FireSeeker Model FS-250Intelligent FireDetection SystemState-of-the-art simplicity, flexibility and value
BASIC FIRE PROTECTION SYSTEM➤➤ CZM-4 Allows existing conventional detec-
tors (not addressable) to report to the MXL.
➤➤ MOM-4/2 Card cages for mounting system modules.
➤➤ TSP-40 A thermal strip printer housed in theMXL enclosure.
➤➤ PIM-1 A port for driving an external printer. It can also be configured to manage a Video Display Terminal (MXL-VDT).
➤➤ MOI-Series Input and Output modules to control graphic LED annunciators.
The following list of equipment is used whenMXL hardware must be installed in remoteenclosures:
➤➤ PSR-1 A remote power supply/control board supports additional MXL modules as the system expands.
➤➤ PAD-2 A self contained 6 amp power supplywith 4 additional circuits for horns and strobes.
➤➤ NET-4/7 Network interface modules used to communicate between the MXL’s main boardand equipment housed in remote enclosures.
➤➤ NIM-1R A network interface module used when 2 or more MXL’s must share information.
➤➤ RCC-1/2/3 Remote control centers that mimic the MXL’s main control panel (MKB-2).
➤➤ NCC-G A PC- based control center for all MXL systems with an intuitive user interface.
Main MXL Enclosure
The following modules can be housed ineither location.
➤➤ MOM-2/4 Card Cage➤➤ ALD-2I Detector Loop Module➤➤ CSM-4 Horn/Strobe Module➤➤ CRM-4 Relay Module➤➤ CZM-4 Conv. Zone Module➤➤ TSP-40 Strip Printer
Main MXL enclosures house thefollowing system components:
MMB-2 Main BoardMPS-6 Power SupplyMKB-2 Control Panel
Remote MXL Enclosure
Remote enclosures house:PSR-1 Power
Supply/Control BoardMPS-6 Power SupplyNET-4/7 Network
➤ MMB-2 The MXL’s main board manages up to 120 detectors/pull stations and 2 circuits for horns or strobes. It also processes all commands within the system.
➤ MPS-6 A 6 amp power supply. A 12-amp version is available.
➤ MKB-2 The main control panel for the MXL.Includes system status LEDs, an LCD display for system messages and function keys.
➤ MME-3 The standard enclosure for MXL. Other sizes are available.
➤ FP-11 The FirePrint Fire Detector.
➤➤ ALD-2I Provides additional circuits to manage another 120 detectors/pull stations.
➤➤ CSM-4 Provides additional circuits for horns and strobes.
➤➤ CRM-4 Provides relay outputs for controlling devices such as door holders.
The following products are used tocreate an MXL fireprotection system.Those that are usedin every system arehighlighted. Theothers are optionaland expand the system’s size andfeatures. (For moredetailed informationplease refer toCatalog Sheet5000.)
Fire Safety
NETWORKED FIRE SYSTEM
Main MXL Enclosure
Each main MXL enclosure houses the following system components:
MMB-2 Main BoardMPS-6 Power SupplyMKB-2 Control Panel and NIM-1R Network
Interface
Fire Safety
Each main MXL enclosurehouses the following system components:
MMB-2 Main BoardMPS-6 Power SupplyMKB-2 Control Paneland NIM-1R Network
Interface
Main MXL Enclosure
Individual MXLSystems can beexpanded asshown in theBasic MXLSystem diagram.The NIM-1Rmodule is usedwhen multipleMXL systemsmust share information.
Firefinder NCCNT is a PC-based control for allnetworked systems. It provides text and graphicdetails of all events, customized for any facility.The simple controls and 4 levels of security adoptthemselves to any operator's requirements.
FireFinder NCCNT Command Center
MXL’s High Level System Network
Networked Fire Systems can have multiple points of control and/orannunciation. Each protected facility has a unique fire response plan.MXL and FireFinder NCCNT can be assembled to meet any variety ofresponse plans as required by building owners or local codes.
NETWORKED FIRE AND VOICE EVACUATION SYSTEMS
MXLV Voice Command Center
Each MXL enclosure houses the following system components:
MMB-2 Main BoardMPS-6 Power SupplyMKB-2 Control PanelNIM-1R Network InterfaceOCC-1 Output ControlTBM-2 Terminal ModuleOMM1/2 Card CageZC-Series Output ASC Series Amp Supervisors ZAC-30 Zone/Amp CardEL-410D Amplifier
Fire Safety
Each Main MXLV enclosure houses the following system com-ponents:MMB-2 Main Board
MPS-6 Power SupplyMKB-2 Control PanelNIM-1R Network InterfaceACM-1 Input ControlTBM-2 Terminal ModuleVSM-1 Switch InputsMMM-1Master MicrophoneTMM-1 Master TelephoneDMC-1 Digital Message CardRCM-1 Remote Page Control
Remote MXLV Enclosure
MXLV Voice Command Center
Main MXL Enclosure
Each Remote MXLV enclosure houses the following system components as required:
OCC-1 Output ControlTBM-2Terminal ModuleOMM-1/2 Card CageZC-Series OutputsASC-Series Amp SupervisorsZAC-30 Zone/Amp CardEL-410D Amplifier
Networked voicesystems can havemultiple commandcenters and can becombined and networked to anyother system in theMXL/V family.Products can bemixed in enclosuresor systems to meetany building’s architecture.
MXL Network and Page Risers
MXL NETWORKED SYSTEM ARCHITECTURE
Bus Configuration
Network paths “A” and “B” with “B” running clockwise and “A”running counterclockwise
Star Configuration
The complexnature of most facilities or campusenvironments dictates a need forwiring flexibility.
Fire Safety
The principle system architectures or wiringmethods in use today are Bus, Star, andLoop. They can also be described as DaisyChain, T-Tap, and Ring respectively. MXLNetworks support all of these configura-tions as well as hybrids or combinations.This can help to reduce the overall networkcost.
Loop Configuration - Style 7
MXL MXL MXL MXL MXL
MXL MXL MXL
MXL
MXL
MXL
MXL MXL MXL MXL MXL
AA A A
BB B B
8 Fernwood Road, Florham Park, NJ 07932 2 Kenview Boulevard IG NFS 5M 8/02Tel: (973) 593-2600 FAX: (973) 593-6670 Brampton, Ontario Canada L6T 5E4
Tel: (905) 799-9937 FAX: (905) 799-9858Visit us on the web: www.sbt.siemens.com/fis
MXL Networks can utilize either NFPAStyle 4 or 7 configurations along with bothstandard copper wire and fiber optic cableor combinations of copper and fiber opticcable.
B. Input Components
➤ ACM-1 An input control card for switch, message and voice inputs to the system.
➤ MMM-1 The system’s microphone is used for paging.
➤ VSM-1 This input module provides switches for selecting zones or floors to page/evacuate/alert as required.
➤➤ VLM-1 This module provides LED’s to indicate the status of remote portions of the system.
➤➤ VFM-1 This module provides control of fans and dampers in the HVAC system.
➤➤ DMC-1 Provides digital prerecorded messages for automatically evacuating or alerting occupants in the building.
➤➤ TMM-1 The master telephone for systems with firefighters’ telephones installed throughout the facility.
➤➤ RCM-1 A module that allows the operator to page to remote areas controlled by other MXLV voice evacuation systems.
A. Output Components
➤ OCC-1 The output control card manages information going to the output modules.
➤ TBM-2 All internal voice system circuits are terminated at this module.
➤ OMM-1/2 Card cages for mounting MXL voice system modules.
➤ ZC Series This series of output modules manages strobes and speakers as necessary inthe system.
➤ EL-410D A 100 Watt bulk amplifier that drives all speaker circuits.
➤ ASC-Series A series of supervision cards for the bulk amplifiers.
➤➤ ZAC-30 A 30 watt amplifier with a speaker circuit. It can be used instead of the EL-410Damplifier and ZC Series output modules above.
Main MXLV Enclosure
Remote enclosures houses thefollowing system components:
OCC-1 Output ControlTBM-2 Terminal
ModuleOMM-1/2 Card CagesZC Series OutputsASC- Series Amp
SupervisorZAC-30 Zone/Amp
Card
Fire Safety
Houses the following system components:
ACM-1 Input ControlMMM-1 Master MicrophoneVSM-1 Switch InputsTBM-2 Terminal ModuleTMM-1 Master TelephoneDMC-1 Digital Message
Card
Remote MXLV Enclosure
EL-410D Bulk Amplifiersoften have their own enclosure.
Note: The enclosures above also house the modules shown in theBasic MXL System diagram. Modules shown in the Remote enclosureabove can be housed in the main enclosure if space is available.
VOICE EVACUATION SYSTEM
The followingproducts are usedto create MXLVvoice evacuationsystems. Thosethat are used inevery system arehighlighted. Theothers are optionaland expand thesystem’s size andfeatures. Theseitems are in addi-tion to the productsin the basic MXLsystem. (For moredetailed informa-tion please refer toCatalog Sheet5035)
Remote MXLV Enclosure