Upload
antonio-da-silva
View
222
Download
3
Embed Size (px)
Citation preview
TECHNICAL PAPER
Parameter identification of a pneumatic proportional pressurevalve
Rodrigo Trentini • Alexandre Campos •
Guilherme Espindola • Antonio da Silva Silveira
Received: 8 September 2012 / Accepted: 15 April 2013
� The Brazilian Society of Mechanical Sciences and Engineering 2014
Abstract In this paper, the internal parameters that define
the dynamic behavior of a pneumatic pressure valve are
identified based on theoretical models and experimental
testbed observations. Pneumatic systems became an usual
solution in many industrial environments in the last years.
Their mainly advantages are the low cost, maintenance
facility and security, besides they are clean, renewable and
abundant. However, their mainly disadvantages are the
nonlinearities due to friction and air compressibility, which
difficult their modeling and control. Proportional valves
play an important role in servopneumatic applications,
although hardly ever their internal components are known,
which may cause significant errors in modeling and sim-
ulations. The theoretical valve model is stated from phys-
ical representation of pneumatic phenomena using Mass
and Energy Conservation Theory, where an eighth order
linear model is obtained. Besides, using experimental
observations and the Least Squares method, an eighth order
black-box model with known parameters is determined.
The unknown internal valve constants determination is
carried out through mathematical and black-box models
comparison, where it is found that the identified model is
able to depict the real valve behavior with errors of less
than 10 %.
Keywords Parameter identification � Pneumatic control
valves � Modeling of pneumatic systems
1 Introduction
It is well known that compressed air is one of the oldest
forms of energy, but its application in industry took place
only since 1950, where it replaced the human power in
repetitive tasks. Nowadays, compressed air became indis-
pensable in several industrial sections. Pneumatic systems
work with high efficiency, performing repetitive opera-
tions, saving time, tools and materials. Furthermore, it is a
renewable, clean, abundant and cheap energy form. Devi-
ces moved by compressed air have a high power/weight
relation, low cost, maintenance facility and flexibility in
installation. Currently, the main applications in pneumatic
field are related to linear motion with final course stopping,
among of cutting, drilling, thinning and finishing.
Lately, servopneumatics are being used when interme-
diate positions are required. These systems use actuators,
electronic systems and control valves to reach high-end
results. It is important to notice that servopneumatic
applications reduce the air consumption by up to 30 % in
comparision to standard systems [8].
However, servopneumatic systems presents several dif-
ficulties in control, as air compressibility and friction
effects. Such characteristics make the mathematical model
more complex with the inclusion of nonlinear behaviour on
Technical Editor: Alexandre Abrao.
R. Trentini (&)
Institute fur Regelungstechnik (IRT), Leibniz Universitt
Hannover (LUH), Appelstr. 11, Hannover, Germany
e-mail: [email protected]
A. Campos � G. Espindola � A. S. Silveira
Center of Technological Sciences (CCT), University of the State
of Santa Catarina (UDESC), R. Paulo Malschitzki s/n, Joinville,
Brazil
e-mail: [email protected]
G. Espindola
e-mail: [email protected]
A. S. Silveira
e-mail: [email protected]
123
J Braz. Soc. Mech. Sci. Eng.
DOI 10.1007/s40430-014-0144-0
it. Ali et al. [1] state that friction is the major difficulty to
obtain a satisfactory model. Pneumatic friction effects, like
Coulomb, static, Stribeck and viscous, cause undesired
effects as steady state and tracking errors, stick-slip
movements and limit cycles around the desired position
[5].
Due to these drawbacks, electric systems are most
commonly used in servopositioning systems than pneu-
matic ones, whereas accurate positions are not easily
reached in pneumatics [14]. Therefore, several researches
aim to minimize the nonlinearities influence using different
control strategies reaching accuracies up to 5 lm [5].
Besides the friction problem, it is important to notice
that an accurate valve model is required to improve com-
puter simulations and control design in pneumatic systems.
However, internal parts of pneumatic proportional valves
are hardly known, hence standard models are often used in
simulations. Nevertheless, researches which aim to repre-
sent the dynamical behaviour of different control valves are
being presented over the last years. For instance, Sorli et al.
[15] show a second order nonlinear model of an ordinary
proportional pressure valve using Mass and Energy Con-
servation Theory. Carneiro and Almeida [4] present a
proportional directional valve static model through artifi-
cial neural networks, reaching errors of less than 5 %.
Taghizadeh et al. [16] demonstrate a nonlinear dynamic
model of a pneumatic fast switching valve to be used with
PWM control applications. Additionally, some researchers
such as Guenther and Perondi [10], Ritter [13] and Barreto
[2] do not consider the dynamical features of pneumatic
servovalves stating that their natural frequency are much
higher than the natural frequency of the pneumatic actua-
tor. It is worth highlighting that this consideration may be
important aiming controllers design, where the goal is to
obtain a reduced model that owns the main system features.
Nevertheless, concerning to servopneumatic system simu-
lations, the valve dynamic equationing plays an important
role on its analysis.
In spite of the cited researches, the valve internal con-
stants remain unidentified, since hardly ever the valve
suppliers inform these parameters in their datasheets,
which justifies the use of computational tools to address
this issue. Hence, this paper presents a generic method for
the parameter identification of a pneumatic proportional
pressure valve using Least Squares (LS) method. A testbed
is developed, where a pressure sensor, a data acquisition
system and an electronic proportional valve are used.
In this paper, the valve description is present in Sect. 2.
The system mass conservation is analysed in Sect. 3, as
well as its mass flow rate and forces balance. Section 4
shows the valve black-box identification using LS methods,
whereas in Sect. 5 the internal parameter determination and
identification methods comparison is carried out. The study
conclusions are presented in Sect. 6.
2 Valve description
The electronic proportional pressure valves, from now on
pressure valves, are a specific case of pressure regulator
valves. This kind of valve operates by the force balance
principle, and the pressure regulation is carried out through
a plunger in opposition to a spring force, spool displace-
ment and internal pressure output [7]. Curatolo et al. [6]
state that these valves operate regulating their output
pressure proportionally to an input reference. A generic
schematic drawing of a pressure valve is shown on Fig. 1.
All of its internal components are considered with cylin-
drical shape.
The dark area on Fig. 1 shows the valve internal control
volume. The plunger, which is separated of the spool, has a
leaked part where the pressure is relieved through the
exhaustion port.
In order to understand the pressure valve operation, it is
considered a null input current/voltage on its solenoid, so
that all the internal components are positioned as on Fig. 1.
When an input signal is applied, the plunger is displaced
from top to bottom. If the produced force on the plunger
spring is higher than the spool spring force, the spool,
which at this moment is in contact with the plunger, moves
downwards so that a upstream mass of air fills the control
volume.
The air volume increment into the control volume
increases the valve internal pressure, being measured by
the pressure sensor. When the measured pressure is equal
to the reference input value, the valve internal controller
decreases the solenoid voltage until the spring force is
higher than the force applied on the spool by solenoid
itself, so that the input port is blocked. Hence, the pressure
valve stays at the position shown on Fig. 1.
Fig. 1 Electronic generic pressure valve schematic drawing. Based
on [6]
J Braz. Soc. Mech. Sci. Eng.
123
However, if the force due to the control volume pressure
is higher than the reference input, the solenoid voltage
decreases and the valve diaphagm deforms itself upwards.
Then, the spool reaches its mechanical limit and an air
volume passes through the leaked plunger, exiting the
valve through the exhaustion port until the force due to the
control volume pressure and the force due to the solenoid
are the same, so that the components return to the position
shown on Fig. 1.
An important feature of these kind of valves is the dead
band on the beginning of their operation range, which may
varies according to their internal components and
manufacturers.
In next section the mathematical modeling using Mass
and Energy Conservation Theory of a generic pressure
valve is present.
3 Mathematical model
In mathematical modeling, it is often required to reach a
trade off between model simplicity and accuracy, also
called Principle of Parsimony. However, in many cases the
simplifications are not easy to be done, and some a priori
system knowledge is required, since if some relevant
dynamics is neglect, the mathematical model may not have
the needed accuracy. In this work the main used simplifi-
cations are:
– the compressed air kinetic energy is neglected;
– the environment and air temperature are constant;
– the air is a perfect gas;
– the specific pressure and volume heat are constant;
– there are no leakages;
– the system entropy is constant.
3.1 Mass conservation
Considering the simplifications, the equating proposed in
this Section concerns to the Mass and Energy Conservation
theory used for compressed fluids presented by Fox and
McDonald [9].
Being the control volume depicted by the dark area on Fig.
1, the system mass conservation indicates that the mass
variation into the control volume is equal to the total mass
flow that enter or exit throughout the control surface [12], so:
o
ot
Z
VC
q dV þZ
SC
qv dA0 ¼ 0 ð1Þ
where dV is the volume differential, v is the fluid speed, qis the density, A0 is the control surface area and VC and SC
are the control volume and surface, respectively.
Considering that the density is invariant with the vol-
ume, the first term on Eq. 1 become:
o
ot
Z
VC
q dV ¼ qdV
dtþ V
dqdt ð2Þ
By being a compressible fluid, q is function of pressure p
and time t, or in other words, q ¼ f ðpðtÞÞ, therefore:
qdV
dtþ V
dqdt¼ q
dV
dtþ V
dqdp
dp
dtð3Þ
The term q dVdt
represents the control volume mass accu-
mulation rate due to the volume variation itself, and the
term V dqdp
dpdt
represents the control volume mass accumu-
lation due to the air compressibility [12].
The second term of Eq. 1 corresponds to the liquid fluid
flow rate, and it could be written considering the mass flow
rate as:Z
SC
qv dA0 ¼ �Dq ð4Þ
where Dq is the liquid difference between the mass flow
rates that enters and exits the system.
Therefore, replacing Eqs. 3 and 4 in Eq. 1,
Dq ¼ qdV
dtþ V
dqdp
dp
dtð5Þ
being p the pressure into the valve control volume.
The air compressibility coefficient b at a constant tem-
perature is given by the applied pressure rate and the vol-
umetric rate of a given control volume (b ¼ �Vdp=dV)
[9], so:
b ¼ qdp
dqð6Þ
Replacing Eqs. 6 in 5:
Dq ¼ qdV
dtþ Vq
bdp
dtð7Þ
For perfect gases q ¼ p=ðRTÞ, where R is the universal gas
constant and T is the absolute temperature. In addition, the
compressibility coefficient for reversible adiabatic pro-
cesses is b ¼ cp, being c the rate between the gas specific
heat for constant pressure and volume (c ¼ Cp=Cv). Then,
neglecting the control volume variation, the mass flow rates
for the control volume pressurization qm and exhaustion qe
are given respectively by:
qm ¼V
cRT_p ð8Þ
qe ¼V
cRT_p ð9Þ
J Braz. Soc. Mech. Sci. Eng.
123
3.2 Mass flow rate
The mass flow rates given by Eqs. 8 and 9 are analysed
using the mass flow equating for compressible fluid shown
also by Fox and McDonald [9]. Some considerations are
taken into account as well:
• the process is adiabatic, reversible and has high speed,
featuring an isentropic process;
• the flow is Unidirectional;
• the fluid speed is uniform;
• the stagnation pressure psup is kept constant.
Generalizing, the valve input may be considered as a
convergent nozzle. Therefore, according to Fox and
McDonald [9] there is a limit for the mass flow rate through
the nozzle, featuring that the flow is blocked and mass flow
rates at supersonic conditions are not reached.
Figure 2 shows the relation between the mass flow rate q
with the absolute stagnation down- and upstream pres-
sures—pm and pj respectively—in the pressure valve.
It is noted that from 52:8 % of the upstream pressure pm,
the mass flow rate has nonlinear behavior. Therefore, taking
into account only the linear range shown on Fig. 2, being the
absolute supply pressure psup ¼ 8 � 105 Pa and the atmo-
spheric pressure patm ¼ 1 � 105 Pa, the absolute pressure pa
into the control volume must be subjected to the restriction
1:894 � 105 Pa � pa� 4:224 � 105 Pa ð10Þ
As the pressure valve operates with manometric pressure,
the restriction become,
0:894 � 105 Pa � p� 3:224 � 105 Pa ð11Þ
which represents the restriction that the pressure p must
have so that the mass flow rate has linear feature.
Hence, the expression which represents the blocked
mass flow rate for a compressible fluid in a convergent
nozzle is [9]:
q ¼ Apm
ffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffic
RT
2
cþ 1
� �cþ1c�1
sð12Þ
where A is the control port area, which for the analised
valve depends on the spool displacement when there is no
mass flow rate through the exhaustion port. On the other
hand, whenever there is mass flow rate through the
exhaustion port, the area A depends only on the plunger
displacement. Then, it may be state that:
A ¼ k1xc for qm ð13Þ
A ¼ k2xe for qe; ð14Þ
being xc the spool displacement, xe the plunger displace-
ment, and k1 and k2 are proportionality constants between
xc and xe and the analised control port cross-sectional area,
respectively. Therefore, Eq. 12 may be written as:
qm ¼ k1kaxcpsup ð15Þ
qe ¼ k2kaxep ð16Þ
which are the final expressions for the mass flow rate, being
qm and qe the flow rate for the valve pressurization and
exhaustion, respectively, and ka ¼ffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffic
RT2
cþ1
� �cþ1c�1
r.
3.3 Force balance
The force balance on the pressure valve is given by New-
ton’s second Law. However, there are two different situa-
tions that must be analised: whenever the control volume
pressure p is lower than the regulated pressure p*, and
whenever p is higher than p*. The reason is that, whenever
p [ p* the spool displacement is mechanically limited, so
its dynamics does not influence the system pressure. These
conditions indicates the air flow direction through the valve:
when p� p* there is an air mass entering the control vol-
ume, whereas if p [ p* the air mass exhaustion happens.
On Fig. 3 is shown the valve force diagram, considering
an unidirectional diaphragm deformation, and also that the
forces FPaand Fp are uniformly distributed.
3.4 Condition 1: for p � p*
At this condition, the force balance is given by Eqs. 17 and
18:
me€xe ¼ Fsol � Fme � Fatreð17Þ
mc€xc ¼ FP � FPaþ Fme � Fatrc
� Fmc ð18Þ
where me is the plunger mass, xe is the plunger displace-
ment, Fsol is the solenoid force, Fme is the plunger spring
force, Fatreis the plunger friction force, mc is the spool
Fig. 2 Relation between down- and upstream pressures with the mass
flow rate for a compressible fluid through a nozzle. Based on [9]
J Braz. Soc. Mech. Sci. Eng.
123
mass, xc is the spool displacement, FP is the force due to
the air pressure into the control volume, Fatrcis the spool
friction force, Fmc is the spool spring force and FPaare the
atmospheric pressure force.
The solenoid force is given by:
Fsol ¼ ksu ð19Þ
being ks the solenoid constant and u the voltage input.
The plunger spring force Fme and the spool spring force
Fmc are given by:
Fme ¼ kme xe � xcð Þ ð20Þ
Fmc ¼ kmcxc ð21Þ
where kme and kmc are the spring elasticity constants of the
plunger and the spool, respectively.
The friction forces Fatreand Fatrc
are considered only
with their viscous component Bme and Bmc, being:
Fatre¼ Bme _xe ð22Þ
Fatrc¼ Bmc _xc ð23Þ
The force due to the control volume pressure FP is given
by:
FP ¼ Adp ð24Þ
where Ad is the diaphragm area.
Similarly, the force due to the atmospheric pressure FPa
is:
FPa¼ Adpatm ð25Þ
Therefore, the force balance on the pressure valve for the
condition when p � p* is given by:
€xe ¼�Bme _xe � kmexe þ ksuþ kmexc
me
ð26Þ
€xc ¼�Bmc _xc � kmc þ kmeð Þxc þ Ad patm � pð Þ þ kmexe
mc
ð27Þ
3.5 Condition 2: for p [ p*
As cited previously, whenever p [ p*, there is a mechan-
ical limit for the spool, so that its dynamics do not affect
the pressure output. Thus, using the same analysis shown
previously, the force balance for the cited condition is:
€xe ¼�Bme _xe � kmexe þ Ad patm � pð Þ þ ksu
me
ð28Þ
3.6 Linear model
The complete model of the pressure valve, taking into
account only the linear range of the mass flow rate, is
depicted by Eqs. 8, 26 and 27—using also Eq. 15—for the
control volume pressurization condition, which are linear.
For the exhausting condition, the mathematical model is
depicted by Eqs. 9 and 28—using also Eq. 16—, which are
nonlinear due to the multiplication of two system states in
Eq. 16, named xe and p.
Using Taylor series for the system linearization, the
equilibrium points for the condition p [ p* are obtained
considering _p ¼ _xe ¼ €xe ¼ 0. Assuming that the control
volume equilibrium pressure is different than zero, it is
obtained:
xe ¼ 0
p ¼ ks
Ad
u:ð29Þ
Hence, expanding Eq. 16 in Taylor series and neglecting
the terms with order higher than one:
qe ¼ k2kapxe ¼ 0
A ¼ oqe
oxe
����p¼p
¼ k2kap
B ¼ oqe
op
����xe¼xe
¼ 0
Then, the linearized equation for the mass flow rate
exhaustion qe is given by,
Fig. 3 Pressure valve force
diagram
J Braz. Soc. Mech. Sci. Eng.
123
qe � qe þ A xe � xeð Þ þ B p� pð Þ� k2kapxe
ð30Þ
Considering only the manometric pressure (patm ¼ 0) and
converting the equations to Laplace complex domain, after
some algebraic manipulations the control volume dynamics
for the pressurization and exhaustion conditions are
depicted respectively by:
PðsÞUðsÞ ¼
c1
s5 þ c2s4 þ c3s3 þ c4s2 þ c5sþ c6
ð31Þ
PðsÞUðsÞ ¼
c7
s3 þ c8s2 þ c9sþ c10
ð32Þ
where,
c1 ¼k1kakmekspsupcRT
mcmeðVi þ VaÞ
c2 ¼Bmcme þ Bmemc
mcme
c3 ¼ðkme þ kmcÞme þ kmemc þ BmcBme
mcme
c4 ¼Adk1kamepsupcRT þ ðBme þ BmcÞkme þ Bmekmc½ �ðVi þ VaÞ
mcmeðVi þ VaÞ
c5 ¼AdBmek1kapsupcRT þ kmckmeðVi þ VaÞ
mcmeðVi þ VaÞ
c6 ¼Adk1kakmepsupcRT
mcmeðVi þ VaÞ
c7 ¼k2kapkscRT
meðVi þ VaÞ
c8 ¼Bme
me
c9 ¼kme
me
c10 ¼k2kapAdcRT
meðVi þ VaÞ
4 Black-box model
This Section describes the black-box pressure valve iden-
tification using LS method based on the valve mathemati-
cal model presented in the previous section, in order to
obtain the internal valve parameters values.
Converting Eqs. 31 and 32 to complex discrete time
domain using Euler Method and considering the sampling
input delay, the pressurization and exhaustion conditions
are depicted respectively by:
Pðz�1ÞUðz�1Þ ¼
b0z�1
1þ a1z�1 þ a2z�2 þ a3z�3 þ a4z�4 þ a5z�5for p � p�
ð33Þ
Pðz�1ÞUðz�1Þ ¼
b1z�1
1þ a6z�1 þ a7z�2 þ a8z�3for p [ p�
ð34Þ
being,
b0 ¼ c1t5s a4 ¼ c5t4
s � 2c4t3s þ 3c3t2
s � 4c2ts þ 5
b1 ¼ c7t3s a5 ¼ c6t5
s � c5t4s þ c4t3
s � c3t2s þ c2ts � 1
a1 ¼ c2ts � 5 a6 ¼ c8ts � 3
a2 ¼ c3t2s � 4c2ts þ 10 a7 ¼ c9t2
s � 2c8ts þ 3
a3 ¼ c4t3s � 3c3t2
s þ 6c2ts � 10 a8 ¼ c10t3s � c9t2
s þ c8ts � 1
ð35Þ
where ts is the sampling time.
The experiments are carried out using a testbed
composed by an electronic pressure valve, a pressure
sensor and a data acquisition system, consisted by an
electronic board and computational software. In Table
1 is shown the main characteristics of the used devi-
ces, whereas Fig. 4 presents the testbed schematic
drawing.
An initial step experiment is carried out in order to
verify the acquisition system sampling time. Besides, the
manufacturer datasheet states that each 1 V on the valve
input corresponds to 0:9 � 105 Pa on the valve output (in
steady state), with a linear behavior. Hence, an 1.4 V step
input is applied on the system at t ¼ 0, considering a
system previous manometric pressure of 0:9 � 105 Pa.
Additionally, the used valve allows some external tuning in
order to make faster or slower the output response. In the
performed experiment, the pressure output was empirically
subjected to not have overshoot. The experiment result is
shown on Fig. 5.
It is noted in Fig. 5 that the experimented curve may be
approximated to a first order with transport delay system,
so that its time constant s is determined, neglecting the 0.3
s delay, as being s ¼ 0:3 s, allowing the maximum board
data acquisition time (ts ¼ 0:005 s).
Assuming that the output pressure behavior is linear
within the range of interest where the mass flow rate is also
linear (0:894 � 105 Pa � p � 3:224 � 105 Pa ), the valve
linearity features do not need to be experimented. There-
fore, the system is submitted to the increasing and
decreasing step experiment shown on Fig. 6.
Table 1 Testbed used devices
Component Brand Part number
Electronic pressure
valve
SMC ITV
1050-31F1BL3
Pressure sensor Sensata
technologies
100CP2-74
Data acquisition board National
instruments
NI USB-6009
J Braz. Soc. Mech. Sci. Eng.
123
Considering the cited linear pressure valve model, the
parameter identification using Least Squares method is
presented in the following section.
4.1 Least squares identification
In many science fields, the linear system parameters
determination is often carried out using Least Squares (LS)
method, which was proposed by Karl Friedrich Gauss at
the end of the eighteenth century.
The non-recursive LS method is used in offline batched
analisys, or in other words, it is assumed that all the input
and output data are available for the estimation algorithm.
The estimated parameters vector H is given by [11]:
H ¼ WTW� �1
WTY: ð36Þ
where W is the regressors matrix and Y is the experimental
output data vector, which in this paper are given by,
W ¼
�pðk � 1Þ � pðk � 2Þ � pðk � 3Þ xpðk � 1Þ... ..
. ... ..
.
�pðN � 1Þ � pðN � 2Þ � pðN � 3Þ xpðN � 1Þ
2664
3775
Y ¼
pðkÞ...
pðNÞ
2664
3775
being k the discrete time and N the experimented data
number. It is important to notice that, in order to better fit
the experimented and estimated parameters, the input and
output vector are considered with zero mean.
Two different parameters estimation are performed,
according to the linear valve conditions presented in Eqs.
33 and 34. For the cited conditions, the identified param-
eters using LS method are:Fig. 4 Testbed schematic drawing
Fig. 5 Pressure valve time
constant
Fig. 6 Step experiment
J Braz. Soc. Mech. Sci. Eng.
123
b0 ¼ 73:40 b1 ¼ 88:72 a1 ¼ �1:084
a2 ¼ �0:296 a3 ¼ 0:043
a4 ¼ 0:219 a5 ¼ 0:118 a6 ¼ �1:333
a7 ¼ �0:217 a8 ¼ 0:551
ð37Þ
5 Internal parameter determination
The identification of the empirical parameters shown in the
previous sections allows the internal pressure valve
unknown constant determination.
The access to the valve diaphragm is obtained through
four screws, according to Fig. 7, so that the diaphragm area
is measured.
Solving the linear system composed by the equations
shown in (35) using the identified values presented in (37)
in addition to Eq. 29 and considering the viscous friction
components Bme ¼ Bmc ¼ 12 Ns/m according to Carducci
et al. [3], the identified valve parameters are presented in
Table 2. The system constants are shown in Table 3.
In Fig. 8 is shown the model validation using the
experimented parameters obtained with LS method, con-
sidering only the valve linear behavior range (0:894 � 105
Pa � p � 3:224 � 105 Pa). The validation input is given by
random steps.
In order to evaluate the identification method, the fitting
coefficient shown in Eq. 38 is used, being y, y and y the
measured, the estimated and the mean value of the mea-
sured output, respectively.
fit ¼ 100 � 1� jjy� yjjjjy� yjj
� �¼ 91:66 %: ð38Þ
6 Conclusions
Although pneumatics is widely known as an important
alternative way to control mechanical systems, its intrinsic
issues, such as friction, air compressibility and unknown
valve internal parameters, hamper the modeling and con-
trol of such systems.
Fig. 7 Access to the valve diaphragm
Table 2 Identified internal
pressure valve parametersParameter (unity) LS
me (kg) 35:99 � 10�3
mc (kg) 26:68 � 10�3
kme (N/m) 168:45
kmc (N/m) 1434:31
k1 (m) 8:52 � 10�7
k2 (m) 6:51 � 10�7
ks (C/m) 102:92
Table 3 System constants
Parameter Value (Unity) Parameter Value (unity)
c 1:4 [1] R 287:04 [J/(K� kg)]
Ad 1:16 � 10�3 (m2) T 298 (K)
psup 8 � 105 (Pa) ka 2:34 � 10�3 (s/m)
Bme 12 (Ns/m) Bmc 12 (Ns/m)
Vi 6 � 10�6 (m3) Va 140:74 � 10�6 (m3)
u 2:25 (V) ts 0:005 (s)
Fig. 8 Model validation
J Braz. Soc. Mech. Sci. Eng.
123
In this paper, it is shown a systematic way to determine
the internal parameters of a proportional pressure valve
working within its linear mass flow rate range. The study is
performed using Mass and Energy Conservation Theory in
conjunction with empirical experiments that use Least
Squares (LS) method, so that the valve internal parameters
are determined through the analytic and empiric models
comparison. The result shows that the identified parameters
are able to depict the system dynamic behavior with an
accuracy of 91.66 %.
In further studies it will be investigated the full range
identification of the used pressure valve through nonlinear
methods, such as Particle Swarm Identification (PSO).
Acknowledgments R. Trentini acknowledges the financial support
of the Brazilian Research Agency (CNPq).
References
1. Ali HI, Bahari S, Noor BM, Bashi SM, Marhaban MH (2009) A
review of pneumatic actuators (modeling and control). Austral J
Basic Appl Sci 3(2):440–454
2. Barreto F (2003) Modelagem e controle nao-lineares de um
posicionador servopneumatico industrial. Master’s thesis, Uni-
versidade Federal de Santa Catarina, Florianopolis
3. Carducci G, Giannoccaro NI, Messina A, Rollo G (2006) Iden-
tification of viscous friction coefficients for a pneumatic system
model using optimization methods. Math Comp Simul
71(71):385–394
4. Carneiro JF, Almeida FG (2006) Modeling pneumatic servoval-
ves using neural networks. Computer aided control system
design. In: 2006 IEEE International Conference on Control
Applications, 2006 IEEE International Symposium on Intelligent
Control, 2006 IEEEMunique, DE, pp 790–795
5. Carneiro JF, Almeida FG (2011) Undesired oscillations in
pneumatic systems. In: Nonlinear science and complexity,
Springer, Netherlands, pp 229–243
6. Curatolo D, Hoffmann M, Stein B (2003) Festo: FluidSIM 3.6
Pneumatik - Handbuch, Universitat Paderborn, Paderborn, DE
7. Dall’Amico R (2011) SMC Pneumaticos do Brasil: Fundamentos
da Pneumatica II
8. Festo (2010) Servopneumatics, Denkendorf, DE
9. Fox RW, McDonald AT (1985) Introduction to fluid mechanics.
Wiley, New York
10. Guenther R, Perondi EA (2004) O controle em cascata de um
sistema pneumatico de posicionamento. Revista Controle &
Automacao 15:149–161
11. Ljung L (1987) System identification: theory for the user.,
Prentice-Hall information and system sciences seriesPrentice-
Hall, USA
12. Perondi E (2002) Controle nao-linear em cascata de um servo-
posicionador pneumatico com compensacao do atrito. Ph.D. the-
sis, Universidade Federal de Santa Catarina-UFSC, Florianopolis
13. Ritter CS (2010) Modelagem matematica das caracterısticas nao-
lineares de atuadores pneumaticos. Master’s thesis, Universidade
Regional do Nordeste do Estado do Rio Grande do Sul-UNIJUI,
Brazil
14. Scholz D, Zimmermann A (1993) Pneumatic NC Axes, vol 1.
Festo Didactic KG, Esslingen
15. Sorli M, Figliolini G, Pastorelli S (2001) Dynamic model of a
pneumatic proportional pressure valve. IEEE/ASME Intern Conf
Adv Intell Mechatron 1:630–635
16. Taghizadeh M, Ghaffari A, Najafi F (2009) Modeling and iden-
tification of a solenoid valve for PWM control applications.
Comptes Rendus Mecanique 337:131–140
J Braz. Soc. Mech. Sci. Eng.
123