614,000
51
516
200
683,000
57
573
45 1
940
33,182
1.2 4
1,950
1,973
300
1,024,000
85
860
335
1,143,000
95
960
37 2
1,620
57,186
0.8 8
4B Flange (100A HG20593-97)
2,395 4,400 2,000
3,600
3,636
355
1,212,000
101
1,018
400
1,365,000
114
1,147
45 2
1,880
66,364
1.2 8
3,900
3,942
Notes:*1 Cooling capacity is based on the following conditions : Leaving chilled water temp.7 (44.5 F), entering chilled water temp.12 (53.6 F), and outdoor air temp. 35 DB(95 FDB).*2 Heating capacity is based on the following conditions : Leaving hot water temp.45 (113 F), entering hot water temp.40 (104 F), and outdoor air temp. 7 DB(44.5 FDB),and
6 WB(43 FWB).*3 The following safety devices are equipped as standard. High pressure protector. Low pressure protector. Compressor thermal protector. Fusible plug. Reverse-phase
protector. Overheat protection of discharge gas. Overcurrent relay(compressor). Freeze-up protection thermostat. Overcurrent relay(fan). Safety valve.
*4 Standard for the max. chilled water pressure is 0.7MPa, but1.6MPa is available if required. *5 Installation/operating weight includes the weight of refrigerant and refrigerant oil(charged before delivery).
Specifications
Type
Motor output
Type
Drive
Air flow rate
Motor output
UWY200AY1
(200 )UWY220AY1
(220 )UWY240AY1
(240 )UWY280AY1
(280 )UWY320AY1
(320 )UWY360AY1
(360 )UWY480AY1
(480 )UWY400AY1
(400 )UWY420AY1
(420 )
*1
Model
Cooling capacity
Chilled water flow rate
Heating capacity
Power supply
Hot water flow rate
Capacity steps
Compressor
Evaporator type
Condenser type
Condenser
fan
Refrigerant
Pipe connections Water inlet/outlet
Dimensions (H W D)
Weight
Operating weight
Operation range
kW
Btu/h
USRT
/min
kW
Btu/h
USRT
/min
%
kW
m3/min
cfm
kW
mm
kg
kg
630
2,150,000
179
1,806
720
2,457,000
205
2,064
60 3
2,820
99,546
6,350
6,450
740
2,525,000
210
2,121
840
2,867,000
239
2,408
(45+60) 2
3,560
125,668
(1.2 8) 2
4B Flange (100A HG20593-97)
(2,395 4,400 2,000) 2
4,020 2
4,084 2
530
1,809,000
151
1,519
600
2,048,000
171
3 phase, 50 Hz 380/400/415 V, 4 wires sys tem
1,720
100~10-0 (continuous capacity control)
Semi-hermetic sealed single-screw type
45 2+60
Blazing plate type
Cross fin coil
Propeller
Direct drive
2,620
92,486
1.2 12
R-22
5B Flange (125A HG20593-97)
(2,460 6,600 2,000) 2
6,260
6,337
cooling -5 to 43, heating -20 to 21
*2
580
1,979,000
165
1,663
660
2,252,000
188
1,892
45+60 2
2,720
96,016
6,295
6,382
840
2,867,000
239
2,408
960
3,276,000
273
2,752
(60 2) 2
3,760
132,728
4,040 2
4,104 2
960
3,276,000
273
2,752
1,080
3,686,000
307
3,096
(45 3) 2
5,040
177,912
(1.2 12) 2
5B Flange (125A H G20593-97)
(2,460 6,600 2,000) 2
6,205 2
6,270 2
1,060
3,617,000
301
3,039
1,200
4,095,000
341
3,440
(45 2+60) 2
5,240
184,972
6,260 2
6,337 2
1,260
4,300,000
358
3,612
1,440
4,914,000
410
4,128
(60 3) 2
5,640
199,092
6,350 2
6,450 2
1,160
3,959,000
330
3,325
1,320
4,505,000
375
3,784
(45+60 2) 2
5,440
192,032
6,295 2
6,382 2
530 1,260kW class
UWY200 480AY1Standard Unit
50Hz
Notes:*1 Cooling capacity is based on the following conditions : Leaving chilled water temp.7 (44.5 F), entering chilled water temp.12 (53.6 F), and outdoor air temp. 35 DB(95 FDB).*2 Heatinging capacity is based on the following conditions : Leaving hot water temp.45 (113 F), entering hot water temp.40 (104 F), and outdoor air temp. 7 DB(44.5 FDB),and
6 WB(43 FWB).
*3 The following safety devices are equipped as standard. High pressure protector. Low pressure protector. Compressor thermal protector. Fusible plug. Reverse-phaseprotector.
Overheat protection of discharge gas. Overcurrent relay(compressor). Freeze-up protection thermostat. Overcurrent relay(fan). Safety valve.*4 Standard for the max. chilled water pressure is 0.7MPa, but1.6MPa is available if required. *5 Installation/operating weight includes the weight of refrigerant and refrigerant oil(charged before delivery).*6 This product is manufactured in China.
Specifications
Type
Motor output
Type
Drive
Air flow rate
Motor output
UWY40AY1
(40 )
UWY50AY1
(50 )
UWY60AY1
(60 )
UWY80AYAY1
(80 )
UWY100AY1
(100 )UWY120AY1
(120 )UWY180AY1
(180 )UWY140AY1
(140 )UWY160AY1
(160 )
*1
Model
Cooling capacity
Chilled water flow rate
Heating capacity
Power supply
Hot water flow rate
Capacity steps
Compressor
Evaporator type
Condenser type
Condenser
fan
Refrigerant
Pipe connections water inlet/outlet
Dimensions (H W D)
Weight
Operating weight
Operation range
kW
Btu/h
USRT
/min
kW
Btu/h
USRT
/min
%
kW
m3/min
cfm
kW
mm
kg
kg
160
546,000
46
459
180
614,000
51
516
45 1
840
29,652
1.2 4
1,950
1,973
210
717,000
60
602
240
819,000
68
688
60 1
940
33,182
2,020
2,052
106
362,000
30
304
118
403,000
34
3 phase, 50 Hz 380/400/415 V, 4 wires sys tem
338
100~10-0 (continuous capacity control)
Semi-hermetic sealed single-screw type
30 1
Brazed plate type
Cross fin coil
Propeller
Direct drive
700
24,710
0.5 4
R-22
3B Flange (80A HG20593-97)
2,395 2,200 2,000
1,700
1,717
cooling -5 to 43, heating -20 to 21
*2
132
450,000
38
378
150
512,000
43
430
37 1
710
25,063
0.8 4
1,800
1,820
265
904,000
75
760
300
1,024,000
85
860
37 2
1,420
50,126
0.8 8
4B Flange (100A HG20593-97)
2,395 4,400 2,000
3,600
3,636
320
1,092,000
91
917
355
1,212,000
101
1,018
45 2
1,680
59,304
1.2 8
3,900
3,942
370
1,263,000
105
1,061
420
1,433,000
119
1,204
45+60
1,780
62,834
4,020
4,084
480
1,638,000
137
1,376
540
1,843,000
154
1,548
45 3
2,520
88,956
1.2 12
5B Flange (125AHG20593-97)
2,460 6,600
2,000
6,205
6,270
420
1,433,000
119
1,204
480
1,638,000
137
1,376
60 2
1,880
66,364
4,040
4,104
106 480kW class
UWY40 180AY1Standard Unit
50Hz
Air CooledWater Chillers -Heat PumpType
23 24
8/2/2019 PCU0610A - Chiller [Small]
14/16
A single built-in control box simplifies operation and control.
Provides a stable supply of chilled water throughout the
Since the heat exchanger employs water, operation of the unit is not affected by
changes in the outdoor temperature. A stable water temperature is maintained
year round.
All controls and indicators are centralized in a single control box, making it possi-
ble to control the system using fewer personnel. Installation is simplified by inte-
gration of the control box with the main unit.
The water temperature setting can be set to any valuebetween 4 and 25 .
The 10 HP model has a footprint measuring only 0.32square meters.
8 to 30 HP models have a modular design that enables u nits with different capaci-
ties to be used together in a single system and simplifies increasing system ca-
pacity later on 3 5 HP models have a similar configuration and are designed
for compactness.
The starter panel is built into the control panel, simplifying
Easy Installation
UWP90AY3 900AY3
All models are fitted with a pressure gauge as standard.
Performance characteristics under partial load are efficient.
Reliability
Efficient Performance
Well Appointed
The new double-pipe heat exchanger design reduces clogging, significantly in-
creasing resistance to dirty cooling water.
The double-pipe heat exchanger and an individual error
indication function help reduce the manpower required for
Maintenance
UWP90AY3 900AY3UWD1320DY1 4000DY1
Year Round Cooling Operation
Applies to All Models
Wide Water Temperature Control Range
RangeUWP90AY3 900AY3
Simple Operation and Control
UWD1320DY1 4000DY1
UWD1320DY1UWP900AY3
Model Lineup
Refrigerant Uni ts ser ie s Mod el No.Capacity (kW)
page
50/60Hz
50Hz
R-407C
R-134a
Standard Unit
Standard Unit
UWPAY3
UWDDY1
8/9
90
13.2/15
150
20/22.4
224
26.5/30
300
40/45
450
53/60
600
67/75
750
80/90
900
118
1320
150
1700
180
2000
236
2650
300
3350
355
4000
27
27
Refrigerant Uni ts ser ie s Mod el No.
50Hz
60Hz
50Hz
60Hz
R-134a
Standard Unit
Brine Cooling Unit
ZUWAY1
ZUWAYB
ZUWAY1Z
ZUWAYBZ
Capacity
100RT
100
100
120RT
120
120
120
120
150RT
150
150
150
150
175RT
175
175
175
175
200RT
200
200
200
200
240RT
240
240
240
240
280RT
280
280
280
300RT
300
300
300
350RT
350
350
400RT
400
400
28
28
29
29
page
: UWP Series
: UWD S eries ZUW Series
Employs the new refrigerants R-407C and R-134a.
New Refrigerant
UWP90 900AY3
UWD1320 40000DY1ZUW 100 400AY(1)(B)ZUW 100 400AY(1)(B)Z
To improve their operational reliability, 5 -- 30HP modelsemploy scroll compressors, while 40 -- 120HP models areequipped with semi-hermetic single screw compressors.
Refrigerant inlet
Refrigerant outlet
Semi-hermetic singlescrew compressor
Efficient and Reliable Compressors
Applies to All Models
WaterCoole
d
WaterChille
rs
WaterCoole
d
WaterChille
rs
ZUW175AY1
1 compressoris operating
2compressors
100
50
0 25 50 100
Powerconsumptionratio(%)
Cooling capacity ratio (%)
Increased characteristicunder partial load
Water Cooled Water Chillers
25 26
8/2/2019 PCU0610A - Chiller [Small]
15/16
Specifications
UWP90AY3
(3 )UWP150AY3
(5 )UWP224AY3
(8 )UWP300AY3
(10 )UWP450AY3
(15 )UWP600AY3
(20 )UWP750AY3
(25 )UWP900AY3
(30 )Model
Cooling capacity
(50/60 Hz)
Power supply
Chilled water flow rate
(50/60 Hz)
Capacity steps
Compressor
Evaporator type
Condenser type
Refrigerant
Pipe
connections
Dimensions (H W D)
Weight
Operating weight
Type
Motor output
Condenserwater inlet/outlet
Chilled water inlet/outlet
Drain outlet
kW
Btu/h
USRT
/min
%
kW
mm
kg
kg
8.0/9.0
27,300/30,700
2.28/2.56
3 phase, 50 Hz 380/400/415 V, 60 Hz 400/440 V, 3 wi res system
23/26
100-0
Hermetically sealed scroll type
3.0 1
Brazed plate heat exchanger
Double pipe condenser
R-407C
FPT1 (25A)
FPT1 (25A)
FPT3/4 (20A)
1,280 405 690
100
102
13.2/15.0
45,100/51,200
3.75/4.27
38/43
3.75 1
110
112
20.0/22.4
68,300/76,500
5.69/6.37
57/64
5.5 1
FPT1 1/2 (40A)
FPT1 1/2 (40A)
1,280 405 790
150
154
26.5/30.0
90,500/102,000
7.54/8.53
76/86
7.5 1
160
165
40.0/45.0
137,000/154,000
11.4/12.8
115/129
100-50-0
5.5 2
FPT1 1/2 2 (40A)
FPT1 1/2 2 (40A)
1,280 808 790
305
313
53.0/60.0
181,000/205,000
15.1/17.1
152/172
7.5 2
325
335
67.0/75.0
229,000/256,000
19.1/21.3
192/215
100-60-0
7.5+5.5 2
FPT1 1/2 3 (40A)
FPT1 1/2 3 (40A)
1,280 1,211 790
465
478
80.0/90.0
273,000/307,000
22.8/25.6
229/258
100-67-0
7.5 3
485
500
Notes:*1 Cooling capacity is based on the following conditions : Leaving chilled water temp.7 (44.5 F), entering chilled water temp.12 (53.6 F), leaving condenser water temp. 35 (95 F), entering
condenser water temp.30 (86 F).*2 The following safety devices are equipped as standard. High/low pressure switch. Freeze-up protection thermostat. Overcurrent relay for compressors. Reverse-phase protector. Discharge gas overheat protector. Fusible plug. Safety valve.
*3 This product is manufactured in Japan.
*1
8 / 9 80 / 90kW class
UWP90 900AY3Standard Unit
50/60Hz
SpecificationsUWD1320DY1
(40 )UWD1700DY1
(50 )UWD2000DY1
(60 )UWD2650DY1
(80 )UWD3350DY1
(100 )UWD4000DY1
(120 )Model
Cooling capacity
Power supply
Chilled water flow rate
Condenser water flow rate
Compressor
Evaporator type
Condenser type
Refrigerant
Pipe
connections
Dimensions (H W D)
Weight (Approx.)
Operating weight (Approx.)
Type
Motor output
Capacitycontrol
Condenserwater inlet/outlet
Chilledwater inlet/outlet
Chilledwaterdrain outlet
Condenserwaterdrain outlet
kW
Btu/h
USRT
/min
/min
kW
%
mm
kg
kg
118
403,000
33.6
3 phase, 50 Hz 380/400/415 V, 3 wires sy stem
338
420
Semi-hermetic sealed single screw type
30 1
100-70-40-0
Shell and Hi-X tube type
Shell and cross fin tube type
R-134a
FPT3 (80A)
FPT3 (80A)
FPT3/4
FPT1/4
1,600 2,320 759
1,100
1,220
150
512,000
42.7
430
534
37 1
1,702 2,600 759
1,250
1,390
180
615,000
51.2
516
640
45 1
FPT4 (100A)
4B Flange (JIS10K)(100A)
FPT1
1,280
1,420
236
806,000
67.1
677
837
30 2
100-70-40-20-0
FPT3 (80A)
1,623 3,330 994
1,800
1,980
300
1,020,000
85.3
860
1,068
37 2
1,745 3,338 1,050
2,200
2,420
355
1,210,000
101
1,018
1,263
45 2
FPT4 (100A)