NYC Department of Education Building Condition Assessment Survey 2018-2019 M144 Architectural Inspection Inspection Type Last Edited Time In InspectionId P.S. 242 (OLD P144) - MANHATTAN, 134 WEST 122 STREET, MANHATTAN, NY, 10027 School: 434 2018-11-28 09:07AM 2019-01-18 02:30PM ARCHITECTURAL - ASSOCIATE 463 2018-11-28 07:18AM 2019-06-21 10:43AM ARCHITECTURAL - SENIOR Asset Data Question Answer Was the Building Fully Accessible for Inspection? Yes Principal(s) Information Principal Name Denise Gomez Principal Organization P.S. 242- Manhattan Meeting with Principal? No Principal Feedback No Feedback from Principal Principal Name Alyssa Brown, Operations Manager Principal Organization Future Leaders Charter School Meeting with Principal? Yes Principal Feedback The Principal provided the following comments: 1- The heating system is inconsistent with many classrooms either too hot or too cold, and needs to be repaired. 2- Given our current enrollment, the school needs an elevator to accommodate the handicapped. 3- Ongoing water infiltration have caused damage in some of our classrooms and repairs need to take place. 4- The water pressure is deficient in the Student Toilet Rooms and repairs or upgrades are necessary. Custodian Jose Medina Fireman Pete Perrolas Building Square Footage 83,000 Comments on the Area (Square Feet) None Comments on the Stories (Floors) plus Basements 3+B Comments on the Year Built 1959 Comments on the Student Population 506 Comments on the Staff Population 94 Comments on the Number of Classrooms 39 Weather Fair Facade Photo West 122 Street - Southeast view Page 1 of 33 Print Date: 7/3/2019 Mobile Validity Version 2.0 (P)

NYC Department of Education Building Condition Assessment ...Custodian Jose Medina Fireman Pete Perrolas Building Square Footage 83,000 Comments on the Area (Square Feet) None Comments

  • Upload
    others

  • View
    1

  • Download
    0

Embed Size (px)

Citation preview

Page 1: NYC Department of Education Building Condition Assessment ...Custodian Jose Medina Fireman Pete Perrolas Building Square Footage 83,000 Comments on the Area (Square Feet) None Comments

NYC Department of Education

Building Condition Assessment Survey 2018-2019

M144Architectural Inspection

Inspection Type Last EditedTime InInspectionId

P.S. 242 (OLD P144) - MANHATTAN, 134 WEST 122 STREET, MANHATTAN, NY, 10027School:

434 2018-11-28 09:07AM 2019-01-18 02:30PMARCHITECTURAL - ASSOCIATE

463 2018-11-28 07:18AM 2019-06-21 10:43AMARCHITECTURAL - SENIOR

Asset DataQuestion Answer

Was the Building Fully Accessible for Inspection? Yes

Principal(s) Information

Principal Name Denise Gomez

Principal Organization P.S. 242- Manhattan

Meeting with Principal? No

Principal Feedback No Feedback from Principal

Principal Name Alyssa Brown, Operations Manager

Principal Organization Future Leaders Charter School

Meeting with Principal? Yes

Principal Feedback The Principal provided the following comments:

1- The heating system is inconsistent with many classrooms either

too hot or too cold, and needs to be repaired.

2- Given our current enrollment, the school needs an elevator to

accommodate the handicapped.

3- Ongoing water infiltration have caused damage in some of our

classrooms and repairs need to take place.

4- The water pressure is deficient in the Student Toilet Rooms and

repairs or upgrades are necessary.

Custodian Jose Medina

Fireman Pete Perrolas

Building Square Footage 83,000

Comments on the Area (Square Feet) None

Comments on the Stories (Floors) plus Basements 3+B

Comments on the Year Built 1959

Comments on the Student Population 506

Comments on the Staff Population 94

Comments on the Number of Classrooms 39

Weather Fair

Facade Photo

West 122 Street - Southeast view

Page 1 of 33 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 2: NYC Department of Education Building Condition Assessment ...Custodian Jose Medina Fireman Pete Perrolas Building Square Footage 83,000 Comments on the Area (Square Feet) None Comments

NYC Department of Education

Building Condition Assessment Survey 2018-2019

M144Architectural InspectionMain Entrance Photo

Facade A - West 122 Street

Roof Photo

Roof 1 - East view

Have any Systems/Major Building Components been upgraded? Systems: Replaced the Curtains in the auditorium

Years: 2018

Systems: Exterior walls repair

Years: 2017

Systems: Limited Structural repairs; New Exterior stairs, HC

Ramp and (2) Exterior Doors and Frames at Facade C;

Limited Interior Door replacement.

Years: 2016

Systems: Complete Exterior Masonry Modernization and

Roofing replacement including Parapet reconstruction

and Coping replacement (at Roofs 1 and 3 only).

Years: 2013

Systems: Bulkhead and Chimney repairs, Complete Bulkhead

Roofing replacement; Limited Floor Tile replacement

(at Kindergarten Rooms).

Years: 2010

Systems: New Elevator, Exterior Ramp and limited Student

Toilet Room HC Upgrades.

Years: 2001

Systems: Limited Exterior Masonry, Coping, Flashing and

Roofing repairs.

Years: 2006

Systems: Complete Roofing, Windows, and Exterior Guards

replacement

Years: 1999

Have there been any New Building Additions? No New Construction

Tandem No Tandem

Page 2 of 33 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 3: NYC Department of Education Building Condition Assessment ...Custodian Jose Medina Fireman Pete Perrolas Building Square Footage 83,000 Comments on the Area (Square Feet) None Comments

NYC Department of Education

Building Condition Assessment Survey 2018-2019

M144Architectural InspectionLeased Space? No

Priority ConditionExist

Last Year?

Priority

Category

Condition

Description

Component

Affected

Location

Description

Person(s)

Notified

Person(s)

Title

Photo

Image

Protruding Elements Protruding metal sill

poses a potential safety

hazard

Other

(Non-PBS

Related)

Toilet Room

115

Pete

Perkolias

No Fireman

Structural Engineer Required

Structural

Condition Type

Condition

Description

Component

Affected

Location

Description

Person(s)

Notified

Person(s)

Title

Photo

Image

No condition recorded

Accessibility

Accessibility Status Question Response

Physical Breakdown Structure Exists Complies Required Deficiency

FUNCTIONAL ACCESSIBILITY

Exterior Routes

YesExterior Entrances & Exits

NoNoExterior H/C Lifts

NoYesExterior Ramps and Railings

Interior Routes

NoNoCorridor and Lobby H/C Lifts

NoYesInterior Corridor Doors And Hardware

YesInterior Corridors & Lobbies

YesYesInterior Elevators

YesInterior Lobby Doors And Hardware

NoInterior Ramps

Rooms & Spaces

Art Rooms

Yes YesRoom 129

Auditorium

Yes Yes1st Floor

Cafeteria

Yes Yes1st Floor

Classrooms

Yes Yes1st through 3rd Floor

NoComputer Rooms

Gymnasium

Yes Yes1st Floor

Library

Yes YesRoom 201

Main Office

Yes YesRooms 107 and 304

NoMulti-purpose Room

Nurse's Office

Yes YesRoom 113

NoPool

NoScience Lab

Page 3 of 33 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 4: NYC Department of Education Building Condition Assessment ...Custodian Jose Medina Fireman Pete Perrolas Building Square Footage 83,000 Comments on the Area (Square Feet) None Comments

NYC Department of Education

Building Condition Assessment Survey 2018-2019

M144Architectural Inspection

Physical Breakdown Structure Exists Complies Required Deficiency

Toilet Rooms (boys)

Yes Yes1st and 3rd Floors

Toilet Rooms (girls)

Yes Yes1st and 3rd Floors

Toilet Rooms (staff)

Yes Yes1st through 3rd Floors

Building Template

Inspection

Question Response

Architectural

ATHLETIC FIELDS Does not exist

EXTERIOR Inspected

InspectedAREAWAY

Instance on Adjacent to Facade A Inspected

3- FairInstance Condition

Instance Quantity 1

Instance Quantity Uom EACH

AREAWAY WALLS:CRACKS AND SPALLINGDeficiency

Deficiency Location/Instance

30Deficiency Quantity

Quantity Uom S.F.

Potential Action REPAIR

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Page 4 of 33 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 5: NYC Department of Education Building Condition Assessment ...Custodian Jose Medina Fireman Pete Perrolas Building Square Footage 83,000 Comments on the Area (Square Feet) None Comments

NYC Department of Education

Building Condition Assessment Survey 2018-2019

M144Architectural Inspection

Question Response

EXTERIOR

AREAWAY

Deficiency Photo 1

AW1

Violations No violations recorded

InspectedAWNINGS AND CANOPIES

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedCHIMNEY

MasonryMaterial Type(s)

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedCOPING

Condition 2- Between Good and Fair

CAST STONE:CRACKED/BROKEN PIECESDeficiency

Deficiency Location/Instance

20Deficiency Quantity

Quantity Uom L.F.

Potential Action REPLACE-IN-KIND

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Roof 1 - Facade A

Violations No violations recorded

Does not existCORNICE

InspectedDOORS

InspectedDOOR HARDWARE

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedDOORS AND FRAMES

Condition 3- Fair

METAL:DETERIORATED DOOR AND FRAME - MINOR

DETERIORATION

Deficiency

Page 5 of 33 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 6: NYC Department of Education Building Condition Assessment ...Custodian Jose Medina Fireman Pete Perrolas Building Square Footage 83,000 Comments on the Area (Square Feet) None Comments

NYC Department of Education

Building Condition Assessment Survey 2018-2019

M144Architectural Inspection

Question Response

EXTERIOR

DOORS

DOORS AND FRAMES

Deficiency Location/Instance

3Deficiency Quantity

Quantity Uom EACH

Potential Action MAINTENANCE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Main Entrance

Violations No violations recorded

InspectedLINTELS

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedTRANSOM/SIDE LIGHT

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedEXTERIOR SOFFITS

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedEXTERIOR WALLS

Concrete, MasonryMaterial Type(s)

24,000Replacement Quantity

Replacement Uom S.F.

Instance on All Facades Inspected

3- FairInstance Condition

Instance Quantity 24,000

Instance Quantity Uom S.F.

BRICK:MINOR CRACKS AND SPALLINGDeficiency

Roof Plan Reference

Page 6 of 33 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 7: NYC Department of Education Building Condition Assessment ...Custodian Jose Medina Fireman Pete Perrolas Building Square Footage 83,000 Comments on the Area (Square Feet) None Comments

NYC Department of Education

Building Condition Assessment Survey 2018-2019

M144Architectural Inspection

Question Response

EXTERIOR

EXTERIOR WALLS

Elevation

Elevation Reference Facade A

50Deficiency Quantity

Quantity Uom S.F.

Potential Action RESTITCH

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Facade A

Violations No violations recorded

CAST IN PLACE / PRE-CAST CONCRETE:MINOR CRACKS,

SPALLED, DETERIORATED REBAR

Deficiency

Roof Plan Reference

Elevation

Elevation Reference Facade A

60Deficiency Quantity

Quantity Uom S.F.

Potential Action REPAIR

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Facade A

Violations No violations recorded

Page 7 of 33 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 8: NYC Department of Education Building Condition Assessment ...Custodian Jose Medina Fireman Pete Perrolas Building Square Footage 83,000 Comments on the Area (Square Feet) None Comments

NYC Department of Education

Building Condition Assessment Survey 2018-2019

M144Architectural Inspection

Question Response

EXTERIOR

EXTERIOR WALLS

CERAMIC TILE:CHIPPED, SPALLED, BROKEN PIECESDeficiency

Roof Plan Reference

Elevation

Elevation Reference Facade A

30Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 4Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Facade A - Left of Main Entrance

Violations No violations recorded

BRICK:OPEN JOINTSDeficiency

Roof Plan Reference

Elevation

Elevation Reference Facade A

500Deficiency Quantity

Quantity Uom S.F.

Potential Action REPOINT

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Page 8 of 33 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 9: NYC Department of Education Building Condition Assessment ...Custodian Jose Medina Fireman Pete Perrolas Building Square Footage 83,000 Comments on the Area (Square Feet) None Comments

NYC Department of Education

Building Condition Assessment Survey 2018-2019

M144Architectural Inspection

Question Response

EXTERIOR

EXTERIOR WALLS

Deficiency Photo 1

Facade A

Violations No violations recorded

BRICK:DETERIORATED CONTROL/EXPANSION JOINTS

WITH DAMAGED CAULKING

Deficiency

Roof Plan Reference

Elevation

Elevation Reference Facade A

50Deficiency Quantity

Quantity Uom L.F.

Potential Action MAINTENANCE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Facade A - corner near HC Entrance

Violations No violations recorded

BRICK:WATER INFILTRATION IN INSTRUCTIONAL SPACEDeficiency

Roof Plan Reference

Page 9 of 33 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 10: NYC Department of Education Building Condition Assessment ...Custodian Jose Medina Fireman Pete Perrolas Building Square Footage 83,000 Comments on the Area (Square Feet) None Comments

NYC Department of Education

Building Condition Assessment Survey 2018-2019

M144Architectural Inspection

Question Response

EXTERIOR

EXTERIOR WALLS

Elevation

Elevation Reference Facade A

250Deficiency Quantity

Quantity Uom S.F.

Potential Action REPAIR

PRIORITY 5Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Room 325 shown, also Rooms 108, 118, 120, 225, 227, 323

Deficiency Photo 2

Floor at Room 323

Violations No violations recorded

Does not existLOADING DOCK

InspectedLOUVER

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedPARAPETS

Masonry, ConcreteMaterial Type(s)

4,600Replacement Quantity

Replacement Uom C.F.

Instance on All Facades Inspected

3- FairInstance Condition

Instance Quantity 4,600

Instance Quantity Uom CF

STONE:MINOR CRACKS, SPALLINGDeficiency

Deficiency Location/Instance

50Deficiency Quantity

Quantity Uom S.F.

Potential Action REPAIR

Page 10 of 33 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 11: NYC Department of Education Building Condition Assessment ...Custodian Jose Medina Fireman Pete Perrolas Building Square Footage 83,000 Comments on the Area (Square Feet) None Comments

NYC Department of Education

Building Condition Assessment Survey 2018-2019

M144Architectural Inspection

Question Response

EXTERIOR

PARAPETS

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Roof 1, Facade A

Violations No violations recorded

BRICK:OPEN JOINTSDeficiency

Deficiency Location/Instance

100Deficiency Quantity

Quantity Uom S.F.

Potential Action REPOINT

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Facade C

Violations No violations recorded

Does not existPLAZA DECK

InspectedROOF

InspectedROOFING

Replacement Quantity 46,000

Replacement Uom S.F.

InspectedLEADERS, GUTTERS, DOWNSPOUTS, SCUPPERS

2- Between Good and FairCondition

No deficiencies recordedDeficiency

Does not existROOF BARRIER

Does not existROOF CAGE

Does not existROOF FENCE

InspectedROOF HATCH/SMOKE HATCH

2- Between Good and FairCondition

No deficiencies recordedDeficiency

InspectedROOFING

Instance on Modified Bitumen:All roofs Inspected

3- FairInstance Condition

Instance Quantity 46,000

Page 11 of 33 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 12: NYC Department of Education Building Condition Assessment ...Custodian Jose Medina Fireman Pete Perrolas Building Square Footage 83,000 Comments on the Area (Square Feet) None Comments

NYC Department of Education

Building Condition Assessment Survey 2018-2019

M144Architectural Inspection

Question Response

EXTERIOR

ROOF

ROOFING

ROOFING

Instance Quantity Uom S.F.

“Does the roof have major mechanical equipment sitting on Dunnage

Steel less than 18" above the Roofing?"

No

Installation Year 2006

Source of Installation Year Documented

No deficiencies recordedDeficiency

InspectedROOFING DRAINS

2- Between Good and FairCondition

No deficiencies recordedDeficiency

InspectedSPECIALTIES

InspectedBULKHEAD/PENTHOUSE

3- FairCondition

BULKHEAD/PENTHOUSE DOORS:DETERIORATED DOOR

AND FRAME

Deficiency

Deficiency Location/Instance

1Deficiency Quantity

Quantity Uom EACH

Potential Action REPLACE DOOR AND FRAME

PRIORITY 2Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

BH 3

Violations No violations recorded

Does not existCUPOLA/ SPIRES/ TOWERS

Does not existDORMER

Does not existDUNNAGE STEEL

Does not existROOF/GRAVITY TANK

InspectedSKYLIGHT/ROOF VENT

Material Type(s) Other

2- Between Good and FairCondition

No deficiencies recordedDeficiency

InspectedSTAIRS/RAMPS: EXTERIOR

InspectedBUILDING CHEEK/FLANK WALLS

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedRAILINGS

Condition 4- Between Fair and Poor

RUST - MAJORDeficiency

Page 12 of 33 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 13: NYC Department of Education Building Condition Assessment ...Custodian Jose Medina Fireman Pete Perrolas Building Square Footage 83,000 Comments on the Area (Square Feet) None Comments

NYC Department of Education

Building Condition Assessment Survey 2018-2019

M144Architectural Inspection

Question Response

EXTERIOR

STAIRS/RAMPS: EXTERIOR

RAILINGS

Deficiency Location/Instance

20Deficiency Quantity

Quantity Uom L.F.

Potential Action REPLACE

PRIORITY 4Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Main Entrance

Violations No violations recorded

InspectedSTAIRS/RAMPS

Condition 3- Fair

CONCRETE:CRACKS/SPALLING - MINORDeficiency

Deficiency Location/Instance

10Deficiency Quantity

Quantity Uom S.F.

Potential Action REPAIR

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Adjacent to the main entrance

Violations No violations recorded

InspectedWINDOWS

9,000Replacement Quantity

Replacement Uom S.F.

InspectedEXTERIOR GUARDS

Condition 3- Fair

DETERIORATED/TORN-OUT/MISSINGDeficiency

Page 13 of 33 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 14: NYC Department of Education Building Condition Assessment ...Custodian Jose Medina Fireman Pete Perrolas Building Square Footage 83,000 Comments on the Area (Square Feet) None Comments

NYC Department of Education

Building Condition Assessment Survey 2018-2019

M144Architectural Inspection

Question Response

EXTERIOR

WINDOWS

EXTERIOR GUARDS

Roof Plan Reference

Elevation

30Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Facade A

Violations No violations recorded

InspectedLINTELS

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedWINDOWS

Material Type(s) Aluminum, Steel

Instance on Aluminum - Double Hung:All Facades Inspected

3- FairInstance Condition

Instance Quantity 9,000

Instance Quantity Uom S.F.

Installation Year 1999

Source of Installation Year Documented

ALUMINUM - DOUBLE HUNG:DETERIORATEDDeficiency

Roof Plan Reference

Page 14 of 33 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 15: NYC Department of Education Building Condition Assessment ...Custodian Jose Medina Fireman Pete Perrolas Building Square Footage 83,000 Comments on the Area (Square Feet) None Comments

NYC Department of Education

Building Condition Assessment Survey 2018-2019

M144Architectural Inspection

Question Response

EXTERIOR

WINDOWS

WINDOWS

Elevation

Elevation Reference Facade A

200Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE WINDOW

PRIORITY 4Urgency of Action

LEVEL 2Purpose of Action

Violations No violations recorded

INTERIOR Inspected

AUDITORIUM

Instance on 1st Floor Inspected

Ceiling

Instance on 1st Floor Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Door(s)

Instance on 1st Floor Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Fixed H/C Lift

Instance on 1st Floor Does not exist

Fixed Seating

Instance on 1st Floor Inspected

2- Between Good and FairInstance Condition

DAMAGED/BROKEN/INOPERABLEDeficiency

Total Seating (434) - G/6,9, N/14, and R/3Deficiency Location/Instance

4Deficiency Quantity

Quantity Uom EACH

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Seat R/3

Page 15 of 33 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 16: NYC Department of Education Building Condition Assessment ...Custodian Jose Medina Fireman Pete Perrolas Building Square Footage 83,000 Comments on the Area (Square Feet) None Comments

NYC Department of Education

Building Condition Assessment Survey 2018-2019

M144Architectural Inspection

Question Response

INTERIOR

AUDITORIUM

Fixed Seating

Deficiency Photo 2

Seat G/6

Violations No violations recorded

Floor Finish

Instance on 1st Floor Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Sliding-folding Partition

Instance on 1st Floor Does not exist

Stage

Instance on 1st Floor Inspected

Stage

Instance on 1st Floor Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Stage Curtain Rigging

Instance on 1st Floor Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Stage Curtains

Instance on 1st Floor Inspected

1- GoodInstance Condition

No deficiencies recordedDeficiency

Walls

Instance on 1st Floor Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Window Curtains/Shades/Blinds

Instance on 1st Floor Does not exist

CAFETERIA

Instance on 1st Floor Inspected

Ceiling

Instance on 1st Floor Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Door(s)

Instance on 1st Floor Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Fixed Equipment

Instance on 1st Floor Does not exist

Floor Finish

Instance on 1st Floor Inspected

2- Between Good and FairInstance Condition

Page 16 of 33 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 17: NYC Department of Education Building Condition Assessment ...Custodian Jose Medina Fireman Pete Perrolas Building Square Footage 83,000 Comments on the Area (Square Feet) None Comments

NYC Department of Education

Building Condition Assessment Survey 2018-2019

M144Architectural Inspection

Question Response

INTERIOR

CAFETERIA

Floor Finish

No deficiencies recordedDeficiency

Sliding-folding Partition

Instance on 1st Floor Does not exist

Stage

Instance on 1st Floor Does not exist

Walls

Instance on 1st Floor Inspected

2- Between Good and FairInstance Condition

GLAZED BLOCK:CRACKS/SPALLINGDeficiency

Window near ServeryDeficiency Location/Instance

10Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Window near Servery

Violations No violations recorded

Window Curtains/Shades/Blinds

Instance on 1st Floor Does not exist

InspectedCLASSROOMS/CORRIDORS/ADMIN SPACES

InspectedCeiling

Condition 2- Between Good and Fair

ACOUSTIC TILES ON PLASTER:DAMAGED/MISSINGDeficiency

At Corridor near Room 101, 120, 302 and 314Deficiency Location/Instance

50Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

At Corridor near Room 101

Violations No violations recorded

InspectedDoor(s)

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedFloor Finish

Condition 2- Between Good and Fair

Page 17 of 33 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 18: NYC Department of Education Building Condition Assessment ...Custodian Jose Medina Fireman Pete Perrolas Building Square Footage 83,000 Comments on the Area (Square Feet) None Comments

NYC Department of Education

Building Condition Assessment Survey 2018-2019

M144Architectural Inspection

Question Response

INTERIOR

CLASSROOMS/CORRIDORS/ADMIN SPACES

Floor Finish

VINYL TILES:BROKEN/DETERIORATED/MISSING TILESDeficiency

Room 225, At Corridor near Stair A/2Deficiency Location/Instance

20Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Room 225

Deficiency Photo 2

At Corridor near Stair A/2

Violations No violations recorded

VINYL TILES:TRIPPING HAZARD - ELECTRICAL OUTLETDeficiency

Room 112Deficiency Location/Instance

10Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 5Urgency of Action

LEVEL 6Purpose of Action

Deficiency Photo 1

Room 112

Violations No violations recorded

InspectedSpecialties

InspectedClassroom Locker(s)

2- Between Good and FairCondition

No deficiencies recordedDeficiency

Does not existFixed Seating

InspectedWalls

Condition 2- Between Good and Fair

PLASTER:CRACKS/SPALLINGDeficiency

At Corridor near Stair A/2 and 3Deficiency Location/Instance

10Deficiency Quantity

Page 18 of 33 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 19: NYC Department of Education Building Condition Assessment ...Custodian Jose Medina Fireman Pete Perrolas Building Square Footage 83,000 Comments on the Area (Square Feet) None Comments

NYC Department of Education

Building Condition Assessment Survey 2018-2019

M144Architectural Inspection

Question Response

INTERIOR

CLASSROOMS/CORRIDORS/ADMIN SPACES

Walls

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

At Corridor near Room A/3

Violations No violations recorded

PLASTER:CRACKS/SPALLING - ACTIVE LEAKDeficiency

Rooms 118 and 120Deficiency Location/Instance

10Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 5Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Room 120

Violations No violations recorded

GYMNASIUM

Instance on 1st Floor Inspected

Ceiling

Instance on 1st Floor Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Door(s)

Instance on 1st Floor Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Fixed Equipment

Instance on 1st Floor Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Floor Finish

Instance on 1st Floor Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Seating

Instance on 1st Floor Inspected

2- Between Good and FairInstance Condition

Page 19 of 33 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 20: NYC Department of Education Building Condition Assessment ...Custodian Jose Medina Fireman Pete Perrolas Building Square Footage 83,000 Comments on the Area (Square Feet) None Comments

NYC Department of Education

Building Condition Assessment Survey 2018-2019

M144Architectural Inspection

Question Response

INTERIOR

GYMNASIUM

Seating

No deficiencies recordedDeficiency

Sliding-folding Partition

Instance on 1st Floor Does not exist

Stage

Instance on 1st Floor Does not exist

Walls

Instance on 1st Floor Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Window Curtains/Shades/Blinds

Instance on 1st Floor Does not exist

InspectedINTERIOR DOOR HARDWARE

Condition 3- Fair

No deficiencies recordedDeficiency

InspectedINTERIOR GUARDS

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

KITCHEN

Instance on 1st Floor Inspected

Ceiling

Instance on 1st Floor Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Door(s)

Instance on 1st Floor Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Floor Finish

Instance on 1st Floor Inspected

3- FairInstance Condition

CERAMIC TILE:BROKEN/MISSING TILESDeficiency

Near oven and sinkDeficiency Location/Instance

40Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Near oven

Page 20 of 33 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 21: NYC Department of Education Building Condition Assessment ...Custodian Jose Medina Fireman Pete Perrolas Building Square Footage 83,000 Comments on the Area (Square Feet) None Comments

NYC Department of Education

Building Condition Assessment Survey 2018-2019

M144Architectural Inspection

Question Response

INTERIOR

KITCHEN

Floor Finish

Deficiency Photo 2

Near Sink

Violations No violations recorded

Walls

Instance on 1st Floor Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

LIBRARY

Instance on Room 201 Inspected

Built-in Furnishing

Instance on Room 201 Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Ceiling

Instance on Room 201 Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Door(s)

Instance on Room 201 Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Floor Finish

Instance on Room 201 Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Walls

Instance on Room 201 Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Does not existLOCKER ROOM

Does not existMULTI-PURPOSE ROOM

Does not existPOOLS

Does not existSCIENCE DEMO ROOM

Does not existSCIENCE LAB

Does not existSCIENCE PREP ROOM

SHOWER ROOM

Instance on 2nd Floor - Girls Inspected

YesAlternative Use

Instance on 1st Floor - Boys Inspected

YesAlternative Use

Ceiling

Instance on 2nd Floor - Girls Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Page 21 of 33 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 22: NYC Department of Education Building Condition Assessment ...Custodian Jose Medina Fireman Pete Perrolas Building Square Footage 83,000 Comments on the Area (Square Feet) None Comments

NYC Department of Education

Building Condition Assessment Survey 2018-2019

M144Architectural Inspection

Question Response

INTERIOR

SHOWER ROOM

Ceiling

Instance on 1st Floor - Boys Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Door(s)

Instance on 2nd Floor - Girls Does not exist

Instance on 1st Floor - Boys Does not exist

Floor Finish

Instance on 2nd Floor - Girls Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Instance on 1st Floor - Boys Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Walls

Instance on 2nd Floor - Girls Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Instance on 1st Floor - Boys Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

InspectedSTAIRS/RAMPS: INTERIOR

Do Letter Stair Signs Exist? 1

InspectedCeiling

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedDoor(s)

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

Does not existPartition

InspectedRailings

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedStairs and Landings

Condition 2- Between Good and Fair

CONCRETE:CRACKS/SPALLING - MAJORDeficiency

Stair A/BulkheadDeficiency Location/Instance

10Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Stair A/Bulkhead

Violations No violations recorded

Page 22 of 33 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 23: NYC Department of Education Building Condition Assessment ...Custodian Jose Medina Fireman Pete Perrolas Building Square Footage 83,000 Comments on the Area (Square Feet) None Comments

NYC Department of Education

Building Condition Assessment Survey 2018-2019

M144Architectural Inspection

Question Response

INTERIOR

STAIRS/RAMPS: INTERIOR

Stairs and Landings

VINYL TILES:DETERIORATED SUBSTRATEDeficiency

Stair B/2, D/2, and 3Deficiency Location/Instance

30Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Stair B/2

Violations No violations recorded

InspectedWalls

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedSTRUCTURAL

InspectedCOLUMNS/BEAMS/BEARING WALLS

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedFLOOR STRUCTURE

Condition 3- Fair

CONCRETE SLAB ON GRADE:MINOR CRACKSDeficiency

BasementDeficiency Location/Instance

60Deficiency Quantity

Quantity Uom S.F.

Potential Action REPAIR

PRIORITY 3Urgency of Action

LEVEL 5Purpose of Action

Deficiency Photo 1

Crawl Space shown, also in Boiler Room and Gas Meter Room

Violations No violations recorded

InspectedFOUNDATION WALLS

Material Type(s) Concrete

Condition 3- Fair

CONCRETE:CRACKED/SPALLED/REINFORCEMENT

EXPOSED

Deficiency

BasementDeficiency Location/Instance

30Deficiency Quantity

Quantity Uom S.F.

Potential Action REPAIR

Page 23 of 33 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 24: NYC Department of Education Building Condition Assessment ...Custodian Jose Medina Fireman Pete Perrolas Building Square Footage 83,000 Comments on the Area (Square Feet) None Comments

NYC Department of Education

Building Condition Assessment Survey 2018-2019

M144Architectural Inspection

Question Response

INTERIOR

STRUCTURAL

FOUNDATION WALLS

PRIORITY 3Urgency of Action

LEVEL 5Purpose of Action

Deficiency Photo 1

Boiler Room

Violations No violations recorded

InspectedROOF STRUCTURE

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedVAULTS-BUNKERS

InspectedFoundation Walls

2- Between Good and FairCondition

No deficiencies recordedDeficiency

InspectedSlab Structure

2- Between Good and FairCondition

No deficiencies recordedDeficiency

InspectedVault/Ash Hoist Doors and Framing

5- PoorCondition

DETERIORATED/DAMAGED VAULT/ASH HOIST DOORS

AND FRAMING

Deficiency

Basement VaultDeficiency Location/Instance

2Deficiency Quantity

Quantity Uom EACH

Potential Action REPLACE

PRIORITY 4Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Sidewalk Elevator Vault

Violations No violations recorded

InspectedTOILET ROOMS - STAFF

InspectedCeiling

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedDoor(s)

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedFloor Finish

Condition 2- Between Good and Fair

Page 24 of 33 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 25: NYC Department of Education Building Condition Assessment ...Custodian Jose Medina Fireman Pete Perrolas Building Square Footage 83,000 Comments on the Area (Square Feet) None Comments

NYC Department of Education

Building Condition Assessment Survey 2018-2019

M144Architectural Inspection

Question Response

INTERIOR

TOILET ROOMS - STAFF

Floor Finish

No deficiencies recordedDeficiency

InspectedStalls

Condition 4- Between Fair and Poor

RUST - MAJORDeficiency

Room 102Deficiency Location/Instance

1Deficiency Quantity

Quantity Uom EACH

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Room 102

Violations No violations recorded

InspectedWalls

Condition 2- Between Good and Fair

CERAMIC TILE:BROKEN/ MISSINGDeficiency

Room 205 and Toilet Room within GymnasiumDeficiency Location/Instance

10Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Room 205

Violations No violations recorded

PLASTER:CRACKS/SPALLINGDeficiency

1st Floor - Locker Room/Office, Gym OfficeDeficiency Location/Instance

10Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Page 25 of 33 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 26: NYC Department of Education Building Condition Assessment ...Custodian Jose Medina Fireman Pete Perrolas Building Square Footage 83,000 Comments on the Area (Square Feet) None Comments

NYC Department of Education

Building Condition Assessment Survey 2018-2019

M144Architectural Inspection

Question Response

INTERIOR

TOILET ROOMS - STAFF

Walls

Deficiency Photo 1

1st Floor - Locker Room/Office

Violations No violations recorded

InspectedTOILET ROOMS - STUDENTS

InspectedCeiling

Condition 2- Between Good and Fair

PLASTER:CRACKS/SPALLINGDeficiency

Room 213Deficiency Location/Instance

20Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Room 213

Violations No violations recorded

InspectedDoor(s)

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedFloor Finish

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedStalls

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedWalls

Condition 2- Between Good and Fair

CERAMIC TILE:BROKEN/ MISSINGDeficiency

Rooms 115, 219, 311Deficiency Location/Instance

20Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Page 26 of 33 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 27: NYC Department of Education Building Condition Assessment ...Custodian Jose Medina Fireman Pete Perrolas Building Square Footage 83,000 Comments on the Area (Square Feet) None Comments

NYC Department of Education

Building Condition Assessment Survey 2018-2019

M144Architectural Inspection

Question Response

INTERIOR

TOILET ROOMS - STUDENTS

Walls

Deficiency Photo 1

Room 311

Violations No violations recorded

LIFE SAFETY Inspected

Does not existF.D. HOLDING AREA

Does not existSTEEL STAIRS

SITE Inspected

Does not existCONTAINERIZATION

InspectedDRAINAGE SYSTEM FOR ASPHALT

InspectedCatch Basins/Manhole - Surrounded by Asphalt

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

Does not existCulverts - Asphalt Covering

InspectedDRAINAGE SYSTEM FOR CONCRETE

InspectedCatch Basins/Manhole - Surrounded by Concrete

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

Does not existCulverts - Concrete Covering

Does not existDRAINAGE SYSTEM FOR SOIL

InspectedDRINKING FOUNTAINS

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedFENCES

Condition 3- Fair

CONCRETE CURB:DAMAGED/DETERIORATEDDeficiency

Along West 121st StreetDeficiency Location/Instance

30Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Along West 121st Street

Violations No violations recorded

WROUGHT IRON:DAMAGED/DETERIORATEDDeficiency

Along West 122nd StreetDeficiency Location/Instance

40Deficiency Quantity

Page 27 of 33 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 28: NYC Department of Education Building Condition Assessment ...Custodian Jose Medina Fireman Pete Perrolas Building Square Footage 83,000 Comments on the Area (Square Feet) None Comments

NYC Department of Education

Building Condition Assessment Survey 2018-2019

M144Architectural Inspection

Question Response

SITE

FENCES

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Along West 122nd Street

Violations No violations recorded

Does not existIRRIGATION SYSTEM

InspectedPAVING

InspectedDOT Sidewalk

Does not existAsphalt

InspectedConcrete

4- Between Fair and PoorCondition

DAMAGED/DETERIORATED/MISSING SECTIONSDeficiency

Along West 122nd StreetDeficiency Location/Instance

550Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Along West 122nd Street

Deficiency Photo 2

Along West 121st Street

Violations No violations recorded

DAMAGED CURBSDeficiency

Along West 122nd StreetDeficiency Location/Instance

5Deficiency Quantity

Quantity Uom L.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Page 28 of 33 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 29: NYC Department of Education Building Condition Assessment ...Custodian Jose Medina Fireman Pete Perrolas Building Square Footage 83,000 Comments on the Area (Square Feet) None Comments

NYC Department of Education

Building Condition Assessment Survey 2018-2019

M144Architectural Inspection

Question Response

SITE

PAVING

DOT Sidewalk

Concrete

Deficiency Photo 1

Along West 122nd Street

Violations No violations recorded

HEAVINGDeficiency

Along West 121st Street and 122nd StreetDeficiency Location/Instance

125Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Along West 122nd Street

Deficiency Photo 2

Along West 121st Street

Violations No violations recorded

Does not existPavers

InspectedSite Sidewalks & Walkways

Does not existAsphalt

InspectedConcrete

2- Between Good and FairCondition

DAMAGED/DETERIORATED/MISSING SECTIONSDeficiency

Along West 121st StreetDeficiency Location/Instance

25Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Page 29 of 33 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 30: NYC Department of Education Building Condition Assessment ...Custodian Jose Medina Fireman Pete Perrolas Building Square Footage 83,000 Comments on the Area (Square Feet) None Comments

NYC Department of Education

Building Condition Assessment Survey 2018-2019

M144Architectural Inspection

Question Response

SITE

PAVING

Site Sidewalks & Walkways

Concrete

Deficiency Photo 1

Along West 121st Street

Violations No violations recorded

Does not existPavers

InspectedStudent Non-Use

Gravel Exists? No

Does not existAsphalt

InspectedConcrete

2- Between Good and FairCondition

No deficiencies recordedDeficiency

Does not existPavers

InspectedStudent Use

Gravel Exists? No

InspectedAsphalt

3- FairCondition

CRACKS - MAJORDeficiency

Center of East Schoolyard, West side of East SchoolyardDeficiency Location/Instance

300Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

West side of East Schoolyard

Deficiency Photo 2

Center of East Schoolyard

Violations No violations recorded

InspectedConcrete

3- FairCondition

DAMAGED/DETERIORATED/MISSING SECTIONSDeficiency

EntranceDeficiency Location/Instance

Page 30 of 33 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 31: NYC Department of Education Building Condition Assessment ...Custodian Jose Medina Fireman Pete Perrolas Building Square Footage 83,000 Comments on the Area (Square Feet) None Comments

NYC Department of Education

Building Condition Assessment Survey 2018-2019

M144Architectural Inspection

Question Response

SITE

PAVING

Student Use

Concrete

50Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Entrance

Violations No violations recorded

InspectedPavers

2- Between Good and FairCondition

No deficiencies recordedDeficiency

InspectedPLAYGROUNDS

South of West SchoolyardInstance

East SchoolyardInstance

West SchoolyardInstance

Benches

Instance on South of West Schoolyard Does not exist

Instance on East Schoolyard Does not exist

Instance on West Schoolyard Does not exist

Fence

Instance on South of West Schoolyard Does not exist

Instance on East Schoolyard Does not exist

Instance on West Schoolyard Does not exist

Pavement

Instance on South of West Schoolyard Does not exist

Instance on East Schoolyard Does not exist

Instance on West Schoolyard Does not exist

Play Equipment

Instance on South of West Schoolyard Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Instance on East Schoolyard Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Instance on West Schoolyard Inspected

3- FairInstance Condition

BROKEN/DETERIORATED/MISSINGDeficiency

Middle of playgroundDeficiency Location/Instance

1Deficiency Quantity

Quantity Uom EACH

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Page 31 of 33 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 32: NYC Department of Education Building Condition Assessment ...Custodian Jose Medina Fireman Pete Perrolas Building Square Footage 83,000 Comments on the Area (Square Feet) None Comments

NYC Department of Education

Building Condition Assessment Survey 2018-2019

M144Architectural Inspection

Question Response

SITE

PLAYGROUNDS

Play Equipment

Deficiency Photo 1

Middle of playground

Violations No violations recorded

Safety Surfacing

Instance on South of West Schoolyard Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Instance on East Schoolyard Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Instance on West Schoolyard Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Unpaved Area

Instance on South of West Schoolyard Does not exist

Instance on East Schoolyard Does not exist

Instance on West Schoolyard Does not exist

InspectedPLAYING SURFACE

InspectedPlaying Field

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

East SchoolyardInstance

Does not existRunning Track

InspectedRETAINING WALLS

Condition 2- Between Good and Fair

Are there any Retaining Walls 6' OR higher facing public street/sidewalk? No

No deficiencies recordedDeficiency

InspectedSEATING

InspectedBenches

InspectedConcrete

2- Between Good and FairCondition

No deficiencies recordedDeficiency

InspectedMetal/Wood/Plastic

2- Between Good and FairCondition

No deficiencies recordedDeficiency

Does not existBleachers

InspectedSITE WALLS (NOT RETAINING WALLS)

Condition 2- Between Good and Fair

BRICK:CRACKS/SPALLING - MAJORDeficiency

West Schoolyard near center of perimeter fenceDeficiency Location/Instance

5Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

Page 32 of 33 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 33: NYC Department of Education Building Condition Assessment ...Custodian Jose Medina Fireman Pete Perrolas Building Square Footage 83,000 Comments on the Area (Square Feet) None Comments

NYC Department of Education

Building Condition Assessment Survey 2018-2019

M144Architectural Inspection

Question Response

SITE

SITE WALLS (NOT RETAINING WALLS)

LEVEL 2Purpose of Action

Deficiency Photo 1

West Schoolyard near center of perimeter fence

Violations No violations recorded

InspectedSTAIRS/RAMPS: EXTERIOR

InspectedRailings

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedSite Cheek/flank Walls

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedStairs/ramps

Condition 2- Between Good and Fair

STONE:CRACKS/SPALLINGDeficiency

East and West of West SchoolyardDeficiency Location/Instance

10Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

East of West Schoolyard

Violations No violations recorded

Page 33 of 33 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)