  • OUTSULATION® PE SYSTEM™ A Pressure – Equalized Rainscreen Exterior Insulation and Finish System With Moisture Drainage That Incorporates Continuous Insulation and An Air/Water-Resistive Barrier

    Outsulation PE System Installation Details

    DS846

  • OUTSULATION® PE SYSTEM®

    - GROOVE PATTERN

    DRYVIT SYSTEMS, INC. MAKES NO REPRESENTATIONREGARDING CONFORMITY OF ITS SUGGESTIONS TO MODELBUILDING CODES, ENGINEERING CRITERIA, SPECIFICAPPLICATIONS OR PROJECT LOCATIONS. ALL COMPONENTSINDICATED IN ILLUSTRATIONS, AS WELL AS OTHERS THATMAY BE REQUIRED FOR THE INTEGRITY OF THE SYSTEMSHALL BE DESIGNED, DETAILED AND ENGINEERED BYREPRESENTATIVES OF THE ARCHITECT, OWNER ORCONTRACTOR TO BE IN CONFORMANCE WITH MODEL CODES,ARCHITECTURAL AND ENGINEERING REQUIREMENTSPERTAINING TO SPECIFIC BUILDING PROJECTS.

    DRYVIT SYSTEMS, INC. MAKES NO WARRANTY, EXPRESSEDOR IMPLIED, AS TO THE ARCHITECTURAL DESIGN,ENGINEERING, OR WORKMANSHIP OF PROJECTS UTILIZINGDRYVIT SYSTEMS OR PRODUCTS.

    THE LIABILITIES OF DRYVIT SYSTEMS, INC. SHALL BE ASSTATED IN THE OUTSULATION PE LIMITED COMMERCIALWARRANTY. CONTACT DRYVIT SYSTEMS, INC. FOR A FULLAND COMPLETE COPY OF THE OUTSULATION PE WARRANTY.

    TABLE OF CONTENTS

    NOTE

    OSPE 0.0.02

    HEAD/SILL

    DETAIL

    OUTSULATION PE SYSTEM

    INSULATION BOARD LAYOUT

    INSULATION BOARD

    FOUNDATION

    PARAPET - STEEL FRAMED,

    OUTSIDE CORNER- INSULATION BOARD LAYOUT

    TERMINATION AT CONCRETE

    PARAPET - SOLID SUBSTRATE,

    INSIDE/OUTSIDE CORNERSOUTSIDE CORNER - HIGH IMPACT

    METAL COPING

    METAL COPING

    BUILDING FACADE

    JAMB

    OSPE 0.0.14OSPE 0.0.13

    OSPE 0.0.12

    OSPE 0.0.11OSPE 0.0.10OSPE 0.0.09OSPE 0.0.08

    OSPE 0.0.06

    OSPE 0.0.05

    OSPE 0.0.04OSPE 0.0.03

    OSPE 0.0.01

    OSPE 0.0.15

    COMPARTMENT SEPARATION OSPE 0.0.07

    SOFFIT/FASCIA INTERSECTION

    VERTICAL EXPANSION JOINT OPTIONS

    HORIZONTAL EXPANSION JOINT

    MINOR PENETRATIONS

    HORIZONTAL SLIP JOINT

    MAJOR PENETRATIONS

    AESTHETIC REVEALSPROJECTING GRAPHICSRECESSED GRAPHICSDRYVIT VENT ASSEMBLY™

    SIGN ATTACHMENT

    OSPE 0.0.16OSPE 0.0.17OSPE 0.0.18OSPE 0.0.19OSPE 0.0.20OSPE 0.0.21OSPE 0.0.22OSPE 0.0.23

    STRUCTURAL EXPANSION JOINTS

    OSPE 0.0.24

    OSPE 0.0.26OSPE 0.0.25

    The architecture, engineering and design of the project using

    the Dryvit products is the responsibility of the project's design

    professional. All systems must comply with local building

    codes and standards. This detail is for general information

    and guidance only and Dryvit specifically disclaims any

    liability for the use of this detail and for the architecture,

    design, engineering or workmanship of any project. The

    project design professional determines, in its sole discretion,

    whether this detail or a functionally equivalent alternative is

    best suited for the project. Use of a functionally equivalent

    detail does not violate Dryvit's warranty. This detail is subject

    to change without notice. Contact Dryvit to insure you have

    the most recent version.

    ©

    Dryvit Systems, Inc.

    Issued: 6/2020

  • Outsulation PE System

    NOTE:DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVETHE BASE COAT REINFORCED WITHDRYVIT PANZER® MESH PRIOR TODRYVIT REINFORCING MESH. LOCATION OFHIGH IMPACT ZONES SHOULD BEINDICATED ON CONTRACT DRAWINGS.

    1.

    without notice. Contact Dryvit to insure you have the most recent

    does not violate Dryvit's warranty. This detail is subject to change

    is best suited for the project. Use of a functionally equivalent detail

    discretion, whether this detail or a functionally equivalent alternative

    any project. The project design professional determines, in its sole

    detail and for the architecture, design, engineering or workmanship of

    and Dryvit specifically disclaims any liability for the use of this

    standards. This detail is for general information and guidance only

    professional. All systems must comply with local building codes and

    Dryvit products is the responsibility of the project's design

    The architecture, engineering and design of the project using the

    version.

    EIMA

    STANDARD

    IMPACT

    EIMA

    ULTRA-HIGH

    IMPACT

    OUTSULATION® PE SYSTEM®LIGHTLY SAND SURFACE OF DRAINAGETRACK TO MAXIMIZE ADHESION.

    2.

    OSPE 0.0.01

    APPROVED SUBSTRATE

    FRAMING

    DRYVIT AIR/WATER-RESISTIVEBARRIER COATING

    INSULATION BOARD

    DRYVIT REINFORCING MESH

    APPROVED SUBSTRATEFRAMING

    DRYVIT AIR/WATER-RESISTIVEBARRIER COATING

    EPS INSULATION BOARD

    DRYVIT REINFORCING MESH

    DRYVIT FINISHDRYVIT VENT ASSEMBLY

    DRYVIT BASE COAT

    PANZER® 15 OR 20 REINFORCINGMESH (SEE NOTE 1)

    DRYVIT BASE COAT

    DRYVIT ADHESIVE IN VERTICALNOTCHED TROWEL CONFIGURATION

    DRYVIT ADHESIVE IN VERTICALNOTCHED TROWEL CONFIGURATION

    DRYVIT VENT TRACK™

    DRYVIT FINISH

    DRYVIT VENT ASSEMBLY™

    DRYVIT BASE COAT

    DRYVIT AQUAFLASH® SYSTEM ORDRYVIT BACKSTOP® NT TEXTUREOVER GRID TAPE™(SEE NOTE 2)DRYVIT BASE COAT

    DRYVIT AQUAFLASH SYSTEM ORDRYVIT BACKSTOP NT TEXTUREOVER GRID TAPE LAPPED OVERDRYVIT VENT TRACK(SEE NOTE 2)

    DRYVIT BASE COAT

    ©

    Dryvit Systems, Inc.

    Issued: 6/2020

  • Building Facade

    OSPE 0.0.02

    without notice. Contact Dryvit to insure you have the most recent

    does not violate Dryvit's warranty. This detail is subject to change

    is best suited for the project. Use of a functionally equivalent detail

    discretion, whether this detail or a functionally equivalent alternative

    any project. The project design professional determines, in its sole

    detail and for the architecture, design, engineering or workmanship of

    and Dryvit specifically disclaims any liability for the use of this

    standards. This detail is for general information and guidance only

    professional. All systems must comply with local building codes and

    Dryvit products is the responsibility of the project's design

    The architecture, engineering and design of the project using the

    version.

    v

    v

    v

    v

    v

    v

    v

    v

    v

    v

    v

    v

    COMPARTMENT LOCATIONSDETERMINED PER ASCE 7-10 ANDDRYVIT OUTSULATION PE SYSTEMSPECIFICATIONS DS844.

    NOTES:1.

    OUTSULATION® PE SYSTEM®

    DRYVIT VENT ASSEMBLY™

    DRYVIT VENT TRACK™(DRAIN HOLE LOCATED ATVENT ASSEMBLY)DRYVIT TRACK (NO DRAINHOLES)

    305 MM (12") DRYVITCLOSURE BLOCKS TYP.

    152 MM (6") DRYVITSTARTER STRIP TYP.

    152 MM (6") DRYVITCLOSURE BLOCKS TYP.

    COMPARTMENTSEPARATION TYP.

    ©

    Dryvit Systems, Inc.

    Issued: 6/2020

  • OUTSULATION® PE SYSTEM®

    OUTSULATION PESYSTEM

    BY OTHERS

    The architecture, engineering and design of the project using the

    Dryvit products is the responsibility of the project's design

    professional. All systems must comply with local building codes and

    standards. This detail is for general information and guidance only

    and Dryvit specifically disclaims any liability for the use of this

    detail and for the architecture, design, engineering or workmanship of

    any project. The project design professional determines, in its sole

    discretion, whether this detail or a functionally equivalent alternative

    is best suited for the project. Use of a functionally equivalent detail

    does not violate Dryvit's warranty. This detail is subject to change

    without notice. Contact Dryvit to insure you have the most recent

    Insulation Board Layout

    version.

    OSPE 0.0.03

    FRAMING, BY OTHERS

    APPROVED SUBSTRATE,BY OTHERS

    INSULATION BOARD

    VERTICAL DRAINAGEGROOVES (ALIGNED)

    HORIZONTAL BEVELEDGROOVES

    DRYVIT STARTER STRIP

    DRYVIT VENT ASSEMBLY™

    DRYVIT VENT TRACK™

    ©

    Dryvit Systems, Inc.

    Issued: 6/2020

  • 305 MM(1'-0")"

    OUTSULATION® PE SYSTEM®INSTALL SQUARE EDGED CORNERCLOSURE BLOCKS ON ALTERNATINGSIDES OF OUTSIDE CORNERS.

    NOTES:1.

    152 MM (0'-6")

    610 MM (2'-0")

    The architecture, engineering and design of the project using the

    Dryvit products is the responsibility of the project's design

    professional. All systems must comply with local building codes and

    standards. This detail is for general information and guidance only

    and Dryvit specifically disclaims any liability for the use of this

    detail and for the architecture, design, engineering or workmanship of

    any project. The project design professional determines, in its sole

    discretion, whether this detail or a functionally equivalent alternative

    is best suited for the project. Use of a functionally equivalent detail

    does not violate Dryvit's warranty. This detail is subject to change

    without notice. Contact Dryvit to insure you have the most recent

    Outside Corner - Insulation Board

    version.

    OSPE 0.0.04

    ALTERNATING SQUAREEDGED CORNER CLOSURE

    BLOCKS (TYPICAL)

    DRYVIT VENTASSEMBLY™

    VERTICAL DRAINAGEGROOVES (ALIGNED)

    DRYVIT STARTER STRIP

    MITER JOINT BETWEEN STARTER STRIPS

    ©

    Dryvit Systems, Inc.

    Issued: 6/2020

  • 45

    Insulation Board- Groove Pattern

    OSPE 0.0.05

    without notice. Contact Dryvit to insure you have the most recent

    does not violate Dryvit's warranty. This detail is subject to change

    is best suited for the project. Use of a functionally equivalent detail

    discretion, whether this detail or a functionally equivalent alternative

    any project. The project design professional determines, in its sole

    detail and for the architecture, design, engineering or workmanship of

    and Dryvit specifically disclaims any liability for the use of this

    standards. This detail is for general information and guidance only

    professional. All systems must comply with local building codes and

    Dryvit products is the responsibility of the project's design

    The architecture, engineering and design of the project using the

    version.

    BEVEL

    DETAIL

    51 MM (2") MIN

    12.7 MM (1/2")

    OUTSULATION® PE SYSTEM®

    1.2 M (4'-0")

    305 MM (12")

    ON CENTER

    610 MM(2'-0")

    6.4 MM X 25 MM (14" X 1")VERTICAL DRAINAGE GROOVE

    BEVEL ALONG PERIMETEROF INSULATION BOARD

    ©

    Dryvit Systems, Inc.

    Issued: 6/2020

  • OUTSULATION® PE SYSTEM®

    FILL DRYVIT VENT TRACK ATCLOSURE BLOCK LOCATION WITH APADHESIVE PRIOR TO SETTINGCLOSURE BLOCK, TO PROVIDECOMPARTMENT CLOSURE.

    ADHERE CLOSURE BLOCKS ANDSTARTER STRIPS USING "RIBBON &DAB" ADHESIVE PATTERN TOPROVIDE COMPARTMENT CLOSURE.

    2.

    NOTES:1.

    The architecture, engineering and design of the project using the

    Dryvit products is the responsibility of the project's design

    professional. All systems must comply with local building codes and

    standards. This detail is for general information and guidance only

    and Dryvit specifically disclaims any liability for the use of this

    detail and for the architecture, design, engineering or workmanship of

    any project. The project design professional determines, in its sole

    discretion, whether this detail or a functionally equivalent alternative

    is best suited for the project. Use of a functionally equivalent detail

    does not violate Dryvit's warranty. This detail is subject to change

    without notice. Contact Dryvit to insure you have the most recent

    Compartment Separation

    version.

    OUTSULATION PESYSTEM

    BY OTHERS

    OSPE 0.0.06

    LIGHTLY SAND SURFACE OF DRAINAGETRACK TO MAXIMIZE ADHESION.

    3.

    VERTICAL DRAINAGEGROOVES (ALIGNED)

    INSULATION BOARD

    DRYVIT VENT ASSEMBLY™

    INSULATION BOARD CLOSURE BLOCK(SEE NOTE 1)

    DRYVIT STARTER STRIP(SEE NOTE 1)

    DRYVIT VENT TRACK™

    DRYVIT AP ADHESIVE(SEE NOTE 2)

    DRYVIT AQUAFLASH® SYSTEM OR DRYVITBACKSTOP® NT TEXTURE OVER GRID TAPEOVER VERTICAL LEG OF DRYVIT VENTTRACK OR TRACK (SEE NOTE 3)

    DRYVIT AIR/WATER-RESISTIVEBARRIER COATING

    APPROVED SUBSTRATE

    FRAMING

    ©

    Dryvit Systems, Inc.

    Issued: 6/2020

  • without notice. Contact Dryvit to insure you have the most recent

    does not violate Dryvit's warranty. This detail is subject to change

    is best suited for the project. Use of a functionally equivalent detail

    discretion, whether this detail or a functionally equivalent alternative

    of any project. The project design professional determines, in its sole

    detail and for the architecture, design, engineering or workmanship

    and Dryvit specifically disclaims any liability for the use of this

    standards. This detail is for general information and guidance only

    professional. All systems must comply with local building codes and

    Dryvit products is the responsibility of the project's design

    The architecture, engineering and design of the project using the

    DRYVIT RECOMMENDS THAT GROUND FLOORAPPLICATIONS AND ALL FACADES EXPOSEDTO ABNORMAL STRESS, HIGH TRAFFIC, ORDELIBERATE IMPACT HAVE THE BASE COATREINFORCED WITH PANZER® MESH PRIOR TOSTANDARD™ OR STANDARDPLUS™ MESH. LOCATION OF HIGH IMPACTZONES SHOULD BE INDICATED ON CONTRACTDRAWINGS.DRYVIT VENT ASSEMBLY IS INSTALLED ONLYAT PUNCHOUT IN DRYVIT VENT TRACK.

    OUTSULATION® PE SYSTEM® NOTE:

    2.

    1.

    LIGHTLY SAND SURFACE OF DRAINAGETRACK TO MAXIMIZE ADHESION.

    EXPANSION JOINT IS REQUIRED ALONGTOP OF FOUNDATION IF 610 MM (2'-0')DIMENSION IS EXCEEDED.

    4.

    3.

    version.

    203 MM (8") MIN.

    Foundation

    BY OTHERS

    OSPE 0.0.07

    SLOPE GRADE AWAYFROM FOUNDATION WALL

    OUTSULATION PESYSTEM

    19 MM (3/4") MIN.APPROVED SUBSTRATE

    DRYVIT AIR/WATER-RESISTIVEBARRIER COATING

    DRYVIT AQUAFLASH® SYSTEM OR DRYVITBACKSTOP® NT-TEXTURE OVER GRID TAPE™OVER VERTICAL LEG OF DRYVIT VENT TRACK(SEE NOTE 4)

    INSULATION BOARD

    DRYVIT VENT TRACK™

    DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COATDRYVIT FINISH

    WRAP DRYVIT DETAIL MESH®64 MM (2 1/2") MIN. AT UNDERSIDEOF INSULATION

    DRYVIT VENT ASSEMBLY™

    DRYVIT ADHESIVE

    DRYVIT AQUAFLASH SYSTEM OR DRYVITBACKSTOP NT-TEXTURE OVER GRID TAPE

    ©

    Dryvit Systems, Inc.

    Issued: 6/2020

  • OUTSULATION® PE SYSTEM®DRYVIT RECOMMENDS THAT GROUND FLOORAPPLICATIONS AND ALL FACADES EXPOSEDTO ABNORMAL STRESS, HIGH TRAFFIC, ORDELIBERATE IMPACT HAVE THE BASE COATREINFORCED WITH PANZER® MESH PRIOR TOSTANDARD™ OR STANDARDPLUS™ MESH. LOCATION OF HIGH IMPACTZONES SHOULD BE INDICATED ON CONTRACTDRAWINGS.

    NOTE:1. LIGHTLY SAND SURFACE OF TRACK

    TO MAXIMIZE ADHESION.2.

    The architecture, engineering and design of the project using the

    Dryvit products is the responsibility of the project's design

    professional. All systems must comply with local building codes and

    standards. This detail is for general information and guidance only

    and Dryvit specifically disclaims any liability for the use of this

    detail and for the architecture, design, engineering or workmanship of

    any project. The project design professional determines, in its sole

    discretion, whether this detail or a functionally equivalent alternative

    is best suited for the project. Use of a functionally equivalent detail

    does not violate Dryvit's warranty. This detail is subject to change

    without notice. Contact Dryvit to insure you have the most recent

    version.

    Termination At Concrete

    BY OTHERS OUTSULATION PESYSTEM

    OSPE 0.0.08

    19 MM (3/4") MIN.

    19 MM (3/4") MIN.

    APPROVED SUBSTRATEDRYVIT AIR/WATER-RESISTIVEBARRIER COATING

    DRYVIT VENT TRACK™

    COMPATIBLE SEALANT ANDCLOSED CELL BACKER ROD,BY OTHERS

    DRYVIT FINISH

    DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COATDRYVIT AQUAFLASH® SYSTEM OR DRYVITBACKSTOP® NT-TEXTURE OVER GRID TAPE™OVER VERTICAL LEG OF DRYVIT VENT TRACK(SEE NOTE 2)

    DRYVIT VENT ASSEMBLY™

    WRAP DRYVIT DETAIL MESH® 64 MM(2 1/2") MIN. AT BACKSIDE OF INSULATION

    DRYVIT DEMANDIT® OR COLOR PRIME™ON SURFACES TO RECEIVE SEALANT

    DRYVIT ADHESIVEINSULATION BOARD

    DRYVIT AQUAFLASH SYSTEM OR DRYVITBACKSTOP NT-TEXTURE OVER GRID TAPE

    ©

    Dryvit Systems, Inc.

    Issued: 6/2020

  • Head/Sill

    SILL PAN FLASHING

    LIGHTLY SAND SURFACE OF TRACK TOMAXIMIZE ADHESION.

    SEALANT SHOULD NOT BE IN DIRECTCONTACT WITH ASPHALTIC ADHESIVE ONDRYVIT FLASHING TAPE. COVER DRYVITFLASHING TAPE LAPS WITHPOLYETHYLENE TAPE OR BACKER ROD.

    The architecture, engineering and design of the project using the

    Dryvit products is the responsibility of the project's design

    professional. All systems must comply with local building codes and

    standards. This detail is for general information and guidance only

    and Dryvit specifically disclaims any liability for the use of this

    detail and for the architecture, design, engineering or workmanship

    of any project. The project design professional determines, in its sole

    discretion, whether this detail or a functionally equivalent alternative

    is best suited for the project. Use of a functionally equivalent detail

    does not violate Dryvit's warranty. This detail is subject to change

    without notice. Contact Dryvit to insure you have the most recent

    version.

    SILL

    1.

    2. FOR CONTINUOUS WINDOWS, USE CLOSUREBLOCKS TO TERMINATE SYSTEM AT SILL.

    DRYVIT RECOMMENDS THAT GROUND FLOORAPPLICATIONS AND ALL FACADES EXPOSEDTO ABNORMAL STRESS, HIGH TRAFFIC, ORDELIBERATE IMPACT HAVE THE BASE COATREINFORCED WITH PANZER® MESH PRIOR TOSTANDARD™ OR STANDARDPLUS™ MESH. LOCATION OF HIGH IMPACTZONES SHOULD BE INDICATED ON CONTRACTDRAWINGS.

    NOTE:OUTSULATION® PE SYSTEM®

    3.

    4.

    OSPE 0.0.09

    HEAD

    BY OTHERS OUSTULATION PESYSTEM

    AS AN OPTION, DRYVIT FLASHING TAPESURFACE CONDITIONER™ AND DRYVITFLASHING TAPE™ MAY BE USED IN LIEUOF AQUAFLASH SYSTEM.

    5.

    64 MM(2-1/2") MIN.

    12.7 MM(1/2")

    19 MM (3/4") MIN.

    APPROVED SUBSTRATE

    DRYVIT AIR/WATER-RESISTIVE BARRIER COATING

    DRYVIT VENT TRACK™

    DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT

    DRYVIT STARTER STRIP

    DRYVIT FINISH

    WRAP DRYVIT DETAIL MESH® 64 MM (2 1/2")MIN. AT BACKSIDE OF INSULATION BOARD

    DRYVIT AQUAFLASH SYSTEM (SEE NOTE 5)

    COMPATIBLE SEALANT WITHBOND BREAKER, BY OTHERS

    INSULATION BOARD

    INSULATION BOARD CLOSURE BLOCK

    DRYVIT ADHESIVE

    DRYVIT AQUAFLASH® SYSTEM OR DRYVITBACKSTOP® NT-TEXTURE OVER GRIDTAPE™ OVER VERTICAL LEG OF DRYVIT VENTTRACK™ (SEE NOTE 4)

    DRYVIT AQUAFLASH SYSTEM OR DRYVITBACKSTOP NT-TEXTURE OVER GRID TAPE

    DRYVIT DEMANDIT® OR COLOR PRIME™ON SURFACE(S) TO RECEIVE SEALANT

    CONTINUOUS FLASHING, BY OTHERS

    CONTINUOUS FLASHING, BY OTHERS

    COMPATIBLE SEALANT WITH CLOSED CELLBACKER ROD, BY OTHERS (SEE NOTE 3)

    ©

    Dryvit Systems, Inc.

    Issued: 6/2020

  • OUTSULATION® PE SYSTEM®1.

    NOTE:DRYVIT RECOMMENDS THAT GROUND FLOORAPPLICATIONS AND ALL FACADES EXPOSEDTO ABNORMAL STRESS, HIGH TRAFFIC, ORDELIBERATE IMPACT HAVE THE BASE COATREINFORCED WITH PANZER® MESH PRIOR TOSTANDARD™ OR STANDARDPLUS™ MESH. LOCATION OF HIGH IMPACTZONES SHOULD BE INDICATED ON CONTRACTDRAWINGS.

    version.

    The architecture, engineering and design of the project using the

    Dryvit products is the responsibility of the project's design

    professional. All systems must comply with local building codes and

    standards. This detail is for general information and guidance only

    and Dryvit specifically disclaims any liability for the use of this

    detail and for the architecture, design, engineering or workmanship

    of any project. The project design professional determines, in its sole

    discretion, whether this detail or a functionally equivalent alternative

    is best suited for the project. Use of a functionally equivalent detail

    does not violate Dryvit's warranty. This detail is subject to change

    without notice. Contact Dryvit to insure you have the most recent

    AS AN OPTION DRYVIT FLASHING TAPESURFACE CONDITIONER™ AND DRYVITFLASHING TAPE™ MAY BE USED INLIEU OF DRYVIT AQUAFLASH SYSTEM.

    SEALANT SHOULD NOT BE IN DIRECTCONTACT WITH ASPHALTIC ADHESIVEON DRYVIT FLASHING TAPE. COVERDRYVIT FLASHING TAPE LAPS WITHPOLYETHYLENE TAPE OR BACKER ROD.

    3.

    2.

    Jamb

    OUTSULATION PESYSTEM

    BY OTHERS

    OSPE 0.0.10

    19 MM(3/4" MIN)

    DRYVIT DEMANDIT® OR COLOR PRIME™ON SURFACES TO RECEIVE SEALANT

    COMPATIBLE SEALANT ANDCLOSED CELL BACKER ROD, BY OTHERS

    DRYVIT AQUAFLASH® SYSTEM ORDRYVIT BACKSTOP® NT-TEXTURE OVERGRID TAPE™ (SEE NOTE 3)

    WRAP DRYVIT DETAIL MESH®64 MM (2 1/2") MIN. AT BACKSIDEOF INSULATION BOARD

    DRYVIT ADHESIVE

    APPROVED SUBSTRATE

    INSULATION BOARDCLOSURE BLOCK

    DRYVIT FINISH

    DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT

    BASE COAT

    DRYVITAIR/WATER-RESISTIVE

    BARRIER COATING

    ©

    Dryvit Systems, Inc.

    Issued: 6/2020

  • OSPE 0.0.11

    Parapet - Steel Framed, Metal Coping

    without notice. Contact Dryvit to insure you have the most recent

    does not violate Dryvit's warranty. This detail is subject to change

    is best suited for the project. Use of a functionally equivalent detail

    discretion, whether this detail or a functionally equivalent alternative

    of any project. The project design professional determines, in its sole

    detail and for the architecture, design, engineering or workmanship

    and Dryvit specifically disclaims any liability for the use of this

    standards. This detail is for general information and guidance only

    professional. All systems must comply with local building codes and

    Dryvit products is the responsibility of the project's design

    The architecture, engineering and design of the project using the

    DRYVIT RECOMMENDS THAT GROUND FLOORAPPLICATIONS AND ALL FACADES EXPOSEDTO ABNORMAL STRESS, HIGH TRAFFIC, ORDELIBERATE IMPACT HAVE THE BASE COATREINFORCED WITH PANZER® MESH PRIOR TOREINFORCING MESH. LOCATION OF HIGH IMPACTZONES SHOULD BE INDICATED ON CONTRACTDRAWINGS.

    OUTSULATION® PE SYSTEM® NOTE:

    1.

    BY OTHERS

    AS AN OPTION DRYVIT FLASHING TAPESURFACE CONDITIONER™ AND DRYVITFLASHING TAPE™ MAY BE USED IN LIEUOF DRYVIT AQUAFLASH SYSTEM.

    2.

    version.

    OUTSULATION PESYSTEM

    64 MM (2 1/2") MIN.64 MM (2 1/2") MIN.

    SEALANT WITH BONDBREAKER (TYP.),

    BY OTHERS

    INSULATION BOARDCLOSURE BLOCK

    DRYVIT FINISH

    DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT

    INSULATION BOARD

    CONTINUOUS COPING,BY OTHERS

    DRYVIT AQUAFLASH® SYSTEM OR DRYVITBACKSTOP® NT-TEXTURE OVER GRID TAPE™(SEE NOTE 2)

    APPROVED SUBSTRATE

    WRAP DRYVIT DETAIL MESH®64 MM (2 1/2") MIN. AT BACKSIDEOF INSULATION

    COMPATIBLE SEALANT WITH BONDBREAKER (TYP.), BY OTHERS

    DRYVIT ADHESIVE

    DRYVIT AIR/WATER-RESISTIVEBARRIER COATING

    ©

    Dryvit Systems, Inc.

    Issued: 6/2020

  • OSPE 0.0.12

    professional. All systems must comply with local building codes and

    of any project. The project design professional determines, in its sole

    version.

    Dryvit products is the responsibility of the project's design

    standards. This detail is for general information and guidance only

    and Dryvit specifically disclaims any liability for the use of this

    detail and for the architecture, design, engineering or workmanship

    discretion, whether this detail or a functionally equivalent alternative

    is best suited for the project. Use of a functionally equivalent detail

    does not violate Dryvit's warranty. This detail is subject to change

    without notice. Contact Dryvit to insure you have the most recent

    The architecture, engineering and design of the project using the

    BY OTHERS OUTSULATION PESYSTEM

    Parapet - Solid Substrate, Metal Coping

    1. NOTE:

    OUTSULATION® PE SYSTEM®

    DRYVIT RECOMMENDS THAT GROUND FLOORAPPLICATIONS AND ALL FACADES EXPOSEDTO ABNORMAL STRESS, HIGH TRAFFIC, ORDELIBERATE IMPACT HAVE THE BASE COATREINFORCED WITH PANZER® MESH PRIOR TOREINFORCING MESH. LOCATION OF HIGH IMPACTZONES SHOULD BE INDICATED ON CONTRACTDRAWINGS.

    2. AS AN OPTION DRYVIT FLASHING TAPESURFACE CONDITIONER™ AND DRYVITFLASHING TAPE™ MAY BE USED IN LIEUOF DRYVIT AQUAFLASH SYSTEM.

    3. DIMENSIONS GREATER THAN 600 MM(2'-0") REQUIRE SYSTEM CONFIGURATIONSIMILAR TO WALL FACE.

    64 MM (2-1/2") MIN.

    SOLID SUBSTRATE

    INSULATION BOARDCLOSURE BLOCK

    COMPATIBLE SEALANT WITHBOND BREAKER (TYP.),BY OTHERS

    WRAP DRYVIT DETAIL MESH®64 MM (2 1/2") MIN. AT BACKSIDEOF INSULATION

    DRYVIT AIR/WATER-RESISTIVEBARRIER COATING

    ROOF ASSEMBLY

    WRAP DRYVIT DETAILMESH 64 MM (2 1/2") MIN.

    AT BACKSIDE OF INSULATION

    ROOF FLASHING ANDCOUNTERFLASHING,

    BY OTHERS

    203 MM(8") MIN.

    METAL CAP FLASHING, BY OTHERS

    DRYVIT ADHESIVE

    DRYVIT FINISH

    DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT

    INSULATION BOARD

    DRYVIT AQUAFLASH® SYSTEM OR DRYVITBACKSTOP® NT-TEXTURE OVER GRID TAPE™(SEE NOTE 2)

    (SEE NOTE 3) DRYVIT AQUAFLASHLAPPED OVER ROOF

    FLASHING (SEE NOTE 2)

    ©

    Dryvit Systems, Inc.

    Issued: 6/2020

  • detail and for the architecture, design, engineering or workmanship of

    professional. All systems must comply with local building codes and DRYVIT RECOMMENDS THAT GROUND FLOORAPPLICATIONS AND ALL FACADES EXPOSEDTO ABNORMAL STRESS, HIGH TRAFFIC, ORDELIBERATE IMPACT HAVE THE BASE COATREINFORCED WITH PANZER® MESH PRIOR TOSTANDARD™ OR STANDARDPLUS™ MESH. LOCATION OF HIGH IMPACTZONES SHOULD BE INDICATED ON CONTRACTDRAWINGS.

    OUTSULTION® PE SYSTEM® NOTE:

    1.

    OVERLAP 64 MM (2-1/2") MIN.

    19 MM (3/4") MIN.

    AS AN OPTION DRYVIT FLASHING TAPESURFACE CONDITIONER™ AND DRYVITFLASHING TAPE™ MAY BE USED IN LIEUOF DRYVIT AQUAFLASH SYSTEM.

    LIGHTLY SAND SURFACE OF TRACK TOMAXIMIZE ADHESION.

    DRYVIT VENT ASSEMBLY IS INSTALLEDONLY AT PUNCHOUT IN DRYVIT VENTTRACK.

    4.

    2.

    3.

    The architecture, engineering and design of the project using the

    without notice. Contact Dryvit to insure you have the most recent

    does not violate Dryvit's warranty. This detail is subject to change

    is best suited for the project. Use of a functionally equivalent detail

    discretion, whether this detail or a functionally equivalent alternative

    any project. The project design professional determines, in its sole

    and Dryvit specifically disclaims any liability for the use of this

    standards. This detail is for general information and guidance only

    Dryvit products is the responsibility of the project's design

    version.

    Soffit/Fascia Intersection

    BY OTHERS OUTSULATION PESYSTEM

    OSPE 0.0.13

    19MM (3/4") MIN.

    DRYVIT VENT ASSEMBLY™(SEE NOTE 4)

    DRIP GROOVE

    DRYVIT DETAIL MESH®EMBEDDED IN BASE COAT

    DRYVIT AQUAFLASH SYSTEM ORDRYVIT BACKSTOP NT-TEXTUREOVER GRID TAPE

    APPROVED SUBSTRATEDRYVIT AIR/WATER-RESISTIVEBARRIER COATING

    INSULATION BOARD

    DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT

    DRYVIT VENT TRACK

    DRYVIT FINISH

    DRYVIT ADHESIVE

    DRYVIT AQUAFLASH® SYSTEM ORDRYVIT BACKSTOP® NT-TEXTUREOVER GRID TAPE™ OVER VERTICALLEG OF DRYVIT VENT TRACK™(SEE NOTES 2 AND 3)

    ©

    Dryvit Systems, Inc.

    Issued: 6/2020

  • 203 MM (8") MIN.SEE NOTES 2 AND 3

    without notice. Contact Dryvit to insure you have the most recent

    does not violate Dryvit's warranty. This detail is subject to change

    is best suited for the project. Use of a functionally equivalent detail

    discretion, whether this detail or a functionally equivalent alternative

    any project. The project design professional determines, in its sole

    detail and for the architecture, design, engineering or workmanship of

    and Dryvit specifically disclaims any liability for the use of this

    standards. This detail is for general information and guidance only

    professional. All systems must comply with local building codes and

    Dryvit products is the responsibility of the project's design

    The architecture, engineering and design of the project using the

    DRYVIT RECOMMENDS THAT GROUND FLOORAPPLICATIONS AND ALL FACADES EXPOSEDTO ABNORMAL STRESS, HIGH TRAFFIC, ORDELIBERATE IMPACT HAVE THE BASE COATREINFORCED WITH PANZER® MESH PRIOR TOSTANDARD™ OR STANDARDPLUS™ MESH. LOCATION OF HIGH IMPACTZONES SHOULD BE INDICATED ON CONTRACTDRAWINGS.

    OUTSULATION® PE SYSTEM® NOTE:

    1.

    DO NOT LAP REINFORCING MESH WITHIN203 MM (8") OF A CORNER.

    DOUBLE WRAP OUTSIDE AND INSIDECORNERS WITH REINFORCING MESH ORUSE CORNER MESH.

    3.

    2.

    version.

    Inside/Outside Corners

    BY OTHERS

    OSPE 0.0.14

    AS AN OPTION, DRYVIT FLASHING TAPESURFACE CONDITIONER™ AND DRYVITFLASHING TAPE™ MAY BE USED IN LIEUOF DRYVIT AQUAFLASH SYSTEM.

    4.

    DRYVIT AQUAFLASH SYSTEM ORDRYVIT BACKSTOP NT-TEXTUREOVER GRID TAPE (SEE NOTE 4)APPROVED SUBSTRATE

    DRYVIT AIR/WATER-RESISTIVEBARRIER COATINGINSULATION BOARDDRYVIT REINFORCING MESH EMBEDDEDIN DRYVIT BASE COATDRYVIT FINISH

    APPROVED SUBSTRATEDRYVIT AIR/WATER-RESISTIVEBARRIER COATING

    DRYVIT FINISH

    DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT

    DRYVIT AQUAFLASH® SYSTEM ORDRYVIT BACKSTOP® NT-TEXTUREOVER GRID TAPE™ (SEE NOTE 4)INSULATION BOARDCLOSURE BLOCK

    INSULATION BOARD

    OUTSULATION PESYSTEM

    203 MM (8") MIN.SEE NOTES 2 AND 3

    DRYVIT ADHESIVE

    DRYVIT ADHESIVE

    ©

    Dryvit Systems, Inc.

    Issued: 6/2020

  • DO NOT LAP REINFORCING MESH WITHIN203 MM (8") OF A CORNER.

    OUTSULATION® PE SYSTEM®DRYVIT RECOMMENDS THAT GROUND FLOORAPPLICATIONS AND ALL FACADES EXPOSEDTO ABNORMAL STRESS, HIGH TRAFFIC, ORDELIBERATE IMPACT HAVE THE BASE COATREINFORCED WITH PANZER® MESH PRIOR TODRYVIT REINFORCING MESH. LOCATION OF HIGHIMPACT ZONES SHOULD BE INDICATED ONCONTRACT DRAWINGS.

    NOTE:1. 2.

    203 MM (8") MIN

    (SEE NOTE 2)

    The architecture, engineering and design of the project using the

    Dryvit products is the responsibility of the project's design

    professional. All systems must comply with local building codes and

    standards. This detail is for general information and guidance only

    and Dryvit specifically disclaims any liability for the use of this

    detail and for the architecture, design, engineering or workmanship of

    any project. The project design professional determines, in its sole

    discretion, whether this detail or a functionally equivalent alternative

    is best suited for the project. Use of a functionally equivalent detail

    does not violate Dryvit's warranty. This detail is subject to change

    without notice. Contact Dryvit to insure you have the most recent

    Outside Corner - High Impact

    version.

    BY OTHERS

    OSPE 0.0.15

    OUTSULATION PESYSTEM

    DRYVIT BASE COAT

    DRYVIT REINFORCING MESH OVERLAPMIN. OF 203 MM (8") AT CORNER

    DRYVIT CORNER MESH

    DRYVIT FINISH

    DRYVIT ADHESIVE

    DRYVIT BASE COAT

    DRYVIT PANZER® 15 OR 20REINFORCING MESH

    DRYVIT BASE COAT

    INSULATION BOARDCLOSURE BLOCK

    DRYVIT AIR/WATER-RESISTIVEBARRIER COATING

    APPROVED SUBSTRATE

    ©

    Dryvit Systems, Inc.

    Issued: 6/2020

  • OSPE 0.0.16

    Horizontal Expansion Joint

    The architecture, engineering and design of the project using the

    Dryvit products is the responsibility of the project's design

    professional. All systems must comply with local building codes and

    standards. This detail is for general information and guidance only

    and Dryvit specifically disclaims any liability for the use of this

    detail and for the architecture, design, engineering or workmanship of

    any project. The project design professional determines, in its sole

    discretion, whether this detail or a functionally equivalent alternative

    is best suited for the project. Use of a functionally equivalent detail

    does not violate Dryvit's warranty. This detail is subject to change

    without notice. Contact Dryvit to insure you have the most recent

    DRYVIT RECOMMENDS THAT GROUND FLOORAPPLICATIONS AND ALL FACADES EXPOSEDTO ABNORMAL STRESS, HIGH TRAFFIC, ORDELIBERATE IMPACT HAVE THE BASE COATREINFORCED WITH PANZER® MESH PRIORTO DRYVIT REINFORCING MESH. LOCATIONOF HIGH IMPACT ZONES SHOULD BEINDICATED ON CONTRACT DRAWINGS.DRYVIT VENT ASSEMBLY IS INSTALLEDONLY AT PUNCHOUT IN DRYVIT VENTTRACK.

    OUTSULATION® PE SYSTEM®NOTE:

    1.

    2.

    BY OTHERS

    LIGHTLY SAND SURFACE OF TRACK TOMAXIMIZE ADHESION.DRYVIT FLASHING TAPE SURFACECONDITIONER™ AND DRYVIT FLASHINGTAPE™ MAY BE USED IN LIEU OF DRYVITAQUAFLASH SYSTEM.SEALANT SHOULD NOT BE IN DIRECTCONTACT WITH ASPHALTIC ADHESIVE ONDRYVIT FLASHING TAPE. COVER DRYVITFLASHING TAPE LAPS WITHPOLYETHYLENE TAPE OR BACKER ROD.

    Section A-A

    5.

    4.

    3.

    OUTSULATIONPE SYSTEM

    version.

    A A

    LOCATION OFVENT ASSEMBLY

    SEALANT AND BOND BREAKER AGAINSTDRYVIT AQUAFLASH SYSTEMAT VENT ASSEMBLY ONLY (SEE NOTE 4)

    SEALANT MATERIAL,BY OTHERS

    CLOSED CELL BACKERROD, BY OTHERS

    DRYVIT AQUAFLASH SYSTEM(SEE NOTE 4)

    INSULATION BOARD CLOSURE BLOCKWRAP DRYVIT DETAIL MESH®64 MM (2 1/2") MIN. AT BACKSIDE OF INSULATION

    INSULATION BOARD

    COMPATIBLE SEALANT WITH BONDBREAKER TAPE, BY OTHERS (SEE NOTE 5)

    DRYVIT DEMANDIT® OR COLOR PRIME™ON SURFACE(S) TO RECEIVE SEALANT

    DRYVIT AQUAFLASH® SYSTEM OR DRYVITBACKSTOP® NT-TEXTURE OVER GRID TAPE™OVER VERTICAL LEG OF DRYVIT TRACK(SEE NOTE 3)

    DRYVIT ADHESIVEDRYVIT AIR/WATER-RESISTIVE BARRIER COATINGAPPROVED SUBSTRATE

    DRYVIT AQUAFLASH SYSTEM(SEE NOTE 4)

    INSULATION BOARD

    DRYVIT VENT TRACK™DRYVIT VENT ASSEMBLY™

    DRYVIT REINFORCING MESH EMBEDDEDIN DRYVIT BASE COAT

    SLOPE SURFACE TO DRAIN (MIN. 1:5)

    DRYVIT FINISH

    19 MM (3/4") MIN

    19MM (3/4") MIN.

    ©

    Dryvit Systems, Inc.

    Issued: 6/2020

  • version.

    The architecture, engineering and design of the project using the

    Dryvit products is the responsibility of the project's design

    professional. All systems must comply with local building codes and

    standards. This detail is for general information and guidance only

    and Dryvit specifically disclaims any liability for the use of this

    detail and for the architecture, design, engineering or workmanship of

    any project. The project design professional determines, in its sole

    discretion, whether this detail or a functionally equivalent alternative

    is best suited for the project. Use of a functionally equivalent detail

    does not violate Dryvit's warranty. This detail is subject to change

    without notice. Contact Dryvit to insure you have the most recent

    NOTE:OUTSULATION® PE SYSTEM®

    EXPANSION JOINT IN THE OUTSULATIONPE SYSTEM IS NECESSARY WHERE

    DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVETHE BASE COAT REINFORCED WITHPANZER® MESH PRIOR TO DRYVITREINFORCING MESH. LOCATION OF HIGHIMPACT ZONES SHOULD BE INDICATED ONCONTRACT DRAWINGS.

    2.

    1.

    DRYVIT FLASHING TAPE SURFACECONDITIONER™ AND DRYVIT FLASHINGTAPE™ MAY BE USED IN LIEU OF DRYVITAQUAFLASH SYSTEM.

    LIGHTLY SAND SURFACE OF TRACK TOMAXIMIZE ADHESION.

    LOCATE EXTERNAL SEALANT JOINT A MAXIMUMOF 51 MM (2") BELOW BREAK IN SUBSTRATE.SEALANT SHOULD NOT BE IN DIRECT CONTACTWITH ASPHALTIC ADHESIVE ON DRYVITFLASHING TAPE. COVER FLASHING TAPE LAPSWITH POLYETHYLENE TAPE OR BACKER ROD.

    3.

    6.

    5.

    4.

    BY OTHERS

    Section A-A

    OUTSULATION PESYSTEM

    Horizontal Slip Joint

    SLIP TYPECONNECTION

    A A

    OSPE 0.0.17

    LOCATION OF VENT ASSEMBLY

    SEALANT AND BOND BREAKER AGAINSTDRYVIT AQUAFLASH SYSTEMAT VENT ASSEMBLY ONLY (SEE NOTE 6)

    SEALANT MATERIAL, BY OTHERS

    CLOSED CELL BACKERROD, BY OTHERS

    INSULATION BOARD CLOSURE BLOCK

    INSULATION BOARD

    INSULATION BOARD

    DRYVIT VENT ASSEMBLY™

    DRYVIT AQUAFLASH® SYSTEM OR DRYVITBACKSTOP® NT-TEXTURE OVER GRID TAPE™OVER VERTICAL LEG OF DRYVIT VENT TRACK™(SEE NOTE 5)

    WRAP DRYVIT DETAIL MESH®64 MM (2 1/2") MIN. AT BACKSIDE OF INSULATION

    DRYVIT DEMANDIT® OR COLOR PRIME™ON SURFACES TO RECEIVE SEALANT

    SLOPE SURFACE TO DRAIN (MIN. 1:5)

    COMPATIBLE SEALANT WITH BOND BREAKERTAPE, BY OTHERS (SEE NOTE 4)

    DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COATDRYVIT FINISH

    19 MM (3/4") MIN.

    DRYVIT VENT TRACK

    19 MM (3/4") MIN.

    DRYVIT ADHESIVEDRYVIT AIR/WATER-RESISTIVE BARRIER COATINGAPPROVED SUBSTRATE

    DRYVIT AQUAFLASH SYSTEM (SEE NOTE 6)

    SIGNIFICANT DIFFERENTIAL MOVEMENT ISEXPECTED AT FLOOR LINES.

    ©

    Dryvit Systems, Inc.

    Issued: 6/2020

  • SEALANT SHOULD NOT BE IN DIRECTCONTACT WITH ASPHALTIC ADHESIVEON DRYVIT FLASHING TAPE. COVERDRYVIT FLASHING TAPE LAPS WITHPOLYETHYLENE TAPE OR BACKER ROD.

    19 MM (3/4") MIN.

    OPTION

    OUTSULATION® PE SYSTEM®DRYVIT RECOMMENDS THAT GROUND FLOORAPPLICATIONS AND ALL FACADES EXPOSEDTO ABNORMAL STRESS, HIGH TRAFFIC, ORDELIBERATE IMPACT HAVE THE BASE COATREINFORCED WITH PANZER® MESH PRIOR TOSTANDARD™ OR STANDARDPLUS™ MESH. LOCATION OF HIGH IMPACTZONES SHOULD BE INDICATED ON CONTRACTDRAWINGS.

    NOTE:1.

    3.

    A-A

    The architecture, engineering and design of the project using the

    Dryvit products is the responsibility of the project's design

    professional. All systems must comply with local building codes and

    standards. This detail is for general information and guidance only

    and Dryvit specifically disclaims any liability for the use of this

    detail and for the architecture, design, engineering or workmanship of

    any project. The project design professional determines, in its sole

    discretion, whether this detail or a functionally equivalent alternative

    is best suited for the project. Use of a functionally equivalent detail

    does not violate Dryvit's warranty. This detail is subject to change

    without notice. Contact Dryvit to insure you have the most recent

    Vertical Expansion Joint Options

    version.

    BY OTHERS

    OUTSULATION PESYSTEM

    OSPE 0.0.18

    AS AN OPTION DRYVIT FLASHING TAPESURFACE CONDITIONER™ AND DRYVITFLASHING TAPE™ MAY BE USED IN LIEUOF DRYVIT AQUAFLASH SYSTEM.

    2.

    REAR SEAL

    VENT

    REAR SEALFACE SEAL

    DRYVIT DEMANDIT® OR COLOR PRIME™ON SURFACES TO RECEIVE SEALANT

    DRYVIT FINISH

    DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT

    INSULATION BOARDCLOSURE BLOCK

    DRYVIT ADHESIVE

    DRYVITAIR/WATER-RESISTIVE

    BARRIER COATING

    SOLID SUBSTRATE

    COMPATIBLE SEALANT WITHCLOSED CELL BACKER ROD,BY OTHERS (SEE NOTE 3)

    WRAP DRYVIT DETAIL MESH®64 MM (2 1/2") MIN. AT UNDERSIDE OF EPS

    DRYVIT AQUAFLASH® SYSTEM OR DRYVITBACKSTOP® NT-TEXTURE OVER GRIDTAPE™ OVER VERTICAL LEG OF DRYVITTRACK (SEE NOTE 2)

    APPROVED SUBSTRATE

    COMPATIBLE SEALANT WITHCLOSED CELL BACKER ROD,BY OTHERS (SEE NOTE 3)

    DRYVIT DEMANDIT OR COLOR PRIME

    ©

    Dryvit Systems, Inc.

    Issued: 6/2020

    AutoCAD SHX TextA

    AutoCAD SHX TextA

  • Structural Expansion Joints

    OUTSULATION PESYSTEM

    OSPE 0.0.19

    without notice. Contact Dryvit to insure you have the most recent

    does not violate Dryvit's warranty. This detail is subject to change

    is best suited for the project. Use of a functionally equivalent detail

    discretion, whether this detail or a functionally equivalent alternative

    any project. The project design professional determines, in its sole

    detail and for the architecture, design, engineering or workmanship of

    and Dryvit specifically disclaims any liability for the use of this

    standards. This detail is for general information and guidance only

    professional. All systems must comply with local building codes and

    Dryvit products is the responsibility of the project's design

    The architecture, engineering and design of the project using the

    version.

    BY OTHERS

    19 MM (3/4") MIN.

    19 MM (3/4") MIN.

    DRYVIT RECOMMENDS THAT GROUND FLOORAPPLICATIONS AND ALL FACADES EXPOSEDTO ABNORMAL STRESS, HIGH TRAFFIC, ORDELIBERATE IMPACT HAVE THE BASE COATREINFORCED WITH PANZER® MESH PRIOR TOSTANDARD™ OR STANDARDPLUS™ MESH. LOCATION OF HIGH IMPACTZONES SHOULD BE INDICATED ON CONTRACTDRAWINGS.

    NOTE:1.

    3. SEALANT SHOULD NOT BE IN DIRECTCONTACT WITH ASPHALTIC ADHESIVE ONDRYVIT FLASHING TAPE. COVER DRYVITFLASHING TAPE LAPS WITHPOLYETHYLENE TAPE OR BACKER ROD.

    2. AS AN OPTION DRYVIT FLASHING TAPESURFACE CONDITIONER™ AND DRYVITFLASHING TAPE™ CAN BE USED.

    OUTSULATION® PE SYSTEM®

    OPTIONAL SECONDARYSEAL, BY OTHERSAPPROVED SUBSTRATE

    DRYVIT AIR/WATER-RESISTIVE BARRIER COATING

    INSULATION BOARDCLOSURE BLOCK

    WRAP DRYVIT DETAIL MESH64 MM (2 1/2") MIN. AT BACKSIDE OF INSULATION

    OPTIONAL SECONDARYSEAL, BY OTHERS

    DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT

    DRYVIT DEMANDIT OR COLORPRIME ON SURFACES TO

    RECEIVE SEALANT

    DRYVIT AQUAFLASHSYSTEM (SEE NOTE 2)

    DRYVIT AIR/WATER-RESISTIVEBARRIER COATING

    APPROVED SUBSTRATE

    INSULATION BOARDCLOSURE BLOCK

    COMPATIBLE SEALANT WITHCLOSED CELL BACKER ROD,BY OTHERS (SEE NOTE 3)

    DRYVIT DEMANDIT® ORCOLOR PRIME™ ON SURFACES

    TO RECEIVE SEALANT

    WRAP DRYVIT DETAIL MESH®64 MM (2 1/2") MIN. AT BACKSIDE

    OF INSULATION

    SOLID SUBSTRATE

    DRYVIT AQUAFLASH® SYSTEM(SEE NOTE 2)

    DRYVIT ADHESIVE

    DRYVIT REINFORCING MESHEMBEDDED IN DRYVITBASE COAT

    INSULATION BOARD

    DRYVIT ADHESIVE

    INSULATION BOARDDRYVIT FINISH

    COMPATIBLE SEALANT WITHCLOSED CELL BACKER ROD,BY OTHERS (SEE NOTE 3)

    WRAP DRYVIT DETAIL MESH64 MM (2 1/2") MIN. AT BACKSIDE

    OF INSULATION

    ©

    Dryvit Systems, Inc.

    Issued: 6/2020

  • 19 MM (3/4") MIN.

    version.

    The architecture, engineering and design of the project using the

    Dryvit products is the responsibility of the project's design

    professional. All systems must comply with local building codes and

    standards. This detail is for general information and guidance only

    and Dryvit specifically disclaims any liability for the use of this

    detail and for the architecture, design, engineering or workmanship of

    any project. The project design professional determines, in its sole

    discretion, whether this detail or a functionally equivalent alternative

    is best suited for the project. Use of a functionally equivalent detail

    does not violate Dryvit's warranty. This detail is subject to change

    without notice. Contact Dryvit to insure you have the most recent

    NOTE:DRYVIT RECOMMENDS THAT GROUND FLOORAPPLICATIONS AND ALL FACADES EXPOSEDTO ABNORMAL STRESS, HIGH TRAFFIC, ORDELIBERATE IMPACT HAVE THE BASE COATREINFORCED WITH PANZER® MESH PRIOR TOSTANDARD™ OR STANDARDPLUS™ MESH. LOCATION OF HIGH IMPACTZONES SHOULD BE INDICATED ON CONTRACTDRAWINGS.

    1. FOR LARGER PENETRATIONS REFER TODETAIL OSPE 0.0.21

    2.

    Minor Penetrations

    102 MM (4") MAX.(SEE NOTE 2)

    BY OTHERS OUTSULATION PESYSTEM

    OSPE 0.0.20

    19 MM (3/4") MIN.

    OUTSULATION® PE SYSTEM®

    AS AN OPTION DRYVIT FLASHING TAPESURFACE CONDITIONER™ AND DRYVITFLASHING TAPE™ CAN BE USED.

    3.

    DRYVIT DEMANDIT® OR COLOR PRIME™ON SURFACES TO RECEIVE SEALANT

    DRYVIT AQUAFLASH® SYSTEM(SEE NOTE 3)

    COMPATIBLE SEALANT WITHCLOSED CELL BACKER ROD, BY OTHERS

    OPTIONAL SECONDARY SEAL, BY OTHERS

    INSULATION BOARD

    WRAP DRYVIT DETAIL MESH® 64 MM(2 1/2") MIN. AT BACKSIDE OF INSULATION

    DRYVIT FINISH

    DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT

    DRYVIT AIR/WATER-RESISTIVEBARRIER COATING

    APPROVED SUBSTRATE

    DRYVIT ADHESIVE

    ©

    Dryvit Systems, Inc.

    Issued: 6/2020

  • TO MINIMIZE CRACKING AT CORNERS OFPENETRATIONS INSTALL DIAGONALREINFORCING MESH.

    LOCATE INSULATION BOARDS SUCH THATBOARD EDGES DO NOT ALIGN WITHCORNERS OF PENETRATION.

    OUTSULATION® PE SYSTEM®DRYVIT RECOMMENDS THAT GROUND FLOORAPPLICATIONS AND ALL FACADES EXPOSEDTO ABNORMAL STRESS, HIGH TRAFFIC, ORDELIBERATE IMPACT HAVE THE BASE COATREINFORCED WITH PANZER® MESH PRIOR TOSTANDARD™ OR STANDARDPLUS™ MESH. LOCATION OF HIGH IMPACTZONES SHOULD BE INDICATED ON CONTRACTDRAWINGS.

    NOTE:1.

    3.

    2.The architecture, engineering and design of the project using the

    Dryvit products is the responsibility of the project's design

    professional. All systems must comply with local building codes and

    standards. This detail is for general information and guidance only

    and Dryvit specifically disclaims any liability for the use of this

    detail and for the architecture, design, engineering or workmanship of

    any project. The project design professional determines, in its sole

    discretion, whether this detail or a functionally equivalent alternative

    is best suited for the project. Use of a functionally equivalent detail

    does not violate Dryvit's warranty. This detail is subject to change

    without notice. Contact Dryvit to insure you have the most recent

    version.

    Major Penetrations

    OSPE 0.0.21

    EXTEND DETAIL MESH 152 MM (6") ONSILL & JAMB; HEAD & JAMB SIMILAR

    241 MM X 305 MM(9-1/2" X 12") DETAILMESH® "BUTTERFLIES"

    DRYVIT TRACK

    INSULATION BOARD CLOSUREBLOCKS WRAPPED WITHDRYVIT DETAIL MESH®

    INSULATION BOARD

    WRAP DRYVIT DETAIL MESHTO BACKSIDE OF EPS MIN. 64 MM (2 1/2")

    SPLICE PIECE OF DETAIL REINFORCINGMESH REQUIRED AT CORNER

    ©

    Dryvit Systems, Inc.

    Issued: 6/2020

  • without notice. Contact Dryvit to insure you have the most recent

    does not violate Dryvit's warranty. This detail is subject to change

    is best suited for the project. Use of a functionally equivalent detail

    discretion, whether this detail or a functionally equivalent alternative

    any project. The project design professional determines, in its sole

    detail and for the architecture, design, engineering or workmanship of

    and Dryvit specifically disclaims any liability for the use of this

    standards. This detail is for general information and guidance only

    professional. All systems must comply with local building codes and

    Dryvit products is the responsibility of the project's design

    The architecture, engineering and design of the project using the

    DRYVIT RECOMMENDS THAT GROUND FLOORAPPLICATIONS AND ALL FACADES EXPOSEDTO ABNORMAL STRESS, HIGH TRAFFIC, ORDELIBERATE IMPACT HAVE THE BASE COATREINFORCED WITH PANZER® MESH PRIOR TOSTANDARD™ OR STANDARDPLUS™ MESH. LOCATION OF HIGH IMPACTZONES SHOULD BE INDICATED ON CONTRACTDRAWINGS.

    OUTSULATION® PE SYSTEM® NOTE:

    1.

    OUTSULATIONPE SYSTEM

    ENTIRE PERIMETER OF PIPE SLEEVE ISCAULKED TO PREVENT WATER ENTRYINTO WALL.

    2.

    BY OTHERS

    version.

    BY OTHERS

    Sign Attachment

    12.7 MM (1/2") MIN.

    OSPE 0.0.22

    INSULATION BOARDDRYVIT ADHESIVE

    DRYVIT FINISH

    DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT

    APPROVED SUBSTRATE

    NON-CORROSIVE SLEEVE

    DRYVIT AIR/WATER-RESISTIVEBARRIER COATING

    SIGN FIXTURE

    COMPATIBLE SEALANT WITHBOND BREAKER TAPE, BY OTHERS(SEE NOTE 2)

    SCREW/BOLT ATTACHMENTTO BUILDING FRAMING

    BEARING WASHER

    BLOCKING (SECURETO FRAMING)

    ©

    Dryvit Systems, Inc.

    Issued: 6/2020

  • Aesthetic Reveals

    professional. All systems must comply with local building codes and

    standards. This detail is for general information and guidance only

    detail and for the architecture, design, engineering or workmanship of

    any project. The project design professional determines, in its sole

    discretion, whether this detail or a functionally equivalent alternative

    is best suited for the project. Use of a functionally equivalent detail

    does not violate Dryvit's warranty. This detail is subject to change

    OUTSULATION® PE SYSTEM®DRYVIT RECOMMENDS THAT GROUND FLOORAPPLICATIONS AND ALL FACADES EXPOSEDTO ABNORMAL STRESS, HIGH TRAFFIC, ORDELIBERATE IMPACT HAVE THE BASE COATREINFORCED WITH PANZER® MESH PRIOR TOSTANDARD™ OR STANDARDPLUS™ MESH. LOCATION OF HIGH IMPACTZONES SHOULD BE INDICATED ON CONTRACTDRAWINGS.

    NOTE:1. MIN. 51 MM (2") THICKNESS OF EPS IS

    REQUIRED AT BASE OF REVEALS.2.

    The architecture, engineering and design of the project using the

    Dryvit products is the responsibility of the project's design

    and Dryvit specifically disclaims any liability for the use of this

    without notice. Contact Dryvit to insure you have the most recent

    version.

    64 MM (2 1/2")

    BY OTHERS OUTSULATION PESYSTEM

    51 MM (2") MIN.(SEE NOTE 2)

    OSPE 0.0.23

    SLOPE BOTTOM SURFACEFOR DRAINAGE (TYP.)

    APPROVED SUBSTRATE

    DRYVIT FINISHDRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT

    INSULATION BOARDDRYVIT DETAIL MESH®EMBEDDED IN DRYVIT BASE COAT

    DRYVIT ADHESIVE

    DRYVIT AIR/WATER-RESISTIVEBARRIER COATING

    ©

    Dryvit Systems, Inc.

    Issued: 6/2020

  • BY OTHERS

    does not violate Dryvit's warranty. This detail is subject to change

    is best suited for the project. Use of a functionally equivalent detail

    discretion, whether this detail or a functionally equivalent alternative

    any project. The project design professional determines, in its sole

    detail and for the architecture, design, engineering or workmanship of

    standards. This detail is for general information and guidance only

    professional. All systems must comply with local building codes and

    Projecting Graphics

    OSPE 0.0.24

    OUTSULATIONPE SYSTEM

    version.

    without notice. Contact Dryvit to insure you have the most recent

    and Dryvit specifically disclaims any liability for the use of this

    Dryvit products is the responsibility of the project's design

    The architecture, engineering and design of the project using the

    OVERLAP 64 MM (2 1/2")

    1.

    2.

    NOTE:

    PERCENTAGE OF WALL AREA COVERED BY EPSFOAM SHAPES IN EXCESS OF 102 MM (4 IN) INTHICKNESS SHALL NOT EXCEED 15%.

    MAXIMUM THICKNESS OF EPS BUILT OUT SHAPESSHALL NOT EXCEED 305 MM (12 INCHES) AT ANYPOINT MEASURED FROM THE SUBSTRATE.

    OUTSULATION® PE SYSTEM®

    SLOPE TOP SURFACE FORPOSITIVE DRAINAGE

    DRYVIT FINISH

    DRYVIT REINFORCINGMESH EMBEDDED INDRYVIT BASE COAT

    DRYVIT ADHESIVE

    DRYVIT AIR/WATER-RESISTIVEBARRIER COATING

    APPROVED SUBSTRATE

    INSULATION BOARD

    DRYVIT FINISH

    INSULATION BOARDDRYVIT ADHESIVE

    DRYVIT DETAIL MESH®LAPPED 64 MM (2 1/2") MIN.ONTO ADJACENT EPS

    EPS FOAM SHAPE (SEE NOTES 1 AND 2)DRYVIT ADHESIVE

    APPROVED SUBSTRATE

    DRYVIT AIR/WATER-RESISTIVEBARRIER COATING

    ©

    Dryvit Systems, Inc.

    Issued: 6/2020

  • SLOPE GRAPHIC FORPOSITIVE DRAINAGE

    OUTSULATION® PE SYSTEM®

    51 MM (2") MIN.

    The architecture, engineering and design of the project using the

    Dryvit products is the responsibility of the project's design

    and Dryvit specifically disclaims any liability for the use of this

    without notice. Contact Dryvit to insure you have the most recent

    version.

    OUTSULATION PESYSTEM

    BY OTHERS

    Recessed Graphics

    professional. All systems must comply with local building codes and

    standards. This detail is for general information and guidance only

    detail and for the architecture, design, engineering or workmanship of

    any project. The project design professional determines, in its sole

    discretion, whether this detail or a functionally equivalent alternative

    is best suited for the project. Use of a functionally equivalent detail

    does not violate Dryvit's warranty. This detail is subject to change

    OSPE 0.0.25

    DRYVIT DETAIL MESH®LAPPED 64 MM (2 1/2") MIN.BENEATH DRYVIT REINFORCINGMESH EMBEDDED IN DRYVITBASE COAT

    INSULATION BOARD

    DRYVIT ADHESIVE

    DRYVIT AIR/WATER RESISTIVEBARRIER COATING

    APPROVED SUBSTRATE

    DRYVIT FINISH

    DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT

    INSULATION BOARD

    APPROVED SUBSTRATEDRYVIT AIR/WATER-RESISTIVE

    BARRIER COATING

    DRYVIT FINISH

    DRYVIT ADHESIVE

    DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT

    ©

    Dryvit Systems, Inc.

    Issued: 6/2020

  • Dryvit Vent Assembly™

    is best suited for the project. Use of a functionally equivalent detail

    discretion, whether this detail or a functionally equivalent alternative

    detail and for the architecture, design, engineering or workmanship of

    professional. All systems must comply with local building codes and

    OUTSULATION® PE SYSTEM®

    OSPE 0.0.26

    version.

    without notice. Contact Dryvit to insure you have the most recent

    does not violate Dryvit's warranty. This detail is subject to change

    any project. The project design professional determines, in its sole

    and Dryvit specifically disclaims any liability for the use of this

    standards. This detail is for general information and guidance only

    Dryvit products is the responsibility of the project's design

    The architecture, engineering and design of the project using the

    51 MM (2")

    152 MM(6")

    305 MM (12")

    203 MM (8")

    19 MM (3/4")

    143 MM(5 5/8")

    ©

    Dryvit Systems, Inc.

    Issued: 6/2020

    OPE-ds846_COVOPE-ds846_TOC_2020-06Sheets and ViewsModel

    OPE-ds846_01_2020-06Sheets and ViewsModel

    OPE-ds846_02_2020-06Sheets and ViewsModel

    OPE-ds846_03_2020-06Sheets and ViewsModel

    OPE-ds846_04_2020-06Sheets and ViewsModel

    OPE-ds846_05_2020-06Sheets and ViewsModel

    OPE-ds846_06_2020-06Sheets and ViewsModel

    OPE-ds846_07_2020-06Sheets and ViewsModel

    OPE-ds846_08_2020-06Sheets and ViewsModel

    OPE-ds846_09_2020-06Sheets and ViewsModel

    OPE-ds846_10_2020-06Sheets and ViewsModel

    OPE-ds846_11_2020-06Sheets and ViewsModel

    OPE-ds846_12_2020-06Sheets and ViewsModel

    OPE-ds846_13_2020-06Sheets and ViewsModel

    OPE-ds846_14_2020-06Sheets and ViewsModel

    OPE-ds846_15_2020-06Sheets and ViewsModel

    OPE-ds846_16_2020-06Sheets and ViewsModel

    OPE-ds846_17_2020-06Sheets and ViewsModel

    OPE-ds846_18_2020-06Sheets and ViewsModel

    OPE-ds846_19_2020-06Sheets and ViewsModel

    OPE-ds846_20_2020-06Sheets and ViewsModel

    OPE-ds846_21_2020-06Sheets and ViewsModel

    OPE-ds846_22_2020-06Sheets and ViewsModel

    OPE-ds846_23_2020-06Sheets and ViewsModel

    OPE-ds846_24_2020-06Sheets and ViewsModel

    OPE-ds846_25_2020-06Sheets and ViewsModel

    OPE-ds846_26_2020-06Sheets and ViewsModel