BA213F/24/ae/03.06

52005008

Operating Instructions

Liquiphant M FTL50, FTL51

Level Limit Switch

Page 2: Operating Instructions Liquiphant M FTL50, FTL51axonautomation.ca/E+H Literature/Manuals/menu/docs/IOMs/Level... · Operating Instructions Liquiphant M FTL50 / FTL51 ... 8 FEL58*

Operating Instructions Liquiphant M FTL50 / FTL51

2 Endress+Hauser

Table of Contents

Safety Instructions

Order Codes

Installation

Setup

Maintenance & Cleaning

Technical Data

Troubleshooting

Spare Parts

Supplemental documentation

Page 3: Operating Instructions Liquiphant M FTL50, FTL51axonautomation.ca/E+H Literature/Manuals/menu/docs/IOMs/Level... · Operating Instructions Liquiphant M FTL50 / FTL51 ... 8 FEL58*

Liquiphant M FTL50 / FTL51 Operating Instructions

Endress+Hauser 3

1 Safety Instructions

Safe and secure operation of the unit can only be guaranteed if the operating instructions and all

safety notes are read, understood and followed.

1.1 Approved usage

The Liquiphant M FTL50 and FTL51 is designed for level limit detection in liquids. If used incor-

rectly, it is possible that application-related dangers may arise. The level limit switch Liquiphant M

FTL50 and 51 may be installed, connected, commissioned, operated and maintained by qualified

and authorized personnel only, under strict observance of these operating instructions, any relevant

standards, legal requirements, and, where appropriate, the certificate.

1.2 Safety pictograms and symbols

Safe and reliable operation of this unit can only be guaranteed if the safety hints and warnings in

these operating instructions are followed. The safety hints in these instructions are highlighted using

the following symbols:

" Caution!

This symbol indicates activities and actions that, if followed incorrectly, could lead to faulty opera-

tion or even damage to the unit.

! Note!

This symbol indicates activities and actions that, if followed incorrectly, could have an indirect influ-

ence on the unit operation or could lead to an unforeseen unit reaction.

0- Hazardous area, certified equipment!

If this character is shown on the unit, then it may be operated in hazardous areas.

. Non-hazardous area!

This symbol identifies the non-hazardous areas in these instructions. Units that operate in the non-

hazardous areas but that are connected to the hazardous areas must also be certified.

1.3 Handling

Hold by housing, flange or

extension tube

kA

143Y

02ae

.eps

Page 4: Operating Instructions Liquiphant M FTL50, FTL51axonautomation.ca/E+H Literature/Manuals/menu/docs/IOMs/Level... · Operating Instructions Liquiphant M FTL50 / FTL51 ... 8 FEL58*

Operating Instructions Liquiphant M FTL50 / FTL51

4 Endress+Hauser

Do not bend.

Do not shorten.

Do not lengthen

2 Order Codes

Product structure

KA

143Y

03ae

.eps

Design Basic weight

FTL50 Compact 1.3 lb 0.6 kg

FTL51 With extension pipe 1.3 lb 0.6 kg

10 Certificates, applications

A Version for non-hazardous area

P FM IS, Class I, II, III Division 1, Group A-G

Q FM XP, Class I, II, III Division 1, Group B-G, for E5 housing Group A-G

R FM NI, Class I Division 2, Group A-D

S CSA IS, Class I, II, III Division 1, Group A-G

T CSA XP, Class I, II, III Division 1, Group A-G

U CSA General Purpose

Y Special version

ATEX and TIIS certified units available

on request

20 Process connection, material Additional weight

Note: For 1450 psi (100 bar) process pressure, please select the appropriate option under "Additional option"

Installation in welding neck accessory

GM2 ¾" NPT Thread ANSI 316L

GM5 ¾" NPT Thread ANSI Alloy C4

GN2 1" NPT Thread ANSI 316L 0.4 lb 0.2 kg

GN5 1" NPT Thread ANSI Alloy C4 0.4 lb 0.2 kg

A82 1" 150 lb RF Flange ANSI B16.5 316/316L 2.2 lb 1.0 kg

AA2 1-¼" 150 lb RF Flange ANSI B16.5 316/316L 2.6 lb 1.2 kg

AB2 1-¼" 300 lb RF Flange ANSI B16.5 316/316L (FTL 51) 4.4 lb 2.0 kg

AC2 1-½" 150 lb RF Flange ANSI B16.5 316/316L 3.3 lb 1.5 kg

AD2 1-½" 300 lb RF Flange ANSI B16.5 316/316L (FTL 51) 6.0 lb 2.7 kg

AE2 2" 150 lb RF Flange ANSI B16.5 316/316L 5.3 lb 2.4 kg

AE5 2" 150 lb RF Flange ANSI B16.5 Alloy C4 >316/316L 5.3 lb 2.4 kg

AF2 2" 300 lb RF Flange ANSI B16.5 316/316L 7.1 lb 3.2 kg

AG2 2" 600 lb RF Flange ANSI B16.5 316/316L (FTL 51) 9.3 lb 4.2 kg

AJ2 2-½" 300 lb RF Flange ANSI B16.5 316/316L (FTL 51) 10.6 lb 4.8 kg

AL2 3" 150 lb RF Flange ANSI B16.5 316/316L 10.8 lb 4.9 kg

AM2 3" 300 lb RF Flange ANSI B16.5 316/316L (FTL 51) 15 lb 6.8 kg

AN2 3" 600 lb RF Flange ANSI B16.5 316/316L (FTL 51)

AP2 4" 150 lb RF Flange ANSI B16.5 316/316L 15.4 lb 7.0 kg

AQ2 4" 300 lb RF Flange ANSI B16.5 316/316L (FTL 51) 25.4 lb 11.5 kg

AR2 4" 600 lb RF Flange ANSI B16.5 316/316L (FTL 51) 38.1 lb 17.3 kg

TC2 DN 25-38 (1 to 1-½") ISO 2852 Tri-Clamp 316L 0.2 lb 0.1 kg

TE2 DN 40-51 (2") ISO 2852 Tri-Clamp 316L 0.7 lb 0.3 kg

YY9 Special version

Other process connections available, contact Endress+Hauser

Page 5: Operating Instructions Liquiphant M FTL50, FTL51axonautomation.ca/E+H Literature/Manuals/menu/docs/IOMs/Level... · Operating Instructions Liquiphant M FTL50 / FTL51 ... 8 FEL58*

Liquiphant M FTL50 / FTL51 Operating Instructions

Endress+Hauser 5

30 Length, spacer, pressure tight bushing

FTL50

AA Compact Ra <3.2 µm/80 grit

IA 66 mm / 2.6" + temperature spacer 1.3 lb 0.6 kg

QA 66 mm / 2.6" + pressure tight bushing 1.5 lb 0.7 kg

FTL51

CB ....... in (6 in to 115 in) Ra 3.2 µm 316L**

CE ....... in (6 in to 115 in) Ra 3.2 µm Alloy C4** 5 lb (2.3 kg)/100 in

DB Length II* Ra 3.2 µm 316L 0.2 lb 0.1 kg

DE Length II* Ra 3.2 µm Alloy C4 0.2 lb 0.1 kg

KB ....... in (6 in to 115 in)

+ temperature spacer

316L** 5 lb (2.3 kg)/100 in

+1.3 lb (+0.6 kg)

KE ....... in (6 in to 115 in)

+ temperature spacer

316L** 5 lb (2.3 kg)/100 in

+1.3 lb (+0.6 kg)

LB Length II*

+ temperature spacer

316L 0.2 lb+1.3 lb

0.1 kg

+0.6 kg

LE Length II*

+ temperature spacer

Alloy C4 0.2 lb+1.3 lb

0.1 kg

+0.6 kg

SB ....... in (6 in to 115 in)

+ pressure tight bushing

316L** 5 lb (2.3 kg)/100 in

+1.5 lb +0.7 kg

SE ....... in (6 in to 115 in)

+ pressure tight bushing

Alloy C4** 5 bl (2.3 kg)/100 in

+1.5 lb +0.7 kg

TB Length II*

+ pressure tight bushing

316L 0.2 lb+1.5 lb

0.1 kg

+0.7 kg

TE Length II*

+ pressure tight bushing

Alloy C4 0.2 lb+1.5 lb

0.1 kg

+0.7 kg

YY Special version

*) Replacing instruments: when vertically mounting a Liquiphant M

FTL51 with length II, the switch point is at the same height as for the

Liquiphant II FTL360, FTL365, FDL30, FDL35

**) order 3001 to 6000 mm (116 to 235 in) via yy

40 Electronic insert

1 FEL51* Contact-free two-wire, 19 to 253 V AC

2 FEL52* PNP three-wire, 10 to 55 V DC

4 FEL54 Floating change-over contacts, DPDT, 19 to 253 V AC, 19 to 55 V DC

5 FEL55 8/16 mA, 11 to 36 V DC

6 FEL56 NAMUR

7 FEL57 Two-wire PFM

8 FEL58* NAMUR with push button (disconnects wire)

9 Special version

*) Also available in compact housing

50 Housing, cable entry

C3 Compact housing 316L IP66/68 5m cable

D3 Compact housing 316L IP65 Pg11 connector

E3 Compact housing 316L NEMA4x NPT1/2" connector

N3 Compact housing 316L IP66/68 M12 connector

E4 Polyester housing Nema 4x, NPT ½"

E5 Aluminum housing Nema 4x,NPT ¾" 1.1 lb/0.5 kg

E6 316L housing Nema 4x, NPT ½" 0.2 lb/0.1 kg

E7 Aluminum housing IP66 NPT ¾",

with separate connection compartment

2.0 lb/0.9 kg

Y9 Special version

60 Additional fittings

A No additional fittings

C 3.1.B material, wetted parts 316L,

Inspection certificate to EN 10204, in accordance with Specification 52005759

N NACE 3.1.B

P 1450 psi (100 bar) process pressure (FTL51)

R 1450 psi (100 bar) process pressure, EN 10204 - 3.1 material, NACE

MR0175 (316L wetted parts) (FTL51)

Inspection certificate

S GL marine approval (FTL 51: max. length 63"/1600 mm)

Y Special version

FTL 5# - Complete product designation

Page 6: Operating Instructions Liquiphant M FTL50, FTL51axonautomation.ca/E+H Literature/Manuals/menu/docs/IOMs/Level... · Operating Instructions Liquiphant M FTL50 / FTL51 ... 8 FEL58*

Operating Instructions Liquiphant M FTL50 / FTL51

6 Endress+Hauser

3 Installation

3.1 Application

Level limit detection in

liquids

3.2 Measuring System

For direct connection

KA

143Y

10ae

.eps

"T"

Order code:FTL 5# - # # # # # # # # ##

FEL 5FEL 5FEL 5

124

Electronic inserts

External load

KA

143Y

11ae

.eps

Page 7: Operating Instructions Liquiphant M FTL50, FTL51axonautomation.ca/E+H Literature/Manuals/menu/docs/IOMs/Level... · Operating Instructions Liquiphant M FTL50 / FTL51 ... 8 FEL58*

Liquiphant M FTL50 / FTL51 Operating Instructions

Endress+Hauser 7

For connection via

switching unit

3.3 Installation

Switchpoint depends on

mounting position

! Note!

The switchpoints of the Liquiphant M are at different positions than those of the previous version

Liquiphant II.

Order code:FTL 5# - # # # # # # # # ##

FEL 5FEL 5FEL 5FEL 5

5678

Electronic insert

KA

143Y

12

ae.e

ps

EX EX

I.S.

*)FTL…,SIF…, SIN…,FXN…

*) Switching unit, PLC,isolating amplifier

KA

143Y

13ae

.eps

KA

14

3Y

15ae

.eps

Page 8: Operating Instructions Liquiphant M FTL50, FTL51axonautomation.ca/E+H Literature/Manuals/menu/docs/IOMs/Level... · Operating Instructions Liquiphant M FTL50 / FTL51 ... 8 FEL58*

Operating Instructions Liquiphant M FTL50 / FTL51

8 Endress+Hauser

Mounting examples as a

function of liquid viscosity

Consider buildup.

Fork may not contact the

buildup

min. 1 inmin. 25 mm( )

min. 1.5 in(min. 40 mm)

min. 2"(min. DN 50)

* *

� = 0 - 10,000 cP

� = 0 - 2000 cP

*Deburr

KA

143Y

16ae

.eps

**

*DistanceK

A143Y

17ae

.eps

Page 9: Operating Instructions Liquiphant M FTL50, FTL51axonautomation.ca/E+H Literature/Manuals/menu/docs/IOMs/Level... · Operating Instructions Liquiphant M FTL50 / FTL51 ... 8 FEL58*

Liquiphant M FTL50 / FTL51 Operating Instructions

Endress+Hauser 9

In cases of dynamic forces

support

Allow clearance

KA

143

Y18ae

.eps

.. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. ..

....

....

....

....

....

....

....

....

....

..

.. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. ..

....

....

....

....

....

....

....

....

....

..

.. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. ..

....

....

....

....

....

....

....

....

....

..

.. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .

....

....

....

....

....

....

....

....

....

..

"T"

"T" = with temperature spacer for insulated tanks

KA

143Y

19ae

.eps

Page 10: Operating Instructions Liquiphant M FTL50, FTL51axonautomation.ca/E+H Literature/Manuals/menu/docs/IOMs/Level... · Operating Instructions Liquiphant M FTL50 / FTL51 ... 8 FEL58*

Operating Instructions Liquiphant M FTL50 / FTL51

10 Endress+Hauser

Orientation of fork tines:

marking above or below

Screw Liquiphant into

process connection.

DON’T use housing to turn.

KA

143Y

20ae

.eps,

KA

143Y

21ae

.eps

A

4141

B

!

41

PTFE

TEFLON

¾ NPT, R ¾, G ¾ A, SW ( )1 NPT, R 1, G 1 A, SW ( )

1¼" 32 mm1 " 41 mm5 8

Above or below

G ¾ A, SW ( )G 1 A, SW ( )

1¼" 32 mm1 " 41 mm5 8

KA

143Y

22ae

.eps

Page 11: Operating Instructions Liquiphant M FTL50, FTL51axonautomation.ca/E+H Literature/Manuals/menu/docs/IOMs/Level... · Operating Instructions Liquiphant M FTL50 / FTL51 ... 8 FEL58*

Liquiphant M FTL50 / FTL51 Operating Instructions

Endress+Hauser 11

Orientation in pipes:

marking in direction of

flow

Cable entry orientation*Torque

Ø(ø )

min. 2"min. 50 mm

Max. 16 ft/s

5 m/s(max. )

KA

143

Y23ae

.eps

12

3 to 4turns

*0.9 Nm

1 21 2

... 270°

... 300°

1. 2. 3.

F16, F13, F17

F15

KA

143Y

24ae

.eps

Page 12: Operating Instructions Liquiphant M FTL50, FTL51axonautomation.ca/E+H Literature/Manuals/menu/docs/IOMs/Level... · Operating Instructions Liquiphant M FTL50 / FTL51 ... 8 FEL58*

Operating Instructions Liquiphant M FTL50 / FTL51

12 Endress+Hauser

4 Setup

Minimum/maximum fail-

safe mode

Liquid density.

Density ρ measured in

g/cm3 (SGU) or in kg/l

0 V

Max.

Max.

Min.Min.

KA

143Y

25ae

.eps

lbs5.9

1US gal

lbs4.2

1US gal

1 US. gal = min. 5.9 lbs(1 l (1 dm³) = min 0.7 kg)(1 imp.gal = min. 7.0 lbs)

0 V

> 0.7 ( 5.9 lbs.)�

FEL , FEL , FEL , FEL , FEL , FEL , FEL51 52 54 55 56 57 58

> 0.5

( 4.2 - 5.9 lbs.)�

1 US. gal = 4.2 - 5.9 lbs

1 l ( 1 dm³) = 0.5 - 0.7 kg(1 imp.gal = 5.0 - 0.7 lbs)( )

Standard

e.g. Propane

KA

143Y

26ae

.eps

Page 13: Operating Instructions Liquiphant M FTL50, FTL51axonautomation.ca/E+H Literature/Manuals/menu/docs/IOMs/Level... · Operating Instructions Liquiphant M FTL50 / FTL51 ... 8 FEL58*

Liquiphant M FTL50 / FTL51 Operating Instructions

Endress+Hauser 13

Self test FEL57 (See page 21 and

switching unit for

sequence)

4.1 Display elements

FEL 57

STD

~ 8 s

~ 41 s

EXT

+–

Switching unit

With corrosion test

Standard

KA

143Y

27ae

.eps

KA

143Y

38ae

.eps

Page 14: Operating Instructions Liquiphant M FTL50, FTL51axonautomation.ca/E+H Literature/Manuals/menu/docs/IOMs/Level... · Operating Instructions Liquiphant M FTL50 / FTL51 ... 8 FEL58*

Operating Instructions Liquiphant M FTL50 / FTL51

14 Endress+Hauser

4.2 Connections, Function

Max. AWG 14

1/8 in3 mm( )

(Max. )2,5 mm²

Max. AWG 12

(Max. )4 mm²

FEL…

Note national regulations!

KA

14

3Y

29ae

.eps

Page 15: Operating Instructions Liquiphant M FTL50, FTL51axonautomation.ca/E+H Literature/Manuals/menu/docs/IOMs/Level... · Operating Instructions Liquiphant M FTL50 / FTL51 ... 8 FEL58*

Liquiphant M FTL50 / FTL51 Operating Instructions

Endress+Hauser 15

Connections FEL51

Two-wire AC connection

Function FEL51

∆VFEL51 max. 3V

KA

143Y

30ae

.eps

KA

143Y

39ae

.eps

Page 16: Operating Instructions Liquiphant M FTL50, FTL51axonautomation.ca/E+H Literature/Manuals/menu/docs/IOMs/Level... · Operating Instructions Liquiphant M FTL50 / FTL51 ... 8 FEL58*

Operating Instructions Liquiphant M FTL50 / FTL51

16 Endress+Hauser

Connections FEL52

DC connection (PNP)

Function FEL52

∆VFEL52 max. 3V

KA

143Y

31ae

.eps

KA

143

Y40ae

.eps

Page 17: Operating Instructions Liquiphant M FTL50, FTL51axonautomation.ca/E+H Literature/Manuals/menu/docs/IOMs/Level... · Operating Instructions Liquiphant M FTL50 / FTL51 ... 8 FEL58*

Liquiphant M FTL50 / FTL51 Operating Instructions

Endress+Hauser 17

Connections FEL54

Universal connection

Relay output

Function FEL54

KA

143Y

32ae

.eps

Max.

Min.

GN RD

3 54

3 54

6 87

6 87

3 54

3

3

3

5

5

5

4

4

4

6 87

6

6

6

8

8

8

7

7

7

FEL 54

FEL 54

1 2 6 7 83 4 5

V 0 V12

KA

143Y

41ae

.eps

Page 18: Operating Instructions Liquiphant M FTL50, FTL51axonautomation.ca/E+H Literature/Manuals/menu/docs/IOMs/Level... · Operating Instructions Liquiphant M FTL50 / FTL51 ... 8 FEL58*

Operating Instructions Liquiphant M FTL50 / FTL51

18 Endress+Hauser

Connections FEL55

Output

8/16 mA

Function FEL55

R

IS

11 - 36 VDC

R =max. 11 V16.8 mA

+–

1 2

EX

EX

FEL 55

e.g. PLC, AI modules

Hazardous Area

Non-HazardousArea

FM

KA

143Y

33ae

.eps

Max.

Min.

GN RD FEL 55

~ 8 mA1

~ 16 mA1

~ 16 mA1

~ 8 mA1

FEL 55

1 2

< 3.6 mA1

+ 2

+ 2

+ 2

+ 2

+ 2

KA

143Y

42.e

ps

Page 19: Operating Instructions Liquiphant M FTL50, FTL51axonautomation.ca/E+H Literature/Manuals/menu/docs/IOMs/Level... · Operating Instructions Liquiphant M FTL50 / FTL51 ... 8 FEL58*

Liquiphant M FTL50 / FTL51 Operating Instructions

Endress+Hauser 19

Connections FEL56

NAMUR output L-H

<1.0 mA / >2.2 mA

Function FEL56

H

L

IH2.2 - 2.8 mA

0.6 - 1.0 mAL

+–

IS

1 2

EX

EX

FEL 56

e.g. FXN 421, FXN 422, SIN 100, SIN 110FTL 325N, FTL 375N

Multiplexer: pulse cycle minimum 2 sduty

HazardousArea

Non-HazardousArea

FM

Isolating amplifier toNAMUR (IEC 60947-5-6)

KA

143Y

34ae

.eps

0.6…1.0 mA

0.6…1.0 mA

2.2…2.8 mA

2.2…2.8 mA

2.2…2.8 mA

Max.

Min.

FEL 56GN RD

FEL 56

1 2

1

1

1

1

1

+ 2

+ 2

+ 2

+ 2

+ 2

KA

143Y

43ae

.eps

Page 20: Operating Instructions Liquiphant M FTL50, FTL51axonautomation.ca/E+H Literature/Manuals/menu/docs/IOMs/Level... · Operating Instructions Liquiphant M FTL50 / FTL51 ... 8 FEL58*

Operating Instructions Liquiphant M FTL50 / FTL51

20 Endress+Hauser

Connections FEL57

PFM output

150 Hz/50 Hz

Function FEL57

IS

+–

1 2

EX

EX

7 833 3437 38

NivotesterFTL 320, FTL 120ZFTL 325 P CH1FTL 325 P CH3

FTL 370/372, FTL 170ZFTL 375 P CH1Input 1

FTL 372, FTL 170ZFTL 375 P CH2Input 2

FTL 375 P CH3Input 3

Commutec SSIF 101, SIF 111

d4 d2

z4 z2

z6 d6

2 1

FEL 57

H H 150 Hz

50 HzL L

f

Note function!

HazardousArea

Non-HazardousArea

See page 21

FM

KA

143Y

35

ae.e

ps

0 Hz

0 Hz

150 HzI

t

I

tI

t

I

t

50 Hz

FEL 57GN YE

V 0 V12

FEL 57

*

*Switch-on behavior

See page 21

KA

143Y

44ae

.eps

Page 21: Operating Instructions Liquiphant M FTL50, FTL51axonautomation.ca/E+H Literature/Manuals/menu/docs/IOMs/Level... · Operating Instructions Liquiphant M FTL50 / FTL51 ... 8 FEL58*

Liquiphant M FTL50 / FTL51 Operating Instructions

Endress+Hauser 21

Switch-on behavior STD

(Self test)

Switch-on behavior EXT

(Self test)

0 Hz 50 Hz 50 Hz

0 Hz 150 Hz 50 Hz 150 Hz

1 s 7 s

1 s 4 s 3 s

FEL 57

FEL 57

FEL 57

STD

Simulation

Simulation

KA

143Y

45ae

.eps

0 Hz 150 Hz 50 Hz 0 Hz 150 Hz

0 Hz 50 Hz 0 Hz 50 Hz

1 s 4 s 30 s 6 s

1 s 34 s 6 s

FEL 57

FEL 57

FEL 57

EXT

Simulation

Simulation

KA

14

3Y

47ae

.eps

Page 22: Operating Instructions Liquiphant M FTL50, FTL51axonautomation.ca/E+H Literature/Manuals/menu/docs/IOMs/Level... · Operating Instructions Liquiphant M FTL50 / FTL51 ... 8 FEL58*

Operating Instructions Liquiphant M FTL50 / FTL51

22 Endress+Hauser

Connections FEL58

NAMUR output H-L

>2.2 mA / <1.0 mA

Function FEL58

H

L

IH2.2 - 3.5 mA

0.6 - 1.0 mAL

+–

IS

1 2

EX

EX

FEL 58

e.g. FXN 421, FXN 422, SIN 100, SIN 110FTL 325 N, FTL 375 N

Multiplexer: pulse cycle minimum 2 sduty

HazardousArea

Non-HazardousArea

FM

Isolating amplifier toNAMUR (IEC 60947-5-6)

KA

143

Y36ae

.eps

2.2…3.5 mA

2.2…3.5 mA

0.6…1.0 mA

0.6…1.0 mA

< 1.0 mA0.3 Hz

1 Hz

1 Hz

1 Hz

1 Hz

Max.

Min.

FEL 58GN YE

FEL 58

1 2

1

1

1

1

1

+ 2

+ 2

+ 2

+ 2

+ 2

KA

143

Y49ae

.eps

Page 23: Operating Instructions Liquiphant M FTL50, FTL51axonautomation.ca/E+H Literature/Manuals/menu/docs/IOMs/Level... · Operating Instructions Liquiphant M FTL50 / FTL51 ... 8 FEL58*

Liquiphant M FTL50 / FTL51 Operating Instructions

Endress+Hauser 23

Function test button FEL58

Fail-safe mode MAX

Function test button FEL58

Fail-safe mode MIN

* T

T

Ex dEx d

MAX

GN

1 Hz

YE

0.6…1.0 mA

1+2

GN YE

0 mA1

+2

GN

1 Hz

YE

2.2…3.5 mA

1+2

GN

1 Hz

YE

0.6…1.0 mA

1+2

1. Normal operation GN YE

2.2…3.5 mA

1+2

1 Hz

2. Press test button

3. Release the test button,after ~2 s normal operation

GN YE

0 mA1

+2

>3 s

T+

KA

143Y

64

ae.e

ps

* T

T

Ex dEx d

MIN

GN

1 Hz

YE

0.6…1.0 mA

1+2

GN YE

0 mA1

+2

GN

1 Hz

YE

2.2…3.5 mA

1+2

GN

1 Hz

YE

0.6…1.0 mA

1+2

1. Normal operation GN YE

2.2…3.5 mA

1+2

1 Hz

2. Press test button

3. Release the test button,after ~2 s normal operation

GN YE

0 mA1

+2

>3 s

T+

KA

143Y

65ae

.eps

Page 24: Operating Instructions Liquiphant M FTL50, FTL51axonautomation.ca/E+H Literature/Manuals/menu/docs/IOMs/Level... · Operating Instructions Liquiphant M FTL50 / FTL51 ... 8 FEL58*

Operating Instructions Liquiphant M FTL50 / FTL51

24 Endress+Hauser

5 Maintenance & Cleaning

Removal of encrustation

KA

14

3Y

53ae

.eps

KA

143Y

54ae

.eps

Do not use as a step!

Page 25: Operating Instructions Liquiphant M FTL50, FTL51axonautomation.ca/E+H Literature/Manuals/menu/docs/IOMs/Level... · Operating Instructions Liquiphant M FTL50 / FTL51 ... 8 FEL58*

Liquiphant M FTL50 / FTL51 Operating Instructions

Endress+Hauser 25

6 Technical Data

Ambient temperature Ta

Process temperature Tp

Process pressure pe

Process temperature Tp

6.1 Accessories

Weld-in sockets max. 360 psi/300°F

(max. 25 bar/150°C)

max. 580 psi/210°F

(max. 40 bar/100°C)

T

( )158 °F70 °C

32 °F

( )122 °F50 °C

T

T

T–58(–5 ) ( ) ( ) ( )

°F 32 °F 194 °F 300 °F0 °C 0 °C 90 °C 150 °C

–58 °F(–50 °C)

Available whenused with temperaturespacer.See order codes.

aa

p

P

°F

°F

KA

143Y

55ae

.eps

pe

psi(bar)

FTL51-FTL51-

# ### ## # ### ### ## # ##

P

R

Tp

( )°F°C

92864( )

–58–50( )

300150( )

320( )

–14.5–1( )

1450( )100

See order codes

KA

143Y

70ae

.eps

1.02 (26)

0.97(24.6)

1.02(26)

0.20 (5)

1.16 (29.6)

G ¾

E+H 52001052

G 1

E+H 52001051

G 1

E+H 52001221

Ø 2.5( 65Ø )

Ø 2.36( 60Ø )G1

ISO 228Ø1.61(ø41)

Ø 2.16(Ø55 )G ¾

ISO 228Ø1.26(ø32)

0.83(21)

Dimensions are in inches (mm)

-0.02

-0.4

-0.4

-0.3

-0.02

-0.01

KA

143Y

56ae

.eps

Page 26: Operating Instructions Liquiphant M FTL50, FTL51axonautomation.ca/E+H Literature/Manuals/menu/docs/IOMs/Level... · Operating Instructions Liquiphant M FTL50 / FTL51 ... 8 FEL58*

Operating Instructions Liquiphant M FTL50 / FTL51

26 Endress+Hauser

Lap joint flanges with BSP 1

(G1) thread; Covers with

window

Sliding sleeves for

unpressurized operation

See KA151F

(G 1, NPT 1)

See KA152F

(G 1½, NPT 1½)

Corrosion-resistant steel1.4571(AISI 316 Ti)

PA 12

AISI 316 L1.4435( )

PC

( )AISI 316 L1.4435

Glass

Lap joint flange with G1 thread2”, 150 psi, RF, ANSI B 16.5E+H 918144-0000

Transparent coverFor plastic housing

E+H 943461-0001

Stainless steel cover with glass windowFor stainless steel housing

E+H 943301-1000

With polycarbonate window

E+H 52001403

KA

143Y

58ae

.eps

0.87(22)

0.75(19)

0.75(19)

0.71(18)

M6 (3x)

M6 (3x)

G 1E+H 52003978

G 1½E+H 52003980

p = 0 psi(p = 0 bar)

max. 300 °F(max. 150 °C)

e

e

1 - 11½ NPTE+H 52003979

1.4435(AISI 316 L)

1.4435(AISI 316 L)

1½ - 11½ NPTE+H 52003981

Ø0.86

(21.8)

Ø0.86

(21.8)

1.61

(41)

2.16

(55)

KA

143Y

59ae

.eps

Page 27: Operating Instructions Liquiphant M FTL50, FTL51axonautomation.ca/E+H Literature/Manuals/menu/docs/IOMs/Level... · Operating Instructions Liquiphant M FTL50 / FTL51 ... 8 FEL58*

Liquiphant M FTL50 / FTL51 Operating Instructions

Endress+Hauser 27

High pressure

sliding sleeves

See KA153F

(G 1, NPT 1)

See KA154F

(G 1½, NPT 1½)

High pressure

sliding sleeves:

Process pressure pe

Process temperature Tp

G 11.4435 (AISI 316 L)E+H 52003663

G 1½1.4435 (AISI 316L)E+H 52003665

1 - 11½ NPT1.4435 (AISI 316 L)E+H 52003667

1½ - 11½ NPT1.4435 (AISI 316L)E+H 52003669

0.86(22)

0.98(25)

0.98(25)

0.71(18)

Ø2.36 (60)

Ø2.36 (60)

0.08(2)

0.08(2)

Alloy C4E+H 52003664

Alloy C4E+H 52003668

Alloy C4E+H 52003666

Alloy C4E+H 52003670

~2.83(72)

~2.75(70)

KA

143Y

60ae

.eps

Liquiphant S

Liquiphant M

1160 (80)

psi(bar)

°F (°C)-76

(-60) -58(-50)

500(260)

300(150)

540(280)

-14.5 (-1)

32(0)

1450 (100)

928 (64)

KA

143

Y69ae

.eps

Page 28: Operating Instructions Liquiphant M FTL50, FTL51axonautomation.ca/E+H Literature/Manuals/menu/docs/IOMs/Level... · Operating Instructions Liquiphant M FTL50 / FTL51 ... 8 FEL58*

Operating Instructions Liquiphant M FTL50 / FTL51

28 Endress+Hauser

7 Troubleshooting

Troubleshooting

Supplement

If the switching behavior of the fork is abnormal, the fork frequency can be measured at PIN 4 of

the diagnosis socket. With electronic inserts FEL 51/52/54/55/56/57/58, this is a sinusoidal

vibration whose amplitude makes it possible to determine the condition of the fork.

Fault Reason Remedy

Does not switch No power Check power

Faulty signal line Check signal line

Faulty electronic insert

– FEL51 connected directly to L1 and N

Exchange

– always connect FEL51 via external load

Density of liquid too low Set density to >0.5 at electronic insert

Fork encrusted Clean fork

Fork corroded

(Indication on FEL: red/yellow flashes,

FEL58: green flashes (0.3 Hz)

Exchange fork and process connection

FEL51: Internal resistance of connected

relay too large

Connect suitable relay

FEL51: Holding current of connected

relay too low

Connected resistor in parallel with relay

FEL54: Contacts welded together (after

short-circuit)

Exchange FEL54; put fuse in contact circuit

Switches incorrectly Min-/Max- fail-safe mode set wrong Set correct mode at electronic insert

Sporadic faulty

switching

Thick heavy foam, very turbulent

conditions, foaming liquid

Mount Liquiphant in bypass

Extreme RFI Use shielded cable

Extreme vibration Decouple, damp, turn fork 90°

Water in housing Screw cover and cable gland tight

FEL52: Output overloaded Reduce load, (cable) capacitance

Switches incorrectly

after power failure

FEL57: behavior during switch-on test

(functional test)

Observe switching behavior of FEL57; after

power failure block plant control for up to 45 s

Page 29: Operating Instructions Liquiphant M FTL50, FTL51axonautomation.ca/E+H Literature/Manuals/menu/docs/IOMs/Level... · Operating Instructions Liquiphant M FTL50 / FTL51 ... 8 FEL58*

Liquiphant M FTL50 / FTL51 Operating Instructions

Endress+Hauser 29

8 Spare Parts

Electronic inserts Installation specification:

During installation, please keep in mind that

electrical resources (electronic inserts) which

are powered by non-intrinsically-safe circuits

may no longer be interconnected with intri-

niscally-safe circuits.

Housing covers, seals

9 Repair

Repair is done at

Endress+Hauser

KA

143Y

61ae

.eps

FEL51 52002304

FEL52 52002305

FEL54 52002306

FEL55 52002307

FEL56 52002308

FEL57 52002309

FEL58 52006454

*

*

*

* KA

143Y

62ae

.eps

Lubricate with silicone grease or graphite.

Alu

EPDM

Alu w/EPDM O-ring E+H 52002699

Alu (EX) w/EPDM O-ring E+H 52002698

PBT-FR (cover only) E+H 943461-0000

EPDM O-ring E+H 017717-0003

AISI 304/316L E+H 943301-0000

(cover only)

(1.4301/1.4435)

MVQ Silicone Seal E+H 943304-0000

1.

2.

3.

Endress+Hauser

Clean

Transportprotection

KA

143Y

63ae

.eps

Page 30: Operating Instructions Liquiphant M FTL50, FTL51axonautomation.ca/E+H Literature/Manuals/menu/docs/IOMs/Level... · Operating Instructions Liquiphant M FTL50 / FTL51 ... 8 FEL58*

Operating Instructions Liquiphant M FTL50 / FTL51

30 Endress+Hauser

10 Supplemental Documentation

Technical Information

TI328F Liquiphant FTL50, FTL50H, FTL51, FTL51H

Notes on Safety

XA031F 4 0 II 1/2 G EEx d IIC/IIB

XA063F 4 0 II 1/2 G, II 1/2 D EEx ia/ib IIC/IIB

XA064F 4 0 II 1 G EEx ia IIC/IIB

XA108F 4 0 II 1/2 G EEx de IIC/IIB

XA154F 4 0 II 1/2 G, II 1/2 D EEx ia/ib IIC/IIB

XA159F 4 0 II 1 G EEx ia IIC/IIB

XA182F 4 0 II 3 G, II 3 D EEx nA/nC II

Page 31: Operating Instructions Liquiphant M FTL50, FTL51axonautomation.ca/E+H Literature/Manuals/menu/docs/IOMs/Level... · Operating Instructions Liquiphant M FTL50 / FTL51 ... 8 FEL58*

Liquiphant M FTL50 / FTL51 Operating Instructions

Endress+Hauser 31

Page 32: Operating Instructions Liquiphant M FTL50, FTL51axonautomation.ca/E+H Literature/Manuals/menu/docs/IOMs/Level... · Operating Instructions Liquiphant M FTL50 / FTL51 ... 8 FEL58*

United States Canada Mexico

Endress+Hauser, Inc.2350 Endress PlaceGreenwood, IN 46143Tel: 317-535-7138Sales: 888-ENDRESSService: 800-642-8737FAX: [email protected]

Endress+Hauser Canada1075 Sutton DriveBurlington, ON L7L 5Z8Tel: 905-681-9292800-668-3199FAX: 905-681-9444www.ca.endress.com

Endress+Hauser (Mexico) S.A. de C.V.Calle de Gustavo Baz No. 43Fraccionamiento Bosques de EchegarayCP 53310 Naucalpan de JuárezMexicoTel: +52 55 5371 1110FAX: +52 55 5371 1128

BA213F/24/ae/03.06

52005008

FM+SGML 6.0

Endress+Hauser Mexico, S.A. de C.V.Av. Gustavo Baz No. 43Fracc. Bosques de EchegarayNaucalpan de Juaraz, C.P. 53310Estada de MexicoMexicoPhone: (52)-55-5371-1110FAX: (52)-55-5371-1128E-mail: [email protected]