MS5001 PA Complete Maintenance MANUAL

Embed Size (px)

Citation preview

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    1/986

    g

    GE Power SystemsOil & Gas

    Technical Training

    MS5001 PA

    GAS TURBINE

    Operation and Maintenance

    Training Manual

    Customer: AGIP GAS BV LYBIAN BRANCH

    Plant location: WAFA COAST- LYBIA

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    2/986MOD. ARGE 2/S

    INDEX

    CHAP. 1Page

    1. INTRODUCTION................................................................................................1-1

    1.1 STATIONARY APPLICATIONS .............................................................1-1

    1.2 MOBILE APPLICATIONS........................................................................1-2

    1.3 HISTORICAL NOTES...............................................................................1-2

    1.4 NUOVO PIGNONE GAS TURBINE MANUFACTURING PLANT ......1-3

    09-98-E P. 1-0

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    3/986MOD. ARGE 2/S

    09-98-E P. 1-1

    1. INTRODUCTION

    A gas turbine is an internal combustion motive machine. From all points of view, it canbe considered as a self-sufficient system: in fact, it is capable to aspirate and compress

    ambient air via its own compressor, to enrich the energetic power of air in its own

    combustion chamber and to convert this power into useful mechanical energy during the

    expanding process that takes place in its own turbine section. The resulting mechanical

    energy is transmitted via a coupling to a driven operating machine, which produces work

    useful for the industrial process in which the gas turbine belongs.

    1.1 STATIONARY APPLICATIONS

    These applications are the subject of this traning course. They are intended for the

    following industrial uses:

    Generator drive, in order to produce electric energy by an open cycle.

    Generator drive, to produce electric energy by a combined cycle.

    Generator drive, to produce electric energy by co-generation.

    Compressor drive

    Pump drive

    Pipeline compressor drive

    Pipeline pump drive

    Particular industrial processes

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    4/986MOD. ARGE 2/S

    09-98-E P. 1-2

    1.2 MOBILE APPLICATIONS

    These applications were the first ones to be introduced in terms of time. Theyinclude the following fields:

    railways

    marine propulsion

    aviation

    road traction

    1.3 HISTORICAL NOTES

    The first gas turbines to be used in operating applications appeared on the market

    at the end of the Forties; they were generally used in railways and presented the

    advantage of burning liquid fuel, even of poor quality. In this regard, we will

    mention the MS3001 turbine built by General Electric, with a power of 4500 HP,

    which was used just for this purpose.

    Successive achievements in material technology and extensive research into

    combustion resulted in rapid improvements in performance, in terms of specificpower and efficiency, obtained by increasing maximum temperatures in the

    thermodynamic cycle.

    In this matter, three generations of evolution can be defined, distinguished by the

    maximum temperature (C) ranges of gases entering the first rotor stage of the

    turbine:

    First generation 760

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    5/986MOD. ARGE 2/S

    09-98-E P. 1-3

    1.4 NUOVO PIGNONE GAS TURBINE MANUFACTURING PLANT

    Nuovo Pignone has built gas turbines of heavy duty type for industrial applicationssince 1961. These are made in the Florence workshop under a Manufacturing

    Agreement with General Electric, Schenectady - N.Y. - USA, which, in time, has

    led to the acquisition of complete licences (MS5002 gas turbine) and to the

    complete execution of some gas turbine models (turbines of the PGT range),

    starting from engineering and on to all construction phases.

    As a complement to their main activities, Nuovo Pignone converts gas turbines

    intended originally for the aircraft industry into packages for industrial applications

    which use the originary gas generator in conjunction with power turbines made

    by General Electric (LM range), or by Nuovo Pignone (PGT16 and PGT25

    ranges).Since 1962 up to the present time, Nuovo Pignone has built about 1000 turbines,

    complete with all auxiliaries required for their operation; of these, a good deal are

    part of turnkey plants for all application purposes listed at para. 1.1.

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    6/986MOD. ARGE 2/S

    09-98-E P. 1-4

    In the following tables, gas turbines currently produced by Nuovo Pignone are divided

    by model and by type of application.

    TABLE 1.1 GAS TURBINES FOR MECHANICAL DRIVE APPLICATIONS(1)

    Model Continuous Heat Rate RPM

    duty on the

    Power load side

    KW Kj/Kwh

    PGT 2 2180 13360 22500

    PGT 5 5500 13680 10290

    PGT 5 R 4850 10530 10290

    PGT 10 10440 10590 7900

    MS 3002 10890 13480 6500

    MS 3002 R 10440 10480 6500

    PGT 1614260 9935 7900

    PGT 25 23270 9565 6500

    H.S.P.T 29980 8935 6100

    LM 2500 22670 9720 3600

    MS 5002(D) 32600 11890 4670

    LM 5000 34450 9960 3600

    MS 6001 41010 10780 5100

    LM 6000 44850 8435 3600

    MS 7001 86280 10750 3600

    _____________________________

    (1) The values in the table refer to the turbine loading flange, under ISO conditions andthe use of natural gas.

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    7/986MOD. ARGE 2/S

    09-98-E P. 1-5

    Model Continuous Heat Rate Hz

    duty on

    Power load side

    KW Kj/Kwh

    PGT 2 2150 13536 60/50

    PGT 5 5500 12852 60/50

    PGT 10 10700 11052 60/50

    PGT 16 13760 10295 60/50

    PGT 25 22450 9910 60/50

    H.S.P.T 28930 9260 60/50

    LM 2500 22330 10110 60/50

    MS 5001 26300/27830 12650/12640 60/50

    LM 5000 33060 10270 60/50

    MS 6001 38340/41400 10780 60/50

    LM 6000 43450 8710/ 60/50

    MS 6001 FA 70140 10530 60/50

    MS 7001 EA 83500/90200 11060 60

    MS 9001 E 123400/133000 10850 50

    MS 9001 EC 169200 10300 50

    MS 9001 FA 226500 10090 50

    _____________________________(1) The values in the table refer to the turbine loading flange, under ISO conditions and the

    use of natural gas.

    TABLE 1.2 TURBINE S FOR GENERATOR DRIVE APPLICATIONS

    (1)

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    8/986NTRODUCTION

    P. 1-4

    GE 2 (PGT 2)

    OverviewOverviewOverviewOverviewOverviewThe GE2 is a 2MW single shaft machine for base load power generation. Thanks to the high exhaust tem-

    perature, the GE2 is perfectly suited for cogeneration in industrial and civil applications (over 5MW ofthermal power) and emergency electric power generation. The single combustion chamber can operate with

    a wide variety of liquid and gaseous fuels (or dual fuels) and it is designed to reduce environmental impact

    to a minimum, thus satisfying the most restrictive environmental regulations. The load reduction gear is

    integrated with the gas turbine and provides output speeds suitable for power generation (1500/1800 RPM).

    A microprocessor system for regulation, control and protection has been designed to render the management

    and operation of the GE2 gas turbine completely automatic.

    Design InfoDesign InfoDesign InfoDesign InfoDesign InfoCompressor

    Two stage centrifugal compressor

    Pressure ratio 12.5:1

    Combustion

    Single, combustion chamber

    Turbine

    Two stage turbine

    Investment cast blades, forged discs

    Package

    The complete Gen Set ismounted on a single baseplate

    The enclosure is integral with the baseplate providing maximum accessibility for gas

    turbine and auxiliaries maintenance; noise level < 85dB (A) at 1m

    In outdoor applications the filter plenum is flanged on top of the enclosure

    The package design is standardized for quick delivery; custom applications can beprovided

    Package dimensions (including generators and filters) LxWxH = 5.5mx3.8mx2.3m;

    Weight = 12t

    Emissions Control

    Steam or water injection for standard combustion chamber

    Dry Low Emission configuration available to satisfy the most stringent environmental

    regulations

    Performance InfoPerformance InfoPerformance InfoPerformance InfoPerformance InfoGenerator Drive (Expected Performance at ISO Conditions with fuel natural gas)

    Model Output Heat Rate Exhaust Flow Exhaust TemperatureGE2 2000 kWe 14400 kJ/kWh 10.7 kg/s 525 C

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    9/986INTRODUCTIONS

    P. 1-5

    GE 5 (PGT 5)

    OverviewOverviewOverviewOverviewOverviewThe PGT5 heavy-duty gas turbine has been designed with modular concepts to facilitate accessibility and

    maintainability.The gas generator consists of a 15-stage, high efficiency, axial-flow compressor directly coupled to a single

    stage turbine.

    The low pressure shaft (two-shaft version) is a single-stage, high-energy turbine, with variable second stage

    nozzles which grant maximum flexibility for mechanical drive service.

    The PGT5 has a single combustion chamber system which is rugged, reliable and able to burn a wide range

    of fuels, from liquid distillates and residuals to all gaseous fuels, including low BTU gas.

    Typical applications include pump drive for oil pipelines and compressor drive for gas pipelines.

    Design InfoDesign InfoDesign InfoDesign InfoDesign InfoCompressor

    Axial flow compressor, 15 stages

    Pressure ratio 9.1:1

    Combustion

    Single, reverse flow combustion can

    TurbineTwo shafts

    High Pressure turbine one reaction stage

    Low Pressure turbine one reaction stage

    Package

    The gas turbine module on a single baseplate includes the engine, starting system, auxilia-

    ries and acoustic enclosure

    Std. Configuration (excluding inlet/exhaust ducts/system):

    size 8mLxWxH = 8.5mx2.5mx3.0m

    weight 28 t

    Emissions Control

    DLE combustion system

    Steam and water injection system

    Performance InfoPerformance InfoPerformance InfoPerformance InfoPerformance Info

    Generator Drive: Single Shaft version(Expected Performance at ISO Conditions with fuel natural gas)

    Model Output Heat Rate Exhaust Flow Exhaust Temperature

    PGT5 5220 kWe 13422 kJ/kWh 24.6 kg/s 524 C

    Mechanical Drive:Two Shafts version (Expected Performance at ISO Conditions with fuel natural gas)

    Model Output Heat Rate Exhaust Flow Exhaust Temperature

    PGT5 5450 kW 13450 kJ/kWh 25.8 kg/s 533 C

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    10/986NTRODUCTION

    P. 1-6

    GE 5B (PGT 5B)OverviewOverviewOverviewOverviewOverviewThe GE5B series is a 6 MW range industrial duty gas turbine designed in two configurations: A single shaft

    configuration for power generation and a two shaft configuration for mechanical drive applications. The

    completely new design of the GE5B combines the technology of aircraft engine design with the ruggednessof the heavy duty PGT class of turbines. The flexibility, simplicity and compactness of the GE5B make it

    ideal for industrial power generation, including steam production, Oil & Gas applications in remote areas

    and Offshore installations. The control system is configured for fully automatic operation and has provisions

    for connection to Remote Monitoring and Diagnostics. The GE5B is ideally suited for applications, which

    require a continuous supply of electrical power with high availability and reliability. The exhaust energy is

    enough to provide a substantial quantity of steam at various pressures and temperatures when coupled to a

    Heat Recovery Steam Generator.

    Design InfoDesign InfoDesign InfoDesign InfoDesign InfoCompressor

    Axial flow compressor, 11 stages

    First three stator stages are variable geometry

    Pressure ratio 15:1

    Combustion

    Annular combustion chamber, 18 fuel nozzles

    Turbine

    Two reaction stages

    First stage cooled

    Package

    The gas turbine module on a single baseplate includes engine, starting system, load gear,

    auxiliaries and acoustic enclosure

    The off-base equipment is limited to the lube oil coolers and electric generator

    The inlet filtration module is designed for mounting above the gas turbine enclosure

    The enclosure has wide double-joined doors allowing for ease of access to all turbinecomponents and auxiliaries or engine removal

    The package design is standardized for quick delivery; custom applications can be

    provided

    Package dimensions (including filters on top of the enclosure)

    LxWxH = 5.9mx2.5mx5.7m;Weight = 30t

    Emissions Control

    The standard unit is configured with a DLE combustion system

    Performance InfoPerformance InfoPerformance InfoPerformance InfoPerformance InfoGenerator Drive (Expected Performance at ISO Conditions with fuel natural gas)

    Model Output Heat Rate Exhaust Flow Exhaust Temperature

    GE5 5500 kWe 11720 kJ/kWh 19.7 kg/s 571 C

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    11/986INTRODUCTIONS

    P. 1-7

    PGT 10A (two shaft)

    OverviewOverviewOverviewOverviewOverviewThe PGT10 is a high efficiency gas turbine designed and developed by Nuovo Pignone for shaft outputs

    ranging between 9,500 and 15,000 HP at ISO conditions. Since first introduced to the market in 1988, the

    PGT10 has met its design goals by providing customers with high performance and high reliability and

    availability while keeping its design simplicity and easy maintenance concepts. To achieve high

    efficiencies over an extended spectrum of power range, an uncommon combination of features has been

    incorporated into the design: High pressure ratio, firing temperature level in line with second generation gas

    turbines, variable axial compressor stator vanes and power turbine nozzles. The PGT10 combustion system

    consists of a single combustion chamber designed for low NOx emissions and is suitable for a large variety

    of gaseous and liquid fuels. Typical applications for PGT10 two-shaft gas turbines are not only natural gas

    compression, centrifugal pump drive and process application, but also power generation as well as

    Cogeneration and Offshore applications.

    Design InfoDesign InfoDesign InfoDesign InfoDesign InfoCompressor

    Axial flow compressor, 17 stages

    Pressure ratio 14.1:1

    Combustion

    Single combustion chamberTurbine (Two shafts)

    High Pressure turbine two stages

    Low Pressure turbine two reaction stages

    Package

    The gas turbine module on a single baseplate includes the engine and a load gear; the

    auxiliaries are installed on a separate baseplate joined to that of the gas turbine to form a

    single lift on which the sound-insulated enclosure is mounted

    The electric generator is installed on a concrete foundation to limit overall shipping

    dimension

    The package design is standardized for quick delivery, but custom applications can be

    provided

    Package dimensions (excluding generator and filters) 9.1mx2.5mx3.0m; Weight: 32t

    Emissions Control

    The combustion system is available both in conventional and DLE configuration to

    satisfy the most stringent environmental regulations

    Steam and water injection systems are available for NOx reduction and power augmenta-

    tion

    Performance InfoPerformance InfoPerformance InfoPerformance InfoPerformance InfoGenerator Drive: Two Shaft version(Expected Performance at ISO Conditions with fuel natural gas)

    Model Output Heat Rate Exhaust Flow Exhaust Temperature

    PGT10 10220 kWe 11540 kJ/kWh 42.1 kg/s 484 C

    Mechanical Drive:Two Shafts version (Expected Performance at ISO Conditions with fuel natural gas)

    Model Output Heat Rate Exhaust Flow Exhaust Temperature

    PGT10 10660 kW 11250 kJ/kWh 42.3 kg/s 493 C

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    12/986NTRODUCTION

    P. 1-8

    GE 10B (single/two shaft) (PGT 10B 1/2)OverviewOverviewOverviewOverviewOverviewThe GE10 is a high efficiency and environmental friendly Heavy Duty Gas Turbine designed and developed

    by Nuovo Pignone for Power Generation (including industrial co-generation) and Mechanical Drive appli-

    cations.Since it was first introduced to the market in 1988, the model PGT10A has been providing high perform-

    ance, reliability and availability to worldwide customers while keeping with easy maintenance concepts.

    From this starting point, in 1998 Nuovo Pignone launched on the market the high performance version of

    this model with two different configurations:

    Two shafts for mechanical drive and single shaft for power generation and cogeneration applications.

    The GE10 Gas Turbine, with its ability to burn different fuels (natural gas, distillate oil, low BTU fuel), can

    be installed in many countries with different environmental conditions: continental, tropical, offshore and

    desert.

    Continuous improvement of the model is carried out with reference to performance and emissions reduction

    capability. In this context particular emphasis has been placed on the design of a DLN system for Nitrogen

    Oxides (NOx) reduction in order to meet present and future standards for pollutant emissions.

    Design InfoDesign InfoDesign InfoDesign InfoDesign InfoCompressor

    Axial flow compressor, 11 stages

    First three stages of stator are variable geometry

    Pressure ratio 15.5:1Combustion

    Single combustion chamber

    Turbine

    Single shaft GE10/1 Two shaft GE10/2

    Three reaction stages High Pressure turbine two reaction stages (cooled)

    First two stages cooled Low Pressure turbine two reaction stages

    Package

    The gas turbine module on a single baseplate includes the engine and the load gear; the auxiliaries

    are installed on a separate baseplate joined to that of the gas turbine to form a single lift on which

    the sound-insulated enclosure is mounted

    The electric generator is installed on a concrete foundation to limit overall shipping dimensions

    The package design is standardized for quick delivery; but custom applications can be provided Package dimensions (excluding generator and filters) LxWxH = 9mx2.5mx3; Weight = 40t

    Emissions Control

    The combustion system is available both in conventional and DLN configuration to satisfy strin-

    gent environmental regulations

    Steam and water injection systems are available for NOx reduction and power augmentation

    Performance InfoPerformance InfoPerformance InfoPerformance InfoPerformance Info

    Generator Drive: Single Shaft version(Expected Performance at ISO Conditions with fuel natural gas)

    Model Output Heat Rate Exhaust Flow Exhaust Temperature

    GE10 11250kW 11467 kJ/kWh 47.3 kg/s 490 C

    Mechanical Drive:Two Shafts version (Expected Performance at ISO Conditions with fuel natural gas)

    Model Output Heat Rate Exhaust Flow Exhaust Temperature GE10 11690 kW 11060 kJ/kWh 46.9 kg/s 487 C

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    13/986INTRODUCTIONS

    P. 1-9

    PGT 16

    OverviewOverviewOverviewOverviewOverviewThe PGT16 gas turbine is composed of the twin spool GE Aeroderivative LM1600 Gas Generator coupled

    with a rugged, industrial power turbine designed by Nuovo Pignone.

    The LM1600 Gas Generator is derived from the F404 turbofan aircraft engine, while the power turbine of the

    PGT16 gas turbine is identical to the power turbine of the PGT10 Nuovo Pignone Heavy Duty, high effi-

    ciency gas turbine, which has been in operation for more than half a million hours.

    The power turbine shaft speed (7900 RPM) is optimized for direct coupling to pipelines and injection and

    process centrifugal compressors with speed ranges that suit all operating conditions.

    High efficiency and reliability are just two of a large number of benefits contributing to LM2500+ customer

    value.

    For generator drive applications the LM1600, coupled to its synchronous generator with a speed reduction

    gear, is a highly flexible turbogenerator that can also cover combined cycle/cogeneration applications with

    an electrical efficiency close to 50%.

    Design Info

    Compressor Twin spool axial compressor (3 stages LP compressor, 7 stages HP compressor)

    Pressure ratio 20.1:1

    Combustion

    Annular combustion chamber (18 fuel nozzles)

    Turbine

    Twin Spool Gas Generator turbine (1 stage HP turbine, 1 stage LP turbine)

    Two stages Power turbine (7900 RPM) with variable angle first stage nozzles

    Package

    The complete gas turbine module is mounted on a single baseplate

    The enclosure is integrated with the baseplate providing maximum accessibility for gas

    turbine and auxiliaries maintenance

    Standard Configuration (excluding inlet/exhaust ducts/system):

    Size LxWxH = 8.1mx2.5mx3.8m

    Weight 19t

    Emissions Control

    Steam or water injection systems for NOx abatement

    Dry Low Emission (DLE) combustion system

    Performance InfoPerformance InfoPerformance InfoPerformance InfoPerformance InfoGenerator Drive: (Expected Performance at ISO Conditions with fuel natural gas)

    Model Output Heat Rate Exhaust Flow Exhaust Temperature

    PGT16 13735 kWe 10314 kJ/kWh 47.4 Kg/s 493 C

    Mechanical Drive: (Expected Performance at ISO Conditions with fuel natural gas)

    Model Output Heat Rate Exhaust Flow Exhaust TemperaturePGT16 14252 kW 9756 kJ/kWh 47.4 kg/s 493 C

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    14/986NTRODUCTION

    P. 1-10

    PGT 25OverviewOverviewOverviewOverviewOverviewThe PGT25 gas turbine consists of the GE Aeroderivative LM2500 Gas Generator coupled with a rugged,

    industrial power turbine designed by Nuovo Pignone. The LM2500 gas generator and the PGT25 power

    turbine demonstrated the best overall performances to cover the 17,000-31,000 HP range with maximumefficiency above 37%.

    The speed of the output shaft, 6500 rpm, as well as the high capacity and simplicity of maintenance have

    made the PGT25 highly suitable for driving direct coupled centrifugal compressors for pipeline service or

    natural gas reinjection plants. Its light weight and high efficiency makes it well suitable for offshore and

    industrial power generation.

    The modular design, extended to all accessory equipment, takes into account the special requirements of

    platform applications (minimum weights and overall dimensions), as well as drastically reduces erection

    time and costs.

    The gas generator can be easily dismantled with a simple translation within the package space, thus reduc-

    ing the time required for maintenance.

    Simplicity of construction and the high quality of the materials employed allow for long intervals between

    overhauls and reduced maintenance costs.

    Design InfoDesign InfoDesign InfoDesign InfoDesign InfoCompressor

    Sixteen stages axial compressor

    Pressure ratio 17.9:1

    Combustion

    Annular combustion chamber (30 fuel nozzles)

    Turbine

    Two stages Gas Generator turbine

    Two stages Power turbine (6500 RPM)

    Package

    The complete gas turbine module comes mounted on a single baseplate

    The enclosure is integrated with the baseplate providing for maximum accessibility for gasturbine and its auxiliaries maintenance

    Standard Configuration (excluding inlet/exhaust ducts/system):

    LxWxH = 9.1mx3.5mx3.7m ,Weight 38t

    Emissions Control

    Steam or water injection systems for NOx abatement

    Dry Low Emission (DLE) combustion system

    Performance InfoPerformance InfoPerformance InfoPerformance InfoPerformance InfoGenerator Drive: (Expected Performance at ISO Conditions with fuel natural gas)

    Model Output Heat Rate Exhaust Flow Exhaust Temperature

    PGT25 22417 kWe 9919 kJ/kWh 68.9 Kg/s 525 C

    Mechanical Drive: (Expected Performance at ISO Conditions with fuel natural gas)Model Output Heat Rate Exhaust Flow Exhaust Temperature

    PGT25 23260 kW 9560 kJ/kWh 68.9 kg/s 525 C

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    15/986INTRODUCTIONS

    P. 1-11

    MS 5001

    OverviewOverviewOverviewOverviewOverviewThe MS5001 single shaft turbine is a compact heavy-duty turbine designed for long life and easy mainte-

    nance.The MS5001 gas turbine is the ideal solution for industrial power generation where low maintenance,

    reliability and economy of fuel utilization are required.

    Low investment costs make the MS5001 package power plant an economically attractive system for peak

    load generation.

    The MS5001 is ideally suited for cogeneration achieving very high fuel utilization indexes and allowing for

    considerable fuel savings. Typical applications are industrial plants for cogeneration of power and process

    steam or in district heating systems.

    Design InfoDesign InfoDesign InfoDesign InfoDesign InfoCompressor

    Axial flow compressor, 17 stages

    Pressure ratio 10.5:1Combustion

    Can-annular combustion, 10 chambers

    Turbine

    2 stages

    First stage nozzles cooled

    Package

    Complete turbine package mounted on a single baseplate

    Enclosure integrated with the baseplate providing maximum accessibility for gas turbine

    and auxiliaries maintenance

    Standard configuration (excluding inlet/exhaust ducts/system):

    size LxWxH = 11.6mx3.2mx3.7m;

    weight 87.5tEmissions Control

    Steam or water injection systems for NOx abatement

    Dry Low NOx (DLN) combustion system

    Performance InfoPerformance InfoPerformance InfoPerformance InfoPerformance InfoGenerator Drive (Expected Performance at ISO Conditions with fuel natural gas)

    Model Output Heat Rate Exhaust Flow Exhaust Temperature

    MS5001 26300 kWe 12650 kJ/kWh 124.1 kg/s 487 C

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    16/986NTRODUCTION

    P. 1-12

    MS 5002OverviewOverviewOverviewOverviewOverviewThe MS5002 gas turbine was launched in the 1970s and it has been updated and up-rated along the years to

    match the higher power demand.

    Presently two versions are available:

    MS5002C - 38000 HP at ISO condition

    MS5002D - 43700 HP at ISO condition.

    The MS5002 is a gas turbine specifically designed for mechanical drive applications with a wide operating

    speed range to meet operating conditions of the most common driven equipment, centrifugal compressors

    and pumps. It also has the capability to burn a large variety of gaseous and liquid fuels.

    Almost 500 units (more than 300 of which were manufactured by Nuovo Pignone) have been installed

    world-wide in all possible environments including arctic, desert, offshore, etc., always demonstrating easy

    operability as well as very high reliability and availability. The simple design and robustness of the ma-

    chine allow for complete maintenance to be performed on site without the need for special tools or service

    shop assistance. Typical applications include Gas Boosting, Gas Injection/Reinjection, Oil & Gas Pipelines,

    LNG plants and Gas Storage

    Design InfoDesign InfoDesign InfoDesign InfoDesign Info

    CompressorMS5002C

    Sixteen stages axial compressor

    Pressure ratio 8.9:1

    MS5002D

    Seventeen stages axial compressor

    Pressure ratio 10.8:1

    Combustion

    Reverse flow, multi chamber (can-annular) combustion system (12 chambers)

    Turbine

    Single stage Gas Generator turbine

    Single stage power turbine (4670 RPM rated speed) with variable angle nozzles.

    Package

    Two baseplates configuration (gas turbine flange to flange unit and auxiliary system.

    Enclosures integrated with the baseplates providing maximum accessibility for gas turbine

    and auxiliaries maintenance

    Standard configuration (excluding inlet/exhaust ducts/system):

    size LxWxH = 15.0mx3.2mx3.8m

    weight 110t

    Emissions Control

    Steam or water injection systems for NOx abatement

    Dry Low NOx (DLN) combustion system

    Performance InfoPerformance InfoPerformance InfoPerformance InfoPerformance InfoMechanica Drive (Expected Performance at ISO Conditions with fuel natural gas)

    Model Output Heat Rate Exhaust Flow Exhaust Temperature

    MS5002C 28340 kW 12310 kJ/kWh 126.0 kg/s 515 C

    MS5002D 32590 kW 11900 kJ/kWh 141.3 kg/s 510 C

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    17/986INTRODUCTIONS

    P. 1-13

    PGT 25+

    OverviewOverviewOverviewOverviewOverviewThe PGT25+ gas turbine has been developed for 30 MW ISO shaft power service with the highest thermal

    efficiency level (approx. 40%).The PGT25+ gas turbine consists of the GE Aeroderivative LM2500+ Gas Generator (updated version of

    LM2500 gas generator with the addition of zero stage to axial compressor) coupled with a 6100 RPM Power

    Turbine. Built on the LM2500 heritage and with demonstrated 99.6% reliability, the PGT25+ incorporates

    proven technology improvements and a large percentage of parts in common with LM2500 in order to

    deliver the same outstanding level of reliability. Designed for its ease of maintenance, the PGT25+ also

    provides a high level of availability.

    High efficiency and reliability are just two of large number of benefits contributing to PGT25+ customer

    value.

    Application flexibility makes the PGT25+ ideal for a range of mechanical drive (gas pipeline etc.), power

    generation, industrial cogeneration and offshore platform applications in any environment.

    Design InfoDesign InfoDesign InfoDesign InfoDesign Info

    Compressor Seventeen stages axial compressor

    Pressure ratio 21.5:1

    Combustion

    Annular combustion chamber (30 fuel nozzles)

    Turbine

    Two stage Gas Generator turbine

    Two stage Power turbine (6100 RPM)

    Package

    Gas Generator, Power Turbine and auxiliary System mounted on a single baseplate

    The enclosure is integrated with the baseplate providing maximum accessibility for gas

    turbine and auxiliaries maintenance

    Standard Configuration (excluding inlet/exhaust ducts/system):

    size LxWxH = 6.5mx3.6mx3.9m (gas turbine and auxiliary baseplate)

    weight 38t (gas turbine and auxiliary baseplate)

    Emissions Control

    Steam or water injection systems for NOx abatement

    Dry Low Emission (DLE) combustion system

    Performance InfoPerformance InfoPerformance InfoPerformance InfoPerformance InfoGenerator Drive: (Expected Performance at ISO Conditions with fuel natural gas)

    Model Output Heat Rate Exhaust Flow Exhaust Temperature

    PGT25+ 30226 kWe 9084 kJ/kWH 84.3 Kg/s 500 C

    Mechanical Drive: (Expected Performance at ISO Conditions with fuel natural gas)Model Output Heat Rate Exhaust Flow Exhaust Temperature

    PGT25+ 31360 kW 8754 kJ/kWh 84.3 kg/s 500 C

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    18/986NTRODUCTION

    P. 1-14

    MS 6001

    OverviewOverviewOverviewOverviewOverviewThe MS6001 is a single shaft heavy-duty gas turbine. Its design was based on the well proven mechanical

    features of the MS5001 in order to achieve a compact, high efficency unit.The MS6001 is widely applied in power generation applications for base, mid-range and peak load service.

    Other typical applications include driving of process machines, such as compressors, in LNG plants.

    Combined cycle plants based on MS6001 achieve very high efficiencies with higher availability and

    reliability than conventional thermal plants.

    Design InfoDesign InfoDesign InfoDesign InfoDesign InfoCompressor

    Axial flow compressor, 17 stages

    Pressure ratio 11.9:1

    Combustion

    Can-annular combustion, 10 chambers

    Dual fuel capability

    Turbine 3 stages, first two cooled buckets

    First 2 stage nozzles cooled

    Package

    Complete turbine package mounted on a single baseplate

    Enclosure integrated with the baseplate providing for maximum accessibility for gas

    turbine and its auxiliaries maintenance

    Standard configuration (excluding inlet/exhaust ducts/system):

    size LxWxH = 15.9mx3.2mx3.8m;

    weight 96t

    Emissions Control

    Steam or water injection systems for NOx abatement

    Dry Low NOx (DLN) combustion system

    Performance InfoPerformance InfoPerformance InfoPerformance InfoPerformance InfoGenerator Drive: (Expected Performance at ISO Conditions with fuel natural gas)

    Model Output Heat Rate Exhaust Flow Exhaust Temperature

    MS6001B 42100 kWe 11230 kJ/kWh 145.8 kg/s 552 C

    Mechanical Drive: (Expected Performance at ISO Conditions with fuel natural gas)

    Model Output Heat Rate Exhaust Flow Exhaust Temperature

    MS6001B 43530 kW 10825 kJ/kWh 145 kg/s 544 C

    ExperiencesExperiencesExperiencesExperiencesExperiences

    More than 46 units sold

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    19/986INTRODUCTIONS

    P. 1-15

    LM 6000

    OverviewOverviewOverviewOverviewOverviewThe GE LM6000 delivers more than 44.8 MW of power at over 42.7% thermal efficiency.

    It is the worlds most fuel-efficient, simple-cycle gas turbine. High efficiency, low cost and easy installationmake the LM6000 the perfect modular building block for electrical power applications such as industrial

    cogeneration of utility peaking, both midrange and base-load operations. As an aircraft engine aboard the

    Boeing 747, the LM6000 has logged more than 10 million flight hours, with the lowest shop visit rate of

    any jet engine.

    Continuing the tradition of GEs LM6000 established record, the LM6000 is ideal as a source of drive-

    power for pipeline compression, offshore platforms, gas reinjection and LNG compressors. The LM6000 has

    been GEs first aeroderivative gas turbine to employ the new Dry-Low Emission premixed combustion

    system; this system is retrofittable on LM6000s already in operation. Water or steam injection can also be

    used to achieve low NOx emissions.

    Design InfoDesign InfoDesign InfoDesign InfoDesign InfoCompressor

    Low pressure compressor 5 stages

    High pressure compressor 14 stages

    Pressure ratio 30:1Combustion

    Annular combustion chamber

    Turbine

    High Pressure turbine 2 stages

    Low Pressure turbine 5 stages

    Package

    Gas Generator, Power Turbine and auxiliary system mounted on a single baseplate

    The enclosure is integrated with the baseplate providing maximum accessibility for gas

    turbine and auxiliaries maintenance

    Standard configuration (excluding inlet/exhaust ducts/system):

    size LxWxH = 9.3mx4.2mx4.4m

    weight 31t

    Emissions Control

    Steam or water injection system for NOx abatement

    Dry Low Emission (DLE) combustion system

    Performance InfoPerformance InfoPerformance InfoPerformance InfoPerformance Info

    Generator Drive: (Expected Performance at ISO Conditions with fuel natural gas)

    Model Output Heat Rate Exhaust Flow Exhaust Temperature

    LM6000 43076 kWe 8707 kJ/kWh 131 Kg/s 450 C

    Mechanical Drive: (Expected Performance at ISO Conditions with fuel natural gas)

    Model Output Heat Rate Exhaust Flow Exhaust TemperatureLM6000 44740 kW 8455 kJ/kWh 127 kg/s 456 C

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    20/986NTRODUCTION

    P. 1-16

    MS 7001

    OverviewOverviewOverviewOverviewOverviewThe MS7001EA is a single shaft heavy-duty gas turbine for power generation and industrial applications

    requiring the maximum reliability and availability.With design emphasis placed on energy efficiency, availability, performance and maintainability, the

    MS7001EA is a proven technology machine with more than 500 units of its class in service.

    Typical applications in addition to the 60Hz power generation service are large compressor train drives for

    LNG plants.

    Design InfoDesign InfoDesign InfoDesign InfoDesign InfoCompressor

    Seventeen stages axial compressor

    Pressure ratio 12.5:1

    Combustion

    Reverse flow, multi chamber (can-annular) combustion system (10 chambers)

    Turbine

    Three stages turbine (3600 RPM)

    Package

    Two baseplates configuration (gas turbine flange to flange unit and auxiliary system)

    Enclosures integrated with the baseplates providing maximum accessibility for gas turbine

    and auxiliaries maintenance

    Standard configuration (excluding inlet/exhaust ducts/system):

    size LxWxH = 11.6mx3.3mx3.8m

    weight 121t

    Emissions Control

    Steam or water injection systems for NOx abatement

    Dry Low NOx (DLN) combustion system

    Performance InfoPerformance InfoPerformance InfoPerformance InfoPerformance Info

    Generator Drive: (Expected Performance at ISO Conditions with fuel natural gas)

    Model Output Heat Rate Exhaust Flow Exhaust Temperature

    MS7001EA 85100 kWe 11000 kJ/kWh 300 kg/s 537 C

    Mechanical Drive: (Expected Performance at ISO Conditions with fuel natural gas)

    Model Output Heat Rate Exhaust Flow Exhaust Temperature

    MS7001EA 81590 kW 11020 kJ/kWh 278 kg/s 546 C

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    21/986INTRODUCTIONS

    P. 1-17

    MS 9001OverviewOverviewOverviewOverviewOverviewThe MS9001E is a single shaft heavy-duty gas turbine. It was developed for generator drive service in the 50

    Hertz market.The MS9001E is widely applied in power generation for base, mid-range and peak load service.

    Combined cycle plants based on MS9001E achieve very high efficiencies with higher availability and

    reliability than conventional thermal plants.

    Design InfoDesign InfoDesign InfoDesign InfoDesign InfoCompressor

    Axial flow compressor, 17 stages

    Pressure ratio 12.6:1

    Combustion

    Can-annular combustion, 14 chambers

    Dual fuel capability

    Turbine

    3 stages, first two cooled buckets

    First 2 stage nozzles cooledPackage

    Two baseplates configuration (gas turbine flange to flange unit and auxiliary system)

    Enclosures integrated with the baseplates providing maximum accessibility for gas turbine

    and auxiliaries maintenance

    Standard configuration (excluding inlet/exhaust ducts/system):

    size LxWxH = 22.1mx4.5mx6.3m

    weight 217.5

    Emissions Control

    Steam or water injection systems for NOx abatement

    Dry Low NOx (DLN) combustion system

    Performance InfoPerformance InfoPerformance InfoPerformance InfoPerformance Info

    Generator Drive: (Expected Performance at ISO Conditions with fuel natural gas)

    Model Output Heat Rate Exhaust Flow Exhaust Temperature

    MS9001E 123400 kWe 10650 kJ/kWh 412.8 kg/s 543 C

    ExperiencesExperiencesExperiencesExperiencesExperiences

    44 Units sold

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    22/986NTRODUCTION

    P. 1-18

    GE 5 (1/2 shaft) 5,2 - 5,4 MW 26,9 %

    GE 5 B 5,9 - 6,2 MW 32 %

    PGT 10 10,5 MW 32,6 %

    GE 10 B(1/2 shaft) 11,7 MW 33 %

    PGT 16 14,2 MW 36,9 %

    PGT 25 23,2 MW 37,7 %

    MS 5001 26,3 MW 28,5 %

    MS 5002 C-D 28,3 -32,5 MW 29,2 - 30,3%

    PGT 25+ 29,9 MW 40, 3 %

    MS 6001 B 42 MW 32,5 %

    LM 6000 44,8 MW 41,1 %

    MS 7001 EA 81,5 MW 32,7 %

    MS 9001 E 123,4 MW 33,8 %

    GE 2 2,0MW 25 %

    TYPE POWER MAX EFFiCIENCY

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    23/986MOD. ARGE 2/S

    INDEX

    CHAP. 2Page

    2. THEORETICAL OPERATING SCHEME .........................................................2-1

    2.1 OPERATING PRINCIPLE ........................................................................2-2

    2.2 MAIN COMPONENT PARTS OF A GAS TURBINE .............................2-4

    2.2.1 Compressor .....................................................................................2-5

    2.2.2 Combustion section ........................................................................2-62.2.3 Turbine section ...............................................................................2-7

    2.3 BRAYTON CYCLE ...................................................................................2-7

    2.4 INFLUENCE OF EXTERNAL FACTORS ON

    GAS TURBINE PERFORMANCE .........................................................2-14

    2.5 INFLUENCE OF INTERNAL FACTORS ON

    GAS TURBINE PERFORMANCE .........................................................2-16

    09-98-E P. 2-0

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    24/986MOD. ARGE 2/S

    09-98-E P. 2-1

    2. THEORETICAL OPERATING SCHEME

    Fig. 2.1 shows an example of a gas turbine (in this specific case, it is our MS6001 gasturbine) with a sectional view of the machine properly said. This figure has the purpose

    to highlight the main component parts involved in the operating cycle.

    Fig. 2.1 - Example of a simple cycle gas turbine (single shaft)

    The main component parts illustrated in Fig. 2.1 are:

    machine, generally calledflange - flange

    auxiliary equipment

    baseplate

    The above systems are completed by the suction, exhaust and control systems,

    which, like the auxiliary equipment and the baseplate, are dealt with in the relevant

    chapters, whereas here only details about their arrangement and interface with the

    flange-flange assembly (Fig. 2.1) are described.

    In fact, this chapter deals exclusively with the operating principles of a flange-

    flange.

    BASAMENTO

    AUSILIARI FLANGIA-FLANGIA

    BASEPLATE

    FLANGE TO FLANGEAUXILIARIES

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    25/986MOD. ARGE 2/S

    09-98-E P. 2-2

    2.1 OPERATING PRINCIPLE

    A gas turbine works in the following way:

    it aspirates air from the surrounding environment;

    it compresses it to a higher pressure;

    it increases the energy level of compressed air by the addition of fuel gas

    which undergoes combustion in a combustion chamber;

    it directs high pressure and high temperature air to a turbine section, which

    converts thermal energy into mechanical energy that makes the shaftrevolve; this serves, on the one hand, to supply useful energy to the driven

    machine, coupled to the machine by means of a coupling and, on the other

    hand, to supply energy necessary for air compression, which takes place in

    a compressor connected directly with the turbine section itself;

    it expels low pressure and low temperature gases resulting from the above-

    mentioned converting process into the atmosphere.

    Fig. 2.2 overleaf shows the behavioral pattern of pressures and temperatures, in

    terms of quality, inside the different machine sections corresponding to the above-

    mentioned operating phases.

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    26/986MOD. ARGE 2/S

    09-98-E P. 2-3

    Fig. 2.2

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    27/986MOD. ARGE 2/S

    09-98-E P. 2-4

    Fig. 2.2 enhances the fact that combustion takes place under almost constant

    pressure conditions.

    Unlike alternative motors, compression and expansion take place on a continualbasis, as happens for power generation.

    On the contrary, in an alternative motor (for ex., a four-stroke, eight cycle motor),

    though power is generated in the expansion phase, like in a turbine, this process

    takes only 1/4 of the complete cycle, whereas in a gas turbine expansion takes place

    continually all through the cycle. The same applies to compression.

    For the same reason, along with the fact that there are no masses in alternate

    motion, the degree of regularity of the running cycle of a gas turbine is incomparably

    greater than that of an alternative motor (eight or Diesel cycle).

    2.2 MAIN COMPONENT PARTS OF A GAS TURBINE

    Fig. 2.3 - A sectional View of a Gas Turbine

    A gas turbine (Fig. 2.3) is composed of three main sections, described in the following

    paragraphs. As concerns design and construction features, these are extensively dealt with in

    Chapter 3.

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    28/986MOD. ARGE 2/S

    09-98-E P. 2-5

    2.2.1 Compressor

    The compressor shall be of the axial type (Fig. 2.3). The choice of this typeof compressor depends on the fact that this compressor is capable to deliver

    high air output ratings, necessary to obtain high values of useful power in a

    reduced size. This concept will be resumed later, when the main

    thermodynamic ratios in the operating cycle of a gas turbine are described.

    A compressor consists of a series of stages of rotating blades, which increase

    air speed in terms of kinetic energy, followed alternately by stages of stator

    blades, which convert kinetic energy into higher pressure.

    The number of compression stages is related to the structure of the gas

    turbine and, above all, to the compression ratio to be obtained.At the compressor inlet side, there are Inlet Guide Vanes (or, IGV), whose

    primary purpose is to direct air, delivered by the suction system, towards the

    first stage of rotating blades. Another important function of IGVs is to

    ensure a correct behaviour by the compressor, in terms of fluid dynamics,

    under different transient operating conditions (for example, during start-up

    and shut down) when, due to different running speeds as apposed to normal

    operating speed, the opening angle of IGVs is changed: this serves to vary

    the air delivery rate and to restore ideal speed triangles in transient phases.

    Finally, in combined cycles and in the co-generation process, the capability

    to change the geometrical position of IGVs permits to optimise temperaturesat the turbine exhaust side and, thus, to increase the efficiency of the recovery

    cycle by varying the flow rate of the air entering the compressor.

    At the compressor output side there are a few stages of Exit Guide Vanes or

    EGV, necessary to obtain maximum pressure recovery before air enters the

    combustion chamber.

    The compressor serves also to supply a source of air needed to cool the walls

    of nozzles, buckets and turbine disks, which are reached via channels inside

    the gas turbine, and via external connecting pipings. Additionally, the

    compressor supplies sealing air to bearing labyrinth seals.

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    29/986MOD. ARGE 2/S

    09-98-E P. 2-6

    2.2.2 Combustion Section

    In the case of "heavy duty" gas turbines as the one shown in Fig. 2.3, thecombustion section consists of a system of one or more tubular combustion

    chambers (in this specific case there are ten combustion chambers) arranged

    symmetrically and evenly in a circumference; these chambers receive and

    burn fuel by means of an equal number of burners (one per combustion

    chamber).

    Air enters each chamber with a flow direction inverse to that of the hot gases

    inside (for this reason, this method of air distribution is called "reverse

    flow"). This external flow, which marginally touches the various chambers,

    serves to cool them. In addition, the part of air that does not take part in thecombustion process is used for cooling the combustion products; in fact, it

    is introduced into the chambers through diluition holes until optimal

    temperature conditions are established to allow the gas and air mixture into

    the turbine section.

    Air passage from the combustion section properly said to the gas turbine

    inlet takes place inside manifolds called transition pieces; here, the gases

    flowing out of the single combustion chambers are led to form a continuous

    annular profile, equal to the one that leads into the first stage nozzles ring.

    Initially, the combustion process is ignited by one or more spark plugs. Once

    ignited, combustion proceeds in a self-sufficient way without the help of

    spark plugs, as long as the delivery conditions of fuel and combustion air are

    fulfilled.

    In the case of gas turbines built for the aviation industry (LM , PGT16 and

    25 range), the combustion section consists of a single chamber of toroidal

    shape, with direct and not "reverse flow" cooling; in fact, this helped reduce

    external diametral sizes, since a smaller frontal section was needed in order

    to offer as little resistance as possible to aircraft motion.

    For the same reason, this combustion chamber does not need any separate

    transition pieces. The other operating principles are the same as those

    described for tubular chambers.

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    30/986MOD. ARGE 2/S

    09-98-E P. 2-7

    2.2.3 Turbine Section

    In the case of "heavy duty" turbines, as shown in Fig. 2.1, the turbine sectioncomprises a certain number of stages (in this specific case, three stages), each

    one of them consisting of one stator stage (distributor nozzle); in this stage,

    high temperature and high pressure gases delivered by the transition piece

    described beforehand are accelerated and directed towards the rotor stage of

    buckets mounted on a disk connected with the power shaft.

    As mentioned before (para. 2.1), the conversion of thermal energy and

    pressure into kinetic energy takes place in the stator stage.

    The rotor stage completes this conversion, as here kinetic energy is

    transformed into energy that drives the shaft, thus generating the power

    required to drive the compressor (internal compression work, cannot be usedas externally useful work) and to operate the driven machine (generator,

    compressor, etc.) connected to the gas turbine by means of a coupling.

    The energy of gases supplied by the combustion system can be varied by

    changing the delivery rate of fuel. In this way you can regulate the useful

    power values needed for the technological process of which the gas turbine

    is the motor.

    2.3 BRAYTON CYCLE

    The thermodynamic cycle according to which a gas turbine works is known asthe Brayton cycle.

    Fig. 2.4 illustrates a diagram of a gas turbine (in this specific case, an MS6001

    single shaft turbine). This diagram is useful to understand the meaning of the

    thermodynamic cycle more easily.

    Fig. 2.4 - Gas Turbine Operating Diagram

    Air enters the compressor at point (1), which represents ambient air conditions. These

    conditions are classified according to pressure, temperature and relative humidity values.

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    31/986MOD. ARGE 2/S

    09-98-E P. 2-8

    It was agreed that standard design conditions be classified as ISO Conditions, to which there

    correspond the following reference values:

    ISO CONDITIONS

    Ambient temperature (C) 15

    Ambient pressure (mbar) 1013

    Relative humidity (%) 60

    Afterwards, air is compressed inside the compressor, and exits in the condition indicated at

    point (2). During the converting process from (1)to(2),no heat is released outside. However,air temperature increases, due to polytropic compression, up to a value variable depending on

    gas turbine model and ambient temperature.

    After leaving the compressor, air enters the combustion area, practically under the same

    pressure and temperature conditions as at point (2)(except for losses undergone on the wayfrom the compressor delivery side to the combustion chamber inlet, which amount to about 3

    to 4% of the absolute value of delivery pressure). Fuel is injected into the combustion chamber

    via a burner, and combustion takes place at practically constant pressure.

    Conversion between points(2)and(3)represents not only combustion. In fact, the temperature

    of the combustion process properly said, which takes place under virtually stechiometric

    conditions, reaches excessively high values (around 2000 C) locally in the combustion area

    next to the burner, due to the resistance of materials downstream.

    Therefore, the conversion final temperature, relative to point(3),is lower, as it is the result ofprimary gases mixing with cooling and dilution air as described previously.

    In this regard, it is useful to give some definitions of temperature at point (3), which is the

    maximum cycle temperature or firing temperature (see Fig. 2.5).

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    32/986MOD. ARGE 2/S

    09-98-E P. 2-9

    Fig. 2.5 - Firing temperature

    SectionA refers to the so-called "turbine inlet temperature", which is the averagetemperature of gases in plane A.

    Section Brefers to the so-called firing temperature, which is the average gas

    temperature in plane B.

    SectionCrefers to the so-called ISO firing temperature", which is the average gas

    temperature in plane C, calculated as a function of the air and fuel flow rates via

    a thermal balance of combustion according to the ISO 2314 procedure.

    The difference in the interpretation of temperatures in sections Aand Bconsists

    in the fact that, on gas turbines like those which we are dealing with in this training

    course, in section Bwe take into account the mixture of 1st stage nozzle cooling

    air, which was not involved in the combustion process, but mixes with burnt gasesafter cooling the surface of the nozzle.

    According to the Nuovo Pignone - General Electric standard, the temperature that

    best represents point (3)is the one in section B.

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    33/986MOD. ARGE 2/S

    09-98-E P. 2-10

    The following transformation, comprised between points (3) and (4), represents

    the expansion of gases through the turbine section, which, as mentioned before,

    converts therma energy and pressure into kinetic energy and, thanks to therevolutions of the power shaft, into work used for compression (internal, not

    useable) and external useful work, thanks to the connection with an operating

    machine.

    Over 50% of the energy developed by expansion in the gas turbine is absorbed by

    the axial compressor for its compressing work.

    Downstream of section (4), gases are exhausted into the atmosphere.

    The thermodynamic representation of the events described so far is visible in Fig.

    2.6 (pressure diagrams - volume P-V and temperature - entropy T-S).

    Fig. 2.6 - Brayton Cycle

    In the cycle illustrated in the above figure, the 4 points correspond to the same

    described before.

    In particolar, note the compression and expansion transformations, obviously

    these are not isoentropic.

    In this respect, please remember that:

    thespecific compression work Wc

    , from (1) to(2), is expressed with good

    approximation by the following ratio:

    Wc = Cpm(T2-T1) (T2-T1) (Kj/Kgasp. air)

    thespecific expansion work Wt

    , from(3) through(4), is expressed by:

    Wt = Cpm(T3-T4) (T3-T4) (Kj/Kggas.)

    Heat Q1, supplied to the combustion chamber from(2)to(3),is expressed by:

    Q1 = Cpm(T3-T2) (T3-T2) (Kj/Kggas.)

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    34/986MOD. ARGE 2/S

    09-98-E P. 2-11

    The gas turbine cycle "closes" ideally with the transformation from (4)to (1),

    which corresponds to the cooling of exhaust gases, in that heat Q2is aspirated out

    into the atmosphere, as though the latter were a refrigerant of infinite capability.The thermodynamic ratio that describes the cooling process of exhaust gasesis

    the following:

    Q2 = Cpm(T4-T1) (T4-T1) (Kj/Kggas.)

    The various values for Cpm

    , expressed in the preceding ratios, represent the average

    specific heat at constant pressure between the extreme temperature values in the

    interval examined.

    For a more rigorous evaluation, it would be necessary to proceed by means of

    integral calculation.

    Once Q1, Q

    2, W

    cand W

    t, are known, you can obtain the valuesforthe following

    significant parameters:

    Thermodynamic efficiency= (Q1- Q

    2)/Q

    1

    This ratio means that, by parity of heat Q1, introduced into the combustion chamber

    by fuel, efficiency will increase as heat Q2

    decreases, dissipated into the

    atmosphere. We will see in Chap. 8 how to recover this heat partially in combined

    cycles and in the regenerative cycle.

    Useful work Nusupplied to the driven machine= G

    gasW

    t- G

    ariaW

    c

    In the latter ratio, Ggas and Garia correspond respectively the weight of gasesdelivered to the turbine inlet section, and to the air aspirated by te compressor,

    necessary to pass from specific to global values.

    So far, all descriptions and examples refer to a single shaft turbine like MS 6001.

    In fact, in the diagram illustrated in Fig. 2.4, the entire turbine section is connected

    mechanically witht the axial compressor.

    Such types of single shaft turbines are suitable for driving operating machines that

    run at constant speed, such as alternators and, for this reason, are used typically in

    the generation of electric energy.

    In applications, in which power regulation is achieved by means of speed variationin the driven machine, two-shaft gas turbines are usually employed (see diagram

    in Fig. 2.7); in this case, the turbine is divided into two mechanically separate

    sections:

    A high pressure section, which runs at constant speed within a wide range

    of powers, and drives exclusively an axial compressor.

    A low pressure section, connected with the operating machine via a coupling;

    this section can vary its running speed independent of the high pressure

    turbine section.

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    35/986MOD. ARGE 2/S

    09-98-E P. 2-12

    This configuration, with the addition of other elements which will be described in

    Chapter 4, serves to regulate the driven machine speed without the need to vary the

    speed of the axial compressor; thus, the latter may continue to run at its designspeed, with optimal efficiency.

    Fig. 2.7 - Two Shaft Gas Turbine Diagram

    The ratios described so far apply in general to all machine types.

    The classical concepts of thermodynamics permit to give a correct evaluation to

    the Brayton cycle and to the influence by parameters such as pressures, temperatures,

    specific heats, polytropic exponents, etc.

    A diagram in Fig. 2.8 expresses the ratios among the following parameters:

    Firing temperature T3(C) Compression ratio

    Thermal efficiency

    Specific power (KW/(Kg/sec.))

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    36/986MOD. ARGE 2/S

    09-98-E P. 2-13

    Fig. 2.8 - Relations between significant thermodynamic quantities

    This diagram indicates that:

    a) under equal temperature T3, maximum efficiency is reached by increasing

    the compression ratio. The maximum efficiency value does not corresponds

    to the maximum specific power.

    b) The higher the increase in the compression ratio, the greater the benefit

    provided by increased firing temperature T3

    for specific power and

    efficiency values.

    However, it is not possible to exceed certain values for T3, because of

    limitations imposed by the resistance of the materials currently available.

    The increase in temperature T3represents therefore a very important parameter

    that requires vast and constant efforts in the research about materials, blade

    cooling technology, etc., in order to achieve reliable and efficient products

    capable to meet ever growing demands by the market.

    c) Specific power is important, because, to a higher specific power there

    corresponds a gas turbine of smaller size, though of equal power output.

    d) Efficiency is important, because the higher the efficiency, the lower the

    consumption and operating costs.

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    37/986MOD. ARGE 2/S

    09-98-E P. 2-14

    2.4 INFLUENCE OF EXTERNAL FACTORS ON GAS TURBINE PER-

    FORMANCE

    A gas turbine uses ambient air, therefore, its performance is greatly affected by allfactors that influence the flow rate of air delivered to the compressor, in terms of

    weight.

    These factors are:

    Temperature

    Pressure

    Relative humidity

    In this regard, we remind you that reference conditions for the three above-

    mentioned factors are, by convention, ISO standards (para. 2.3).

    As the compressor inlet temperature increases, there increases the specific

    compression work, while the weight of the air delivered decreases (because of a

    decrease in specific weight ). Consequently, the turbine efficiency and useful

    work (and, therefore, power) diminish as well. If temperature decreases, the

    reverse occurs.

    This dependence of temperature on the air aspirated by the compressor and power

    and efficiency varies from turbine to turbine, according to cycle parameters,

    compression and expansion output and air delivery rate.

    Fig. 2.9 shows an example of how power, specific consumption (heat rate) and the

    delivery rate of exhaust gases depend on ambient temperature.

    Fig. 2.9 - Influence of ambient temperature on turbine performance

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    38/986MOD. ARGE 2/S

    09-98-E P. 2-15

    Specific consumption, dimensionally represented in figure 2.9 as HEAT RATE,

    is the inverse of efficiency, in that it indicates the ratio between thermal energy,

    resulting from the combustion process, and mechanical energy, supplied to thepower shaft (or to the generator terminals, if we consider the performance of a load

    gear and generator, if present).

    To summarise, we call Q1

    the energy resulting from combustion and Nu the

    external useful work: thus, specific consumption or Heat Rate is defined as:

    HR = Q1/Nu

    and is generally expressed as Kj/Kwh.

    If the atmospheric pressure decrases in comparison with the ISO reference

    pressure, there decreases the weight of air delivered (because of a reduction in its

    specific weight) and, proportionally, there decreases the useful power, which is

    proportional to the weight of the gas delivered. On the contrary, the other

    parameters of the thermodynamic cycle (HR, etc.) are left uninfluenced.

    Fig. 2.10 shows the percentage pattern of the useful power of a gas turbine in

    relation to its installation altitude.

    Fig. 2.10

    ATMOSPHERIC

    PRESSURE

    ALTITUDE - 1000 FEET

    CORRECTION

    FACTOR

    CORRECTION

    FACTOR

    ATMOSPHERIC

    PRESSURE

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    39/986MOD. ARGE 2/S

    09-98-E P. 2-16

    Relative humidity influences the specific weight of air aspirated by the compressor.

    In fact, humid air is less dense than dry air, so if the relative humidity increases,there

    decreases the power output and there increases specific consumption (HR) (Fig.2.11).

    In the past, such an effect used to be neglected. Nowadays, as ever more powerful

    gas turbines are made and humidity is added in the form of water or steam by

    reduction of NOx, this effect must be taken into consideration.

    Fig. 2.11

    2.5 INFLUENCE OF INTERNAL FACTORS ON GAS TURBINE PERFORM-

    ANCE

    Next to the three external factors described in the preceding paragraph, there are

    other factors which notably affect the performance of a gas turbine. These may be

    called internal factors, because they are related to the auxiliary systems of the gas

    turbine.

    They are the following:

    Pressure drop in the compressor inlet section

    Pressure drop in the turbine exhaust system

    Fuel type

    Air extraction from the axial compressor

    Steam injection

    Water injection

    Evaporative cooling

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    40/986MOD. ARGE 2/S

    09-98-E P. 2-17

    Pressure drops in the compressor inlet section

    Pressure drops are caused by the gas turbine suction system, composed of an

    airfiler, a silencer, a length of duct, pipe section regulators, etc., installed upstreamof the compressor suction flange. When air flows through this system, it is

    subjected to friction, which reduces its pressure and thus its specific weight. These

    drops cause a reduction in useful power and an increase in specific consumption

    or "heat rate", as mentioned previously in the case of the influence exerted by

    ambient pressure.

    Pressure drops in the turbine exhaust system

    These are caused by the exhaust system of the gas turbine, composed of one or

    more silencers, a length of duct, a recovery boiler (in the case of combined cycles

    or co-generation), diverters, shutters, etc., through which exhaust gases areexpelled into the atmosphere.

    Exhaust gases flowing through this system are subjected to friction, which

    increases the value of back pressure as opposed to the value of external, atmospheric

    pressure. This reduces the amount of turbine expansion, as the latter terminates

    one isobar higher than the reference one, which results in reduced useful power

    and increased specific consumption (heat rate).

    Table 2.1 reports the typical values by which performance is dependent on pressure

    drops at the compressor inlet section and at the turbine exhaust section. For the

    reasons explained above, this dependance is proportional to the values of pressure

    drop.TABLE 2.1 EFFECTS OF PRESSURE DROPS

    Every 100 mm H2O at suction : Every 100 mm H2O at exhaust :

    1.42 % power loss 0.42 % power loss

    0.45 % increase in Heat Rate 0.42 % increase in Heat Rate

    1 C increase in exhaust temperature 1 C increase in exhaust temperature

    Fuel gas influence

    Best performance is achieved if natural gas rather than diesel oil is used. In fact,

    output power under base load power and under equal conditions (environmental,pressure drops , etc.) will be about 2% greater and specific consumption (Heat

    Rate) between 0.7 and 1% lower, depending on gas turbine model.

    These differences will become all the more remarkable if we compare performances

    obtained with natural gas and with progressively "heavier"fuel types, such as

    residuals, Bunker C, etc.

    This behavior is due to the higher heating power of products originated by the

    combustion of natural gas, as the latter has a higher content of water vapour,

    resulting from a higher ratio between hydrogen and carbon, which is typical of

    methane, the main component part of natural gas.

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    41/986MOD. ARGE 2/S

    09-98-E P. 2-18

    Gaseous fuels with a lower calorific value than natural gas (commonly called "low

    btu gases") can greatly influence the performance of a gas turbine.

    In fact, if the calorific value diminishes (Kj/Nm3

    ), the weight of fuel delivered tothe combustion chamber must increase to provide the necessary amount of energy

    (Kj/h).

    This addition in the weight of the fluid, which is not even compressed by the

    compressor, provokes an increase in power (see the definition of useful workat

    para. 2.3) and a reduction in specific consumption.

    In this case, the power absorbed by the compressor is left substantially unvaried.

    However, in the case of combustion of low btu gases, the following side effects

    must be taken into consideration:

    An increase in the weight of fluid delivered to the turbine increases thecompression ratio in the compressor, which must not come too near the

    surging limit.

    An increase in the fuel delivered often requires larger diameters of tubings

    and control valves (and, consequently, higher costs). This effect is all the

    more conspicuous in the case in which also the temperature of a gas and,

    therefore, its specific volume, are higher (for example, gases produced by

    coal gassing).

    Gases with a low calorific value are frequently enough saturated with water

    vapour upstream of the gas turbine combustion system. This provokes an

    increase in the coefficients of heat transmission by combustion products,and an increase in metal temperature on hot parts of the turbine.

    Air extraction from the axial compressor

    On some gas turbine applications (chemical processes, pipe blowing during the

    commissioning stage, etc.) it may become necessary to extract compressed air

    from the compressor delivery side.

    As a general rule, and unless prescribed otherwise in the case of machines

    originally built for the aviation industry, it is possible to extract as much as 5% of

    the air delivered by the compressor without the need to alter the turbine layout at

    all.It is possible to achieve extraction values ranging between 6 and 20 % , depending

    on the machine and combustion chamber configuration, if alterations are made to

    casings, pipings and the control system.

    Fig. 2.12 shows how percentages of air extraction influence output power and

    specific consumption (heat rate), taking into consideration also ambient temperature.

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    42/986MOD. ARGE 2/S

    09-98-E P. 2-19

    Fig. 2.12

    Steam injection and water injection

    Steam or water injection may have the following two purposes:

    a reduction in nitrogen oxide (NOx) level.

    an increase in output power.

    Reducing the nitrogen oxide (NOx) level

    The method of steam or water injection was introduced in the early 70s to limit and

    control the presence of nitrogen oxides or NOX.

    Injection is usually performed in the area where the combustion chamber cap is

    present. The injection system is built in a way to set a limit to the amount of

    injectable steam or water, in order to safeguard stability and continuity in the

    combustion process. Anyway, the amount of steam and water injected is sufficientto guarantee a massive reduction in the level of NOx.

    According to the amount of steam or water injected into the combustion chamber,

    which the turbine control system automatically monitors in relation to the NOx

    level desired, output power will increase consequently to an increase in the mass

    of fluid delivered through the gas turbine.

    In the case of steam injection, the Heat Rate or specific consumption will also

    decrease for the same reasons that apply to fuel gases with a low calorific value.

    On the contrary, the latter advantage does not exist in the case of water injection,

    as here a higher quantity of fuel is needed to vaporize water to the condition that

    allows it to be injected into the combustion chamber.

    HEATRATE(%)

    HEAT

    RATE(%)

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    43/986MOD. ARGE 2/S

    09-98-E P. 2-20

    In condition of peak duty, with a maximum of 1250 hours/year, it is possible to

    increase the water delivered through the combustion chamber cap area in order to

    increase the gas turbine power output. Obviously, this calls for shorter maintenanceintervals.

    As concerns the maximum water flow rates and maintenance procedures, these

    must be evaluated case by case, depending on the machine model and its

    combustion system.

    Output power increase

    Steam injection for increasing the gas turbine output power has been available and

    warranted by over 30 years' experience.

    Unlike water, steam is injected into the compressor exhaust casing, thus eliminating

    all limitations imposed in order to safeguard stability in the combustion process.For this reason, the maximum amount of injectable steam is limited to percentage

    values of the weight of air aspirated by the compressor.

    Steam must be overheated, and there must be at least 25 C difference with respect

    to the compressor delivery temperature; steam supply limit pressure must be at

    least 4 bar(g) greater than maximum pressure in the combustion chamber.

    In the case of steam or water injection, the amount of steam injected in conditin

    of partial load must be equal to the amount required to abate NOx. Once the load

    base value is reached, the control system gives the OK to inject the additional

    steam needed to increase the turbine output power.

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    44/986MOD. ARGE 2/S

    09-98-E P. 2-21

    Fig. 2.13 shows the typical effects of steam injection on the output power of a gas

    turbine (in this case, an MS 5002 gas turbine) as a function of ambient temperature.

    Fig. 2.13 - Effects of steam injection on output power(MS5002 Gas Turbine)

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    45/986MOD. ARGE 2/S

    09-98-E P. 2-22

    COALESCER/DEMISTER

    SUMP TANK

    CELLE AD EVAPORAZIONE

    COLLETTORE H2O

    POMPA DI CIRCOLAZIONE H2O

    ARIA REFRIGERATA

    VERSO IL FILTRO

    DELLARIA

    ARIA CALDAAMBIENTE

    Evaporative cooling

    Curves in fig. 2.9 show clearly how power and efficiency increase as the

    compressor inlet temperature decreases.The latter can be reduced artificially by using an evaporative cooler located

    upstream of the suction filter.

    Water, fractioned into drops or in the form of a liquid film, cools the air by

    evaporating in the cooler as it flows in contrary direction, thus originating an

    adiabatic-isoenthalpic exchange (see fig. 2.14).

    Fig. 2.14 Evaporative cooler

    In order to prevent water from being drawn towards the compressor and fouling it,

    downstreams of the cooler there are one or more stages of drop separators

    (demisters), which, by inertia, separate any water drops that might be carried away

    downstream of the cooler by the flow of air aspirated by the turbine.

    Fig. 2.15 shows the effects of evaporative cooling on the gas turbine output power

    and specific consumption.

    As can be noted, benefits increase as relative humidity decreases and ambient

    temperature increases.

    Unfortunately, the above requirements are met in environments (for example,

    deserts), in which water is not always available in the amounts needed by the

    cooler.

    COOLED AIR

    TOWARD AIR

    FILTER

    AMBIENT HOT AIR

    EVAPORATION CELLS

    H20 HEADER

    COALESCER/DEMISTER

    SUMP TANK

    H20 CIRCULATING PUMP

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    46/986MOD. ARGE 2/S

    09-98-E P. 2-23

    Fig. 2.15 Effects of Evaporative Cooling on Performance

    Inlet chillingIn environments in which a high degree of average relative humidity is present

    (higher than 60%) and ambient temperatures are not excessively high, it is

    advisable to cool air with a different method, commonly called "inlet chilling";

    according to this method, air is cooled during a refrigerating cycle (based generally

    on absorption) carried out in a closed circuit. In this way, the restrictions imposed

    by relative humidity and by ambient temperature, described in the preceding

    system, can be eliminated. The minimum temperature reached by air at the end of

    the cooling process is strictly dependent on the capability of the refrigerating cycle

    to produce cold liquid and on the efficiency of the thermal exchange that takes

    place in the water - air exchanger.

    Figure 2.16 shows an operating diagram of this system (in this example, steam

    is used for the absorption cycle), composed of a chiller, water connecting pipings

    and a water - air exchanger, installed downstream of the gas turbine suction filter.

    Same as in evaporative cooling, also in this case it is necessary to install a

    coalescer/demister downstream of the system, in order to prevent humidity from

    reaching the compressor inlet section.

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    47/986MOD. ARGE 2/S

    09-98-E P. 2-24

    Fig. 2.16 Air "chilling cooling" system, based on absorption

    Figure 2.17 shows a comparison between the cooling powers of the two systems.

    Fig. 2.17 Comparison psychometric chart

    DRENAGGIO

    CHILLER

    CAMERA

    FILTRI

    SCAMBIATORE

    DEMISTER/COALESCER

    ARIA AMBIENTE

    ARIA FREDDA VERSO

    IL COMPRESSORE

    INGRESSO VAPOREALLA TORRE DI RAFFREDDAMENTO

    INGRESSO AC UA FREDDA

    RITORNO AC UA DA RAFFREDDARE

    % RH const. lines

    Saturation line

    constant moisture content line

    Kgwater/Kgaira

    b

    c

    d

    TaTc Td

    constant enthalpy line

    PSYCHROMETRIC

    CHART

    Tb

    DEMISTER/COALESCER

    COOLED AIR

    TOWARD COMPRESSOR

    DRAIN

    CHILLER

    STEAM INLETTO COOLING

    TOWER

    FILTERS

    CHAMBERAMBIENT AIR

    HEAT EXCHANGER

    COOLING WATER INLET

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    48/986MOD. ARGE 2/S

    09-98-E P. 2-25

    Line a - d represents air cooling in the case of evaporative cooling. As mentioned

    before, this line follows the constant enthalpy line, resulting in a progressive

    increase in relative humidity.The restriction imposed by this cooling method consists in the fact that there

    remains a minimum distance from the saturation curve, compatibly with realistic

    exchange surfaces, considered from the point of view of construction. Normal

    values indicate around 90% relative humidity, that is, there still remains a 10%

    margin before the saturation line is reached.

    Under these conditions, the final air temperature is equal to Td.

    In the case of the chilling process, the cooling line has a constant moisture content

    along segment a - b. If the potential of the refrigerating cycle and the efficiency of

    the exchanger allow it, cooling can reach the saturation line and follow it along

    segment b - c, in which heat is removed to form condensate (H2O). In this secondsegment, there is a smaller temperature reduction, because most of the cooling

    energy serves for the condensing process and only a small part of it participates

    in lowering temperature.

    In the chilling system, the air final temperature will be equal to Tb or Tc, according

    to the chosen degree of cooling.

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    49/986

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    50/986

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    51/986

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    52/986

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    53/986

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    54/986

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    55/986

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    56/986

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    57/986

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    58/986

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    59/986

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    60/986

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    61/986

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    62/986

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    63/986

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    64/986

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    65/986

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    66/986

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    67/986

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    68/986

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    69/986

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    70/986

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    71/986

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    72/986

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    73/986

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    74/986

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    75/986

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    76/986

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    77/986

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    78/986

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    79/986

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    80/986

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    81/986

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    82/986

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    83/986

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    84/986

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    85/986

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    86/986

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    87/986

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    88/986

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    89/986

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    90/986

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    91/986

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    92/986

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    93/986

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    94/986

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    95/986

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    96/986

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    97/986

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    98/986

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    99/986

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    100/986

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    101/986

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    102/986

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    103/986

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    104/986

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    105/986

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    106/986

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    107/986

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    108/986

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    109/986

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    110/986

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    111/986

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    112/986

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    113/986

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    114/986

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    115/986

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    116/986

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    117/986

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    118/986

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    119/986

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    120/986

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    121/986

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    122/986

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    123/986

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    124/986

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    125/986

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    126/986

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    127/986

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    128/986

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    129/986

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    130/986

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    131/986

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    132/986

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    133/986

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    134/986

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    135/986

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    136/986

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    137/986

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    138/986

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    139/986

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    140/986

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    141/986

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    142/986

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    143/986

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    144/986

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    145/986

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    146/986

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    147/986

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    148/986

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    149/986

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    150/986

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    151/986

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    152/986

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    153/986

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    154/986

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    155/986

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    156/986

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    157/986

  • 7/27/2019 MS5001 PA Complete Maintenance MANUAL

    158/986

  • 7/27