SICAM
Multifunctional RecorderSICAM Q200 7KG97
V2.20
Manual
Table of Contents
Operational Indications andOperating Parameters
1
E50417-H1040-C606-A5
NOTE
For your own safety, observe the warnings and safety instructions contained in this document, if available.
Disclaimer of LiabilityThis document has been subjected to rigorous technical review before beingpublished. It is revised at regular intervals, and any modifications andamendments are included in the subsequent issues. The content of thisdocument has been compiled for information purposes only. AlthoughSiemens AG has made best efforts to keep the document as precise and up-to-date as possible, Siemens AG shall not assume any liability for defects anddamage which result through use of the information contained herein.This content does not form part of a contract or of business relations; nordoes it change these. All obligations of Siemens AG are stated in the relevantcontractual agreements.Siemens AG reserves the right to revise this document from time to time.Document version: E50417-H1040-C606-A5.00Edition: 03.2018Version of the product described: V2.20
CopyrightCopyright © Siemens AG 2018. All rights reserved.The disclosure, duplication, distribution and editing of this document, orutilization and communication of the content are not permitted, unlessauthorized in writing. All rights, including rights created by patent grant orregistration of a utility model or a design, are reserved.
TrademarksSIPROTEC™, DIGSI™, SIGUARD™, SIMEAS™, and SICAM™ are trademarks ofSiemens AG. Any unauthorized use is illegal. All other designations in thisdocument can be trademarks whose use by third parties for their own pur-poses can infringe the rights of the owner.
SICAM, Multifunctional Recorder, Manual 3
E50417-H1040-C606-A5, Edition 03.2018
Table of Contents
1 Operational Indications and Operating Parameters..........................................................................................5
1.1 Operational Indications ......................................................................................................................6
1.2 Process Connections ...........................................................................................................................9
1.2.1 AC Measurement ..........................................................................................................................9
1.2.2 Binary Inputs S and R................................................................................................................... 10
1.2.3 Binary Outputs ............................................................................................................................ 11
1.2.4 LEDs ........................................................................................................................................... 11
1.3 Automation Functions ...................................................................................................................... 13
1.3.1 Limit Violation 1-8 and 9-16 ........................................................................................................ 13
1.3.2 Group Indications 1-4 .................................................................................................................. 13
1.4 Display............................................................................................................................................. 14
1.4.1 Display Settings .......................................................................................................................... 14
1.4.2 User-Defined Screen ................................................................................................................... 14
1.5 Energy Management ........................................................................................................................ 16
1.5.1 Load Profile ................................................................................................................................ 16
1.5.2 Tariffs (TOU) ............................................................................................................................... 16
1.6 Recording and Reporting .................................................................................................................. 17
1.6.1 Event Recorders .......................................................................................................................... 17
1.6.2 Waveform Recorder .................................................................................................................... 17
1.6.3 Measurement Recorder ............................................................................................................... 20
1.6.4 Trend Recorder ........................................................................................................................... 20
1.6.5 Mains Signaling Voltage .............................................................................................................. 21
1.6.6 Transient Recorder ...................................................................................................................... 21
1.6.7 Memory Management ................................................................................................................. 22
1.6.8 Report Configuration................................................................................................................... 22
1.6.9 Start and Stop of Recorders ......................................................................................................... 23
1.7 Administration ................................................................................................................................. 25
1.7.1 Time Synchronization.................................................................................................................. 25
1.7.2 Ethernet Communication ............................................................................................................ 26
Table of Contents
4 SICAM, Multifunctional Recorder, Manual
E50417-H1040-C606-A5, Edition 03.2018
1.7.3 Protocol IEC 61850 ..................................................................................................................... 27
1.7.4 Protocol Modbus TCP and Modbus TCP/RTU Gateway .................................................................... 28
1.7.5 Protocol SNMP ............................................................................................................................ 29
1.7.6 Protocol DNP3 IP ......................................................................................................................... 29
1.7.7 Communication Serial ................................................................................................................. 30
1.7.8 Serial Communication ................................................................................................................. 31
1.7.8.1 Basic Settings ........................................................................................................................ 31
1.7.8.2 Mapping – Measured Values 1 to 15 ....................................................................................... 32
1.7.8.3 Mapping – Indications ........................................................................................................... 33
1.7.9 Device and Language .................................................................................................................. 34
1.7.10 Password Change........................................................................................................................ 35
SICAM, Multifunctional Recorder, Manual 5
E50417-H1040-C606-A5, Edition 03.2018
1 Operational Indications and Operating Parameters1.1 Operational Indications 61.2 Process Connections 91.3 Automation Functions 131.4 Display 141.5 Energy Management 161.6 Recording and Reporting 171.7 Administration 25
Operational Indications and Operating Parameters1.1 Operational Indications
6 SICAM, Multifunctional Recorder, Manual
E50417-H1040-C606-A5, Edition 03.2018
1.1 Operational Indications
Indication Description Notes
Device OK The device startup was successful. Indication ON: Device readyIndication OFF: Device startup not successful or I/O boardsdetection failed
Battery Failure Battery voltage < 2.7 V or no bat-tery inserted
Indication ON: Battery failureThe battery is checked during each device startup and oncea day during operation. A possible battery failure is indicat-ed only after the corresponding check.
Time SynchronizationError
Error during the time synchroniza-tion from the NTP server or fieldbus
Indication OFF: At least 1 time message was received duringthe set timer (Error indication after). The time stamp is setwhen the first valid time information or time synchroniza-tion is received.Indication ON: No time message was received during the settimer (Error indication after).The time stamp is set after the Error indication after timerhas expired and no synchronization message was received.Parameter range: see chapter 1.7.1 Time Synchronization
Error during internal time synchro-nization
Indication ON: RTC time invalid (during device start in caseof battery failure)Indication OFF: After setting the clock via HTML
Default IP Address The device has started with a de-fault IP address after pressing theF4 button for more than 3 s duringoperation.
Indication ON: F4 was pressed and default IP is set in thedevice.
Primary NTP ServerError
Faulty or no response from theprimary NTP server
Indication ON: ErrorIndication OFF: Valid time messages have been received fora period of 10 minOnly for time synchronization via Ethernet NTP
Secondary NTP ServerError
Faulty or no response from thesecondary NTP server
Indication ON: ErrorIndication OFF: Valid time messages have been received fora period of 10 minOnly for time synchronization via Ethernet NTP
Daylight Saving Time Switching between daylight savingtime/standard time
Indication ON: Daylight saving timeIndication OFF: Standard time
Ethernet Link Error For Ethernet function = Switch:No Ethernet connection on Ch1and Ch2For Ethernet function = Two inter-faces:No Ethernet connection on Ch1
Indication ON: ErrorIndication OFF: Ethernet link recognized
Operational Indications and Operating Parameters1.1 Operational Indications
SICAM, Multifunctional Recorder, Manual 7
E50417-H1040-C606-A5, Edition 03.2018
Indication Description Notes
Ethernet Link 2 Error For Ethernet Function = Switch:IrrelevantFor Ethernet Function = Two inter-faces:No Ethernet connection on Ch2
Indication ON: ErrorIndication OFF: Ethernet link recognized
Modbus TCP OK(Modbus TCP Server)
At least 1 Modbus TCP server con-nection has received Modbus mes-sages.
Indication ON: At least 1 Modbus message was receivedduring the set communication supervision time. The timestamp is set when the first valid message is received.Indication OFF: No Modbus message was received duringthe set communication supervision time
Modbus RTU MasterOK
All configured Modbus slave devic-es respond to request telegrams.
Indication ON: If all configured Modbus slave devices re-spond successfully to request telegrams.Indication OFF: If at least one Modbus slave device does notrespond to a request telegram or if at least one Modbusslave device responds with a Modbus exception code. For more information, see Communication Manual SICAMQ200 and Device Manual SICAM Q200.
IEC 61850 Communi-cation OK
IEC 61850 server is ready/not readyto accept IEC 61850 client connec-tions.
Indication ON: IEC 61850 server is ready to acceptIEC 61850 client connections.Indication OFF: IEC 61850 server is not ready to acceptIEC 61850 client connections.
Modbus Serial OK(Modbus RTU (Slave))
The Modbus serial communicationhas received a valid Modbus mes-sage.
Indication ON: At least 1 serial message was received duringthe set communication supervision time. The time stamp isset when the first valid message is received.Indication OFF: No serial message was received during theset communication supervision time.
Settings Load Starting to change the parametersof the passive set of parameters.
Indication ON: Start of changesIndication OFF: Changes complete
Settings Check The passive set of parameters is tobe activated; the internal parame-ter check is running.
Indication ON: Check startedIndication OFF: Check complete
Settings Activate The passive set of parameters isenabled and the device works withthese parameters.
Indication ON: Activation startedIndication OFF: Activation complete
Limit Violation x Indication that a parameterizedlimiting value has been violated
Indication ON: The limit of the monitored measured valuehas been violated or no measured value is parameterized asinput of the limiting value.Indication OFF: The limit of the monitored measured valueis not violated.Message invalid: The monitored measured value is invalid(for example, frequency at V < 15 % of Vrated).x = 1 to 16
Operational Indications and Operating Parameters1.1 Operational Indications
8 SICAM, Multifunctional Recorder, Manual
E50417-H1040-C606-A5, Edition 03.2018
Indication Description Notes
Indication x from Re-mote
Status of any indications which canbe set for control via communica-tion.
Indication ONIndication OFFMessage invalid: Not yet updated via the communication oragain invalid via the communication.x = 1 to 14
Binary Input x-SBinary Input x-R
Indication of the logic state of thebinary input (ON/OFF)
Indication invalid: in startup not updatedBinary input high: ON (OFF if inverted)Binary input low: OFF (ON if inverted)If the binary input has not been set to a function (load pro-file, tariff TOU), a change is logged as an operational indica-tion.x = 1 to 3
Rotating Field Clock-wise
Indication of rotation voltage Indication ON: Phase sequence Va-Vb-Vc, rotation clockwiseIndication OFF: Phase sequence Va-Vc-Vb, (2 phases inter-changed); rotation counter-clockwiseIndication invalid: Direction of rotation cannot be calculated(for example, no voltage applied)
Group indication x Up to 4 single-point indications canbe linked logically and combined toa group indication.
A total of 4 group indications can be parameterized.x = 1 to 4
Voltage Event Availa-ble
Indication of a supply-voltageevent
Overvoltage, undervoltage, frequency interruption
SD Card Error Indication of an SD card error SD card defective or read/write error
Load Profile PeriodClosed
Indication that a period has beenclosed.
Only Indication on is logged.
Load Profile Synchr.Period
Indication that a synchronizationsignal was received.
Only Indication on is logged.
Load Profile Tariff x Indication that the tariff x has beenset.
Only Indication on is logged.x = 1 to 4
Power Supply Failure The power supply of the devicedropped below the lower limit.
Indication only is logged in the Operational log; can not berouted as input for automation functions or to communica-tion.
Operational Indications and Operating Parameters1.2 Process Connections
SICAM, Multifunctional Recorder, Manual 9
E50417-H1040-C606-A5, Edition 03.2018
1.2 Process Connections
1.2.1 AC Measurement
Table 1-1 Settings for Measured-Value Acquisition
Parameter Default Settings Range
AC measurement
Rated frequency 50 Hz 50 Hz ± 15 %60 Hz ± 15 %
Network type1 4-wire, 3-phase, unbal-anced
1-phase network3-wire, 3-phase balanced3-wire, 3-phase, unbalanced (2 * I)3-wire, 3-phase, unbalanced (3 * I)4-wire, 3-phase, balanced4-wire, 3-phase, unbalanced
Primary nominal voltage1
(Phase-N/PE)230.00 V 57.7 V to 400 V (autorange)
IEC 61000-4-30 Class A:· Up to AC 230 V: 200 % overvoltage· > AC 230 V to 400 V:
200 % to 15 % overvoltage
UL conditions:· Up to AC 170 V:
200 % overvoltage
· > AC 170 V to 300 V:200 % to 15 % overvoltage
Using IN connection as2 IN not connectedIN3
I4
Zero-point suppression4 0.3 %(of Vrated, Irated)
0.0 % to 10.0 %
Measurement interval Base 10-cycle (at 50 Hz)orBase 12-cycle (at 60 Hz)
Base 10-cycle at 50 Hz orBase 12-cycle at 60 HzAggregation 150-cycle at 50 Hz orAggregation 180-cycle at 60 Hz
1 In the case of contradictory parameter settings, Primary nominal voltage is indicated as faulty (red) and Network type as not ad-justable (gray). Moreover, the Send button is disabled.
2 This parameter is not available when the connection type is 1-phase network .
3 This option is only available when the connection type is 4-wire, 3-phase, unbalanced .
4 Voltage and current values smaller than/equal to the setting referred to 100 % are not included in the calculation and display.
Operational Indications and Operating Parameters1.2 Process Connections
10 SICAM, Multifunctional Recorder, Manual
E50417-H1040-C606-A5, Edition 03.2018
Parameter Default Settings Range
Flicker lamp model 230 V 230 V120 V
Transformer settings
Voltage transformer no noyes
Primary rated voltage AC 10 000.0 V AC 100.0 V to 1 000 000.0 V
Secondary rated voltage AC 100.0 V AC 1.0 V to 460.0 V
Current transformer no noyes
Primary rated current AC 1000.0 A AC 1.0 A to 100 000.0 A
Secondary rated current AC 1.0 A AC 1.0 A to 10.0 A
Depending on the configuration of the Using IN connection as parameter, the following parameters show INor I4, or are not visible.
Current transformer IN/I4 no noyes
Ratio CT IN/I4 equal CT?5 yes noyes
Primary rated current IN/I46 AC 1000.0 A AC 1.0 A to 100 000.0 A
Secondary rated current IN/I46 AC 1.0 A AC 1.0 A to 10.0 A
1.2.2 Binary Inputs S and R
Table 1-2 Settings for Binary Inputs S and R
Parameter Default Settings Setting Range
Threshold voltage 19 V 19 V88 V176 V
Software filter time(only settable if Routed as:Status information hasbeen set)
1 (* 2 ms) 2 ms to 120 000 ms(settable in 2-ms increments)
Value For example for terminalS11/12:Binary input 3-S
Max. 31 characters
5 This parameter is only visible if you set both the Current transformer parameter and the Current transformer IN/I4 parameter toyes .
6 This parameter is only visible in one of the following cases: 1) Both the Current transformer parameter and the Current transform-er IN/I4 parameter are set to yes , and the Ratio CT IN/I4 equal CT? parameter is set to no ; 2) The Current transformer parameter isset to no , and the Current transformer IN/I4 parameter is set to yes .
Operational Indications and Operating Parameters1.2 Process Connections
SICAM, Multifunctional Recorder, Manual 11
E50417-H1040-C606-A5, Edition 03.2018
1.2.3 Binary Outputs
Table 1-3 Settings for Binary Outputs
Parameter Default Settings Setting Range
Source type Indication IndicationEnergy counter
Source Type Indication
Indication7 -none- Acc. to list box
BO description (can be set for all binary out-puts individually)
For example for terminalS1/2:Binary output 1-S
Max. 31 characters
Source inverted (can be set individually for allrelay outputs)
No NoYes
Operating mode8
(can be set individually for allrelay outputs)
Persistent PersistentPersistent with fail safePulsePulse with retrigger
Output time for pulse operatingmode (setting only possible foroperating modes Pulse andPulse with retrigger)
20 (* 10 ms) 50 ms to 3 600 000 ms
Source Type Energy Counter
Energy counter 7 -none- Acc. to list box
Energy increase per pulse 1.00 Wh 0.10 Wh/VAh/varh to1 000 000.00 Wh/VAh/varh
Output time for pulse operatingmode
20 * 10 ms = 200 ms 50 ms to 3 600 000 ms
1.2.4 LEDs
Parameter Default Settings Setting Range
ERROR -none- -none-Battery failureEthernet link errorTime synchronization errorPrimary NTP server errorSecondary NTP serverSD card error
7 If you select -none- as the source of an indication or energy counter , the corresponding binary output is inactive.
8 If you have selected one of the 2 Pulse types in the Operating mode list box, enter an output time x (in x *10 ms) in the Outputtime for pulse operating mode field.
Operational Indications and Operating Parameters1.2 Process Connections
12 SICAM, Multifunctional Recorder, Manual
E50417-H1040-C606-A5, Edition 03.2018
Parameter Default Settings Setting Range
H1H2H3H4
Only the indications for theparameterization of the binaryoutputs are displayed whichcan be used according to thecurrent device settings. Indica-tions which are read by Mod-bus slave devices are availablein the list box if they are pa-rameterized in Modbus MasterMapping.
-none- Acc. to list boxLimit violation, group indication and binaryinputs:Designation can be changed during parameteri-zation.
Indication inverted No NoYes
Operational Indications and Operating Parameters1.3 Automation Functions
SICAM, Multifunctional Recorder, Manual 13
E50417-H1040-C606-A5, Edition 03.2018
1.3 Automation Functions
1.3.1 Limit Violation 1-8 and 9-16
Parameter Default Settings Setting Range
Measurement -none- Measurement value selection list depending onnetwork type
Limit 0.00 -1 000 000 000 to 1 000 000 000 (unit)
Limit type Lower LowerUpper
Hysteresis (%) 1.0 0.0 to 10.0
Violation indication Limit Violation x(x = 1 to 16)
The name of the limiting value indication iscustomizable; max. 31 characters.
1.3.2 Group Indications 1-4
Parameter Default Settings Setting Range
Source
Only the indications for theparameterization of the binaryoutputs are displayed whichcan be used according to thecurrent device settings.Indications which are read byModbus slave devices are avail-able in the list box if they areparameterized in the ModbusMaster Mapping.
-none- Acc. to list boxLimit violation, group indication and binaryinputs:Designation can be changed during the parame-terization.
Source inverted No NoYes
Logic operation NONE NONEORAND
Group indication name Group Indication x(x = 1 to 4)
Any, max. 31 characters
Operational Indications and Operating Parameters1.4 Display
14 SICAM, Multifunctional Recorder, Manual
E50417-H1040-C606-A5, Edition 03.2018
1.4 Display
1.4.1 Display Settings
Table 1-4 Settings for Display
Parameter Default Setting Setting Options
Contrast 8 0 to 10
Time until dimmed 10 1 min to 99 min
Refresh time 1000 330 ms to 3000 ms
Inverse display No NoYes
Phase label (L1, L2, L3) (L1, L2, L3)(a, b, c)
Voltage harmonics unit % %V
1.4.2 User-Defined Screen
Table 1-5 Settings for User-Defined Screens
Parameter Default Settings Setting Range
Screen type -none-9 -none-2 measured values, numerical4 measured values, numerical2 measured values, graphical + numerical3 measured values, graphical + numerical
Screen name USER_SCREEN_x(x = 1 to 4)
You can update and edit it directly; max.18 characters
2 measured values, numerical:- Display 1, numerical- Display 2, numerical
-none- Measuring-values selection depending on net-work type
4 measured values, numerical:- Display 1, numerical- Display 2, numerical- Display 3, numerical- Display 4, numerical
-none-
2 measured values, graphicaland numerical:- Display 1, graph./num.- Display 2, graph./num.
-none-
9 If there is no selection the displays explained in the following do not exist.
Operational Indications and Operating Parameters1.4 Display
SICAM, Multifunctional Recorder, Manual 15
E50417-H1040-C606-A5, Edition 03.2018
Parameter Default Settings Setting Range
3 measured values, graphicaland numerical:- Display 1, graph./num.- Display 2, graph./num.- Display 3, graph./num.
-none-
Display x, graph./num.(x = 1 to 3) - Min value- Max value
Unit according to measur-ing values1.010.0
The minimum and maximum value are definedby the selected parameters.
Operational Indications and Operating Parameters1.5 Energy Management
16 SICAM, Multifunctional Recorder, Manual
E50417-H1040-C606-A5, Edition 03.2018
1.5 Energy Management
1.5.1 Load Profile
Parameter Default Settings Setting Range
Subperiod time 15 minutes 1 min to 6 min in 1-min steps,10 min, 12 min, 15 min, 20 min, 30 min, 60min
Number of subperiods 1 1 to 5
Synchronization source Internal clock NoneProtocolBinary input 1Binary input 2Internal clock
Type reactive power used Q1 Q1QnQtot
1.5.2 Tariffs (TOU)
Parameter Default Settings Setting Range
Synchronization source Protocol ProtocolBinary input x-SBinary input x-R(x = 1 to 3)
Operational Indications and Operating Parameters1.6 Recording and Reporting
SICAM, Multifunctional Recorder, Manual 17
E50417-H1040-C606-A5, Edition 03.2018
1.6 Recording and Reporting
1.6.1 Event Recorders
Parameter Default Setting Default Options
Voltage event
Reference voltage Primary nominal voltage (Vn) Sliding reference voltage (Vsr)Primary nominal voltage (Vn)
Swell threshold10 110 % 105 % to 140 %, increments of 5 %
Dip threshold10 90 % 75 % to 95 %, increments of 5 %
Interruption threshold 5 % 1 %, 2 %, 3 %, 5 %, 8 %, 10 %
Hysteresis 2 % 1 % to 6 %, increments of 1 %
Event detection mode11 ph-N ph-Nph-ph
RVC event
RVC threshold 6 % 1 %, 2 %, 3 %, 4 %, 5 %, 6 %
RVC hysteresis12 3 % 0.5 %, 1 %, 1.5 %, 2 %, 2.5 %, 3 %
RVC event detectionmode13
ph-N ph-Nph-ph
1.6.2 Waveform Recorder
Table 1-6 Settings for Waveform Recorder and Trigger Management
Parameter Default Setting Setting Options
Voltage trigger limits14
Trigger active No NoYes
Tolerance unit Percentage PercentageNumerical
Trigger by ph-N15 Yes NoYes
10 According to EN 50160 standard in the PQ report, the default settings of dip and swell (90 % and 110 %) are recommended.
11 Only for 3P4W (3-phase/4-wire) unbalanced network types, you can select the ph-N or ph-ph option as event detection mode.
12 According to IEC 61000-4-30 Edition 3.0, RVC hysteresis is recommended to be half of the threshold.
13 RVC event detection mode will always be synchronized with the setting Event detection mode .
14 You must follow the setting rules as below: Upper threshold > lower threshold and (upper threshold - lower threshold) > 2 * hystere-sis
Operational Indications and Operating Parameters1.6 Recording and Reporting
18 SICAM, Multifunctional Recorder, Manual
E50417-H1040-C606-A5, Edition 03.2018
Parameter Default Setting Setting Options
Upper threshold 110.00 % of the primary nominal volt-age
100.00 % to 200.00 % of the primarynominal voltage1 to 2 times the primary nominal volt-age16
Lower threshold 90.00 % of the primary nominal voltage 0.00 % to 99.99 % of the primary nom-inal voltage0.00 V to the primary nominal volt-age16
Hysteresis 2.00 % of the primary nominal voltage 0.00 % to 50.00 % of the primary nom-inal voltage
Trigger by ph-ph15 Yes NoYes
Upper threshold17 110.00 % of the primary voltage 100.00 % to 200.00 % of the primaryvoltage1 to 2 times the primary voltage16
Lower threshold17 90.00 % of the primary voltage 0.00 % to 99.99 % of the primary volt-age0.00 V to the primary voltage16
Hysteresis17 2.00 % of the primary voltage 0.00 % to 50.00 % of the primary volt-age
Current trigger limits14
Trigger active No NoYes
Tolerance unit Percentage PercentageNumerical
Upper threshold 120.00 % of the nominal current In 5.00 % to 200.00 % of the nominalcurrent In(0.05 × In) A18 to 1 000 000.00 A16
Lower threshold 0.00 % of the nominal current In 0.00 % to 100.00 % of the nominalcurrent In0.00 A to 1 000 000.00 A16
Hysteresis 2.00 % of the nominal current In 0.00 % to 50.00 % of the nominal cur-rent In0.00 A to 500 000.00 A
Configuration binary trigger
Trigger active No NoYes
15 This parameter is only available when the connection type is 4-wire, 3-phase, unbalanced .
16 When Tolerance unit is selected as numerical , the threshold is in number.
17 This parameter is only available when the connection type is 4-wire, 3-phase, unbalanced , and the Trigger by ph-ph is activated.
18 In is equal to 5 A in case of no CT; otherwise, In is the primary rated CT current.
Operational Indications and Operating Parameters1.6 Recording and Reporting
SICAM, Multifunctional Recorder, Manual 19
E50417-H1040-C606-A5, Edition 03.2018
Parameter Default Setting Setting Options
Trigger source Binary input 1-S Indication 1 from RemoteIndication 2 from RemoteBinary Input 1-SBinary Input 2-SBinary Input 3-SBinary Input 1-RBinary Input 2-RBinary Input 3-RGroup Indication 1Group Indication 2Group Indication 3Group Indication 4
NOTE: By default the option for group indications is not available for the parameter Trigger source. It is onlyavailable in the list after you configure the group indication in the menu Select automation functions.
Trigger value OFF OFFON
Zero sequence component voltage trigger limits
Trigger active No NoYes
Threshold 5 % 0.5 % to 10 %
Zero sequence component current trigger limits
Trigger active no NoYes
Threshold 5 % 0.5 % to 10 %
Frequency trigger limits
Trigger active No NoYes
Upper threshold 50.50 Hz19 50 Hz to 55 Hz19
60.60 Hz20 60 Hz to 66 Hz20
Lower threshold 49.50 Hz19 45 Hz to 50 Hz19
59.40 Hz20 54 Hz to 60 Hz20
Note: The default setting and setting options of the frequency trigger limits automatically adapt to the net-work rated frequency range which is configured at AC measurement.
Manual trigger
Trigger active No NoYes
Action Trigger If you set the Trigger active parameterto yes, the button Trigger is enabled.
Cyclic trigger
19 The rated frequency of the network set under the menu AC measurement is 50 Hz.
20 The rated frequency of the network set under the menu AC measurement is 60 Hz.
Operational Indications and Operating Parameters1.6 Recording and Reporting
20 SICAM, Multifunctional Recorder, Manual
E50417-H1040-C606-A5, Edition 03.2018
Parameter Default Setting Setting Options
Trigger active No NoYes
Trigger time 00:00:00 You can edit the text box directly orselect the trigger time from the calen-dar.
Recorder routing
Voltage Yes Not settableThe channels of voltage are mandatori-ly recorded in COMTRADE files.
Current Yes NoYes
Binary inputs Yes NoYes
Frequency No NoYes
Waveform capture setting
Pretrigger time 0.2 s 0.1 s to 0.5 s, step: 0.1 s
Recording time 2.0 s 0.5 s to 10.0 s, step: 0.5 s
1.6.3 Measurement Recorder
Table 1-7 Settings from Measurement Recorder
Parameter Default Setting Setting Options
Template IEC 61000-4-30 IEC 61000-4-30 Ed. 3All measurementUser-defined
Aggregation interval21 10 min 1 min, 10 min
File generation inter-val22
24 h 2 h, 24 h
1.6.4 Trend Recorder
Table 1-8 Settings for Trend Recorder
Parameter Default Setting Setting Options
Tolerance number Percentage: 3 % of the primary nominalvoltage
1 % to 5 %, increments of 1 %
21 For short-term flicker, the aggregation interval is fixed to 10 min; for long-term flicker, the aggregation interval is fixed to 2 h; for 10-s frequency , the aggregation interval is fixed to 10 s.
22 For 30 s aggregation, the file generate interval is fixed to 1 h; for 1-min aggregation, the file generate interval is fixed to 2 h; forother aggregations, the file generate interval is optional.
Operational Indications and Operating Parameters1.6 Recording and Reporting
SICAM, Multifunctional Recorder, Manual 21
E50417-H1040-C606-A5, Edition 03.2018
Parameter Default Setting Setting Options
Maximum recordinginterval
2 h 2 h, 24 h
1.6.5 Mains Signaling Voltage
NOTE
Only parameterizable for the following network types: 1P2W, 3P3W unbal, 3P4W unbal.
Table 1-9 Settings for Mains Signaling Voltage
Parameter Default Settings Setting Range
Mains Signaling Voltage Measurement
MSV active No NoYes
No. of MSV frequencies 1 frequency 1 frequency2 frequencies
Frequency 1 216.60 Hz 100.00 Hz to 3000.00 Hz
Frequency 2 1060.00 Hz 100.00 Hz to 3000.00 Hz
Mains Signaling Voltage Capture Setting
Detection threshold 1.00 % of Un 1.00 % to 15.00 % of Un
Pretrigger time 5 s 0 s to 10 s, step: 1 s
Recording time 60 s 10 s to 120 s, step: 10 s
The Total recording time is the sum of the Pretrigger time and the Recording time, and cannot be changed.
1.6.6 Transient Recorder
Table 1-10 Setting for Transients
Parameter Default Settings Setting Options
Transient active No NoYesIf you set the Transient active parame-ter to no, the transient configurationitems are hidden, the transient record isdisabled, and no data is recorded. Whenthe transient is active again, the lastselected values are used.
Cross trigger active No NoYesIf you set the Cross trigger active toyes, the detected transient can triggerthe waveform recorder.
Operational Indications and Operating Parameters1.6 Recording and Reporting
22 SICAM, Multifunctional Recorder, Manual
E50417-H1040-C606-A5, Edition 03.2018
Parameter Default Settings Setting Options
If you set the Transient active parameter to yes, the following parameters are visible:
Transient threshold 20 % of the primary nominal voltage 10 %, 15 %, 20 %, 25 %
Pretrigger time 5 ms 1 ms to 5 ms, increments of 1 ms
Recording time 10 ms 5 ms to 40 ms, increments of 5 ms
1.6.7 Memory Management
Table 1-11 Default Settings and Setting Ranges
Parameter Default Setting Setting Range
Event recorder 10000 records 5000 records to 20000 records
Waveform recorder 21.74 % (the number of records depends on thewaveform record time)
Min. 10.58 %
Measurement recorder 49.35 %(the recording time depends on theaggregation interval)
Min. 13.16 %
Trend recorder 6.63 % Min. 3.23 %
Transient recorder(wave)
10.87 % Min 5.44 % in the device.
Mains signaling voltagerecorder
10.87 % Min 5.44 % in the device.
Free memory 0.41 %
1.6.8 Report Configuration
Parameter Default Setting Default Options/Description
General Information
Company:Department:Supervisor:Inspector:Location:Comment:
– Any text displayed in the printoutof the power-quality reportMax. 32 characters
Power Quality report
Evaluation mode according to EN 50160 LV EN 50160 LVEN 50160 MVEN 50160 HVUser-defined
Flagging acc. to IEC 61000-4-30 No NoYes
Operational Indications and Operating Parameters1.6 Recording and Reporting
SICAM, Multifunctional Recorder, Manual 23
E50417-H1040-C606-A5, Edition 03.2018
Parameter Default Setting Default Options/Description
Power frequency 99.5 % of the measurement should be within adeviation of -1.0 % to 1.0 %
The default setting is fixed for thetemplate of EN 50160 LV, EN50160 MV, and EN 50160 HV.You can edit the limiting values inthe text box directly under theuser-defined evaluation mode.
100 % of the measurement should be within adeviation of -6.0 % to 4.0 %
Power-supply voltage magnitude 95 % of the measurement should be within adeviation of -10.0 % to 10.0 %
100 % of the measurement should be within adeviation of -15.0 % to 10.0 %
Flicker severity 95 % of the measurement should be less than1.0
Voltage unbalance23 95 % of the measurement should be less than2.0 %
100 % of the measurement should be less than3.0 %
Total harmonic distortion (THDS) 95 % of the measurement should be less than8.0 %
Voltage event interruptions Short interruption until 1-s duration
Short interruption until 3-min duration
Long interruption longer than 3-min duration
Harmonic voltages Odd harmonics H3: 5.0, H5: 6.0, H7: 5.0, H9: 1.5, H11: 3.5,H13: 3.0, H15: 0.5, H17: 2.0, H19: 1.5, H21:0.5, H23: 1.5, H25: 1.5
Even harmon-ics
H2: 2.0, H4: 1.0, H6: 0.5, H8: 0.5, H10: 0.5,H12: 0.5, H14: 0.5, H16: 0.5, H18: 0.5, H20:0.5, H22: 0.5, H24: 0.5
Mains signalling voltage 99.0 % of 216.60 Hz MSV should be less than9.0 % of primary nominal voltage
1.6.9 Start and Stop of Recorders
Table 1-12 Settings for Start and Stop of Recorders
Parameter Default Settings Setting Range
Start record option Start next 10th minute Start next minuteStart next 10th minuteStart immediatelyStart next hourStart next day
Start time – Display of the start time in:Depends on the configuration ofdate/time format.
23 According to EN 50160, up to 3 % unbalance can occur in 3-wire networks in areas with many 1-wire and 2-wire connections.
Operational Indications and Operating Parameters1.6 Recording and Reporting
24 SICAM, Multifunctional Recorder, Manual
E50417-H1040-C606-A5, Edition 03.2018
Parameter Default Settings Setting Range
Recording status – Not settableStatus display of recorder started orrecorder stopped
Operational Indications and Operating Parameters1.7 Administration
SICAM, Multifunctional Recorder, Manual 25
E50417-H1040-C606-A5, Edition 03.2018
1.7 Administration
1.7.1 Time Synchronization
Parameter Default Settings Setting Range
Source time synchronization Internal InternalEthernet NTPFieldbus
Time zone offset to UTC +00:00 -12 to +13 (hours)(in increments of 0.5 h)
Daylight Saving Time switch-over
Yes NoYes
DST offset +01:00 0 to + 2 (hours)(in increments of 0.5 h)
Start of DST MarchLast week
January to DecemberFirst weekSecond weekThird weekFourth weekLast week
Sunday02:00 AM
Sunday to Saturday0:00 to 23:00 (full hour)
End of DST OctoberLast week
January to DecemberFirst weekSecond weekThird weekFourth weekLast week
Sunday03:00 AM
Sunday to Saturday0:00 to 23:00 (full hour)
Additional Parameters if the Source is Ethernet NTP (Modbus TCP and IEC 61850)
Primary NTP server IP Address 192.168.0.254 Any
Secondary NTP server IP Ad-dress
0.0.0.0 AnyNo polling of the NTP server if 0.0.0.0 was en-tered
Error indication after 10 min 2 min to 120 min
Additional Parameters if Source is Fieldbus
Error indication after 10 min 2 min to 120 min
Operational Indications and Operating Parameters1.7 Administration
26 SICAM, Multifunctional Recorder, Manual
E50417-H1040-C606-A5, Edition 03.2018
1.7.2 Ethernet Communication
Table 1-13 Settings for Ethernet
Parameter Default Settings Setting Range Description
Ethernet Configuration
Function24 Switch SwitchTwo interfaces
Configuration of both Ethernet ports:Switch: 2 switched ports in 1 network2 interfaces: 2 Ethernet interfaces in2 networks
Ethernet Channel 1
DHCP24 No NoYes
Determines whether DHCP is used forautomatic receiving of network parame-ters instead of fixed network configurationsettingsDHCP can only be used if IEC 61850 isdisabled.
IP address24 192.168.0.55 Any Network configuration for Ethernet Chan-nel 1(only available for Channel 1 DHCP = no)Subnet mask24 255.255.255.0
Default gateway24 192.168.0.1
Ethernet Channel 2
DHCP24 No NoYes
Determines whether DHCP is used forautomatic receiving of network parame-ters instead of fixed network configurationsettingsDHCP can only be used if IEC 61850 isdisabled.
IP address24 192.168.1.55 Any Network configuration for Ethernet Chan-nel 2(only available for Channel 2 DHCP = no)Subnet mask24 255.255.255.0
Default gateway24 192.168.1.1
Protocol Assignments
IEC 6185024 -none- -none-Ch1Ch2Ch1, Ch2
Activation and assignment of theIEC 61850 communication protocol to theEthernet channels (only available forSICAM Q200 devices with IEC 61850communication option acc. to order num-ber)The options Ch1 and Ch 2 are only availa-ble for the function = Two interfaces.IEC 61850 can only be used with fixed IPaddresses (no DHCP).
24 After the parameter changes have been enabled, the device will be reset.
Operational Indications and Operating Parameters1.7 Administration
SICAM, Multifunctional Recorder, Manual 27
E50417-H1040-C606-A5, Edition 03.2018
Parameter Default Settings Setting Range Description
Modbus TCP -none- -none-Ch1Ch2Ch1, Ch2
Activation and assignment of the Mod-bus TCP communication protocol to theEthernet channelsThe options Ch1 and Ch 2 are only availa-ble for the function = Two interfaces.
HTTPS24 Ch1, Ch2 Ch1Ch2Ch1, Ch2
Activation and assignment of the HTTPScommunication protocol to the EthernetchannelsThe options Ch1 and Ch2 are only availa-ble for the function = Two interfaces.Cannot be completely deactivated in orderto ensure access to the device for parame-terization.
SNMP24 -none- -none-Ch1Ch2Ch1, Ch2
Activation and assignment of the SNMPcommunication protocol to the EthernetchannelsThe options Ch1 and Ch 2 are only availa-ble for the function = Two interfaces.
DNP3 IP -none- -none-Ch1Ch2Ch1, Ch2
Activation and assignment of the DNP3 IPcommunication protocol to the EthernetchannelsThe options Ch1 and Ch 2 are only availa-ble for function = Two interfaces.
1.7.3 Protocol IEC 61850
Table 1-14 Settings for IEC 61850
Parameter Default Settings Setting Range
IED Name SICAM_Q200_01 Any, max. 60 charactersOnly a-z, A-Z, "_", 0-9 are permittedThe first character must be an alpha character.
Voltage - Dead band 5 % 1 % to 5 %, in 1-% steps
Current - Dead band 5 % 1 % to 5 %, in 1-% steps
Voltage unbalance - Dead band 5 % 1 % to 5 %, in 1-% steps
Current unbalance - Dead band 5 % 1 % to 5 %, in 1-% steps
Power - Dead band 5 % 1 % to 5 %, in 1-% steps
Power factor - Dead band 5 % 2 % to 5 %, in 1-% steps
Frequency - Dead band 0.05 % 0.02 %0.05 %
Operational Indications and Operating Parameters1.7 Administration
28 SICAM, Multifunctional Recorder, Manual
E50417-H1040-C606-A5, Edition 03.2018
1.7.4 Protocol Modbus TCP and Modbus TCP/RTU Gateway
Table 1-15 Settings for Modbus TCP
Parameter Default Settings Setting Range
Use a user-port number25 No NoYes
User-port number25
(can only be set when Use auser-port number is parameter-ized with yes)
10000 10 000 to 65 535
Access rights for user port(can only be set when Use auser-port number is parameter-ized with yes)
Full FullRead only
Access rights for port 502 Full FullRead only
Keep Alive time 10 s 0 s = switch off1 s to 65 535 s
Communication supervisiontime
600 (* 100 ms) 0 s = none100 ms to 6 553 400 ms
Voltage harmonics unit % %V
Table 1-16 Settings for Modbus TCP/RTU Gateway
Parameter Default Settings Setting Range
Activated No NoYes
Unit ID of this device 255 1 to 255
Retry limit26 2 0 to 10
Response timeout26 10 (* 10 ms) (1 to 6000) * 10 ms = 10 ms to 60 s
25 After enabling the parameter changes, any currently active Modbus TCP connections will be closed. The Modbus TCP client later mustreopen these connections.
26 These values are necessary if the Modbus slave device has not been configured for the requested Unit ID. If a Modbus slave devicewas configured, its values are used.
Operational Indications and Operating Parameters1.7 Administration
SICAM, Multifunctional Recorder, Manual 29
E50417-H1040-C606-A5, Edition 03.2018
1.7.5 Protocol SNMP
Table 1-17 Settings for SNMPv3
Settings Default Settings Setting Range
User name(User name for SNMPv3 access)
Empty,for example: not set
Up to 24 characters· Numbers 0 to 9· Small and capital latin letters· Basic special characters
Authentication password 8 to 24 characters· Numbers 0 to 9· Small and capital latin letters· Basic special characters
Privacy password
1.7.6 Protocol DNP3 IP
Table 1-18 Settings for DNP3 IP
Parameter Default Settings Setting Range Chapters in DNP3 DeviceProfile27
Protocol DNP3 IP
Device address 1 1 to 65519 1.4.1
Master address 10 1 to 65519 1.4.31.8.2
TCP port number 20000 1 to 65535 1.3.8
Connection supervisiontime
30 s 1 s to 3600 s 1.3.10
Response confirmationtimeout
90 (9 s) 0.01 s to 3600.00 s, step: 100 ms 1.7.11.8.3
Unsolicited transmission
Support unsolicitedreporting
no noyes
1.8.1
The following parameters are only available when Support unsolicited reporting is set to yes.
Number of unsolicitedretries
5 0 to 200 1.8.4
Number of class Xevents
10 1 to 100 1.9.11.9.21.9.3
Hold time after class Xevent
50 (5 s) 0 s to 3600 s, step: 100 ms 1.9.51.9.61.9.7
27 Refer to the Siemens download area for SICAM Q200 .
Operational Indications and Operating Parameters1.7 Administration
30 SICAM, Multifunctional Recorder, Manual
E50417-H1040-C606-A5, Edition 03.2018
Parameter Default Settings Setting Range Chapters in DNP3 DeviceProfile27
Threshold values
AC voltage 5.00 % 0.00 % to 10.00 % -
AC current 5.00 % 0.00 % to 10.00 % -
Power 5.00 % 0.00 % to 10.00 % -
Power factor 5.00 % 0.00 % to 10.00 % -
Frequency 0.05 % 0.00 % to 10.00 % -
Percentage value 5.00 % 0.00 % to 10.00 % -
1.7.7 Communication Serial
Parameter Default Settings Setting Range
Bus protocol Modbus RTU -none-Modbus RTUModbus RTU Master
Bus Protocol Modbus RTU (Slave)
Device address 1 1 to 247
Baud rate 19 200 bit/s 1200 bit/s, 2400 bit/s,4800 bit/s, 9600 bit/s,19 200 bit/s, 38 400 bit/s,57 600 bit/s, 115 200 bit/s
Parity Even None, 1 stop bitEvenOddNone, 2 stop bit
Access rights Full FullRead only
Communication supervisiontime
600 * 100 ms 0 s = none100 ms to 6 553 400 ms
Bus Protocol Modbus RTU Master
Baud rate 19 200 bit/s 1200 bit/s, 2400 bit/s,4800 bit/s, 9600 bit/s,19 200 bit/s, 38 400 bit/s,57 600 bit/s, 115 200 bit/s
Parity Even None, 1 stop bitEvenOddNone, 2 stop bit
Operational Indications and Operating Parameters1.7 Administration
SICAM, Multifunctional Recorder, Manual 31
E50417-H1040-C606-A5, Edition 03.2018
Parameter Default Settings Setting Range
Additional inter-charactertimeout
1 ms 0 ms to 100 msThe Modbus specification requires that theindividual characters of a serial Modbus RTUtelegram have to be transmitted successivelywith a maximum character gap of 1.5 charactertimes (or max. 750 μs for Baud rates >19 200bit/s). Longer silent intervals between the char-acters are interpreted as telegram end.A longer gap between the characters can betolerated with this parameter. Note that thisalso causes longer cycle times.If at least one SICAM P50 device is connected tothe bus, at least the following values have to beset for additional inter-character timeout:1200 bit/s, 2400 bit/s: 04800 bit/s, 9600 bit/s: 219 200 bit/s: 338 400 bit/s: 457 600 bit/s, 115 200 bit/s: 6
Maximum 0x/1x register gap 40 0 to 200Maximum number of not-mapped registerswhich are being requested between mappedregisters in 1 request telegram.
Maximum 3x/4x register gap 10
1.7.8 Serial Communication
1.7.8.1 Basic Settings
Parameter Default Settings Setting Range
Name Modbus slave device 1 Max. 31 characters
Activated No NoYes (= Activation of the option field): The but-tons for parameterization of the mapping dataare also activated for the slave device here.
Device address / Unit ID(Modbus slave device address)
1 1 to 247Address corresponds to the unit ID in the Mod-bus TCP telegram with simultaneous use of theModbus gateway function.
Response timeout 10 (*10 ms) 1 to 6000 * 10 ms(10 ms to 60 s)
Retry limit 2 0 to 10(0 = no request retries)Number of request retries after expiration ofResponse timeout before a communicationerror for the Modbus slave is identified.
Operational Indications and Operating Parameters1.7 Administration
32 SICAM, Multifunctional Recorder, Manual
E50417-H1040-C606-A5, Edition 03.2018
Parameter Default Settings Setting Range
Scan cycle for measured values 50 (*10 ms) 0 to 36 0000 * 10 ms(10 ms to 1 h)0 = Each request cycleMinimum time difference between the meas-ured-value requests.
Scan cycle for indications 0 (*10 ms) 0 to 36 0000 * 10 ms(10 ms to 1 h)0 = Each request cycleMinimum time difference between the meas-ured-value requests.
Scan cycle on error 5 s 1 to 3600 s( 1 s to 1 h)Retry cycle for sending request telegrams if theretry limits are exceeded or in the case of errorresponses.
1.7.8.2 Mapping – Measured Values 1 to 15
Parameter Default Settings Setting Range
Name MV x Slv 1(x = 1 to 15)
Max. 31 charactersMax. 10 characters if the name is also to bedisplayed on the device display.
UnitFrequency measuring values:If a frequency measured value(unit: Hz) has been parameter-ized without a multiplier (mul-tiplier: -), an additional check ismade whether the resultingvalue is in the range of 15 Hz to65 Hz. Measured values outsidethis range are marked as inva-lid.
Factors:Selecting a multiplier for thefollowing units is not recom-mended and will be rejected:-none-°°C°F%
Multiplier: – m (milli)c (centi)d (deci)–h (hecto)k (kilo)M (Mega)G (Giga)
Unit: -none- -none-mkgsA°CVHzWPam2
m3
VAvar°WhVAhvarh%°F
Operational Indications and Operating Parameters1.7 Administration
SICAM, Multifunctional Recorder, Manual 33
E50417-H1040-C606-A5, Edition 03.2018
Parameter Default Settings Setting Range
Register type -none- -none-Input registersHolding registersFor -none-, the assignment is ignored and thecorresponding measuring value cannot be se-lected for other functions.
Data format on bus Float32 (2 registers) Float32 (2 registers)Int16 (1 register)Int16_Ung8000h (1 register)UInt16 (1 register)UInt32 (2 registers)
Register number 1 1 to 65 535
Scaling factor 1.000 Any float value0.00: resulting measured value = 0.00
Table 1-19 Data Format on Bus
Data Format on Bus Description Setting Range Invalid Recognition Used by (Example)
Float32(2 registers)
IEEE Float value -1038 to +1038 NaN = invalidINF = overflow
SENTRON PAC3x00,SICAM AI 7XV5674,SICAM T 7KG966,SICAM P50 7KG775
Int16(1 register)
16 bit signed integer - 32 768 to +32 768 -none- SENTRON 3WL/3VLSICAM P50 7KG775
Int16_Ung8000(1 register)
16 bit signed integer -32768 bis +32768 -32768 (8000h) =invalid
SIPROTEC 4
UInt16 (1 register) 16 bit integer,≥ 0
0 to +65 535 -none- SENTRON 3WL/3VL
UInt32 (2 registers) 32 bit integer,≥ 0
0 to +4 294 967 295 -none- SIPROTEC 4,SENTRON 3WL/3VL
1.7.8.3 Mapping – Indications
Parameter Default Settings Setting Range
Name Indication x Slv 1(x = 1 to 15)
Max. 31 characters
Register type -none- -none-Coil status registersInput status registersInput registersHolding registersFor -none-, the assignment is ignored and thecorresponding indication cannot be selected forother functions.
Operational Indications and Operating Parameters1.7 Administration
34 SICAM, Multifunctional Recorder, Manual
E50417-H1040-C606-A5, Edition 03.2018
Parameter Default Settings Setting Range
Data format on bus 1 Bit 1 Bit1 Bit in UInt32Data format which is used to transmit the indi-cation via Modbus
Register number 1 1 to 65 535
Bit offset(only relevant for register typesInput register or Holding regis-ter)
0 0 to 15 (for data format 1 Bit)0 to 31 (for data format 1 Bit in UInt32)(depending on selection for Data format onbus)
Table 1-20 Data format on Bus
Data Format onBus
Description Setting Range Invalid Recogni-tion
Used by (Example)
1 bit 1 bit(for all registertypes; additionallyselect Bit offset forthe Input registerand the Holdingregister)
0 = of1 = on
None SICAM P50 7KG775,SENTRON 3WL/3VL,SIPROTEC4
1 bit in UInt32 1 bit in 2 succes-sive Input registersor Holding registerswhich have to beread together.
0 = of1 = on
None SENTRON PAC3x00
1.7.9 Device and Language
Parameter Default Settings Setting Range
Device name SICAM xxx Max. 31 ASCII charactersMax. 16 non-ASCII characters
Language English (US) ENGLISH (US)User language acc. to User languagepreselection:DEUTSCH (DE) orCHINESE (CN)
Date/time format YYYY-MM-DD,Time with 24 hours
YYYY-MM-DD, time with 24 hoursYYYY-MM-DD, time 12 h AM/PMDD-MM-YYYY, time with 24 hoursDD-MM-YYYY, time 12 h AM/PMMM/DD/YYYY, time with 24 hoursMM/DD/YYYY, time 12 h AM/PM
Operational Indications and Operating Parameters1.7 Administration
SICAM, Multifunctional Recorder, Manual 35
E50417-H1040-C606-A5, Edition 03.2018
1.7.10 Password Change
Table 1-21 Settings for Passwords
Password Default Settings Setting Range
Logon activationView data password for Web UI LogonandSession time-out (min)
yes99999999and10 [min]
Logon activation:To disable the logon feature, select no.To enable the logon feature, select yes.Password:8 to 24 characters· Numbers 0 to 9· Small and capital latin letters· Basic special charactersSession time-out:0 min (no time-out) to 1440 min (1 day)If the device restarts, you must log onagain.
Configuration change password 00000000 8 to 24 characters· Numbers 0 to 9· Small and capital latin letters· Basic special characters
Force values password 11111111
Firmware change password 22222222
Audit log password 44444444
HMI password Use HMI password:no
· No· Yes
New password:empty
6 numbersOnly numbers 0 to 9
Access management password 33333333 8 to 24 characters· Numbers 0 to 9· Small and capital latin letters· Basic special characters