www.rosenberger.com/osi OPTICAL SOLUTIONS & INFRASTRUCTURE Cleaning and inspection fiber optic connectors

OPTICAL SOLUTIONS & INFRASTRUCTURE...2.4µm 8.6µm Source: VIAVI Cleaning and inspection of fiber optic connectors IEC 61300-3-35 Pass or Fail? 10 Pass or Fail??? Pass, since metallic

  • Upload
    others

  • View
    3

  • Download
    0

Embed Size (px)

Citation preview

Page 1: OPTICAL SOLUTIONS & INFRASTRUCTURE...2.4µm 8.6µm Source: VIAVI Cleaning and inspection of fiber optic connectors IEC 61300-3-35 Pass or Fail? 10 Pass or Fail??? Pass, since metallic

www.rosenberger.com/osi

OPTICAL SOLUTIONS & INFRASTRUCTURECleaning and inspection fiber optic connectors

Page 2: OPTICAL SOLUTIONS & INFRASTRUCTURE...2.4µm 8.6µm Source: VIAVI Cleaning and inspection of fiber optic connectors IEC 61300-3-35 Pass or Fail? 10 Pass or Fail??? Pass, since metallic

Cleaning and inspection of fiber optic connectorsGeneral information

Process of inspection and cleaning of fiber optic connectors

2

Source: VIAVI

CONTROL CLEAN?

CLEANNO YES

CONNECT

The process must be adhered to in order to achieve an optimal result.

The process applies to both sides of the connector. Only when both connector faces are clean may they be connected.

Page 3: OPTICAL SOLUTIONS & INFRASTRUCTURE...2.4µm 8.6µm Source: VIAVI Cleaning and inspection of fiber optic connectors IEC 61300-3-35 Pass or Fail? 10 Pass or Fail??? Pass, since metallic

Cleaning and inspection of fiber optic connectorsOverview connector inspection tools

Dry cleaning tools for loose connectors (lint-free cleaning cloths or tapes)

Dry cleaning tools for installed connectors

Dry and wet cleaning tools

3

Seikoh FerruleProOptipop Pipe CleanerAMS ReelcleanerAFL Fiber Wipes Sticklers Clean Wipes AFL Card Cleaner

AFL Cletop Sticks Fujikura Oneclick Seikoh FerruleMate UC Conec MTP®-Cleaner

Page 4: OPTICAL SOLUTIONS & INFRASTRUCTURE...2.4µm 8.6µm Source: VIAVI Cleaning and inspection of fiber optic connectors IEC 61300-3-35 Pass or Fail? 10 Pass or Fail??? Pass, since metallic

Cleaning and inspection of fiber optic connectorsOverview connector inspection tools

Wet cleaning tools for loose connectors and installed connectors

CleanBlast

Dry and wet cleaning tools

4

AFL pump buttle FIS soaked wipes AFL cleaning fluid

Source: VIAVI

Page 5: OPTICAL SOLUTIONS & INFRASTRUCTURE...2.4µm 8.6µm Source: VIAVI Cleaning and inspection of fiber optic connectors IEC 61300-3-35 Pass or Fail? 10 Pass or Fail??? Pass, since metallic

Cleaning and inspection of fiber optic connectorsOverview connector inspection tools

Cleaning with different types of contamination

Cleaning tools in use

5

Cleaning of dust

beforehand afterwards

Cleaning of grease

beforehand afterwards

Sourc

e:

AF

L

Page 6: OPTICAL SOLUTIONS & INFRASTRUCTURE...2.4µm 8.6µm Source: VIAVI Cleaning and inspection of fiber optic connectors IEC 61300-3-35 Pass or Fail? 10 Pass or Fail??? Pass, since metallic

Cleaning and inspection of fiber optic connectorsOverview connector inspection tools

How to clean optical connectors correctly?

Cleaning process of heavily dirty connector faces

6

Heavily dirty plug With Isopropyl precleaning Always dry clean again

Is the resultsufficient?

Page 7: OPTICAL SOLUTIONS & INFRASTRUCTURE...2.4µm 8.6µm Source: VIAVI Cleaning and inspection of fiber optic connectors IEC 61300-3-35 Pass or Fail? 10 Pass or Fail??? Pass, since metallic

Cleaning and inspection of fiber optic connectorsOverview connector inspection tools

Inspection tools in the field and for production

7

Handheld microscope Microscope probe with LCD display

Source: VIAVI

Microscope probe for production Microscope probe on the measuring instrument in the field

Page 8: OPTICAL SOLUTIONS & INFRASTRUCTURE...2.4µm 8.6µm Source: VIAVI Cleaning and inspection of fiber optic connectors IEC 61300-3-35 Pass or Fail? 10 Pass or Fail??? Pass, since metallic

Cleaning and inspection of fiber optic connectorsIEC 61300-3-35

IEC 61300-3-35 describes the usability of a connector face with regard to possible damage or contamination.

The connector front surface is divided into four zones to be considered, core area,

sheath area, adhesive edge, inner ferrule area.

Criteria have been defined for damage or contamination with regard to its size and

location in relation to the centre of the core.

There are different criteria for multimode and singlemode.

What does IEC 61300-3-35 say?

8

Source: VIAVI

Page 9: OPTICAL SOLUTIONS & INFRASTRUCTURE...2.4µm 8.6µm Source: VIAVI Cleaning and inspection of fiber optic connectors IEC 61300-3-35 Pass or Fail? 10 Pass or Fail??? Pass, since metallic

Cleaning and inspection of fiber optic connectorsIEC 61300-3-35

Pass or Fail?

9

Subjective view: Pass or Fail??? Evaluation with pass/fail analysis results in Fail!!!

3.0µm

2.4µm

8.6µm

Sourc

e:

VIA

VI

Page 10: OPTICAL SOLUTIONS & INFRASTRUCTURE...2.4µm 8.6µm Source: VIAVI Cleaning and inspection of fiber optic connectors IEC 61300-3-35 Pass or Fail? 10 Pass or Fail??? Pass, since metallic

Cleaning and inspection of fiber optic connectorsIEC 61300-3-35

Pass or Fail?

10

Pass or Fail??? Pass, since metallic plug and only the glass jacket and glass core and not the ferrule is analyzed.

Page 11: OPTICAL SOLUTIONS & INFRASTRUCTURE...2.4µm 8.6µm Source: VIAVI Cleaning and inspection of fiber optic connectors IEC 61300-3-35 Pass or Fail? 10 Pass or Fail??? Pass, since metallic

Cleaning and inspection of fiber optic connectorsIEC 61300-3-35

Documentation for acceptance in the event of a fault

11

Connector before cleaning Connector after cleaning

Page 12: OPTICAL SOLUTIONS & INFRASTRUCTURE...2.4µm 8.6µm Source: VIAVI Cleaning and inspection of fiber optic connectors IEC 61300-3-35 Pass or Fail? 10 Pass or Fail??? Pass, since metallic

Cleaning and inspection of fiber optic connectorsResume

When do you... and who has to clean and inspect?

12

When must cleaning and inspection be carried out? Installation of the passive network for acceptance For each measurement During initial operation (wiring) During maintenance

Who needs to clean and inspect? Manufacturer Installater Maintenance technician Systems engineer

In principle, it must be inspected and cleaned by anyone who dissolves or establishes an optical connection!

Sourc

e:

VIA

VI

Page 13: OPTICAL SOLUTIONS & INFRASTRUCTURE...2.4µm 8.6µm Source: VIAVI Cleaning and inspection of fiber optic connectors IEC 61300-3-35 Pass or Fail? 10 Pass or Fail??? Pass, since metallic

Cleaning and inspection of fiber optic connectorsPractice

Examples of contaminated connectors

13