    DESIGN OF BEAM TO COLUMN MOMENT CONNECTIONS

    (acc. to AISC EDICIN 9 PGS 4-116 A 4-122)

    BEAM ID:

  • 8/21/2019 Moment Connections.xls

    2/15

    2007

  • 8/21/2019 Moment Connections.xls

    3/15

    DESIGN OF BEAM TO COLUMN MOMENT CONNECTIONS

    (acc. to AISC EDICIN 9 PGS 4-116 A 4-122)

    BEAM ID: 2007

    GEOMETRIC DATA FOR CONNECTION:

    Total bolt number = 8.00 Bolts distances (cm):

    Number of bolts in Tension= 4.00 a= 4.00

    Bolt diameter to be used ,dbo (mm)= 25.00 Pf= 4.00

    Bolt area (cm2)= 5.00 b= 6.50

    Thickness of head plate(mm)= 19 c= 32.00

    Total lengh of head plate(cm)= 61 d= 4.00

    Width of head plate(cm)= 23 gh= 15.00 (see Note 1)

    Effective width of head plate (cm)= 21.5 gv= 10.50 (see Note 2)

    =(bfb beam + 2.5 cm)

    Note 1: recomended 9 cm if tfc 13 mmNota 2:recomended 9 cm mn. if tfc 13 mm

    DATA OF BEAM AND COLUMN TO BE CONNECTED:

    db beam (cm)= 45.00 dc col (cm)= 35.00

    bfb beam (cm)= 19.00 cfw col (cm)= 30.00

    tfb beam (cm)= 1.46 tfc col (cm)= 1.75

    twb beam (cm)= 0.94 twc col (cm)= 1.00

    k (cm)= 4.4

    T (cm)= 26.2

    MATERIALS:

    Bolts:

    Fv allow(k/cm2)=

    DESIGN FORCES: Steel:

    Axial force (T(+)/C(-)),(kg)= 352.00 Fy(k/cm2)=

    Shear (V),(kg)= 3784.00 Fu(k/cm2)=

    Weldements:

    Bending Moment (M),(k-m)= 11581.00 Fv (k/cm2)=

    Is a load comb. with earthquake or wind? (YES=1,NO=0): 1

    a)Forces on beam flanges (kg): 26774.53 (tension flange)

    26422.53 (compression fla

    b)Stresses acting on bolts:

    Shear stress (fv),(k/cm2)= 94.60

    Allowable shear stress (Fv),(k/cm2)= 1973.33 OK!

    Tension stress (ft max),(k/cm2)= 1338.73

    Allowable tension stress (Ft),(k/cm2)= 4110.00 OK!

  • 8/21/2019 Moment Connections.xls

    4/15

    c)Clculation of Head Plate thickness:

    Pe=Pf - dbo/4, (cm)= 3.38

    Ca= 1.13

    Cb= ( bfb/bep)^1/2= 0.94

    Af ,(cm2)= 27.74

    Aw,(cm2)= 39.5552

    Cm=CaCb(Af/Aw)^1/3*(Pe/dbo)^1/4= 1.02

    Me=Cm Ft Pe/4, (kg-cm)= 22982.08

    tep req= (6Me/eff. width.*0.75Fy)^1/2,(cm)= 1.60 required thk

    USE HEAD PLATE THICKNESS tep,(cm)= 1.9

    d)Flange of beam-head plate weldment (it must support max.tension on beam flange):

    l weld = 39.98 cm

    t weld= 0.48 cm

    USE WELD. THICNESS MIN. w,(cm)= 0.60

    e)Beam web-head plate weldement (it must support max. tension due to bending in beam web 0.6Fy):

    l weld = 84.16 cm

    t weld= 0.67 cm

    USE WELD. THICNESS MIN. w,(cm)= 0.70

    f)Check of Column stiffeners:

    Pbf: compression force in flange. Value shall be multiplied by 4/3 if earthquake or wind loads act

    or by 5/3 if includes only live and dead loads.

    Pbf (kg)= 35230.04

    Ductility of web column failure:

    Pbf

  • 8/21/2019 Moment Connections.xls

    5/15

    trig= tfb beam (recomended)= 1.46 cm

    brig/trigtrig (mnimum)= 0.88 cm

    Ast used= 45.26 cm2 Increase stiffener thickness

    Weldement of stiffeners= 7.72 mm

    h)Shear failure of column web:

    twc>=2,67.M/(Abc*Fy)

    Abc=(dc col-tfc)*(db beam-tfb) Abc= 1447.71 cm2

    2,67.M/(Abc.Fy)= 0.85 cm Reinforcement of column web not needed

  • 8/21/2019 Moment Connections.xls

    6/15

    A-3251480.00

    A36

    2500.00

    3700.00

    E70

    1480.00

    ge)

  • 8/21/2019 Moment Connections.xls

    7/15

  • 8/21/2019 Moment Connections.xls

    8/15

  • 8/21/2019 Moment Connections.xls

    9/15

  • 8/21/2019 Moment Connections.xls

    10/15

  • 8/21/2019 Moment Connections.xls

    11/15

  • 8/21/2019 Moment Connections.xls

    12/15

    11.5 700 -16200 -16200 -28150 -35500523024.29 523024.29 427972.82 373081.85

    966750

    OK!No cumple

  • 8/21/2019 Moment Connections.xls

    13/15

    OK!No cumple. Aumentar espesor plancha o numero de pernos

    OK!

    Stiffener RequiredNo stiffener required

    Use minimun dimensions

  • 8/21/2019 Moment Connections.xls

    14/15

    OK!Increase stiffener thickness

    Reinforce column webReinforcement of column web not needed