On-Site Leaching Chamber Specifications & Features
Design & Installation Manual – Maine
2
•This manual provides general design and installation information for Arc/BioDiffuserLeachingChambers.
•AllArc/BioDiffuserchamberconfigurationsandinstallationsmustcomply withstateandlocalrules.
•Thismanual containsabriefdescription foreachchambermodeland generaldesignandinstallationprocedures.Formoredetailedinformation pleasecontactcustomerserviceat1-800-733-0535.
•ForCADdrawingsrefertoourwebsite:www.arc-chamber.com.
Contents
Introduction 2
ProductSpecificationsandTypicalConfigurations
Arc36System 4
Arc36HighCapacitySystem 6
11"StandardSystem 8
16"HighCapacitySystem 10
Arc18System 12
Bio2System 14
InstallationInstructions 16
TypicalInstallations:Trench,BedandSerial 18-20
AdditionalSystemConfigurations
MoundConfigurationSystem 21
PumpSystems 22-23
PressureDosingSystem 24
SidePortCouplerSystemOptions 25-26
SystemSizingCharts 27-30
3
Arc 18 System•16”WideChamber•NewLightweightDesignwithArticulating JointsandPivotLockoutFeature•H–10loadratedwithproperinstallation.•SeePages12-13
Arc 36 System•34"WideChamber•NewLightweightDesignwithArticulatingJoints• H–10loadratedwithproperinstallation.•SeePages4-5
INCLUDED SYSTEMS
Arc 36 HC System•34"WideChamber•NewLightweightDesignwithArticulatingJoints• H–10loadratedwithproperinstallation.•SeePages6-7
11” Standard System•34”WideChamber•H–10loadratedwithproperinstallation.•SeePages8-9
16” High Capacity System•34”WideChamber•H–10loadratedwithproperinstallation.•SeePages10-11
Bio 2 System•15”WideChamber•H-10loadratedwithproperinstallation.•SeePages14-15
4
Before beginning installation, please note the following engineered features of the Arc 36 model chambers and end caps.
Arc 36 System
60"EffectiveLength
PostEnd 7"InvertHeight
14"InstalledLength
34"
13"6.5" 9"
Arc 36 ChamberLength 63"
RepeatLength 60"OverallWidth 34"
SidewallHeight 7.13"InvertHeight 7.25"
OverallHeight 13"Capacity 8.04cuft(60.14gal)
Calculationsanddimensionsarenominal
Arc 36 Chamber—Top, Side, and End Views (nottoscale)
Arc 36 End Cap—Side, and End Views (nottoscale)
Side Port Coupler (SPC)
ArC 36 SYSTEM
5
Arc 36 Features
•The post and dome creates a positive lock securing the chambersfor finalengagement.Lockanddropfeaturefor fasterinstallation.•TheArc36chamberfeetaredesignedwithanextralarge surfaceareatoprovidesupport,particularlyinsandysoils.•Sidewall louversaredesigned toalloweffluent toexit the chambersidewallsinhighflowsituations,whilepreventing soilsfrommigratingintothechambervoid.•Observation/venting knockout ports provide for inspection ofsystemperformanceaswellasaconvenientlocationfor drainfieldventilationpipes.•Eachchamberendhassmallknockoutsontheroofpositionedinthe“Post”endjoint.Whenremoved,theseknockoutsallowfortheuseofziptiestosupportpipingindosingsystems.
Arc 36 Universal End Cap
•Upperand lowerknockoutsaccommodatebothSchedule 40 and SDR 35 piping. Knockouts can be removed with a knife or hole saw. Dimples are also offered for thepositioningofholesawpilotdrills.•Endcapsaredesignedtoattachtothechamber’sdomeor postendinthesamefashionforeachendwiththeArc36 logofacingoutward.
Arc 36 Swivel Feature
•The engagement mechanism of the Arc 36 chamber is designedtoallowforapivotbetweenjoinedchambersofupto 10°ineitherdirection.
Arc 36 System Configurations
•TrenchInstallation:Page18•BedInstallation:Page19•AdditionalConfigurations:Pages20-25 (Serial,Pump,PressureDosing,andSidePortCouplerSystemOptions)
•ObservationPort
ArC 36 SYSTEM
•LockandDrop •LouversandFeet
Arc 36 Side Port Coupler
•SidePortCouplercomponentsnapsinplacetoallowsideentry atanyjointthroughoutthetrenchline.Thisaccessoryprovides avarietyofdesignandinstallationoptions.Refertopages22 and23fordesignconfigurations.
6
Before beginning installation, please note the following engineered features of the Arc 36 HC model chambers and end caps.
Arc 36 HC System
60"EffectiveLength 34"
Arc 36 HC ChamberLength 63"
RepeatLength 60"OverallWidth 34"
SidewallHeight 10.75"InvertHeight 10.75"
OverallHeight 16"Capacity 10.7cuft(80gal)
Calculationsanddimensionsarenominal
Arc 36 HC Chamber—Top, Side, and End Views (nottoscale)
Arc 36 HC End Cap—Side, and End Views (nottoscale)
ArC 36 HC SYSTEM
PostEnd 10.5"Invert Height
14"InstalledLength
16"
9.5"
12.5"
Side Port Coupler (SPC)
7
Arc 36 HC Features
•The post and dome creates a positive lock securing the chambersfor finalengagement.Lockanddropfeaturefor fasterinstallation.•TheArc36HCchamberfeetaredesignedwithanextralarge surfaceareatoprovidesupport,particularlyinsandysoils.•Sidewall louversaredesigned toalloweffluent toexit the chambersidewallsinhighflowsituations,whilepreventing soilsfrommigratingintothechambervoid.•Observation/venting knockout ports provide for inspection ofsystemperformanceaswellasaconvenientlocationfor drainfieldventilationpipes.•Eachchamberendhassmallknockoutsontheroofpositionedinthe“Post”endjoint.Whenremoved,theseknockoutsallowfortheuseofziptiestosupportpipingindosingsystems.
Arc 36 HC Universal End Cap
•Upperand lowerknockoutsaccommodatebothSchedule 40 and SDR 35 piping. Knockouts can be removed with a knife or hole saw. Dimples are also offered for thepositioningofholesawpilotdrills.•Endcapsaredesignedtoattachtothechamber’sdomeor postendinthesamefashionforeachendwiththeArc36 logofacingoutward.
•ObservationPort
ArC 36 HC SYSTEM
•LockandDrop •LouversandFeet
Arc 36 HC Swivel Feature
•The engagement mechanism of the Arc 36 chamber is designedtoallowforapivotbetweenjoinedchambersofupto 10°ineitherdirection.
Arc 36 HC System Configurations
•TrenchInstallation:Page18•BedInstallation:Page19•AdditionalConfigurations:Pages20-25 (Serial,Pump,PressureDosing,andSidePortCouplerSystemOptions)
Arc 36 HC Side Port Coupler
•SidePortCouplercomponentsnapsinplacetoallowsideentry atanyjointthroughoutthetrenchline.Thisaccessoryprovides avarietyofdesignandinstallationoptions.Refertopages22 and23fordesignconfigurations.
8
Before beginning installation, please note the following engineered features of the 11” Standard model chambers and end caps.
11” Standard System
• Each chamber end is either marked “Dome” or “Post” on the roundobservation/ventknockoutports.Theseindicatedirectionof assembly,domeoverpost.
11” Std ChamberLength 76”
RepeatLength 75”OverallWidth 34”
SidewallHeight 6.35”InvertHeight 6.5”
OverallHeight 11”Capacity 9.21cuft(68.42gal)
Calculationsanddimensionsarenominal
75”EffectiveLength 34”
11” STANDArD SYSTEM
11” Standard Chamber — Top, Side, and End Views(nottoscale)
11” Standard End Cap — Side, and End Views(nottoscale)
9
11” Standard Features
•The post and dome creates a positive lock securing the chambersforfinalengagement.•The11”Standardchamberfeetaredesignedwithanextra largesurfaceareatoprovidesupport,particularlyinsandy soils.•Sidewall louversaredesigned toalloweffluent toexit the chambersidewallsinhighflowsituations,whilepreventing soilsfrommigratingintothechambervoid.•Observation/ventingknockoutportsprovideforinspectionof systemperformanceaswell as a convenient location for drainfieldventilationpipes.•Each chamber end has small knockouts on the roof positioned in the “Post” end joint.When removed, these knockoutsallfortheuseofziptiestosupportpipingindosing systems.
11” Standard Universal End Cap
•Upperand lowerknockoutsaccommodatebothSchedule 40 and SDR 35 piping. Dimples are also offered for thepositioningofholesawpilotdrills.•Endcapsaredesignedtoattach thechamber’sdomeor postend.
11” Standard System Configurations
•TrenchInstallation:Page18•BedInstallation:Page19•AdditionalConfigurations:Pages20-23 (Serial,PumpandPressureDosingOptions)
•Interlockingjoint •LouversandFeet
•ObservationPort •ZipTieKnockouts
11” STANDArD SYSTEM
10
Before beginning installation, please note the following engineered features of the 16” High Capacity model chambers and end caps.
16” High Capacity System
• Each chamber end is either marked “Dome” or “Post” on the roundobservation/ventknockoutports.Theseindicatedirectionof assembly,domeoverpost.
16” High Capacity Chamber
Length 76”RepeatLength 75”OverallWidth 34”
SidewallHeight 11.17”InvertHeight 11.6”
OverallHeight 16”Capacity 13.6cuft(101.0gal)
Calculationsanddimensionsarenominal
75”EffectiveLength 34”
16” HIGH CAPACITY
16” High Capacity Chamber — Top, Side, and End Views(nottoscale)
16” High Capacity End Cap — End View(nottoscale)
11
16” High Capacity Features
•The post and dome creates a positive lock securing the chambersforfinalengagement.•The16”HighCapacitychamberfeetaredesignedwithanextra largesurfaceareatoprovidesupport,particularlyinsandy soils.•Sidewall louversaredesigned toalloweffluent toexit the chambersidewallsinhighflowsituations,whilepreventing soilsfrommigratingintothechambervoid.•Observation/ventingknockoutportsprovideforinspectionof systemperformanceaswell as a convenient location for drainfieldventilationpipes.•Each chamber end has small knockouts on the roof positioned in the “Post” end joint.When removed, these knockoutsallfortheuseofziptiestosupportpipingindosing systems.
16” High Capacity Universal End Cap
•Upperand lowerknockoutsaccommodatebothSchedule 40 and SDR 35 piping. Dimples are also offered for thepositioningofholesawpilotdrills.•Endcapsaredesignedtoattach thechamber’sdomeor postend.
16” High Capacity System Configurations
•TrenchInstallation:Page18•BedInstallation:Page19•AdditionalConfigurations:Pages20-23 (Serial,PumpandPressureDosingOptions)
•Interlockingjoint •LouversandFeet
•ObservationPort •ZipTieKnockouts
16” HIGH CAPACITY
12
Arc 18 System •Each chamber end is either marked “Dome” or “Post” on the roundobservation/ventknockoutports.Theseindicatedirectionof assembly,domeoverpost.
Before beginning installation, please note the following engineered features of the Arc 18 model chambers and end caps.
Arc 18 ChamberLength 67”
RepeatLength 60”OverallWidth 16”
SidewallHeight 7.7”InvertHeight 6.24”
OverallHeight 12”Capacity 3.42cuft(25.6gal)
Calculationsanddimensionsarenominal
60”EffectiveLength 16”
ArC 18 SYSTEM
Arc 18 End Cap — Side, and End Views(nottoscale)
Arc 18 Chamber — Top, Side, and End Views(nottoscale)
13
Arc 18 Features
• Baseflangesonthechambersendsoverlockduringfinal engagementtoformaverystrongjoint.
• TheArc18chamberfeetaredesignedwithanextralarge surfaceareatoprovidesupportparticularlyinsandysoils.
• Sidewall louversaredesignedtoalloweffluenttoexitthe chambersidewallsinhighflowsituations,whilepreventing soilsfrommigratingintothechambervoid.
• Observation/ventingknockoutportsprovideforinspectionof systemperformanceaswellasaconvenient location for drainfieldventilationpipes.
• Each chamber end has small knockouts on the roof positioned in the “Post” end joint.When removed, these knockoutsarefortheuseofziptiestosupportpipingindosing systems.
Arc 18 End Cap
• UpperandlowerknockoutsaccommodatebothSchedule 40 and SDR 35 piping. Dimples are also offered for thepositioningofholesawpilotdrills.
•Endcapsaredesignedtoattachthechamber’sdomeor postend.
Arc 18 System Configurations
•TrenchInstallation:Page18•BedInstallation:Page19•AdditionalConfigurations:Pages20-23 (Serial,PumpandPressureDosingOptions)
•OverlockingEnds •LouversandFeet
•ObservationPort •ZipTieKnockouts
ArC 18 SYSTEM
Arc 18 Swivel Feature
•Eachchamber’spostendhasswivellockouttabsateitherbase flange.When removed, the incoming chamberwillturn up to ten degrees in the direction of the removedlockouttab.Withoutremovaloftheswivellockouttab,thechamberswillaligninastraightpattern.
•Swivellockouttabsmayberemovedcarefullywithautilityknife.
14
Before beginning installation, please note the following engineered features of the Bio 2 model chambers and end caps.
Bio 2 System
• Each chamber end has either a rectangular dome or “H” postTheseindicatedirectionofassembly,domeoverpost.
Bio 2 ChamberLength 87”
RepeatLength 86”OverallWidth 15”
SidewallHeight 9.03”InvertHeight 6.95”
OverallHeight 12”Capacity 5.0cuft(37.1gal)Weight 19lbs
Calculationsanddimensionsarenominal
86”EffectiveLength 15”
Bio 2 System
Bio 2 Chamber - Top, Side, and End Views (nottoscale)
Bio 2 End Cap - Side, and End Views (nottoscale)
15
Bio 2 Features
•Sideflangesonthechambersendsover lockduringfinal engagementtoformaverystrongjoint.•TheBio2chamberfeetaredesignedwithanextralarge surfaceareatoprovidesupport,particularlyinsandysoils.•Sidewall louversaredesigned toalloweffluent toexit the chambersidewallsinhighflowsituations,whilepreventing soilsfrommigratingintothechambervoid.•Observation/ventingknockoutportsprovideforinspectionof systemperformanceaswell as a convenient location for drainfieldventilationpipes.•Eachchamberpostendhassmallholesoneithersideof thepost.Whenremoved,theseallowfortheuseofzipties tosupportpipinginlowpressuredosingsystems.•BioDiffuserchamberscanbeinstalledtomeetanH-10live load(16,000lbs/axle).Backfillingwithaminimumof12”of properly compacted cover is required for these applications.
Bio 2 Universal End Cap
•UpperandlowerknockoutsaccommodatebothSchedule40 (4.5” OD) and SDR 35 (4.25” OD) pipes. Dimples arealsoofferedforthepositioningofholesawpilotdrills.•Endcapsaredesigned toattach thechamber’sdomeor postend.
Bio 2 System Configurations
•TrenchInstallation:Page18•BedInstallation:Page19•AdditionalConfigurations:Pages20-23 (Serial,PumpandPressureDosingOptions)
•OverLockingEnds •LouversandFeet
•ObservationPort •ZipTieOpenings
Bio 2 System
16
Installation of End Caps & Pipe Connections•Prior to installing end caps, remove the appropriate knockout for pipe connections. Snap an end cap on each end of the drain lines with the product or company logo facing out (knockouts can be removed withaknifeora4"holesaw).
•Upperendcap4"knockouts—alwaysusedasinletfor eachline.Afour-inchholesawmaybeused.•Lowerendcap4"knockouts—usedforreturnlinesor continuouscircuitpipingperstateor localcode.These lower knockouts may also be used to create turns in the drain lines greater than the ten degrees provided bythechamberswivelfeature.
Splash Plates
•Splashplatesmustbeinstalledoneachinletendcap.•SplashplatesareprovidedwithArcsystemendcaps.•Knockoutmaterialmaybeused ifscrewedto thebase flangeoftheendcapwithastainlesssteelscrew.
Preparation•Excavatetoproperwidthanddepthasdescribedinthe systemdesignorpermitandasrequiredbystateand localcodes.•Smoothirregularitiesintheexcavationandclearanylarge rocksordebrisfromthebottomsurfacearea.Slopeof the bottom area shall be determined by the system design, as well as state and local codes. For bed installations,aminimumof6inchesisrequiredbetween chamberrows.
Installation
•Installation of the any ADS/Hancor Arc/BioDiffuser leachingsystembeginswithlayingthefirstchamberonto thepreparedbottomsurfacearea,withthe“dome”end ofthechamberattheheaderendoftheexcavation.Each additionalincomingchamberistheninstalledbyplacing itsdomeoverthepostofthechamberalreadyinplace. Asyoulowerthechambertotheground,pullittowards youtoengagethelockingmechanism.
•As the incoming chamber is lowered down onto the excavationbottom,thetwochambersfullyengageina straight-linepatterncreatingaverystrongjoint.
(Note: if the followingchamber issimply laidonto the precedingchamberthejointwillnotbefullyengaged.)
Turns
•TheArc36,Arc36HCandArc18chambersaredesigned withanarticulatingjointthatallowsforaturnofupto20°, withmaximumof10°ineitherdirection.
(Note:TheArc18isdesignedwithlockouttabs)
•IfaturnapplicationisdesiredwiththeArc18chamber, the lockout tabshouldberemovedbefore installing the incomingchamber.Thelockouttabislocatedatthebase flangeofthepreviously–installedchamber(onits“Post”end).•Remove the lockout tab and clean any remaining tab materialawayfromthechamber.
ArC/BIODIFFUSEr LEACHING SYSTEMS: INSTALLATION PrOCEDUrES
17
•AllArc/BioDiffuserchambersareH–10 load rated. Wherevehicularloadingisanticipated,H–10loading (16,000 lbs/axle) is achieved by backfilling with aminimumof12"ofproperlycompactedcover.
•Do not drive heavy equipment over a system comprisedofnon-compactedcovermaterialwithout first bridging the excavation. Use lightweight or trackedequipmenttopushthesoilontothesystemto theproperheightsetforthbylocalandstatecodes.
Final Grade •Makecertainthatstormwaterisdivertedawayfrom the drain field. System final grade should be crested or sloped, never left flat or concave. Channelwaterawayfromthedrainfield.•Final grading subcontractors and landscapers shouldbealertedandinstructedtopropercovering procedures, cover materials, and finish contours andelevations.•Finalgradematerialshouldbeslightlytomoderately limitedsoiltohelpmaintainanaerobicstateinthe drainfield.•Stabilize the drain field area with grass-type vegetationpriortoheavyrainsifpossible.
Mound Installation Procedure
• Review Plans and stake out the entire leachingbed area. Confirm elevations of the septic tank,distributionboxandchambers.
•Clearandscarifyentireleachfieldareaincludingfillextensions.
•Confirm backfill material meets the Maine 804.2Backfill Standard. Place backfill material and usetheteethonthebuckettomixwiththeoriginalsoil.Placebackfillmaterialin12inlifts(300mm),compactusing a track vehicle. Continue placing backfillmaterialtothebottomelevationofthechambers.
•Refer tostandard installationproceduresonpage16andcontinuefromInstallationheading.
Ventilation Drainfieldventilationisrecommended,butnotrequired,toallowoxygentoaccessthedrainfieldespeciallywhencoversoilqualityisquestionable.•Knockoutsareprovidedonthe11"Standard,Arc36, andBio3chambers.Thedome/postfeatureoftheArc 18chamberalsoactsasaknock-outforobservation/ ventports.HereaPVCpipemaybeintroducedintothe chamberandventedtoatmosphere.•Makecertaintheventisassembledinsuchafashion astopreventrainwaterfromentering,effluentwaterfrom exiting,andpossibleodorsfromcausingissues.•Severaloutletproductsareavailableforthispurpose.
Backfilling
•After chamber assembly is completed, fill to top ofchamberswithpreferablycompactible,slightlylimitedtomoderatelylimitedsoil.
•Backfill material to meet Maine Backfill standard:804.2Backfillstandards:Thebackfillmaterialshallbeacoarsesandtoagravellycoarsesandwhichmeetsthefollowingrequirements:
804.2.1 Coarse fragments: The upper limit ofcoarsefragmentsshallbe3inchesindiameterandapproximately5%byvolume;
804.2.2Texturalanalysis:Thesoiltextureforbackfill,unlessotherwiseauthorizedbythiscode,iscoarsesandtogravellycoarsesandwithapproximately4to8%ofthesand,siltandclayfractionpassinga#200sieve.Theupperlimitofclaysizedparticlesinthesand,silt,andclay fractionshallbeapproximately2%.Thebackfillshallcontainapproximately15%to30%(byweight)coarsefragments(gravel2mmto3inches).
•Modestly compact the sidewall area backfill material by simply walking down the sides of the chambers. Sidewall compaction is important to begin the stabilization process of the soil, to support the chamber sidewalls, and help prevent fine sand migration into the chamber louvers. This procedure may be accomplished any time duringtheinstallationorcoveringprocess.
ArC/BIODIFFUSEr LEACHING SYSTEMS: INSTALLATION PrOCEDUrES
18
Typical Trench: Cross Section
36"Typ
34"
6"MinTopsoil
Backfill
Sewer&Drainand/orTripleWallorPer LocalRegulation
SepticTankD-Box
InspectionPorts EndCapsMustbeInstalledonBothEndsofEveryChamberRow
DeterminedbyStateandLocalCodes
Typical Installation: I. Trench Configuration•Thetypicalinstallationisusedinmostapplications.
Typical Trench: Plan View
19
Typical Installation:
II. Bed Configuration
Typical Bed: Cross Section
36"Typ
34"
6"MinTopsoil
Backfill
Typical Bed: Plan View
Sewer&Drainand/or TripleWallorPer LocalRegulation
SepticTankD-Box
InspectionPorts
EndCapsMustbeInstalledonBothEndsofEveryChamberRow
DeterminedbyStateandLocalCodes
20
Typical Configurations: III. Serial Configuration – Direct (End Cap-to-End Cap)
36"Typ34"
6"MinTopsoilBackfill
Center-to-CenterPerCode
Serial to Direct: Cross Section (slope)
Serial to Direct: Plan View
Sewer&Drainand/or TripleWallorPer LocalRegulation
D-Box
InspectionPorts
EndCapsMustbeInstalledonBothEndsofEveryChamberRow
DeterminedbyStateandLocalCodes
SepticTank
HighFlowSplashPlate(notshown)
21
Additional Configurations: I. Mound Configuration
Cross Section:
3inor4inSolidPVCSewerPipe 24inMaxCover12inofCoverH-10LoadRated(Including4in-6inTopSoil)
34inArcChamber
SpecifiedFillExistingGrade
SidePortCoupler
EndCap
DeterminedbyStateandLocalCodes
22
Additional Configurations: II. Pump Systems: Pump to D-Box – For Equal Length Chamber rows
Pump to D-Box: D-Box Section View
Pump to D-Box: Plan View
Sewer&Drainand/or TripleWallorPer LocalRegulation
PumpTank
D-Box
InspectionPorts
EndCapsMustbeInstalledonBothEndsofEvery
ChamberRow
DeterminedbyStateandLocalCodes
SepticTank
HighFlowSplashPlate(notshown)
3"to4"OverflowtoTopInletofEndPipe
ForceMainfromPumpTank
1/4"HoleFacingWallofD-Box
D-Box(D-BoxEnlargedView)
23
Additional Configurations: III. Pump Systems: Pump to Serial – For Sloping Terrain
Pump to Serial: Plan View
Sewer&Drainand/or TripleWallorPer LocalRegulation
PumpTank
InspectionPorts
EndCapsMustbeInstalledonBothEndsofEvery
ChamberRow
DeterminedbyStateandLocalCodes
SepticTank
HighFlowSplashPlate(notshown)
24
Additional Configurations: IV. Pressure Dosing System
SepticTank
InspectionPorts
EndCapsMustbeInstalledonBothEndsofEveryChamberRow
DeterminedbyStateandLocalCodes
PumpTank
SpitterValve
Pressure Dosing: Plan ViewPressurePipeDetail
Pressure Dosing:Pipe Support Installation Cross Section
36"Typ
34"
6"MinTopsoil
Backfill Chamber
PressurePipewithHolesat12O’clock
InstallaPipeSupportEvery10'toMaintainPositionandPreventPipeRotation
Chamber
PressurePipewithHolesat12O’clock
PressurePipewithAllWeatherPipeStrapsatEveryChamberConnection
Pressure Dosing:Pipe Support Installation Cross Section
25
Additional Configurations: V. Side Port Layout – Header- Middle - radius
26
Additional Configurations: VI. Side Port Layout – Serial
27
Sizing of ArC 36 Standard Chamber For Trench SystemsChambers are to be installed with 3 foot trench separation from edge to edge The following table will determine the minimum number of chambers needed (For residential Use)
Soil NumberofBedrooms Additional
Profile 2 3 4 5 6 Bedroom
180GPD 270GPD 360GPD 450GPD 540GPD 90GPD
1 22 33 43 53 65 12
2 18 26 35 43 52 9
3 18 26 35 43 52 9
4 15 22 28 35 42 8
5 15 22 28 35 42 8
6 15 22 28 35 42 8
7 18 26 35 43 52 9
8 22 33 43 53 65 12
9 26 39 52 65 78 13
Notes: 1.TheeffectivelengthoftheARC36standardchamberis60-inches. 2.SizingcreditfortheArc36standardchamberequals35sq.ft.perchamberor7.0sq.ft.linearfoot.3.Arc36SPCsizingcreditof6.0sq.ft.perunit.
Soil NumberofBedrooms Additional
Profile 2 3 4 5 6 Bedroom
180GPD 270GPD 360GPD 450GPD 540GPD 90GPD
1 19 29 38 47 57 10
2 15 23 30 38 45 8
3 15 23 30 38 45 8
4 13 19 24 30 37 7
5 13 19 24 30 37 7
6 13 19 24 30 37 7
7 15 23 30 38 45 8
8 19 29 38 47 57 10
9 23 34 45 57 68 12
Sizing of ArC 36 High Capacity Chamber For Trench SystemsChambers are to be installed with 3 foot trench separation from edge to edgeThe following table will determine the minimum number of chambers needed (For residential Use)
Notes:1.TheeffectivelengthoftheARC36highcapacitychamberis60-inches.2.SizingcreditfortheARC36highcapacitychamberequals40sq.ft.perchamberor8.0sq.ft.perlinearfoot.3.Arc36highcapacitySPCsizingcreditof6.0sq.ft.perunit.
28
Soil NumberofBedrooms Additional
Profile 2 3 4 5 6 Bedroom
180GPD 270GPD 360GPD 450GPD 540GPD 90GPD
1 17 26 34 42 51 9
2 14 21 27 34 41 7
3 14 21 27 34 41 7
4 11 16 22 27 32 6
5 11 16 22 27 32 6
6 11 16 22 27 32 6
7 14 21 27 34 41 7
8 17 26 34 42 51 9
9 21 31 41 52 62 11
Sizing of 1100BD Standard Chamber For Trench Systems Chambers are to be installed with 3 foot trench separation from edge to edge The following table will determine the minimum number of chambers needed (For residential Use)
Notes:1.Theeffectivelengthofthe1100BDstandardchamberis75-inches.2.Sizingcreditforthe1100BDchamberequals44sq.ft.perchamberor7.0sq.ft.perlinearfoot.
Soil NumberofBedrooms Additional
Profile 2 3 4 5 6 Bedroom
180GPD 270GPD 360GPD 450GPD 540GPD 90GPD
1 27 39 52 65 77 14
2 21 32 42 52 60 11
3 21 32 42 52 60 11
4 18 26 33 42 50 10
5 18 26 33 42 50 10
6 18 26 33 42 50 10
7 21 32 42 52 60 11
8 27 40 52 65 77 14
9 33 48 64 79 95 16
Sizing of 1500BD Bio 2 Narrow Chamber For Trench Systems
Chambers are to be installed with 18-inch trench separation from edge to edge The following table will determine the minimum number of chambers needed (For residential Use)
Notes:1.Theeffectivelengthofthe1500BDBio2narrowchamberis86-inches.2.Sizingcreditforthe1500BDBio2narrowchamberequals28.8sq.ft.perchamberor4.0sq.ft.perlinearfoot.
29
Soil NumberofBedrooms Additional
Profile 2 3 4 5 6 Bedroom
180GPD 270GPD 360GPD 450GPD 540GPD 90GPD
1 15 23 30 37 45 8
2 12 18 24 30 36 6
3 12 18 24 30 36 6
4 10 15 19 24 29 5
5 10 15 19 24 29 5
6 10 15 19 24 29 5
7 12 18 24 30 36 6
8 15 23 30 37 45 8
9 18 27 36 45 54 9
Sizing of 1600BD High Capacity Chamber For Trench Systems
Chambers are to be installed with 3 foot trench separation from edge to edge The following table will determine the minimum number of chambers needed (For residential Use)
Notes:1.Theeffectivelengthofthe1600BDhighcapacitychamberis75-inches.2.Sizingcreditforthe1600BDhighcapacitychamberequals50sq.ft.perchamberor8.0sq.ft.perlinearfoot.
Soil NumberofBedrooms Additional
Profile 2 3 4 5 6 Bedroom
180GPD 270GPD 360GPD 450GPD 540GPD 90GPD
1 38 58 75 93 113 20
2 30 45 60 75 90 15
3 30 45 60 75 90 15
4 25 38 48 60 73 13
5 25 38 48 60 73 13
6 25 38 48 60 73 13
7 30 45 60 75 90 15
8 38 58 75 93 113 20
9 45 68 90 113 135 23
Sizing of ArC 18 Narrow Chamber For Trench Systems
Chambers are to be installed with 18-inch trench separation from edge to edge The following table will determine the minimum number of chambers needed (For residential Use)
Notes:1.TheeffectivelengthoftheARC18narrowchamberis60-inches.2.SizingcreditfortheARC18narrowchamberequals20sq.ft.perchamberor4.0sq.ft.perlinearfoot.
30
Soil NumberofBedrooms Additional
Profile 2 3 4 5 6 Bedroom
180GPD 270GPD 360GPD 450GPD 540GPD 90GPD
1 26 40 52 65 79 14
2 21 32 42 52 63 11
3 21 32 42 52 63 11
4 18 26 33 42 51 9
5 18 26 33 42 51 9
6 18 26 33 42 51 9
7 21 32 42 52 63 11
8 26 40 52 65 79 14
9 32 47 63 79 94 16
Sizing of ArC 36 & 36 High Capacity Chambers For Cluster Systems recommended 6-inch separation between chamber rowsThe following table will determine the minimum number of chambers needed (For residential Use)
Notes:1.TheeffectivelengthoftheARC3613BD2&3616BD2chambersis60-inches.2.SizingcreditfortheARC3613BD2&3616BD2chambers(bottomareaonly)equals29sq.ft.perchamberor5.8sq.ft.perlinearfoot.
Soil NumberofBedrooms Additional
Profile 2 3 4 5 6 Bedroom
180GPD 270GPD 360GPD 450GPD 540GPD 90GPD
1 21 31 41 52 62 11
2 17 25 33 42 50 9
3 17 25 33 42 50 9
4 13 20 26 33 39 7
5 13 20 26 33 39 7
6 13 20 26 33 39 7
7 17 25 33 42 50 9
8 21 31 41 52 62 11
9 25 38 50 63 75 13
Sizing of 1100BD & 1600BD Chamber For Cluster Systems
recommended 6-inch separation between chamber rows The following table will determine the minimum number of chambers needed (For residential Use)
Notes:1.Theeffectivelengthofthe1100BD&1600BDchambersis75-inches.2.Sizingcreditforthe1100BD&1600BDchambers(bottomareaonly)equals36sq.ft.perchamberor5.76sq.ft.perlinearfoot.
31
Notes:1.TheeffectivelengthoftheARC3613BD2&3616BD2chambersis60-inches.2.SizingcreditfortheARC3613BD2&3616BD2chambers(bottomareaonly)equals29sq.ft.perchamberor5.8sq.ft.perlinearfoot.
Soil NumberofBedrooms Additional
Profile 2 3 4 5 6 Bedroom
180GPD 270GPD 360GPD 450GPD 540GPD 90GPD
1 21 31 41 52 62 11
2 17 25 33 42 50 9
3 17 25 33 42 50 9
4 13 20 26 33 39 7
5 13 20 26 33 39 7
6 13 20 26 33 39 7
7 17 25 33 42 50 9
8 21 31 41 52 62 11
9 25 38 50 63 75 13
1-800-821-6710 www.ads-pipe.com
888-FOR PIPE (367-7473) www.hancor.com
Innovation in product, process and technology.
That’s ADS and Hancor.
Beginning with single wall corrugated polyethylene pipe, ADS and Hancor have
continually introduced drainage products that have set the industry standard –
bringing to market a remarkable alternative to concrete and steel pipe. Our
commitment to being the best means that we continue to refine the structural
design of our pipe and redefine the limits of its application in the structural
design community.
Advanced Drainage Systems, the ADS logo, the green stripe, “The Most Advanced Name in Drainage Systems” and ARC™ are registered trademarks of Advanced Drainage Systems, Inc. Hancor is a
registered trademark of Hancor, Inc. ADS “Terms and Conditions of Sale” are available on the ADS website, www.ads-pipe.com. © 2009 Advanced Drainage Systems, Inc.
INS10636/0909