36
Mounting and Operating Instructions EB 8395 EN Firmware version 1.01 Edition October 2014 Type 3724 Positioner (cover removed) Series 3724 Type 3724 Electropneumatic Positioner

Mounting and Operating Instructions EB 8395 EN - samson-ag.ch · Mounting and Operating Instructions EB 8395 EN Firmware version 1.01 Edition October 2014 Type 3724 Positioner (cover

  • Upload
    others

  • View
    4

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Mounting and Operating Instructions EB 8395 EN - samson-ag.ch · Mounting and Operating Instructions EB 8395 EN Firmware version 1.01 Edition October 2014 Type 3724 Positioner (cover

Mounting andOperating Instructions

EB 8395 ENFirmware version 1.01Edition October 2014

Type 3724 Positioner (cover removed)

Series 3724Type 3724 Electropneumatic Positioner

Page 2: Mounting and Operating Instructions EB 8395 EN - samson-ag.ch · Mounting and Operating Instructions EB 8395 EN Firmware version 1.01 Edition October 2014 Type 3724 Positioner (cover

Definition of signal words

DANGER!Hazardous situations which, if not avoided, will result in death or serious injury

WARNING!Hazardous situations which, if not avoided, could result in death or seri-ous injury

NOTICEProperty damage message or mal-function

Note:Additional information

Tip:Recommended action

2 EB 8395 EN

Page 3: Mounting and Operating Instructions EB 8395 EN - samson-ag.ch · Mounting and Operating Instructions EB 8395 EN Firmware version 1.01 Edition October 2014 Type 3724 Positioner (cover

Contents

EB 8395 EN 3

1 General safety instructions .............................................................................42 Article code ...................................................................................................53 Design and principle of operation ..................................................................63.1 Technical data ...............................................................................................84 Connections ................................................................................................104.1 Pneumatic connections..................................................................................104.1.1 Supply pressure ...........................................................................................104.2 Electrical connections ...................................................................................114.2.1 Selecting cables and wires ............................................................................124.2.2 Cable entry .................................................................................................125 Operation ...................................................................................................135.1 Operating controls .......................................................................................136 Start-up and settings ...................................................................................156.1 Adapting the display ....................................................................................166.2 Enableconfigurationtochangeparameters ...................................................166.3 Adjusting the volume restriction Q .................................................................176.4 Entering the opening direction/direction of action ..........................................186.5 Entering the direction of action ......................................................................186.6 Limiting the signal pressure ...........................................................................186.7 Adjusting the limit contacts ...........................................................................196.8 Setting other parameters ...............................................................................196.9 Initialization ................................................................................................206.10 Zero calibration ...........................................................................................216.11 Manual mode ..............................................................................................226.12 Reset ...........................................................................................................236.13 Faults ..........................................................................................................247 Code list .....................................................................................................257.1 Parameter codes ..........................................................................................257.2 Error codes ..................................................................................................278 Appendix ....................................................................................................298.1 Maintenance ...............................................................................................298.2 Nameplate ..................................................................................................298.3 Customer inquiries .......................................................................................298.4 Dimensions in mm ........................................................................................30 Index ..........................................................................................................31

Page 4: Mounting and Operating Instructions EB 8395 EN - samson-ag.ch · Mounting and Operating Instructions EB 8395 EN Firmware version 1.01 Edition October 2014 Type 3724 Positioner (cover

4 EB 8395 EN

General safety instructions

1 General safety instructionsFor your own safety, follow these instructions concerning the mounting, start up and opera-tion of the positioner: − The positioner is to be mounted, started up or operated only by trained and experienced

personnel familiar with the product. According to these mounting and operating instruc-tions, trained personnel is referred to as individuals who are able to judge the work they are assigned to and recognize possible dangers due to their specialized training, their knowledge and experience as well as their knowledge of the applicable standards.

− Any hazards that could be caused in the valve by the process medium, the signal pres-sure or by moving parts are to be prevented by taking appropriate precautions.

− If inadmissible motions or forces are produced in the pneumatic actuator as a result of the supply pressure level, it must be restricted using a suitable supply pressure reducing station.

To avoid damage to any equipment, the following also applies: − Proper shipping and storage are assumed.

Note:Devices with a CE marking fulfill the requirements of the Directives 2004/108/EC and 2006/95/EC. The Declaration of Conformity is available on request.

Page 5: Mounting and Operating Instructions EB 8395 EN - samson-ag.ch · Mounting and Operating Instructions EB 8395 EN Firmware version 1.01 Edition October 2014 Type 3724 Positioner (cover

EB 8395 EN 5

Article code

2 Article codePositioner Type 3724- 0 0 0 0 0 0 x 0 0 0 0 0Housing material

Housing: 1.4409 · Cover: 1.4404 0

Surfacefinish

Micro-bead blasted 1

Polished (Ra≤0.6µm) 2

Permissible ambient temperature

–20 to +80 °C 0

Degree of protection

IP 65 1) (only applies in combination with Type 3379 Pneumatic Actuator) 0

1) In preparation

Page 6: Mounting and Operating Instructions EB 8395 EN - samson-ag.ch · Mounting and Operating Instructions EB 8395 EN Firmware version 1.01 Edition October 2014 Type 3724 Positioner (cover

6 EB 8395 EN

Design and principle of operation

3 Design and principle of oper-ation

The Type 3724 Positioner is delivered as a ready-mountedunitonType 3379PneumaticActuators.The positioner is used to assign the valve po-sition (controlled variable x) to the control signal (reference variable w). The positioner compares the electric control signal of a con-trol system to the travel of the control valve (1) and issues a signal pressure (output vari-able y)forthepneumaticactuator.The positioner mainly consists of the follow-ing components (see Fig. 1): − Magnetoresistive sensor (2) − Analog i/p converter (6) with a down-

stream air capacity booster (7) − Electronics unit with microcontroller (4) − Software limit contacts (12)

The travel is measured by an internal pick-up rod, which is connected to a magnet, as well as a non-contact magnetoresistive sensor and the downstream electronics.The motion of the pick-up rod causes the di-rectionofthemagneticfieldtochange.Thischange is sensed by the sensor (2). The elec-tronics unit determines the current valve posi-tion from this information.The position of the valve is transmitted to the microcontroller (4) over its A/D converter (3).ThemicrocontrollercontainsamodifiedPID controller which compares the actual valvepositionwiththe4to20 mAcontrolsignal. The resulting output value is passed on to the D/A converter. In case of a system deviation, the activation of the i/p module

(6) is changed so that the actuator (1) is pressurized or vented accordingly over the downstream air capacity booster (7). The supply air is supplied to the booster (7) and the pressure regulator (8).

NOTICEUnauthorized manual adjustments to the positioner will damage it!Do not move the pick-up rod manually!

The output signal pressure supplied by the boostercanbelimitedto2.3 barbysoft-ware.The volume restriction Q (10) is used to opti-mize the positioner by adapting it to the ac-tuator.

Tight-closing functionThepneumaticactuatoriscompletelyfilledwith air or vented as soon as the reference variablefallsbelow1 %orexceeds99 %(see end positions set in P10 and P11 pa-rameters).

Page 7: Mounting and Operating Instructions EB 8395 EN - samson-ag.ch · Mounting and Operating Instructions EB 8395 EN Firmware version 1.01 Edition October 2014 Type 3724 Positioner (cover

EB 8395 EN 7

Design and principle of operation

Q

3 4

11

6

7

8 10

1

w

9

xy

2

5

A2

A1

12

1 Control valve2 Sensor3 A/D converter4 Microcontroller5 D/A converter6 i/p converter

7 Air capacity booster 8 Pressure regulator 9 Flow regulator10 Volume restriction11 Display12 Limit contacts

Fig. 1: Schematic diagram

Page 8: Mounting and Operating Instructions EB 8395 EN - samson-ag.ch · Mounting and Operating Instructions EB 8395 EN Firmware version 1.01 Edition October 2014 Type 3724 Positioner (cover

8 EB 8395 EN

Design and principle of operation

3.1 Technical data

Table 1: General technical data

Positioner

Attachment Type 3379 piston Ø: 63 mm · Effective area: 31 cm²Type 3379 piston Ø: 90 mm · Effective area: 63 cm²

Travel 4 to 16 mm, adjustable in steps of 0.5 mm

Reference variable w (reverse polarity protection)

Signal range 4 to 20 mA · Two-wire device Split-range operation 4 to 11.9 mA and 12.1 to 20 mA

Static destruction limit ± 32 V

Minimum current 3.8 mA

Load impedance Max.6.3 V

Supply air Air quality acc. to ISO 8573-1

1.4to7 bar(20to105 psi) Max. particle size and density: Class 4 · Oil content: Class 3 · Pressure dewpoint:Class3oratleast10 Kbelowthelowestambienttemperature to be expected

Signal pressure (output) 0baruptothecapacityofthesupplypressureminus0.4 bar Canbelimitedtoapprox.2.3 barbysoftware

Characteristic Three selectable characteristics: Linear · Equal percentage · Reverse equal percentage

Transit time Only for actuators with initialization time > 0.4 s 1)

Direction of action w/x reversible

Perm. ambient temperature –20 to +80 °C

Electromagnetic compati-bility

Complying with EN 61000-6-2, EN 61000-6-3 and NAMUR RecommendationNE 21

Degree of protection IP 652) (only applies in combination with Type 3379 Pneumatic Actuator)

Materials

Housing 1.4409

Cover 1.4404

Dome (visual indicator) Polycarbonate

Weight (without actuator) Approx. 1.2 kg

1) For faster actuators, a volume restriction must be used. Otherwise, the initialization cannot be performed successfully.

2) In preparation

Page 9: Mounting and Operating Instructions EB 8395 EN - samson-ag.ch · Mounting and Operating Instructions EB 8395 EN Firmware version 1.01 Edition October 2014 Type 3724 Positioner (cover

EB 8395 EN 9

Design and principle of operation

Table 2: Limit contacts

Binary contacts Two software limit contacts (min. and max.)

Version Reverse polarity protection, galvanic isolation

Adjustment range 0to100%(seesection6.7,page19)

Step size 0.5%

Static destruction limit ± 32 V

Signal state

No response Non-conducting(highlyresistive),I<100µA

Response Conducting(R=330Ω)

For connection to − Binary input of a PLC acc. to IEC 61131-2 − Pmax = 400 mW

Page 10: Mounting and Operating Instructions EB 8395 EN - samson-ag.ch · Mounting and Operating Instructions EB 8395 EN Firmware version 1.01 Edition October 2014 Type 3724 Positioner (cover

10 EB 8395 EN

Connections

4 Connections

4.1 Pneumatic connectionsTheType 3724PositionerisdeliveredreadymountedontheType 3379PneumaticActu-ator. The pneumatic connections of the posi-tioner are connected internally to the con-nections of the actuator.The pneumatic connections of the actuator are used (refer to the Mounting and Operat-ing Instructions of the Type 3379 Pneumatic Actuator u EB 8315 EN)forstart-up(seesection 6, page 15).

NOTICEDirty supply air will cause the position-er to malfunction!Only use supply air that is dry and free of oil and dust!Blow through all air pipes and hoses thoroughly before connecting them!

4.1.1 Supply pressureThe required supply air pressure depends on the bench range and the actuator's operat-ing direction (fail-safe action). The bench range is written on the nameplate either as spring range or signal pressure range. The operating direction is marked FA or FE, or by a symbol.

Actuator stem extends FA (air to open)Fail-close (for globe and angle valves): Required supply pressure = Upper bench rangevalue+0.4 bar,minimum1.4bar.

Actuator stem retracts FE (air to close)Fail-open (for globe and angle valves):For tight-closing valves, the maximum signal pressure pstmax is roughly estimated as fol-lows:

pstmax = F + d²·π·∆p [bar]4 · A

d = Seat diameter [cm]∆p =Differentialpressureacrossthevalve [bar]A = Actuator area [cm²]F = Upper bench range value [bar]

If there are no specifications, calculate as follows:Recommended supply pressure =Upper bench range value + 1 bar

Note:The signal pressure at the output (38) of the positioner can be restricted to approx. 2.3 bar by setting P9 param-eter to ON.

Page 11: Mounting and Operating Instructions EB 8395 EN - samson-ag.ch · Mounting and Operating Instructions EB 8395 EN Firmware version 1.01 Edition October 2014 Type 3724 Positioner (cover

EB 8395 EN 11

Connections

4.2 Electrical connections

DANGER!Risk of electric shock!For electrical installation, observe the relevant electrotechnical regulations and the accident prevention regula-tions that apply in the country of use.

NOTICEAn incorrect electric signal will dam-age the positioner!Only use a current source and never a voltage source!

Perform the electrical connections according to Fig. 2. Guide the wires to the cage clamp terminals of the positioner as described in sections 4.2.1 and 4.2.2.

+11 –12 +41 –42 +51 –52

+11/–12: mA control signal+41/–42: Limit contact 1 (min.)+51/–52: Limit contact 2 (max.)

Fig. 2: Electrical connections

Accessories

Description Order no.

Cable gland:Black plastic, M16 x 1.5 8808-1010

Page 12: Mounting and Operating Instructions EB 8395 EN - samson-ag.ch · Mounting and Operating Instructions EB 8395 EN Firmware version 1.01 Edition October 2014 Type 3724 Positioner (cover

12 EB 8395 EN

Connections

4.2.1 Selecting cables and wires

The minimum radial thickness of the conduc-tor insulation must be suitable for the con-ductor diameter and type of insulation. It mustbeatleast0.2 mm.Thediameterofanindividualwireinafine-stranded conductor must not be smaller than 0.1 mm.Protect the conductor ends against splicing, e.g. by using wire-end ferrules.

4.2.2 Cable entryThe M16 x 1.5 cable gland is designed for a clampingrangeof6to12 mm.The cage clamp terminals hold wire cross-sectionsof0.2to1.5 mm².

Î Turn the cover counterclockwise to un-screw it. Remove cover.

Î To unlock the cage clamp terminals: place a slotted screwdriver on the plastic part (Fig. 3) and lightly push it into the terminal block.

Î Insert or remove the wire without force. Î Guide wires for the reference variable to the terminals +11 and –12 located on the housing.

NOTICEA reference variable above or below the static destruction limit will damage the positioner!Keep the reference variable within the static destruction limit of ±32 V!

Plastic part of cage clamp terminal

Fig. 3: Cage clamp terminals

Placing on the cover Î Placeoncoverwhilebrieflyturningitcounterclockwise to center it and then fasten by turning it clockwise.

Page 13: Mounting and Operating Instructions EB 8395 EN - samson-ag.ch · Mounting and Operating Instructions EB 8395 EN Firmware version 1.01 Edition October 2014 Type 3724 Positioner (cover

EB 8395 EN 13

Operation

5 OperationThe positioner is operated by three pushbut-tons for menu navigation on the display (see Fig. 4):

: Up

: Confirm

: Down Î To adapt the air capacity, adjust the vol-ume restriction (see section 6.3).

5.1 Operating controlsPress or button to select a parameter code (P0 to P20). Then press button to confirmtheselectedcode.

To save changes to parameters in a non-vol-atile memory, proceed as follows:

Î After changing parameters, press or to change to Code P0 or

Î Wait three minutes until the display re-turns automatically to P0.

Note: − The icon on the display indicates that the changed parameter settings have not yet been saved in the non-volatile memory. − The selected parameter code re-mains active until you change the setting or exit the parameter code. − After changing settings in P2, P4 and P8 parameter codes, the posi-tioner must be re-initialized.

Settings not yet saved in a non-volatile memory

Unit/sign

Bar graph/system deviation

Fault

Manual mode Closed-loop control

Parameter/error code

Fail-safe position active

Limit contact 2 (max.)Limit contact 1 (min.)

Operation locked

Fig. 4: Display with all readings

Page 14: Mounting and Operating Instructions EB 8395 EN - samson-ag.ch · Mounting and Operating Instructions EB 8395 EN Firmware version 1.01 Edition October 2014 Type 3724 Positioner (cover

14 EB 8395 EN

Operation

Cover

Pick-up rod

Positioner

Actuator

Pushbuttons

Terminals

Venting

Fig. 5: Type 3724 Positioner mounted on Type 3379 Pneumatic Actuator

Page 15: Mounting and Operating Instructions EB 8395 EN - samson-ag.ch · Mounting and Operating Instructions EB 8395 EN Firmware version 1.01 Edition October 2014 Type 3724 Positioner (cover

EB 8395 EN 15

Start-up and settings

Volume restriction QThe volume restriction serves to adapt the air output capacity to the size of the actuator. Twofixedsettingsarepossible(refertosec-tion 6.3).

Display

Display Meaning

ESC Cancel

Err Error

LOW w too low

MAN Manual mode

MAX Maximum range

RST Reset

INIT Initialization

ON/OFF Activated/deactivated

ZERO Zero calibration

Icons which are assigned to certain codes and functions are indicated on the display. The bar elements indicate the system devia-tion that depends on the sign (+/–) and the value.Onebarelementappearsper1 %systemdeviation.If the positioner has not yet been initialized, the position of the pick-up rod in the working rangeof±10 mmisindicated.If the fault indication icon appears on the display, press or until ERR appears on the display to view the relevant E0 to E15 er-ror code(s) (see code list in section 7.2, page 27).

6 Start-up and settings

NOTICEThe process is disturbed by the move-ment of the actuator stem!Do not perform the initialization while the process is running! First isolate the plant by closing the shut-off valves!

Î Perform pneumatic connections on the actuator as described in u EB 8315 EN.

Î Connect the supply air to the loading pressure connection.

Î Check whether a vent plug or silencer is screwed into the exhaust port.

Î Connect the 4 to 20 mA signal.à Terminals +11/–12

Î Connect software limit contacts, if appli-cable.à Terminals +41/–42: Limit contact 1 (min.)à Terminals +51/–52: Limit contact 2 (max.)

Note: − LOW on the display indicates that the reference variable is lower than 3.8 mA. − The positioner is ready for operation with its default settings for most ap-plications.

Page 16: Mounting and Operating Instructions EB 8395 EN - samson-ag.ch · Mounting and Operating Instructions EB 8395 EN Firmware version 1.01 Edition October 2014 Type 3724 Positioner (cover

16 EB 8395 EN

Start-up and settings

Reading after connecting the electrical sig-nalCode P0 appears on the display. The fault indication icon and und S (fail-safe position) appear on the display when the positioner has not yet been initialized. The reading in-dicates the position of the pick-up rod in the workingrangeof±10 mm.

Reading when the posi-tioner has not yet been initialized

Code P0andthevalvepositionin%appearon the display after connecting the electrical signal to an initialized positioner.

Initialization successfully completed, positioner runs in closed-loop operation

Note:The positioner has a function to moni-tor the working range. If the pick-up rod moves too close to the mechanical stops (risk of mechanical damage), the positioner vents the actuator and the valve moves to its fail-safe position (S displayed together with E8 error code).

6.1 Adapting the displayThe display reading direction can be rotated by 180°. If the displayed data appear up-side down, proceed as follows:Press or until Code P1 appears.

Code P1: Reading direction

Press toconfirmtheselectedcode.P1 blinks.Press or until the display is set in the desired direction.Press toconfirmdisplaydirection.

6.2 Enable configuration to change parameters

Before changing parameter settings in an initializedpositioner,configurationmustbeenabledfirstbyselectingCodeP19.

LOCK and the key icon indicate that the configuration is locked.

Press or until Code P19 appears.Press toconfirmtheselectedcode.P19 blinks.Press until OPEN appears on the display.Press toenableconfiguration.If no settings are entered within three min-utes,theenabledconfigurationfunctionbe-comes invalid.

Page 17: Mounting and Operating Instructions EB 8395 EN - samson-ag.ch · Mounting and Operating Instructions EB 8395 EN Firmware version 1.01 Edition October 2014 Type 3724 Positioner (cover

EB 8395 EN 17

Start-up and settings

6.3 Adjusting the volume re-striction Q

The volume restriction Q serves to adapt the air output capacity to the size of the actua-tor: − Actuators with a transit time < 0.4 s re-quirearestrictedairflowrate.Setting to MIN

− Actuators with a transit time ≥ 0.4 s do notrequiretheairflowratetoberestrict-ed.Setting to MAX

Intermediate settings are not permitted.

NOTICERisk of malfunction due to a change to the volume restriction setting!Re-initialize positioner after changing the volume restriction setting!

MIN setting:Arrow points toward the positioner

MAX setting:Arrow points away from the positioner

Location of the volume restriction Q

Fig. 6: Setting the volume restriction

Page 18: Mounting and Operating Instructions EB 8395 EN - samson-ag.ch · Mounting and Operating Instructions EB 8395 EN Firmware version 1.01 Edition October 2014 Type 3724 Positioner (cover

18 EB 8395 EN

Start-up and settings

6.4 Entering the opening direc-tion/direction of action

− AIR TO OPEN (ATO) applies to a valve opening as the signal pressure increases.

− AIR TO CLOSE (ATC) applies to a valve closing as the signal pressure increases.

The signal pressure is the pneumatic pressure at the internal output of the positioner ap-plied to the actuator.Enableconfiguration(section6.2).

Default ATO

Press or until Code P2 appears.Press toconfirmselectedcode.P2 blinks.Press or until the required fail-safe po-sition appears.Press toconfirmsetting.

Note:The changed opening direction/direc-tion of action first becomes effective after the positioner has been re-initial-ized.

6.5 Entering the direction of ac-tion

The direction of action (P7) is set to increas-ing/increasing by default.For checking purposes: After successfully completing initialization, the positioner dis-

playshouldread0 %whenthevalveisclosedand100 %whenthevalveisopen.If necessary, the direction of action can be changed either before or after initialization.The following correlation applies:

Valve CLOSED OPEN

Reading 0% 100%

>> 4 mA 20 mA

<> 20 mA 4 mA

>> Increasing/increasing<> Increasing/decreasing

6.6 Limiting the signal pressureIf the maximum actuator force may cause damage to the valve, the signal pressure must be limited. Set Code P9 to ON. This limitsthesignalpressuretoapprox.2.3 bar.Makesuretheconfigurationisenabled(sec-tion 6.2) before changing this setting.

Page 19: Mounting and Operating Instructions EB 8395 EN - samson-ag.ch · Mounting and Operating Instructions EB 8395 EN Firmware version 1.01 Edition October 2014 Type 3724 Positioner (cover

EB 8395 EN 19

Start-up and settings

6.7 Adjusting the limit contactsThe electronic limit contacts can be triggered by the position of pick-up rod exceeding or falling below an adjustable switching point.Limit contact 1 (min., Code P12):The limit contact is activated when the pick-up rod moves below the adjusted switching val-ue. The limit contact is deactivated when the pick-up rod moves above the adjusted switch-ingvalueby1 %again.

Î indicates it is active

Limit contact 2 (max., Code P13):The limit contact is activated when the pick-up rod moves above the adjusted switching val-ue. The limit contact is deactivated when the pick-up rod moves below the adjusted switch-ingvalueby1 %again.

Î indicates it is active

Press or to select Code P12 for limit contact 1 or P13 for limit contact 2.Press , P12 or P13 blinks.Press or to adjust the required switch-ingvalueinstepsof0.5 %andpress to confirmthevalue.

Note:The switching values for P12 and P13 must be adjusted to be at least 5 % away from each another. It is not pos-sible to enter switching values that are less than 5 % away from one another.

6.8 Setting other parametersThe following table lists all the parameter codes and their default settings. If you want to change the default setting of a parameter, proceed in the same manner as previously described.More details concerning the parameter codes can be found in section 7.

Parameter codes [Default setting] Codes marked with * indicate that the positioner needs to be re-initialized afterwards

P0 Status indication

P1 Reading direction

P2* ATO/ATC [ATO]

P4* Nominal range [MAX]

P5 Characteristic [0]

P6 Reference variable [4 to 20 mA]

P7 w/x direction of action [>>]

P8* GainKp[50]

P9 Pressure limitation 2.3 bar [OFF]

P10 End position w < [ON]

P11 End position w > [OFF]

P12 LimitA1,min.[2%]

P13 LimitA2,max.[98%]

P14 Display of reference variable w

P15 INIT Start initialization

P16 ZERO Start zero calibration

P17 MAN Manual mode

P18 RST Reset

P19 Enableconfiguration

P20 Firmware version

Page 20: Mounting and Operating Instructions EB 8395 EN - samson-ag.ch · Mounting and Operating Instructions EB 8395 EN Firmware version 1.01 Edition October 2014 Type 3724 Positioner (cover

20 EB 8395 EN

Start-up and settings

6.9 InitializationDuring initialization the positioner adapts it-self optimally to the friction conditions and the signal pressure required by the control valve.

NOTICEThe process is disturbed by the move-ment of the actuator stem!Do not perform the initialization while the process is running! First isolate the plant by closing the shut-off valves!

The type and extent of self-adaptation de-pends on the preset parameters.MAX is the default setting for the nominal range (Code P4).During the initialization process, the posi-tioner determines the travel range of the valve (from the CLOSED position to the op-posite end position).Alternatively, a different travel can be select-ed in Code P4 (see code list in section 7.1).

Note:The travel set in Code P4 is only limited during initialization. However, it might be exceeded in closed-loop control when the control signal is higher than 20 mA.

Start initialization by activating Code P15 as follows:

Press or to select Code P15.Press six seconds long. 6-5-4-3-2-1- is counted down on the display.Initialization starts. INIT blinks on the dis-play!

Note:The time required for the initialization procedure depends on the actuator transit time and can take a few minutes.

Initialization successfully completed, positioner runs in closed-loop operation

After a successful initialization, the position-er changes to closed-loop operation indicat-ed by the

%

closed-loop operation icon and controlpositionreadingin%predeterminedby the reference variable on the display. Configurationislocked.A malfunction leads to the process being in-terrupted and the positioner moving to the fail-safe position. The fault indication icon appears on the display (see section 6.13).

Page 21: Mounting and Operating Instructions EB 8395 EN - samson-ag.ch · Mounting and Operating Instructions EB 8395 EN Firmware version 1.01 Edition October 2014 Type 3724 Positioner (cover

EB 8395 EN 21

Start-up and settings

Canceling initialization The initialization can be canceled by press-ing . − ESC blinks on the display. − Press toconfirm.

Note:This code must be confirmed by press-ing . Otherwise, the code remains active.

Initial state 1: Positioner has not been initializedThe positioner goes to the fail-safe position after the initialization process has been can-celed.Initial state 2: Positioner has been initializedOn canceling a new initialization process, the positioner returns to closed-loop opera-tion. The settings of the previous initialization are used.A new initialization can be started directly afterwards.

6.10 Zero calibrationIn case of inconsistencies in the closing posi-tion of the valve, e.g. with soft-seated plugs, it might be necessary to recalibrate zero. En-ableconfigurationasdescribedinsection6.2.Start the zero calibration by activating Code P16 as follows:

Press or until Code P16 appears.Press six seconds long. 6-5-4-3-2-1- is counted down on the display.Zero calibration starts, the display blinks!The positioner moves the control valve to the CLOSED position and recalibrates the inter-nal electric zero point.When the zero calibration has been success-fully completed, the positioner returns to closed-loop operation (display with status in-dication).

Page 22: Mounting and Operating Instructions EB 8395 EN - samson-ag.ch · Mounting and Operating Instructions EB 8395 EN Firmware version 1.01 Edition October 2014 Type 3724 Positioner (cover

22 EB 8395 EN

Start-up and settings

Canceling zero calibrationThe zero calibration can be canceled by pressing . − ESC blinks on the display. − Press toconfirm.

Note:This code must be confirmed by press-ing . Otherwise, the code remains active.

The positioner returns to closed-loop opera-tion without performing a zero calibration.A new zero calibration can be started direct-ly afterwards.

6.11 Manual modeThe valve position can be moved as follows using the Manual mode function:Enableconfigurationasdescribedinsection6.2.Press or until Code P17 appears.Press six seconds long. 6-5-4-3-2-1- is counted down on the display.P17 blinks.The set point for manual mode is indicated on the display of an initialized positioner.

If the positioner has not yet been initialized, the position of the pick-up rod is indicated in theworkingrangeof±10 mm.Press or to change the set point for manual mode.

Initialized positionerThe manual mode starts using the last set point of the closed-loop control, ensuring a bumpless changeover.The bar elements on the display indicate the system deviation between the set point for manual mode and set point used for closed-loop control while manually moving the valve in Code P17.The set point for manual mode is adjusted in stepsof0.1%.Youcanmovethevalvecon-trolled within its range.

Page 23: Mounting and Operating Instructions EB 8395 EN - samson-ag.ch · Mounting and Operating Instructions EB 8395 EN Firmware version 1.01 Edition October 2014 Type 3724 Positioner (cover

EB 8395 EN 23

Start-up and settings

Positioner that has not been initializedPress or for a long time to move the valve manually.The valve is only moved in one direction un-controlled. The bar elements on the display indicate the change in direction.

Press to deactivate manual mode.

Note:The Manual mode function can only be exited as described or by interrupting the electrical supply (cold start). The positioner does not automatically exit this function and return to the display with the status indication.

6.12 ResetA reset causes an initialization to be undone and all parameters settings are reset to the default settings (see parameter code list in section 7.1,page25).Enableconfiguration(section6.2).Press or until Code P18 appears.

Press six seconds long. 6-5-4-3-2-1- is counted down on the display.RST blinks while is pressed. As soon as the button is released, the reset process is complet-ed and the display returns to status indication (P0).

Note:The fault indication icon appears on the display after a reset since the po-sitioner needs to be re-initialized. The error code E2 is also activated (see section 6.13).

Page 24: Mounting and Operating Instructions EB 8395 EN - samson-ag.ch · Mounting and Operating Instructions EB 8395 EN Firmware version 1.01 Edition October 2014 Type 3724 Positioner (cover

24 EB 8395 EN

Start-up and settings

6.13 FaultsIn case of a fault, the fault indication icon appears on the display.If the fault indication icon appears after a parameter code setting has been changed, this indicates that this setting does not match the values determined during initialization. See Code E1 (see code list in section 7.2).Press buttons past Code P0 or P20. The re-spective error code E0 to E15 together with ERR appear on the display.Refer to the code list for the cause of the er-rors and the recommended action.Example:If, for instance, a travel has been entered in Code P4 (nominal range) which is larger than the maximum valve travel possible, the initialization process would be interrupted (E2 error code) because the rated travel would not have been reached (E6 error code). The valve moves to the fail-safe posi-tion (S indicated on the display).

mm

Display of the fault indication

The nominal range (Code P4) must be changed and the positioner re-initialized to remedy this problem.

Resetting error codesThe E0 and E8 error codes can be reset as follows:Press or to select the error code.

Press toconfirmtheerrorcode.ESC ap-pears on the display. E8 blinks.

Press or until RST appears.

Press to reset the error.The reset procedure can be canceled by pressing when ESC appears.

Page 25: Mounting and Operating Instructions EB 8395 EN - samson-ag.ch · Mounting and Operating Instructions EB 8395 EN Firmware version 1.01 Edition October 2014 Type 3724 Positioner (cover

EB 8395 EN 25

Code list

7 Code list

7.1 Parameter codesCode Display, values

[default setting]Description

Note: Codes marked by an asterisk (*) indicate that the positioner needs to be re-initialized after-wards

P0 Status reading with basic information

Thereadingindicatesthevalvepositionin%whenthepositionerisinitialized. Press to display the actual valve position when the positioner is initialized.

P1 Reading direction The reading direction of the display is turned by 180°.

P2* ATO / ATC [ATO]

Parameter to adapt the positioner to how the control valve functions: ATO – Air to open (valve CLOSED in fail-safe position) ATC – Air to close (valve OPEN in fail-safe position)

P4* Nominal range [MAX]

Thetravelisadjustablefrom4to16 mminstepsof0.5 mm.MAX: Maximum possible travel

P5 Characteristic 0 to 2 [0]

Threedifferentcharacteristicscanbeselectedtodefinetherelation-ship between the input variable and the position of the actuator stem: 0 à Linear1 à Equal percentage2 à Reverse equal percentage

P6 Reference variable [4 to 20 mA] SRLO/SRHI

For split-range operation: SRLO: low range 4 to 11.9 mA SRHI: high range 12.1 to 20 mA

P7 w/x [>>]/<>

Direction of action of the reference variable w to the travel x (in-creasing/increasing or increasing/decreasing)

P8* Gain KP 30/[50]

On initializing the positioner, the gain is set to the selected value. Ifthepositionerhunts,theKp value can be reduced.

P9 Pressure limitation ON/[OFF]

The signal pressure can take on the same pressure as the supply air at the maximum [OFF] or, in the case that the maximum actuator force can damage the valve, the pressure is limited to approx. 2.3 bar.

P10 End position w < [ON]/OFF

Lower tight-closing function: Ifwreachesupto1%towardsthefinalvaluethatcausesthevalveto close, the actuator is immediately completely vented (with ATO - airtoopen)orfilledwithair(withATC - air to close).

Page 26: Mounting and Operating Instructions EB 8395 EN - samson-ag.ch · Mounting and Operating Instructions EB 8395 EN Firmware version 1.01 Edition October 2014 Type 3724 Positioner (cover

26 EB 8395 EN

Code list

Code Display, values [default setting]

Description

P11 End position w > ON/[OFF]

Upper tight-closing function: Ifwreachesupto99%towardsthefinalvaluethatcausesthevalvetoopen,theactuatorisimmediatelycompletelyfilledwithair(withATO - air to open) or vented (with ATC - air to close).

P12 Limit A1, min.[2%]

Thelowerswitchingpointcanbeadjustedinstepsof0.5 %.Note: Keepadistanceof5%totheswitchingvalueadjustedinP13.

P13 Limit A2, max.[98%]

Theupperswitchingpointcanbeadjustedinstepsof0.5 %.Note: Keepadistanceof5%totheswitchingvalueadjustedinP12.

P14 Info w Initialized Indicates the internally adjusted set point in the positioner (adjusted setpointin0to100 %accordingtothesettingsinP6 and P7). Press to display external set point (applied set point in 0 to 100 %accordingtothe4-20mAsignal).

Not initialized Displaysexternalsetpointin0to100%accordingtothe4-20mAsignal.

P15 Start initialization The initialization process can be interrupted by pressing . The control valve moves to the fail-safe position. After a power supply failure during initialization, the positioner starts with the settings from the last initialization (if they exist).

P16 Start zero calibration The zero calibration process can be interrupted by pressing . The control valve returns to closed-loop operation.Note: A zero calibration cannot be started when E1 error code ex-ists.After a power supply failure during zero calibration, the positioner starts with the settings from the last zero calibration.

P17 Manual mode 1) Press or to enter the set point.

P18 Reset Parameters are reset to their default setting. The positioner can only return to closed-loop operation after it has been re-initialized.

P19 Enable configuration [LOCK]/OPEN

Enableconfigurationtochangeparametersettings. This function is automatically canceled when none of the buttons are pressed within three minutes.

P20 Firmware version Installedfirmwareversionisdisplayed.Press to display the last four digits of the serial number.

1) Also not available when the positioner has not been initialized

Page 27: Mounting and Operating Instructions EB 8395 EN - samson-ag.ch · Mounting and Operating Instructions EB 8395 EN Firmware version 1.01 Edition October 2014 Type 3724 Positioner (cover

EB 8395 EN 27

Code list

7.2 Error codesIn case of a fault, the fault indication icon appears on the display.The errors listed in the following table are assigned to error classes:Error class 1: No operation possibleError class 2: Manual operation only possibleError class 3: Manual operation and closed-loop control possible

Code Description Class

E0 Zero error (operational error)

Only with tight-closing function P10 (end position w < set to ON). Thezeropointhasshiftedbymorethan5 %comparedtoinitialization. The error may arise when the valve seat trim is worn. 3

Recommended action Check valve and positioner attachment.IfOK,performazerocalibrationoverCodeP16 (see sec-tion 6.10).Error code can be reset (see section 6.13).

E1 Displayed and INIT val-ues are not identical (operational error)

Adjusted and displayed valves are not identical to the INIT values as the parameters were changed after initialization. 3

Recommended action Reset parameters or perform initialization.

E2 Positioner has not been initialized

Malfunction or parameter change requiring the positioner to be re-initialized. 2

Recommended action Set parameters and initialize the positioner over Code P15.

E3 KP setting (initialization error)

Positioner hunts. Volume restriction set incorrectly, too much gain.

2Recommended action Check the volume restriction setting as described in section

6.3.LimitgainKP in Code P8. Re-initialize the positioner.

E4 Transit time too short(initialization error)

The transit times of the actuator determined during initializa-tion are so short (below 0.4 second) that optimal positioner tuning is not possible. 2

Recommended action Check the volume restriction setting as described in section 6.3. Re-initialize the positioner.

Page 28: Mounting and Operating Instructions EB 8395 EN - samson-ag.ch · Mounting and Operating Instructions EB 8395 EN Firmware version 1.01 Edition October 2014 Type 3724 Positioner (cover

28 EB 8395 EN

Code list

E5 Standstill detection is not possible (initialization error)

Supply pressure varies. Mounting incorrect.2

Recommended action Check supply air and mounting. Re-initialize the positioner.

E6 Travel is not achieved during initialization (initialization error)

Supply pressure is too low, actuator leaks, incorrect travel adjusted or pressure limit function activated.

2Recommended action Check supply air, mounting and setting.

Re-initialize the positioner.

E7 Actuator does not move (initialization error) No supply air, mounting blocked.

2Recommended action Check supply air, mounting and mA input signal.

Re-initialize the positioner.

E8 x > range Pick-up rod near to the end stops1Recommended action Check mounting and re-initialize the positioner.

Error code can be reset (see section 6.13).

E9 to

E15Device error (internal) Return positioner to SAMSON AG for repair. 1/3

Page 29: Mounting and Operating Instructions EB 8395 EN - samson-ag.ch · Mounting and Operating Instructions EB 8395 EN Firmware version 1.01 Edition October 2014 Type 3724 Positioner (cover

EB 8395 EN 29

Appendix

8 Appendix

8.1 MaintenanceThe positioner does not require any mainte-nance.The maintenance instructions of any up-stream supply air pressure reducing stations must be observed.

8.2 Nameplate

1 23

4

5

1 ConfigurationID(Var.-ID)2 Firmware version3 Serial number4 Reference variable5 Supply air

8.3 Customer inquiriesPlease submit the following details: − Type designation − ConfigurationID(Var.-ID) − Serial no. − Firmware version

Page 30: Mounting and Operating Instructions EB 8395 EN - samson-ag.ch · Mounting and Operating Instructions EB 8395 EN Firmware version 1.01 Edition October 2014 Type 3724 Positioner (cover

30 EB 8395 EN

Appendix

8.4 Dimensions in mm

Actuator Piston Ø Ød

Type 337963 mm 69 mm

90 mm 94 mm

Ø10

8

285

135

Ød

130

Fig. 7: Dimensional drawings of Type 3724 Positioner with Type 3379 Pneumatic Actuator

Page 31: Mounting and Operating Instructions EB 8395 EN - samson-ag.ch · Mounting and Operating Instructions EB 8395 EN Firmware version 1.01 Edition October 2014 Type 3724 Positioner (cover

Index

EB 8395 EN 31

Index

AAccessories .......................................... 11Actuator ........................................ 10, 14

transit time ..................................... 17Article code ........................................... 5CCable .................................................. 12Cable entry .......................................... 12Characteristic ....................................... 25Connections

electrical connections ...................... 11pneumatic connections .................... 10terminals ........................................ 12

DDefault settings ..................................... 19Dimensions in mm ................................ 30Direction of action ................................ 18Display ................................................ 13

adapting ........................................ 16readings ........................................ 13

EEnableconfiguration............................. 16End position ......................................... 25Error codes .......................................... 27

reset .............................................. 24FFaults .................................................. 24Firmware ............................................. 26

GGain ................................................... 25IInitialization ................................... 20, 21

cancel ............................................ 21LLimit contacts ................................... 9, 19MMaintenance ........................................ 29Manual mode ...................................... 22Materials ............................................... 8NNameplate .......................................... 29OOperating controls ............................... 13

display ..................................... 13, 15pushbuttons .................................... 13volume restriction ............................ 15

Operation ...................................... 13–14PParameter codes............................. 19, 25Pressure limit ........................................ 25Principle of operation ......................... 6, 7RReference variable ................................ 25Reset ................................................... 23SSafety instructions............................. 4, 11Schematic diagram ................................ 7

Page 32: Mounting and Operating Instructions EB 8395 EN - samson-ag.ch · Mounting and Operating Instructions EB 8395 EN Firmware version 1.01 Edition October 2014 Type 3724 Positioner (cover

Index

32 EB 8395 EN

Index

Signal pressure .................................... 18Start-up ............................................... 15Supply pressure .................................... 10TTechnical data ........................................ 8Tight-closing function .............................. 6Transit time .......................................... 17VVolume restriction ........................... 15, 17WWires .................................................. 12ZZero calibration ................................... 21

Page 33: Mounting and Operating Instructions EB 8395 EN - samson-ag.ch · Mounting and Operating Instructions EB 8395 EN Firmware version 1.01 Edition October 2014 Type 3724 Positioner (cover
Page 34: Mounting and Operating Instructions EB 8395 EN - samson-ag.ch · Mounting and Operating Instructions EB 8395 EN Firmware version 1.01 Edition October 2014 Type 3724 Positioner (cover
Page 35: Mounting and Operating Instructions EB 8395 EN - samson-ag.ch · Mounting and Operating Instructions EB 8395 EN Firmware version 1.01 Edition October 2014 Type 3724 Positioner (cover
Page 36: Mounting and Operating Instructions EB 8395 EN - samson-ag.ch · Mounting and Operating Instructions EB 8395 EN Firmware version 1.01 Edition October 2014 Type 3724 Positioner (cover