NYC Department of Education
Building Condition Assessment Survey 2018-2019
M144Architectural Inspection
Inspection Type Last EditedTime InInspectionId
P.S. 242 (OLD P144) - MANHATTAN, 134 WEST 122 STREET, MANHATTAN, NY, 10027School:
434 2018-11-28 09:07AM 2019-01-18 02:30PMARCHITECTURAL - ASSOCIATE
463 2018-11-28 07:18AM 2019-06-21 10:43AMARCHITECTURAL - SENIOR
Asset DataQuestion Answer
Was the Building Fully Accessible for Inspection? Yes
Principal(s) Information
Principal Name Denise Gomez
Principal Organization P.S. 242- Manhattan
Meeting with Principal? No
Principal Feedback No Feedback from Principal
Principal Name Alyssa Brown, Operations Manager
Principal Organization Future Leaders Charter School
Meeting with Principal? Yes
Principal Feedback The Principal provided the following comments:
1- The heating system is inconsistent with many classrooms either
too hot or too cold, and needs to be repaired.
2- Given our current enrollment, the school needs an elevator to
accommodate the handicapped.
3- Ongoing water infiltration have caused damage in some of our
classrooms and repairs need to take place.
4- The water pressure is deficient in the Student Toilet Rooms and
repairs or upgrades are necessary.
Custodian Jose Medina
Fireman Pete Perrolas
Building Square Footage 83,000
Comments on the Area (Square Feet) None
Comments on the Stories (Floors) plus Basements 3+B
Comments on the Year Built 1959
Comments on the Student Population 506
Comments on the Staff Population 94
Comments on the Number of Classrooms 39
Weather Fair
Facade Photo
West 122 Street - Southeast view
Page 1 of 33 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
M144Architectural InspectionMain Entrance Photo
Facade A - West 122 Street
Roof Photo
Roof 1 - East view
Have any Systems/Major Building Components been upgraded? Systems: Replaced the Curtains in the auditorium
Years: 2018
Systems: Exterior walls repair
Years: 2017
Systems: Limited Structural repairs; New Exterior stairs, HC
Ramp and (2) Exterior Doors and Frames at Facade C;
Limited Interior Door replacement.
Years: 2016
Systems: Complete Exterior Masonry Modernization and
Roofing replacement including Parapet reconstruction
and Coping replacement (at Roofs 1 and 3 only).
Years: 2013
Systems: Bulkhead and Chimney repairs, Complete Bulkhead
Roofing replacement; Limited Floor Tile replacement
(at Kindergarten Rooms).
Years: 2010
Systems: New Elevator, Exterior Ramp and limited Student
Toilet Room HC Upgrades.
Years: 2001
Systems: Limited Exterior Masonry, Coping, Flashing and
Roofing repairs.
Years: 2006
Systems: Complete Roofing, Windows, and Exterior Guards
replacement
Years: 1999
Have there been any New Building Additions? No New Construction
Tandem No Tandem
Page 2 of 33 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
M144Architectural InspectionLeased Space? No
Priority ConditionExist
Last Year?
Priority
Category
Condition
Description
Component
Affected
Location
Description
Person(s)
Notified
Person(s)
Title
Photo
Image
Protruding Elements Protruding metal sill
poses a potential safety
hazard
Other
(Non-PBS
Related)
Toilet Room
115
Pete
Perkolias
No Fireman
Structural Engineer Required
Structural
Condition Type
Condition
Description
Component
Affected
Location
Description
Person(s)
Notified
Person(s)
Title
Photo
Image
No condition recorded
Accessibility
Accessibility Status Question Response
Physical Breakdown Structure Exists Complies Required Deficiency
FUNCTIONAL ACCESSIBILITY
Exterior Routes
YesExterior Entrances & Exits
NoNoExterior H/C Lifts
NoYesExterior Ramps and Railings
Interior Routes
NoNoCorridor and Lobby H/C Lifts
NoYesInterior Corridor Doors And Hardware
YesInterior Corridors & Lobbies
YesYesInterior Elevators
YesInterior Lobby Doors And Hardware
NoInterior Ramps
Rooms & Spaces
Art Rooms
Yes YesRoom 129
Auditorium
Yes Yes1st Floor
Cafeteria
Yes Yes1st Floor
Classrooms
Yes Yes1st through 3rd Floor
NoComputer Rooms
Gymnasium
Yes Yes1st Floor
Library
Yes YesRoom 201
Main Office
Yes YesRooms 107 and 304
NoMulti-purpose Room
Nurse's Office
Yes YesRoom 113
NoPool
NoScience Lab
Page 3 of 33 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
M144Architectural Inspection
Physical Breakdown Structure Exists Complies Required Deficiency
Toilet Rooms (boys)
Yes Yes1st and 3rd Floors
Toilet Rooms (girls)
Yes Yes1st and 3rd Floors
Toilet Rooms (staff)
Yes Yes1st through 3rd Floors
Building Template
Inspection
Question Response
Architectural
ATHLETIC FIELDS Does not exist
EXTERIOR Inspected
InspectedAREAWAY
Instance on Adjacent to Facade A Inspected
3- FairInstance Condition
Instance Quantity 1
Instance Quantity Uom EACH
AREAWAY WALLS:CRACKS AND SPALLINGDeficiency
Deficiency Location/Instance
30Deficiency Quantity
Quantity Uom S.F.
Potential Action REPAIR
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Page 4 of 33 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
M144Architectural Inspection
Question Response
EXTERIOR
AREAWAY
Deficiency Photo 1
AW1
Violations No violations recorded
InspectedAWNINGS AND CANOPIES
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedCHIMNEY
MasonryMaterial Type(s)
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedCOPING
Condition 2- Between Good and Fair
CAST STONE:CRACKED/BROKEN PIECESDeficiency
Deficiency Location/Instance
20Deficiency Quantity
Quantity Uom L.F.
Potential Action REPLACE-IN-KIND
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Roof 1 - Facade A
Violations No violations recorded
Does not existCORNICE
InspectedDOORS
InspectedDOOR HARDWARE
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedDOORS AND FRAMES
Condition 3- Fair
METAL:DETERIORATED DOOR AND FRAME - MINOR
DETERIORATION
Deficiency
Page 5 of 33 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
M144Architectural Inspection
Question Response
EXTERIOR
DOORS
DOORS AND FRAMES
Deficiency Location/Instance
3Deficiency Quantity
Quantity Uom EACH
Potential Action MAINTENANCE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Main Entrance
Violations No violations recorded
InspectedLINTELS
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedTRANSOM/SIDE LIGHT
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedEXTERIOR SOFFITS
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedEXTERIOR WALLS
Concrete, MasonryMaterial Type(s)
24,000Replacement Quantity
Replacement Uom S.F.
Instance on All Facades Inspected
3- FairInstance Condition
Instance Quantity 24,000
Instance Quantity Uom S.F.
BRICK:MINOR CRACKS AND SPALLINGDeficiency
Roof Plan Reference
Page 6 of 33 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
M144Architectural Inspection
Question Response
EXTERIOR
EXTERIOR WALLS
Elevation
Elevation Reference Facade A
50Deficiency Quantity
Quantity Uom S.F.
Potential Action RESTITCH
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Facade A
Violations No violations recorded
CAST IN PLACE / PRE-CAST CONCRETE:MINOR CRACKS,
SPALLED, DETERIORATED REBAR
Deficiency
Roof Plan Reference
Elevation
Elevation Reference Facade A
60Deficiency Quantity
Quantity Uom S.F.
Potential Action REPAIR
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Facade A
Violations No violations recorded
Page 7 of 33 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
M144Architectural Inspection
Question Response
EXTERIOR
EXTERIOR WALLS
CERAMIC TILE:CHIPPED, SPALLED, BROKEN PIECESDeficiency
Roof Plan Reference
Elevation
Elevation Reference Facade A
30Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 4Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Facade A - Left of Main Entrance
Violations No violations recorded
BRICK:OPEN JOINTSDeficiency
Roof Plan Reference
Elevation
Elevation Reference Facade A
500Deficiency Quantity
Quantity Uom S.F.
Potential Action REPOINT
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Page 8 of 33 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
M144Architectural Inspection
Question Response
EXTERIOR
EXTERIOR WALLS
Deficiency Photo 1
Facade A
Violations No violations recorded
BRICK:DETERIORATED CONTROL/EXPANSION JOINTS
WITH DAMAGED CAULKING
Deficiency
Roof Plan Reference
Elevation
Elevation Reference Facade A
50Deficiency Quantity
Quantity Uom L.F.
Potential Action MAINTENANCE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Facade A - corner near HC Entrance
Violations No violations recorded
BRICK:WATER INFILTRATION IN INSTRUCTIONAL SPACEDeficiency
Roof Plan Reference
Page 9 of 33 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
M144Architectural Inspection
Question Response
EXTERIOR
EXTERIOR WALLS
Elevation
Elevation Reference Facade A
250Deficiency Quantity
Quantity Uom S.F.
Potential Action REPAIR
PRIORITY 5Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Room 325 shown, also Rooms 108, 118, 120, 225, 227, 323
Deficiency Photo 2
Floor at Room 323
Violations No violations recorded
Does not existLOADING DOCK
InspectedLOUVER
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedPARAPETS
Masonry, ConcreteMaterial Type(s)
4,600Replacement Quantity
Replacement Uom C.F.
Instance on All Facades Inspected
3- FairInstance Condition
Instance Quantity 4,600
Instance Quantity Uom CF
STONE:MINOR CRACKS, SPALLINGDeficiency
Deficiency Location/Instance
50Deficiency Quantity
Quantity Uom S.F.
Potential Action REPAIR
Page 10 of 33 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
M144Architectural Inspection
Question Response
EXTERIOR
PARAPETS
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Roof 1, Facade A
Violations No violations recorded
BRICK:OPEN JOINTSDeficiency
Deficiency Location/Instance
100Deficiency Quantity
Quantity Uom S.F.
Potential Action REPOINT
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Facade C
Violations No violations recorded
Does not existPLAZA DECK
InspectedROOF
InspectedROOFING
Replacement Quantity 46,000
Replacement Uom S.F.
InspectedLEADERS, GUTTERS, DOWNSPOUTS, SCUPPERS
2- Between Good and FairCondition
No deficiencies recordedDeficiency
Does not existROOF BARRIER
Does not existROOF CAGE
Does not existROOF FENCE
InspectedROOF HATCH/SMOKE HATCH
2- Between Good and FairCondition
No deficiencies recordedDeficiency
InspectedROOFING
Instance on Modified Bitumen:All roofs Inspected
3- FairInstance Condition
Instance Quantity 46,000
Page 11 of 33 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
M144Architectural Inspection
Question Response
EXTERIOR
ROOF
ROOFING
ROOFING
Instance Quantity Uom S.F.
“Does the roof have major mechanical equipment sitting on Dunnage
Steel less than 18" above the Roofing?"
No
Installation Year 2006
Source of Installation Year Documented
No deficiencies recordedDeficiency
InspectedROOFING DRAINS
2- Between Good and FairCondition
No deficiencies recordedDeficiency
InspectedSPECIALTIES
InspectedBULKHEAD/PENTHOUSE
3- FairCondition
BULKHEAD/PENTHOUSE DOORS:DETERIORATED DOOR
AND FRAME
Deficiency
Deficiency Location/Instance
1Deficiency Quantity
Quantity Uom EACH
Potential Action REPLACE DOOR AND FRAME
PRIORITY 2Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
BH 3
Violations No violations recorded
Does not existCUPOLA/ SPIRES/ TOWERS
Does not existDORMER
Does not existDUNNAGE STEEL
Does not existROOF/GRAVITY TANK
InspectedSKYLIGHT/ROOF VENT
Material Type(s) Other
2- Between Good and FairCondition
No deficiencies recordedDeficiency
InspectedSTAIRS/RAMPS: EXTERIOR
InspectedBUILDING CHEEK/FLANK WALLS
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedRAILINGS
Condition 4- Between Fair and Poor
RUST - MAJORDeficiency
Page 12 of 33 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
M144Architectural Inspection
Question Response
EXTERIOR
STAIRS/RAMPS: EXTERIOR
RAILINGS
Deficiency Location/Instance
20Deficiency Quantity
Quantity Uom L.F.
Potential Action REPLACE
PRIORITY 4Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Main Entrance
Violations No violations recorded
InspectedSTAIRS/RAMPS
Condition 3- Fair
CONCRETE:CRACKS/SPALLING - MINORDeficiency
Deficiency Location/Instance
10Deficiency Quantity
Quantity Uom S.F.
Potential Action REPAIR
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Adjacent to the main entrance
Violations No violations recorded
InspectedWINDOWS
9,000Replacement Quantity
Replacement Uom S.F.
InspectedEXTERIOR GUARDS
Condition 3- Fair
DETERIORATED/TORN-OUT/MISSINGDeficiency
Page 13 of 33 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
M144Architectural Inspection
Question Response
EXTERIOR
WINDOWS
EXTERIOR GUARDS
Roof Plan Reference
Elevation
30Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Facade A
Violations No violations recorded
InspectedLINTELS
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedWINDOWS
Material Type(s) Aluminum, Steel
Instance on Aluminum - Double Hung:All Facades Inspected
3- FairInstance Condition
Instance Quantity 9,000
Instance Quantity Uom S.F.
Installation Year 1999
Source of Installation Year Documented
ALUMINUM - DOUBLE HUNG:DETERIORATEDDeficiency
Roof Plan Reference
Page 14 of 33 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
M144Architectural Inspection
Question Response
EXTERIOR
WINDOWS
WINDOWS
Elevation
Elevation Reference Facade A
200Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE WINDOW
PRIORITY 4Urgency of Action
LEVEL 2Purpose of Action
Violations No violations recorded
INTERIOR Inspected
AUDITORIUM
Instance on 1st Floor Inspected
Ceiling
Instance on 1st Floor Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Door(s)
Instance on 1st Floor Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Fixed H/C Lift
Instance on 1st Floor Does not exist
Fixed Seating
Instance on 1st Floor Inspected
2- Between Good and FairInstance Condition
DAMAGED/BROKEN/INOPERABLEDeficiency
Total Seating (434) - G/6,9, N/14, and R/3Deficiency Location/Instance
4Deficiency Quantity
Quantity Uom EACH
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Seat R/3
Page 15 of 33 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
M144Architectural Inspection
Question Response
INTERIOR
AUDITORIUM
Fixed Seating
Deficiency Photo 2
Seat G/6
Violations No violations recorded
Floor Finish
Instance on 1st Floor Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Sliding-folding Partition
Instance on 1st Floor Does not exist
Stage
Instance on 1st Floor Inspected
Stage
Instance on 1st Floor Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Stage Curtain Rigging
Instance on 1st Floor Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Stage Curtains
Instance on 1st Floor Inspected
1- GoodInstance Condition
No deficiencies recordedDeficiency
Walls
Instance on 1st Floor Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Window Curtains/Shades/Blinds
Instance on 1st Floor Does not exist
CAFETERIA
Instance on 1st Floor Inspected
Ceiling
Instance on 1st Floor Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Door(s)
Instance on 1st Floor Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Fixed Equipment
Instance on 1st Floor Does not exist
Floor Finish
Instance on 1st Floor Inspected
2- Between Good and FairInstance Condition
Page 16 of 33 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
M144Architectural Inspection
Question Response
INTERIOR
CAFETERIA
Floor Finish
No deficiencies recordedDeficiency
Sliding-folding Partition
Instance on 1st Floor Does not exist
Stage
Instance on 1st Floor Does not exist
Walls
Instance on 1st Floor Inspected
2- Between Good and FairInstance Condition
GLAZED BLOCK:CRACKS/SPALLINGDeficiency
Window near ServeryDeficiency Location/Instance
10Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Window near Servery
Violations No violations recorded
Window Curtains/Shades/Blinds
Instance on 1st Floor Does not exist
InspectedCLASSROOMS/CORRIDORS/ADMIN SPACES
InspectedCeiling
Condition 2- Between Good and Fair
ACOUSTIC TILES ON PLASTER:DAMAGED/MISSINGDeficiency
At Corridor near Room 101, 120, 302 and 314Deficiency Location/Instance
50Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
At Corridor near Room 101
Violations No violations recorded
InspectedDoor(s)
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedFloor Finish
Condition 2- Between Good and Fair
Page 17 of 33 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
M144Architectural Inspection
Question Response
INTERIOR
CLASSROOMS/CORRIDORS/ADMIN SPACES
Floor Finish
VINYL TILES:BROKEN/DETERIORATED/MISSING TILESDeficiency
Room 225, At Corridor near Stair A/2Deficiency Location/Instance
20Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Room 225
Deficiency Photo 2
At Corridor near Stair A/2
Violations No violations recorded
VINYL TILES:TRIPPING HAZARD - ELECTRICAL OUTLETDeficiency
Room 112Deficiency Location/Instance
10Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 5Urgency of Action
LEVEL 6Purpose of Action
Deficiency Photo 1
Room 112
Violations No violations recorded
InspectedSpecialties
InspectedClassroom Locker(s)
2- Between Good and FairCondition
No deficiencies recordedDeficiency
Does not existFixed Seating
InspectedWalls
Condition 2- Between Good and Fair
PLASTER:CRACKS/SPALLINGDeficiency
At Corridor near Stair A/2 and 3Deficiency Location/Instance
10Deficiency Quantity
Page 18 of 33 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
M144Architectural Inspection
Question Response
INTERIOR
CLASSROOMS/CORRIDORS/ADMIN SPACES
Walls
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
At Corridor near Room A/3
Violations No violations recorded
PLASTER:CRACKS/SPALLING - ACTIVE LEAKDeficiency
Rooms 118 and 120Deficiency Location/Instance
10Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 5Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Room 120
Violations No violations recorded
GYMNASIUM
Instance on 1st Floor Inspected
Ceiling
Instance on 1st Floor Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Door(s)
Instance on 1st Floor Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Fixed Equipment
Instance on 1st Floor Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Floor Finish
Instance on 1st Floor Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Seating
Instance on 1st Floor Inspected
2- Between Good and FairInstance Condition
Page 19 of 33 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
M144Architectural Inspection
Question Response
INTERIOR
GYMNASIUM
Seating
No deficiencies recordedDeficiency
Sliding-folding Partition
Instance on 1st Floor Does not exist
Stage
Instance on 1st Floor Does not exist
Walls
Instance on 1st Floor Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Window Curtains/Shades/Blinds
Instance on 1st Floor Does not exist
InspectedINTERIOR DOOR HARDWARE
Condition 3- Fair
No deficiencies recordedDeficiency
InspectedINTERIOR GUARDS
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
KITCHEN
Instance on 1st Floor Inspected
Ceiling
Instance on 1st Floor Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Door(s)
Instance on 1st Floor Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Floor Finish
Instance on 1st Floor Inspected
3- FairInstance Condition
CERAMIC TILE:BROKEN/MISSING TILESDeficiency
Near oven and sinkDeficiency Location/Instance
40Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Near oven
Page 20 of 33 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
M144Architectural Inspection
Question Response
INTERIOR
KITCHEN
Floor Finish
Deficiency Photo 2
Near Sink
Violations No violations recorded
Walls
Instance on 1st Floor Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
LIBRARY
Instance on Room 201 Inspected
Built-in Furnishing
Instance on Room 201 Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Ceiling
Instance on Room 201 Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Door(s)
Instance on Room 201 Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Floor Finish
Instance on Room 201 Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Walls
Instance on Room 201 Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Does not existLOCKER ROOM
Does not existMULTI-PURPOSE ROOM
Does not existPOOLS
Does not existSCIENCE DEMO ROOM
Does not existSCIENCE LAB
Does not existSCIENCE PREP ROOM
SHOWER ROOM
Instance on 2nd Floor - Girls Inspected
YesAlternative Use
Instance on 1st Floor - Boys Inspected
YesAlternative Use
Ceiling
Instance on 2nd Floor - Girls Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Page 21 of 33 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
M144Architectural Inspection
Question Response
INTERIOR
SHOWER ROOM
Ceiling
Instance on 1st Floor - Boys Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Door(s)
Instance on 2nd Floor - Girls Does not exist
Instance on 1st Floor - Boys Does not exist
Floor Finish
Instance on 2nd Floor - Girls Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Instance on 1st Floor - Boys Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Walls
Instance on 2nd Floor - Girls Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Instance on 1st Floor - Boys Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
InspectedSTAIRS/RAMPS: INTERIOR
Do Letter Stair Signs Exist? 1
InspectedCeiling
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedDoor(s)
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
Does not existPartition
InspectedRailings
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedStairs and Landings
Condition 2- Between Good and Fair
CONCRETE:CRACKS/SPALLING - MAJORDeficiency
Stair A/BulkheadDeficiency Location/Instance
10Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Stair A/Bulkhead
Violations No violations recorded
Page 22 of 33 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
M144Architectural Inspection
Question Response
INTERIOR
STAIRS/RAMPS: INTERIOR
Stairs and Landings
VINYL TILES:DETERIORATED SUBSTRATEDeficiency
Stair B/2, D/2, and 3Deficiency Location/Instance
30Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Stair B/2
Violations No violations recorded
InspectedWalls
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedSTRUCTURAL
InspectedCOLUMNS/BEAMS/BEARING WALLS
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedFLOOR STRUCTURE
Condition 3- Fair
CONCRETE SLAB ON GRADE:MINOR CRACKSDeficiency
BasementDeficiency Location/Instance
60Deficiency Quantity
Quantity Uom S.F.
Potential Action REPAIR
PRIORITY 3Urgency of Action
LEVEL 5Purpose of Action
Deficiency Photo 1
Crawl Space shown, also in Boiler Room and Gas Meter Room
Violations No violations recorded
InspectedFOUNDATION WALLS
Material Type(s) Concrete
Condition 3- Fair
CONCRETE:CRACKED/SPALLED/REINFORCEMENT
EXPOSED
Deficiency
BasementDeficiency Location/Instance
30Deficiency Quantity
Quantity Uom S.F.
Potential Action REPAIR
Page 23 of 33 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
M144Architectural Inspection
Question Response
INTERIOR
STRUCTURAL
FOUNDATION WALLS
PRIORITY 3Urgency of Action
LEVEL 5Purpose of Action
Deficiency Photo 1
Boiler Room
Violations No violations recorded
InspectedROOF STRUCTURE
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedVAULTS-BUNKERS
InspectedFoundation Walls
2- Between Good and FairCondition
No deficiencies recordedDeficiency
InspectedSlab Structure
2- Between Good and FairCondition
No deficiencies recordedDeficiency
InspectedVault/Ash Hoist Doors and Framing
5- PoorCondition
DETERIORATED/DAMAGED VAULT/ASH HOIST DOORS
AND FRAMING
Deficiency
Basement VaultDeficiency Location/Instance
2Deficiency Quantity
Quantity Uom EACH
Potential Action REPLACE
PRIORITY 4Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Sidewalk Elevator Vault
Violations No violations recorded
InspectedTOILET ROOMS - STAFF
InspectedCeiling
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedDoor(s)
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedFloor Finish
Condition 2- Between Good and Fair
Page 24 of 33 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
M144Architectural Inspection
Question Response
INTERIOR
TOILET ROOMS - STAFF
Floor Finish
No deficiencies recordedDeficiency
InspectedStalls
Condition 4- Between Fair and Poor
RUST - MAJORDeficiency
Room 102Deficiency Location/Instance
1Deficiency Quantity
Quantity Uom EACH
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Room 102
Violations No violations recorded
InspectedWalls
Condition 2- Between Good and Fair
CERAMIC TILE:BROKEN/ MISSINGDeficiency
Room 205 and Toilet Room within GymnasiumDeficiency Location/Instance
10Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Room 205
Violations No violations recorded
PLASTER:CRACKS/SPALLINGDeficiency
1st Floor - Locker Room/Office, Gym OfficeDeficiency Location/Instance
10Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Page 25 of 33 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
M144Architectural Inspection
Question Response
INTERIOR
TOILET ROOMS - STAFF
Walls
Deficiency Photo 1
1st Floor - Locker Room/Office
Violations No violations recorded
InspectedTOILET ROOMS - STUDENTS
InspectedCeiling
Condition 2- Between Good and Fair
PLASTER:CRACKS/SPALLINGDeficiency
Room 213Deficiency Location/Instance
20Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Room 213
Violations No violations recorded
InspectedDoor(s)
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedFloor Finish
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedStalls
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedWalls
Condition 2- Between Good and Fair
CERAMIC TILE:BROKEN/ MISSINGDeficiency
Rooms 115, 219, 311Deficiency Location/Instance
20Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Page 26 of 33 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
M144Architectural Inspection
Question Response
INTERIOR
TOILET ROOMS - STUDENTS
Walls
Deficiency Photo 1
Room 311
Violations No violations recorded
LIFE SAFETY Inspected
Does not existF.D. HOLDING AREA
Does not existSTEEL STAIRS
SITE Inspected
Does not existCONTAINERIZATION
InspectedDRAINAGE SYSTEM FOR ASPHALT
InspectedCatch Basins/Manhole - Surrounded by Asphalt
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
Does not existCulverts - Asphalt Covering
InspectedDRAINAGE SYSTEM FOR CONCRETE
InspectedCatch Basins/Manhole - Surrounded by Concrete
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
Does not existCulverts - Concrete Covering
Does not existDRAINAGE SYSTEM FOR SOIL
InspectedDRINKING FOUNTAINS
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedFENCES
Condition 3- Fair
CONCRETE CURB:DAMAGED/DETERIORATEDDeficiency
Along West 121st StreetDeficiency Location/Instance
30Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Along West 121st Street
Violations No violations recorded
WROUGHT IRON:DAMAGED/DETERIORATEDDeficiency
Along West 122nd StreetDeficiency Location/Instance
40Deficiency Quantity
Page 27 of 33 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
M144Architectural Inspection
Question Response
SITE
FENCES
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Along West 122nd Street
Violations No violations recorded
Does not existIRRIGATION SYSTEM
InspectedPAVING
InspectedDOT Sidewalk
Does not existAsphalt
InspectedConcrete
4- Between Fair and PoorCondition
DAMAGED/DETERIORATED/MISSING SECTIONSDeficiency
Along West 122nd StreetDeficiency Location/Instance
550Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Along West 122nd Street
Deficiency Photo 2
Along West 121st Street
Violations No violations recorded
DAMAGED CURBSDeficiency
Along West 122nd StreetDeficiency Location/Instance
5Deficiency Quantity
Quantity Uom L.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Page 28 of 33 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
M144Architectural Inspection
Question Response
SITE
PAVING
DOT Sidewalk
Concrete
Deficiency Photo 1
Along West 122nd Street
Violations No violations recorded
HEAVINGDeficiency
Along West 121st Street and 122nd StreetDeficiency Location/Instance
125Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Along West 122nd Street
Deficiency Photo 2
Along West 121st Street
Violations No violations recorded
Does not existPavers
InspectedSite Sidewalks & Walkways
Does not existAsphalt
InspectedConcrete
2- Between Good and FairCondition
DAMAGED/DETERIORATED/MISSING SECTIONSDeficiency
Along West 121st StreetDeficiency Location/Instance
25Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Page 29 of 33 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
M144Architectural Inspection
Question Response
SITE
PAVING
Site Sidewalks & Walkways
Concrete
Deficiency Photo 1
Along West 121st Street
Violations No violations recorded
Does not existPavers
InspectedStudent Non-Use
Gravel Exists? No
Does not existAsphalt
InspectedConcrete
2- Between Good and FairCondition
No deficiencies recordedDeficiency
Does not existPavers
InspectedStudent Use
Gravel Exists? No
InspectedAsphalt
3- FairCondition
CRACKS - MAJORDeficiency
Center of East Schoolyard, West side of East SchoolyardDeficiency Location/Instance
300Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
West side of East Schoolyard
Deficiency Photo 2
Center of East Schoolyard
Violations No violations recorded
InspectedConcrete
3- FairCondition
DAMAGED/DETERIORATED/MISSING SECTIONSDeficiency
EntranceDeficiency Location/Instance
Page 30 of 33 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
M144Architectural Inspection
Question Response
SITE
PAVING
Student Use
Concrete
50Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Entrance
Violations No violations recorded
InspectedPavers
2- Between Good and FairCondition
No deficiencies recordedDeficiency
InspectedPLAYGROUNDS
South of West SchoolyardInstance
East SchoolyardInstance
West SchoolyardInstance
Benches
Instance on South of West Schoolyard Does not exist
Instance on East Schoolyard Does not exist
Instance on West Schoolyard Does not exist
Fence
Instance on South of West Schoolyard Does not exist
Instance on East Schoolyard Does not exist
Instance on West Schoolyard Does not exist
Pavement
Instance on South of West Schoolyard Does not exist
Instance on East Schoolyard Does not exist
Instance on West Schoolyard Does not exist
Play Equipment
Instance on South of West Schoolyard Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Instance on East Schoolyard Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Instance on West Schoolyard Inspected
3- FairInstance Condition
BROKEN/DETERIORATED/MISSINGDeficiency
Middle of playgroundDeficiency Location/Instance
1Deficiency Quantity
Quantity Uom EACH
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Page 31 of 33 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
M144Architectural Inspection
Question Response
SITE
PLAYGROUNDS
Play Equipment
Deficiency Photo 1
Middle of playground
Violations No violations recorded
Safety Surfacing
Instance on South of West Schoolyard Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Instance on East Schoolyard Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Instance on West Schoolyard Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Unpaved Area
Instance on South of West Schoolyard Does not exist
Instance on East Schoolyard Does not exist
Instance on West Schoolyard Does not exist
InspectedPLAYING SURFACE
InspectedPlaying Field
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
East SchoolyardInstance
Does not existRunning Track
InspectedRETAINING WALLS
Condition 2- Between Good and Fair
Are there any Retaining Walls 6' OR higher facing public street/sidewalk? No
No deficiencies recordedDeficiency
InspectedSEATING
InspectedBenches
InspectedConcrete
2- Between Good and FairCondition
No deficiencies recordedDeficiency
InspectedMetal/Wood/Plastic
2- Between Good and FairCondition
No deficiencies recordedDeficiency
Does not existBleachers
InspectedSITE WALLS (NOT RETAINING WALLS)
Condition 2- Between Good and Fair
BRICK:CRACKS/SPALLING - MAJORDeficiency
West Schoolyard near center of perimeter fenceDeficiency Location/Instance
5Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
Page 32 of 33 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
M144Architectural Inspection
Question Response
SITE
SITE WALLS (NOT RETAINING WALLS)
LEVEL 2Purpose of Action
Deficiency Photo 1
West Schoolyard near center of perimeter fence
Violations No violations recorded
InspectedSTAIRS/RAMPS: EXTERIOR
InspectedRailings
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedSite Cheek/flank Walls
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedStairs/ramps
Condition 2- Between Good and Fair
STONE:CRACKS/SPALLINGDeficiency
East and West of West SchoolyardDeficiency Location/Instance
10Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
East of West Schoolyard
Violations No violations recorded
Page 33 of 33 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)