Daikin Water Chillers are of the self-contained type. This means that they are assembled, internally wired and charged with refrigerant at the factory for easy installation, only requiring external wiring and plumbing on site. They are compatible with Daikin's Air Handling and/or Fan Coil Units.
All rights reservedPrinted in Japan 11/06/005 SW.HP.ADc
DealerHead Office:Umeda Center Bldg., 2-4-12, Nakazaki-Nishi,Kita-ku, Osaka, 530-8323 Japan
Tokyo Office:JR Shinagawa East Bldg., 2-18-1, Konan,Minato-ku, Tokyo, 108-0075 Japan
http://www.daikin.com/global/
1. Air conditioners should not be installed in areas where corrosive gases, such as acid gas or alkaline gas, are produced.2. If the outdoor unit is to be installed close to the sea shore, direct exposure to the sea breeze should be avoided and choose an outdoor unit with anti-corrosion treatment.
Cautions on product corrosion
Warning Daikin Industries, Ltd.’s products are manufactured for export to numerous countries throughout the world. Daikin Industries, Ltd. does not have control over which products are exported to and used in a particular country. Prior to purchase, please therefore confirm with your local authorised importer, distributor and/or retailer whether this product conforms to the applicable standards, and is suitable for use, in the region where the product will be used. This statement does not purport to exclude, restrict or modify the application of any local legislation.Ask a qualified installer or contractor to install this product. Do not try to install the product yourself. Improper installation can result in water or refrigerant leakage, electrical shock, fire or explosion.Use only those parts and accessories supplied or specified by Daikin. Ask a qualified installer or contractor to install those parts and accessories. Use of unauthorised parts and accessories or improper installation of parts and accessories can result in water or refrigerant leakage, electrical shock, fire or explosion.Read the User's Manual carefully before using this product. The User's Manual provides important safety instructions and warnings. Be sure to follow these instructions and warnings.
If you have any enquiries, please contact your local importer, distributor and/or retailer.
Printed on 100% recycled paper with soy ink.Specifications, designs and other content appearing in this brochure are current as of November 2006 but subject to change without notice.
ISO 14001 is the standard defined by the International Organization for Standardization (ISO) relating to environmental management systems. Our group has been acknowledged by an internationally accredited compliance organisation as having an appropriate programme of environmental protection procedures and activities to meet the requirements of ISO 14001.
About ISO 14001ISO 9001 is a plant certification system defined by the International Organization for Standardization (ISO) relating to quality assurance. ISO 9001 certification covers quality assurance aspects related to the “ design, development, manufacture, installation, and supplementary service” of products manufactured at the plant.
About ISO9001
JMI-0107 EC99J2044
2
H ig h -pe r fo r m a n c e D a ik in W a t e r C h i l le r s a r e A v a i la ble in a B r o a d R a n g e o f M o de ls t o S u it D iv e r s e A ppl ic a t io n s .
Lis t of Daikin Water C hiller Models
1 2
Air Cooled Water Chillers : UWAP S eries / UWAXP S eries : UWA S eries / ( For High Outdoor Temperature Use )
Dedicated water chillers are able to operate year round because they can accommodate a wide range of outdoor temperatures. The high-performance models with capacities of over 40 HP can deliver between 10% (12% ) and 100% of their capacities. They are able to withstand the demanding conditions typical of industrial applications.
Air Cooled Water Chillers - Heat Pump Type
Water Cooled Water Chillers
Air cooled heat pump system units are an ideal way to provide a reliable supply of hot and cold water. Of compact s ize because no cooling tower is required, they are also suitable for office building air conditioning. These high-end models provide an answer to a variety of air conditioning requirements.
Water cooled units provide a s table supply of chilled water year round and are unaffected by changes in the outdoor temperature. In addition to air conditioning applications , they are also a highly reliable industrial process cooling solution thanks to their s tability and wide temperature control range.
Air Cooled Water Chillers
Air
Coo
led
Wat
er C
hill
ers20 40 60 80 100 150 200 250 300 350 450 500 600 700 800 900 1000 1200 1400 P age
11
12 13
14
14 15
17
18
21
21 22
23
27
27
28
29
9 10
9
C apac ity R ange (kW)
Air Cooled Water Chillers - Heat Pump Type
Water Cooled Water Chillers
Standard Unit
Standard Unit
Standard Unit
Brine Cooling Unit
Standard Unit
ForHigh Outdoor Temperature Use
Standard Unit
Inverter Cooling Unit
Brine Cooling Unit
Year - Round Cooling Only Unit
Standard Unit
Air Cooled Water Chillers20 40 60 80 100 150 200 250 300 350 450 500 600 700 800 900 1000 1200 1400 P age
12
13
15
18
21
22
24
27
28
29
10
9
C apac ity R ange (kW)
Air Cooled Water Chillers - Heat Pump Type
Water Cooled Water Chillers
Standard Unit
Standard Unit
Standard Unit
Brine Cooling Unit
Standard Unit
For High Outdoor Temperature Use
Standard Unit
Brine Cooling Unit
Year - Round Cooling Only Unit
Standard Unit
Wat
er C
oole
d W
ater
Chi
ller
sA
ir C
oole
d W
ater
Chi
ller
s- H
eat P
ump
Type
: UWY P S eries : UWY S eries
: UWP S eries : UWD S eries ZUW S eries
50Hz
60Hz
106 1260 UWAP-BY1
106 1260 UWAP-BY1K
12.5 75
11.2 67
106 1260 UWA-AY1
106 1260 UWYP-BY1
106 1260 UWY-AY1
8 80
118 355 UWD-DY1
UWAXP-AY1
108.4 319.2 UWA-JAY1
351.6 791 UWA-JY1
UWP-AY3
6.7 67 UWAP-AY3
68 808 UWAP-BY1Z
UWYP-AY3
367 1450 ZUW-AY1
190 715 ZUW-AY1Z
118 355 UWAP-BYB
118 355 UWAP-BYBK
118 355 UWYP-BYB
118 355 UWY-AYB
9 90 UWP-AY3
79 370 UWA-JATJ
7.5 75 UWAP-AY3
79 242
118 355 UWA-AYB
UWYP-AY312.5 75
441 1040 ZUW-AYB
233 555 ZUW-AYBZ
UWAP-BYBZ
Daikin chilling units employ advanced technology that provides highly accurate temperature control to within 0.5 . They are widely used in applications ranging from air conditioning to industrial equipment. Recent changes have introduced new models with substantially increased capacities of up to 480 HP and various model series, including advanced inverter type units, year-round cooling type units, and units with brine-resistant specifications. By providing a full lineup of heat source series choices, Daikin offers an even more flexible array of solutions for a wide range of heat source applications.
2
H ig h -pe r fo r m a n c e D a ik in W a t e r C h i l le r s a r e A v a i la ble in a B r o a d R a n g e o f M o de ls t o S u it D iv e r s e A ppl ic a t io n s .
Lis t of Daikin Water C hiller Models
1 2
Air Cooled Water Chillers : UWAP S eries / UWAXP S eries : UWA S eries / ( For High Outdoor Temperature Use )
Dedicated water chillers are able to operate year round because they can accommodate a wide range of outdoor temperatures. The high-performance models with capacities of over 40 HP can deliver between 10% (12% ) and 100% of their capacities. They are able to withstand the demanding conditions typical of industrial applications.
Air Cooled Water Chillers - Heat Pump Type
Water Cooled Water Chillers
Air cooled heat pump system units are an ideal way to provide a reliable supply of hot and cold water. Of compact s ize because no cooling tower is required, they are also suitable for office building air conditioning. These high-end models provide an answer to a variety of air conditioning requirements.
Water cooled units provide a s table supply of chilled water year round and are unaffected by changes in the outdoor temperature. In addition to air conditioning applications , they are also a highly reliable industrial process cooling solution thanks to their s tability and wide temperature control range.
Air Cooled Water Chillers
Air
Coo
led
Wat
er C
hill
ers20 40 60 80 100 150 200 250 300 350 450 500 600 700 800 900 1000 1200 1400 P age
11
12 13
14
14 15
17
18
21
21 22
23
27
27
28
29
9 10
9
C apac ity R ange (kW)
Air Cooled Water Chillers - Heat Pump Type
Water Cooled Water Chillers
Standard Unit
Standard Unit
Standard Unit
Brine Cooling Unit
Standard Unit
ForHigh Outdoor Temperature Use
Standard Unit
Inverter Cooling Unit
Brine Cooling Unit
Year - Round Cooling Only Unit
Standard Unit
Air Cooled Water Chillers20 40 60 80 100 150 200 250 300 350 450 500 600 700 800 900 1000 1200 1400 P age
12
13
15
18
21
22
24
27
28
29
10
9
C apac ity R ange (kW)
Air Cooled Water Chillers - Heat Pump Type
Water Cooled Water Chillers
Standard Unit
Standard Unit
Standard Unit
Brine Cooling Unit
Standard Unit
For High Outdoor Temperature Use
Standard Unit
Brine Cooling Unit
Year - Round Cooling Only Unit
Standard Unit
Wat
er C
oole
d W
ater
Chi
ller
sA
ir C
oole
d W
ater
Chi
ller
s- H
eat P
ump
Type
: UWY P S eries : UWY S eries
: UWP S eries : UWD S eries ZUW S eries
50Hz
60Hz
106 1260 UWAP-BY1
106 1260 UWAP-BY1K
12.5 75
11.2 67
106 1260 UWA-AY1
106 1260 UWYP-BY1
106 1260 UWY-AY1
8 80
118 355 UWD-DY1
UWAXP-AY1
108.4 319.2 UWA-JAY1
351.6 791 UWA-JY1
UWP-AY3
6.7 67 UWAP-AY3
68 808 UWAP-BY1Z
UWYP-AY3
367 1450 ZUW-AY1
190 715 ZUW-AY1Z
118 355 UWAP-BYB
118 355 UWAP-BYBK
118 355 UWYP-BYB
118 355 UWY-AYB
9 90 UWP-AY3
79 370 UWA-JATJ
7.5 75 UWAP-AY3
79 242
118 355 UWA-AYB
UWYP-AY312.5 75
441 1040 ZUW-AYB
233 555 ZUW-AYBZ
UWAP-BYBZ
Daikin chilling units employ advanced technology that provides highly accurate temperature control to within 0.5 . They are widely used in applications ranging from air conditioning to industrial equipment. Recent changes have introduced new models with substantially increased capacities of up to 480 HP and various model series, including advanced inverter type units, year-round cooling type units, and units with brine-resistant specifications. By providing a full lineup of heat source series choices, Daikin offers an even more flexible array of solutions for a wide range of heat source applications.
E quipped with an E fficient, Durable S emi-hermetically S ealed S crew C ompressor.
60,000Sales volume
Gate Rotor
ScrewRotor Suction
Pressure
SuctionPressure
Discharge Pressure
Discharge Pressure
E quipped with a Newly Developed, Highly E ffic ient C ompac t C ompres s or.Optimization of the unit enhances efficient operation. A newly developed denture mold enabled the production of a compact model with reduced volume and weight.
High Operational E ffic ienc y R educ es E nergy Los s .In addition to effic ient operation afforded by a 12-compress ion s ingle cycle, the s ingle screw construction eliminates blow-by from high to low pressure sections to reduce energy loss . Daikin water chillers are equipped with a tightly sealed gate rotor to reduce refrigerant loss from leakage. Our compressors are des igned for efficient operation
High Ac c urac y and High Durability.C areful construction features gate rotors pos itioned to the right and left of the screw to eliminate eccentric load produced by pressure differential. The orthogonal rotor shaft uses high-precis ion ball and roller bearings , which extends its life compared to conventional types . In addition, power transmiss ion between rotors is reduced, thus eliminating friction wear and maintaining stable operating performance over an extended period of time.
Low Vibration and S ound Levels .Daikin water chillers us e gate rotors made of high-performance engineering plastic for smooth meshing with the screw rotor, thereby reducing shock and vibration. while maintaining stable operation. The gate rotors are well balanced to equalize pressure, which reduces noise and
L ightweight C ompac t Des ign S ave S pac e.In addition to the s imple s ingle rotor construction, the compact, lightweight des ign eliminates the need for an oil cooler while incorporating the oil separator into a s ingle part to reduce the space required for setup.
Durable C ons truc tion Inc reas es Ins pec tion Intervals thereby Dec reas ing Maintenanc e.Durability of the equipment increases the maintenance interval to approximately 40,000 hours (or about seven years ). The s implified lubrication system, including a high/low pressure differential lubrication system and ball and roller bearings , reduces the factors that can contribute to problems. Along with increas ing the maintenance and inspection interval, the careful construction of Daikin water chillers enhances reliability.
C as ingS crew rotorS lide valveB all bearingMotorG ate rotorHigh efficient oil separatorHigh-low pressure differential lubricating mechanismB earing lubricating oil for models us ing new refrigerantR efrigerant inletR efrigerant outlet
1
2
3
4
5
6
7
8
9
10
11
12
4
5
63
8
9
7
10
11
High Function Microcomputer C ontrol P anel and Multifunctional R emote C ontroller R ealise E fficient Operation C ontrol.
S imple key operation displays required operating and settings data. Displays a complete of operating data for easy comprehension.
Up to eight units c an be group c ontrolled by a s ingle remote c ontroller.E quipped with s imultaneous defros t prevention c ontrol for avoiding radic al water temperature c hange when operating multiple units .*S imultaneous defrost can be carried out for up to two units when five or more units are connected.
Note : C ustom orders may take more time for delivery.
R otation c ontrol
Mic roc omputer C ontrol P anel Makes Operation C ontrol E as y.
Multi-display
Controls Multiple Units Effectively
A Multifunc tional L iquid C rys tal R emote C ontroller for E ffec tive G roup C ontrol.
Function for Equal Control using Microcomputer Control Panel
E nables different types of remote control, such as control by commands from the host computer, the Daikin B uilding Air-C onditioning C ontrol S ystem (D-B AC S ), or the multifunctional remote controller.
Remote Control by Remote Command
On/Off remote c ontrol
R emote s etting of water temperature
S etting for heat s torage operationY ou can s witch s ettings from normal operation to either temperature setting for heat s torage or control by the external
Lower nois e operation for during nighttimeY ou can reduce the operating noise by stopping half the fan. Note that the capacity control of the chiller should be limited to less than 70% .
Forc ed fan operation c ontrol*Y ou can force fan operation even when the unit is s topped, which is convenient for removing the snow collected on the fan.*This function is des igned for in areas where snow rarely falls . An optional snow hood should be used in areas prone to snow.
Demand c ontrol(1) Y ou can have Three demand controls are poss ible thermostat Off, less than 40% or less than 70% . (Factory set:70% )(2) Demand control may also be achieved by setting the operating current of the compressor.*Demand control is available on all models , with the exception of those lis ted below.UWAP 75 — 750AY 3, UWAXP 125 — 750AY 1, UWA37 — 109J AY 1, UWA120 — 270J Y 1, UWA27 — 122J ATJ , UWY P 125 — 750AY 3,UWP 90 — 900AY 3
Outdoor temperature
Inlet/Outlet temperature
Dis c harge gas temperature
Dis plays operating data for eas y c omprehens ion of s ys tem s tatus .
High and low pres s ure
Water temperature s etting
Malfunc tion c ode
*For details , refer to the Operation Manual of each model.
On/Off c ontrol
Water temperature s etting
S witc hing of operatingmode
Defros t c yc le s etting*
Heat s torage operation
E nables different types of remote c ontrol.
Low nois e operation duringnighttime
Forc ed fan operation
Demand c ontrol*
R otation c ontrol
Ins pec tion/Tes t operation
Memorizes the number of s tops for each unit (therefore not effective for systems in continuous operation), and smooths operation by starting in order from the unit with the least number of s tarts and stops to increase the life time of all apparatus in the system.
B R C 307 (Option)
*Applies to all models , with the exc eption of thos e lis ted below.UWA37 — 109J AY 1, UWA120 — 270J Y 1, UWA27 — 122J ATJ , UWP 90 — 900AY 3
*Demand control is not available with
*Applies to heat-pump type only.
Outdoor temp.
Discharge gas temp.
Water temp. setting
Inlet/outlet water temp.
H/L pressure of refrigerant
Centralized control
Malfunction code display
3 4
E quipped with an E fficient, Durable S emi-hermetically S ealed S crew C ompressor.
60,000Sales volume
Gate Rotor
ScrewRotor Suction
Pressure
SuctionPressure
Discharge Pressure
Discharge Pressure
E quipped with a Newly Developed, Highly E ffic ient C ompac t C ompres s or.Optimization of the unit enhances efficient operation. A newly developed denture mold enabled the production of a compact model with reduced volume and weight.
High Operational E ffic ienc y R educ es E nergy Los s .In addition to effic ient operation afforded by a 12-compress ion s ingle cycle, the s ingle screw construction eliminates blow-by from high to low pressure sections to reduce energy loss . Daikin water chillers are equipped with a tightly sealed gate rotor to reduce refrigerant loss from leakage. Our compressors are des igned for efficient operation
High Ac c urac y and High Durability.C areful construction features gate rotors pos itioned to the right and left of the screw to eliminate eccentric load produced by pressure differential. The orthogonal rotor shaft uses high-precis ion ball and roller bearings , which extends its life compared to conventional types . In addition, power transmiss ion between rotors is reduced, thus eliminating friction wear and maintaining stable operating performance over an extended period of time.
Low Vibration and S ound Levels .Daikin water chillers us e gate rotors made of high-performance engineering plastic for smooth meshing with the screw rotor, thereby reducing shock and vibration. while maintaining stable operation. The gate rotors are well balanced to equalize pressure, which reduces noise and
L ightweight C ompac t Des ign S ave S pac e.In addition to the s imple s ingle rotor construction, the compact, lightweight des ign eliminates the need for an oil cooler while incorporating the oil separator into a s ingle part to reduce the space required for setup.
Durable C ons truc tion Inc reas es Ins pec tion Intervals thereby Dec reas ing Maintenanc e.Durability of the equipment increases the maintenance interval to approximately 40,000 hours (or about seven years ). The s implified lubrication system, including a high/low pressure differential lubrication system and ball and roller bearings , reduces the factors that can contribute to problems. Along with increas ing the maintenance and inspection interval, the careful construction of Daikin water chillers enhances reliability.
C as ingS crew rotorS lide valveB all bearingMotorG ate rotorHigh efficient oil separatorHigh-low pressure differential lubricating mechanismB earing lubricating oil for models us ing new refrigerantR efrigerant inletR efrigerant outlet
1
2
3
4
5
6
7
8
9
10
11
12
4
5
63
8
9
7
10
11
High Function Microcomputer C ontrol P anel and Multifunctional R emote C ontroller R ealise E fficient Operation C ontrol.
S imple key operation displays required operating and settings data. Displays a complete of operating data for easy comprehension.
Up to eight units c an be group c ontrolled by a s ingle remote c ontroller.E quipped with s imultaneous defros t prevention c ontrol for avoiding radic al water temperature c hange when operating multiple units .*S imultaneous defrost can be carried out for up to two units when five or more units are connected.
Note : C ustom orders may take more time for delivery.
R otation c ontrol
Mic roc omputer C ontrol P anel Makes Operation C ontrol E as y.
Multi-display
Controls Multiple Units Effectively
A Multifunc tional L iquid C rys tal R emote C ontroller for E ffec tive G roup C ontrol.
Function for Equal Control using Microcomputer Control Panel
E nables different types of remote control, such as control by commands from the host computer, the Daikin B uilding Air-C onditioning C ontrol S ystem (D-B AC S ), or the multifunctional remote controller.
Remote Control by Remote Command
On/Off remote c ontrol
R emote s etting of water temperature
S etting for heat s torage operationY ou can s witch s ettings from normal operation to either temperature setting for heat s torage or control by the external
Lower nois e operation for during nighttimeY ou can reduce the operating noise by stopping half the fan. Note that the capacity control of the chiller should be limited to less than 70% .
F orc ed fan operation c ontrol*Y ou can force fan operation even when the unit is s topped, which is convenient for removing the snow collected on the fan.*This function is des igned for in areas where snow rarely falls . An optional snow hood should be used in areas prone to snow.
Demand c ontrol(1) Y ou can have Three demand controls are poss ible thermostat Off, less than 40% or less than 70% . (Factory set:70% )(2) Demand control may also be achieved by setting the operating current of the compressor.*Demand control is available on all models , with the exception of those lis ted below.UWAP 75 — 750AY 3, UWAXP 125 — 750AY 1, UWA37 — 109J AY 1, UWA120 — 270J Y 1, UWA27 — 122J ATJ , UWY P 125 — 750AY 3,UWP 90 — 900AY 3
Outdoor temperature
Inlet/Outlet temperature
Dis c harge gas temperature
Dis plays operating data for eas y c omprehens ion of s ys tem s tatus .
High and low pres s ure
Water temperature s etting
Malfunc tion c ode
*For details , refer to the Operation Manual of each model.
On/Off c ontrol
Water temperature s etting
S witc hing of operatingmode
Defros t c yc le s etting*
Heat s torage operation
E nables different types of remote c ontrol.
Low nois e operation duringnighttime
F orc ed fan operation
Demand c ontrol*
R otation c ontrol
Ins pec tion/Tes t operation
Memorizes the number of s tops for each unit (therefore not effective for systems in continuous operation), and smooths operation by starting in order from the unit with the least number of s tarts and stops to increase the life time of all apparatus in the system.
B R C 307 (Option)
*Applies to all models , with the exc eption of thos e lis ted below.UWA37 — 109J AY 1, UWA120 — 270J Y 1, UWA27 — 122J ATJ , UWP 90 — 900AY 3
*Demand control is not available with
*Applies to heat-pump type only.
Outdoor temp.
Discharge gas temp.
Water temp. setting
Inlet/outlet water temp.
H/L pressure of refrigerant
Centralized control
Malfunction code display
3 4
Daikin's C ontrol S ystem for C entral Air C onditioning S ystem Offers Appropriate C ontrol for Use and S ize of B uilding.
Daikin's intelligent control solution for the whole air-conditioning system.
Daikin's Control System for Central Air Conditioning.
Daikin introduces its "C ontrol S ystem for C entral Air C onditioning" The system lets you freely combine a number of optional controllers for centralized control to construct the air conditioning control system that is appropriate for your needs . The system executes total central control of chillers and air conditioners , to save management labour while realizing ideal central air conditioning performance.
Different C ontrol Apparatus C ombinations E nable a Multipurpos e S ys tem.Daikin offers a lineup of c entral controllers equipped with a variety of functions . The unified ON/OFF controller lets you turn equipment on and off individually or in groups . The schedule timer lets you program the time for connected equipment to be turned on and off for eac h week. C ontrol apparatus with different functions can be freely combined, and up to 64 groups can be centrally controlled.*Number of units that c an be
Note:The system shown above is applicable only to Series UWAJ-G, UWYJ-B, UWAP-G and UWYP-G.Note:Air handling and Fan coil units can be connected by custom orders.
C entral remote controller Unified ON/OFF controller S chedule timer
Model
S top-running c ommandC ooling/heating mode settingTemp. settingS c hedule func tionInterloc k settingPower proportion limitationS top-runningC ooling/heating modeTemperature setR oom temp. (suc tion inlet)Water temp. (inlet/outlet)AbnormalAbnormal s ignalFilter s ignalC ontinuous running periodTemp. upper/lower limit
S tandard c onnec tion
Air-c ooling Unit
UWAP,UWYP,UWA,UWY
Water-c ooling Unit
ZUW
AIR NE T
DioUnit
C ommodity from other c ompanies
Pump, R efrigerating Unit, C ooling Tower
(Note1)
System Structure(VRV+central conditioning)
C ool/warm water pump 1C ooling tower 1
iPU(R eservedfor VR V)
E themet
VR V(4 ports )256 indoor units
Dio Unit Dio Unit
Wiring adaptor is required for c onnec ting Dio unit to Airnet
1. C entral air-c onditioning system c an be c ontrolled together with VR V.
2. Operating interfac e is based on the windows interfac e, whic h is easy to use.
3. 1024 units (groups) of indoor unit or water c ooled c hiller c an be c onnec ted.
4. Power distribution in proportions , c alc ulation the power rate and other AC -related c osts of user.
5. C an be c onnec ted with Air C onditioning Network S ervic e S ystem
6. Ordinary 2-c ore c able is used for wiring, the field wiring work is very s imple.
Features of I-Manager
( realised func tion irrespec tive item only data information, c an't be ac hieved up till now)
Note1: C an realize partial func tion of Air C onditioning Network S ervic e S ystem.
* Please contact Daikin for detailed data for connection of Fan coil and AC(terminal products)
R emote c ontroller(units No. c ontrol)
C ool/warm water pump 3
Monitoring func tion
C ontrollingfunc tion
Func tion
R emote monitor c enter
Max. 4 iPUs are
iPU(R eserved for c entral
air-c onditioning system)
E quipment~pump of other c ompany, c ooling tower(1
port) Pump 4 units
Note: It is not poss ible to c onnec t a high outdoor temperature spec ific ation unit and the UWAP75 — 750.
D -NE T
I-Manager
D -NE T
D -NE T wiring adaptor
Water c ooled c hiller (1 port)Air-c ooling 240HP 2 units
Water-c ooling 400US R T 1 unit
Unified ON/OFF controller
Chilling unit
Possible to link withhost computer
Schedule timer
SkyAir series
VRV system
Central remote controllerPossible to have a forcedshut-down input
Enables control of other air conditioning systemssuch as VRV, SkyAir or HRV.
Enables individual control from chillers to air conditioners by using a single line.
Enables group control by remote controllers of both chillers and air conditioners.
Lets you develop a system that doesn't use individual remote controllers.(Central remote controller required)
Air handling unit Air handling unit Fan coil unit Possiblewireless remote controller
System configuration
D adaptor I-Manager option
Control Function List of I-Manager
I-Manager Control heat resources system by using I-Manager
New VersionNew Version
5 6
Daikin's C ontrol S ystem for C entral Air C onditioning S ystem Offers Appropriate C ontrol for Use and S ize of B uilding.
Daikin's intelligent control solution for the whole air-conditioning system.
Daikin's Control System for Central Air Conditioning.
Daikin introduces its "C ontrol S ystem for C entral Air C onditioning" The system lets you freely combine a number of optional controllers for centralized control to construct the air conditioning control system that is appropriate for your needs . The system executes total central control of chillers and air conditioners , to save management labour while realizing ideal central air conditioning performance.
Different C ontrol Apparatus C ombinations E nable a Multipurpos e S ys tem.Daikin offers a lineup of c entral controllers equipped with a variety of functions . The unified ON/OFF controller lets you turn equipment on and off individually or in groups . The schedule timer lets you program the time for connected equipment to be turned on and off for eac h week. C ontrol apparatus with different functions can be freely combined, and up to 64 groups can be centrally controlled.*Number of units that c an be
Note:The system shown above is applicable only to Series UWAJ-G, UWYJ-B, UWAP-G and UWYP-G.Note:Air handling and Fan coil units can be connected by custom orders.
C entral remote controller Unified ON/OFF controller S chedule timer
Model
S top-running c ommandC ooling/heating mode settingTemp. settingS c hedule func tionInterloc k settingPower proportion limitationS top-runningC ooling/heating modeTemperature setR oom temp. (suc tion inlet)Water temp. (inlet/outlet)AbnormalAbnormal s ignalFilter s ignalC ontinuous running periodTemp. upper/lower limit
S tandard c onnec tion
Air-c ooling Unit
UWAP,UWYP,UWA,UWY
Water-c ooling Unit
ZUW
AIR NE T
DioUnit
C ommodity from other c ompanies
Pump, R efrigerating Unit, C ooling Tower
(Note1)
System Structure(VRV+central conditioning)
C ool/warm water pump 1C ooling tower 1
iPU(R eservedfor VR V)
E themet
VR V(4 ports )256 indoor units
Dio Unit Dio Unit
Wiring adaptor is required for c onnec ting Dio unit to Airnet
1. C entral air-c onditioning system c an be c ontrolled together with VR V.
2. Operating interfac e is based on the windows interfac e, whic h is easy to use.
3. 1024 units (groups) of indoor unit or water c ooled c hiller c an be c onnec ted.
4. Power distribution in proportions , c alc ulation the power rate and other AC -related c osts of user.
5. C an be c onnec ted with Air C onditioning Network S ervic e S ystem
6. Ordinary 2-c ore c able is used for wiring, the field wiring work is very s imple.
Features of I-Manager
( realised func tion irrespec tive item only data information, c an't be ac hieved up till now)
Note1: C an realize partial func tion of Air C onditioning Network S ervic e S ystem.
* Please contact Daikin for detailed data for connection of Fan coil and AC(terminal products)
R emote c ontroller(units No. c ontrol)
C ool/warm water pump 3
Monitoring func tion
C ontrollingfunc tion
Func tion
R emote monitor c enter
Max. 4 iPUs are
iPU(R eserved for c entral
air-c onditioning system)
E quipment~pump of other c ompany, c ooling tower(1
port) Pump 4 units
Note: It is not poss ible to c onnec t a high outdoor temperature spec ific ation unit and the UWAP75 — 750.
D -NE T
I-Manager
D -NE T
D -NE T wiring adaptor
Water c ooled c hiller (1 port)Air-c ooling 240HP 2 units
Water-c ooling 400US R T 1 unit
Unified ON/OFF controller
Chilling unit
Possible to link withhost computer
Schedule timer
SkyAir series
VRV system
Central remote controllerPossible to have a forcedshut-down input
Enables control of other air conditioning systemssuch as VRV, SkyAir or HRV.
Enables individual control from chillers to air conditioners by using a single line.
Enables group control by remote controllers of both chillers and air conditioners.
Lets you develop a system that doesn't use individual remote controllers.(Central remote controller required)
Air handling unit Air handling unit Fan coil unit Possiblewireless remote controller
System configuration
D adaptor I-Manager option
Control Function List of I-Manager
I-Manager Control heat resources system by using I-Manager
New VersionNew Version
5 6
Model Lineup
50Hz60Hz50Hz60Hz50Hz60Hz50Hz60Hz
R-407C
R-22
Standard Unit
Year - Round Cooling Only Unit
Brine Cooling Unit
Standard Unit
Refrigerant Units series Model No.
UWAP—BY1UWAP—BYBUWAP—BY1KUWAP—BYBKUWAP—BY1ZUWAP—BYBZUWA—AY1UWA—AYB
Capacity (kW)
9, 10101112
12, 1313
14, 1515
page315120120120120120120120120
370140—
140—
140—
140—
420160—
160—
160—
160—
480180—
180—
180—
180—
530200—
200—
200—
200—
580220—
220—
220—
220—
630240—
240—
240—
240—
740280—
280—
280—
280—
840320—
320—
320—
320—
960360—
360—
360—
360—
1060400—
400—
400—
400—
1160440—
440—
440—
440—
1260480—
480—
480—
480—
50/60Hz50Hz60Hz50Hz60Hz50Hz60Hz50Hz50Hz60Hz
Refrigerant
R-407C
R-22
Units series
Standard Unit
Year - Round Cooling Only Unit
Brine Cooling Unit
Inverter Cooling Unit
Standard Unit
Model No.
UWAP—AY3*UWAP—BY1UWAP—BYBUWAP—BY1KUWAP—BYBKUWAP—BY1ZUWAP—BYBZUWAXP—AY1UWA—AY1UWA—AYB
Capacity (kW)6.7/7.5
75—————————
11.2/12.5125——————
125——
17/19190——————
190——
22.4/25250——————
250——
33.5/37.5375——————
375——
45/50500——————
500——
56/63630——————
630——
67/75750——————
750——
106—404040404040—4040
132—505050505050—5050
160—606060606060—6060
212—80—80—80——80—
265—
100100100100100100—
100100
99, 10101112
12, 131314
14, 1515
page
Note: Capacity figures are provided for reference and assume a power supply frequency of 60 Hz.
E mploys the new refrigerant R -407C .
UWAP 75 — 750AY 3 UWAXP 125 — 750AY 1UWAP 40 — 480B Y 1(K ) (Z) UWAP 40 — 120B Y B (K ) (Z)
New Refrigerant Efficient and Reliable Compressors
To improve their operational reliability, 5 -- 30HP models employ scroll compressors , while 40 -- 480HP models are equipped with semi-hermetic s ingle screw compressors .
R efrigerant inlet
R efrigerant outlet
S emi-hermetic s ingle screw compressor
The user can select to give priority to either precis ion or reduced power consumption.
C ontinues operation to levels as low as 10(12)% of total capacity to provide stable water temperature c ontrol even during low-load peri-ods .
This mode can be used to re-duce power cons umption if highly precise water temperature control is not necessary dur-ing low-load periods. It shuts down the compressor when the load drops below 40% .
High-P rec is ion Mode Low-P ower Mode
Note: Switching between the above modes is accomplished using a control on the outdoor unit.
Multiple Operating Modes
Refrigerant Inlet
Refrigerant Outlet
Water Outlet
WaterInlet
Heat Exchanger with Stainless Steel Plates
S tainles s s teel heat ex-changer plates prevent rust, thereby improving their dura-bility and the system's op-
ReliabilityApplies to All Models
The compact des ign of these units s ignificantly reduces the space required for installation.
The horizontal linkup des ign increases installation flexibility.
In the outdoor unit, component parts of a small size have been used wherever possible to reduced its size and correspondingly reduce how much space it re-quires. Furthermore, replacing the 2-way refrigerant inlets with 4-way inlets has reduced the amount of space the outdoor unit needs even further.
This design provides the installation does not protrude so far, making it possible to install water chillers along a wall or under a roof overhang.
Note: Water supply piping must be purchased separately.(UWAP375AY3 — 750AY3)
UWAP 40 — 480B Y 1 (K ) (Z) UWAP 40 — 120B Y B (K ) (Z)
Easy Installation
UWAP 125AY 3 — 750AY 3
High load compliance and highly efficient inverter control provide highly precise adjustment of the water temperature, making it possible to reduce the size of the peripheral equipment.
UWAXP 125 — 750AY 1
C ompressor duty cycling control together with emergency operation and power-interruption auto-restart functions pro-vide enhanced air conditioning system reliability.
UWA40 — 480AY 1UWA40 — 120AY B
A choice of three control system is available.UWA40 — 480AY 1
Outflow water temperature controlProvides precise control of the water temprerature.(UWAP40 — 160BY1, UWA40 — 160AY1)
Compressor count controlControls the number of compressors operating depending on the load.(UWAP40 — 480BY1, UWA40 — 480AY1)
In flow water temperature controlPerforms duty cycling control.(UWAP40 — 480BY1, UWA40 — 480AY1)
Reduced Energy Wastage
C ontinuous capacity control with a range from 10% to 100% helps to reduce energy wastage during low-load
UWAP 40 — 160B Y 1 (K ) (Z) UWAP 40 — 120B Y B (K ) (Z)
UWAP 40 — 160B Y 1 (K ) (Z) UWAP 40 — 120B Y B (K ) (Z)
UWA40 — 160AY 1 UWA40 — 120AY B
UWA40 — 480AY 1UWAP 40 — 120AY B
UWAP 40 — 480B Y 1 (Z)UWAP 40 — 120B Y B (Z)
UWAP 40 — 480B Y 1
C apacityWater Temperature C ontrol R ange
Models E mploying R -407C Models E mploying R -22
3 — 30
40 — 480
5 to 16
4 to 25 (Inver C ooling Unit)
4 to 25
-10 to 0 (B rine C ooling Unit)
—
—
4 to 16
Wide Water Temperature Control Range
T he wide water temperature c ontrol range provides compatibility with a variety of heat source requirements .
A variety of brine-res is tant specification models are available that provide stable cooling operation at brine outflow temperatures down to -10 .
Applies to All Models
Applies to All Models
UWAP 120B Y 1KUWAXP 750AY 1 UWAP 180B Y 1
Wide Operation Range
A variety of year-round cooling type models are available that provide stable operation at outdoor temperatures down
The wide outdoor air temperature range ensures a s table supply of chilled water year round.
Applies to All Models
C apacityOutdoor Air Temperature R ange where C ooling P oss ible
Models E mploying R -407C Models E mploying R -22
3 — 30
40 — 480
-15 to 43
-5 to 43
-15 to 43 ( Y ear-R ound C ooling Only Unit )
0 to 43 ( B rine C ooling Unit )
—
—
-5 to 43
High Precision
10
9
8
7
Upper Limit S ignal
Water Temp. ( )
E xample of Outlet Water Temperature C ontrol
If outlet water temperature rises above the upper limit s ignal, the load starts to increase in 10% increments
As the temperature falls below the upper limit s ignal, the load increase increments are reduced to 5% .
As the temperature falls below the set value, the load increase increments remain at 5% .
When changes in outlet water temperature become 1 or less , the thermostat is turned off.
Value S et
The outlet water temperature is precisely controlled to within 0.5 (with a s table load) through the use of electric expansion
UWAXP 125 — 750AY 1
UWAP 40 — 160B Y 1 (K ) (Z) UWAP 40 — 120B Y B (K ) (Z)
UWA40 — 160AY 1UWA40 — 120AY B
Inverter control with high load compliance achieves highly accurate outflow water temperature control to within 0.5
Note: In systems with one compressor installed and where the load factor is 30% or more, and in systems with two or more compressors installed and where the load factor is 30% or more, control to within 0.5 is possible.
Air
Coo
led
Wat
er C
hill
ers
Air
Coo
led
Wat
er C
hill
ers
Air Cooled Water Chillers
: UWAP S eries UWAXP S eries : UWA S eries
7 8
Model Lineup
50Hz60Hz50Hz60Hz50Hz60Hz50Hz60Hz
R-407C
R-22
Standard Unit
Year - Round Cooling Only Unit
Brine Cooling Unit
Standard Unit
Refrigerant Units series Model No.
UWAP—BY1UWAP—BYBUWAP—BY1KUWAP—BYBKUWAP—BY1ZUWAP—BYBZUWA—AY1UWA—AYB
Capacity (kW)
9, 10101112
12, 1313
14, 1515
page315120120120120120120120120
370140—
140—
140—
140—
420160—
160—
160—
160—
480180—
180—
180—
180—
530200—
200—
200—
200—
580220—
220—
220—
220—
630240—
240—
240—
240—
740280—
280—
280—
280—
840320—
320—
320—
320—
960360—
360—
360—
360—
1060400—
400—
400—
400—
1160440—
440—
440—
440—
1260480—
480—
480—
480—
50/60Hz50Hz60Hz50Hz60Hz50Hz60Hz50Hz50Hz60Hz
Refrigerant
R-407C
R-22
Units series
Standard Unit
Year - Round Cooling Only Unit
Brine Cooling Unit
Inverter Cooling Unit
Standard Unit
Model No.
UWAP—AY3*UWAP—BY1UWAP—BYBUWAP—BY1KUWAP—BYBKUWAP—BY1ZUWAP—BYBZUWAXP—AY1UWA—AY1UWA—AYB
Capacity (kW)6.7/7.5
75—————————
11.2/12.5125——————
125——
17/19190——————
190——
22.4/25250——————
250——
33.5/37.5375——————
375——
45/50500——————
500——
56/63630——————
630——
67/75750——————
750——
106—404040404040—4040
132—505050505050—5050
160—606060606060—6060
212—80—80—80——80—
265—
100100100100100100—
100100
99, 10101112
12, 131314
14, 1515
page
Note: Capacity figures are provided for reference and assume a power supply frequency of 60 Hz.
E mploys the new refrigerant R -407C .
UWAP 75 — 750AY 3 UWAXP 125 — 750AY 1UWAP 40 — 480B Y 1(K ) (Z) UWAP 40 — 120B Y B (K ) (Z)
New Refrigerant Efficient and Reliable Compressors
To improve their operational reliability, 5 -- 30HP models employ scroll compressors , while 40 -- 480HP models are equipped with semi-hermetic s ingle screw compressors .
R efrigerant inlet
R efrigerant outlet
S emi-hermetic s ingle screw compressor
The user can select to give priority to either precis ion or reduced power consumption.
C ontinues operation to levels as low as 10(12)% of total capacity to provide stable water temperature c ontrol even during low-load peri-ods .
This mode can be used to re-duce power cons umption if highly precise water temperature control is not necessary dur-ing low-load periods. It shuts down the compressor when the load drops below 40% .
High-P rec is ion Mode Low-P ower Mode
Note: Switching between the above modes is accomplished using a control on the outdoor unit.
Multiple Operating Modes
Refrigerant Inlet
Refrigerant Outlet
Water Outlet
WaterInlet
Heat Exchanger with Stainless Steel Plates
S tainles s s teel heat ex-changer plates prevent rust, thereby improving their dura-bility and the system's op-
ReliabilityApplies to All Models
The compact des ign of these units s ignificantly reduces the space required for installation.
The horizontal linkup des ign increases installation flexibility.
In the outdoor unit, component parts of a small size have been used wherever possible to reduced its size and correspondingly reduce how much space it re-quires. Furthermore, replacing the 2-way refrigerant inlets with 4-way inlets has reduced the amount of space the outdoor unit needs even further.
This design provides the installation does not protrude so far, making it possible to install water chillers along a wall or under a roof overhang.
Note: Water supply piping must be purchased separately.(UWAP375AY3 — 750AY3)
UWAP 40 — 480B Y 1 (K ) (Z) UWAP 40 — 120B Y B (K ) (Z)
Easy Installation
UWAP 125AY 3 — 750AY 3
High load compliance and highly efficient inverter control provide highly precise adjustment of the water temperature, making it possible to reduce the size of the peripheral equipment.
UWAXP 125 — 750AY 1
C ompressor duty cycling control together with emergency operation and power-interruption auto-restart functions pro-vide enhanced air conditioning system reliability.
UWA40 — 480AY 1UWA40 — 120AY B
A choice of three control system is available.UWA40 — 480AY 1
Outflow water temperature controlProvides precise control of the water temprerature.(UWAP40 — 160BY1, UWA40 — 160AY1)
Compressor count controlControls the number of compressors operating depending on the load.(UWAP40 — 480BY1, UWA40 — 480AY1)
In flow water temperature controlPerforms duty cycling control.(UWAP40 — 480BY1, UWA40 — 480AY1)
Reduced Energy Wastage
C ontinuous capacity control with a range from 10% to 100% helps to reduce energy wastage during low-load
UWAP 40 — 160B Y 1 (K ) (Z) UWAP 40 — 120B Y B (K ) (Z)
UWAP 40 — 160B Y 1 (K ) (Z) UWAP 40 — 120B Y B (K ) (Z)
UWA40 — 160AY 1 UWA40 — 120AY B
UWA40 — 480AY 1UWAP 40 — 120AY B
UWAP 40 — 480B Y 1 (Z)UWAP 40 — 120B Y B (Z)
UWAP 40 — 480B Y 1
C apacityWater Temperature C ontrol R ange
Models E mploying R -407C Models E mploying R -22
3 — 30
40 — 480
5 to 16
4 to 25 (Inver C ooling Unit)
4 to 25
-10 to 0 (B rine C ooling Unit)
—
—
4 to 16
Wide Water Temperature Control Range
T he wide water temperature c ontrol range provides compatibility with a variety of heat source requirements .
A variety of brine-res is tant specification models are available that provide stable cooling operation at brine outflow temperatures down to -10 .
Applies to All Models
Applies to All Models
UWAP 120B Y 1KUWAXP 750AY 1 UWAP 180B Y 1
Wide Operation Range
A variety of year-round cooling type models are available that provide stable operation at outdoor temperatures down
The wide outdoor air temperature range ensures a s table supply of chilled water year round.
Applies to All Models
C apacityOutdoor Air Temperature R ange where C ooling P oss ible
Models E mploying R -407C Models E mploying R -22
3 — 30
40 — 480
-15 to 43
-5 to 43
-15 to 43 ( Y ear-R ound C ooling Only Unit )
0 to 43 ( B rine C ooling Unit )
—
—
-5 to 43
High Precision
10
9
8
7
Upper Limit S ignal
Water Temp. ( )
E xample of Outlet Water Temperature C ontrol
If outlet water temperature rises above the upper limit s ignal, the load starts to increase in 10% increments
As the temperature falls below the upper limit s ignal, the load increase increments are reduced to 5% .
As the temperature falls below the set value, the load increase increments remain at 5% .
When changes in outlet water temperature become 1 or less , the thermostat is turned off.
Value S et
The outlet water temperature is precisely controlled to within 0.5 (with a s table load) through the use of electric expansion
UWAXP 125 — 750AY 1
UWAP 40 — 160B Y 1 (K ) (Z) UWAP 40 — 120B Y B (K ) (Z)
UWA40 — 160AY 1UWA40 — 120AY B
Inverter control with high load compliance achieves highly accurate outflow water temperature control to within 0.5
Note: In systems with one compressor installed and where the load factor is 30% or more, and in systems with two or more compressors installed and where the load factor is 30% or more, control to within 0.5 is possible.
Air
Coo
led
Wat
er C
hill
ers
Air
Coo
led
Wat
er C
hill
ers
Air Cooled Water Chillers
: UWAP S eries UWAXP S eries : UWA S eries
7 8
10
Air
Coo
led
Wat
er C
hill
ers
Air
Coo
led
Wat
er C
hill
ers
Notes:*1 Cooling capacity is based on the following conditions : Leaving chilled water temp.7 (44.5 F), entering chilled water temp.12 (53.6 F), and outdoor air temp. 35 DB(95 FDB).*2 The following safety devices are equipped as standard. • High pressure protector. • Low pressure protector. • Compressor thermal protector. • Fusible plug. • Reverse-phase protector. • Overheat protection of discharge gas. • Overcurrent relay(compressor). • Freeze-up protection thermostat. • Overcurrent relay(fan). • Safety valve.*3 The unit is equipped with standard water filter.*4 This product is manufactured in China.
S pecifications
kWBtu/hUSRT /min%
kW
m3/mincfmkW
mmkgkg
Model
Cooling capacity
Power supplyChilled water flow rate Capacity steps
Compressor
Evaporator typeCondenser type
Condenserfan
RefrigerantPipe connections water inlet/outletDimensions (H W D)WeightOperating weightOperation range
TypeMotor output
TypeDrive
Air flow rate
Motor output
118 — 355kW class
UWAP 40 — 120B Y BStandard Unit
60Hz
UWAP40BYB(40 )
UWAP50BYB(50 )
UWAP60BYB(60 )
UWAP100BYB(100 )
UWAP120BYB(120 )
118403,000 34 3 phase, 60 Hz 400/440 V, 4 wires system338 100~10-0Semi-hermetic sealed single-screw type 30 1Brazing Plate type Cross fin coil Propeller Direct drive 81028,5930.5 4R-407C
3B Flange (80A HG20593-97)
2,456 2,200 2,0001,6901,7230 to 43
150512,000 43
430
37 1
1,01035,6531.0 4
1,8101,846
180614,000 51
516
45 1
1,8701,910
3001,024,000 85
860
37 2
2,02071,3061.0 8
4B Flange (100A HG20593-97)
2,456 4,400 2,0003,5003,551
3551,212,000 101
1,018
45 2
3,6053,662
Notes:*1 Cooling capacity is based on the following conditions : Leaving chilled water temp.7 (44.5 F), entering chilled water temp.12 (53.6 F), and outdoor air temp. 35 DB(95 FDB).*2 The following safety devices are equipped as standard. • High pressure protector. • Low pressure protector. • Compressor thermal protector. • Fusible plug. • Reverse-phase protector. • Overheat protection of discharge gas. • Overcurrent relay(compressor). • Freeze-up protection thermostat. • Overcurrent relay(fan). • Safety valve.*3 The unit is equipped with standard water filter.*4 This product is manufactured in China.
530 — 1,260kW class
UWAP 200 — 480B Y 1Standard Unit
50Hz
S pecifications
kWBtu/hUSRT /min%
kW
m3/mincfmkW
mm
kgkg
TypeMotor output
TypeDrive
Air flow rate
Motor output
UWAP200BY1(200 )
UWAP220BY1(220 )
UWAP240BY1(240 )
UWAP280BY1(280 )
UWAP320BY1(320 )
UWAP360BY1(360 )
UWAP480BY1(460 )
5301,809,000 151 3 phase, 50 Hz 380/400/415 V, 4 wires system1,519 100~10-0 Semi-hermetic sealed single-screw type45 2+60Brazing Plate type Cross fin coil Propeller Direct drive3,010106,2531.0 14R-407C
5B Flange (125A HG20593-97)
2,456 7,050 2,0006,0006,1980 to 43
UWAP400BY1(400 )
UWAP440BY1(440 )
Model
Cooling capacity Power SupplyChilled Water Flow Rate Capacity Steps
Compressor
Evaporetor type Comdenser type
Condenserfan
RefrigerantPipe connections water inlet/outlet
Dimensions (H W D)
Weight Operation weight Operation range
5801,979,000 165
1,663
45+60 2
3,440121,4321.0 16
2,456 7,500 2,0006,5006,719
6302,150,000179
1,806
60 3
3,870136,6111.0 18
2,456 7,950 2,0007,0057,245
7402,525,000 210
2,121
(45+60) 2
4,300151,790(1.0 10) 2
4B Flange (100A HG20593-97) (2,456 4,850 2,000) 24,125 24,196 2
8402,867,000 239
2,408
(60 2) 2
5,160182,148(1.0 12) 2
(2,456 5,300 2,000) 24,590 24,661 2
9603,276,000 273
2,752
(45 3) 2
5B Flange (125A HG20593-97)
(2,456 6,600 2,000) 25,500 25,691 2
1,0603,617,000 301
3,039
(45 2+60) 2
6,020212,506(1.0 14) 2
(2,456 7,050 2,000) 26,000 26,198 2
1,1603,959,000 330
3,325
(45+60 2) 2
6,880242,864(1.0 16) 2
(2,456 7,500 2,000) 26,500 26,719 2
1,2604,300,000 358
3,612
(60 3) 2
7,740273,222(1.0 18) 2
(2,456 7,950 2,000) 27,005 27,245 2
Notes:*1 Cooling capacity is based on the following conditions : Leaving chilled water temp.7 (44.5 F), entering chilled water temp.12 (53.6 F), and outdoor air temp. 35 DB(95 FDB).*2 The following safety devices are equipped as standard. • High pressure protector. • Low pressure protector. • Compressor thermal protector. • Fusible plug. • Reverse-phase protector. • Overheat protection of discharge gas. • Overcurrent relay(compressor). • Freeze-up protection thermostat. • Overcurrent relay(fan). • Safety valve.*3 The unit is equipped with standard water filter.*4 This product is manufactured in China.
S pecifications
kWBtu/hUSRT /min%
kW
m3/mincfmkW
mm
kgkg
TypeMotor output
TypeDrive
Air flow rate
Motor output
UWAP40BY1(40 )
UWAP50BY1(50 )
UWAP60BY1(60 )
UWAP80BY1(80 )
UWAP100BY1(100 )
UWAP120BY1(120 )
UWAP180BY1(180 )
106362,000 30 3 phase, 50 Hz 380/400/415 V, 4 wires system304100~10-0 Semi-hermetic sealed single-screw type30 1Brazing Plate type Cross fin coil Propeller Direct drive78027,5340.5 4R-407C
3B Flange (80A HG20593-97)
2,456 2,200 2,000
1,6901,7230 to 43
UWAP140BY1(140 )
UWAP160BY1(160 )
106 — 480kW class
UWAP 40 — 180B Y 1Standard Unit
50Hz
Model
Cooling capacity Power SupplyChilled Water Flow Rate Capacity Steps
Compressor
Evaporetor type Comdenser type
Condenserfan
RefrigerantPipe connections water inlet/outlet
Dimensions (H W D)
Weight Operation weight Operation range
132450,000 38
378
37 1
86030,3581.0 4
1,8101,846
160546,000 46
459
45 1
1,8701,910
210717,000 60
602
60 1
1,29045,5371.0 6
2,456 2,650 2,0002,3752,422
265904,000 75
760
37 2
1,60056,4801.0 8
4B Flange (100A HG20593-97)
2,456 4,400 2,000
3,5003,551
3201,092,000 91
917
45 2
1,72060,716
3,6053,662
3701,263,000 105
1,061
45+60
2,15075,8951.0 10
2,456 4,850 2,0004,1254,196
4201,433,000 119
1,204
60 2
2,58091,0741.0 12
2,456 5,300 2,0004,5904,661
4801,638,000 137
1,376
45 3
5B Flange (125A HG20593-97) 2,456 6,600 2,0005,5005,691
Notes:*1 Cooling capacity is based on the following conditions : Leaving chilled water temp.7 (44.5 F), entering chilled water temp.12 (53.6 F), and outdoor air temp. 35 DB(95 FDB). *2 The following safety devices are equipped as standard. • High pressure switch. • Reverse-phase protector. • Fusible plug. • Freeze up thermostat. • Overcurrent relay for compressor
and fan motor. • Overheat protection for discharge gas. • fan thermal protector.*3 This product is manufactured in Japan.
S pecifications
kWBtu/hUSRT
/min
%
kW
m3/mincfmkW
mmkgkg
Model
Cooling capacity(50/60 Hz)
Power supplyChilled water flow rate (50/60 Hz)Capacity steps
Compressor
Evaporator typeCondenser type
Condenserfan
Refrigerant
Pipe connections water inlet/outlet
Dimensions (H W D)WeightOperating weightOperation range
TypeMotor output
TypeDriveAir flow rate(50/60 Hz)Motor output
UWAP75AY3(3 )
UWAP125AY3(5 )
UWAP190AY3(8 )
UWAP250AY3(10 )
UWAP375AY3(15 )
UWAP750AY3(30 )
6.7/7.522,900/25,6001.91/2.133 phase, 50 Hz 380/400/415 V, 60 Hz 400/440 V, 3 wires system
19/22
100-0Hermetically sealed scroll type2.2 1Brazed plate heat exchangerCross fin coilPropellerDirect drive75/852,650/3,0000.14 1R-407C
1B Flange (JIS10K)(25A) 2
1,450 635 (839) 690136138-15 to 43
11.2/12.538,200/42,7003.19/3.55
32/36
3.75 1
90/953,180/3,3500.20 1
140142
17.0/19.058,000/64,9004.83/5.40
49/54
5.5 1
140/1604,940/5,6500.215+0.14
1 1/2B Flange (JIS10K)(40A) 2
1,450 1,280 690248253
22.4/25.076,500/85,4006.37/7.11
64/72
7.5 1
175/1856,180/6,5300.215+0.22
260264
33.5/37.5114,000/128,0009.53/10.7
96/108
100-67-34-0
7.5+3.75
265/2809,350/9,880(0.215+0.22)+0.2
1B Flange (JIS10K)(25A) 2+1 1/2B Flange(JIS10K)(40A) 21,500 1,925 690400407
45.0/50.0154,000/171,00012.8/14.2
129/143
100-50-0
7.5 2
350/37012,400/13,100(0.215+0.22) 2
1 1/2B Flange(JIS10K)(40A) 4
1,500 2,570 690515525
56.0/63.0191,000/215,00015.9/17.9
161/181
100-80-60-40-20-0
7.5 2+3.75
440/46515,500/16,400(0.215+0.22) 2+0.2
1B Flange (JIS10K)(25A) 2+1 1/2B Flange(JIS10K)(40A) 41,550 3,230 758680695
67.0/75.0229,000/256,00019.1/21.3
192/215
100-67-34-0
7.5 3
525/55518,500/19,600(0.215+0.22) 3
1 1/2B Flange(JIS10K)(40A) 6
1,550 3,870 758800820
UWAP500AY3(20 )
UWAP630AY3(25 )
*1
6.7/7.5 — 67/75kW class
UWAP 75 — 750AY 3Standard Unit
50/60Hz
9
Air Cooled Water Chillers
10
Air
Coo
led
Wat
er C
hill
ers
Air
Coo
led
Wat
er C
hill
ers
Notes:*1 Cooling capacity is based on the following conditions : Leaving chilled water temp.7 (44.5 F), entering chilled water temp.12 (53.6 F), and outdoor air temp. 35 DB(95 FDB).*2 The following safety devices are equipped as standard. • High pressure protector. • Low pressure protector. • Compressor thermal protector. • Fusible plug. • Reverse-phase protector. • Overheat protection of discharge gas. • Overcurrent relay(compressor). • Freeze-up protection thermostat. • Overcurrent relay(fan). • Safety valve.*3 The unit is equipped with standard water filter.*4 This product is manufactured in China.
S pecifications
kWBtu/hUSRT /min%
kW
m3/mincfmkW
mmkgkg
Model
Cooling capacity
Power supplyChilled water flow rate Capacity steps
Compressor
Evaporator typeCondenser type
Condenserfan
RefrigerantPipe connections water inlet/outletDimensions (H W D)WeightOperating weightOperation range
TypeMotor output
TypeDrive
Air flow rate
Motor output
118 — 355kW class
UWAP 40 — 120B Y BStandard Unit
60Hz
UWAP40BYB(40 )
UWAP50BYB(50 )
UWAP60BYB(60 )
UWAP100BYB(100 )
UWAP120BYB(120 )
118403,000 34 3 phase, 60 Hz 400/440 V, 4 wires system338 100~10-0Semi-hermetic sealed single-screw type 30 1Brazing Plate type Cross fin coil Propeller Direct drive 81028,5930.5 4R-407C
3B Flange (80A HG20593-97)
2,456 2,200 2,0001,6901,7230 to 43
150512,000 43
430
37 1
1,01035,6531.0 4
1,8101,846
180614,000 51
516
45 1
1,8701,910
3001,024,000 85
860
37 2
2,02071,3061.0 8
4B Flange (100A HG20593-97)
2,456 4,400 2,0003,5003,551
3551,212,000 101
1,018
45 2
3,6053,662
Notes:*1 Cooling capacity is based on the following conditions : Leaving chilled water temp.7 (44.5 F), entering chilled water temp.12 (53.6 F), and outdoor air temp. 35 DB(95 FDB).*2 The following safety devices are equipped as standard. • High pressure protector. • Low pressure protector. • Compressor thermal protector. • Fusible plug. • Reverse-phase protector. • Overheat protection of discharge gas. • Overcurrent relay(compressor). • Freeze-up protection thermostat. • Overcurrent relay(fan). • Safety valve.*3 The unit is equipped with standard water filter.*4 This product is manufactured in China.
530 — 1,260kW class
UWAP 200 — 480B Y 1Standard Unit
50Hz
S pecifications
kWBtu/hUSRT /min%
kW
m3/mincfmkW
mm
kgkg
TypeMotor output
TypeDrive
Air flow rate
Motor output
UWAP200BY1(200 )
UWAP220BY1(220 )
UWAP240BY1(240 )
UWAP280BY1(280 )
UWAP320BY1(320 )
UWAP360BY1(360 )
UWAP480BY1(460 )
5301,809,000 151 3 phase, 50 Hz 380/400/415 V, 4 wires system1,519 100~10-0 Semi-hermetic sealed single-screw type45 2+60Brazing Plate type Cross fin coil Propeller Direct drive3,010106,2531.0 14R-407C
5B Flange (125A HG20593-97)
2,456 7,050 2,0006,0006,1980 to 43
UWAP400BY1(400 )
UWAP440BY1(440 )
Model
Cooling capacity Power SupplyChilled Water Flow Rate Capacity Steps
Compressor
Evaporetor type Comdenser type
Condenserfan
RefrigerantPipe connections water inlet/outlet
Dimensions (H W D)
Weight Operation weight Operation range
5801,979,000 165
1,663
45+60 2
3,440121,4321.0 16
2,456 7,500 2,0006,5006,719
6302,150,000179
1,806
60 3
3,870136,6111.0 18
2,456 7,950 2,0007,0057,245
7402,525,000 210
2,121
(45+60) 2
4,300151,790(1.0 10) 2
4B Flange (100A HG20593-97) (2,456 4,850 2,000) 24,125 24,196 2
8402,867,000 239
2,408
(60 2) 2
5,160182,148(1.0 12) 2
(2,456 5,300 2,000) 24,590 24,661 2
9603,276,000 273
2,752
(45 3) 2
5B Flange (125A HG20593-97)
(2,456 6,600 2,000) 25,500 25,691 2
1,0603,617,000 301
3,039
(45 2+60) 2
6,020212,506(1.0 14) 2
(2,456 7,050 2,000) 26,000 26,198 2
1,1603,959,000 330
3,325
(45+60 2) 2
6,880242,864(1.0 16) 2
(2,456 7,500 2,000) 26,500 26,719 2
1,2604,300,000 358
3,612
(60 3) 2
7,740273,222(1.0 18) 2
(2,456 7,950 2,000) 27,005 27,245 2
Notes:*1 Cooling capacity is based on the following conditions : Leaving chilled water temp.7 (44.5 F), entering chilled water temp.12 (53.6 F), and outdoor air temp. 35 DB(95 FDB).*2 The following safety devices are equipped as standard. • High pressure protector. • Low pressure protector. • Compressor thermal protector. • Fusible plug. • Reverse-phase protector. • Overheat protection of discharge gas. • Overcurrent relay(compressor). • Freeze-up protection thermostat. • Overcurrent relay(fan). • Safety valve.*3 The unit is equipped with standard water filter.*4 This product is manufactured in China.
S pecifications
kWBtu/hUSRT /min%
kW
m3/mincfmkW
mm
kgkg
TypeMotor output
TypeDrive
Air flow rate
Motor output
UWAP40BY1(40 )
UWAP50BY1(50 )
UWAP60BY1(60 )
UWAP80BY1(80 )
UWAP100BY1(100 )
UWAP120BY1(120 )
UWAP180BY1(180 )
106362,000 30 3 phase, 50 Hz 380/400/415 V, 4 wires system304100~10-0 Semi-hermetic sealed single-screw type30 1Brazing Plate type Cross fin coil Propeller Direct drive78027,5340.5 4R-407C
3B Flange (80A HG20593-97)
2,456 2,200 2,000
1,6901,7230 to 43
UWAP140BY1(140 )
UWAP160BY1(160 )
106 — 480kW class
UWAP 40 — 180B Y 1Standard Unit
50Hz
Model
Cooling capacity Power SupplyChilled Water Flow Rate Capacity Steps
Compressor
Evaporetor type Comdenser type
Condenserfan
RefrigerantPipe connections water inlet/outlet
Dimensions (H W D)
Weight Operation weight Operation range
132450,000 38
378
37 1
86030,3581.0 4
1,8101,846
160546,000 46
459
45 1
1,8701,910
210717,000 60
602
60 1
1,29045,5371.0 6
2,456 2,650 2,0002,3752,422
265904,000 75
760
37 2
1,60056,4801.0 8
4B Flange (100A HG20593-97)
2,456 4,400 2,000
3,5003,551
3201,092,000 91
917
45 2
1,72060,716
3,6053,662
3701,263,000 105
1,061
45+60
2,15075,8951.0 10
2,456 4,850 2,0004,1254,196
4201,433,000 119
1,204
60 2
2,58091,0741.0 12
2,456 5,300 2,0004,5904,661
4801,638,000 137
1,376
45 3
5B Flange (125A HG20593-97) 2,456 6,600 2,0005,5005,691
Notes:*1 Cooling capacity is based on the following conditions : Leaving chilled water temp.7 (44.5 F), entering chilled water temp.12 (53.6 F), and outdoor air temp. 35 DB(95 FDB). *2 The following safety devices are equipped as standard. • High pressure switch. • Reverse-phase protector. • Fusible plug. • Freeze up thermostat. • Overcurrent relay for compressor
and fan motor. • Overheat protection for discharge gas. • fan thermal protector.*3 This product is manufactured in Japan.
S pecifications
kWBtu/hUSRT
/min
%
kW
m3/mincfmkW
mmkgkg
Model
Cooling capacity(50/60 Hz)
Power supplyChilled water flow rate (50/60 Hz)Capacity steps
Compressor
Evaporator typeCondenser type
Condenserfan
Refrigerant
Pipe connections water inlet/outlet
Dimensions (H W D)WeightOperating weightOperation range
TypeMotor output
TypeDriveAir flow rate(50/60 Hz)Motor output
UWAP75AY3(3 )
UWAP125AY3(5 )
UWAP190AY3(8 )
UWAP250AY3(10 )
UWAP375AY3(15 )
UWAP750AY3(30 )
6.7/7.522,900/25,6001.91/2.133 phase, 50 Hz 380/400/415 V, 60 Hz 400/440 V, 3 wires system
19/22
100-0Hermetically sealed scroll type2.2 1Brazed plate heat exchangerCross fin coilPropellerDirect drive75/852,650/3,0000.14 1R-407C
1B Flange (JIS10K)(25A) 2
1,450 635 (839) 690136138-15 to 43
11.2/12.538,200/42,7003.19/3.55
32/36
3.75 1
90/953,180/3,3500.20 1
140142
17.0/19.058,000/64,9004.83/5.40
49/54
5.5 1
140/1604,940/5,6500.215+0.14
1 1/2B Flange (JIS10K)(40A) 2
1,450 1,280 690248253
22.4/25.076,500/85,4006.37/7.11
64/72
7.5 1
175/1856,180/6,5300.215+0.22
260264
33.5/37.5114,000/128,0009.53/10.7
96/108
100-67-34-0
7.5+3.75
265/2809,350/9,880(0.215+0.22)+0.2
1B Flange (JIS10K)(25A) 2+1 1/2B Flange(JIS10K)(40A) 21,500 1,925 690400407
45.0/50.0154,000/171,00012.8/14.2
129/143
100-50-0
7.5 2
350/37012,400/13,100(0.215+0.22) 2
1 1/2B Flange(JIS10K)(40A) 4
1,500 2,570 690515525
56.0/63.0191,000/215,00015.9/17.9
161/181
100-80-60-40-20-0
7.5 2+3.75
440/46515,500/16,400(0.215+0.22) 2+0.2
1B Flange (JIS10K)(25A) 2+1 1/2B Flange(JIS10K)(40A) 41,550 3,230 758680695
67.0/75.0229,000/256,00019.1/21.3
192/215
100-67-34-0
7.5 3
525/55518,500/19,600(0.215+0.22) 3
1 1/2B Flange(JIS10K)(40A) 6
1,550 3,870 758800820
UWAP500AY3(20 )
UWAP630AY3(25 )
*1
6.7/7.5 — 67/75kW class
UWAP 75 — 750AY 3Standard Unit
50/60Hz
9
Air Cooled Water Chillers
S pecifications
kWBtu/hUSRT /min%
kW
m3/mincfmkW
mmkgkg
Model
Cooling capacity
Power supplyChilled water flow rate Capacity steps
Compressor
Evaporator typeCondenser type
Condenserfan
Refrigerant
Pipe connections water inlet/outlet
Dimensions (H W D)WeightOperating weightOperation range
TypeMotor output
TypeDrive
Air flow rate
Motor output
Notes:*1 Cooling capacity is based on the following conditions : Leaving chilled water temp.7 (44.5 F), entering chilled water temp.12 (53.6 F), and outdoor air temp. 35 DB(95 FDB).*2 The following safety devices are equipped as standard. • High pressure protector. • Low pressure protector. • Compressor thermal protector. • Fusible plug. • Reverse-phase protector. • Overheat protection of discharge gas. • Overcurrent relay(compressor). • Freeze-up protection thermostat. • Overcurrent relay(fan). • Safety valve.*3 The unit is equipped with standard water filter.*4 This product is manufactured in China.
*1
118 — 355kW class
UWAP 40 — 120B Y B KYear - Round Cooling Only Unit
60Hz
UWAP40BYBK(40 )
UWAP50BYBK(50 )
UWAP60BYBK(60 )
UWAP100BYBK(100 )
UWAP120BYBK(120 )
S pecifications
kWBtu/hUSRT /min%
kW
m3/mincfmkW
mm
kgkg
Model
Cooling capacity
Power supplyChilled water flow rate Capacity steps
Compressor
Evaporator typeCondenser type
Condenserfan
RefrigerantPipe connections water inlet/outlet
Dimensions (H W D)
WeightOperating weightOperation range
TypeMotor output
TypeDrive
Air flow rate
Motor output
Notes:*1 Cooling capacity is based on the following conditions : Leaving chilled water temp.7 (44.5 F), entering chilled water temp.12 (53.6 F), and outdoor air temp. 35 DB(95 FDB).*2 The following safety devices are equipped as standard. • High pressure protector. • Low pressure protector. • Compressor thermal protector. • Fusible plug. • Reverse-phase protector. • Overheat protection of discharge gas. • Overcurrent relay(compressor). • Freeze-up protection thermostat. • Overcurrent relay(fan). • Safety valve.*3 The unit is equipped with standard water filter.*4 This product is manufactured in China.
*1
530 — 1,260kW class
UWAP 200 — 480B Y 1KYear - Round Cooling Only Unit
50Hz
UWAP200BY1K(200 )
UWAP220BY1K(220 )
UWAP240BY1K(240 )
UWAP280BY1K(280 )
UWAP320BY1K(320 )
UWAP360BY1K(360 )
UWAP400BY1K(400 )
UWAP440BY1K(440 )
UWAP480BY1K(480 )
S pecifications
kWBtu/hUSRT /min%
kW
m3/mincfmkW
mm
kgkg
Model
Cooling capacity
Power supplyChilled water flow rate Capacity steps
Compressor
Evaporator typeCondenser type
Condenserfan
RefrigerantPipe connections water inlet/outlet
Dimensions (H W D)
WeightOperating weightOperation range
TypeMotor output
TypeDrive
Air flow rate
Motor output
Notes:*1 Cooling capacity is based on the following conditions : Leaving chilled water temp.7 (44.5 F), entering chilled water temp.12 (53.6 F), and outdoor air temp. 35 DB(95 FDB).*2 The following safety devices are equipped as standard. • High pressure protector. • Low pressure protector. • Compressor thermal protector. • Fusible plug. • Reverse-phase protector. • Overheat protection of discharge gas. • Overcurrent relay(compressor). • Freeze-up protection thermostat. • Overcurrent relay(fan). • Safety valve.*3 The unit is equipped with standard water filter.*4 This product is manufactured in China.
*1
106 — 480kW class
UWAP 40 — 180B Y 1KYear - Round Cooling Only Unit
50Hz
UWAP40BY1K(40 )
UWAP50BY1K(50 )
UWAP60BY1K(60 )
UWAP80BY1K(80 )
UWAP100BY1K(100 )
UWAP120BY1K(120 )
UWAP140BY1K(140 )
UWAP160BY1K(160 )
UWAP180BY1K(180 )
Air Cooled Water Chillers
S pecifications
kWBtu/hUSRT /min%
kW
m3/mincfmkW
mm
kgkg
Model
Cooling capacity
Power supplyChilled water flow rate Capacity steps
Compressor
Evaporator typeCondenser type
Condenserfan
RefrigerantPipe connections water inlet/outlet
Dimensions (H W D)
WeightOperating weightOperation range
TypeMotor output
TypeDrive
Air flow rate
Motor output
Notes:*1 Cooling capacity is based on the following conditions : Leaving chilled water temp.-5 (23.0 F), entering chilled water temp.-2 (28.4 F), and outdoor air temp. 35 DB(95 FDB).*2 The following safety devices are equipped as standard. • High pressure protector. • Low pressure protector. • Compressor thermal protector. • Fusible plug. • Reverse-phase protector. • Overheat protection of discharge gas. • Overcurrent relay(compressor). • Freeze-up protection thermostat. • Overcurrent relay(fan). • Safety valve.*3 The unit is equipped with standard water filter.*4 This product is manufactured in China.
68 — 303kW class
UWAP 40 — 180B Y 1ZBrine Cooling Unit
50Hz
UWAP40BY1Z(40 )
UWAP50BY1Z(50 )
UWAP60BY1Z(60 )
UWAP80BY1Z(80 )
UWAP100BY1Z(100 )
UWAP120BY1Z(120 )
UWAP140BY1Z(140 )
UWAP160BY1Z(160 )
UWAP180BY1Z(180 )
68232,000 193 phase, 50 Hz 380/400/415 V, 4 wires system 428 100~10-0 Semi-hermetic sealed single-screw type30 1Brazing Plate type Cross fin coil Propeller Direct drive78027,5340.5 4R-407C
3B Flange (80A HG20593-97)
2,456 2,200 2,000
1,6901,723ambient temp. 0 to 43, Brine temp. -10 to 16
83283,000 24
522
37 1
86030,3581.0 4
1,8101,846
101345,000 29
635
45 1
1,8701,910
135460,000 38
848
60 1
1,29045,5371.0 6
2,456 2,650 2,0002,3752,422
166567,000 47
1,044
37 2
1,60056,4801.0 8
4B Flange (100A HG20593-97)
2,456 4,400 2,000
3,5003,551
205700,000 58
1,290
45 2
1,72060,716
3,6053,662
236804,00067
1,483
45+60
2,15075,8951.0 10
2,456 4,850 2,0004,1254,196
269918,00077
1,693
60 2
2,58091,0741.0 12
2,456 5,300 2,0004,5904,661
3031,034,000 86
1,906
45 3
5B Flange (125A HG20593-97)2,456 6,600 2,0005,5005,691
118403,000 343 phase, 60 Hz 400/440 V, 4 wires system 338100~10-0 Semi-hermetic sealed single-screw type30 1Brazing Plate type Cross fin coil Propeller Direct drive81028,5930.5 4R-407C
3B Flange (80A HG20593-97)
2,456 2,200 2,000 1,7151,748-15 to 43
150512,00043
430
37 1
1,01035,6531.0 4
1,8351,871
180614,00051
516
45 1
1,8951,935
3001,024,00085
860
37 2
2,02071,3061.0 8
4B Flange (100A HG20593-97)
2,456 4,400 2,0003,5503,601
3551,212,000101
1,018
45 2
3,6553,712
106362,000 303 phase, 50 Hz 380/400/415 V, 4 wires system 304 100~10-0 Semi-hermetic sealed single-screw type30 1Brazing Plate type Cross fin coil Propeller Direct drive78027,5340.5 4R-407C
3B Flange (80A HG20593-97)
2,456 2,200 2,000
1,7151,748-15 to 43
5301,809,000 1513 phase, 50 Hz 380/400/415 V, 4 wires system 1,519100~10-0 Semi-hermetic sealed single-screw type40 2+60Brazing Plate type Cross fin coil Propeller Direct drive3,010106,2531.0 14R-407C
5B Flange (125A HG20593-97)
2,456 7,050 2,000 6,0856,283-15 to 43
5801,979,000165
1,663
45+60 2
3,440121,4321.0 16
2,456 7,500 2,0006,5956,814
6302,150,000179
1,806
60 3
3,870136,6111.0 18
2,456 7,950 2,0007,1107,350
7402,525,000210
2,121
(45+60) 2
4,300151,790(1.0 10) 2
4B Flange (100A HG20593-97)
(2,450 4,850 2,000) 24,185 24,256 2
8402,867,000239
2,408
(60 2) 2
5,160182,148(1.0 12) 2
(2,456 5,300 2,000) 24,660 24,731 2
9603,276,000273
2,752
(45 3) 2
5B Flange (125A HG20593-97)
(2,456 6,600 2,000) 25,575 25,766 2
1,0603,617,000301
3,039
(45 2+60) 2
6,020212,506(1.0 14) 2
(2,456 7,050 2,000) 26,085 26,283 2
1,1603,959,000330
3,325
(45+60 2) 2
6,880242,864(1.0 16) 2
(2,456 7,500 2,000) 26,595 26,814 2
1,2604,300,000358
3,612
(60 3) 2
7,740273,222(1.0 18) 2
(2,456 7,950 2,000) 27,110 27,350 2
132450,00038
378
37 1
86030,3581.0 4
1.8351.871
160546,00046
459
45 1
1,8951,935
210717,00060
602
60 1
1,29045,5371.0 6
2,456 2,650 2,0002,4102,457
265904,00075
760
37 2
1,60056,4801.0 8
4B Flange (100A HG20593-97)
2,456 4,400 2,000
3,5503,601
3201,092,00091
917
45 2
1,72060,716
3,6553,712
3701,263,000105
1,061
45+60
2,15075,8951.0 10
2,456 4,850 2,0004,1854,256
4201,433,000119
1,204
60 2
2,58091,0741.0 12
2,456 5,300 2,0004,6604,731
4801,638,000137
1,376
45 3
5B Flange (125A HG20593-97)2,456 6,600 2,0005,5755,766
Air
Coo
led
Wat
er C
hill
ers
Air
Coo
led
Wat
er C
hill
ers
11 12
S pecifications
kWBtu/hUSRT /min%
kW
m3/mincfmkW
mmkgkg
Model
Cooling capacity
Power supplyChilled water flow rate Capacity steps
Compressor
Evaporator typeCondenser type
Condenserfan
Refrigerant
Pipe connections water inlet/outlet
Dimensions (H W D)WeightOperating weightOperation range
TypeMotor output
TypeDrive
Air flow rate
Motor output
Notes:*1 Cooling capacity is based on the following conditions : Leaving chilled water temp.7 (44.5 F), entering chilled water temp.12 (53.6 F), and outdoor air temp. 35 DB(95 FDB).*2 The following safety devices are equipped as standard. • High pressure protector. • Low pressure protector. • Compressor thermal protector. • Fusible plug. • Reverse-phase protector. • Overheat protection of discharge gas. • Overcurrent relay(compressor). • Freeze-up protection thermostat. • Overcurrent relay(fan). • Safety valve.*3 The unit is equipped with standard water filter.*4 This product is manufactured in China.
*1
118 — 355kW class
UWAP 40 — 120B Y B KYear - Round Cooling Only Unit
60Hz
UWAP40BYBK(40 )
UWAP50BYBK(50 )
UWAP60BYBK(60 )
UWAP100BYBK(100 )
UWAP120BYBK(120 )
S pecifications
kWBtu/hUSRT /min%
kW
m3/mincfmkW
mm
kgkg
Model
Cooling capacity
Power supplyChilled water flow rate Capacity steps
Compressor
Evaporator typeCondenser type
Condenserfan
RefrigerantPipe connections water inlet/outlet
Dimensions (H W D)
WeightOperating weightOperation range
TypeMotor output
TypeDrive
Air flow rate
Motor output
Notes:*1 Cooling capacity is based on the following conditions : Leaving chilled water temp.7 (44.5 F), entering chilled water temp.12 (53.6 F), and outdoor air temp. 35 DB(95 FDB).*2 The following safety devices are equipped as standard. • High pressure protector. • Low pressure protector. • Compressor thermal protector. • Fusible plug. • Reverse-phase protector. • Overheat protection of discharge gas. • Overcurrent relay(compressor). • Freeze-up protection thermostat. • Overcurrent relay(fan). • Safety valve.*3 The unit is equipped with standard water filter.*4 This product is manufactured in China.
*1
530 — 1,260kW class
UWAP 200 — 480B Y 1KYear - Round Cooling Only Unit
50Hz
UWAP200BY1K(200 )
UWAP220BY1K(220 )
UWAP240BY1K(240 )
UWAP280BY1K(280 )
UWAP320BY1K(320 )
UWAP360BY1K(360 )
UWAP400BY1K(400 )
UWAP440BY1K(440 )
UWAP480BY1K(480 )
S pecifications
kWBtu/hUSRT /min%
kW
m3/mincfmkW
mm
kgkg
Model
Cooling capacity
Power supplyChilled water flow rate Capacity steps
Compressor
Evaporator typeCondenser type
Condenserfan
RefrigerantPipe connections water inlet/outlet
Dimensions (H W D)
WeightOperating weightOperation range
TypeMotor output
TypeDrive
Air flow rate
Motor output
Notes:*1 Cooling capacity is based on the following conditions : Leaving chilled water temp.7 (44.5 F), entering chilled water temp.12 (53.6 F), and outdoor air temp. 35 DB(95 FDB).*2 The following safety devices are equipped as standard. • High pressure protector. • Low pressure protector. • Compressor thermal protector. • Fusible plug. • Reverse-phase protector. • Overheat protection of discharge gas. • Overcurrent relay(compressor). • Freeze-up protection thermostat. • Overcurrent relay(fan). • Safety valve.*3 The unit is equipped with standard water filter.*4 This product is manufactured in China.
*1
106 — 480kW class
UWAP 40 — 180B Y 1KYear - Round Cooling Only Unit
50Hz
UWAP40BY1K(40 )
UWAP50BY1K(50 )
UWAP60BY1K(60 )
UWAP80BY1K(80 )
UWAP100BY1K(100 )
UWAP120BY1K(120 )
UWAP140BY1K(140 )
UWAP160BY1K(160 )
UWAP180BY1K(180 )
Air Cooled Water Chillers
S pecifications
kWBtu/hUSRT /min%
kW
m3/mincfmkW
mm
kgkg
Model
Cooling capacity
Power supplyChilled water flow rate Capacity steps
Compressor
Evaporator typeCondenser type
Condenserfan
RefrigerantPipe connections water inlet/outlet
Dimensions (H W D)
WeightOperating weightOperation range
TypeMotor output
TypeDrive
Air flow rate
Motor output
Notes:*1 Cooling capacity is based on the following conditions : Leaving chilled water temp.-5 (23.0 F), entering chilled water temp.-2 (28.4 F), and outdoor air temp. 35 DB(95 FDB).*2 The following safety devices are equipped as standard. • High pressure protector. • Low pressure protector. • Compressor thermal protector. • Fusible plug. • Reverse-phase protector. • Overheat protection of discharge gas. • Overcurrent relay(compressor). • Freeze-up protection thermostat. • Overcurrent relay(fan). • Safety valve.*3 The unit is equipped with standard water filter.*4 This product is manufactured in China.
68 — 303kW class
UWAP 40 — 180B Y 1ZBrine Cooling Unit
50Hz
UWAP40BY1Z(40 )
UWAP50BY1Z(50 )
UWAP60BY1Z(60 )
UWAP80BY1Z(80 )
UWAP100BY1Z(100 )
UWAP120BY1Z(120 )
UWAP140BY1Z(140 )
UWAP160BY1Z(160 )
UWAP180BY1Z(180 )
68232,000 193 phase, 50 Hz 380/400/415 V, 4 wires system 428 100~10-0 Semi-hermetic sealed single-screw type30 1Brazing Plate type Cross fin coil Propeller Direct drive78027,5340.5 4R-407C
3B Flange (80A HG20593-97)
2,456 2,200 2,000
1,6901,723ambient temp. 0 to 43, Brine temp. -10 to 16
83283,000 24
522
37 1
86030,3581.0 4
1,8101,846
101345,000 29
635
45 1
1,8701,910
135460,000 38
848
60 1
1,29045,5371.0 6
2,456 2,650 2,0002,3752,422
166567,000 47
1,044
37 2
1,60056,4801.0 8
4B Flange (100A HG20593-97)
2,456 4,400 2,000
3,5003,551
205700,000 58
1,290
45 2
1,72060,716
3,6053,662
236804,00067
1,483
45+60
2,15075,8951.0 10
2,456 4,850 2,0004,1254,196
269918,00077
1,693
60 2
2,58091,0741.0 12
2,456 5,300 2,0004,5904,661
3031,034,000 86
1,906
45 3
5B Flange (125A HG20593-97)2,456 6,600 2,0005,5005,691
118403,000 343 phase, 60 Hz 400/440 V, 4 wires system 338100~10-0 Semi-hermetic sealed single-screw type30 1Brazing Plate type Cross fin coil Propeller Direct drive81028,5930.5 4R-407C
3B Flange (80A HG20593-97)
2,456 2,200 2,000 1,7151,748-15 to 43
150512,00043
430
37 1
1,01035,6531.0 4
1,8351,871
180614,00051
516
45 1
1,8951,935
3001,024,00085
860
37 2
2,02071,3061.0 8
4B Flange (100A HG20593-97)
2,456 4,400 2,0003,5503,601
3551,212,000101
1,018
45 2
3,6553,712
106362,000 303 phase, 50 Hz 380/400/415 V, 4 wires system 304 100~10-0 Semi-hermetic sealed single-screw type30 1Brazing Plate type Cross fin coil Propeller Direct drive78027,5340.5 4R-407C
3B Flange (80A HG20593-97)
2,456 2,200 2,000
1,7151,748-15 to 43
5301,809,000 1513 phase, 50 Hz 380/400/415 V, 4 wires system 1,519100~10-0 Semi-hermetic sealed single-screw type40 2+60Brazing Plate type Cross fin coil Propeller Direct drive3,010106,2531.0 14R-407C
5B Flange (125A HG20593-97)
2,456 7,050 2,000 6,0856,283-15 to 43
5801,979,000165
1,663
45+60 2
3,440121,4321.0 16
2,456 7,500 2,0006,5956,814
6302,150,000179
1,806
60 3
3,870136,6111.0 18
2,456 7,950 2,0007,1107,350
7402,525,000210
2,121
(45+60) 2
4,300151,790(1.0 10) 2
4B Flange (100A HG20593-97)
(2,450 4,850 2,000) 24,185 24,256 2
8402,867,000239
2,408
(60 2) 2
5,160182,148(1.0 12) 2
(2,456 5,300 2,000) 24,660 24,731 2
9603,276,000273
2,752
(45 3) 2
5B Flange (125A HG20593-97)
(2,456 6,600 2,000) 25,575 25,766 2
1,0603,617,000301
3,039
(45 2+60) 2
6,020212,506(1.0 14) 2
(2,456 7,050 2,000) 26,085 26,283 2
1,1603,959,000330
3,325
(45+60 2) 2
6,880242,864(1.0 16) 2
(2,456 7,500 2,000) 26,595 26,814 2
1,2604,300,000358
3,612
(60 3) 2
7,740273,222(1.0 18) 2
(2,456 7,950 2,000) 27,110 27,350 2
132450,00038
378
37 1
86030,3581.0 4
1.8351.871
160546,00046
459
45 1
1,8951,935
210717,00060
602
60 1
1,29045,5371.0 6
2,456 2,650 2,0002,4102,457
265904,00075
760
37 2
1,60056,4801.0 8
4B Flange (100A HG20593-97)
2,456 4,400 2,000
3,5503,601
3201,092,00091
917
45 2
1,72060,716
3,6553,712
3701,263,000105
1,061
45+60
2,15075,8951.0 10
2,456 4,850 2,0004,1854,256
4201,433,000119
1,204
60 2
2,58091,0741.0 12
2,456 5,300 2,0004,6604,731
4801,638,000137
1,376
45 3
5B Flange (125A HG20593-97)2,456 6,600 2,0005,5755,766
Air
Coo
led
Wat
er C
hill
ers
Air
Coo
led
Wat
er C
hill
ers
11 12
S pecifications
kWBtu/hUSRT
/min%
kW
m3/mincfmkW
mmkgkg
Model
Cooling capacity
Power supplyChilled water flow rate Capacity steps
Compressor
Evaporator typeCondenser type
Condenserfan
Refrigerant
Dimensions (H W D)WeightOperating weightOperation range
TypeMotor output
TypeDrive
Air flow rate
Motor output
12.542,7003.553 phase, 50 Hz 380/400/415 V, 4 wires system36100~35Hermetically sealed scroll type3.5 1Blazing plate heat exchangersCross fin coilPropellerDirect drive (Inverter system)803,1800.20 1R-407C1B Flange (JIS10K)(25A)1,450 835 690 150152-15 to 43
19.064,9005.40
54100~20
(3.5+2.2) 1
1504,940(0.20+0.14) 1
1 1/2B Flange (JIS10K)(25A)
1,450 1,280 690250252
25.085,4007.11
72
(3.5+3.75) 1
1706,180(0.20+0.18) 1
260263
50.0171,00014.2
143
(5.5+7.5) 1
34012,400(0.14+0.20) 2
1,500 2,570 690510517
63.0215,00017.9
181
(3.5+3.75)+(5.5+5.5)
170+2656,180+9,350(0.20+0.18)+0.20 3
2 1/2B Flange (JIS10K)(65A)
1,550 3,230 758715730
75.0256,00021.3
215
(3.5+3.75)+(5.5+7.5)
170+3406,180+12,400(0.20+0.18)+(0.14 2+0.20 2)
1,550 3,870 758790820
UWAXP750AY1(30 )
UWAXP630AY1(25 )
UWAXP500AY1(20 )
UWAXP375AY1(15 )
UWAXP250AY1(10 )
UWAXP190AY1(8 )
UWAXP125AY1(5 )
37.5128,00010.7
108
(5.5+5.5) 1
2659,3500.20 3
2B Flange (JIS10K)(50A)
1,500 1,925 690440446
*1
Pipe connections water inlet/outlet
Notes:*1 Cooling capacity is based on the following conditions : Entering water temp.12 (53.6 F), Ieaving chilled water temp.7 (44.5 F), and outdoor temp. 35 DB (95 FDB). *2 The following safety devices are equipped as standard. • High/ pressure switch. • Reverse-phase protector. • Fusible plug. • Freeze-up thermostat. • Overcurrent relay for compressor and fan motor. • Overheat protection for discharge gas. • Fan thermal protector. *3 This product is manufactured in Japan.
12.5 — 75kW class
UWAXP 125 — 750AY 1Inverter Cooling Unit
50Hz
S pecifications
kWBtu/hUSRT /min%
kW
m3/mincfmkW
mm
kgkg
Model
Cooling capacity
Power supplyChilled water flow rate Capacity steps
Compressor
Evaporator typeCondenser type
CondenserFans
RefrigerantPipe connections water inlet/outlet
Dimensions (H W D)
WeightOperating weightOperation range
TypeMotor output
TypeDrive
Air flow rate
Motor output
Brine Cooling Unit
337 — 808kW class
UWAP 200 — 480B Y 1Z50Hz
UWAP480BY1Z(480 )
UWAP440BY1Z(440 )
UWAP400BY1Z(400 )
UWAP360BY1Z(360 )
UWAP320BY1Z(320 )
UWAP280BY1Z(280 )
UWAP240BY1Z(240 )
UWAP220BY1Z(220 )
UWAP200BY1Z(200 )
3371,149,000 96 3 phase,50 Hz 380/400/415 V, 4 wires system 2,119100~10-0Semi-hermetic sealed single-screw type 45 2+60Brazing Plate type Cross fin coil Propeller Direct drive 3,010106,2531.0 14R-407C
5B Flange (125A HG20593-97)
2,456 7,050 2,0006,0006,198 ambient temp. 0 to 43, Brine temp. -10 to 16
Notes:*1 Cooling capacity is based on the following conditions : Leaving chilled water temp.-5 (23.0 F), entering chilled water temp.-2 (28.4 F), and outdoor air temp. 35 DB(95 FDB).*2 The following safety devices are equipped as standard. • High pressure protector. • Low pressure protector. • Compressor thermal protector. • Fusible plug. • Reverse-phase protector. • Overheat protection of discharge gas. • Overcurrent relay(compressor). • Freeze-up protection thermostat. • Overcurrent relay(fan). • Safety valve.*3 The unit is equipped with standard water filter.*4 This product is manufactured in China.
3701,263,000 105
2,328
45+60 2
3,440121,4321.0 16
2,456 7,500 2,0006,5006,719
4041,379,000 115
2,542
60 3
3,870136,6111.0 18
2,456 7,950 2,0007,0057,245
4721,611,000 134
2,970
(45+60) 2
4,300151,790(1.0 10) 2
4B Flange (100A HG20593-97)
(2,456 4,850 2,000) 24,125 24,196 2
5381,836,000 153
3,385
(60 2) 2
5,160182,148(1.0 12) 2
(2,456 5,300 2,000) 2 4,590 24,661 2
6062,068,000 172
3,813
(45 3) 2
5B Flange (125A HG20593-97)
(2,456 6,600 2,000) 2 5,500 25,691 2
6742,300,000 192
4,241
(45 2+60) 2
6,020212,506(1.0 14) 2
(2,456 7,050 2,000) 2 6,000 26,198 2
7402,525,000 210
4,656
(45+60 2) 2
6,880242,864(1.0 16) 2
(2,456 7,500 2,000) 2 6,500 26,719 2
8082,757,000 230
5,084
(60 3) 2
7,740273,222(1.0 18) 2
(2,456 7,950 2,000) 2 7,005 27,245 2
Brine Cooling Unit
79 — 242kW class
UWAP 40 — 120B Y B Z60Hz
S pecifications
kWBtu/hUSRT /min%
kW
m3/mincfmkW
mmkgkg
Model
Cooling capacity
Power supplyChilled water flow rate Capacity steps
Compressor
Evaporator typeCondenser type
CondenserFans
RefrigerantPipe connections water inlet/outletDimensions (H W D)WeightOperating weightOperation range
TypeMotor output
TypeDrive
Air flow rate
Motor output
Notes:*1 Cooling capacity is based on the following conditions : Leaving chilled water temp.-5 (23.0 F), entering chilled water temp.-2 (28.4 F), and outdoor air temp. 35 DB(95 FDB).*2 The following safety devices are equipped as standard. • High pressure protector. • Low pressure protector. • Compressor thermal protector. • Fusible plug. • Reverse-phase protector. • Overheat protection of discharge gas. • Overcurrent relay(compressor). • Freeze-up protection thermostat. • Overcurrent relay(fan). • Safety valve.*3 The unit is equipped with standard water filter.*4 This product is manufactured in China.
UWAP40BYBZ(40 )
UWAP50BYBZ(50 )
UWAP60BYBZ(60 )
UWAP100BYBZ(100 )
UWAP120BYBZ(120 )
242826,000 69
1,523
45 2
3,6053,662
79270,000 22 3 phase,60 Hz 400/440 V, 3 wires system 497 100~10-0Semi-hermetic sealed single-screw type30 1Brazing Plate type Cross fin coil Propeller Direct drive81028,5930.5 4R-407C
3B Flange (80A HG20593-97)
2,456 2,200 2,0001,6901,723ambient temp. 0 to 43, Brine temp. -10 to 16
94321,000 27
591
37 1
1,01035,6531.0 4
1,8101,846
121413,000 34
761
45 1
1,8701,910
188642,000 53
1,183
37 2
2,02071,3061.0 8
4B Flange (100A HG20593-97)
2,456 4,400 2,0003,5003,551
S pecifications
kWBtu/hUSRT
/min%
kW
m3/mincfmkW
mmkgkg
Model
Cooling capacity
Power supplyChilled water flow rate Capacity steps
Compressor
Evaporator typeCondenser type
Condenserfan
RefrigerantPipe connections water inlet/outletDimensions (H W D)WeightOperating weightOperation range
TypeMotor output
TypeDrive
Air flow rate
Motor output
UWA40AY1(40 )
UWA50AY1(50 )
UWA60AY1(60 )
UWA80AYAY1(80 )
UWA100AY1(100 )
UWA120AY1(120 )
UWA180AY1(180 )
106362,000303 phase, 50 Hz 380/400/415 V, 4 wires system304100~10-0 (continuous capacity control)Semi-hermetic sealed single-screw type30 1Blazing Plate typeCross fin coilPropellerDirect drive70024,7100.5 4R-22
3B Flange (80A HG20593-97)
2,395 2,200 2,000 1,5001,517-5 to 43
132450,00038
378
37 1
71025,0630.8 4
1,6501,670
160546,00046
459
45 1
84029,6521.2 4
1,7501,773
265904,00075
760
37 2
1,42050,1260.8 8
4B Flange (100A HG20593-97)
2,395 4,400 2,0003,3003,336
3201,092,00091
917
45 2
1,68059,3041.2 8
3,5003,542
3701,263,000105
1,061
45+60
1,78062,834
3,6203,684
4201,433,000119
1,204
60 2
1,88066,364
3,6403,704
4801,638,000137
1,376
45 3
2,52088,9561.2 12
5B Flange (125A HG20593-97)2,460 6,600 2,0005,6055,670
UWA140AY1(140 )
UWA160AY1(160 )
Notes:*1 Cooling capacity is based on the following conditions : Leaving chilled water temp.7 (44.5 F), entering chilled water temp.12 (53.6 F), and outdoor air temp. 35 DB(95 FDB).*2 The following safety devices are equipped as standard. • High pressure protector. • Low pressure protector. • Compressor thermal protector. • Fusible plug. • Reverse-phase protector. • Overheat protection of discharge gas. • Overcurrent relay(compressor). • Freeze-up protection thermostat. • Overcurrent relay(fan). • Safety valve.*3 Standard for the max. chilled water pressure is 0.7MPa, but1.6MPa is available if required.*4 Installation/operating weight includes the weight of refrigerant and refrigerant oil(charged before delivery).
210717,00060
602
60 1
94033,182
1,8201,852
*1
106 — 480kW class
UWA40 — 180AY 1Standard Unit
50Hz
Air Cooled Water Chillers
Air
Coo
led
Wat
er C
hill
ers
Air
Coo
led
Wat
er C
hill
ers
13 14
S pecifications
kWBtu/hUSRT
/min%
kW
m3/mincfmkW
mmkgkg
Model
Cooling capacity
Power supplyChilled water flow rate Capacity steps
Compressor
Evaporator typeCondenser type
Condenserfan
Refrigerant
Dimensions (H W D)WeightOperating weightOperation range
TypeMotor output
TypeDrive
Air flow rate
Motor output
12.542,7003.553 phase, 50 Hz 380/400/415 V, 4 wires system36100~35Hermetically sealed scroll type3.5 1Blazing plate heat exchangersCross fin coilPropellerDirect drive (Inverter system)803,1800.20 1R-407C1B Flange (JIS10K)(25A)1,450 835 690 150152-15 to 43
19.064,9005.40
54100~20
(3.5+2.2) 1
1504,940(0.20+0.14) 1
1 1/2B Flange (JIS10K)(25A)
1,450 1,280 690250252
25.085,4007.11
72
(3.5+3.75) 1
1706,180(0.20+0.18) 1
260263
50.0171,00014.2
143
(5.5+7.5) 1
34012,400(0.14+0.20) 2
1,500 2,570 690510517
63.0215,00017.9
181
(3.5+3.75)+(5.5+5.5)
170+2656,180+9,350(0.20+0.18)+0.20 3
2 1/2B Flange (JIS10K)(65A)
1,550 3,230 758715730
75.0256,00021.3
215
(3.5+3.75)+(5.5+7.5)
170+3406,180+12,400(0.20+0.18)+(0.14 2+0.20 2)
1,550 3,870 758790820
UWAXP750AY1(30 )
UWAXP630AY1(25 )
UWAXP500AY1(20 )
UWAXP375AY1(15 )
UWAXP250AY1(10 )
UWAXP190AY1(8 )
UWAXP125AY1(5 )
37.5128,00010.7
108
(5.5+5.5) 1
2659,3500.20 3
2B Flange (JIS10K)(50A)
1,500 1,925 690440446
*1
Pipe connections water inlet/outlet
Notes:*1 Cooling capacity is based on the following conditions : Entering water temp.12 (53.6 F), Ieaving chilled water temp.7 (44.5 F), and outdoor temp. 35 DB (95 FDB). *2 The following safety devices are equipped as standard. • High/ pressure switch. • Reverse-phase protector. • Fusible plug. • Freeze-up thermostat. • Overcurrent relay for compressor and fan motor. • Overheat protection for discharge gas. • Fan thermal protector. *3 This product is manufactured in Japan.
12.5 — 75kW class
UWAXP 125 — 750AY 1Inverter Cooling Unit
50Hz
S pecifications
kWBtu/hUSRT /min%
kW
m3/mincfmkW
mm
kgkg
Model
Cooling capacity
Power supplyChilled water flow rate Capacity steps
Compressor
Evaporator typeCondenser type
CondenserFans
RefrigerantPipe connections water inlet/outlet
Dimensions (H W D)
WeightOperating weightOperation range
TypeMotor output
TypeDrive
Air flow rate
Motor output
Brine Cooling Unit
337 — 808kW class
UWAP 200 — 480B Y 1Z50Hz
UWAP480BY1Z(480 )
UWAP440BY1Z(440 )
UWAP400BY1Z(400 )
UWAP360BY1Z(360 )
UWAP320BY1Z(320 )
UWAP280BY1Z(280 )
UWAP240BY1Z(240 )
UWAP220BY1Z(220 )
UWAP200BY1Z(200 )
3371,149,000 96 3 phase,50 Hz 380/400/415 V, 4 wires system 2,119100~10-0Semi-hermetic sealed single-screw type 45 2+60Brazing Plate type Cross fin coil Propeller Direct drive 3,010106,2531.0 14R-407C
5B Flange (125A HG20593-97)
2,456 7,050 2,0006,0006,198 ambient temp. 0 to 43, Brine temp. -10 to 16
Notes:*1 Cooling capacity is based on the following conditions : Leaving chilled water temp.-5 (23.0 F), entering chilled water temp.-2 (28.4 F), and outdoor air temp. 35 DB(95 FDB).*2 The following safety devices are equipped as standard. • High pressure protector. • Low pressure protector. • Compressor thermal protector. • Fusible plug. • Reverse-phase protector. • Overheat protection of discharge gas. • Overcurrent relay(compressor). • Freeze-up protection thermostat. • Overcurrent relay(fan). • Safety valve.*3 The unit is equipped with standard water filter.*4 This product is manufactured in China.
3701,263,000 105
2,328
45+60 2
3,440121,4321.0 16
2,456 7,500 2,0006,5006,719
4041,379,000 115
2,542
60 3
3,870136,6111.0 18
2,456 7,950 2,0007,0057,245
4721,611,000 134
2,970
(45+60) 2
4,300151,790(1.0 10) 2
4B Flange (100A HG20593-97)
(2,456 4,850 2,000) 24,125 24,196 2
5381,836,000 153
3,385
(60 2) 2
5,160182,148(1.0 12) 2
(2,456 5,300 2,000) 2 4,590 24,661 2
6062,068,000 172
3,813
(45 3) 2
5B Flange (125A HG20593-97)
(2,456 6,600 2,000) 2 5,500 25,691 2
6742,300,000 192
4,241
(45 2+60) 2
6,020212,506(1.0 14) 2
(2,456 7,050 2,000) 2 6,000 26,198 2
7402,525,000 210
4,656
(45+60 2) 2
6,880242,864(1.0 16) 2
(2,456 7,500 2,000) 2 6,500 26,719 2
8082,757,000 230
5,084
(60 3) 2
7,740273,222(1.0 18) 2
(2,456 7,950 2,000) 2 7,005 27,245 2
Brine Cooling Unit
79 — 242kW class
UWAP 40 — 120B Y B Z60Hz
S pecifications
kWBtu/hUSRT /min%
kW
m3/mincfmkW
mmkgkg
Model
Cooling capacity
Power supplyChilled water flow rate Capacity steps
Compressor
Evaporator typeCondenser type
CondenserFans
RefrigerantPipe connections water inlet/outletDimensions (H W D)WeightOperating weightOperation range
TypeMotor output
TypeDrive
Air flow rate
Motor output
Notes:*1 Cooling capacity is based on the following conditions : Leaving chilled water temp.-5 (23.0 F), entering chilled water temp.-2 (28.4 F), and outdoor air temp. 35 DB(95 FDB).*2 The following safety devices are equipped as standard. • High pressure protector. • Low pressure protector. • Compressor thermal protector. • Fusible plug. • Reverse-phase protector. • Overheat protection of discharge gas. • Overcurrent relay(compressor). • Freeze-up protection thermostat. • Overcurrent relay(fan). • Safety valve.*3 The unit is equipped with standard water filter.*4 This product is manufactured in China.
UWAP40BYBZ(40 )
UWAP50BYBZ(50 )
UWAP60BYBZ(60 )
UWAP100BYBZ(100 )
UWAP120BYBZ(120 )
242826,000 69
1,523
45 2
3,6053,662
79270,000 22 3 phase,60 Hz 400/440 V, 3 wires system 497 100~10-0Semi-hermetic sealed single-screw type30 1Brazing Plate type Cross fin coil Propeller Direct drive81028,5930.5 4R-407C
3B Flange (80A HG20593-97)
2,456 2,200 2,0001,6901,723ambient temp. 0 to 43, Brine temp. -10 to 16
94321,000 27
591
37 1
1,01035,6531.0 4
1,8101,846
121413,000 34
761
45 1
1,8701,910
188642,000 53
1,183
37 2
2,02071,3061.0 8
4B Flange (100A HG20593-97)
2,456 4,400 2,0003,5003,551
S pecifications
kWBtu/hUSRT
/min%
kW
m3/mincfmkW
mmkgkg
Model
Cooling capacity
Power supplyChilled water flow rate Capacity steps
Compressor
Evaporator typeCondenser type
Condenserfan
RefrigerantPipe connections water inlet/outletDimensions (H W D)WeightOperating weightOperation range
TypeMotor output
TypeDrive
Air flow rate
Motor output
UWA40AY1(40 )
UWA50AY1(50 )
UWA60AY1(60 )
UWA80AYAY1(80 )
UWA100AY1(100 )
UWA120AY1(120 )
UWA180AY1(180 )
106362,000303 phase, 50 Hz 380/400/415 V, 4 wires system304100~10-0 (continuous capacity control)Semi-hermetic sealed single-screw type30 1Blazing Plate typeCross fin coilPropellerDirect drive70024,7100.5 4R-22
3B Flange (80A HG20593-97)
2,395 2,200 2,000 1,5001,517-5 to 43
132450,00038
378
37 1
71025,0630.8 4
1,6501,670
160546,00046
459
45 1
84029,6521.2 4
1,7501,773
265904,00075
760
37 2
1,42050,1260.8 8
4B Flange (100A HG20593-97)
2,395 4,400 2,0003,3003,336
3201,092,00091
917
45 2
1,68059,3041.2 8
3,5003,542
3701,263,000105
1,061
45+60
1,78062,834
3,6203,684
4201,433,000119
1,204
60 2
1,88066,364
3,6403,704
4801,638,000137
1,376
45 3
2,52088,9561.2 12
5B Flange (125A HG20593-97)2,460 6,600 2,0005,6055,670
UWA140AY1(140 )
UWA160AY1(160 )
Notes:*1 Cooling capacity is based on the following conditions : Leaving chilled water temp.7 (44.5 F), entering chilled water temp.12 (53.6 F), and outdoor air temp. 35 DB(95 FDB).*2 The following safety devices are equipped as standard. • High pressure protector. • Low pressure protector. • Compressor thermal protector. • Fusible plug. • Reverse-phase protector. • Overheat protection of discharge gas. • Overcurrent relay(compressor). • Freeze-up protection thermostat. • Overcurrent relay(fan). • Safety valve.*3 Standard for the max. chilled water pressure is 0.7MPa, but1.6MPa is available if required.*4 Installation/operating weight includes the weight of refrigerant and refrigerant oil(charged before delivery).
210717,00060
602
60 1
94033,182
1,8201,852
*1
106 — 480kW class
UWA40 — 180AY 1Standard Unit
50Hz
Air Cooled Water Chillers
Air
Coo
led
Wat
er C
hill
ers
Air
Coo
led
Wat
er C
hill
ers
13 14
UWAP40BY1UWAP40BYB
UWAP50BY1UWAP50BYB
UWAP60BY1UWAP60BYB UWAP80BY1 UWAP100BY1
UWAP100BYBUWAP120BY1
UWAP120BYB UWAP140BY1 UWAP160BY1 UWAP180BY1
Model
Remote controllerCommunication I/F P.C. boardCommunication I/F P.C. B storage boxTransmission wireCentral remote controllerUnified ON/OFF controllerSchedule timer
BRC307C50BRP66B3 1BRP66A97 1(external)BER66A5 1DCS302CA61DCS301BA61DST301BA61
BRP66A100 1(internal)BER66A7 1
Not required (S.Box installed)
UWAP75AY3 UWAP125AY3 UWAP190AY3 UWAP250AY3 UWAP375AY3 UWAP500AY3 UWAP630AY3 UWAP750AY3*1
*1*1*1
Model
Remote controllerChilling water supply interrupting relayWater high pressure (1.6 MPa) upgraderIPUDio unitD Air unitInterface for use in LONWORKS
Interface for use in BACnetCentral remote controllerUnified ON/OFF controllerSchedule timer
BRC307D503GWEL-UWYP40BGWP-UWYP40BDAM602A5DEC102ADAM101ADMS504B51DMS502A51DCS302CA61DCS301BA61DST301BA61
GWP-UWYP80BGWEL-UWYP100BGWP-UWYP100B
GWEL-UWYP180BGWP-UWYP180B
UWAP200BY1 UWAP220BY1 UWAP240BY1 UWAP280BY1 UWAP320BY1 UWAP360BY1 UWAP400BY1 UWAP440BY1 UWAP480BY1Model
Remote controllerChilling water supply interrupting relayWater high pressure (1.6 MPa) upgraderIPUDio unitD Air unitInterface for use in LONWORKS
Interface for use in BACnetCentral remote controllerUnified ON/OFF controllerSchedule timer
BRC307D503GWEL-UWYP180BGWP-UWYP180BDAM602A5DEC102ADAM101ADMS504B51DMS502A51DCS302CA61DCS301BA61DST301BA61
GWEL-UWYP280BGWP-UWYP280B
GWEL-UWYP360BGWP-UWYP360B
Notes:*1 Communication I/F P.C. board, Communication I/F P.C. B storage box and Transmission wire are also required.
Model
Remote controller *1Communication I/F P.C. boardCommunication I/F P.C. B storage boxTransmission wire
UWAXP125AY1
UWA40AY1UWA40AYB
UWA50AY1UWA50AYB
UWA60AY1UWA60AYB UWA80AY1 UWA100AY1
UWA100AYBUWA120AY1UWA120AYB UWA140AY1 UWA160AY1 UWA180AY1
UWAXP190AY1 UWAXP250AY1 UWAXP375AY1 UWAXP500AY1 UWAXP630AY1 UWAXP750AY1BRC307C50BRP66B3 1— BER66A5
BPR66A97BER66A6
—BER66A7
BRP66B3 2BRP66A96BER66A8
Model
Remote controllerChilling water supply interrupting relayWater high pressure (1.6 MPa) upgraderIPUDio unitD Air unitInterface for use in LONWORKS
Interface for use in BACnetCentral remote controllerUnified ON/OFF controllerSchedule timer
Model
Remote controllerChilling water supply interrupting relayWater high pressure (1.6 MPa) upgraderIPUDio unitD Air unitInterface for use in LONWORKS
Interface for use in BACnetCentral remote controllerUnified ON/OFF controllerSchedule timer
UWA200AY1 UWA220AY1 UWA240AY1 UWA280AY1 UWA320AY1 UWA360AY1 UWA400AY1 UWA440AY1 UWA480AY1
BRC307D503GWEL-UWY40AGWP-UWY40ADAM602A5DEC102ADAM101ADMS504B51DMS502A51DCS302CA61DCS301BA61DST301BA61
BRC307D503GWEL-UWY180AGWP-UWY180ADAM602A5DEC102ADAM101ADMS504B51DMS502A51DCS302CA61DCS301BA61DST301BA61
GWEL-UWY80A GWP-UWY80A GWP-UWY100A
GWEL-UWY180AGWP-UWY180A
GWEL-UWY280AGWEL-UWY281A
GWEL-UWY360AGWP-UWY360A
Notes: *1 Communication I/F P.C. board, Communication I/F P.C. B storage box and Transmission waire are also required.
Option L is t
S pecifications
kWBtu/hUSRT /min%
kW
m3/mincfmkW
mmkgkg
Model
Cooling capacity
Power supplyChilled water flow rate Capacity steps
Compressor
Evaporator typeCondenser type
Condenserfan
Refrigerant
Pipe connections water inlet/outlet
Dimensions (H W D)WeightOperating weightOperation range
TypeMotor output
TypeDrive
Air flow rate
Motor output
Notes:*1 Cooling capacity is based on the following conditions : Leaving chilled water temp.7 (44.5 F), entering chilled water temp.12 (53.6 F), and outdoor air temp. 35 DB(95 FDB).*2 The following safety devices are equipped as standard. • High pressure protector. • Low pressure protector. • Compressor thermal protector. • Fusible plug. • Reverse-phase protector. • Overheat protection of discharge gas. • Overcurrent relay(compressor). • Freeze-up protection thermostat. • Overcurrent relay(fan). • Safety valve.*3 The unit is equipped with standard water filter.*4 The limited length of wire represents its max. length when the pressure is lower than 2%.*5 This product is manufactured in China.
*1
118 — 355kW class
UWA40 — 120AY BStandard Unit
60Hz
UWA120AYB(120 )
UWA100AYB(100 )
UWA60AYB(60 )
UWA50AYB(50 )
UWA40AYB(40 )
118403,000343 phase, 60 Hz 400/440 V, 4 wires system 338100~10-0 (continuous capacity control)Semi-hermetic sealed single-screw type30 1Blazing Plate typeCross fin coilPropellerDirect drive80028,2400.5 4R-22
3B Flange (80A)
2,395 2,200 2,0001,5001,517-5 to 43
150512,00043
430
37 1
81028,5930.8 4
1,6501,670
180614,00051
516
45 1
94033,1821.2 4
1,7501,773
3001,024,00085
860
37 2
1,62057,1860.8 8
4B Flange (100A)
2,395 4,400 2,0003,3003,336
3551,212,000101
1,018
45 2
1,88066,3641.2 8
3,5003,542
S pecifications
kWBtu/hUSRT
/min%
kW
m3/mincfmkW
mm
kgkg
Model
Cooling capacity
Power supplyChilled water flow rate Capacity steps
Compressor
Evaporator typeCondenser type
Condenserfan
RefrigerantPipe connections water inlet/outlet
Dimensions (H W D)
WeightOperating weightOperation range
TypeMotor output
TypeDrive
Air flow rate
Motor output
UWA200AY1(200 )
UWA220AY1(220 )
UWA240AY1(240 )
UWA280AY1(280 )
UWA320AY1(320 )
UWA360AY1(360 )
UWA480AY1(480 )
5301,809,0001513 phase, 50 Hz 380/400/415 V, 4 wires system1,519100~10-0 (continuous capacity control)Semi-hermetic sealed single-screw type45 2+60Blazing Plate typeCross fin coilPropellerDirect drive2,62092,4861.2 12R-22
5B Flange (125A HG20593-97)
2,460 6,600 2,000
5,6605,737-5 to 43
5801,979,000165
1,663
45+60 2
2,72096,016
5,6955,782
6302,150,000179
1,806
60 3
2,82099,546
5,7505,850
8402,867,000239
2,408
(60 2) 2
3.760132,728
3,640 23,704 2
9603,276,000273
2,752
(45 3) 2
5,040177,912(1.2 12) 2
5B Flange (125A HG20593-97)
(2,460 6,600 2,000) 2
5,605 25,670 2
1,0603,617,000301
3,039
(45 2+60) 2
5,240184,972
5,660 25,737 2
1,1603,959,000330
3,325
(45+60 2) 2
5,440192,032
5,695 25,782 2
1,2604,300,000358
3,612
(60 3) 2
5,640199,092
5,750 25,850 2
UWA400AY1(400 )
UWA440AY1(440 )
Notes:*1 Cooling capacity is based on the following conditions : Leaving chilled water temp.7 (44.5 F), entering chilled water temp.12 (53.6 F), and outdoor air temp. 35 DB(95 FDB).*2 The following safety devices are equipped as standard. • High pressure protector. • Low pressure protector. • Compressor thermal protector. • Fusible plug. • Reverse-phase protector. • Overheat protection of discharge gas. • Overcurrent relay(compressor). • Freeze-up protection thermostat. • Overcurrent relay(fan). • Safety valve.*3 Standard for the max. chilled water pressure is 0.7MPa, but1.6MPa is available if required.*4 Installation/operating weight includes the weight of refrigerant and refrigerant oil(charged before delivery).
7402,525,000210
2,121
(45+60) 2
3,560125,668(1.2 8) 2
4B Flange (100A HG20593-97)
(2,395 4,400 2,000) 2
3,620 23,684 2
*1
530 — 1,260kW class
UWA200 — 480AY 1Standard Unit
50Hz
Air
Coo
led
Wat
er C
hill
ers
Air
Coo
led
Wat
er C
hill
ers
15 16
Air Cooled Water Chillers
UWAP40BY1UWAP40BYB
UWAP50BY1UWAP50BYB
UWAP60BY1UWAP60BYB UWAP80BY1 UWAP100BY1
UWAP100BYBUWAP120BY1
UWAP120BYB UWAP140BY1 UWAP160BY1 UWAP180BY1
Model
Remote controllerCommunication I/F P.C. boardCommunication I/F P.C. B storage boxTransmission wireCentral remote controllerUnified ON/OFF controllerSchedule timer
BRC307C50BRP66B3 1BRP66A97 1(external)BER66A5 1DCS302CA61DCS301BA61DST301BA61
BRP66A100 1(internal)BER66A7 1
Not required (S.Box installed)
UWAP75AY3 UWAP125AY3 UWAP190AY3 UWAP250AY3 UWAP375AY3 UWAP500AY3 UWAP630AY3 UWAP750AY3*1
*1*1*1
Model
Remote controllerChilling water supply interrupting relayWater high pressure (1.6 MPa) upgraderIPUDio unitD Air unitInterface for use in LONWORKS
Interface for use in BACnetCentral remote controllerUnified ON/OFF controllerSchedule timer
BRC307D503GWEL-UWYP40BGWP-UWYP40BDAM602A5DEC102ADAM101ADMS504B51DMS502A51DCS302CA61DCS301BA61DST301BA61
GWP-UWYP80BGWEL-UWYP100BGWP-UWYP100B
GWEL-UWYP180BGWP-UWYP180B
UWAP200BY1 UWAP220BY1 UWAP240BY1 UWAP280BY1 UWAP320BY1 UWAP360BY1 UWAP400BY1 UWAP440BY1 UWAP480BY1Model
Remote controllerChilling water supply interrupting relayWater high pressure (1.6 MPa) upgraderIPUDio unitD Air unitInterface for use in LONWORKS
Interface for use in BACnetCentral remote controllerUnified ON/OFF controllerSchedule timer
BRC307D503GWEL-UWYP180BGWP-UWYP180BDAM602A5DEC102ADAM101ADMS504B51DMS502A51DCS302CA61DCS301BA61DST301BA61
GWEL-UWYP280BGWP-UWYP280B
GWEL-UWYP360BGWP-UWYP360B
Notes:*1 Communication I/F P.C. board, Communication I/F P.C. B storage box and Transmission wire are also required.
Model
Remote controller *1Communication I/F P.C. boardCommunication I/F P.C. B storage boxTransmission wire
UWAXP125AY1
UWA40AY1UWA40AYB
UWA50AY1UWA50AYB
UWA60AY1UWA60AYB UWA80AY1 UWA100AY1
UWA100AYBUWA120AY1UWA120AYB UWA140AY1 UWA160AY1 UWA180AY1
UWAXP190AY1 UWAXP250AY1 UWAXP375AY1 UWAXP500AY1 UWAXP630AY1 UWAXP750AY1BRC307C50BRP66B3 1— BER66A5
BPR66A97BER66A6
—BER66A7
BRP66B3 2BRP66A96BER66A8
Model
Remote controllerChilling water supply interrupting relayWater high pressure (1.6 MPa) upgraderIPUDio unitD Air unitInterface for use in LONWORKS
Interface for use in BACnetCentral remote controllerUnified ON/OFF controllerSchedule timer
Model
Remote controllerChilling water supply interrupting relayWater high pressure (1.6 MPa) upgraderIPUDio unitD Air unitInterface for use in LONWORKS
Interface for use in BACnetCentral remote controllerUnified ON/OFF controllerSchedule timer
UWA200AY1 UWA220AY1 UWA240AY1 UWA280AY1 UWA320AY1 UWA360AY1 UWA400AY1 UWA440AY1 UWA480AY1
BRC307D503GWEL-UWY40AGWP-UWY40ADAM602A5DEC102ADAM101ADMS504B51DMS502A51DCS302CA61DCS301BA61DST301BA61
BRC307D503GWEL-UWY180AGWP-UWY180ADAM602A5DEC102ADAM101ADMS504B51DMS502A51DCS302CA61DCS301BA61DST301BA61
GWEL-UWY80A GWP-UWY80A GWP-UWY100A
GWEL-UWY180AGWP-UWY180A
GWEL-UWY280AGWEL-UWY281A
GWEL-UWY360AGWP-UWY360A
Notes: *1 Communication I/F P.C. board, Communication I/F P.C. B storage box and Transmission waire are also required.
Option L is t
S pecifications
kWBtu/hUSRT /min%
kW
m3/mincfmkW
mmkgkg
Model
Cooling capacity
Power supplyChilled water flow rate Capacity steps
Compressor
Evaporator typeCondenser type
Condenserfan
Refrigerant
Pipe connections water inlet/outlet
Dimensions (H W D)WeightOperating weightOperation range
TypeMotor output
TypeDrive
Air flow rate
Motor output
Notes:*1 Cooling capacity is based on the following conditions : Leaving chilled water temp.7 (44.5 F), entering chilled water temp.12 (53.6 F), and outdoor air temp. 35 DB(95 FDB).*2 The following safety devices are equipped as standard. • High pressure protector. • Low pressure protector. • Compressor thermal protector. • Fusible plug. • Reverse-phase protector. • Overheat protection of discharge gas. • Overcurrent relay(compressor). • Freeze-up protection thermostat. • Overcurrent relay(fan). • Safety valve.*3 The unit is equipped with standard water filter.*4 The limited length of wire represents its max. length when the pressure is lower than 2%.*5 This product is manufactured in China.
*1
118 — 355kW class
UWA40 — 120AY BStandard Unit
60Hz
UWA120AYB(120 )
UWA100AYB(100 )
UWA60AYB(60 )
UWA50AYB(50 )
UWA40AYB(40 )
118403,000343 phase, 60 Hz 400/440 V, 4 wires system 338100~10-0 (continuous capacity control)Semi-hermetic sealed single-screw type30 1Blazing Plate typeCross fin coilPropellerDirect drive80028,2400.5 4R-22
3B Flange (80A)
2,395 2,200 2,0001,5001,517-5 to 43
150512,00043
430
37 1
81028,5930.8 4
1,6501,670
180614,00051
516
45 1
94033,1821.2 4
1,7501,773
3001,024,00085
860
37 2
1,62057,1860.8 8
4B Flange (100A)
2,395 4,400 2,0003,3003,336
3551,212,000101
1,018
45 2
1,88066,3641.2 8
3,5003,542
S pecifications
kWBtu/hUSRT
/min%
kW
m3/mincfmkW
mm
kgkg
Model
Cooling capacity
Power supplyChilled water flow rate Capacity steps
Compressor
Evaporator typeCondenser type
Condenserfan
RefrigerantPipe connections water inlet/outlet
Dimensions (H W D)
WeightOperating weightOperation range
TypeMotor output
TypeDrive
Air flow rate
Motor output
UWA200AY1(200 )
UWA220AY1(220 )
UWA240AY1(240 )
UWA280AY1(280 )
UWA320AY1(320 )
UWA360AY1(360 )
UWA480AY1(480 )
5301,809,0001513 phase, 50 Hz 380/400/415 V, 4 wires system1,519100~10-0 (continuous capacity control)Semi-hermetic sealed single-screw type45 2+60Blazing Plate typeCross fin coilPropellerDirect drive2,62092,4861.2 12R-22
5B Flange (125A HG20593-97)
2,460 6,600 2,000
5,6605,737-5 to 43
5801,979,000165
1,663
45+60 2
2,72096,016
5,6955,782
6302,150,000179
1,806
60 3
2,82099,546
5,7505,850
8402,867,000239
2,408
(60 2) 2
3.760132,728
3,640 23,704 2
9603,276,000273
2,752
(45 3) 2
5,040177,912(1.2 12) 2
5B Flange (125A HG20593-97)
(2,460 6,600 2,000) 2
5,605 25,670 2
1,0603,617,000301
3,039
(45 2+60) 2
5,240184,972
5,660 25,737 2
1,1603,959,000330
3,325
(45+60 2) 2
5,440192,032
5,695 25,782 2
1,2604,300,000358
3,612
(60 3) 2
5,640199,092
5,750 25,850 2
UWA400AY1(400 )
UWA440AY1(440 )
Notes:*1 Cooling capacity is based on the following conditions : Leaving chilled water temp.7 (44.5 F), entering chilled water temp.12 (53.6 F), and outdoor air temp. 35 DB(95 FDB).*2 The following safety devices are equipped as standard. • High pressure protector. • Low pressure protector. • Compressor thermal protector. • Fusible plug. • Reverse-phase protector. • Overheat protection of discharge gas. • Overcurrent relay(compressor). • Freeze-up protection thermostat. • Overcurrent relay(fan). • Safety valve.*3 Standard for the max. chilled water pressure is 0.7MPa, but1.6MPa is available if required.*4 Installation/operating weight includes the weight of refrigerant and refrigerant oil(charged before delivery).
7402,525,000210
2,121
(45+60) 2
3,560125,668(1.2 8) 2
4B Flange (100A HG20593-97)
(2,395 4,400 2,000) 2
3,620 23,684 2
*1
530 — 1,260kW class
UWA200 — 480AY 1Standard Unit
50Hz
Air
Coo
led
Wat
er C
hill
ers
Air
Coo
led
Wat
er C
hill
ers
15 16
Air Cooled Water Chillers
For High Outdoor Temperature Us e
S pecifications
Model
Cooling capacity
Power supplyChilled water flow rate
Cooling capacity
Chilled water flow rate Capacity steps
Compressor
Evaporator typeCondenser type
Condenserfan
RefrigerantPipe connections water inlet/outlet
Dimensions (H W D)
WeightOperating weightOperation range
kWBtu/hUSRT
kWBtu/hUSRT
%
kW
m3/mincfmkW
mm
kgkg
TypeMotor output
TypeDrive
Air flow rate
Motor output
UWA27JATJ(25 )
79.0269,80022.43 phase, 60 Hz, 208/230 V, 3 wires system20671.0242,00020.1185100-50-0Semi-hermetically sealed reciprocating22Dry expansion shell and Hi-X tubeCross fin coil (Waffle louver fins and Hi-X tubes)PropellerDirect drive58020,4801.7ea. 2R-22FPT2 (50A)1,765 2,025 1,06575079015 to 49
UWA32JATJ(30 )
UWA43JATJ(40 )
UWA53JATJ(50 )
UWA62JATJ(60 )
UWA70JATJ(70 )
UWA80JATJ(80 )
UWA90JATJ(90 )
UWA108JATJ(100 )
UWA122JATJ(120 )
94.3320,60026.7
24582.0280,90023.4215100-66-33-0
48016,9501.0ea. 2
1,915 2,025 1,065900970
125.0426,60035.5
326111.0378,90031.5289
30
1,16040,9601.0ea. 4
FPT2 1/2 (65A)
1,890 2,005 2,000
1,3001,3705 to 49
162.0553,50046.1
423145.0494,00041.0377100-75-50-25-0
37
1.7ea. 4
1,5401,630
185.0632,10052.6
483171.0584,10048.6466
45
1,40049,4302.5ea. 4
FPT3 (80A)
1,6101,700
212.0722,20060.0
552191.0653,10054.2497100-83-66-50-33-0
26 2
1,92067,8001.0ea. 8
4B Flange (JIS16K)(100A)1,745 2,005 4,0002,5002,60015 to 49
253.0865,00072.0
661219.0746,40062.1570
30 2
1,915 2,005 4,000
2,6002,730
274.0936,40078.0
715248.0845,20070.4645100-88-75-63-50-25-0
2,8502,980
324.01,107,00092.2
845285.0972,20081.0742
37 2
2,32081,9201.7ea. 8
5B Flange (JIS16K)(125A)
2,8703,000
370.01,262,000105.0
964335.01,145,00095.3873
45 2
2,80098,8702.5ea. 8
3,0503,210
Notes:*1 Cooling capacity is based on the following conditions : Leaving chilled water temp.6.7 (44 F), entering chilled water temp.12.2 (54 F), and outdoor air temp. 35 DB(95 FDB).*2 Cooling capacity is based on the following conditions : Leaving chilled water temp.6.7 (44 F), entering chilled water temp.12.2 (54 F), and outdoor air temp. 46 DB(115 FDB).*3 The following safety devices are equipped as standard. • High/low pressure switch. • Oil pressure control switch. • Compressor thermal protector. • Recycling guard timer.
• Crankcase heater. • 3-element overcurrent relay for compressors and fan motors. • Freeze-up protection thermostat. • Fusible plug. • Safety valve(for UWA53, 62, 90, 108, 122JATJ).
*4 This product is manufactured in Japan.
*1
*2
79 — 370kW class
UWA27 — 122J ATJFor High Outdoor Temperature Use
60Hz
S pecifications
Model
Cooling capacity
Power supplyChilled water flow rate
Compressor
Evaporator type
Condenser type
Condenserfan
RefrigerantPipe connections water inlet/outletDimensions (H W D)Weight Operation range
TypeMotor output
TypeDrive
Air flow rate
Motor output
kWBtu/hUSRT
kW
m3/mincfmkW
mmkg
351.61,201,50099.93 phase, 50 Hz 380/400/415 V, 4 wires system100-83-67-50-33-17-0Semi-hermetic sealed reciprocating30 3
Dry expansion shell and Hi-X tubes
Cross fin coil (Waffle louver fins and Hi-X tubes)PropellerDirect drive2,58091,1000.9ea. 12R-225B Flange (JIS16K)(125A)2,095 2,005 5,7004,3605 to 49
404.41,380,800115.0
37 3
3,000105,900
4,470
474.71,620,600135.0
45 3
3,720131,4001.5ea. 12
4,660
562.81,921,500160.0
100-88-75-63-50-25-0
37 4
Dry expansion shell and corrugated tubes
4,000141,3000.9ea. 16
2,075 2,005 8,0006,110
667.92,280,400189.9
45 4
4,960175,2001.5ea. 16
6,340
791.02,700,800224.7
100-83-67-50-33-17-0
37 6Dry expansion shell and Hi-X tubes
6,000211,9000.9ea. 24
2,095 2,005 11,400 8,940
UWA270JY1(300 )UWA228JY1(240 )UWA192JY1(200 )UWA162JY1(180 )UWA138JY1(150 )UWA120JY1(130 )
Notes:*1 Cooling capacity is based on the following conditions : Leaving chilled water temp.6.7 (44 F), entering chilled water temp.12.2 (54 F), and outdoor air temp. 35 DB(95 FDB).*2 The following safety devices are equipped as standard. • High pressure switch. • Low pressure switch. • Oil pressure control switch. • Compressor thermal protector. • Recycling
guard timer. • Crankcase heater. • 3-element overcurrent relay (Compressor, Fan motors). • Freeze-up protection thermostat. • Fusible plug. • Safety valve (except for UWA120JY1).*3 This product is manufactured in Japan.
*1
351.6 — 791kW class
UWA120 — 270J Y 1For High Outdoor Temperature Use
50Hz
S pecifications
Model
Cooling capacity
Power supplyChilled water flow rate
Cooling capacity
Chilled water flow rateCapacity steps
Compressor
Evaporator typeCondenser type
Condenserfan
RefrigerantPipe connections water inlet/outletDimensions (H W D)WeightOperating weightOperation range
TypeMotor output
TypeDrive
Air flow rate
Motor output
108.4369,80030.83 phase, 50 Hz 380/400/415 V, 4 wires system28297.4332,50027.7279100-66-33-0Semi-hermetically sealed reciprocating30Dry expansion shell and Hi-X tubeCross fin coil (Waffle louver fins and Hi-X tubes)PropellerDirect drive86030,3700.9ea. 4R-22
FPT2 1/2 (65A)
1,720 2,005 2,0001,2301,3005 to 52
137.2468,20039.0
358124.8425,80035.4325100-75-50-25-0
37
1,00035,310
1,890 2,005 2,0001,4201,490
161.3550,40045.8
420149.9511,50042.6391
45
1,24043,7901.5ea. 4
FPT3 (80A)
1,5201,610
186.0634,90052.9
485167.4571,40047.6436100-83-66-50-33-0
1,72060,7300.9ea. 8
1,745 2,005 4,0002,5002,600
219.1747,60062.3
571197.1672,60056.0514
30 2
4B Flange (JIS16K)(100A)
2,6002,730
250.6855,10071.2
653225.5769,40064.1588100-88-75-63-50-25-0
2,00070,620
1,915 2,005 4,0002,8502,980
272.7930,50077.5
711250.8855,90071.3654
37 2
2,8703,000
319.21,089,20090.7
832290.5991,20082.6757
45 2
2,48087,5801.5ea. 8
5B Flange(JIS16K)(125A)
3,0503,210
Notes:*1 Cooling capacity is based on the following conditions : Leaving chilled water temp.6.7 (44 F), entering chilled water temp.12.2 (54 F), and outdoor air temp. 35 DB(95 FDB).*2 Cooling capacity is based on the following conditions : Leaving chilled water temp.6.7 (44 F), entering chilled water temp.12.2 (54 F), and outdoor air temp. 46 DB(115 FDB).*3 The following safety devices are equipped as standard. • High/low pressure switch. • Oil pressure control switch. • Compressor thermal protector. • Recycling guard timer.
• Crankcase heater. • 3-element overcurrent relay for compressors and fan motors. • Freeze-up prorection thermostat. • Fusible plug. • Safety valve(for UWA47, 55, 93, 109JAY1).*4 This product is manufactured in Japan.
UWA37JAY1(40 )
UWA47JAY1(50 )
UWA55JAY1(60 )
UWA63JAY1(70 )
UWA75JAY1(80 )
UWA80JAY1(90 )
UWA93JAY1(100 )
*1
*2
kWBtu/hUSRT
kWBtu/hUSRT
%
kW
m3/mincfmkW
mmkgkg
UWA109JAY1(120 )
108.4 — 319.2kW class
UWA37 — 109J AY 1For High Outdoor Temperature Use
50Hz
UWA55J AY 1 UWA138J Y 1 UWA80J ATJ
P rovides a s table supply of chilled water even when the outdoor temperature is as high as 49 .
C apacity can be controlled in multiple steps of between 3 and 7 for efficient energy use.
Full Lineup Includes Models with Capacities Ranging from 79 — 791kW.
Equipped with a Compact and Powerful Semi-hermetically Sealed Reciprocating Compressor.
: UWA S eries
UWA37J AY 1 — 109J AY 1UWA120J Y 1 — 270J Y 1U W A27J AT J / 32J AT J , 70J AT J — 122J AT JUWA43J ATJ — 62J ATJ
5 to 525 to 49
15 to 495 to 49
Wide Operating RangeTemperature range by model.
Wide Capacity RangeUWA37J AY 1 — 109J AY 1UWA43J ATJ — 122J ATJUWA120J Y 1 — 270J Y 1
A selector switch makes it possible to operate only one refrig-erant circuit while the other is under repair.
Two Independent Refrigerant CircuitsUWA63J AY 1 — 10 9J AY 1UWA70J ATJ — 122 J ATJUWA120J Y 1 — 270 J Y 1
Air Cooled Water Chillers
Air
Coo
led
Wat
er C
hill
ers
Air
Coo
led
Wat
er C
hill
ers
1718
For High Outdoor Temperature Us e
S pecifications
Model
Cooling capacity
Power supplyChilled water flow rate
Cooling capacity
Chilled water flow rate Capacity steps
Compressor
Evaporator typeCondenser type
Condenserfan
RefrigerantPipe connections water inlet/outlet
Dimensions (H W D)
WeightOperating weightOperation range
kWBtu/hUSRT
kWBtu/hUSRT
%
kW
m3/mincfmkW
mm
kgkg
TypeMotor output
TypeDrive
Air flow rate
Motor output
UWA27JATJ(25 )
79.0269,80022.43 phase, 60 Hz, 208/230 V, 3 wires system20671.0242,00020.1185100-50-0Semi-hermetically sealed reciprocating22Dry expansion shell and Hi-X tubeCross fin coil (Waffle louver fins and Hi-X tubes)PropellerDirect drive58020,4801.7ea. 2R-22FPT2 (50A)1,765 2,025 1,06575079015 to 49
UWA32JATJ(30 )
UWA43JATJ(40 )
UWA53JATJ(50 )
UWA62JATJ(60 )
UWA70JATJ(70 )
UWA80JATJ(80 )
UWA90JATJ(90 )
UWA108JATJ(100 )
UWA122JATJ(120 )
94.3320,60026.7
24582.0280,90023.4215100-66-33-0
48016,9501.0ea. 2
1,915 2,025 1,065900970
125.0426,60035.5
326111.0378,90031.5289
30
1,16040,9601.0ea. 4
FPT2 1/2 (65A)
1,890 2,005 2,000
1,3001,3705 to 49
162.0553,50046.1
423145.0494,00041.0377100-75-50-25-0
37
1.7ea. 4
1,5401,630
185.0632,10052.6
483171.0584,10048.6466
45
1,40049,4302.5ea. 4
FPT3 (80A)
1,6101,700
212.0722,20060.0
552191.0653,10054.2497100-83-66-50-33-0
26 2
1,92067,8001.0ea. 8
4B Flange (JIS16K)(100A)1,745 2,005 4,0002,5002,60015 to 49
253.0865,00072.0
661219.0746,40062.1570
30 2
1,915 2,005 4,000
2,6002,730
274.0936,40078.0
715248.0845,20070.4645100-88-75-63-50-25-0
2,8502,980
324.01,107,00092.2
845285.0972,20081.0742
37 2
2,32081,9201.7ea. 8
5B Flange (JIS16K)(125A)
2,8703,000
370.01,262,000105.0
964335.01,145,00095.3873
45 2
2,80098,8702.5ea. 8
3,0503,210
Notes:*1 Cooling capacity is based on the following conditions : Leaving chilled water temp.6.7 (44 F), entering chilled water temp.12.2 (54 F), and outdoor air temp. 35 DB(95 FDB).*2 Cooling capacity is based on the following conditions : Leaving chilled water temp.6.7 (44 F), entering chilled water temp.12.2 (54 F), and outdoor air temp. 46 DB(115 FDB).*3 The following safety devices are equipped as standard. • High/low pressure switch. • Oil pressure control switch. • Compressor thermal protector. • Recycling guard timer.
• Crankcase heater. • 3-element overcurrent relay for compressors and fan motors. • Freeze-up protection thermostat. • Fusible plug. • Safety valve(for UWA53, 62, 90, 108, 122JATJ).
*4 This product is manufactured in Japan.
*1
*2
79 — 370kW class
UWA27 — 122J ATJFor High Outdoor Temperature Use
60Hz
S pecifications
Model
Cooling capacity
Power supplyChilled water flow rate
Compressor
Evaporator type
Condenser type
Condenserfan
RefrigerantPipe connections water inlet/outletDimensions (H W D)Weight Operation range
TypeMotor output
TypeDrive
Air flow rate
Motor output
kWBtu/hUSRT
kW
m3/mincfmkW
mmkg
351.61,201,50099.93 phase, 50 Hz 380/400/415 V, 4 wires system100-83-67-50-33-17-0Semi-hermetic sealed reciprocating30 3
Dry expansion shell and Hi-X tubes
Cross fin coil (Waffle louver fins and Hi-X tubes)PropellerDirect drive2,58091,1000.9ea. 12R-225B Flange (JIS16K)(125A)2,095 2,005 5,7004,3605 to 49
404.41,380,800115.0
37 3
3,000105,900
4,470
474.71,620,600135.0
45 3
3,720131,4001.5ea. 12
4,660
562.81,921,500160.0
100-88-75-63-50-25-0
37 4
Dry expansion shell and corrugated tubes
4,000141,3000.9ea. 16
2,075 2,005 8,0006,110
667.92,280,400189.9
45 4
4,960175,2001.5ea. 16
6,340
791.02,700,800224.7
100-83-67-50-33-17-0
37 6Dry expansion shell and Hi-X tubes
6,000211,9000.9ea. 24
2,095 2,005 11,400 8,940
UWA270JY1(300 )UWA228JY1(240 )UWA192JY1(200 )UWA162JY1(180 )UWA138JY1(150 )UWA120JY1(130 )
Notes:*1 Cooling capacity is based on the following conditions : Leaving chilled water temp.6.7 (44 F), entering chilled water temp.12.2 (54 F), and outdoor air temp. 35 DB(95 FDB).*2 The following safety devices are equipped as standard. • High pressure switch. • Low pressure switch. • Oil pressure control switch. • Compressor thermal protector. • Recycling
guard timer. • Crankcase heater. • 3-element overcurrent relay (Compressor, Fan motors). • Freeze-up protection thermostat. • Fusible plug. • Safety valve (except for UWA120JY1).*3 This product is manufactured in Japan.
*1
351.6 — 791kW class
UWA120 — 270J Y 1For High Outdoor Temperature Use
50Hz
S pecifications
Model
Cooling capacity
Power supplyChilled water flow rate
Cooling capacity
Chilled water flow rateCapacity steps
Compressor
Evaporator typeCondenser type
Condenserfan
RefrigerantPipe connections water inlet/outletDimensions (H W D)WeightOperating weightOperation range
TypeMotor output
TypeDrive
Air flow rate
Motor output
108.4369,80030.83 phase, 50 Hz 380/400/415 V, 4 wires system28297.4332,50027.7279100-66-33-0Semi-hermetically sealed reciprocating30Dry expansion shell and Hi-X tubeCross fin coil (Waffle louver fins and Hi-X tubes)PropellerDirect drive86030,3700.9ea. 4R-22
FPT2 1/2 (65A)
1,720 2,005 2,0001,2301,3005 to 52
137.2468,20039.0
358124.8425,80035.4325100-75-50-25-0
37
1,00035,310
1,890 2,005 2,0001,4201,490
161.3550,40045.8
420149.9511,50042.6391
45
1,24043,7901.5ea. 4
FPT3 (80A)
1,5201,610
186.0634,90052.9
485167.4571,40047.6436100-83-66-50-33-0
1,72060,7300.9ea. 8
1,745 2,005 4,0002,5002,600
219.1747,60062.3
571197.1672,60056.0514
30 2
4B Flange (JIS16K)(100A)
2,6002,730
250.6855,10071.2
653225.5769,40064.1588100-88-75-63-50-25-0
2,00070,620
1,915 2,005 4,0002,8502,980
272.7930,50077.5
711250.8855,90071.3654
37 2
2,8703,000
319.21,089,20090.7
832290.5991,20082.6757
45 2
2,48087,5801.5ea. 8
5B Flange(JIS16K)(125A)
3,0503,210
Notes:*1 Cooling capacity is based on the following conditions : Leaving chilled water temp.6.7 (44 F), entering chilled water temp.12.2 (54 F), and outdoor air temp. 35 DB(95 FDB).*2 Cooling capacity is based on the following conditions : Leaving chilled water temp.6.7 (44 F), entering chilled water temp.12.2 (54 F), and outdoor air temp. 46 DB(115 FDB).*3 The following safety devices are equipped as standard. • High/low pressure switch. • Oil pressure control switch. • Compressor thermal protector. • Recycling guard timer.
• Crankcase heater. • 3-element overcurrent relay for compressors and fan motors. • Freeze-up prorection thermostat. • Fusible plug. • Safety valve(for UWA47, 55, 93, 109JAY1).*4 This product is manufactured in Japan.
UWA37JAY1(40 )
UWA47JAY1(50 )
UWA55JAY1(60 )
UWA63JAY1(70 )
UWA75JAY1(80 )
UWA80JAY1(90 )
UWA93JAY1(100 )
*1
*2
kWBtu/hUSRT
kWBtu/hUSRT
%
kW
m3/mincfmkW
mmkgkg
UWA109JAY1(120 )
108.4 — 319.2kW class
UWA37 — 109J AY 1For High Outdoor Temperature Use
50Hz
UWA55J AY 1 UWA138J Y 1 UWA80J ATJ
P rovides a s table supply of chilled water even when the outdoor temperature is as high as 49 .
C apacity can be controlled in multiple steps of between 3 and 7 for efficient energy use.
Full Lineup Includes Models with Capacities Ranging from 79 — 791kW.
Equipped with a Compact and Powerful Semi-hermetically Sealed Reciprocating Compressor.
: UWA S eries
UWA37J AY 1 — 109J AY 1UWA120J Y 1 — 270J Y 1U W A27J AT J / 32J AT J , 70J AT J — 122J AT JUWA43J ATJ — 62J ATJ
5 to 525 to 49
15 to 495 to 49
Wide Operating RangeTemperature range by model.
Wide Capacity RangeUWA37J AY 1 — 109J AY 1UWA43J ATJ — 122J ATJUWA120J Y 1 — 270J Y 1
A selector switch makes it possible to operate only one refrig-erant circuit while the other is under repair.
Two Independent Refrigerant CircuitsUWA63J AY 1 — 10 9J AY 1UWA70J ATJ — 122 J ATJUWA120J Y 1 — 270 J Y 1
Air Cooled Water Chillers
Air
Coo
led
Wat
er C
hill
ers
Air
Coo
led
Wat
er C
hill
ers
1718
19 20
Air
Coo
led
Wat
er C
hill
ers
- Hea
t Pum
p Ty
pe
Air
Coo
led
Wat
er C
hill
ers
- Hea
t Pum
p Ty
pe
Low Power Consumption
C ontinuous capacity control with a range from 10(12)% to 100% helps to reduce energy wastage during low-load
UWY P 40 — 160B Y 1 UWY P 40 — 120B Y BUWY 40 — 120AY 1 UWY 40 — 120AY B
UWY P 40 — 160B Y 1 UWY P 40 — 120B Y B
UWA40 — 160AY 1 UWA40 — 120AY B
High Precision
10
9
8
7
Upper Limit S ignal
Water Temp. ( )
E xample of Outlet Water Temperature C ontrol
If outlet water temperature rises above the upper limit s ignal, the load starts to increase in 10% increments
As the temperature falls below the upper limit s ignal, the load increase increments are reduced to 5% .
As the temperature falls below the set value, the load increase increments remain at 5% .
When changes in outlet water temperature become 1 or less , the thermostat is turned off.
Value S et
The outlet water temperature is precisely controlled to within 0.5 (with a s table load) through the use of electric expansion
: UW Y P S eries : UW Y S eries
New RefrigerantUWY P 125 — 750AY 3 UWY P 40 — 480B Y 1UWY P 40 — 120B Y B
E mploys the new refrigerant R -407C .
Efficient and Reliable Compressors
To improve their operational reliability, 40 -- 480HP models are equipped with semi-hermetic s ingle screw compressors .
Applies to All Models
R efrigerant inlet
R efrigerant outlet
S emi-hermetic s ingle screw compressor
UWY P 40 — 160B Y 1 UWY P 40 — 120B Y B
UWY 40 — 160AY 1 UWY 40 — 120AY B
UWY P 100 — 480B Y 1 UWY P 100 — 120B Y B
Duty cycling control equalizes the operating time of the
UWY 100 — 480AY 1
UWY 40 — 160AY 1
A choice of three control systems is available.
Outflow water temperature controlProvides precise control of the water temperature.
Compressor count controlControls the number of compressors operating depending on the load.
Inflow water temperature controlPerforms duty cycling control.
UWY 100 — 120AY B
UWY P 40 — 160B Y 1UWY 40 — 480AY BUWY P 40 — 120B Y B
C ontinues operation to levels as low as 12% of total ca-pacity to provide stable wa-ter temperature control even during low-load periods .
This mode can be used to reduce power consumption if highly precise water tempera-ture control is not necessary during low- load periods . It shuts down the compressor when the load drops below 40% .
High-P rec is ion Mode Low-P ower Mode
Multiple Operating Modes
The user can select to give priority to either precis ion or reduced power consumption.
Capacity Control Mode
The maximum current level of the compressor can be specified in order to control demand for power. S ince this function allows setting of the upper limit current value, comfortable operation is maintained while effectively controlling demand. In contrast to conventional capacity control s tep limit s ys tems , maximum capacity is maintained at the des ired demand value.
C urrent Demand Func tion
Demand Mode
Users can select the operating mode that best matches the heat source application.
Note: Switching between the above modes is accomplished using a control on the outdoor unit.
Note: Water supply piping must be purchased separately. (UWYP375AY3 — 750AY3)
UWY P 40 — 480B Y 1 UWY P 40 — 120B Y B
UWY 40 — 120AY 1 UWY 40 — 120AY B
Wide Operation Range
Note: Measures to protect against drain water freezing are necessary in cold re-gions where the highest temperature stays below 0 on several consecutive days.
A new defrosting system makes poss ible heating operation even when the outdoor temperature is as low as -15 .
C apacityOutdoor Air Temperature R ange where C ooling P oss ible
Models E mploying R -407C Models E mploying R -22
5 — 30
40 — 480
-15 to 43
-5 to 43 -5 to 43
—
UWY P 40 — 480B Y 1 UWY P 40 — 120B Y B
UWY 40 — 480AY 1 UWY 40 — 120AY B
UWY P 40 — 480B Y 1 UWY P 40 — 120B Y B
UWY 40 — 480AY 1 UWY 40 — 120AY B
Applies to All Models
Refrigerant Inlet
Refrigerant Outlet
Water Outlet
Heat Exchanger with Stainless Steel Plates
S tainles s s teel heat ex-changer plates prevent rust, thereby improving their du-rability and the system's operational reliability.
ReliabilityApplies to All Models
Easy Installation
Defrosting is performed under computer control as part of continuous capacity control, resulting in s table heating performance.
The system detects ice formation by constantly monitoring the outdoor tempera-ture, the pressures of the high- and low-pressure components, and the timers. In addition, continuous capacity control allows smooth control of capacity even af-ter a rise in the pressure of the high-pressure components. Remaining ice is melted a little at a time, and stable heating performance is maintained.
The compact des ign of these units s ignificantly reduces the space required for installation.
In the outdoor unit, component parts of a small size have been used wherever possible to reduced its size and correspondingly reduce how much space it re-quires. Furthermore, replacing the 2-way refrigerant inlets with 4-way inlets has reduced the amount of space the outdoor unit needs even further.
UWY P 125 — 750AY 3The horizontal linkup des ign increases installation flexibility.
This design ensures the installation does not protrude so far, making it possible to install water chillers along a wall or under a roof overhang.
Air heat exchangers employ fins with acrylic coating for superior durability.
50/60Hz50Hz60Hz50Hz60Hz
R-407C
R-22
Standard Unit
Standard Unit
Refrigerant Units series Model No.
UWYP—AY3UWYP—BY1UWYP—BYBUWY—AY1UWY—AYB
Capacity (kW)
2121, 22
222324
page6.7/7.5
—————
11.2/12.5125————
17/19190————
22.4/25250————
33.5/37.5375————
45/50500————
56/63630————
67/75750————
106—40404040
132—50505050
160—60606060
212—80—8080
265—
100100100100
50Hz60Hz50Hz60Hz
R-407C
R-22
Standard Unit
Standard Unit
Refrigerant Units series Model No.
UWYP—BY1UWYP—BYBUWY—AY1UWY—AYB
Capacity (kW)
21, 22222324
page315120120120120
370140—
140—
420160—
160—
480180—
180—
530200—
200—
580220—
220—
630240—
240—
740280—
280—
840320—
320—
960360—
360—
1060400—
400—
1160440—
440—
1260480—
480—
Model Lineup
UWY P 750AY 3 UWY P 120B Y 1 UWY P 180B Y 1
Air Cooled Water Chillers - Heat Pump Type
19 20
Air
Coo
led
Wat
er C
hill
ers
- Hea
t Pum
p Ty
pe
Air
Coo
led
Wat
er C
hill
ers
- Hea
t Pum
p Ty
pe
Low Power Consumption
C ontinuous capacity control with a range from 10(12)% to 100% helps to reduce energy wastage during low-load
UWY P 40 — 160B Y 1 UWY P 40 — 120B Y BUWY 40 — 120AY 1 UWY 40 — 120AY B
UWY P 40 — 160B Y 1 UWY P 40 — 120B Y B
UWA40 — 160AY 1 UWA40 — 120AY B
High Precision
10
9
8
7
Upper Limit S ignal
Water Temp. ( )
E xample of Outlet Water Temperature C ontrol
If outlet water temperature rises above the upper limit s ignal, the load starts to increase in 10% increments
As the temperature falls below the upper limit s ignal, the load increase increments are reduced to 5% .
As the temperature falls below the set value, the load increase increments remain at 5% .
When changes in outlet water temperature become 1 or less , the thermostat is turned off.
Value S et
The outlet water temperature is precisely controlled to within 0.5 (with a s table load) through the use of electric expansion
: UW Y P S eries : UW Y S eries
New RefrigerantUWY P 125 — 750AY 3 UWY P 40 — 480B Y 1UWY P 40 — 120B Y B
E mploys the new refrigerant R -407C .
Efficient and Reliable Compressors
To improve their operational reliability, 40 -- 480HP models are equipped with semi-hermetic s ingle screw compressors .
Applies to All Models
R efrigerant inlet
R efrigerant outlet
S emi-hermetic s ingle screw compressor
UWY P 40 — 160B Y 1 UWY P 40 — 120B Y B
UWY 40 — 160AY 1 UWY 40 — 120AY B
UWY P 100 — 480B Y 1 UWY P 100 — 120B Y B
Duty cycling control equalizes the operating time of the
UWY 100 — 480AY 1
UWY 40 — 160AY 1
A choice of three control systems is available.
Outflow water temperature controlProvides precise control of the water temperature.
Compressor count controlControls the number of compressors operating depending on the load.
Inflow water temperature controlPerforms duty cycling control.
UWY 100 — 120AY B
UWY P 40 — 160B Y 1UWY 40 — 480AY BUWY P 40 — 120B Y B
C ontinues operation to levels as low as 12% of total ca-pacity to provide stable wa-ter temperature control even during low-load periods .
This mode can be used to reduce power consumption if highly precise water tempera-ture control is not necessary during low- load periods . It shuts down the compressor when the load drops below 40% .
High-P rec is ion Mode Low-P ower Mode
Multiple Operating Modes
The user can select to give priority to either precis ion or reduced power consumption.
Capacity Control Mode
The maximum current level of the compressor can be specified in order to control demand for power. S ince this function allows setting of the upper limit current value, comfortable operation is maintained while effectively controlling demand. In contrast to conventional capacity control s tep limit s ys tems , maximum capacity is maintained at the des ired demand value.
C urrent Demand F unc tion
Demand Mode
Users can select the operating mode that best matches the heat source application.
Note: Switching between the above modes is accomplished using a control on the outdoor unit.
Note: Water supply piping must be purchased separately. (UWYP375AY3 — 750AY3)
UWY P 40 — 480B Y 1 UWY P 40 — 120B Y B
UWY 40 — 120AY 1 UWY 40 — 120AY B
Wide Operation Range
Note: Measures to protect against drain water freezing are necessary in cold re-gions where the highest temperature stays below 0 on several consecutive days.
A new defrosting system makes poss ible heating operation even when the outdoor temperature is as low as -15 .
C apacityOutdoor Air Temperature R ange where C ooling P oss ible
Models E mploying R -407C Models E mploying R -22
5 — 30
40 — 480
-15 to 43
-5 to 43 -5 to 43
—
UWY P 40 — 480B Y 1 UWY P 40 — 120B Y B
UWY 40 — 480AY 1 UWY 40 — 120AY B
UWY P 40 — 480B Y 1 UWY P 40 — 120B Y B
UWY 40 — 480AY 1 UWY 40 — 120AY B
Applies to All Models
Refrigerant Inlet
Refrigerant Outlet
Water Outlet
Heat Exchanger with Stainless Steel Plates
S tainles s s teel heat ex-changer plates prevent rust, thereby improving their du-rability and the system's operational reliability.
ReliabilityApplies to All Models
Easy Installation
Defrosting is performed under computer control as part of continuous capacity control, resulting in s table heating performance.
The system detects ice formation by constantly monitoring the outdoor tempera-ture, the pressures of the high- and low-pressure components, and the timers. In addition, continuous capacity control allows smooth control of capacity even af-ter a rise in the pressure of the high-pressure components. Remaining ice is melted a little at a time, and stable heating performance is maintained.
The compact des ign of these units s ignificantly reduces the space required for installation.
In the outdoor unit, component parts of a small size have been used wherever possible to reduced its size and correspondingly reduce how much space it re-quires. Furthermore, replacing the 2-way refrigerant inlets with 4-way inlets has reduced the amount of space the outdoor unit needs even further.
UWY P 125 — 750AY 3The horizontal linkup des ign increases installation flexibility.
This design ensures the installation does not protrude so far, making it possible to install water chillers along a wall or under a roof overhang.
Air heat exchangers employ fins with acrylic coating for superior durability.
50/60Hz50Hz60Hz50Hz60Hz
R-407C
R-22
Standard Unit
Standard Unit
Refrigerant Units series Model No.
UWYP—AY3UWYP—BY1UWYP—BYBUWY—AY1UWY—AYB
Capacity (kW)
2121, 22
222324
page6.7/7.5
—————
11.2/12.5125————
17/19190————
22.4/25250————
33.5/37.5375————
45/50500————
56/63630————
67/75750————
106—40404040
132—50505050
160—60606060
212—80—8080
265—
100100100100
50Hz60Hz50Hz60Hz
R-407C
R-22
Standard Unit
Standard Unit
Refrigerant Units series Model No.
UWYP—BY1UWYP—BYBUWY—AY1UWY—AYB
Capacity (kW)
21, 22222324
page315120120120120
370140—
140—
420160—
160—
480180—
180—
530200—
200—
580220—
220—
630240—
240—
740280—
280—
840320—
320—
960360—
360—
1060400—
400—
1160440—
440—
1260480—
480—
Model Lineup
UWY P 750AY 3 UWY P 120B Y 1 UWY P 180B Y 1
Air Cooled Water Chillers - Heat Pump Type
Air
Coo
led
Wat
er C
hill
ers
- Hea
t Pum
p Ty
pe
Air
Coo
led
Wat
er C
hill
ers
- Hea
t Pum
p Ty
pe
530 — 1,260kW class
UWY P 200 — 480B Y 1Standard Unit
50Hz
Notes:*1 Cooling capacity is based on the following conditions : Leaving chilled water temp.7 (44.5 F), entering chilled water temp.12 (53.6 F), and outdoor air temp. 35 DB(95 FDB).*2 Heating capacity is based on the following conditions : Leaving hot water temp.45 (113 F), entering hot water temp.40 (104 F), and outdoor air temp. 7 DB(44.5 FDB),and 6 WB(43 FWB).*3 The following safety devices are equipped as standard. • High pressure protector. • Low pressure protector. • Compressor thermal protector. • Fusible plug. • Reverse-phase
protector. • Overheat protection of discharge gas. • Overcurrent relay(compressor). • Freeze-up protection thermostat. • Overcurrent relay(fan). • Safety valve.*4 The unit is equipped with standard water filter. *5 The limited length of wire represents its max. length when the pressure is lower than 2%. *6 This product is manufactured in China.
S pecifications
TypeMotor output
TypeDrive
Air flow rate
Motor output
Water inlet/outletDrain outlet
UWYP200BY1(200 )
UWYP220BY1(220 )
UWYP240BY1(240 )
UWYP280BY1(280 )
UWYP320BY1(320 )
UWYP360BY1(360 )
UWYP480BY1(480 )
UWYP400BY1(400 )
UWYP440BY1(440 )Model
Cooling capacity
Chilled water flow rate
Heating capacity
Power supplyHot water flow rateCapacity steps
Compressor
Evaporator typeCondenser type
CondenserFans
RefrigerantPipe connections Dimensions (H W D)WeightOperating weightOperation range
kWBtu/hUSRT /minkWBtu/hUSRT
/min%
kW
m3/mincfmkW
mmkgkg
5301,809,000 151 1,519 5701,945,000 162 3 phase, 50 Hz 380/400/415 V, 4 wires system 1,634 100~10-0Semi-hermetic sealed single-screw type45 2+60Brazing Plate type Cross fin coil Propeller Direct drive 3,010106,2531.0 14R-407C5B Flange (125A HG20593-97)RP1 1/4 Female screw (32A)2,456 7,050 2,000 6,8207,018cooling -5 to 43, heating -20 to 21
5801,979,000 165 1,663 6302,150,000 179
1,806
45+60 2
3,440121,4321.0 16
2,456 7,500 2,0007,5007,719
6302,150,000 179 1,806 6902,355,000 196
1,978
60 3
3,870136,6111.0 18
2,456 7,950 2,0007,8858,125
7402,525,000 210 2,121 8002,730,000 228
2,293
(45+60) 2
4,300151,790(1.0 10) 2
4B Flange (100A HG20593-97)
(2,456 4,850 2,000) 24,553 24,624 2
8402,867,000 239 2,408 9203,140,000 262
2,637
(60 2) 2
5,160182,148(1.0 12) 2
(2,456 5,300 2,000) 25,110 25,181 2
9603,276,000 273 2,752 1,0203,481,000 290
2,924
(45 3) 2
5B Flange (125A HG20593-97)
(2,456 6,600 2,000) 26,265 26,456 2
1,0603,617,000 301 3,039 1,1403,890,000 324
3,268
(45 2+60) 2
6,020212,506(1.0 14) 2
(2,456 7,050 2,000) 26,820 27,018 2
1,1603,959,000 330 3,325 1,2604,300,000 358
3,612
(45+60 2) 2
6,880242,864(1.0 16) 2
(2,456 7,500 2,000) 27,500 27,719 2
1,2604,300,000 358 3,612 1,3804,710,000 392
3,956
(60 3) 2
7,740273,222(1.0 18) 2
(2,456 7,950 2,000) 27,885 28,125 2
Notes:*1 Cooling capacity is based on the following conditions : Leaving chilled water temp.7 (44.5 F), entering chilled water temp.12 (53.6 F), and outdoor air temp. 35 DB(95 FDB).*2 Heating capacity is based on the following conditions : Leaving hot water temp.45 (113 F), entering hot water temp.40 (104 F), and outdoor air temp. 7 DB(44.5 FDB),and 6 WB(43 FWB).*3 The following safety devices are equipped as standard. • High pressure protector. • Low pressure protector. • Compressor thermal protector. • Fusible plug. • Reverse-phase
protector. • Overheat protection of discharge gas. • Overcurrent relay(compressor). • Freeze-up protection thermostat. • Overcurrent relay(fan). • Safety valve.
S pecifications
TypeMotor output
TypeDrive
Air flow rate
Motor output
Water inlet/outletDrain outlet
Model
Cooling capacity
Chilled water flow rate
Heating capacity
Power supplyHot water flow rateCapacity steps
Compressor
Evaporator typeCondenser type
CondenserFans
RefrigerantPipe connections water inlet/outlet Dimensions (H W D)WeightOperating weightOperation range
kWBtu/hUSRT /minkWBtu/hUSRT
/min%
kW
m3/mincfmkW
mmkgkg
118 — 355kW class
UWY P 40 — 120B Y BStandard Unit
60Hz
UWYP40BYB(40 )
UWYP50BYB(50 )
UWYP60BYB(60 )
UWYP100BYB(100 )
UWYP120BYB(120 )
118403,000 34 338 132450,000 38 3 phase,60 Hz 400/440 V, 3 wires system378 100~10-0Semi-hermetic sealed single-screw type30 1Brazing Plate type Cross fin coil Propeller Direct drive81028,5930.5 4 R-407C3B Flange (80A HG20593-97) RP1 1/4 Female screw (32A)2,456 2,200 2,0001,6901,723cooling -5 to 43, heating -20 to 21
150512,000 43 430 170580,000 48
487
37 1
1,01035,6531.0 4
1,8101,846
180614,000 51 516 200683,000 57
573
45 1
1,8701,910
3001,024,000 85 860 3351,143,000 95
960
37 2
2,02071,3061.0 8
4B Flange (100A HG20593-97)
2,456 4,400 2,0003,5003,551
3551,212,000 101 1,018 4001,365,000 114
1,147
45 2
3,6053,662
Notes:*1 Cooling capacity is based on the following conditions : Leaving chilled water temp.7 (44.5 F), entering chilled water temp.12 (53.6 F), and outdoor air temp. 35 DB(95 FDB).*2 Heating capacity is based on the following conditions : Leaving hot water temp.45 (113 F), entering hot water temp.40 (104 F), and outdoor air temp. 7 DB(44.5 FDB),and 6 WB(43 FWB).*3 The following safety devices are equipped as standard. • High pressure protector. • Low pressure protector. • Compressor thermal protector. • Fusible plug. • Reverse-phase
protector. • Overheat protection of discharge gas. • Overcurrent relay(compressor). • Freeze-up protection thermostat. • Overcurrent relay(fan). • Safety valve.*4 The unit is equipped with standard water filter. *5 The limited length of wire represents its max. length when the pressure is lower than 2%. *6 This product is manufactured in China.
S pecifications
TypeMotor output
TypeDrive
Air flow rate
Motor output
Water inlet/outlet
Drain outlet
UWYP40BY1(40 )
UWYP50BY1(50 )
UWYP60BY1(60 )
UWYP80BY1(80 )
UWYP100BY1(100 )
UWYP120BY1(120 )
UWYP180BY1(180 )
UWYP140BY1(140 )
UWYP160BY1(160 )Model
Cooling capacity
Chilled water flow rate
Heating capacity
Power supplyHot water flow rateCapacity steps
Compressor
Evaporator typeCondenser type
CondenserFans
Refrigerant
Pipe connections water inlet/outlet
Dimensions (H W D)WeightOperating weightOperation range
kWBtu/hUSRT /minkWBtu/hUSRT
/min%
kW
m3/mincfmkW
mmkgkg
106 — 480kW class
UWY P 40 — 180B Y 1Standard Unit
50Hz
106362,000 30 304 112382,000 32 3 phase,50 Hz 380/400/415 V, 4wires system 321100~10-0 Semi-hermetic sealed single-screw type30 1Brazing Plate type Cross fin coil Propeller Direct drive78027,5340.5 4R-407C
3B Flange (80A HG20593-97)
RP1 1/4 Female screw (32A)2,456 2,200 2,0001,8001,833cooling -5 to 43, heating -20 to 21
132450,000 38 378 140478,000 40
401
37 1
86030,3581.0 4
1,9301,966
160546,000 46 459 170580,000 48
487
45 1
1,9902,030
210717,000 60 602 230785,000 65
659
60 1
1,29045,5371.0 6
2,456 2,650 2,0002,6402,687
265904,000 75 760 280956,000 80
803
37 2
1,60056,4801.0 8
4B Flange (100A HG20593-97)
2,456 4,400 2,0003,7403,791
3151,075,000 90 9033401,160,000 97
975
45 2
1,72060,716
3,9954,052
3701,263,000 105 1,061 4001,365,000 114
1,147
45+60
2,15075,8951.0 10
2,456 4,850 2,0004,5534,624
4201,433,000 119 1,204 4601,570,000 131
1,319
60 2
2,58091,0741.0 12
2,456 5,300 2,0005,1105,181
4801,638,000 137 1,376 5101,740,000 145
1,462
45 3
5B Flange (125A HG20593-97)
2,456 6,600 2,0006,2656,456
S pecifications
11.2 / 12.5 — 67 / 75 kW class
UWY P 125 — 750AY 3Standard Unit
50/60Hz
Model
Cooling capacity(50/60 Hz)
Chilled water flow rate (50/60 Hz)
Heating capacity(50/60 Hz)
Power supplyHot water flow rate (50/60 Hz)Capacity steps
Compressor
Evaporator typeCondenser type
Fan
Refrigerant
Pipe connections water inlet/outlet
Dimensions (H W D)WeightOperating weightOperation range
TypeMotor output
TypeDriveAir flow rate(50/60 Hz)Motor output
kWBtu/hUSRT /minkWBtu/hUSRT
/min%
kW
m3/mincfmkW
mmkgkg
UWYP125AY3(5 )
UWYP190AY3(8 )
UWYP250AY3(10 )
UWYP375AY3(15 )
UWYP500AY3(20 )
UWYP630AY3(25 )
UWYP750AY3(30 )
22.4/25.076,500/85,4006.37/7.1164/7225.0/28.085,400/95,6007.11/7.96
72/80
7.5 1
175/1856,180/6,5300.22 2
260264
17.0/19.058,000/64,9004.83/5.4049/5420.0/22.468,300/76,5005.69/6.37
57/64
5.5 1
140/1604,940/5,6500.22+0.14
1 1/2B Fiange(JIS10K)(40A) 2
1,450 1,280 690258261
33.5/37.5114,000/128,0009.53/10.796/10837.5/42.5128,000/145,00010.7/12.1
108/122100-67-34-0
7.5+3.75
265/2809,350/9,8800.22 2+0.20
1B Flange (JIS10K)(25A) 2+1 1/2B Flange(JIS10K)(40A) 21,500 1,925 690420427
45.0/50.0154,000/171,00012.8/14.2129/14350.0/56.0171,000/191,00014.2/15.9
143/161100-50-0
7.5 2
350/37012,400/13,1000.22 4
1 1/2B Flange(JIS10K)(40A) 4
1,500 2,570 690525535
56.0/63.0191,000/215,00015.9/17.9161/18163.0/71.0215,000/242,00017.9/20.2
181/204100-80-60-40-20-0
7.5 2+3.75
440/46515,500/16,4000.22 4+0.20
1B Flange (JIS10K)(25A) 2+1 1/2B Flange(JIS10K)(40A) 41,550 3,230 758700715
67.0/75.0229,000/256,00019.1/21.3192/21575.0/85.0256,000/290,00021.3/24.2
215/244100-67-34-0
7.5 3
525/55518,500/19,6000.22 6
1 1/2B Flange(JIS10K)(40A) 6
1,550 3,870 758820840
Notes:*1 Cooling capacity is based on the following conditions : Leaving chilled water temp.7 (44.5 F), entering chilled water temp.12 (53.6 F), and outdoor air temp. 35 DB(95 FDB).*2 Heating capacity is based on the following conditions : Leaving hot water temp.45 (113 F), entering hot water temp. 40 (104 F), and outdoor air temp. 7 DB(44.5 FDB), and
6 WB(43 FWB).*3 The following safety devices are equipped as standard. • High pressure switch. • Reverse-phase protector. • Fusible plug. • Freeze up thermostat. • Overcurrent relay for compressor
and fan motor. • Overheat protection for discharge gas. • fan thermal protector.*4 This product is manufactured in Japan.
*1
*2
11.2/12.538,200/42,7003.19/3.5532/3613.2/15.045,100/51,2003.75/4.273 phase, 50 Hz 380/400/415 V, 60 Hz 400/440 V, 3 wires system 38/43100-0Hermetically sealed scroll type3.75 1Brazed plate heat exchangerCross fin coilPropellerDirect drive90/953,180/3,3500.20R-407C
1B Flange (JIS10K)(25A) 2
1,450 635 (839) 690150152-15 to 43 in cooling, -15 to 21 in heating
Air Cooled Water Chillers - Heat Pump Type
21 22
Air
Coo
led
Wat
er C
hill
ers
- Hea
t Pum
p Ty
pe
Air
Coo
led
Wat
er C
hill
ers
- Hea
t Pum
p Ty
pe
530 — 1,260kW class
UWY P 200 — 480B Y 1Standard Unit
50Hz
Notes:*1 Cooling capacity is based on the following conditions : Leaving chilled water temp.7 (44.5 F), entering chilled water temp.12 (53.6 F), and outdoor air temp. 35 DB(95 FDB).*2 Heating capacity is based on the following conditions : Leaving hot water temp.45 (113 F), entering hot water temp.40 (104 F), and outdoor air temp. 7 DB(44.5 FDB),and 6 WB(43 FWB).*3 The following safety devices are equipped as standard. • High pressure protector. • Low pressure protector. • Compressor thermal protector. • Fusible plug. • Reverse-phase
protector. • Overheat protection of discharge gas. • Overcurrent relay(compressor). • Freeze-up protection thermostat. • Overcurrent relay(fan). • Safety valve.*4 The unit is equipped with standard water filter. *5 The limited length of wire represents its max. length when the pressure is lower than 2%. *6 This product is manufactured in China.
S pecifications
TypeMotor output
TypeDrive
Air flow rate
Motor output
Water inlet/outletDrain outlet
UWYP200BY1(200 )
UWYP220BY1(220 )
UWYP240BY1(240 )
UWYP280BY1(280 )
UWYP320BY1(320 )
UWYP360BY1(360 )
UWYP480BY1(480 )
UWYP400BY1(400 )
UWYP440BY1(440 )Model
Cooling capacity
Chilled water flow rate
Heating capacity
Power supplyHot water flow rateCapacity steps
Compressor
Evaporator typeCondenser type
CondenserFans
RefrigerantPipe connections Dimensions (H W D)WeightOperating weightOperation range
kWBtu/hUSRT /minkWBtu/hUSRT
/min%
kW
m3/mincfmkW
mmkgkg
5301,809,000 151 1,519 5701,945,000 162 3 phase, 50 Hz 380/400/415 V, 4 wires system 1,634 100~10-0Semi-hermetic sealed single-screw type45 2+60Brazing Plate type Cross fin coil Propeller Direct drive 3,010106,2531.0 14R-407C5B Flange (125A HG20593-97)RP1 1/4 Female screw (32A)2,456 7,050 2,000 6,8207,018cooling -5 to 43, heating -20 to 21
5801,979,000 165 1,663 6302,150,000 179
1,806
45+60 2
3,440121,4321.0 16
2,456 7,500 2,0007,5007,719
6302,150,000 179 1,806 6902,355,000 196
1,978
60 3
3,870136,6111.0 18
2,456 7,950 2,0007,8858,125
7402,525,000 210 2,121 8002,730,000 228
2,293
(45+60) 2
4,300151,790(1.0 10) 2
4B Flange (100A HG20593-97)
(2,456 4,850 2,000) 24,553 24,624 2
8402,867,000 239 2,408 9203,140,000 262
2,637
(60 2) 2
5,160182,148(1.0 12) 2
(2,456 5,300 2,000) 25,110 25,181 2
9603,276,000 273 2,752 1,0203,481,000 290
2,924
(45 3) 2
5B Flange (125A HG20593-97)
(2,456 6,600 2,000) 26,265 26,456 2
1,0603,617,000 301 3,039 1,1403,890,000 324
3,268
(45 2+60) 2
6,020212,506(1.0 14) 2
(2,456 7,050 2,000) 26,820 27,018 2
1,1603,959,000 330 3,325 1,2604,300,000 358
3,612
(45+60 2) 2
6,880242,864(1.0 16) 2
(2,456 7,500 2,000) 27,500 27,719 2
1,2604,300,000 358 3,612 1,3804,710,000 392
3,956
(60 3) 2
7,740273,222(1.0 18) 2
(2,456 7,950 2,000) 27,885 28,125 2
Notes:*1 Cooling capacity is based on the following conditions : Leaving chilled water temp.7 (44.5 F), entering chilled water temp.12 (53.6 F), and outdoor air temp. 35 DB(95 FDB).*2 Heating capacity is based on the following conditions : Leaving hot water temp.45 (113 F), entering hot water temp.40 (104 F), and outdoor air temp. 7 DB(44.5 FDB),and 6 WB(43 FWB).*3 The following safety devices are equipped as standard. • High pressure protector. • Low pressure protector. • Compressor thermal protector. • Fusible plug. • Reverse-phase
protector. • Overheat protection of discharge gas. • Overcurrent relay(compressor). • Freeze-up protection thermostat. • Overcurrent relay(fan). • Safety valve.
S pecifications
TypeMotor output
TypeDrive
Air flow rate
Motor output
Water inlet/outletDrain outlet
Model
Cooling capacity
Chilled water flow rate
Heating capacity
Power supplyHot water flow rateCapacity steps
Compressor
Evaporator typeCondenser type
CondenserFans
RefrigerantPipe connections water inlet/outlet Dimensions (H W D)WeightOperating weightOperation range
kWBtu/hUSRT /minkWBtu/hUSRT
/min%
kW
m3/mincfmkW
mmkgkg
118 — 355kW class
UWY P 40 — 120B Y BStandard Unit
60Hz
UWYP40BYB(40 )
UWYP50BYB(50 )
UWYP60BYB(60 )
UWYP100BYB(100 )
UWYP120BYB(120 )
118403,000 34 338 132450,000 38 3 phase,60 Hz 400/440 V, 3 wires system378 100~10-0Semi-hermetic sealed single-screw type30 1Brazing Plate type Cross fin coil Propeller Direct drive81028,5930.5 4 R-407C3B Flange (80A HG20593-97) RP1 1/4 Female screw (32A)2,456 2,200 2,0001,6901,723cooling -5 to 43, heating -20 to 21
150512,000 43 430 170580,000 48
487
37 1
1,01035,6531.0 4
1,8101,846
180614,000 51 516 200683,000 57
573
45 1
1,8701,910
3001,024,000 85 860 3351,143,000 95
960
37 2
2,02071,3061.0 8
4B Flange (100A HG20593-97)
2,456 4,400 2,0003,5003,551
3551,212,000 101 1,018 4001,365,000 114
1,147
45 2
3,6053,662
Notes:*1 Cooling capacity is based on the following conditions : Leaving chilled water temp.7 (44.5 F), entering chilled water temp.12 (53.6 F), and outdoor air temp. 35 DB(95 FDB).*2 Heating capacity is based on the following conditions : Leaving hot water temp.45 (113 F), entering hot water temp.40 (104 F), and outdoor air temp. 7 DB(44.5 FDB),and 6 WB(43 FWB).*3 The following safety devices are equipped as standard. • High pressure protector. • Low pressure protector. • Compressor thermal protector. • Fusible plug. • Reverse-phase
protector. • Overheat protection of discharge gas. • Overcurrent relay(compressor). • Freeze-up protection thermostat. • Overcurrent relay(fan). • Safety valve.*4 The unit is equipped with standard water filter. *5 The limited length of wire represents its max. length when the pressure is lower than 2%. *6 This product is manufactured in China.
S pecifications
TypeMotor output
TypeDrive
Air flow rate
Motor output
Water inlet/outlet
Drain outlet
UWYP40BY1(40 )
UWYP50BY1(50 )
UWYP60BY1(60 )
UWYP80BY1(80 )
UWYP100BY1(100 )
UWYP120BY1(120 )
UWYP180BY1(180 )
UWYP140BY1(140 )
UWYP160BY1(160 )Model
Cooling capacity
Chilled water flow rate
Heating capacity
Power supplyHot water flow rateCapacity steps
Compressor
Evaporator typeCondenser type
CondenserFans
Refrigerant
Pipe connections water inlet/outlet
Dimensions (H W D)WeightOperating weightOperation range
kWBtu/hUSRT /minkWBtu/hUSRT
/min%
kW
m3/mincfmkW
mmkgkg
106 — 480kW class
UWY P 40 — 180B Y 1Standard Unit
50Hz
106362,000 30 304 112382,000 32 3 phase,50 Hz 380/400/415 V, 4wires system 321100~10-0 Semi-hermetic sealed single-screw type30 1Brazing Plate type Cross fin coil Propeller Direct drive78027,5340.5 4R-407C
3B Flange (80A HG20593-97)
RP1 1/4 Female screw (32A)2,456 2,200 2,0001,8001,833cooling -5 to 43, heating -20 to 21
132450,000 38 378 140478,000 40
401
37 1
86030,3581.0 4
1,9301,966
160546,000 46 459 170580,000 48
487
45 1
1,9902,030
210717,000 60 602 230785,000 65
659
60 1
1,29045,5371.0 6
2,456 2,650 2,0002,6402,687
265904,000 75 760 280956,000 80
803
37 2
1,60056,4801.0 8
4B Flange (100A HG20593-97)
2,456 4,400 2,0003,7403,791
3151,075,000 90 9033401,160,000 97
975
45 2
1,72060,716
3,9954,052
3701,263,000 105 1,061 4001,365,000 114
1,147
45+60
2,15075,8951.0 10
2,456 4,850 2,0004,5534,624
4201,433,000 119 1,204 4601,570,000 131
1,319
60 2
2,58091,0741.0 12
2,456 5,300 2,0005,1105,181
4801,638,000 137 1,376 5101,740,000 145
1,462
45 3
5B Flange (125A HG20593-97)
2,456 6,600 2,0006,2656,456
S pecifications
11.2 / 12.5 — 67 / 75 kW class
UWY P 125 — 750AY 3Standard Unit
50/60Hz
Model
Cooling capacity(50/60 Hz)
Chilled water flow rate (50/60 Hz)
Heating capacity(50/60 Hz)
Power supplyHot water flow rate (50/60 Hz)Capacity steps
Compressor
Evaporator typeCondenser type
Fan
Refrigerant
Pipe connections water inlet/outlet
Dimensions (H W D)WeightOperating weightOperation range
TypeMotor output
TypeDriveAir flow rate(50/60 Hz)Motor output
kWBtu/hUSRT /minkWBtu/hUSRT
/min%
kW
m3/mincfmkW
mmkgkg
UWYP125AY3(5 )
UWYP190AY3(8 )
UWYP250AY3(10 )
UWYP375AY3(15 )
UWYP500AY3(20 )
UWYP630AY3(25 )
UWYP750AY3(30 )
22.4/25.076,500/85,4006.37/7.1164/7225.0/28.085,400/95,6007.11/7.96
72/80
7.5 1
175/1856,180/6,5300.22 2
260264
17.0/19.058,000/64,9004.83/5.4049/5420.0/22.468,300/76,5005.69/6.37
57/64
5.5 1
140/1604,940/5,6500.22+0.14
1 1/2B Fiange(JIS10K)(40A) 2
1,450 1,280 690258261
33.5/37.5114,000/128,0009.53/10.796/10837.5/42.5128,000/145,00010.7/12.1
108/122100-67-34-0
7.5+3.75
265/2809,350/9,8800.22 2+0.20
1B Flange (JIS10K)(25A) 2+1 1/2B Flange(JIS10K)(40A) 21,500 1,925 690420427
45.0/50.0154,000/171,00012.8/14.2129/14350.0/56.0171,000/191,00014.2/15.9
143/161100-50-0
7.5 2
350/37012,400/13,1000.22 4
1 1/2B Flange(JIS10K)(40A) 4
1,500 2,570 690525535
56.0/63.0191,000/215,00015.9/17.9161/18163.0/71.0215,000/242,00017.9/20.2
181/204100-80-60-40-20-0
7.5 2+3.75
440/46515,500/16,4000.22 4+0.20
1B Flange (JIS10K)(25A) 2+1 1/2B Flange(JIS10K)(40A) 41,550 3,230 758700715
67.0/75.0229,000/256,00019.1/21.3192/21575.0/85.0256,000/290,00021.3/24.2
215/244100-67-34-0
7.5 3
525/55518,500/19,6000.22 6
1 1/2B Flange(JIS10K)(40A) 6
1,550 3,870 758820840
Notes:*1 Cooling capacity is based on the following conditions : Leaving chilled water temp.7 (44.5 F), entering chilled water temp.12 (53.6 F), and outdoor air temp. 35 DB(95 FDB).*2 Heating capacity is based on the following conditions : Leaving hot water temp.45 (113 F), entering hot water temp. 40 (104 F), and outdoor air temp. 7 DB(44.5 FDB), and
6 WB(43 FWB).*3 The following safety devices are equipped as standard. • High pressure switch. • Reverse-phase protector. • Fusible plug. • Freeze up thermostat. • Overcurrent relay for compressor
and fan motor. • Overheat protection for discharge gas. • fan thermal protector.*4 This product is manufactured in Japan.
*1
*2
11.2/12.538,200/42,7003.19/3.5532/3613.2/15.045,100/51,2003.75/4.273 phase, 50 Hz 380/400/415 V, 60 Hz 400/440 V, 3 wires system 38/43100-0Hermetically sealed scroll type3.75 1Brazed plate heat exchangerCross fin coilPropellerDirect drive90/953,180/3,3500.20R-407C
1B Flange (JIS10K)(25A) 2
1,450 635 (839) 690150152-15 to 43 in cooling, -15 to 21 in heating
Air Cooled Water Chillers - Heat Pump Type
21 22
Air
Coo
led
Wat
er C
hill
ers
- Hea
t Pum
p Ty
pe
Air
Coo
led
Wat
er C
hill
ers
- Hea
t Pum
p Ty
pe
UWYP40AY1UWYP50AY1UWYP60AY1
UWYP80AY1 UWYP100AY1UWYP120AY1UWYP140AY1UWYP160AY1
UWYP180AY1UWYP200AY1UWYP220AY1UWYP240AY1
UWYP280AY1UWYP320AY1
UWYP380AY1UWYP400AY1UWYP440AY1UWYP480AY1
Model
Remote controllerChilling water supply interrupting relayWater high pressure (1.6 MPa) upgraderIPUDio unitD Air unitInterface for use in LONWORKS
Interface for use in BACnetCentral remote controllerUnified ON/OFF controllerSchedule timer
BRC307D503GWEL-UWYP40BGWP-UWYP40BDAM602A5DEC102ADAM101ADMS504B51DMS502A51DCS302CA61DCS301BA61DST301BA61
GWP-UWYP80BGWEL-UWYP100BGWP-UWYP100B
GWEL-UWYP180BGWP-UWYP180B
GWEL-UWYP280BGWP-UWYP280B
GWEL-UWYP360BGWP-UWYP360B
Option L is tUWYP40BY1UWYP50BY1UWYP60BY1UWYP40BYBUWYP50BYBUWYP60BYB
UWYP80BY1 UWYP100BY1UWYP120BY1UWYP140BY1UWYP160BY1UWYP100BYBUWYP120BYB
UWYP180BY1UWYP200BY1UWYP220BY1UWYP240BY1
UWYP280BY1UWYP320BY1
UWYP360BY1UWYP400BY1UWYP440BY1UWYP480BY1
Model
Remote controllerChilling water supply interrupting relayWater high pressure (1.6 MPa) upgraderIPUDio unitD Air unitInterface for use in LONWORKS
Interface for use in BACnetCentral remote controllerUnified ON/OFF controllerSchedule timer
BRC307D503GWEL-UWYP40BGWP-UWYP40BDAM602A5DEC102ADAM101ADMS504B51DMS502A51DCS302CA61DCS301BA61DST301BA61
GWP-UWYP80BGWEL-UWYP100BGWP-UWYP100B
GWEL-UWYP180BGWP-UWYP180B
GWEL-UWYP280BGWP-UWYP280B
GWEL-UWYP360BGWP-UWYP360B
UWYP125AY3 UWYP190AY3 UWYP250AY3 UWYP375AY3 UWYP500AY3 UWYP630AY3 UWYP750AY3
Notes: *1 Communication I/F P.C. board, Communication I/F P.C. B storage box and Transmission waire are also required.
Remote controller *1Communication I/F P.C. boardCommunication I/F P.C. B storage boxTransmission wire
ModelBRC307C50BRP66B3BPR66A97BER66A5
BPR66A100BER66A7
—
Notes:*1 Cooling capacity is based on the following conditions : Leaving chilled water temp.7 (44.5 F), entering chilled water temp.12 (53.6 F), and outdoor air temp. 35 DB(95 FDB).*2 Heating capacity is based on the following conditions : Leaving hot water temp.45 (113 F), entering hot water temp.40 (104 F), and outdoor air temp. 7 DB(44.5 FDB),and 6 WB(43 FWB).*3 The following safety devices are equipped as standard. • High pressure protector. • Low pressure protector. • Compressor thermal protector. • Fusible plug. • Reverse-phase
protector. • Overheat protection of discharge gas. • Overcurrent relay(compressor). • Freeze-up protection thermostat. • Overcurrent relay(fan). • Safety valve.*4 The unit is equipped with standard water filter. *5 The limited length of wire represents its max. length when the pressure is lower than 2%. *6 This product is manufactured in China.
S pecifications
TypeMotor output
TypeDrive
Air flow rate
Motor output
*1
Model
Cooling capacity
Chilled water flow rate
Heating capacity
Power supplyHot water flow rateCapacity steps
Compressor
Evaporator typeCondenser type
Condenserfan
RefrigerantPipe connectionswater inlet/outletDimensions (H W D)WeightOperating weightOperation range
kWBtu/hUSRT /minkWBtu/hUSRT
/min%
kW
m3/mincfmkW
mmkgkg
*2
118 — 355kW class
UWY 40 — 120AY BStandard Unit
60Hz
UWY40AYB(40 )
UWY50AYB(50 )
UWY60AYB(60 )
UWY100AYB(100 )
UWY120AYB(120 )
118403,00034338132450,000383 phase, 60 Hz 400/440 V, 3 wires system378100~10-0Semi-hermetic sealed single-screw type30 1Blazing Plate typeCross fin coilPropellerDirect drive80028,2400.5 4R-22
3B Flange (80A HG20593-97)
2,395 2,200 2,0001,7001,717cooling -5 to 43, heating -20 to 21
150512,00043430170580,00048
487
37 1
81028,5930.8 4
1,8001,820
180614,00051516200683,00057
573
45 1
94033,1821.2 4
1,9501,973
3001,024,000858603351,143,00095
960
37 2
1,62057,1860.8 8
4B Flange (100A HG20593-97)
2,395 4,400 2,0003,6003,636
3551,212,0001011,0184001,365,000114
1,147
45 2
1,88066,3641.2 8
3,9003,942
Notes:*1 Cooling capacity is based on the following conditions : Leaving chilled water temp.7 (44.5 F), entering chilled water temp.12 (53.6 F), and outdoor air temp. 35 DB(95 FDB).*2 Heating capacity is based on the following conditions : Leaving hot water temp.45 (113 F), entering hot water temp.40 (104 F), and outdoor air temp. 7 DB(44.5 FDB),and 6 WB(43 FWB).*3 The following safety devices are equipped as standard. • High pressure protector. • Low pressure protector. • Compressor thermal protector. • Fusible plug. • Reverse-phase
protector. • Overheat protection of discharge gas. • Overcurrent relay(compressor). • Freeze-up protection thermostat. • Overcurrent relay(fan). • Safety valve.*4 Standard for the max. chilled water pressure is 0.7MPa, but1.6MPa is available if required. *5 Installation/operating weight includes the weight of refrigerant and refrigerant oil(charged before delivery).
S pecifications
TypeMotor output
TypeDrive
Air flow rate
Motor output
UWY200AY1(200 )
UWY220AY1(220 )
UWY240AY1(240 )
UWY280AY1(280 )
UWY320AY1(320 )
UWY360AY1(360 )
UWY480AY1(480 )
UWY400AY1(400 )
UWY420AY1(420 )
*1
Model
Cooling capacity
Chilled water flow rate
Heating capacity
Power supplyHot water flow rateCapacity steps
Compressor
Evaporator typeCondenser type
Condenserfan
RefrigerantPipe connections Water inlet/outlet
Dimensions (H W D)
WeightOperating weightOperation range
kWBtu/hUSRT /minkWBtu/hUSRT
/min%
kW
m3/mincfmkW
mm
kgkg
6302,150,0001791,8067202,457,000205
2,064
60 3
2,82099,546
6,3506,450
7402,525,0002102,1218402,867,000239
2,408
(45+60) 2
3,560125,668(1.2 8) 2
4B Flange (100A HG20593-97)
(2,395 4,400 2,000) 2
4,020 24,084 2
5301,809,0001511,5196002,048,0001713 phase, 50 Hz 380/400/415 V, 4 wires system 1,720100~10-0 (continuous capacity control)Semi-hermetic sealed single-screw type45 2+60Blazing plate typeCross fin coilPropellerDirect drive2,62092,4861.2 12R-225B Flange (125A HG20593-97)
(2,460 6,600 2,000) 2
6,2606,337cooling -5 to 43, heating -20 to 21
*2
5801,979,0001651,6636602,252,000188
1,892
45+60 2
2,72096,016
6,2956,382
8402,867,0002392,4089603,276,000273
2,752
(60 2) 2
3,760132,728
4,040 24,104 2
9603,276,0002732,7521,0803,686,000307
3,096
(45 3) 2
5,040177,912(1.2 12) 2
5B Flange (125A HG20593-97)
(2,460 6,600 2,000) 2
6,205 26,270 2
1,0603,617,0003013,0391,2004,095,000341
3,440
(45 2+60) 2
5,240184,972
6,260 26,337 2
1,2604,300,0003583,6121,4404,914,000410
4,128
(60 3) 2
5,640199,092
6,350 26,450 2
1,1603,959,0003303,3251,3204,505,000375
3,784
(45+60 2) 2
5,440192,032
6,295 26,382 2
530 — 1,260kW class
UWY 200 — 480AY 1Standard Unit
50Hz
Notes:*1 Cooling capacity is based on the following conditions : Leaving chilled water temp.7 (44.5 F), entering chilled water temp.12 (53.6 F), and outdoor air temp. 35 DB(95 FDB).*2 Heatinging capacity is based on the following conditions : Leaving hot water temp.45 (113 F), entering hot water temp.40 (104 F), and outdoor air temp. 7 DB(44.5 FDB),and 6 WB(43 FWB).*3 The following safety devices are equipped as standard. • High pressure protector. • Low pressure protector. • Compressor thermal protector. • Fusible plug. • Reverse-phase
protector. • Overheat protection of discharge gas. • Overcurrent relay(compressor). • Freeze-up protection thermostat. • Overcurrent relay(fan). • Safety valve.*4 Standard for the max. chilled water pressure is 0.7MPa, but1.6MPa is available if required. *5 Installation/operating weight includes the weight of refrigerant and refrigerant oil (charged before delivery). *6 This product is manufactured in China.
S pecifications
TypeMotor output
TypeDrive
Air flow rate
Motor output
UWY40AY1(40 )
UWY50AY1(50 )
UWY60AY1(60 )
UWY80AYAY1(80 )
UWY100AY1(100 )
UWY120AY1(120 )
UWY180AY1(180 )
UWY140AY1(140 )
UWY160AY1(160 )
*1
Model
Cooling capacity
Chilled water flow rate
Heating capacity
Power supplyHot water flow rateCapacity steps
Compressor
Evaporator typeCondenser type
Condenserfan
RefrigerantPipe connections water inlet/outlet
Dimensions (H W D)
WeightOperating weightOperation range
kWBtu/hUSRT /minkWBtu/hUSRT
/min%
kW
m3/mincfmkW
mm
kgkg
160546,00046459180614,00051
516
45 1
84029,6521.2 4
1,9501,973
210717,00060602240819,00068
688
60 1
94033,182
2,0202,052
106362,00030304118403,000343 phase, 50 Hz 380/400/415 V, 4 wires system 338100~10-0 (continuous capacity control)Semi-hermetic sealed single-screw type30 1Brazed plate typeCross fin coilPropellerDirect drive70024,7100.5 4R-223B Flange (80A HG20593-97)
2,395 2,200 2,000
1,7001,717cooling -5 to 43, heating -20 to 21
*2
132450,00038378150512,00043
430
37 1
71025,0630.8 4
1,8001,820
265904,000757603001,024,00085
860
37 2
1,42050,1260.8 8
4B Flange (100A HG20593-97)
2,395 4,400 2,000
3,6003,636
3201,092,000919173551,212,000101
1,018
45 2
1,68059,3041.2 8
3,9003,942
3701,263,0001051,0614201,433,000119
1,204
45+60
1,78062,834
4,0204,084
4801,638,0001371,3765401,843,000154
1,548
45 3
2,52088,9561.2 12
5B Flange (125A HG20593-97) 2,460 6,600 2,0006,2056,270
4201,433,0001191,2044801,638,000137
1,376
60 2
1,88066,364
4,0404,104
106 — 480kW class
UWY 40 — 180AY 1Standard Unit
50Hz
Air Cooled Water Chillers - Heat Pump Type
23 24
Air
Coo
led
Wat
er C
hill
ers
- Hea
t Pum
p Ty
pe
Air
Coo
led
Wat
er C
hill
ers
- Hea
t Pum
p Ty
pe
UWYP40AY1UWYP50AY1UWYP60AY1
UWYP80AY1 UWYP100AY1UWYP120AY1UWYP140AY1UWYP160AY1
UWYP180AY1UWYP200AY1UWYP220AY1UWYP240AY1
UWYP280AY1UWYP320AY1
UWYP380AY1UWYP400AY1UWYP440AY1UWYP480AY1
Model
Remote controllerChilling water supply interrupting relayWater high pressure (1.6 MPa) upgraderIPUDio unitD Air unitInterface for use in LONWORKS
Interface for use in BACnetCentral remote controllerUnified ON/OFF controllerSchedule timer
BRC307D503GWEL-UWYP40BGWP-UWYP40BDAM602A5DEC102ADAM101ADMS504B51DMS502A51DCS302CA61DCS301BA61DST301BA61
GWP-UWYP80BGWEL-UWYP100BGWP-UWYP100B
GWEL-UWYP180BGWP-UWYP180B
GWEL-UWYP280BGWP-UWYP280B
GWEL-UWYP360BGWP-UWYP360B
Option L is tUWYP40BY1UWYP50BY1UWYP60BY1UWYP40BYBUWYP50BYBUWYP60BYB
UWYP80BY1 UWYP100BY1UWYP120BY1UWYP140BY1UWYP160BY1UWYP100BYBUWYP120BYB
UWYP180BY1UWYP200BY1UWYP220BY1UWYP240BY1
UWYP280BY1UWYP320BY1
UWYP360BY1UWYP400BY1UWYP440BY1UWYP480BY1
Model
Remote controllerChilling water supply interrupting relayWater high pressure (1.6 MPa) upgraderIPUDio unitD Air unitInterface for use in LONWORKS
Interface for use in BACnetCentral remote controllerUnified ON/OFF controllerSchedule timer
BRC307D503GWEL-UWYP40BGWP-UWYP40BDAM602A5DEC102ADAM101ADMS504B51DMS502A51DCS302CA61DCS301BA61DST301BA61
GWP-UWYP80BGWEL-UWYP100BGWP-UWYP100B
GWEL-UWYP180BGWP-UWYP180B
GWEL-UWYP280BGWP-UWYP280B
GWEL-UWYP360BGWP-UWYP360B
UWYP125AY3 UWYP190AY3 UWYP250AY3 UWYP375AY3 UWYP500AY3 UWYP630AY3 UWYP750AY3
Notes: *1 Communication I/F P.C. board, Communication I/F P.C. B storage box and Transmission waire are also required.
Remote controller *1Communication I/F P.C. boardCommunication I/F P.C. B storage boxTransmission wire
ModelBRC307C50BRP66B3BPR66A97BER66A5
BPR66A100BER66A7
—
Notes:*1 Cooling capacity is based on the following conditions : Leaving chilled water temp.7 (44.5 F), entering chilled water temp.12 (53.6 F), and outdoor air temp. 35 DB(95 FDB).*2 Heating capacity is based on the following conditions : Leaving hot water temp.45 (113 F), entering hot water temp.40 (104 F), and outdoor air temp. 7 DB(44.5 FDB),and 6 WB(43 FWB).*3 The following safety devices are equipped as standard. • High pressure protector. • Low pressure protector. • Compressor thermal protector. • Fusible plug. • Reverse-phase
protector. • Overheat protection of discharge gas. • Overcurrent relay(compressor). • Freeze-up protection thermostat. • Overcurrent relay(fan). • Safety valve.*4 The unit is equipped with standard water filter. *5 The limited length of wire represents its max. length when the pressure is lower than 2%. *6 This product is manufactured in China.
S pecifications
TypeMotor output
TypeDrive
Air flow rate
Motor output
*1
Model
Cooling capacity
Chilled water flow rate
Heating capacity
Power supplyHot water flow rateCapacity steps
Compressor
Evaporator typeCondenser type
Condenserfan
RefrigerantPipe connectionswater inlet/outletDimensions (H W D)WeightOperating weightOperation range
kWBtu/hUSRT /minkWBtu/hUSRT
/min%
kW
m3/mincfmkW
mmkgkg
*2
118 — 355kW class
UWY 40 — 120AY BStandard Unit
60Hz
UWY40AYB(40 )
UWY50AYB(50 )
UWY60AYB(60 )
UWY100AYB(100 )
UWY120AYB(120 )
118403,00034338132450,000383 phase, 60 Hz 400/440 V, 3 wires system378100~10-0Semi-hermetic sealed single-screw type30 1Blazing Plate typeCross fin coilPropellerDirect drive80028,2400.5 4R-22
3B Flange (80A HG20593-97)
2,395 2,200 2,0001,7001,717cooling -5 to 43, heating -20 to 21
150512,00043430170580,00048
487
37 1
81028,5930.8 4
1,8001,820
180614,00051516200683,00057
573
45 1
94033,1821.2 4
1,9501,973
3001,024,000858603351,143,00095
960
37 2
1,62057,1860.8 8
4B Flange (100A HG20593-97)
2,395 4,400 2,0003,6003,636
3551,212,0001011,0184001,365,000114
1,147
45 2
1,88066,3641.2 8
3,9003,942
Notes:*1 Cooling capacity is based on the following conditions : Leaving chilled water temp.7 (44.5 F), entering chilled water temp.12 (53.6 F), and outdoor air temp. 35 DB(95 FDB).*2 Heating capacity is based on the following conditions : Leaving hot water temp.45 (113 F), entering hot water temp.40 (104 F), and outdoor air temp. 7 DB(44.5 FDB),and 6 WB(43 FWB).*3 The following safety devices are equipped as standard. • High pressure protector. • Low pressure protector. • Compressor thermal protector. • Fusible plug. • Reverse-phase
protector. • Overheat protection of discharge gas. • Overcurrent relay(compressor). • Freeze-up protection thermostat. • Overcurrent relay(fan). • Safety valve.*4 Standard for the max. chilled water pressure is 0.7MPa, but1.6MPa is available if required. *5 Installation/operating weight includes the weight of refrigerant and refrigerant oil(charged before delivery).
S pecifications
TypeMotor output
TypeDrive
Air flow rate
Motor output
UWY200AY1(200 )
UWY220AY1(220 )
UWY240AY1(240 )
UWY280AY1(280 )
UWY320AY1(320 )
UWY360AY1(360 )
UWY480AY1(480 )
UWY400AY1(400 )
UWY420AY1(420 )
*1
Model
Cooling capacity
Chilled water flow rate
Heating capacity
Power supplyHot water flow rateCapacity steps
Compressor
Evaporator typeCondenser type
Condenserfan
RefrigerantPipe connections Water inlet/outlet
Dimensions (H W D)
WeightOperating weightOperation range
kWBtu/hUSRT /minkWBtu/hUSRT
/min%
kW
m3/mincfmkW
mm
kgkg
6302,150,0001791,8067202,457,000205
2,064
60 3
2,82099,546
6,3506,450
7402,525,0002102,1218402,867,000239
2,408
(45+60) 2
3,560125,668(1.2 8) 2
4B Flange (100A HG20593-97)
(2,395 4,400 2,000) 2
4,020 24,084 2
5301,809,0001511,5196002,048,0001713 phase, 50 Hz 380/400/415 V, 4 wires system 1,720100~10-0 (continuous capacity control)Semi-hermetic sealed single-screw type45 2+60Blazing plate typeCross fin coilPropellerDirect drive2,62092,4861.2 12R-225B Flange (125A HG20593-97)
(2,460 6,600 2,000) 2
6,2606,337cooling -5 to 43, heating -20 to 21
*2
5801,979,0001651,6636602,252,000188
1,892
45+60 2
2,72096,016
6,2956,382
8402,867,0002392,4089603,276,000273
2,752
(60 2) 2
3,760132,728
4,040 24,104 2
9603,276,0002732,7521,0803,686,000307
3,096
(45 3) 2
5,040177,912(1.2 12) 2
5B Flange (125A HG20593-97)
(2,460 6,600 2,000) 2
6,205 26,270 2
1,0603,617,0003013,0391,2004,095,000341
3,440
(45 2+60) 2
5,240184,972
6,260 26,337 2
1,2604,300,0003583,6121,4404,914,000410
4,128
(60 3) 2
5,640199,092
6,350 26,450 2
1,1603,959,0003303,3251,3204,505,000375
3,784
(45+60 2) 2
5,440192,032
6,295 26,382 2
530 — 1,260kW class
UWY 200 — 480AY 1Standard Unit
50Hz
Notes:*1 Cooling capacity is based on the following conditions : Leaving chilled water temp.7 (44.5 F), entering chilled water temp.12 (53.6 F), and outdoor air temp. 35 DB(95 FDB).*2 Heatinging capacity is based on the following conditions : Leaving hot water temp.45 (113 F), entering hot water temp.40 (104 F), and outdoor air temp. 7 DB(44.5 FDB),and 6 WB(43 FWB).*3 The following safety devices are equipped as standard. • High pressure protector. • Low pressure protector. • Compressor thermal protector. • Fusible plug. • Reverse-phase
protector. • Overheat protection of discharge gas. • Overcurrent relay(compressor). • Freeze-up protection thermostat. • Overcurrent relay(fan). • Safety valve.*4 Standard for the max. chilled water pressure is 0.7MPa, but1.6MPa is available if required. *5 Installation/operating weight includes the weight of refrigerant and refrigerant oil (charged before delivery). *6 This product is manufactured in China.
S pecifications
TypeMotor output
TypeDrive
Air flow rate
Motor output
UWY40AY1(40 )
UWY50AY1(50 )
UWY60AY1(60 )
UWY80AYAY1(80 )
UWY100AY1(100 )
UWY120AY1(120 )
UWY180AY1(180 )
UWY140AY1(140 )
UWY160AY1(160 )
*1
Model
Cooling capacity
Chilled water flow rate
Heating capacity
Power supplyHot water flow rateCapacity steps
Compressor
Evaporator typeCondenser type
Condenserfan
RefrigerantPipe connections water inlet/outlet
Dimensions (H W D)
WeightOperating weightOperation range
kWBtu/hUSRT /minkWBtu/hUSRT
/min%
kW
m3/mincfmkW
mm
kgkg
160546,00046459180614,00051
516
45 1
84029,6521.2 4
1,9501,973
210717,00060602240819,00068
688
60 1
94033,182
2,0202,052
106362,00030304118403,000343 phase, 50 Hz 380/400/415 V, 4 wires system 338100~10-0 (continuous capacity control)Semi-hermetic sealed single-screw type30 1Brazed plate typeCross fin coilPropellerDirect drive70024,7100.5 4R-223B Flange (80A HG20593-97)
2,395 2,200 2,000
1,7001,717cooling -5 to 43, heating -20 to 21
*2
132450,00038378150512,00043
430
37 1
71025,0630.8 4
1,8001,820
265904,000757603001,024,00085
860
37 2
1,42050,1260.8 8
4B Flange (100A HG20593-97)
2,395 4,400 2,000
3,6003,636
3201,092,000919173551,212,000101
1,018
45 2
1,68059,3041.2 8
3,9003,942
3701,263,0001051,0614201,433,000119
1,204
45+60
1,78062,834
4,0204,084
4801,638,0001371,3765401,843,000154
1,548
45 3
2,52088,9561.2 12
5B Flange (125A HG20593-97) 2,460 6,600 2,0006,2056,270
4201,433,0001191,2044801,638,000137
1,376
60 2
1,88066,364
4,0404,104
106 — 480kW class
UWY 40 — 180AY 1Standard Unit
50Hz
Air Cooled Water Chillers - Heat Pump Type
23 24
A s ingle built- in control box s implifies operation and control.
P rovides a s table supply of chilled water throughout the
Since the heat exchanger employs water, operation of the unit is not affected by changes in the outdoor temperature. A stable water temperature is maintained year round.
All controls and indicators are centralized in a single control box, making it possi-ble to control the system using fewer personnel. Installation is simplified by inte-gration of the control box with the main unit.
The water temperature setting can be set to any value between 4 and 25 .
The 10 HP model has a footprint measuring only 0.32 square meters .
8 to 30 HP models have a modular design that enables units with different capaci-ties to be used together in a single system and simplifies increasing system ca-pacity later on 3 — 5 HP models have a similar configuration and are designed for compactness.
The starter panel is built into the control panel, s implifying
Easy InstallationUWP 90AY 3 — 900AY 3
All models are fitted with a pressure gauge as s tandard.
P erformance characteris tics under partial load are efficient.
Reliability
Efficient Performance
Well Appointed
The new double-pipe heat exchanger design reduces clogging, significantly in-creasing resistance to dirty cooling water.
The double-pipe heat exchanger and an individual error indication function help reduce the manpower required for
MaintenanceUWP 90AY 3 — 900AY 3
UWD1320DY 1 — 4000DY 1
Year Round Cooling OperationApplies to All Models
Wide Water Temperature Control Range RangeUWP 90AY 3 — 900AY 3
Simple Operation and ControlUWD1320DY 1 — 4000DY 1
UWD1320DY 1UWP 900AY 3
Model LineupRefrigerant Units series Model No.
Capacity (kW) page
50/60Hz50Hz
R-407CR-134a
Standard UnitStandard Unit
UWP—AY3UWD—DY1
8/990—
13.2/15150—
20/22.4224—
26.5/30300—
40/45450—
53/60600—
67/75750—
80/90900—
118—
1320
150—
1700
180—
2000
236—
2650
300—
3350
355—
40002727
Refrigerant Units series Model No.
50Hz60Hz50Hz60Hz
R-134aStandard Unit
Brine Cooling Unit
ZUW—AY1ZUW—AYBZUW—AY1ZZUW—AYBZ
Capacity100RT
100—
100—
120RT120120120120
150RT150150150150
175RT175175175175
200RT200200200200
240RT240240240240
280RT280280280—
300RT300—
300300
350RT350—
350—
400RT400—
400—
28282929
page
: UWP S eries : UWD S eries ZUW S eries
E mploys the new refrigerants R -407C and R -134a.
New RefrigerantUWP 90 — 900AY 3UWD1320 — 40000DY 1 ZUW100 — 400AY (1) (B ) ZUW100 — 400AY (1) (B ) Z
To improve their operational reliability, 5 -- 30HP models employ scroll compressors , while 40 -- 120HP models are equipped with semi-hermetic s ingle screw compressors .
R efrigerant inlet
R efrigerant outlet
S emi-hermetic s ingle screw compressor
Efficient and Reliable CompressorsApplies to All Models
Wat
er C
oole
d W
ater
Chi
ller
s
Wat
er C
oole
d W
ater
Chi
ller
s
ZUW175AY 1
1 compressoris operating
2 compressors
100
50
0 25 50 100
Power consum
ption ratio (%)
Cooling capacity ratio (%)
Increased characteristicunder partial load
Water Cooled Water Chillers
25 26
A s ingle built- in control box s implifies operation and control.
P rovides a s table supply of chilled water throughout the
Since the heat exchanger employs water, operation of the unit is not affected by changes in the outdoor temperature. A stable water temperature is maintained year round.
All controls and indicators are centralized in a single control box, making it possi-ble to control the system using fewer personnel. Installation is simplified by inte-gration of the control box with the main unit.
The water temperature setting can be set to any value between 4 and 25 .
The 10 HP model has a footprint measuring only 0.32 square meters .
8 to 30 HP models have a modular design that enables units with different capaci-ties to be used together in a single system and simplifies increasing system ca-pacity later on 3 — 5 HP models have a similar configuration and are designed for compactness.
The starter panel is built into the control panel, s implifying
Easy InstallationUWP 90AY 3 — 900AY 3
All models are fitted with a pressure gauge as s tandard.
P erformance characteris tics under partial load are efficient.
Reliability
Efficient Performance
Well Appointed
The new double-pipe heat exchanger design reduces clogging, significantly in-creasing resistance to dirty cooling water.
The double-pipe heat exchanger and an individual error indication function help reduce the manpower required for
MaintenanceUWP 90AY 3 — 900AY 3
UWD1320DY 1 — 4000DY 1
Year Round Cooling OperationApplies to All Models
Wide Water Temperature Control Range RangeUWP 90AY 3 — 900AY 3
Simple Operation and ControlUWD1320DY 1 — 4000DY 1
UWD1320DY 1UWP 900AY 3
Model LineupRefrigerant Units series Model No.
Capacity (kW) page
50/60Hz50Hz
R-407CR-134a
Standard UnitStandard Unit
UWP—AY3UWD—DY1
8/990—
13.2/15150—
20/22.4224—
26.5/30300—
40/45450—
53/60600—
67/75750—
80/90900—
118—
1320
150—
1700
180—
2000
236—
2650
300—
3350
355—
40002727
Refrigerant Units series Model No.
50Hz60Hz50Hz60Hz
R-134aStandard Unit
Brine Cooling Unit
ZUW—AY1ZUW—AYBZUW—AY1ZZUW—AYBZ
Capacity100RT
100—
100—
120RT120120120120
150RT150150150150
175RT175175175175
200RT200200200200
240RT240240240240
280RT280280280—
300RT300—
300300
350RT350—
350—
400RT400—
400—
28282929
page
: UWP S eries : UWD S eries ZUW S eries
E mploys the new refrigerants R -407C and R -134a.
New RefrigerantUWP 90 — 900AY 3UWD1320 — 40000DY 1 ZUW100 — 400AY (1) (B ) ZUW100 — 400AY (1) (B ) Z
To improve their operational reliability, 5 -- 30HP models employ scroll compressors , while 40 -- 120HP models are equipped with semi-hermetic s ingle screw compressors .
R efrigerant inlet
R efrigerant outlet
S emi-hermetic s ingle screw compressor
Efficient and Reliable CompressorsApplies to All Models
Wat
er C
oole
d W
ater
Chi
ller
s
Wat
er C
oole
d W
ater
Chi
ller
s
ZUW175AY 1
1 compressoris operating
2 compressors
100
50
0 25 50 100
Power consum
ption ratio (%)
Cooling capacity ratio (%)
Increased characteristicunder partial load
Water Cooled Water Chillers
25 26
S pecificationsUWP90AY3
(3 )UWP150AY3
(5 )UWP224AY3
(8 )UWP300AY3
(10 )UWP450AY3
(15 )UWP600AY3
(20 )UWP750AY3
(25 )UWP900AY3
(30 )Model
Cooling capacity(50/60 Hz)
Power supplyChilled water flow rate(50/60 Hz)Capacity steps
Compressor
Evaporator typeCondenser typeRefrigerant
Pipeconnections
Dimensions (H W D)WeightOperating weight
TypeMotor output
Condenser water inlet/outletChilled water inlet/outletDrain outlet
kWBtu/hUSRT
/min
%
kW
mmkgkg
8.0/9.027,300/30,7002.28/2.563 phase, 50 Hz 380/400/415 V, 60 Hz 400/440 V, 3 wires system
23/26
100-0Hermetically sealed scroll type3.0 1Brazed plate heat exchangerDouble pipe condenserR-407CFPT1 (25A)FPT1 (25A)FPT3/4 (20A)1,280 405 690100102
13.2/15.045,100/51,2003.75/4.27
38/43
3.75 1
110112
20.0/22.468,300/76,5005.69/6.37
57/64
5.5 1
FPT1 1/2 (40A)FPT1 1/2 (40A)
1,280 405 790150154
26.5/30.090,500/102,0007.54/8.53
76/86
7.5 1
160165
40.0/45.0137,000/154,00011.4/12.8
115/129
100-50-0
5.5 2
FPT1 1/2 2 (40A)FPT1 1/2 2 (40A)
1,280 808 790305313
53.0/60.0181,000/205,00015.1/17.1
152/172
7.5 2
325335
67.0/75.0229,000/256,00019.1/21.3
192/215
100-60-0
7.5+5.5 2
FPT1 1/2 3 (40A)FPT1 1/2 3 (40A)
1,280 1,211 790465478
80.0/90.0273,000/307,00022.8/25.6
229/258
100-67-0
7.5 3
485500
Notes:*1 Cooling capacity is based on the following conditions : Leaving chilled water temp.7 (44.5 F), entering chilled water temp.12 (53.6 F), leaving condenser water temp. 35 (95 F), entering
condenser water temp. 30 (86 F).*2 The following safety devices are equipped as standard. • High/low pressure switch. • Freeze-up protection thermostat. • Overcurrent relay for compressors. • Reverse-phase protector.
• Discharge gas overheat protector. • Fusible plug. • Safety valve.*3 This product is manufactured in Japan.
*1
8 / 9 — 80 / 90kW class
UWP 90 — 900AY 3Standard Unit
50/60Hz
S pecificationsUWD1320DY1
(40 )UWD1700DY1
(50 )UWD2000DY1
(60 )UWD2650DY1
(80 )UWD3350DY1
(100 )UWD4000DY1
(120 )Model
Cooling capacity
Power supply
Chilled water flow rate
Condenser water flow rate
Compressor
Evaporator typeCondenser typeRefrigerant
Pipeconnections
Dimensions (H W D)Weight (Approx.)Operating weight (Approx.)
TypeMotor outputCapacity control
Condenser water inlet/outletChilled water inlet/outletChilled water drain outletCondenser water drain outlet
kWBtu/hUSRT
/min
/min
kW%
mmkgkg
118403,00033.63 phase, 50 Hz 380/400/415 V, 3 wires system
338
420
Semi-hermetic sealed single screw type30 1100-70-40-0Shell and Hi-X tube typeShell and cross fin tube typeR-134aFPT3 (80A)FPT3 (80A)FPT3/4FPT1/41,600 2,320 7591,1001,220
150512,00042.7
430
534
37 1
1,702 2,600 7591,2501,390
180615,00051.2
516
640
45 1
FPT4 (100A)4B Flange (JIS10K)(100A)FPT1
1,2801,420
236806,00067.1
677
837
30 2100-70-40-20-0
FPT3 (80A)
1,623 3,330 9941,8001,980
3001,020,00085.3
860
1,068
37 2
1,745 3,338 1,0502,2002,420
3551,210,000101
1,018
1,263
45 2
FPT4 (100A)5B Flange (JIS10K)(125A)
2,3002,520
Notes:*1 Cooling capacity is based on the following conditions : Leaving chilled water temp.7 (44.5 F), entering chilled water temp.12 (53.6 F), leaving condenser water temp. 35 (95 F), entering
condenser water temp.30 (86 F).*2 The following safety devices are equipped as standard. • High/low pressure switch. • Freeze-up protection thermostat. • Overcurrent relay for compressors. • Compressor thermal
protector. • Reverse-phase protector. • Discharge gas overheat protector. • Fusible plug. • Safety valve(for UWD2000DY1,UWD4000DY1). *3 This product is manufactured in Japan.
*1
118 — 355kW class
UWD1320 — 4000DY 1Standard Unit
50Hz
Notes:*1 Cooling capacity is based on the following conditions : Leaving chilled water temp.7 (44.5 F), entering chilled water temp.12 (53.6 F), leaving condenser water temp. 35 (95 F), entering
condenser water temp.30 (86 F).*2 The following safety devices are equipped as standard. • High/low pressure switch. • Freeze-up protection thermostat. • Overcurrent relay for compressors. • Compressor thermal
protector. • Reverse-phase protector. • Discharge gas overheat protector. • Fusible plug. • Safety valve. *3 This product is manufactured in China.
S pecifications
Model
Cooling capacity
Power supplyChilled water flow rateCondenser water flow rate
Compressor
Evaporator typeCondenser typeRefrigerant
Pipeconnections
Dimensions (H W D)Weight (Approx.)Operating weight (Approx.)
TypeMotor outputCapacity control
Condenser water inlet/outletChilled water inlet/outletChilled water drain outletCondenser water drain outlet
kWBtu/hUSRT
/min /min
kW%
mmkgkg
367 — 1,450kW class
ZUW100 — 400AY 1Standard Unit
50Hz
ZUW100AY1(100RT)
ZUW120AY1(120RT)
ZUW150AY1(150RT)
ZUW175AY1(175 RT)
ZUW200AY1(200RT)
ZUW240AY1(240RT)
ZUW280AY1(280RT)
ZUW300AY1(300RT)
ZUW350AY1(350RT)
ZUW400AY1(400RT)
3671,252,1321043 phase, 50 HZ 380/400/415 V, 3 wires system1,0521,253 single screw compress37 2100 25-0 continuous capacity controlshell and tube flooded type shell and tube type R-134a5B Flange (125A) 5B Flange (125A) NPT1 1/2 1 NPT1 1/2 1 1,765 1,160 3,5303,500 3,700
4541,548,959129
1,3011,545
45 2
3,650 3,850
5081,733,196144
1,4561,727
3,750 4,000
6312,152,848179
1,8092,153
60 2
1,765 1,210 3,6803,900 4,150
7102,422,381202
2,0352,400
75 2
6B Flange (150A) 6B Flange (150A)
1,830 1,320 3,9604,750 5,050
8572,923,916244
2,4572,930
90 2
2,000 1,400 4,0005,250 5,600
1,0003,411,804284
2,8673,407
90+110
8B Flange (200A)
2,060 1,470 4,5506,650 7,100
1,1143,800,750317
3,1933,773
110 2
6,750 7,200
1,2604,298,874358
3,6124,235
130 2100 10-0 continuous capacity control
8B Flange (200A) NPT1 1/2 1, NPT1 1/4 2NPT1 1/2 1, NPT1 1/4 22,270 1,830 4,2508,300 8,900
1,4504,947,117412
4,1574,883
8,450 9,150
Notes:*1 Cooling capacity is based on the following conditions : Leaving chilled water temp.7 (44.5 F), entering chilled water temp.12 (53.6 F), leaving condenser water temp. 35 (95 F), entering
condenser water temp.30 (86 F).*2 The following safety devices are equipped as standard. • High/low pressure switch. • Freeze-up protection thermostat. • Overcurrent relay for compressors. • Compressor thermal protector.
• Reverse-phase protector. • Discharge gas overheat protector. • Fusible plug. • Safety valve.
S pecifications
Model
Cooling capacity
Power supplyChilled water flow rateCondenser water flow rate
Compressor
Evaporator typeCondenser typeRefrigerant
Pipeconnections
Dimensions (H W D)Weight (Approx.)Operating weight (Approx.)
TypeMotor outputCapacity control
Condenser water inlet/outletChilled water inlet/outletChilled water drain outletCondenser water drain outlet
kWBtu/hUSRT
/min /min
kW%
mmkgkg
441 — 1,040kW class
ZUW120 — 300AY BStandard Unit
60Hz
ZUW120AYB(120RT)
ZUW150AYB(150RT)
ZUW175AYB(175RT)
ZUW200AYB(200RT)
ZUW240AYB(240RT)
ZUW300AYB(300RT)
4411,504,6061253 phase, 60 Hz 400/440 V, 3 wires system 1,2641,517single screw compress 37 2100 25-0 continuous capacity control shell and tube flooded type shell and tube type R-134a5B Flange (125A) 5B Flange (125A) FPT1/2 FPT1/2 1,765 1,160 3,4003,800 4,000
5421,849,198154
1,5531,864
45 2
4,150 4,400
6062,067,554172
1,7372,085
4,450 4,700
7592,589,560216
2,1752,609
60 2
6B Flange (150A) 6B Flange (150A)
1,830 1,320 3,6005,100 5,400
8482,893,211241
2,4302,903
75 2
2,000 1,400 3,9605,850 6,200
1,0403,548,277296
2,9813,584
90 2
8B Flange (200A)
2,060 1,680 4,0006,350 6,800
Water Cooled Water Chillers
Wat
er C
oole
d W
ater
Chi
ller
s
Wat
er C
oole
d W
ater
Chi
ller
s
27 28
S pecificationsUWP90AY3
(3 )UWP150AY3
(5 )UWP224AY3
(8 )UWP300AY3
(10 )UWP450AY3
(15 )UWP600AY3
(20 )UWP750AY3
(25 )UWP900AY3
(30 )Model
Cooling capacity(50/60 Hz)
Power supplyChilled water flow rate(50/60 Hz)Capacity steps
Compressor
Evaporator typeCondenser typeRefrigerant
Pipeconnections
Dimensions (H W D)WeightOperating weight
TypeMotor output
Condenser water inlet/outletChilled water inlet/outletDrain outlet
kWBtu/hUSRT
/min
%
kW
mmkgkg
8.0/9.027,300/30,7002.28/2.563 phase, 50 Hz 380/400/415 V, 60 Hz 400/440 V, 3 wires system
23/26
100-0Hermetically sealed scroll type3.0 1Brazed plate heat exchangerDouble pipe condenserR-407CFPT1 (25A)FPT1 (25A)FPT3/4 (20A)1,280 405 690100102
13.2/15.045,100/51,2003.75/4.27
38/43
3.75 1
110112
20.0/22.468,300/76,5005.69/6.37
57/64
5.5 1
FPT1 1/2 (40A)FPT1 1/2 (40A)
1,280 405 790150154
26.5/30.090,500/102,0007.54/8.53
76/86
7.5 1
160165
40.0/45.0137,000/154,00011.4/12.8
115/129
100-50-0
5.5 2
FPT1 1/2 2 (40A)FPT1 1/2 2 (40A)
1,280 808 790305313
53.0/60.0181,000/205,00015.1/17.1
152/172
7.5 2
325335
67.0/75.0229,000/256,00019.1/21.3
192/215
100-60-0
7.5+5.5 2
FPT1 1/2 3 (40A)FPT1 1/2 3 (40A)
1,280 1,211 790465478
80.0/90.0273,000/307,00022.8/25.6
229/258
100-67-0
7.5 3
485500
Notes:*1 Cooling capacity is based on the following conditions : Leaving chilled water temp.7 (44.5 F), entering chilled water temp.12 (53.6 F), leaving condenser water temp. 35 (95 F), entering
condenser water temp. 30 (86 F).*2 The following safety devices are equipped as standard. • High/low pressure switch. • Freeze-up protection thermostat. • Overcurrent relay for compressors. • Reverse-phase protector.
• Discharge gas overheat protector. • Fusible plug. • Safety valve.*3 This product is manufactured in Japan.
*1
8 / 9 — 80 / 90kW class
UWP 90 — 900AY 3Standard Unit
50/60Hz
S pecificationsUWD1320DY1
(40 )UWD1700DY1
(50 )UWD2000DY1
(60 )UWD2650DY1
(80 )UWD3350DY1
(100 )UWD4000DY1
(120 )Model
Cooling capacity
Power supply
Chilled water flow rate
Condenser water flow rate
Compressor
Evaporator typeCondenser typeRefrigerant
Pipeconnections
Dimensions (H W D)Weight (Approx.)Operating weight (Approx.)
TypeMotor outputCapacity control
Condenser water inlet/outletChilled water inlet/outletChilled water drain outletCondenser water drain outlet
kWBtu/hUSRT
/min
/min
kW%
mmkgkg
118403,00033.63 phase, 50 Hz 380/400/415 V, 3 wires system
338
420
Semi-hermetic sealed single screw type30 1100-70-40-0Shell and Hi-X tube typeShell and cross fin tube typeR-134aFPT3 (80A)FPT3 (80A)FPT3/4FPT1/41,600 2,320 7591,1001,220
150512,00042.7
430
534
37 1
1,702 2,600 7591,2501,390
180615,00051.2
516
640
45 1
FPT4 (100A)4B Flange (JIS10K)(100A)FPT1
1,2801,420
236806,00067.1
677
837
30 2100-70-40-20-0
FPT3 (80A)
1,623 3,330 9941,8001,980
3001,020,00085.3
860
1,068
37 2
1,745 3,338 1,0502,2002,420
3551,210,000101
1,018
1,263
45 2
FPT4 (100A)5B Flange (JIS10K)(125A)
2,3002,520
Notes:*1 Cooling capacity is based on the following conditions : Leaving chilled water temp.7 (44.5 F), entering chilled water temp.12 (53.6 F), leaving condenser water temp. 35 (95 F), entering
condenser water temp.30 (86 F).*2 The following safety devices are equipped as standard. • High/low pressure switch. • Freeze-up protection thermostat. • Overcurrent relay for compressors. • Compressor thermal
protector. • Reverse-phase protector. • Discharge gas overheat protector. • Fusible plug. • Safety valve(for UWD2000DY1,UWD4000DY1). *3 This product is manufactured in Japan.
*1
118 — 355kW class
UWD1320 — 4000DY 1Standard Unit
50Hz
Notes:*1 Cooling capacity is based on the following conditions : Leaving chilled water temp.7 (44.5 F), entering chilled water temp.12 (53.6 F), leaving condenser water temp. 35 (95 F), entering
condenser water temp.30 (86 F).*2 The following safety devices are equipped as standard. • High/low pressure switch. • Freeze-up protection thermostat. • Overcurrent relay for compressors. • Compressor thermal
protector. • Reverse-phase protector. • Discharge gas overheat protector. • Fusible plug. • Safety valve. *3 This product is manufactured in China.
S pecifications
Model
Cooling capacity
Power supplyChilled water flow rateCondenser water flow rate
Compressor
Evaporator typeCondenser typeRefrigerant
Pipeconnections
Dimensions (H W D)Weight (Approx.)Operating weight (Approx.)
TypeMotor outputCapacity control
Condenser water inlet/outletChilled water inlet/outletChilled water drain outletCondenser water drain outlet
kWBtu/hUSRT
/min /min
kW%
mmkgkg
367 — 1,450kW class
ZUW100 — 400AY 1Standard Unit
50Hz
ZUW100AY1(100RT)
ZUW120AY1(120RT)
ZUW150AY1(150RT)
ZUW175AY1(175 RT)
ZUW200AY1(200RT)
ZUW240AY1(240RT)
ZUW280AY1(280RT)
ZUW300AY1(300RT)
ZUW350AY1(350RT)
ZUW400AY1(400RT)
3671,252,1321043 phase, 50 HZ 380/400/415 V, 3 wires system1,0521,253 single screw compress37 2100 25-0 continuous capacity controlshell and tube flooded type shell and tube type R-134a5B Flange (125A) 5B Flange (125A) NPT1 1/2 1 NPT1 1/2 1 1,765 1,160 3,5303,500 3,700
4541,548,959129
1,3011,545
45 2
3,650 3,850
5081,733,196144
1,4561,727
3,750 4,000
6312,152,848179
1,8092,153
60 2
1,765 1,210 3,6803,900 4,150
7102,422,381202
2,0352,400
75 2
6B Flange (150A) 6B Flange (150A)
1,830 1,320 3,9604,750 5,050
8572,923,916244
2,4572,930
90 2
2,000 1,400 4,0005,250 5,600
1,0003,411,804284
2,8673,407
90+110
8B Flange (200A)
2,060 1,470 4,5506,650 7,100
1,1143,800,750317
3,1933,773
110 2
6,750 7,200
1,2604,298,874358
3,6124,235
130 2100 10-0 continuous capacity control
8B Flange (200A) NPT1 1/2 1, NPT1 1/4 2NPT1 1/2 1, NPT1 1/4 22,270 1,830 4,2508,300 8,900
1,4504,947,117412
4,1574,883
8,450 9,150
Notes:*1 Cooling capacity is based on the following conditions : Leaving chilled water temp.7 (44.5 F), entering chilled water temp.12 (53.6 F), leaving condenser water temp. 35 (95 F), entering
condenser water temp.30 (86 F).*2 The following safety devices are equipped as standard. • High/low pressure switch. • Freeze-up protection thermostat. • Overcurrent relay for compressors. • Compressor thermal protector.
• Reverse-phase protector. • Discharge gas overheat protector. • Fusible plug. • Safety valve.
S pecifications
Model
Cooling capacity
Power supplyChilled water flow rateCondenser water flow rate
Compressor
Evaporator typeCondenser typeRefrigerant
Pipeconnections
Dimensions (H W D)Weight (Approx.)Operating weight (Approx.)
TypeMotor outputCapacity control
Condenser water inlet/outletChilled water inlet/outletChilled water drain outletCondenser water drain outlet
kWBtu/hUSRT
/min /min
kW%
mmkgkg
441 — 1,040kW class
ZUW120 — 300AY BStandard Unit
60Hz
ZUW120AYB(120RT)
ZUW150AYB(150RT)
ZUW175AYB(175RT)
ZUW200AYB(200RT)
ZUW240AYB(240RT)
ZUW300AYB(300RT)
4411,504,6061253 phase, 60 Hz 400/440 V, 3 wires system 1,2641,517single screw compress 37 2100 25-0 continuous capacity control shell and tube flooded type shell and tube type R-134a5B Flange (125A) 5B Flange (125A) FPT1/2 FPT1/2 1,765 1,160 3,4003,800 4,000
5421,849,198154
1,5531,864
45 2
4,150 4,400
6062,067,554172
1,7372,085
4,450 4,700
7592,589,560216
2,1752,609
60 2
6B Flange (150A) 6B Flange (150A)
1,830 1,320 3,6005,100 5,400
8482,893,211241
2,4302,903
75 2
2,000 1,400 3,9605,850 6,200
1,0403,548,277296
2,9813,584
90 2
8B Flange (200A)
2,060 1,680 4,0006,350 6,800
Water Cooled Water Chillers
Wat
er C
oole
d W
ater
Chi
ller
s
Wat
er C
oole
d W
ater
Chi
ller
s
27 28
Notes:*1 Cooling capacity is based on the following conditions : Leaving chilled water temp.-5 (23.0 F), entering chilled water temp.-2 (28.4 F), leaving condenser water temp. 35 (95 F), entering
condenser water temp.30 (86 F).*2 The following safety devices are equipped as standard. • High/low pressure switch. • Freeze-up protection thermostat. • Overcurrent relay for compressors. • Compressor thermal protector.
• Reverse-phase protector. • Discharge gas overheat protector. • Fusible plug. • Safety valve.
S pecifications
Model
Cooling capacity
Power supplyChilled water flow rateCondenser water flow rate
Compressor
Evaporator typeCondenser typeRefrigerant
Pipeconnections
Dimensions (H W D)Weight (Approx.)Operating weight (Approx.)
TypeMotor outputCapacity control
Condenser water inlet/outletChilled water inlet/outletChilled water drain outletCondenser water drain outlet
kWBtu/hUSRT
/min /min
kW%
mmkgkg
233 — 555kW class
ZUW120 — 300AY B ZBrine Cooling Unit
60Hz
ZUW120AYBZ(120RT)
ZUW150AYBZ(150RT)
ZUW175AYBZ(175RT)
ZUW200AYBZ(200RT)
ZUW240AYBZ(240RT)
ZUW300AYBZ(300RT)
233794,951663 phase, 60Hz 400/440 V, 3 wires system 1,242909single screw compress 37 2100 25-0 continuous capacity control shell and tube flooded type shell and tube type R-134a5B Flange (125A) 5B Flange (125A) FPT1/2 FPT1/2 1,765 1,160 3,4003,800 4,000
290989,42382
1,5461,118
45 2
4,150 4,400
3201,091,77891
1,7061,238
4,450 4,700
4001,364,722114
2,1321,542
60 2
6B Flange (150A) 6B Flange (150A)
1,830 1,320 3,6005,100 5,400
4601,569,430131
2,4521,783
75 2
2,000 1,400 3,9605,850 6,200
5551,893,552158
2,9582,159
90 2
8B Flange (200A)
2,060 1,680 4,0006,350 6,800
Notes:*1 Cooling capacity is based on the following conditions : Leaving chilled water temp.-5 (23.0 F), entering chilled water temp.-2 (28.4 F), leaving condenser water temp. 35 (95 F), entering
condenser water temp.30 (86 F).*2 The following safety devices are equipped as standard. • High/low pressure switch. • Freeze-up protection thermostat. • Overcurrent relay for compressors. • Compressor thermal protector.
• Reverse-phase protector. • Discharge gas overheat protector. • Fusible plug. • Safety valve.
S pecifications
Model
Cooling capacity
Power supplyChilled water flow rateCondenser water flow rate
Compressor
Evaporator typeCondenser typeRefrigerant
Pipeconnections
Dimensions (H W D)Weight (Approx.)Operating weight (Approx.)
TypeMotor outputCapacity control
Condenser water inlet/outletChilled water inlet/outletChilled water drain outletCondenser water drain outlet
kWBtu/hUSRT
/min /min
kW%
mmkgkg
190 — 715kW class
ZUW100 — 400AY 1ZBrine Cooling Unit
50Hz
ZUW100AY1Z(100RT)
ZUW120AY1Z(120RT)
ZUW150AY1Z(150RT)
ZUW175AY1Z(175RT)
ZUW200AY1Z(200RT)
ZUW240AY1Z(240RT)
ZUW280AY1Z(280RT)
ZUW300AY1Z(300RT)
ZUW350AY1Z(350RT)
ZUW400AY1Z(400RT)
190648,243543 phase, 50Hz 380/400/415V, 3 wires system545730single screw compress37 2100 25-0 continuous capacity controlshell and tube flooded type shell and tube type R-134a5B Flange (125A) 5B Flange (125A) NPT1 1/2 1 NPT1 1/2 1 1,765 1,160 3,4003,500 3,700
243829,06969
697920
45 2
3,650 3,850
272928,01177
7801,032
3,750 4,000
3381,153,19096
9691,287
60 2
1,765 1,210 3,6803,9004,150
3821,303,309109
1,0951,458
75 2
6B Flange (150A) 6B Flange (150A)
1,830 1,320 3,9604,750 5,050
4591,566,018131
1,3161,758
90 2
2,000 1,400 4,0005,250 5,600
5341,821,904152
1,5312,049
90+110
8B Flange (200A)
2,060 1,470 4,5506,650 7,100
5992,043,671170
1,7172,282
110 2
6,750 7,200
6282,142,613179
1,8002,379
130 2 100 10-0 continuous capacity control
8B Flange (200A) NPT1 1/2 1, NPT1 1/4 NPT1 1/2 1, NPT1 1/42,270 1,830 4,2508,300 8,900
7152,439,440203
2,0502,723
8,450 9,150
ZUW200AY1ZUW175AY1ZUW150AY1ZUW120AY1ZUW100AY1Model
IPUDio unitD Air unitInterface for use in LONWORKS
Interface for use in BACnetCentral remote controllerUnified ON/OFF controllerSchedule timerUpgrader adaptor
DAM602A5DEC102ADAM101ADMS504B51DMS502A51DCS302CA61DCS301BA61DST301BA61GD3-ZUW100A
ZUW400AY1ZUW350AY1ZUW300AY1ZUW280AY1ZUW240AY1Model
IPUDio unitD Air unitInterface for use in LONWORKS
Interface for use in BACnetCentral remote controllerUnified ON/OFF controllerSchedule timerUpgrader adaptor
DAM602A5DEC102ADAM101ADMS504B51DMS502A51DCS302CA61DCS301BA61DST301BA61GD3-ZUW100A
Option L is t
Water Cooled Water Chillers
Wat
er C
oole
d W
ater
Chi
ller
s
Wat
er C
oole
d W
ater
Chi
ller
s
29 30
Notes:*1 Cooling capacity is based on the following conditions : Leaving chilled water temp.-5 (23.0 F), entering chilled water temp.-2 (28.4 F), leaving condenser water temp. 35 (95 F), entering
condenser water temp.30 (86 F).*2 The following safety devices are equipped as standard. • High/low pressure switch. • Freeze-up protection thermostat. • Overcurrent relay for compressors. • Compressor thermal protector.
• Reverse-phase protector. • Discharge gas overheat protector. • Fusible plug. • Safety valve.
S pecifications
Model
Cooling capacity
Power supplyChilled water flow rateCondenser water flow rate
Compressor
Evaporator typeCondenser typeRefrigerant
Pipeconnections
Dimensions (H W D)Weight (Approx.)Operating weight (Approx.)
TypeMotor outputCapacity control
Condenser water inlet/outletChilled water inlet/outletChilled water drain outletCondenser water drain outlet
kWBtu/hUSRT
/min /min
kW%
mmkgkg
233 — 555kW class
ZUW120 — 300AY B ZBrine Cooling Unit
60Hz
ZUW120AYBZ(120RT)
ZUW150AYBZ(150RT)
ZUW175AYBZ(175RT)
ZUW200AYBZ(200RT)
ZUW240AYBZ(240RT)
ZUW300AYBZ(300RT)
233794,951663 phase, 60Hz 400/440 V, 3 wires system 1,242909single screw compress 37 2100 25-0 continuous capacity control shell and tube flooded type shell and tube type R-134a5B Flange (125A) 5B Flange (125A) FPT1/2 FPT1/2 1,765 1,160 3,4003,800 4,000
290989,42382
1,5461,118
45 2
4,150 4,400
3201,091,77891
1,7061,238
4,450 4,700
4001,364,722114
2,1321,542
60 2
6B Flange (150A) 6B Flange (150A)
1,830 1,320 3,6005,100 5,400
4601,569,430131
2,4521,783
75 2
2,000 1,400 3,9605,850 6,200
5551,893,552158
2,9582,159
90 2
8B Flange (200A)
2,060 1,680 4,0006,350 6,800
Notes:*1 Cooling capacity is based on the following conditions : Leaving chilled water temp.-5 (23.0 F), entering chilled water temp.-2 (28.4 F), leaving condenser water temp. 35 (95 F), entering
condenser water temp.30 (86 F).*2 The following safety devices are equipped as standard. • High/low pressure switch. • Freeze-up protection thermostat. • Overcurrent relay for compressors. • Compressor thermal protector.
• Reverse-phase protector. • Discharge gas overheat protector. • Fusible plug. • Safety valve.
S pecifications
Model
Cooling capacity
Power supplyChilled water flow rateCondenser water flow rate
Compressor
Evaporator typeCondenser typeRefrigerant
Pipeconnections
Dimensions (H W D)Weight (Approx.)Operating weight (Approx.)
TypeMotor outputCapacity control
Condenser water inlet/outletChilled water inlet/outletChilled water drain outletCondenser water drain outlet
kWBtu/hUSRT
/min /min
kW%
mmkgkg
190 — 715kW class
ZUW100 — 400AY 1ZBrine Cooling Unit
50Hz
ZUW100AY1Z(100RT)
ZUW120AY1Z(120RT)
ZUW150AY1Z(150RT)
ZUW175AY1Z(175RT)
ZUW200AY1Z(200RT)
ZUW240AY1Z(240RT)
ZUW280AY1Z(280RT)
ZUW300AY1Z(300RT)
ZUW350AY1Z(350RT)
ZUW400AY1Z(400RT)
190648,243543 phase, 50Hz 380/400/415V, 3 wires system545730single screw compress37 2100 25-0 continuous capacity controlshell and tube flooded type shell and tube type R-134a5B Flange (125A) 5B Flange (125A) NPT1 1/2 1 NPT1 1/2 1 1,765 1,160 3,4003,500 3,700
243829,06969
697920
45 2
3,650 3,850
272928,01177
7801,032
3,750 4,000
3381,153,19096
9691,287
60 2
1,765 1,210 3,6803,9004,150
3821,303,309109
1,0951,458
75 2
6B Flange (150A) 6B Flange (150A)
1,830 1,320 3,9604,750 5,050
4591,566,018131
1,3161,758
90 2
2,000 1,400 4,0005,250 5,600
5341,821,904152
1,5312,049
90+110
8B Flange (200A)
2,060 1,470 4,5506,650 7,100
5992,043,671170
1,7172,282
110 2
6,750 7,200
6282,142,613179
1,8002,379
130 2 100 10-0 continuous capacity control
8B Flange (200A) NPT1 1/2 1, NPT1 1/4 NPT1 1/2 1, NPT1 1/42,270 1,830 4,2508,300 8,900
7152,439,440203
2,0502,723
8,450 9,150
ZUW200AY1ZUW175AY1ZUW150AY1ZUW120AY1ZUW100AY1Model
IPUDio unitD Air unitInterface for use in LONWORKS
Interface for use in BACnetCentral remote controllerUnified ON/OFF controllerSchedule timerUpgrader adaptor
DAM602A5DEC102ADAM101ADMS504B51DMS502A51DCS302CA61DCS301BA61DST301BA61GD3-ZUW100A
ZUW400AY1ZUW350AY1ZUW300AY1ZUW280AY1ZUW240AY1Model
IPUDio unitD Air unitInterface for use in LONWORKS
Interface for use in BACnetCentral remote controllerUnified ON/OFF controllerSchedule timerUpgrader adaptor
DAM602A5DEC102ADAM101ADMS504B51DMS502A51DCS302CA61DCS301BA61DST301BA61GD3-ZUW100A
Option L is t
Water Cooled Water Chillers
Wat
er C
oole
d W
ater
Chi
ller
s
Wat
er C
oole
d W
ater
Chi
ller
s
29 30
Daikin Water Chillers are of the self-contained type. This means that they are assembled, internally wired and charged with refrigerant at the factory for easy installation, only requiring external wiring and plumbing on site. They are compatible with Daikin's Air Handling and/or Fan Coil Units.
All rights reservedPrinted in Japan 11/06/005 SW.HP.ADc
DealerHead Office:Umeda Center Bldg., 2-4-12, Nakazaki-Nishi,Kita-ku, Osaka, 530-8323 Japan
Tokyo Office:JR Shinagawa East Bldg., 2-18-1, Konan,Minato-ku, Tokyo, 108-0075 Japan
http://www.daikin.com/global/
1. Air conditioners should not be installed in areas where corrosive gases, such as acid gas or alkaline gas, are produced.2. If the outdoor unit is to be installed close to the sea shore, direct exposure to the sea breeze should be avoided and choose an outdoor unit with anti-corrosion treatment.
Cautions on product corrosion
Warning Daikin Industries, Ltd.’s products are manufactured for export to numerous countries throughout the world. Daikin Industries, Ltd. does not have control over which products are exported to and used in a particular country. Prior to purchase, please therefore confirm with your local authorised importer, distributor and/or retailer whether this product conforms to the applicable standards, and is suitable for use, in the region where the product will be used. This statement does not purport to exclude, restrict or modify the application of any local legislation.Ask a qualified installer or contractor to install this product. Do not try to install the product yourself. Improper installation can result in water or refrigerant leakage, electrical shock, fire or explosion.Use only those parts and accessories supplied or specified by Daikin. Ask a qualified installer or contractor to install those parts and accessories. Use of unauthorised parts and accessories or improper installation of parts and accessories can result in water or refrigerant leakage, electrical shock, fire or explosion.Read the User's Manual carefully before using this product. The User's Manual provides important safety instructions and warnings. Be sure to follow these instructions and warnings.
If you have any enquiries, please contact your local importer, distributor and/or retailer.
Printed on 100% recycled paper with soy ink.Specifications, designs and other content appearing in this brochure are current as of November 2006 but subject to change without notice.
ISO 14001 is the standard defined by the International Organization for Standardization (ISO) relating to environmental management systems. Our group has been acknowledged by an internationally accredited compliance organisation as having an appropriate programme of environmental protection procedures and activities to meet the requirements of ISO 14001.
About ISO 14001ISO 9001 is a plant certification system defined by the International Organization for Standardization (ISO) relating to quality assurance. ISO 9001 certification covers quality assurance aspects related to the “ design, development, manufacture, installation, and supplementary service” of products manufactured at the plant.