ARTon Alfa Pro Series 10 ~ 200 kVA Output power factor 1.0 for 10~80 kVA True double conversion DSP technology guarantees high reliability Active power factor correction in all phases Maintenance bypass available Smart battery charger design to optimize battery performance Adjustable battery design (32~40 pcs.) 50Hz/60Hz frequency converter mode ECO mode operation for energy saving Optional parallel operation Adjustable charging current (available for 100kVA and up models) On Line Uninterrutible Power Supply Specifications General Application Areas: Finance Medical Industry IT Energy Construction Emergency power off function (EPO) Optional 10” touchscreen color LCD (available for 100kVA and up models)

On Line Uninterrutible Power Supply ARTon Alfa Pro Series ... · ARTon Alfa Pro Series 10 ~ 200 kVA Output power factor 1.0 for 10~80 kVA True double conversion DSP technology guarantees

  • Upload
    others

  • View
    6

  • Download
    0

Embed Size (px)

Citation preview

  • ARTon Alfa Pro Series 10 ~ 200 kVA

    Output power factor 1.0 for 10~80 kVA True double conversion DSP technology guarantees high reliability Active power factor correction in all phases Maintenance bypass available Smart battery charger design to optimize battery performance Adjustable battery design (32~40 pcs.) 50Hz/60Hz frequency converter mode ECO mode operation for energy saving

    Optional parallel operation Adjustable charging current (available for 100kVA and up models)

    On Line Uninterrutible Power Supply

    Specifications

    General Application Areas:

    Finance Medical Industry IT Energy Construction

    Emergency power off function (EPO)

    Optional 10” touchscreen color LCD (available for 100kVA and up models)

  • 10 / 20 / 30 / 40 / 60 / 80 kVA LCD Front Display

    100 / 120 / 160 / 200 kVA 10” Touchscreen Graphic LCD Front Display

    Frequency Range

    Net Weight (kg)

    Net Weight (kg)

    10” Touch Type color LCDUPS status, load level, battery level, Input/Output voltage,

    discharge timer and fault conditions

    Capacity (kVA)

    Capacity (kW )

    ARTon Alfa Pro Series 10~200 kVA Technical Specifications

    Harmonic Distortion

    Harmonic Distortion

    SNMP (Optional)

    Noise Level (From 1meter)

    Supports Windows® 2000/2003/XP/Vista/2008, Windows® 7/8/10, Linux and MAC

    Power Factor

    Voltage Range

    Nominal Voltage

    Frequency Range (Sync.Range)

    Output Voltage

    AC Voltage Regulation

    Current Crest Ratio

    *If output voltage is set as 3x360VAC, the output power of the unit will be de-rated to 90%

    Operation Temperature

    Power management from SNMP manager and web browser

    Smart RS232 / USB

    Operation Humidity 95% and non-condensing

    Frequency Range (Batt. Mode)

    Parallel Capacity

    >

    60 min. for 105%-110%, 10 min. for 111%-125%, 1 min. for 126%-150%, 200 msec. for 150%

    DimensionsDxWxH (mm)

    DimensionsDxWxH (mm)

    Product specifications are subject to change without further notice by ARTronic.

    Efficiency

    ARTonAlfa Pro 10 *

    ARTonAlfa Pro 20 *

    ARTonAlfa Pro 30

    ARTonAlfa Pro 40

    ARTonAlfa Pro 60

    ARTonAlfa Pro 80

    ARTonAlfa Pro 100

    ARTon Alfa Pro 120

    ARTon Alfa Pro 160

    ARTon Alfa Pro 200

    10 kVA10 kVA 20 kVA 30 kVA 40 kVA 60 kVA 80 kVA 100 kVA 120 kVA 160 kVA 200 kVA

    10 kW9 kW 20 kW 30 kW 40 kW 60 kW 80 kW 90 kW 108 kW 144 kW 180 kW

    AC mode to Batt.

    Inverter to Bypass

    AC Mode

    Numbers

    Charging Current (max.)

    Charging Voltage

    24A 32A 40A 48A

    Less than 70 dB@ 1 meter

    Less than 73 dB@ 1 meter

    % 96 % 94,0

    6 4

    zero

    2 % THD (Lineer Load) 4 % THD (Non Lineer Load)

    208-478 VAC (3-phase) @ %70 load

    load

    full load

    305-478 VAC (3-phase) @ %100 load

    40~70Hz

    3 x 380/400/415 VAC (3Ph+N)

    Transfer Time

    % 98,0

    % 96 % 93,0

    % 99

    1 % THD (Lineer Load) 3 % THD (Non Lineer Load)

    zero

    ± 1%

    3:1 (max)

    3 x 360*/380/400/415 VAC (3Ph+N)

    MODEL

    Battery Mode

    AC Mode

    LCD Display

    ECO Mode

    46~54Hz or 56~64Hz

    50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz

    0-40°C

    32~40 pcs (Adjustable)

    <

    Overload

    Charging Voltage

    Numbers

    1A~12A Adjustable

    % 90.5

    % 96.0

    % 87.0

    Less than 60 dB@ 1 meter

    4A

    16-20 pcs(Adjustable)

    16 pcs

    ARTonAlfa Pro 10

    626 x 250 x750

    626 x 250 x 750

    139

    43

    815 x 300 x 1000

    815 x 300 x 1000

    225 250

    60 61

    N/A

    790 x 360 x 1010

    108 113

    940 x 567 x 1015

    194 229

    1040 x 567 x 1452

    306 340

    StandardModel

    1A~12A (Adjustable) 2A~24A (Adjustable)

    +/-218 VDC ± 10%

    (16 + 16) pcs x2 strings(16 + 16) pcs

    x1 strings

    218.4 VDC ± 1%

    9 hours recover to %90 capacity

    12 V / 7Ah12 V / 9Ah 12 V / 9Ah 12 V / 9Ah 12 V / 9Ah

    N/ATypical Recharge Time

    Battery Type

    592 X 250 X 826

    592 X 250 X 576

    96

    32

    Input

    Output

    Efficiency

    Battery

    Charging Current (max.)

    Long-RunModel

    Indicators

    Physical

    StandardModel

    Long-runModel

    Environment

    Management

    (10+10) pcs x1

    +/-136.5VDC ± 10%

    +/-13.65V x N (N= 16-20) +/-13.7V x N (N= 16-20)

    20 pcs

    124

    28

    Less than 63 dB@ 1 meter

    Less than 65 dB@ 1 meter

    +/- 136.5 VDC± 10%

    273 VDC ± 1%(Based on 20 pcs batteries)

    1A

    60 min. for 100%-110%, 10 min. for 110%-125%, 1 min. for 125%-150%, 400 msec. for 150%