17
1 Introduction to Power System Stability Mohamed A. El-Sharkawi Department of Electrical Engineering University of Washington Seattle, WA 98195 http://SmartEnergyLab.com Email: [email protected] 1 ©Mohamed El-Sharkawi, University of Washington NERC Standard 1. The System remains within acceptable limits; 2. The System performs acceptably after credible contingencies; 3. The System contains (limit) instability and cascading outages; 4. The System’s facilities are protected from severe damage; and 5. The System’s integrity can be restored if it is lost. The bulk power system will achieve an adequate level of reliability when it is planned and operated such that: 2 ©Mohamed El-Sharkawi, University of Washington NERC Standard “Reliable Operation means operating the elements of the Bulk-Power System within equipment and electric system thermal, voltage, and stability limits so that instability, uncontrolled separation, or cascading failures of such system will not occur as a result of sudden disturbance, including a Cybersecurity Incident, or unanticipated failure of system elements.” NERC standard is for dynamic performance requirements Security Stability 3 ©Mohamed El-Sharkawi, University of Washington System Operating Limit (SOL) MW, MVar, Amperes, Frequency or Volts that satisfies the most limiting of the operating criteria for a specified system configuration to ensure operation within acceptable reliability criteria This is a security measure 4 ©Mohamed El-Sharkawi, University of Washington Interconnection Reliability Operating Limit (IROL) IROL is a SOL that, if violated, could lead to instability, uncontrolled separation, or cascading outages that adversely impact the reliability of the bulk power system. This is a stability measure 5 ©Mohamed El-Sharkawi, University of Washington SOL and IROL Following a contingency or other system event that cause the system to operate outside set reliability boundaries, Transmission Operators (TO) are obligated to return its transmission system to within SOL or IROL as soon as possible. 6 ©Mohamed El-Sharkawi, University of Washington

NERC Standard System Operating Limit (SOL) · Ia Xs cos Ef sin s f a X E sin ... Rotation of Phasor Diagram fg f 60 or50Hz V Infinite bus Ef Rotor f is the frequency at the infinite

  • Upload
    others

  • View
    0

  • Download
    0

Embed Size (px)

Citation preview

Page 1: NERC Standard System Operating Limit (SOL) · Ia Xs cos Ef sin s f a X E sin ... Rotation of Phasor Diagram fg f 60 or50Hz V Infinite bus Ef Rotor f is the frequency at the infinite

1

Introduction to Power System Stability

Mohamed A. El-Sharkawi

Department of Electrical Engineering

University of Washington

Seattle, WA 98195

http://SmartEnergyLab.com

Email: [email protected]

1©Mohamed El-Sharkawi, University of Washington

NERC Standard

1. The System remains within acceptable limits;2. The System performs acceptably after credible

contingencies;3. The System contains (limit) instability and

cascading outages;4. The System’s facilities are protected from severe

damage; and5. The System’s integrity can be restored if it is lost.

The bulk power system will achieve an adequate level of reliability when it is planned and operated such that:

2©Mohamed El-Sharkawi, University of Washington

NERC Standard

• “Reliable Operation means operating the elements of the Bulk-Power System within equipment and electric system thermal, voltage, and stability limits so that instability, uncontrolled separation, or cascading failures of such system will not occur as a result of sudden disturbance, including a CybersecurityIncident, or unanticipated failure of system elements.”

• NERC standard is for dynamic performance requirements– Security– Stability

3©Mohamed El-Sharkawi, University of Washington

System Operating Limit (SOL)

• MW, MVar, Amperes, Frequency or Volts that satisfies the most limiting of the operating criteria for a specified system configuration to ensure operation within acceptable reliability criteria

• This is a security measure

4©Mohamed El-Sharkawi, University of Washington

Interconnection Reliability Operating Limit (IROL)

• IROL is a SOL that, if violated, could lead to instability, uncontrolled separation, or cascading outages that adversely impact the reliability of the bulk power system.

• This is a stability measure

5©Mohamed El-Sharkawi, University of Washington

SOL and IROL

• Following a contingency or other system event that cause the system to operate outside set reliability boundaries, Transmission Operators (TO) are obligated to return its transmission system to within SOL or IROL as soon as possible.

6©Mohamed El-Sharkawi, University of Washington

Page 2: NERC Standard System Operating Limit (SOL) · Ia Xs cos Ef sin s f a X E sin ... Rotation of Phasor Diagram fg f 60 or50Hz V Infinite bus Ef Rotor f is the frequency at the infinite

2

What is stability?

• Is the ability of the system to achieve steady state operating condition after a disturbance– All oscillations are damped out

f

60Hz

Time7©Mohamed El-Sharkawi, University of Washington

Stability

• During fault, and right after the fault is cleared, the power system stability is determined by the capabilities of its generators to – maintain connected to the grid– provide the extra reactive power– provide fast ramping down of real power

• Generators are permitted to trip off line only in the case of a permanent fault on a directly connected circuit

8©Mohamed El-Sharkawi, University of Washington

What is security?

• If the system is stable after a disturbance, the system is secure if all its key components are operating within their design limits

9©Mohamed El-Sharkawi, University of Washington

Balance of power in Generators

GPm Pe

MechanicalPower

Controlled atthe power plant

ElectricalPower

Controlled bythe customers

Pm = PeAt steady state

10©Mohamed El-Sharkawi, University of Washington

Turbine Speed and Imbalance of Power

dt

dnPP em ~

GPm

Pe

sem nnPPif ;

sem nnPPif ;

0; dt

dnPPif em

speedrotor constant ;nn s

11©Mohamed El-Sharkawi, University of Washington

Turbine Speed and System Frequency

np

f120

f: The frequency of the terminal voltage of the generatorp: The number of poles of the generatorn: The speed of the generator (turbine)

12©Mohamed El-Sharkawi, University of Washington

Page 3: NERC Standard System Operating Limit (SOL) · Ia Xs cos Ef sin s f a X E sin ... Rotation of Phasor Diagram fg f 60 or50Hz V Infinite bus Ef Rotor f is the frequency at the infinite

3

If Pm>Pe

• The surplus energy is stored in the rotating mass of the generator in the form of kinetic energy– The machine speeds up (frequency

increases)– The current inside the machine increases– Over-speed and over-current protections will

eventually trip the machine

GPm

Pe

13©Mohamed El-Sharkawi, University of Washington

If Pm<Pe

• The deficit in energy is drawn from the kinetic energy of the rotating mass of the generator– The machine initially slows down (frequency

decreases)

– If not corrected, the machine could operate as a motor

– Machine is tripped to prevent mechanical damages

GPm

Pe

14©Mohamed El-Sharkawi, University of Washington

Transient Stability Analysis

• Transient stability analysis determines whether the generator, after a disturbance, reaches a new stable operating point. – The input mechanical power of the generator

is equal to the output electric power, and

– The frequency of the generator is the same as the frequency of the system before the disturbance (i.e. the generator speed is the same as the prefault synchronous speed)

15©Mohamed El-Sharkawi, University of Washington

Unstable System

n (f)

ns=60Hz

16©Mohamed El-Sharkawi, University of Washington

Unstable System

Time

n (f)

ns=60Hz

17©Mohamed El-Sharkawi, University of Washington

Stable System

Time

n (f)

ns=60Hz

18©Mohamed El-Sharkawi, University of Washington

Page 4: NERC Standard System Operating Limit (SOL) · Ia Xs cos Ef sin s f a X E sin ... Rotation of Phasor Diagram fg f 60 or50Hz V Infinite bus Ef Rotor f is the frequency at the infinite

4

Synchronous Generator

El-Sharkawi@University of Washington 20

Power Generation

• 99+ % of all power are generated by the synchronous generators

• Synchronous machines can operate as generators or motors

El-Sharkawi@University of Washington 21 El-Sharkawi@University of Washington 22

El-Sharkawi@University of Washington 23 El-Sharkawi@University of Washington 24

Small Synchronous Machine

Page 5: NERC Standard System Operating Limit (SOL) · Ia Xs cos Ef sin s f a X E sin ... Rotation of Phasor Diagram fg f 60 or50Hz V Infinite bus Ef Rotor f is the frequency at the infinite

5

El-Sharkawi@University of Washington 25

N

S

StatorRotor

X

X

c

b

a

Xc

b

El-Sharkawi@University of Washington 26

Time

Vaa’Vbb’ Vcc’

X

X

c

b

a

Xc

b

N

S

f

El-Sharkawi@University of Washington 27

f

s

Ef

N

S

If

Vf

td

d~E

ff

Open Stator

fE is directly proportional to the excitation current fI

The frequency of fE is proportional to the synchronous speed s

El-Sharkawi@University of Washington 28

Xs R

Ef Vt

sXRcetansisReArmatureR

cetanacResSynchronouX s

Equivalent Circuit

El-Sharkawi@University of Washington 29

Generator Equivalent Circuit

satf XIVE

Ia

Xs

Ef Vt

El-Sharkawi@University of Washington 30

Generator Equivalent Circuit

satf XIVE

Vt

Ia Xs

Ia

Ef

Vt is Fixed (infinite Bus)Ef is function of If

Magnitude and phase of Ia

are dependant variables

Ia

Xs

EfVt

Page 6: NERC Standard System Operating Limit (SOL) · Ia Xs cos Ef sin s f a X E sin ... Rotation of Phasor Diagram fg f 60 or50Hz V Infinite bus Ef Rotor f is the frequency at the infinite

6

El-Sharkawi@University of Washington 31

Power equations

sinIVQ att 3

cosIVP at3

Ia

Xs

Ef Vt

Ia

Vt

Ef

Ia Xs

Vt and Ef are phase quantities

f t

El-Sharkawi@University of Washington 32

Power equation

sinEcosXI fsa

s

fa X

sinEcosI

sinX

EV3P

s

ft

cosIV3P at

Ia

Vt

Ef

Ia Xs

El-Sharkawi@University of Washington 33

Power Characteristics of Generator

sinX

EV3P

s

ft

P

Pmax

l 90o s

ft

X

EVP

3max

Ia

Vt

Ef

Ia Xs

Ia

Xs

Ef Vt

El-Sharkawi@University of Washington 34

Reactive Power equations

sin3 att IVQ

Ia

Xs

Ef Vt

Vt and Ef are phase quantities

f t

tfsa VEXI cossin

Ia

Vt

Ef

Ia Xs

El-Sharkawi@University of Washington 35

sin3 att IVQ

tfsa VEXI cossin

tfs

tatt VE

X

VIVQ cos

3sin3

If Ef cos > Vt ; Qt is positive and Current is lagging

If Ef cos < Vt ; Qt is negative and Current is leading

If Ef cos = Vt ; Qt is zero and Current is in phase

A Synchronous Generator Connected to Large System

Transmission line

G

Terminal busV and f may vary

Infinite busV and f cannot vary

Vt VEf

36©Mohamed El-Sharkawi, University of Washington

Page 7: NERC Standard System Operating Limit (SOL) · Ia Xs cos Ef sin s f a X E sin ... Rotation of Phasor Diagram fg f 60 or50Hz V Infinite bus Ef Rotor f is the frequency at the infinite

7

Power Equation

I

X = Xs+Xline

Ef V

Power Reactive

Power Real

VcosEX

VQ

sinX

VEP

f

f

V

Ef

37©Mohamed El-Sharkawi, University of Washington

Power Characteristics of Generator

sinX

EVP f

38©Mohamed El-Sharkawi, University of Washington

P

Pmax

90o

Pm

Maximum Power

P

Pm

Pmax

l 90o

Phasor Diagram atPmax

V

Ef

39©Mohamed El-Sharkawi, University of Washington

Operating Point

Pm

P

Operating point

sinX

VEP f

40©Mohamed El-Sharkawi, University of Washington

Generation Limit

• The generator must generate less than the Pmax

(called pull-out power).

• The difference between Pmax and the actual power generated is the generation margin.

• The generation margin must be positive and large enough to ensure the dynamic stability of the system.

41©Mohamed El-Sharkawi, University of Washington

Dynamic Stability Assessment (DSA)

42©Mohamed El-Sharkawi, University of Washington

Page 8: NERC Standard System Operating Limit (SOL) · Ia Xs cos Ef sin s f a X E sin ... Rotation of Phasor Diagram fg f 60 or50Hz V Infinite bus Ef Rotor f is the frequency at the infinite

8

Objective of DSA

• Dynamic stability analysis determines whether the system, after a disturbance, reaches a new stable operating point. – The input mechanical power of the generator is equal

to the output electric power

– The frequencies of the generator is the same as the frequency of the system (i.e. the generator speed is the synchronous speed)

– All voltages and currents are within the allowable limits

43©Mohamed El-Sharkawi, University of Washington

Phasor diagram

I

X

Ef V

V

I X

I

Ef

44©Mohamed El-Sharkawi, University of Washington

Rotation of Phasor Diagram

gf

Hzorf 5060

VInfinite bus

EfRotor

f is the frequency at the infinite bus

fg is the frequency of the generator

45©Mohamed El-Sharkawi, University of Washington

Frequency/Speed Relationship

• The frequency (fg) of the generator’s voltage is proportional to the speed of the generator’s shaft (n).

np

fg 120

p is the number of magnetic poles of the generator

46©Mohamed El-Sharkawi, University of Washington

Frequency/Speed Relationship

• If the frequency of the generator (fg) is 60 Hz (or 50 Hz), the speed of the generator’s shaft is called synchronous speed (ns).

np

fg 120

system Hz50in 120

50

system Hz60in 120

60

s

s

np

np

47©Mohamed El-Sharkawi, University of Washington

Power Control

dt

dn~PPm G

Pm P

increasesn;PPif m decreasesn;PPif m

0dt

dn;PPif m speedrotor constant ;nn s

48©Mohamed El-Sharkawi, University of Washington

Page 9: NERC Standard System Operating Limit (SOL) · Ia Xs cos Ef sin s f a X E sin ... Rotation of Phasor Diagram fg f 60 or50Hz V Infinite bus Ef Rotor f is the frequency at the infinite

9

– The current of the machine increases

Power Control• When more power is

needed, the generator speed increases (n>ns) by increasing the mechanical power into the generator– The frequency of the

generator increases (fg>f )

– The angle increases

V

ffg

f1

Ef

Ef

ffg

2I1 X

I2 X

at t1

at t2

– Hence, the power increases

49©Mohamed El-Sharkawi, University of Washington

Swings due to Sudden increase in Mechanical Power

P

3

3

Pm2

2

2

Pm1

1

50©Mohamed El-Sharkawi, University of Washington

Swings due to Sudden increase in Mechanical Power

P

Pm1

1

Operating point Powers Acceleration

Rotor Speed

Power angle

1Before disturbance

Pm1= Pe 0 n = ns 1

51©Mohamed El-Sharkawi, University of Washington

Swings due to Sudden increase in Mechanical Power

P

Pm2

2

2

Pm1

1

Operating point Powers Acceleration

Rotor Speed

Power angle

1 to 2After increasing Pm

Pm2 > Pe + (n↑) n > ns ↑

52©Mohamed El-Sharkawi, University of Washington

Swings due to Sudden increase in Mechanical Power

P

Pm2

2

2

Pm1

1

Operating point Powers Acceleration

Rotor Speed

Power angle

2 Pm2 = Pe 0 n > ns 2

53©Mohamed El-Sharkawi, University of Washington

Swings due to Sudden increase in Mechanical Power

P

Pm2

2

2

Pm1

1

Operating point Powers Acceleration

Rotor Speed

Power angle

After 2 Pm2 < Pe - (n↓) n > ns ↑

54©Mohamed El-Sharkawi, University of Washington

Page 10: NERC Standard System Operating Limit (SOL) · Ia Xs cos Ef sin s f a X E sin ... Rotation of Phasor Diagram fg f 60 or50Hz V Infinite bus Ef Rotor f is the frequency at the infinite

10

Swings due to Sudden increase in Mechanical Power

P

3

3

Pm2

2

2

Pm1

1

Operating point Powers Acceleration

Rotor Speed

Power angle

3 Pm2 < Pe - (n↓) n = ns 3

55©Mohamed El-Sharkawi, University of Washington

Swings due to Sudden increase in Mechanical Power

P

3

3

Pm2

2

2

Pm1

1

Operating point Powers Acceleration

Rotor Speed

Power angle

3 to 2 Pm2 < Pe - (n↓) n < ns ↓

56©Mohamed El-Sharkawi, University of Washington

Swings due to Sudden increase in Mechanical Power

P

3

3

Pm2

2

2

Pm1

1

Operating point Powers Acceleration

Rotor Speed

Power angle

2 Pm2 = Pe 0 n < ns 2

57©Mohamed El-Sharkawi, University of Washington

Swings due to Sudden increase in Mechanical Power

P

3

3

Pm2

2

2

Pm1

1

Operating point Powers Acceleration

Rotor Speed

Power angle

2 to 1 Pm2 > Pe + (n↑) n < ns ↓

58©Mohamed El-Sharkawi, University of Washington

Swings due to Sudden increase in Mechanical Power

P

3

3

Pm2

2

2

Pm1

1

Operating point Powers Acceleration

Rotor Speed

Power angle

1 Pm2 > Pe + (n↑) n = ns1

59©Mohamed El-Sharkawi, University of Washington

Swings due to Sudden increase in Mechanical Power

P

Pm2

2

2

Pm1

1

Operating point Powers Acceleration

Rotor Speed

Power angle

1 to 2 Pm2 > Pe + (n↑) n > ns ↑

60©Mohamed El-Sharkawi, University of Washington

Page 11: NERC Standard System Operating Limit (SOL) · Ia Xs cos Ef sin s f a X E sin ... Rotation of Phasor Diagram fg f 60 or50Hz V Infinite bus Ef Rotor f is the frequency at the infinite

11

Operating point Powers AccelerationRotorSpeed

Power angle

1Before disturbance

Pm1= Pe 0 n = ns 1

1 to 2After Pm increased Pm2 > Pe + (n↑) n > ns ↑

2 Pm2 = Pe 0 n > ns 2

2 to 3 Pm2 < Pe - (n↓) n > ns ↑

3 Pm2 < Pe - (n↓) n = ns 3

3 to 2 Pm2 < Pe - (n↓) n < ns ↓

2 Pm2 = Pe 0 n < ns 2

2 to 1 Pm2 > Pe + (n↑) n < ns ↓

1 Pm2 > Pe + (n↑) n = ns1

Summary

61©Mohamed El-Sharkawi, University of Washington

Swing Angle

3

2

1

Time

dt

dnPPm ~

62©Mohamed El-Sharkawi, University of Washington

Damped Oscillations (Stable)

3

2

1

Time

nDdt

dnMPPm

63©Mohamed El-Sharkawi, University of Washington

Damped Oscillations (Stable)

• Damping is due to several factors such as– Resistances of the various power system

components

– Controllers installed in the power plants

64©Mohamed El-Sharkawi, University of Washington

Undamped Oscillation (Unstable)

3

2

1

Time

When D is negative nDdt

dnMPPm

65©Mohamed El-Sharkawi, University of Washington

P

P m

2

E f2

E f1

E f2 > E f1

1

Effect of Excitation

sinX

EVP f

66©Mohamed El-Sharkawi, University of Washington

Page 12: NERC Standard System Operating Limit (SOL) · Ia Xs cos Ef sin s f a X E sin ... Rotation of Phasor Diagram fg f 60 or50Hz V Infinite bus Ef Rotor f is the frequency at the infinite

12

Effect of Increasing Excitation

• The maximum power that CAN be delivered increases

• The real power is unchanged (Pm

unchanged)

• The power angle decreases

67©Mohamed El-Sharkawi, University of Washington

Increase transmission Capacity

Pm Xl

G

Terminal bus

Xs

Infinite bus

VtVo

sinX

EVP f

68©Mohamed El-Sharkawi, University of Washington

69©Mohamed El-Sharkawi, University of Washington

Ia

Xs

Ef

Xl2

Vt V

Xl1

Pm Xl

G

Xs Vt V

70©Mohamed El-Sharkawi, University of Washington

P

Pm

2

sin)XX(

EVP

ls

f

2

sin)X.X(

EVP

ls

f

501

1

sinX

EVP f

71©Mohamed El-Sharkawi, University of Washington

Dynamic Stability Assessment (DSA)

• DSA Methods• Time-domain solution• Energy Margin• Equal area• Eigenvalues• Pattern Recognition

72©Mohamed El-Sharkawi, University of Washington

Page 13: NERC Standard System Operating Limit (SOL) · Ia Xs cos Ef sin s f a X E sin ... Rotation of Phasor Diagram fg f 60 or50Hz V Infinite bus Ef Rotor f is the frequency at the infinite

13

Time Domain Solution

• Time domain methods seek to set up and solve a set of differential equations that describe the motion of the machines connected to the system

• Advantage:– Direct numerical integration can provide accurate

information on the stability of the system.• Disadvantage:

– The numerical integration is performed in each time interval; time consuming and slow

73©Mohamed El-Sharkawi, University of Washington

Time Domain Solution

Time

Fre

que

ncy

Time

Fre

que

ncy

Unstable System

74©Mohamed El-Sharkawi, University of Washington

Time Domain Solution

Time

Fre

que

ncy

Stable System

75©Mohamed El-Sharkawi, University of Washington

Equal Area Criterion

• A DSA method that represents the kinetic energy gained or lost due to oscillations.

• If the deceleration energy is equal or larger than the acceleration energy, the system is stable.

76©Mohamed El-Sharkawi, University of Washington

Equal Area Criterion

• Kinetic Energy KE

2n~KE Change in Kinetic Energy KE

2n~KE

77©Mohamed El-Sharkawi, University of Washington

Equal Area Criterion• Assume a sudden increase in the mechanical

energy to the generator– The speed of the machines increases from n1 to n2

78©Mohamed El-Sharkawi, University of Washington

P

3

3

Pm2

2

2

Pm1

1

Page 14: NERC Standard System Operating Limit (SOL) · Ia Xs cos Ef sin s f a X E sin ... Rotation of Phasor Diagram fg f 60 or50Hz V Infinite bus Ef Rotor f is the frequency at the infinite

14

Analysis of Equal Area Criterion

• Acceleration Kinetic Energy KEa

21

2212 nn~KEKEKEa

Decelerated Kinetic Energy KEd

23

2232 nn~KEKEKEd

Condition for stable system

ad KEKE

79©Mohamed El-Sharkawi, University of Washington

P

3

3

Pm2

2

2

Pm1

1

Stability Condition

13 nn

21

22

23

22 nnnn

KEKE ad

snn 1Since

Hencesnn 3

80©Mohamed El-Sharkawi, University of Washington

P

3

3

Pm2

2

2

Pm1

1

Equal Area Criterion

d2

a2

3

2

2

1

KEdtPP

KEdtPP

t

t

m

t

t

m

Since

Then

unbalancepower PPm

81©Mohamed El-Sharkawi, University of Washington

Equal Area Criterion

d2

a2

3

2

2

1

1

1

KEdPPn

KEdPPn

m

m

Since

Then

ndt

dnn s

82©Mohamed El-Sharkawi, University of Washington

Stability Condition

da

mm

AA

dPPdPP

areaon Deceleratiareaon Accelerati

3

2

2

1

22

Since

Then da KEKE

n

constant

83©Mohamed El-Sharkawi, University of Washington

Representation of Aa and Ad

P

3

3

Pm2

2

2

Pm1

1

Ad

Aa

For stable SystemAa = Ad

84©Mohamed El-Sharkawi, University of Washington

Page 15: NERC Standard System Operating Limit (SOL) · Ia Xs cos Ef sin s f a X E sin ... Rotation of Phasor Diagram fg f 60 or50Hz V Infinite bus Ef Rotor f is the frequency at the infinite

15

Unstable System

P

3 max

3-maxPm2

2

2

Pm1

1

Ad(max)

AaIf at 3-max

n3 > ns

ThenAa > Ad(max)

85©Mohamed El-Sharkawi, University of Washington

General Stability Condition

(max)

3

2

2

1

22

da

mm

AA

dPPdPPmax

(maximum)da KEKE

86©Mohamed El-Sharkawi, University of Washington

General Stability Condition

(max)

3

2

2

1

22

da

mm

AA

dPPdPPmax

(maximum)da KEKE

87©Mohamed El-Sharkawi, University of Washington

Example: Opened Breaker

TLG

CB

Breaker

Assume that the CB is opened for a short time

88©Mohamed El-Sharkawi, University of Washington

Analysis of Opened Breaker

P

3

3

cClearing angle

2

Pm

1

AdAa

If n3 = ns

OrAa = Ad,

the system is stable

89©Mohamed El-Sharkawi, University of Washington

Critical Clearing Angle

P

3 max

3-max

crCritical Clearing angle

2

Pm

1

Ad min

Aa max

The critical clearing angle (cr)

is the maximum angle for a stable system, i.e. whenAa max = Ad min

90©Mohamed El-Sharkawi, University of Washington

Page 16: NERC Standard System Operating Limit (SOL) · Ia Xs cos Ef sin s f a X E sin ... Rotation of Phasor Diagram fg f 60 or50Hz V Infinite bus Ef Rotor f is the frequency at the infinite

16

Critical Clearing Angle

1

11

0

crmmmmaxa PdPdPPA

crcr

crmcrmax

maxmmmind

PcoscosP

dsinPPdPPAcrcr

11

11

10.91©Mohamed El-Sharkawi, University of Washington

Critical Clearing Angle

1112 cossincos cr

Then

111 crmcrmaxcrm

mindmaxa

PcoscosPP

AA

For stable system

10.92©Mohamed El-Sharkawi, University of Washington

Energy Margin

• To predict the transient behavior of a power system without having to conduct a complete time domain simulation.

• The values of an energy function is calculated and compared with the critical value to determine the stability.

• Accurate only when the operating point is within the region of energy function.

• Because of the approximation in the energy function, results are often pessimistic

93©Mohamed El-Sharkawi, University of Washington

Energy Margin: Steps

• Calculate the transient energy at the instant the disturbance is cleared.

• Determine the critical energy for the current disturbance.

• Calculate the transient energy margin.

94©Mohamed El-Sharkawi, University of Washington

Eigenvalues Method

• The power system is converted into a set of linear equations.

• The dynamic behavior can be analyzed by any of the linear techniques – Eigenvalues– Root locus plots– Nyquist criteria– Routh-Hurwitz criteria

• Inaccuracies resulting from representing a highly nonlinear system by a set of linear equations.

95©Mohamed El-Sharkawi, University of Washington

Eigenvalues Method

• The system is represented by

dxadt

dx

dxax

Where d is a disturbance

96©Mohamed El-Sharkawi, University of Washington

Page 17: NERC Standard System Operating Limit (SOL) · Ia Xs cos Ef sin s f a X E sin ... Rotation of Phasor Diagram fg f 60 or50Hz V Infinite bus Ef Rotor f is the frequency at the infinite

17

Justification

• The solution of the equation is

j

edx t

where

Root (eigenvalue)Real component

Imaginary component

97©Mohamed El-Sharkawi, University of Washington

If is Negative (Stable System)

n

ns

Time

98©Mohamed El-Sharkawi, University of Washington

If is Positive (Unstable System)

n

ns

Time

99©Mohamed El-Sharkawi, University of Washington

Eigenvalues Method

• A linear analysis of the system

• Requires the detailed model of the system and the knowledge of all its parameters

100©Mohamed El-Sharkawi, University of Washington