A l i   D a n e s h p o o y ,   P h D ,   P E

Over‐voltages In Inverter‐based Systemsi‐PCGRID 2019 Workshop

Page 2: Over‐voltages In Inverter‐based Systems i‐PCGRID 2019 Workshop Daneshpooy... · Symmetrical component analysis can provide practical insight Sequence impedance of the Inverter

Confidential & Proprietary  |  Copyright  © 2019 Slide  2

Contents

Inverter vs. Conventional Voltage stresses Inverter TOV Grounding system Analysis methods Mitigation

Page 3: Over‐voltages In Inverter‐based Systems i‐PCGRID 2019 Workshop Daneshpooy... · Symmetrical component analysis can provide practical insight Sequence impedance of the Inverter

Confidential & Proprietary  |  Copyright  © 2019 Slide  3

Introduction

Page 4: Over‐voltages In Inverter‐based Systems i‐PCGRID 2019 Workshop Daneshpooy... · Symmetrical component analysis can provide practical insight Sequence impedance of the Inverter

Confidential & Proprietary  |  Copyright  © 2019 Slide  4

Inverter vs. Rotating Machine

Rotating machines (conventional): Synchronous and Induction (Types 1&2)– Rotating Inertia: Synchronous generator demonstrates continuous

frequency response.• Synchronous voltage cannot jump• Inverter is based on PLL and software generated, limited to dc cap voltage

– Magnetic Inertia: Large short circuit current.• Large units are cooled using liquid or gas• Synchronous: 8-10 times rated current• Induction: 5-6 times the rated current

Note: The above list neither is exclusive nor complete.

Page 5: Over‐voltages In Inverter‐based Systems i‐PCGRID 2019 Workshop Daneshpooy... · Symmetrical component analysis can provide practical insight Sequence impedance of the Inverter

Confidential & Proprietary  |  Copyright  © 2019 Slide  5

Inverter vs. Rotating machine

Inverter: – Current limited switching devices– GTO, IGBT: Semiconductor wafer is thin and expensive– Low thermal inertia– Losses: I2R, Switching losses– Maximum current is the design criteria– Short circuit current < 1.4 times the rated current (large units 1.1)

– Six-pulse bridge• DC AC

Note: The above list neither is exclusive nor complete.

Page 6: Over‐voltages In Inverter‐based Systems i‐PCGRID 2019 Workshop Daneshpooy... · Symmetrical component analysis can provide practical insight Sequence impedance of the Inverter

Confidential & Proprietary  |  Copyright  © 2019 Slide  6

Inverter vs. Rotating Machine

Dominant sources of energization of power systems have been synchronous generators.– Represented in power system analysis by a constant ac voltage source

in series with a reactance. Inverter-based generators, however, generally behave like constant

ac current (or power) sources. – Current source characteristic has impact on the overvoltages caused by

ground faults,

Assessment of system grounding, as defined in IEEE Std. C62.92, must properly consider behavior if inverter-coupled power sources dominate in a system.

Page 7: Over‐voltages In Inverter‐based Systems i‐PCGRID 2019 Workshop Daneshpooy... · Symmetrical component analysis can provide practical insight Sequence impedance of the Inverter

Confidential & Proprietary  |  Copyright  © 2019 Slide  7

Inverter Voltage Performance

Voltage ride-through (PRC-024-2)

Above 120% for0.16 s, ~ 10 cycles

Inverter does not generate TOV above 120% for morethan 10 cycles. – Canyon 2 Fire (NERC)– 400 MW OV tripping

Page 8: Over‐voltages In Inverter‐based Systems i‐PCGRID 2019 Workshop Daneshpooy... · Symmetrical component analysis can provide practical insight Sequence impedance of the Inverter

Confidential & Proprietary  |  Copyright  © 2019 Slide  8

Overvoltages

Over-voltage protection is typically provided using Surge Arresters. – Surge arresters demonstrate low resistance for voltages above their

MCOV and high resistance for voltages below their MCOV.– Limits transient overvoltages –not intended to limit temporary

overvoltages. – Temporary overvoltages are caused by faults, load rejection, line

energizing, resonance conditions, ferro-resonance, or by some combination of these factors.

– Note: inverters are harmonic sources, which can contribute to resonance conditions.

Page 9: Over‐voltages In Inverter‐based Systems i‐PCGRID 2019 Workshop Daneshpooy... · Symmetrical component analysis can provide practical insight Sequence impedance of the Inverter

Confidential & Proprietary  |  Copyright  © 2019 Slide  9

Arrester Power Frequency vs. Time

𝑉𝑉

Source: ABB

TOV ratio versus arrester rated voltage drops with time.

Arrester cannot handle 133% TOV longer than 1 second.

Page 10: Over‐voltages In Inverter‐based Systems i‐PCGRID 2019 Workshop Daneshpooy... · Symmetrical component analysis can provide practical insight Sequence impedance of the Inverter

Confidential & Proprietary  |  Copyright  © 2019 Slide  10

Ground Fault

Page 11: Over‐voltages In Inverter‐based Systems i‐PCGRID 2019 Workshop Daneshpooy... · Symmetrical component analysis can provide practical insight Sequence impedance of the Inverter

Confidential & Proprietary  |  Copyright  © 2019 Slide  11

Ground Fault Overvoltage When a feeder is disconnected, the voltage of feeder collapse due

to lack sources.

Feeders with DER– island detection can be

up to 2 seconds.

Transmission-connectedcan have no load connected.

Source: IEEE

Page 12: Over‐voltages In Inverter‐based Systems i‐PCGRID 2019 Workshop Daneshpooy... · Symmetrical component analysis can provide practical insight Sequence impedance of the Inverter

Confidential & Proprietary  |  Copyright  © 2019 Slide  12

Ground Fault Overvoltage

Study methodologies Symmetrical component

– +/-/0 components Phasor study

– Ac system analysis Time domain

– Inverter control scheme• Proprietary models

– Many manufacturers provide compiled code in PSCAD Source: EPRI

Page 13: Over‐voltages In Inverter‐based Systems i‐PCGRID 2019 Workshop Daneshpooy... · Symmetrical component analysis can provide practical insight Sequence impedance of the Inverter

Confidential & Proprietary  |  Copyright  © 2019 Slide  13

Ground Fault Overvoltage

Inverters control scheme identifies and arrest conditions outside pre-determined thresholds. – Transformer can impact inverter fault identification.

Symmetrical Components: Inverter (current source mode) – Positive sequence: constant current source.

• Phase inductor can be ignored. – Negative sequence: Dependent on control philosophy

• Can range from phase inductor to infinity. • May actively cancel negative sequence currents

– Zero sequence:• w/o neutral connection: Open circuit (more common) • w/ neutral connection: Dependent on control philosophy, can range from

phase inductor to infinity.– Not valid under saturated condition (voltage source at limited output)

Page 14: Over‐voltages In Inverter‐based Systems i‐PCGRID 2019 Workshop Daneshpooy... · Symmetrical component analysis can provide practical insight Sequence impedance of the Inverter

Confidential & Proprietary  |  Copyright  © 2019 Slide  14

Ground Fault Overvoltage

Sym. Components: Load– +/-/0: Shunts– Depending on the

load type: Commercial, Residential, Motor, Service transformer

I1: pre-fault value Z2: Variable, worst case ZGT: Typically open circuit

ZL1=ZL2= V2/Sload

ZL0: Critical & Load dependent

I1 ZL1V1

ZL2V2

ZL0V0

Z2

ZGT

Positive sequence

Negative sequence

Zero sequence

Page 15: Over‐voltages In Inverter‐based Systems i‐PCGRID 2019 Workshop Daneshpooy... · Symmetrical component analysis can provide practical insight Sequence impedance of the Inverter

Confidential & Proprietary  |  Copyright  © 2019 Slide  15

Ground Fault Overvoltage

How good the system is grounded? Effectively grounded:

– Grounded through a connection of sufficiently low impedance (inherent, intentionally added or both) that a ground fault that may occur cannot build up voltages in excess of limits established for apparatus, circuits, or systems so grounded.

– Coefficient of Grounding is the ratio of the highest line-ground voltage during a fault to the line-line voltage with fault removed (location).

– COG does not exceed 80%; i.e. 0.8ꞏ√3 = 1.386. • ratio of the zero-sequence reactance to the positive-sequence reactance

(X0/X1) is positive and < 3, and • ratio of the zero-sequence resistance to the positive-sequence reactance

(R0/X1) is positive and < 1.

Source: IEEE

Page 16: Over‐voltages In Inverter‐based Systems i‐PCGRID 2019 Workshop Daneshpooy... · Symmetrical component analysis can provide practical insight Sequence impedance of the Inverter

Confidential & Proprietary  |  Copyright  © 2019 Slide  16

Non-fault Situations

High Inverter Output to Load ratios– For an isolated DER and load an overvoltage can result if the source

power output exceeds the load demand. – Load Rejection Overvoltage (LROV)– Constant current (source) x Constant impedance (load)

• Grounding is irrelevant– Compounded with ground fault may result in TOV, where the sequence

components become unsuitable, and time domain analysis including emtp-type studies will be needed.

Source: IEEE

Page 17: Over‐voltages In Inverter‐based Systems i‐PCGRID 2019 Workshop Daneshpooy... · Symmetrical component analysis can provide practical insight Sequence impedance of the Inverter

Confidential & Proprietary  |  Copyright  © 2019 Slide  17

Impact of supplemental ground Pre-fault

Post-fault– α: ratio of pre-fault

generationto connected load

Ground Fault Overvoltage

ZL

V0

V2

αZL1

αZL0 Load solidly groundedZGT

αZL20→∞   Z2

V1

V

Page 18: Over‐voltages In Inverter‐based Systems i‐PCGRID 2019 Workshop Daneshpooy... · Symmetrical component analysis can provide practical insight Sequence impedance of the Inverter

Confidential & Proprietary  |  Copyright  © 2019 Slide  18

0 0.2 0.4 0.6 0.8 1 1.2 1.4 1.60

0.2

0.4

0.6

0.8

1

1.2

1.4

1.6

Z2 = InifinityZ2 = 0.02+j0.3Z2 = 0.1+j1

Generation/Load ratio (alpha)

Max

. Pha

se v

olta

ge (p

u)

Maximum phase voltage vs. pre-fault current

Excess generation Can be compounded

with load rejectionovervoltage (LROV)– Inverter controls

only the LROV

Load pf = 1.0 GT = Infinite

Ground Fault Overvoltage

1.13

Page 19: Over‐voltages In Inverter‐based Systems i‐PCGRID 2019 Workshop Daneshpooy... · Symmetrical component analysis can provide practical insight Sequence impedance of the Inverter

Confidential & Proprietary  |  Copyright  © 2019 Slide  19

Non‐effective

Effective

0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 11

1.1

1.2

1.3

1.4

1.5

1.6

1.7

1.8

pf = 1pf = 0.9 lagpf = 0.9 lead

Ratio of Grounded load

Max

. Pha

se v

olta

ge (p

u)

Maximum phase voltage vs. Ratio of grounded load

Load = Generation Impact of load pf on TOV

– Over-compensation– Ungrounded load

– Z2 = 0.1+j1– GT = Infinite

Ground Fault Overvoltage

1.39 = 0.8 x √3

Page 20: Over‐voltages In Inverter‐based Systems i‐PCGRID 2019 Workshop Daneshpooy... · Symmetrical component analysis can provide practical insight Sequence impedance of the Inverter

Confidential & Proprietary  |  Copyright  © 2019 Slide  20

Impact of inverter negative sequence

Sensitive for large X2/R2

Load = Generation Pf = 1.0 GT = Infinite

Ground Fault Overvoltage

0.01 0.1 1 10 1000.8

0.85

0.9

0.95

1

1.05

1.1

1.15

1.2

X2/R2 = 10X2/R2 = 1X2/R2 = 0.1

Inverter X2 (pu)

Max

. Pha

se v

olta

ge (p

u)

Page 21: Over‐voltages In Inverter‐based Systems i‐PCGRID 2019 Workshop Daneshpooy... · Symmetrical component analysis can provide practical insight Sequence impedance of the Inverter

Confidential & Proprietary  |  Copyright  © 2019 Slide  21

0 0.2 0.4 0.6 0.8 1 1.2 1.4 1.60

0.2

0.4

0.6

0.8

1

1.2

1.4

1.6

w/o GT, Load pf=1.0w/GT, Load pf=1.0w/GT, Load pf = 0.9 lagw/GT, Load pf=0.9 leadw/o GT, Load pf=0.9 lead

Generation/Load ratio (alpha)

Max

. Pha

se v

olta

ge (p

u)

Impact of supplemental ground

XGT = 0.6 pu– X/R = 4

Z2 large– Active cancelation

TOV increases with GT

Depends on pf

Ground Fault Overvoltage

1.1

Page 22: Over‐voltages In Inverter‐based Systems i‐PCGRID 2019 Workshop Daneshpooy... · Symmetrical component analysis can provide practical insight Sequence impedance of the Inverter

Confidential & Proprietary  |  Copyright  © 2019 Slide  22

Impact of supplemental grounding Grounding may

increase TOV

Load = Generation Pf = 1

Ground Fault Overvoltage

0.1 1 10 1000.5

0.6

0.7

0.8

0.9

1

1.1

1.2

Z2 = 0.02+j0.3Z2 = 0.1+j1.0Z2 = Infinite

Inverter X0 (pu)

Max

. Pha

se v

olta

ge (p

u)

GT impedance (pu)

Page 23: Over‐voltages In Inverter‐based Systems i‐PCGRID 2019 Workshop Daneshpooy... · Symmetrical component analysis can provide practical insight Sequence impedance of the Inverter

Confidential & Proprietary  |  Copyright  © 2019 Slide  23

Additional Cases

Page 24: Over‐voltages In Inverter‐based Systems i‐PCGRID 2019 Workshop Daneshpooy... · Symmetrical component analysis can provide practical insight Sequence impedance of the Inverter

Confidential & Proprietary  |  Copyright  © 2019 Slide  24

Other Situations

Constant Power Regulation– Fault normally causes a decrease in the voltage.– If the source regulates power the current increases to maintain

reference power level.– Thus it can increase the un-faulted phase voltages. – Practically constant power control is implemented as an outer loop,

hierarchical, and is sufficiently slow. • Thus the source will trip.

– In case of faster scheme, feed-forward, it can cause voltage rise proportional to the allowable current; i.e. 110-120%

Source: IEEE

Page 25: Over‐voltages In Inverter‐based Systems i‐PCGRID 2019 Workshop Daneshpooy... · Symmetrical component analysis can provide practical insight Sequence impedance of the Inverter

Confidential & Proprietary  |  Copyright  © 2019 Slide  25

Load Unbalanced– The simple sequence network is not valid for substantial phase

unbalance under islanded mode. • Detailed network or time-domain analysis

Zero-sequence Isolation– COG =100%

• Full neutral shift– Load < 125% Inverter P

• Mitigation needed

Other Situations

ZT0

• V=√3I1ZL• V2 = 0• V1=‐V0

ZLV1

ZLV2

V0

Z2

Page 26: Over‐voltages In Inverter‐based Systems i‐PCGRID 2019 Workshop Daneshpooy... · Symmetrical component analysis can provide practical insight Sequence impedance of the Inverter

Confidential & Proprietary  |  Copyright  © 2019 Slide  26

Single-phase inverters may not be aware of other phases– 120° separation not guaranteed

Load balanced and grounded star connected. – No inter-phase coupling– No overvoltages during ground fault

Banks of single-phase sources w/o coordinated control

ZY

Page 27: Over‐voltages In Inverter‐based Systems i‐PCGRID 2019 Workshop Daneshpooy... · Symmetrical component analysis can provide practical insight Sequence impedance of the Inverter

Confidential & Proprietary  |  Copyright  © 2019 Slide  27

Single-phase inverters may not be aware of other phases– 120° separation not guaranteed

Load balanced, but not grounded – Post-fault the current sources of un-faulted phases will be in-phase – Un-faulted phase voltage IsourceꞏZY = IsourceꞏZΔ/3– If pre-fault output exceeds ⅓ of the load, sources reach their output

voltage limits

Banks of single-phase sources w/o coordinated control

ZY=ZΔ/3 ZΔ

Page 28: Over‐voltages In Inverter‐based Systems i‐PCGRID 2019 Workshop Daneshpooy... · Symmetrical component analysis can provide practical insight Sequence impedance of the Inverter

Confidential & Proprietary  |  Copyright  © 2019 Slide  28

Single-phase inverters may not be aware of other phases– 120° separation not guaranteed

Load balanced, but not grounded– Post-fault the current sources of un-faulted phases will be in-phase. – Un-faulted phase voltage IsourceꞏZY = IsourceꞏZΔ/3– If pre-fault output exceeds ⅓ of the load, sources may reach their output

voltage limits

Banks of single-phase sources w/o coordinated control

ZY ZY

ZY        ↓I=0

Page 29: Over‐voltages In Inverter‐based Systems i‐PCGRID 2019 Workshop Daneshpooy... · Symmetrical component analysis can provide practical insight Sequence impedance of the Inverter

Confidential & Proprietary  |  Copyright  © 2019 Slide  29

Mitigation measures

Effective grounding– COG is the measure

Adequate load relative to Inverter Output– Supplemental ground may be needed

Coordinated transfer trip– Inverter disconnected before feeder opens

Fast Inverter overvoltage tripping– Inverter may not see TOV on primary side

Fast islanding detection Sacrificial arrester

– Difficult

Page 30: Over‐voltages In Inverter‐based Systems i‐PCGRID 2019 Workshop Daneshpooy... · Symmetrical component analysis can provide practical insight Sequence impedance of the Inverter

Confidential & Proprietary  |  Copyright  © 2019 Slide  30

Conclusion

Ground fault on inverter-based systems can cause TOV Symmetrical component analysis can provide practical insight Sequence impedance of the Inverter and load can impact the

resultant TOV Time domain simulation, including inverter control scheme, provides

better resolution Inductive supplemental grounding can increase TOV Islanding can compound TOV due to mismatch between DER power

to connected load, LROV, worsens under reverse power flow Better modelling should be used for planning studies

Page 31: Over‐voltages In Inverter‐based Systems i‐PCGRID 2019 Workshop Daneshpooy... · Symmetrical component analysis can provide practical insight Sequence impedance of the Inverter

Confidential & Proprietary  |  Copyright  © 2019 Slide  31

References

1. IEEE Std. C62.92, “Guide for Application of Neutral Grounding in Electrical Utility Systems”, Parts I & VI

2. IEEE Std. 1313.1, “Standard for Insulation Coordination”3. UL-1742, “Standard for Inverters, Converters, Controllers and Interconnection System

Equipment for Use With Distributed Energy Resources” 4. IEEE Std. 1547, “Standard for Interconnecting Distributed Resources with Electric Power

Systems” 5. NERC, “Recommended Practices for Modeling Momentary Cessation”