T Check Valve Circulator Pressure Relief Valve Expansion Tank Aquastat Full-port Ball Valve Mixing Valve Storage Vessel DHW Circulator w/Aquastat & Check Valve These drawing are intended as a guide only and not as a replacement for professionally engineered project drawings. These concept system drawings do not imply compliance with local building codes. Actual installations may vary depending on installation location & parameters and it must be done in accordance with all local building codes. Verify with Guide Only NPE Series Application Drawings C H G NPE-240S C H G NPE-210S C H G NPE-180S 20 Goodyear Irvine, CA 92618 800-519-8794 www.Navien.com

NPE Series Application Drawings - Navien

  • Upload
    others

  • View
    20

  • Download
    0

Embed Size (px)

Citation preview

Page 1: NPE Series Application Drawings - Navien

T

Check Valve Circulator

PressureReliefValve Expansion

Tank

AquastatFull-portBall Valve

MixingValve

StorageVessel

DHW Circulatorw/Aquastat & Check Valve

These drawing are intended as a guide only and not as a replacement for professionally engineered project drawings. These concept system drawings do not imply compliance with local building codes. Actual installations may vary depending on installation location & parameters and it must be done in accordance with all local building codes. Verify with

Guide Only

NPE Series Application Drawings

CHG

NPE-240S

CHG

NPE-210S

CHG

NPE-180S

20 GoodyearIrvine, CA 92618

800-519-8794www.Navien.com

Page 2: NPE Series Application Drawings - Navien

20 Goodyear

Irvine, CA 92618

800-519-8794

www.Navien.com T

Check Valve Circulator

Pressure

Relief

Valve Expansion

Tank

AquastatFull-port

Ball Valve

Mixing

Valve

Storage

Vessel

DHW Circulator

w/Aquastat & Check Valve

This drawing is intended only as a guide and not as a replacement for professionally engineered project drawings.

This concept system drawing does not imply compliance with local building codes. Actual installation may vary

depending on installation location & parameters and it must be done in accordance to all local building codes.

Verify with local building officials before commencement of system installation.

Drawn By: B. Fenske NPE-S-1-BF02 August 1, 2013

One NPE-S Tankless

(Includes NPE-A, Internal Circulation Mode)

NPE-S Series Tankless Water Heater

CHG

Gas

Domestic Cold Water

CondensateDomestic Hot Water

Page 3: NPE Series Application Drawings - Navien

20 Goodyear

Irvine, CA 92618

800-519-8794

www.Navien.com T

Check Valve Circulator

Pressure

Relief

Valve Expansion

Tank

AquastatFull-port

Ball Valve

Mixing

Valve

Storage

Vessel

DHW Circulator

w/Aquastat & Check Valve

This drawing is intended only as a guide and not as a replacement for professionally engineered project drawings.

This concept system drawing does not imply compliance with local building codes. Actual installation may vary

depending on installation location & parameters and it must be done in accordance to all local building codes.

Verify with local building officials before commencement of system installation.

Drawn By: B. Fenske NPE-S-2-I-BF02 August 1, 2013

Two NPE-S Tankless

(Includes NPE-A Internal Circulation Mode)

Recommended Pipe Size/Heater Count 1 Unit - ¾” 2 Units - 1" 3 Units - 1-¼” 4 to 5 Units - 1-½” 6 to 8 Units - 2" 9 to 14 Units - 2-½” 15 to 16 Units - 3"

NPE-S Series Tankless Water Heater

CHG

Gas

Domestic Cold Water

Condensate

CHG

Domestic Hot Water

Communication

Cable

Page 4: NPE Series Application Drawings - Navien

20 Goodyear

Irvine, CA 92618

800-519-8794

www.Navien.com T

Check Valve Circulator

Pressure

Relief

Valve Expansion

Tank

AquastatFull-port

Ball Valve

Mixing

Valve

Storage

Vessel

DHW Circulator

w/Aquastat & Check Valve

This drawing is intended only as a guide and not as a replacement for professionally engineered project drawings.

This concept system drawing does not imply compliance with local building codes. Actual installation may vary

depending on installation location & parameters and it must be done in accordance to all local building codes.

Verify with local building officials before commencement of system installation.

Drawn By: B. Fenske NPE-S-2LT-I-BF02 August 1, 2013

Two NPE-S Tankless

With Two Temperature Operation

Recommended Pipe Size/Heater Count 1 Unit - ¾” 2 Units - 1" 3 Units - 1-¼” 4 to 5 Units - 1-½” 6 to 8 Units - 2" 9 to 14 Units - 2-½” 15 to 16 Units - 3"

NPE-S Series Tankless Water Heater

CHG

Gas

Domestic Cold Water

Condensate

CHG

High Temp

Domestic Hot Water

Communication

Cable

Low Temp

Domestic Hot Water

M

CH

Page 5: NPE Series Application Drawings - Navien

20 Goodyear

Irvine, CA 92618

800-519-8794

www.Navien.com T

Check Valve Circulator

Pressure

Relief

Valve Expansion

Tank

AquastatFull-port

Ball Valve

Mixing

Valve

Storage

Vessel

DHW Circulator

w/Aquastat & Check Valve

This drawing is intended only as a guide and not as a replacement for professionally engineered project drawings.

This concept system drawing does not imply compliance with local building codes. Actual installation may vary

depending on installation location & parameters and it must be done in accordance to all local building codes.

Verify with local building officials before commencement of system installation.

Drawn By: B. Fenske NPE-S-3-I-BF02 August 1, 2013

Three NPE-S Tankless

(Includes NPE-A Internal Circulation Mode)

Recommended Pipe Size/Heater Count 1 Unit - ¾” 2 Units - 1" 3 Units - 1-¼” 4 to 5 Units - 1-½” 6 to 8 Units - 2" 9 to 14 Units - 2-½” 15 to 16 Units - 3"

NPE-S Series Tankless Water Heater

CHG

Gas

Domestic Cold Water

Condensate

CHG

Domestic Hot Water

Communication

Cable

CHG

Communication

Cable

Page 6: NPE Series Application Drawings - Navien

20 Goodyear

Irvine, CA 92618

800-519-8794

www.Navien.com T

Check Valve Circulator

Pressure

Relief

Valve Expansion

Tank

AquastatFull-port

Ball Valve

Mixing

Valve

Storage

Vessel

DHW Circulator

w/Aquastat & Check Valve

This drawing is intended only as a guide and not as a replacement for professionally engineered project drawings.

This concept system drawing does not imply compliance with local building codes. Actual installation may vary

depending on installation location & parameters and it must be done in accordance to all local building codes.

Verify with local building officials before commencement of system installation.

Drawn By: B. Fenske NPE-S-4-I-BF02 August 1, 2013

Four NPE-S Tankless

(Includes NPE-A, Internal Circulation Mode)

Recommended Pipe Size/Heater Count 1 Unit - ¾” 2 Units - 1" 3 Units - 1-¼” 4 to 5 Units - 1-½” 6 to 8 Units - 2" 9 to 14 Units - 2-½” 15 to 16 Units - 3"

NPE-S Series Tankless Water Heater

CHG

Gas

Domestic Cold Water

Condensate

CHG

Domestic Hot Water

Communication

Cable

CHG

Communication

Cable

CHG

Communication

Cable

Page 7: NPE Series Application Drawings - Navien

20 Goodyear

Irvine, CA 92618

800-519-8794

www.Navien.com T

Check Valve Circulator

Pressure

Relief

Valve Expansion

Tank

AquastatFull-port

Ball Valve

Mixing

Valve

Storage

Vessel

DHW Circulator

w/Aquastat & Check Valve

This drawing is intended only as a guide and not as a replacement for professionally engineered project drawings.

This concept system drawing does not imply compliance with local building codes. Actual installation may vary

depending on installation location & parameters and it must be done in accordance to all local building codes.

Verify with local building officials before commencement of system installation.

Drawn By: B. Fenske NPE-S-5-I-BF02 August 1, 2013

Five NPE-S Tankless

(Includes NPE-A, Internal Circulation Mode)

Recommended Pipe Size/Heater Count 1 Unit - ¾” 2 Units - 1" 3 Units - 1-¼” 4 to 5 Units - 1-½” 6 to 8 Units - 2" 9 to 14 Units - 2-½” 15 to 16 Units - 3"

NPE-S Series Tankless Water Heater

CHG

Gas

Domestic Cold Water

Condensate

CHG

Domestic

Hot Water

Communication

Cable

CHG

Communication

Cable

CHG

Communication

Cable

CHG

Communication

Cable

Page 8: NPE Series Application Drawings - Navien

20 Goodyear

Irvine, CA 92618

800-519-8794

www.Navien.com T

Check Valve Circulator

Pressure

Relief

Valve Expansion

Tank

AquastatFull-port

Ball Valve

Mixing

Valve

Storage

Vessel

DHW Circulator

w/Aquastat & Check Valve

This drawing is intended only as a guide and not as a replacement for professionally engineered project drawings.

This concept system drawing does not imply compliance with local building codes. Actual installation may vary

depending on installation location & parameters and it must be done in accordance to all local building codes.

Verify with local building officials before commencement of system installation.

Drawn By: B. Fenske NPE-S-6P-I-BF02 August 1, 2013

Six Plus NPE-S Tankless

(Includes NPE-A, Internal Circulation Mode)

Recommended Pipe Size/Heater Count 1 Unit - ¾” 2 Units - 1" 3 Units - 1-¼” 4 to 5 Units - 1-½” 6 to 8 Units - 2" 9 to 14 Units - 2-½” 15 to 16 Units - 3"

NPE-S Series Tankless Water Heater

CHG

Gas

Domestic

Cold Water

Condensate

CHG

Domestic

Hot Water

Communication

Cable

CHG

Communication

Cable

CHG

Communication

Cable

CHG

Communication

CableCommunication

Cable

CHG

Unit 1 Unit 2 Unit 3 Unit 4 Unit 5 Unit 6 - 16. . . . .

Page 9: NPE Series Application Drawings - Navien

20 Goodyear

Irvine, CA 92618

800-519-8794

www.Navien.com T

Check Valve Circulator

Pressure

Relief

Valve Expansion

Tank

AquastatFull-port

Ball Valve

Mixing

Valve

Storage

Vessel

DHW Circulator

w/Aquastat & Check Valve

This drawing is intended only as a guide and not as a replacement for professionally engineered project drawings.

This concept system drawing does not imply compliance with local building codes. Actual installation may vary

depending on installation location & parameters and it must be done in accordance to all local building codes.

Verify with local building officials before commencement of system installation.

Drawn By: B. Fenske NPE-A-10-E-BF02 August 1, 2013

Ten NPE-S Tankless

(Includes NPE-A, Internal Circulation Mode)

Alternative Mounting Shown

Recommended Pipe Size/Heater Count 1 Unit - ¾” 2 Units - 1" 3 Units - 1-¼” 4 to 5 Units - 1-½” 6 to 8 Units - 2" 9 to 14 Units - 2-½” 15 to 16 Units - 3"

NPE-S Series Tankless Water Heater

Gas

Domestic Cold

Water

Condensate

Domestic Hot Water

Page 10: NPE Series Application Drawings - Navien

20 Goodyear

Irvine, CA 92618

800-519-8794

www.Navien.com T

Check Valve Circulator

Pressure

Relief

Valve Expansion

Tank

AquastatFull-port

Ball Valve

Mixing

Valve

Storage

Vessel

DHW Circulator

w/Aquastat & Check Valve

This drawing is intended only as a guide and not as a replacement for professionally engineered project drawings.

This concept system drawing does not imply compliance with local building codes. Actual installation may vary

depending on installation location & parameters and it must be done in accordance to all local building codes.

Verify with local building officials before commencement of system installation.

Drawn By: B. Fenske NPE-S-1-PW-EC-BF02 August 1, 2013

One NPE-S Tankless

Using External Pump for Recirculation

with Part #30011612A External Pump Wire

NPE-S Series Tankless Water Heater

Notes:

1. Use Navien Cord P #30011612A

2. Set DIP Switches on Integrated Controller

#1 – OFF, #2 – OFF, #3 – ON

3. Select External Circulator Performance

to be 2 GPM Minimum, 4 GPM Maximum based

on 11 Psi drop @ 4 GPM at tankless

* Refer to NPE Installation Manual for further details

CHG

Gas

Domestic Cold Water

CondensateDomestic Hot Water

Page 11: NPE Series Application Drawings - Navien

20 Goodyear

Irvine, CA 92618

800-519-8794

www.Navien.com T

Check Valve Circulator

Pressure

Relief

Valve Expansion

Tank

AquastatFull-port

Ball Valve

Mixing

Valve

Storage

Vessel

DHW Circulator

w/Aquastat & Check Valve

This drawing is intended only as a guide and not as a replacement for professionally engineered project drawings.

This concept system drawing does not imply compliance with local building codes. Actual installation may vary

depending on installation location & parameters and it must be done in accordance to all local building codes.

Verify with local building officials before commencement of system installation.

One NPE-S with Storage

to meet Flow/Temp Rise Requirements

Drawn By: B. Fenske August 1, 2013NPE-S-1-ST-BF02

NPE-S Series Tankless Water Heater

Domestic Cold Water

Insulated

Storage

Tank

T

¾” Min

Domestic Hot Water to Fixtures

Optional

DHW

Recirculation

3 or 4

Tap

Tank

(A) Tankless Circulator

(Bronze or S.S) Selected Shall

be 4 GPM Max @ 23' Total Head (10 PSI)

+ pipe, valves, fittings & tank.

(A)

GasCondensate

CHG

Page 12: NPE Series Application Drawings - Navien

20 Goodyear

Irvine, CA 92618

800-519-8794

www.Navien.com T

Check Valve Circulator

Pressure

Relief

Valve Expansion

Tank

AquastatFull-port

Ball Valve

Mixing

Valve

Storage

Vessel

DHW Circulator

w/Aquastat & Check Valve

This drawing is intended only as a guide and not as a replacement for professionally engineered project drawings.

This concept system drawing does not imply compliance with local building codes. Actual installation may vary

depending on installation location & parameters and it must be done in accordance to all local building codes.

Verify with local building officials before commencement of system installation.

Two NPE-S with Storage

to meet Flow/Temp Rise Requirements

Drawn By: B. Fenske August 1, 2013NPE-S-2-ST-BF02

(A) Tankless Circulator

(Bronze or S.S) Selected Shall

be 8 GPM Max (4 Per Tankless)

@ 23' Total Head (10 PSI)

+ pipe, valves, fittings & tank.

(B) Install Circuit Setters to

Maintain Flow into Units @ 4

GPM Maximum

Recommended Pipe Size/Heater Count 1 Unit - ¾” 2 Units - 1" 3 Units - 1-¼” 4 to 5 Units - 1-½” 6 to 8 Units - 2" 9 to 14 Units - 2-½” 15 to 16 Units - 3"

NPE-S Series Tankless Water Heater

(A)Domestic Cold Water

Insulated

Storage

Tank

T

Domestic Hot Water to Fixtures

Optional

DHW

Recirculation

3 or 4

Tap

Tank

CHG

Gas

Condensate

CHG

Communication

Cable

(B) (B)

Page 13: NPE Series Application Drawings - Navien

20 Goodyear

Irvine, CA 92618

800-519-8794

www.Navien.com T

Check Valve Circulator

Pressure

Relief

Valve Expansion

Tank

AquastatFull-port

Ball Valve

Mixing

Valve

Storage

Vessel

DHW Circulator

w/Aquastat & Check Valve

This drawing is intended only as a guide and not as a replacement for professionally engineered project drawings.

This concept system drawing does not imply compliance with local building codes. Actual installation may vary

depending on installation location & parameters and it must be done in accordance to all local building codes.

Verify with local building officials before commencement of system installation.

Three NPE-S with Storage

to meet Flow/Temp Rise Requirements

Drawn By: B. Fenske August 1, 2013NPE-S-3-ST-BF02

(A) Tankless Circulator

(Bronze or S.S) Selected Shall be

12 GPM Max (4 Per Tankless) @

23' Total Head (10 PSI)

+ pipe, valves, fittings & tank.

(B) Install Circuit Setters to Maintain

Flow into Units @ 4 GPM Maximum

Recommended Pipe Size/Heater Count 1 Unit - ¾” 2 Units - 1" 3 Units - 1-¼” 4 to 5 Units - 1-½” 6 to 8 Units - 2" 9 to 14 Units - 2-½” 15 to 16 Units - 3"

NPE-S Series Tankless Water Heater

(A)Domestic Cold Water

Insulated

Storage

Tank

T

Domestic Hot Water to Fixtures

Optional

DHW

Recirculation

3 or 4

Tap

Tank

CHG

Gas

Condensate

CHG

Communication

Cable

CHG

Communication

Cable

(B) (B) (B)

Page 14: NPE Series Application Drawings - Navien

20 Goodyear

Irvine, CA 92618

800-519-8794

www.Navien.com T

Check Valve Circulator

Pressure

Relief

Valve Expansion

Tank

AquastatFull-port

Ball Valve

Mixing

Valve

Storage

Vessel

DHW Circulator

w/Aquastat & Check Valve

This drawing is intended only as a guide and not as a replacement for professionally engineered project drawings.

This concept system drawing does not imply compliance with local building codes. Actual installation may vary

depending on installation location & parameters and it must be done in accordance to all local building codes.

Verify with local building officials before commencement of system installation.

Four NPE-S with Storage

to meet Flow/Temp Rise Requirements

Drawn By: B. Fenske August 1, 2013NPE-S-4-ST-BF02

(A) Tankless Circulator

(Bronze or S.S) Selected Shall be

16 GPM Max (4 Per Tankless) @

23' Total Head (10 PSI)

+ pipe, valves, fittings & tank.

(B) Install Circuit Setters to

Maintain Flow into Units @ 4 GPM

Maximum

Recommended Pipe Size/Heater Count 1 Unit - ¾” 2 Units - 1" 3 Units - 1-¼” 4 to 5 Units - 1-½” 6 to 8 Units - 2" 9 to 14 Units - 2-½” 15 to 16 Units - 3"

NPE-S Series Tankless Water Heater

(A)

Domestic

Cold Water

Insulated

Storage

Tank

T

Domestic Hot Water to Fixtures

Optional

DHW

Recirculation

3 or 4

Tap

Tank

CHG

Gas

Condensate

CHG

Communication

Cable

CHG

Communication

Cable

CHG

Communication

Cable

(B) (B) (B) (B)

Page 15: NPE Series Application Drawings - Navien

20 Goodyear

Irvine, CA 92618

800-519-8794

www.Navien.com T

Check Valve Circulator

Pressure

Relief

Valve Expansion

Tank

AquastatFull-port

Ball Valve

Mixing

Valve

Storage

Vessel

DHW Circulator

w/Aquastat & Check Valve

This drawing is intended only as a guide and not as a replacement for professionally engineered project drawings.

This concept system drawing does not imply compliance with local building codes. Actual installation may vary

depending on installation location & parameters and it must be done in accordance to all local building codes.

Verify with local building officials before commencement of system installation.

Two NPE-S with Two Storage Tanks

to meet Flow/Temp Rise Requirements

Drawn By: B. Fenske August 1, 2013NPE-S-2-2ST-BF02

(A) Tankless Circulator

(Bronze or S.S) Selected Shall

be 8 GPM Max (4 Per Tankless)

@ 23' Total Head (10 PSI)

+ pipe, valves, fittings & tank.

(B) Install Circuit Setters to

Maintain Flow into Units @ 4

GPM Maximum

Recommended Pipe Size/Heater Count 1 Unit - ¾” 2 Units - 1" 3 Units - 1-¼” 4 to 5 Units - 1-½” 6 to 8 Units - 2" 9 to 14 Units - 2-½” 15 to 16 Units - 3"

NPE-S Series Tankless Water Heater

(A)Domestic Cold Water

Domestic Hot Water to Fixtures

CHG

Gas

Condensate

CHG

Communication

Cable

Insulated

Storage

Tank

Insulated

Storage

Tank

T T

Optional DHW Recirculation

(B) (B)

Page 16: NPE Series Application Drawings - Navien

20 Goodyear

Irvine, CA 92618

800-519-8794

www.Navien.com T

Check Valve Circulator

Pressure

Relief

Valve Expansion

Tank

AquastatFull-port

Ball Valve

Mixing

Valve

Storage

Vessel

DHW Circulator

w/Aquastat & Check Valve

This drawing is intended only as a guide and not as a replacement for professionally engineered project drawings.

This concept system drawing does not imply compliance with local building codes. Actual installation may vary

depending on installation location & parameters and it must be done in accordance to all local building codes.

Verify with local building officials before commencement of system installation.

Three NPE-S with Two Storage Tanks

to meet Flow/Temp Rise Requirements

Drawn By: B. Fenske August 1, 2013NPE-S-3-2ST-BF02

(A) Tankless Circulator

(Bronze or S.S) Selected Shall be

12 GPM Max (4 Per Tankless) @

23' Total Head (10 PSI)

+ pipe, valves, fittings & tank.

(B) Install Circuit Setters to

Maintain Flow into Units @ 4 GPM

Maximum

Recommended Pipe Size/Heater Count 1 Unit - ¾” 2 Units - 1" 3 Units - 1-¼” 4 to 5 Units - 1-½” 6 to 8 Units - 2" 9 to 14 Units - 2-½” 15 to 16 Units - 3"

NPE-S Series Tankless Water Heater

(A)Domestic Cold Water

Domestic Hot Water to Fixtures

CHG

Gas

Condensate

CHG

Communication

Cable

Insulated

Storage

Tank

Insulated

Storage

Tank

T T

Optional DHW Recirculation

CHG

Communication

Cable

(B) (B) (B)

Page 17: NPE Series Application Drawings - Navien

20 Goodyear

Irvine, CA 92618

800-519-8794

www.Navien.com T

Check Valve Circulator

Pressure

Relief

Valve Expansion

Tank

AquastatFull-port

Ball Valve

Mixing

Valve

Storage

Vessel

DHW Circulator

w/Aquastat & Check Valve

This drawing is intended only as a guide and not as a replacement for professionally engineered project drawings.

This concept system drawing does not imply compliance with local building codes. Actual installation may vary

depending on installation location & parameters and it must be done in accordance to all local building codes.

Verify with local building officials before commencement of system installation.

Four NPE-S with Two Storage Tanks

to meet Flow/Temp Rise Requirements

Drawn By: B. Fenske August 1, 2013NPE-S-4-2ST-BF02

(A) Tankless Circulator

(Bronze or S.S) Selected Shall be

16 GPM Max (4 Per Tankless) @

23' Total Head (10 PSI)

+ pipe, valves, fittings & tank.

(B) Install Circuit Setters to

Maintain Flow into Units @ 4 GPM

Maximum

Recommended Pipe Size/Heater Count 1 Unit - ¾” 2 Units - 1" 3 Units - 1-¼” 4 to 5 Units - 1-½” 6 to 8 Units - 2" 9 to 14 Units - 2-½” 15 to 16 Units - 3"

NPE-S Series Tankless Water Heater

Condensate

(A)

Domestic Cold

Water

Domestic Hot Water to Fixtures

CHG

Gas

CHG

Communication

Cable

Insulated

Storage

Tank

Insulated

Storage

Tank

T T

Optional DHW Recirculation

CHG

Communication

Cable

CHG

Communication

Cable

(B) (B) (B) (B)

Page 18: NPE Series Application Drawings - Navien

20 Goodyear

Irvine, CA 92618

800-519-8794

www.Navien.com T

Check Valve Circulator

Pressure

Relief

Valve Expansion

Tank

AquastatFull-port

Ball Valve

Mixing

Valve

Storage

Vessel

DHW Circulator

w/Aquastat & Check Valve

This drawing is intended only as a guide and not as a replacement for professionally engineered project drawings.

This concept system drawing does not imply compliance with local building codes. Actual installation may vary

depending on installation location & parameters and it must be done in accordance to all local building codes.

Verify with local building officials before commencement of system installation.

Two NPE-S with Storage

to meet Flow/Temp Rise Requirements

Two Temperature System

Drawn By: B. Fenske August 1, 2013NPE-S-2-STLT-BF02

(A) Tankless Circulator

(Bronze or S.S) Selected Shall

be 8 GPM Max (4 Per Tankless)

@ 23' Total Head (10 PSI)

+ pipe, valves, fittings & tank.

(B) Install Circuit Setters to

Maintain Flow into Units @ 4

GPM Maximum

Recommended Pipe Size/Heater Count 1 Unit - ¾” 2 Units - 1" 3 Units - 1-¼” 4 to 5 Units - 1-½” 6 to 8 Units - 2" 9 to 14 Units - 2-½” 15 to 16 Units - 3"

NPE-S Series Tankless Water Heater

(A)Domestic Cold Water

Insulated

Storage

Tank

T

Domestic Hot Water

to Fixtures

Optional

DHW

Recirculation

3 or 4

Tap

Tank

CHG

Gas

Condensate

CHG

Communication

Cable

(B) (B)

Low Temp

Domestic Hot Water

M

CH

Page 19: NPE Series Application Drawings - Navien

20 Goodyear

Irvine, CA 92618

800-519-8794

www.Navien.com T

Check Valve Circulator

Pressure

Relief

Valve Expansion

Tank

AquastatFull-port

Ball Valve

Mixing

Valve

Storage

Vessel

DHW Circulator

w/Aquastat & Check Valve

This drawing is intended only as a guide and not as a replacement for professionally engineered project drawings.

This concept system drawing does not imply compliance with local building codes. Actual installation may vary

depending on installation location & perameters and it must be done in accordance to all local building codes.

Verify with local building officials before commencement of system installation.

One Navien NPE-S Dishwasher Application

With Storage to meet Flow/Temp

Rise Requirements

1. Tankless circulator selected should be

approved for domestic water (S.S. or Bronze).

2. Tankless circulator selected shall be 4 GPM

@ 23' H (10 PSI) + pipe, valves, fittings & tank.

3. Storage tank volume size selections:

High Temp (180°F)

6 X dishwasher GPM requirements

Low Temp (140°F)

4 X dishwasher GPM requirements

Drawn By: B. Fenske August 1, 2013NPE-S-1-DW-BF02

NPE-S Series Tankless Water Heater

Opt. Recirculation

Domestic Cold Water

Vacuum Breaker

Insulated

Storage

Tank

T

¾” Min

CHG

Gas

Condensate

Page 20: NPE Series Application Drawings - Navien

20 Goodyear

Irvine, CA 92618

800-519-8794

www.Navien.com T

Check Valve Circulator

Pressure

Relief

Valve Expansion

Tank

AquastatFull-port

Ball Valve

Mixing

Valve

Storage

Vessel

DHW Circulator

w/Aquastat & Check Valve

This drawing is intended only as a guide and not as a replacement for professionally engineered project drawings.

This concept system drawing does not imply compliance with local building codes. Actual installation may vary

depending on installation location & perameters and it must be done in accordance to all local building codes.

Verify with local building officials before commencement of system installation.

Drawn By: B. Fenske August 1, 2013

Two Navien NPE-S Dishwasher Application

With Storage to meet Flow/Temp

Rise Requirements

NPE-S-2-DW-DHW-BF02

NPE-S Series Tankless Water Heater

(A) Tankless Circulator (Bronze or S.S) Selected Shall be 4 GPM Max per

Tankless @ 23' Total Head (10 PSI) + pipe, valves, fittings & tank.

(B) Install Circuit Setters to Maintain Flow into Units @ 4 GPM Maximum.

Storage tank volume size selections:

High Temp (180°F)

6 X dishwasher GPM requirements

Low Temp (140°F)

4 X dishwasher GPM requirements

Opt. Recirculation

Vacuum

Breaker

Insulated

Storage

Tank

T

1” Min

Domestic

Water

To Fixtures

(A)

CHG

Gas

Domestic Cold Water

Condensate

CHG

Communication

Cable

(B) (B)M

CH

Page 21: NPE Series Application Drawings - Navien

20 Goodyear

Irvine, CA 92618

800-519-8794

www.Navien.com T

Check Valve Circulator

Pressure

Relief

Valve Expansion

Tank

AquastatFull-port

Ball Valve

Mixing

Valve

Storage

Vessel

DHW Circulator

w/Aquastat & Check Valve

This drawing is intended only as a guide and not as a replacement for professionally engineered project drawings.

This concept system drawing does not imply compliance with local building codes. Actual installation may vary

depending on installation location & perameters and it must be done in accordance to all local building codes.

Verify with local building officials before commencement of system installation.

(A) Tankless Circulator (Bronze or S.S) Selected Shall be 4 GPM Max per

Tankless @ 23' Total Head (10 PSI) + pipe, valves, fittings & tank.

(B) Install Circuit Setters to Maintain Flow into Units @ 4 GPM Maximum.

Storage tank volume size selections:

High Temp (180°F)

6 X dishwasher GPM requirements

Low Temp (140°F)

4 X dishwasher GPM requirements

Drawn By: B. Fenske August 1, 2013

Two Navien NPE-S Dishwasher Application

With Storage to meet Flow/Temp

Rise Requirements

NPE-S-2-DW-BF02

NPE-S Series Tankless Water Heater

Opt. Recirculation

Vacuum

Breaker

Insulated

Storage

Tank

T

1” Min

(A)

CHG

Gas

Domestic Cold Water

Condensate

CHG

Communication

Cable

(B) (B)

Page 22: NPE Series Application Drawings - Navien

20 Goodyear

Irvine, CA 92618

800-519-8794

www.Navien.com T

Check Valve Circulator

Pressure

Relief

Valve Expansion

Tank

AquastatFull-port

Ball Valve

Mixing

Valve

Storage

Vessel

DHW Circulator

w/Aquastat & Check Valve

This drawing is intended only as a guide and not as a replacement for professionally engineered project drawings.

This concept system drawing does not imply compliance with local building codes. Actual installation may vary

depending on installation location & perameters and it must be done in accordance to all local building codes.

Verify with local building officials before commencement of system installation.

(A) Tankless Circulator (Bronze or S.S) Selected Shall be 4 GPM Max per

Tankless @ 23' Total Head (10 PSI) + pipe, valves, fittings & tank.

(B) Install Circuit Setters to Maintain Flow into Units @ 4 GPM Maximum.

Storage tank volume size selections:

High Temp (180°F)

6 X dishwasher GPM requirements

Low Temp (140°F)

4 X dishwasher GPM requirements

Drawn By: B. Fenske August 1, 2013

Three Navien NPE-S Dishwasher Application

With Storage to meet Flow/Temp

Rise Requirements

NPE-S-3-DW-DHW-BF02

NPE-S Series Tankless Water Heater

Gas

Condensate

Opt. Recirculation

Vacuum

Breaker

Insulated

Storage

Tank

T

1-1/4” Min

Domestic

Water

To Fixtures

(A)

CHG

Domestic Cold Water

CHG

Communication

Cable

(B) (B)

CHG

Communication

Cable

(B)

M

CH

Page 23: NPE Series Application Drawings - Navien

20 Goodyear

Irvine, CA 92618

800-519-8794

www.Navien.com T

Check Valve Circulator

Pressure

Relief

Valve Expansion

Tank

AquastatFull-port

Ball Valve

Mixing

Valve

Storage

Vessel

DHW Circulator

w/Aquastat & Check Valve

This drawing is intended only as a guide and not as a replacement for professionally engineered project drawings.

This concept system drawing does not imply compliance with local building codes. Actual installation may vary

depending on installation location & parameters and it must be done in accordance to all local building codes.

Verify with local building officials before commencement of system installation.

NPE-S-Combi-AH-BF02 August 1, 2013Drawn By: B. Fenske

Navien NPE-S Series Tankless

Combi Use Application with Air Handler

NPE-S Series Tankless Water Heater

AIRFLOW

Opt. AC COIL

Gas

Domestic

Cold Water

Domestic

Hot Water

To

Fixtures

Circulator Requirement:

Bronze or Stainless Steel

Select & Set - 4 GPM max @ 23 ft head.

(Alternate pump location shown inside AHU)

Condensate

CHGM

CH

Page 24: NPE Series Application Drawings - Navien

20 Goodyear

Irvine, CA 92618

800-519-8794

www.Navien.com T

Check Valve Circulator

Pressure

Relief

Valve Expansion

Tank

AquastatFull-port

Ball Valve

Mixing

Valve

Air

Elimination

DHW Circulator

w/Aquastat & Check Valve

This drawing is intended only as a guide and not as a replacement for professionally engineered project drawings.

This concept system drawing does not imply compliance with local building codes. Actual installation may vary

depending on installation location & parameters and it must be done in accordance to all local building codes.

Verify with local building officials before commencement of system installation.

NPE-S-Combi-SS-BF02 August 1, 2013Drawn By: B. Fenske

Navien NPE-S Series Tankless

Combi Use Application with Required

SS Heat Exchanger

NPE-S Series Tankless Water Heater

Gas

Domestic

Cold Water

Domestic

Hot Water

To

Fixtures

(A) Circulator Requirement:

Bronze or Stainless Steel

Select & Set - 4 GPM max @ 23 ft head.

(B) Maximum 30 MBTU’s/Hour & 135°F

Maximum Heating System Temperature

with NPE tankless set at 140°F.

Condensate

CH

Closed Loop

Heating Fill

SS Heat

Exchanger

(B)

Field

Supplied

Circulator

Zone PanelT

(A)

GM

CH

Page 25: NPE Series Application Drawings - Navien

20 Goodyear

Irvine, CA 92618

800-519-8794

www.Navien.com T

Check Valve Circulator

Pressure

Relief

Valve Expansion

Tank

AquastatFull-port

Ball Valve

Mixing

Valve

Storage

Vessel

DHW Circulator

w/Aquastat & Check Valve

This drawing is intended only as a guide and not as a replacement for professionally engineered project drawings.

This concept system drawing does not imply compliance with local building codes. Actual installation may vary

depending on installation location & parameters and it must be done in accordance to all local building codes.

Verify with local building officials before commencement of system installation.

NPE-S-G-BF02 August 1, 2013Drawn By: B. Fenske

NPE-S Domestic Hot Water Standard

Installation with Geothermal or

Desuperheater

Notes:

1. For Storage Tank/Geothermal Operation; DIP Switch #6

of 10 located on Integrated Display Panel should be set ON

(UP).

2. With Storage Tank/Geothermal Operation Enabled, NPE

Tankless DHW setting may be set at or near storage tank

thermostatic mixing valve temperature output.

Domestic

Cold Water

NPE-S Series Tankless Water Heater

DHW

Supply

To Fixtures

Gas

Condensate

CH

Domestic

Storage

Tank

Geothermal Unit

or

Desuperheater

G

(A)

(A) Follow GeoThermal Unit and Tank Manufacturer Recommendations and Requirements

Page 26: NPE Series Application Drawings - Navien

20 Goodyear

Irvine, CA 92618

800-519-8794

www.Navien.com T

Check Valve Circulator

Pressure

Relief

Valve Expansion

Tank

AquastatFull-port

Ball Valve

Mixing

Valve

Storage

Vessel

DHW Circulator

w/Aquastat & Check Valve

This drawing is intended only as a guide and not as a replacement for professionally engineered project drawings.

This concept system drawing does not imply compliance with local building codes. Actual installation may vary

depending on installation location & parameters and it must be done in accordance to all local building codes.

Verify with local building officials before commencement of system installation.

NPE-S-S-BF02 August 1, 2013Drawn By: B. Fenske

NPE-S Domestic Hot Water Standard

Installation with Solar Application

Notes:

1. For Storage Tank/Solar Operation; DIP Switch #6 of 10

located on Integrated Display Panel should be set ON (UP).

2. With Storage Tank/Solar Operation Enabled, NPE

Tankless DHW setting may be set at or near storage tank

thermostatic mixing valve temperature output.

Domestic

Cold Water

NPE-S Series Tankless Water Heater

Gas

Condensate

CHG

Solar Fill

DHW

Supply

To Fixtures