1
ndervoltage (Device 27) tripping of generators was the single biggest identifiable cause of generator tripping during the 2003 blackout. The device 27 measures generator terminal voltage. IEEE Standard C37.102 - IEEE Guide for AC Generator Protection -- does not recommend use of the 27 function for tripping, but only to alarm to alert operators to take necessary actions. Undervoltage alarms as experienced by hydro, fossil, combustion and nuclear units are an indicator of possible abnormal operating conditions such as excitation problems and thermal issues within the unit. Other alarms from RTDs and hydrogen pressure are better indicators of thermal concerns. If function 27 tripping is used for an unmanned facility - the settings must coordinate with the stressed

Nder Voltage

Embed Size (px)

DESCRIPTION

ztret

Citation preview

ndervoltage (Device 27) tripping of generators was the single biggest identifiable cause of generator tripping during the 2003 blackout. The device 27 measures generator terminal voltage. IEEE Standard C37.102 - IEEE Guide for AC Generator Protection -- does not recommend use of the 27 function for tripping, but only to alarm to alert operators to take necessary actions. Undervoltage alarms as experienced by hydro, fossil, combustion and nuclear units are an indicator of possible abnormal operating conditions such as excitation problems and thermal issues within the unit. Other alarms from RTDs and hydrogen pressure are better indicators of thermal concerns. If function 27 tripping is used for an unmanned facility - the settings must coordinate with the stressed