On LoadTap Changers

Page 2: On Load Tap Changers

OLTC type RS 5 / RS 5.3 RSV 5.3

Mechanical endurance 500,000 s.o. 500,000 s.o.

Electrical endurance 150,000 s.o. 300,000 s.o.

Maximum rated currents 200, 400, 630, 1250 A up to 1250 A

Highest voltage for equipment up to 72,5 kV up to 36 kV

Step voltage up to 3000 V up to 1000 V

Maximum number of tap operating positions 14 / 27 14 / 27

Tap selector insulation level K, L K

elliptic / round round

Three phase design for transformers with delta connected windings

02www.seielectric.com

On Load Tap Changers

Page 3: On Load Tap Changers

03

OLTC type RS 6 / RS 6.3 RSV 6.3

Mechanical endurance 500,000 s.o. 500,000 s.o.

Electrical endurance 150,000 s.o. 300,000 s.o.

Maximum Rated Currents up to 1250 A up to 1200 A

Highest voltage for equipment up to 300 kV up to 300 kV

Step voltage up to 2500 V up to 2500 V

Maximum number of tap operating positions 14 / 27 14 / 27

Tap selector insulation level K, L, M K, L, M

elliptic / round round

Three phase design for regulation at neutral point

www.seielectric.com

On Load Tap Changers

Page 4: On Load Tap Changers

04

OLTC type RS 7 RSV 7.3

Mechanical endurance 500,000 s.o. 500,000 s.o.

Electrical endurance 500,000 s.o. 500,000 s.o.

Maximum Rated Currents 200, 400, 630, 800 A 400, 550, 700, 1200 A

Highest voltage for equipment up to 300 kV up to 300 kV

Step voltage up to 3000 V up to 3000 V

Maximum number of tap operating positions 107 107

Tap selector insulation level M, N M, N

round round

Single phase design with increased number of operating positions

On Load Tap Changers

www.seielectric.com

Page 5: On Load Tap Changers

OLTC type RS 9 / RS 9.3 RSV 9.3

Mechanical endurance 1 000,000 s.o. 1 200,000 s.o.

Electrical endurance 500,000 s.o. 500,000 s.o.

Maximum Rated CurrentsI ph: 200, 400, 630, 800, 1200, 1600 AIII ph: 200, 400, 630 A

I ph: 400, 550, 700, 1200, 1500 AIII ph: 400, 550, 700

Highest voltage for equipment up to 300 kV up to 300 kV

Step voltage up to 4000 V up to 3500 V

Maximum number of tap operating positions 18 / 35 18 / 35

Tap selector insulation level K, L, M, N, P K, L, M, N, P

elliptic / round elliptic / round

Single phase design for regulation at any point on the winding

Three phase design for regulation at neutral point

05

On Load Tap Changers

www.seielectric.com

Page 6: On Load Tap Changers

OLTC type RS 12 RSV 12

Mechanical endurance 500,000 s.o. 1 200,000 s.o.

Electrical endurance 200,000 s.o. 800,000 s.o.

Maximum Rated Currents 200, 400 A 250, 400, 600 A

Highest voltage for equipment up to 145 kV up to 145kV

Step voltage up to 2500 V up to 2500 V

Maximum number of tap operating positions 14 / 27 12 / 23

round round

Single phase design for regulation at any point on the winding

Compact three phase designfor transformers with star and delta connected windings

06

On Load Tap Changers

www.seielectric.com

Page 7: On Load Tap Changers

OLTC type RS 21

Mechanical endurance 800,000 s.o.

Electrical endurance 200,000 s.o.

Maximum Rated Currents 310 A

Highest voltage for equipment 72,5 kV

Step voltage 1200 V

Maximun number of tap operating positions up to 23

Tap selector insulation level L

Carrying flange shape elliptic

Single phase design used in SF6 Gas Insulated Transformers

07

On Load Tap Changers

www.seielectric.com

Page 8: On Load Tap Changers