modular chiller solutions for industry and commerce modular chillers samurai

modular chiller solutions - Ultimate Air · 2017-09-28 · modular chiller solutions for industry and commerce modular chillers samurai. 2. CONTENTS Content 3 Features and benefits

  • Upload
    others

  • View
    12

  • Download
    0

Embed Size (px)

Citation preview

modular chiller solutions

for industry and commerce

modula

r c

hil

lers

sam

urai

2

CONTENTS

Content 3Features and benefits 4Models 14

– RCME AH1 14

– RHME AH1 15

– RCME WH 16

– RHME WH (with heating option) 17

– RCME CLH 18

Chiller module combinations 19Helping You - supporting software 20Chilled water indoor units 22

HITACHIAIRCON.COM @HITACHIAIRCONUK 3

You require control. With Hitachi’s Modular units you can be

confident of optimising the control of the chiller, saving energy

and efficiently interfacing with Building Management Systems.

Current Limiter settings, second Water Outlet Temperature setting

(4 for Heat Pump), Night Shift mode along Modbus and BACNet

Gateways will provide your site customisation. Whilst dynamic

sequencing of modules for priority, operation time, backup,

maintenance or module failure automatically provides continuity.

INTELLIGENT CONTROLS

Projects change and develop over time. In order to keep up you must

be able to rely on your selected products. Hitachi with its modular

design is an ideal solution for quick compact and space adaptable

installations whilst not limiting your ambitions for high efficiency. And

with up to 116 possible module combinations for both Air and Water

Cooled units, matching your project development couldn’t be easier.

RETROFITTING & REFURBISHMENT PROJECTS

Your Benefits

FEATURES AND BENEFITS

4

5

Safety first. Each module has its own compressor, regulators and

refrigerant circuit. Should a module fail, the remaining modules

maintain operational continuity, whilst Hitachi’s unique Dynamic

Back-up Control automatically starts any standby modules. Smart

defrost, automatic restart after power failure, anti-freeze pump

function, automatic fan on/off cycling for snow protection, remote

alarms all enhance the security of supply.

CONTINUOUS OPERATIONAL SAFETY

What drives your project, High efficiency? Reduced initial costs?

Or is space flexibility the determining factor?

With Hitachi’s Samurai Modular Chiller range you can specify your exact project

requirements by configuring a chiller with 1 or up to 8 modules. Two operating

modes selectable at commissioning allow the installation's performance to focus

on either high efficiency or high accuracy outlet water temperature. Alternatively,

spread the cost of investment and add modules to match your project phases.

PRICE, PERFORMANCE & SPACE FLEXIBILITY

5

Ourunique

modular design

FEATURES AND BENEFITS

Power Meter See page 11

BACnet Gateway See page 11

LCD Touch Panel See page 11

Water Flow Switch See page 13

EBOX LouverSafety Cover See page 11

ModBus Gateway See page 11

Electronic Expansion Valves See page 9

Water Filter See page 13

Plate Heat Exchanger See page 9

6

Pump Kit See page 13

DC Motor and Fan See page 9

Power Cable Routing See page 11

Increased Corrosion ProtectionSee page 13

Dual Pressure Relief Valve See page 13

Screw Compressor

Continuous Capacity Control See page 9

U-Shaped Heat Exchanger See page 9

Optional Accessories

Water Differential Pressure SwitchSee page 13

7

Modular design combined with world-renowned reliability. Samurai chillers are highly effective, even at partial load.

Engineered for tomorrow

FEATURES AND BENEFITS

8

New components

Continuous capacity controlHitachi's Continuous Capacity Control system uses advanced

electronic controls to position the infinitely variable slide valve within

each compressor. Capacity control per module is performed from

100% to 25% load linearly.

Due to the modular ability of the AH series the final Chiller turndown

is 100% to 3% (dependent on quantity of modules.)

Modulation allows exact load control and accurate chilled water

temperature without the need for expensive inverters offering

significant saving compared with step control systems.

Twin screw compressorLatest development of Hitachi’s world renowned screw compressor

technology. Optimised for R134a refrigerant, featuring continuous

capacity control and a unique cyclonic oil chamber.

A new rotor, a lighter casing and easy access to the E-Box enhance

efficiency and handling. Whilst a new bearing system allows the

overhaul period to be increased to 40,000 hours.

Electronic expansion valveTo provide greater efficiency and accuracy, all units are equipped

as standard with two electronic expansion valves to ensure equal

refrigerant distribution to both inlets of the plate heat

exchangers. New model with higher torque and increased pulses

range (656 to 5960) for improved endurance and precision.

DC motor and fanEach module is equipped with 4 DC inverter-controlled fan motors.

This ensures low power consumption especially in partial load. The use

of DC fan motors significantly improves the efficiency compared to

conventional AC motors. The continuous speed control of all motors

ensures precise regulation of airflow.

The new 4-bladed fan (710 mm) is optimized for use in the new AH

Series chillers:

• Low sound emissions

• Increased air throughput

• Reduced energy consumption

Plate heat exchangersThe new AH series units are equipped with true Dual-type brazed

plate exchangers, manufactured from stainless steel AISI316. These

plate heat exchangers have two refrigerant inlets in order to improve

the distribution of gas-liquid mixtures in the interior of the evaporator.

The higher efficiency and compact nature of the refrigeration system

allows for accurate control of the evaporation temperature.

Moreover, the pressure loss on the water inlet side has been

significantly reduced, less than 24 kPa at nominal conditions,

facilitating lower input power of the circulating pumps.

U-shaped heat exchangerThe AH series takes advantage of the latest technology that has

proven itself in the VRF Series. The "U" shaped style provides a 20%

increase in surface area compared with the previous series. 7 mm

piping ensure a high heat transfer ratio, whilst an additional sub-

cooling circuit increases the seasonal efficiency even at low load

conditions.

9

Always well connectedWe've taken care of everything. A range of optional accessories can be added to ensure Samurai meets all your requirements.

FEATURES AND BENEFITS

EBOX safety protectionThanks to this cover, the electrical components located

behind the lower half of the control box are covered and

cannot be touched inadvertently.

This accessory is available for individual modules and

preconfigured factory combinations of 2 or 3 modules.

Circuit breakerUse of a thermal-magnetic circuit breaker (MCB) in place

of fuses to protect the motors, fans and compressors.

A circuit breaker provides higher magnetic protection, since

this device has shorter trip times. Moreover it represents an

additional protection for the motor protection relay.

10

LCD touch panelEach Hitachi Model RC-1 AH series is equipped with its own

user-friendly touch screen panel, which shows the data of

the device and settings of various parameters to optimize the

performance of the device allows.

• 3.5 "TFT display

• 320 × 240 pixels (QVGA)

• 65,536 colors

• Available in multiple languages

• Status indicator of the unit: pump, fan, alarm, error messages

• Operating parameters: temperature, pressure, etc.

• Display of the last 10 alarms. The software saves detailed operating

parameters of the last 3 alarms (at the moment the alarm / 10

seconds before the alarm / 20 seconds before the alarm)

Low noiseCompressor enclosure manufactured from specially designed acoustic

panels. Module noise levels are reduced -3dB(A) or -5dB(A) against

the standard module, without any reduction in performance, efficiency

or footprint.

Power meterFactory installed.

With integrated hour meter.

Communication port protocol: ModBus, RS485 interface

This device is used to display the following data:

• Power Consumption

• Voltage (V), current (I), frequency (Hz), power factor, etc.

Average, maximum and instantaneous values.

ModBus Gateway

• Compatible with R134a modules

• Ports: RS485 & TCP (Ethernet)

• New parameters: High pressure, low pressure, operating time

• Easy configuration

• Din rail mounting

One Gateway per chiller (max. eight modules)

BACnet Gateway

• Compatible with R134a modules

• BACnet IP

• Easy configuration

• Din rail mounting (one Gateway per chiller (max.eight modules)

Regulations and control box

Power cable routingAdditional connectors assembled in a waterproof enclosure to facilitate

easier on site power and control wiring between modules. Factory

configured 2 or 3 module chillers include this as standard.

Common water pipeDesigned to provide balanced water distribution to each module and

for combinations of 2 or 3 modules, the common water pipe accessory

provides a single inlet and outlet connection for water circuit.

11

Engineering excellenceHitachi's vision is to deliver innovative solutions that answer society's challenges. But we never lose sight of the most important factor; our customers.

FEATURES AND BENEFITS

12

Water flow switchSafety device used to prevent the chiller operating when the system

water flow rate is insufficient or stopped. It, therefore, avoids water

freezing inside the Plate Heat Exchanger and protects against, pump

stopped or locked, pipe clogging, or dirty Plate Heat Exchanger.

Water strainerSafety device used to protect the sensitive Plate Heat Exchangers

from dirty water and clogging.

Water differential pressure switchFactory assembled safety device to protect the plate heat exchanger

against freezing caused by low or stopped water flow.

Practical Installation and Service

Pump kit

• Factory installed pump module

• Two versions:

- Single pump

- Double pump

• Two different pump sizes

• Incl. Filter, safety valve, venting and pump shut-off valves

• Unit dimensions remain unchanged

Increased dx coil heat exchanger protectionOptional additional protection applied on top of the standard

acrylic coat to each of the 3 Rows per “U” coil section.

The heat exchangers are protected to 3,500h in the “salty

spray test” according to DIN50021-SS. (Standard protection

is 480h)

Affords additional protection for installations in areas such

as; Industrial areas with high humidity and aggressive

atmospheres, Coastal environments with high salinity.

Increased chiller protectionOptional additional protection for the chiller components and structure.

Protected to 1,440h in the “salty spray test” according to DIN50021-SS.

(Standard protection is 480h)

Modifications are:

• dx coil heat exchanger protection

• Additional coating to the units inner and outer plates, electrical

panel, base, fan and heat exchanger guards.

• Stainless Steel Water Piping

• Painted low noise compressor enclosure

Protection is suitable for installations such as: Industrial areas with

high humidity and aggressive atmosphere and coastal and offshore

environments with high salinity.

Dual pressure relief valveDual Safety Valve assembled together with a changeover valve.

This factory installed option allows one Safety Valve to be removed

for servicing or repair whilst leaving the second valve enabled pro-

tecting the unit against high pressure conditions. Removing the need

to pump down the refrigeration circuit.

Machine protection

13

rcme ah1High Efficiency Cooling Only Air Cooled ChillerModern modular design of RCME AH1 brings maximum space

installation flexibility, whilst allowing investment to be spread to match

project phases.

• Site Customisation based on Price, Efficiency or Space

• Combine up to 8 modules for 100 to 1,400 kw installations

• Intelligent Controls - Dynamic Backup, Current Limiter

• Low Noise Options - No Capacity, Efficiency or footprint reduction

• 14 Factory Configurations, 116 total combinations

RCME 40~70AH1 Air Cooled Individual Modules

Data is based on the following conditions:

1 Chilled Water Inlet / Outlet Temperature: 12 / 7 °C Condenser Inlet Air Temperature: 35 °C.

2 Data is with (without) pump input included (according to the European Standard EN 14511).

water chillers – rcme ah1

Samurai Individual Modules RCME 40AH1 RCME 50AH1 RCME 60AH1 RCME 70AH1Cooling Capacity1 kW 100 125 150 175Total Input Power1 kW 27.2 35.6 47.0 54.5EER2 - 3.68 (3.63) 3.51 (3.47) 3.19 (3.16) 3.21 (3.18)ESEER2 - 4.54 (4.39) 4.34 (4.21) 4.25 (4.14) 4.28 (4.15)Sound Power Level dB(A) 89 91 93 94Sound Pressure Level (10 m) dB(A) 61 63 65 66Dimension (HxWxD) mm 2450 x 2230 x 200 2450 x 2230 x 200 2450 x 2230 x 200 2450 x 2230 x 200Operating weight kg 1340 1380 1460 1480

CompressorType HITACHI Semi-Hermetic Twin Screw, 25~100% variable capacity controlQuantity 1 1 1 1

R134a Refrigerant Circuit Twin Electronic Expansion Valve, high and low pressure sensors, filter, pressures switch and valveWater Side Heat Exchanger - Brazed Plate Heat ExchangerAir Side Heat Exchanger - Multi-Pass Cross Finned Tube (Cu/Al)Water Flow min ~ max (nominal) m3/h 10.8 ~ 24.6 (17.2) 13.4 ~ 30.7 (21.5) 16.1 ~ 36.9 (25.8) 18.8 ~ 43.0 (30.1)Water Pressure Drop (nominal) kPa 15.9 15.5 14.7 19.5Water Pipe Connection inch 2 x 2½” Victaulic (1 x Inlet, 1 x Outlet)Chilled Water Outlet (std, options) °C 5°C ~ +15°C, with Options -10°C ~ +30°CAmbient Air Temperature (Cool/Heat) °C -15°C ~ 46°CElectrical power supply - 3N~ 400V 50Hz

14

RHME 40~70AH1 Air Cooled Heat Pump Individual Modules

High Efficiency Heat Pump Air Cooled ChillerModern modular design of RHME AH1 brings cost effective expansion and redundancy,

whilst allowing investment to be spread to match project phases.

• Match differing installation cooling and heating loads by combining C/O & H/P modules

in the same “Chiller” *

• Combine up to 8 modules for 95 to 1,280 kw installations

• Intelligent Controls - Smart Defrost, Load Up/Down “Learning” Control

• Two Operating Modes - High Efficiency, Precise Water Outlet Temperature

• 14 Factory Configurations, 116 total combinations

rhme ah1

water chillers – rhme ah1

Samurai Individual Modules RHME 40AH1 RHME 50AH1 RHME 60AH1 RHME 70AH1Cooling Capacity1 kW 95 119 143 160Total Input Power1 kW 27.9 36.6 48.4 54.2EER3 - 3.4 (3.37) 3.25 (3.22) 2.96 (2.94) 2.95 (2.93)ESEER3 - 4.10 (4.01) 3.91 (3.84) 3.84 (3.77) 3.83 (3.75)Heating Capacity2 kW 92.00 115.00 138.00 138.00Total Input Power2 kW 28.6 37.4 48.8 48.7COP3 - 3.22 (3.20) 3.07 (3.06) 2.83 (2.83) 2.83 (2.82)SCOP (with pump) - 3.22 3.10 2.98 2.98Sound Power Level dB(A) 89 91 93 94Sound Pressure Level (10 m) dB(A) 61 63 65 66Dimension (HxWxD) mm 2450 x 2230 x 200 2450 x 2230 x 200 2450 x 2230 x 200 2450 x 2230 x 200Operating weight kg 1440 1480 1560 1580

CompressorType HITACHI Semi-Hermetic Twin Screw, 25~100% variable capacity controlQuantity 1 1 1 1

R134a Refrigerant Circuit Twin Electronic Expansion Valve, high and low pressure sensors, filter, pressures switch and valveWater Side Heat Exchanger - Brazed Plate Heat ExchangerAir Side Heat Exchanger - Multi-Pass Cross Finned Tube (Cu/Al)Water Flow min ~ max (nominal) m3/h 10.2 ~ 23.2 (16.3) 12.8 ~ 29.2 (20.5) 15.4 ~ 35.1 (24.6) 17.2 ~ 39.3 (27.5)Water Pressure Drop (nominal) kPa 9.4 9.7 10.6 13.0Water Pipe Connection inch 2 x 2½” Victaulic (1 x Inlet, 1 x Outlet)Chilled Water Outlet (std, options) °C 5°C ~ +15°C, with Options -10°C ~ +30°CHeated Water Outlet °C +35°C ~ +55°CAmbient Air Temperature (Cool/Heat) °C -15°C ~ 46°C / -9.5DB , -10WB ~ +21DB , +15.5WBElectrical power supply - 3N~ 400V 50Hz

Data is based on the following conditions:

1 Cooling operation: Chilled Water Inlet / Outlet Temperature: 12 / 7 °C Condenser Inlet Air Temperature: 35 °C.

2 Heating operation: Heated Water Inlet / Outlet Temperature: 40 / 45 °C Evaporator Air Inlet Temperature: 6°C WB .

3 Data is with (without) pump input included (according to the European Standard EN 14511).* Restrictions apply

15

High Efficiency Water Cooled ChillerModern modular design of RCME WH provides continuous operation

and safety.

• Only 806 mm width for easy site access on refurbishment projects

• Combine up to 8 modules for 140 to 1,920 kw installations

• Intelligent Controls - 2nd Water Temperature settings

• Reduced refrigerant per circuit in large capacity installations

• 116 total combinations

rcme wh

RCME 40~70WH Water Cooled Individual Modules

Samurai Individual Modules RCME 40WH RCME 50WH RCME 60WH RCME 70WHCooling Capacity1 kW 140 180 215 240Total Input Power1 kW 28.0 36.3 44.3 49.3EER3 - 5.00 (4.83) 4.96 (4.80) 4.85 (4.70) 4.87 (4.71)ESEER3 - 5.85 (5.35) 6.22 (5.69) 6.22 (5.71) 6.25 (5.72)Sound Power Level dB(A) 88 89 90 91Sound Pressure Level (10 m) dB(A) 60 61 62 63Dimension (HxWxD) mm 1681 x 806 x 1271 1681 x 806 x 1271 1681 x 806 x 1271 1681 x 806 x 1271Operating weight kg 860 950 1040 1075

CompressorType HITACHI Semi-Hermetic Twin Screw, 25~100% variable capacity controlQuantity 1 1 1 1

R134a Refrigerant Circuit Twin Electronic Expansion Valve, high and low pressure sensors, filter, pressures switch and valveWater Side Heat Exchanger - Evap - Brazed Plate Heat ExchangerWater Side Heat Exchanger - Cond - Brazed Plate Heat ExchangerEvap. Water Flow min ~ max (nom) m3/h 15.1 ~ 52.3 (24.1) 19.4 ~ 67.3 (31.0) 23.1 ~ 80.4 (37.0) 25.8 ~ 83.8 (41.3)Evap Water Pressure Drop (nominal) kPa 20.0 21.5 18.9 23.2Cond. Water Flow min ~ max (nom) m3/h 19.3 ~ 67.1 (30.9) 24.3 ~ 83.8 (38.9) 30.1 ~ 83.8 (48.2) 33.6 ~ 83.8 (53.8)Cond. Water Pressure Drop (nominal) kPa 24.1 25.9 29.3 29.8Water Pipe Connection inch 2 x 2½” Victaulic (1 x Inlet, 1 x Outlet per heat exchanger)Chilled Water Outlet (std, options) °C +5°C ~ +15°C, with Options -10°C ~ +25°CCondenser Water Outlet °C +22°C ~ +50°CElectrical power supply - 3N~ 400V 50Hz

water chillers – rcme wh

Data is based on the following conditions:

1 Cooling operation: Chilled Water Inlet / Outlet Temperature: 12 / 7 °C Condenser Inlet / Outlet Temperature : 30 / 35 °C

3 Data is with (without) pump input included (according to the European Standard EN 14511).

16

High Efficiency Water Cooled ChillerModern modular design of RCME WH provides continuous capacity control.

• Only 806 mm width for easy site access on refurbishment projects

• Combine up to 8 modules for 170 to 2,384 kw heating capacity

• Intelligent Controls - Redundancy with Dynamic Backup

• Site Customization based on – Price, Efficiency, Space

• 116 total combinations

rcme wh option for heating

RCME 40~70WH Water Cooled Individual Modules

water chillers – rcme wh

Samurai Individual Modules RCME 40WH RCME 50WH RCME 60WH RCME 70WHCooling Capacity1 kW 140 180 215 240Total Input Power1 kW 28.0 36.3 44.3 49.3EER3 - 5.00 (4.83) 4.96 (4.80) 4.85 (4.70) 4.87 (4.71)ESEER3 - 5.85 (5.35) 6.22 (5.69) 6.22 (5.71) 6.25 (5.72)Heating Capacity2 (Option) kW 171 215 267 298Total Input Power2 kW 33.4 43.3 52.8 58.8COP3 - 5.12 (5.00) 4.98 (4.86) 5.06 (4.95) 5.07 (4.96)SCOP (with pump) - 4.72 4.59 6.22 6.24Sound Power Level dB(A) 88 89 90 91Sound Pressure Level (10 m) dB(A) 60 61 62 63Dimension (HxWxD) mm 1681 x 806 x 1271 1681 x 806 x 1271 1681 x 806 x 1271 1681 x 806 x 1271Operating weight kg 860 950 1040 1075

CompressorType HITACHI Semi-Hermetic Twin Screw, 25~100% variable capacity controlQuantity 1 1 1 1

R134a Refrigerant Circuit Twin Electronic Expansion Valve, high and low pressure sensors, filter, pressures switch and valveWater Side Heat Exchanger - Evap - Brazed Plate Heat ExchangerWater Side Heat Exchanger - Cond - Brazed Plate Heat ExchangerEvap. Water Flow min ~ max (nom) m3/h 15.1 ~ 52.3 (24.1) 19.4 ~ 67.3 (31.0) 23.1 ~ 80.4 (37.0) 25.8 ~ 83.8 (41.3)Evap Water Pressure Drop (nominal) kPa 20.0 21.5 18.9 23.2Cond. Water Flow min ~ max (nom) m3/h 19.3 ~ 67.1 (30.9) 24.3 ~ 83.8 (38.9) 30.1 ~ 83.8 (48.2) 33.6 ~ 83.8 (53.8)Cond. Water Pressure Drop (nominal) kPa 24.1 25.9 29.3 29.8Water Pipe Connection inch 2 x 2½” Victaulic (1 x Inlet, 1 x Outlet per heat exchanger)Chilled Water Outlet (std, options) °C +5°C ~ +15°C, with Options -10°C ~ +25°CHeated Water Outlet °C +35°C ~ +55°CCondenser Water Outlet °C +22°C ~ +50°CElectrical power supply - 3N~ 400V 50Hz

Data is based on the following conditions:

1 Cooling operation: Chilled Water Inlet / Outlet Temperature: 12 / 7 °C Condenser Inlet / Outlet Temperature : 30 / 35 °C

2 Heating operation: Chilled Water Inlet / Outlet Temperature: 12 / 7 °C Hot Water: Condenser Inlet / Outlet Water Temperature: 40 / 45°C .

3 Data is with (without) pump input included (according to the European Standard EN 14511).

17

rcme clhHigh Efficiency Condenserless ChillerModern modular design of RCME CLH for quick, compact and adaptable installations.

• Only 806 mm width for easy access via site lifts

• Combine up to 8 modules for 135 to 1,720 kw capacity

• Low waterside pressure drop for greater efficiency

• Star-Delta starting per module, provides lower overall installation stating currents

• 80 total combinations

RCME 40~60CLH Condenserles Cooling Only Individual Modules

Samurai Individual Modules RCME 40CLH RCME 50CLH RCME 60CLHCooling Capacity1 kW 135 170 205Total Input Power1 kW 32.0 40.6 50.0EER3 - 4.22 4.19 4.10Sound Power Level dB(A) 88 89 90Sound Pressure Level (10 m) dB(A) 60 61 62Dimension (HxWxD) mm 1681 x 806 x 1271 1681 x 806 x 1271 1681 x 806 x 1271Operating weight kg 765 835 900

CompressorType HITACHI Semi-Hermetic Twin Screw, 25~100% variable capacity controlQuantity 1 1 1

R134a Refrigerant Circuit Twin Electronic Expansion Valve, high and low pressure sensors, filter, pressures switch and valveEvaporator Heat Exchanger - Brazed Plate Heat ExchangerEvap. Water Flow min ~ max (nom) m3/h 14.5 ~ 50.5 (23.2) 18.3 ~ 63.6 (29.2) 22.0 ~ 76.7 (35.3)Evap Water Pressure Drop (nominal) kPa 18.7 19.4 17.3Water Pipe Connection inch 2½” Victaulic (1 x Inlet, 1 x Outlet)Refrigerant Pipe Connection in (mm) Gas: 2 1/8" (53.98) Outer Dia. / Liquid: 1 1/8" (28.60) Outer DiaChilled Water Outlet (std, options) °C +5°C ~ +15°C, with Options -10°C ~ +25°CCondensing Temperature °C +30°C ~ +60°CElectrical power supply - 3N~ 400V 50Hz

water chillers – rcme clh

Data is based on the following conditions:

1 Cooling operation: Chilled Water Inlet / Outlet Temperature: 12 / 7 °C Condensing Temperature: 45 °C.

3 Data is without pump input included (according to the European Standard EN 14511).

18

RCME AH1 Air Cooled Cooling Only

Combinations1 Individual Module Two Modules Three ModulesRCME AH1 (Factory Configued) -

40 50 60 7080 90 100 110 120 130 140 150 160

RCME AH1 (Individual Modules) - 40/40 40/50 50/50 50/60 60/60 60/70 70/70 50/50/50 50/50/60Cooling Capacity kW 100 125 150 175 200 275 250 275 300 325 350 375 400ESEER (according to EN 14511) - 4.4 4.2 4.1 4.2 4.8 4.7 4.6 4.6 4.5 4.5 4.5 4.8 4.8

Chiller Module Combinations

Combinations1 Three Modules Four Modules Five ModulesRCME AH1 (Factory Configued) - 170 180 190 200 210 4 x 40 4 x 50 4 x 60 4 x 70 5 x 40 5 x 50 5 x 60 5 x 70RCME AH1 (Individual Modules) - 50/60/60 60/60/60 60/60/70 60/70/70 70/70/70 - - - - - - - -Cooling Capacity kW 425 450 475 500 525 400 500 600 700 500 625 750 875ESEER (according to EN 14511) - 4.7 4.6 4.6 4.6 4.6 4.9 4.7 4.6 4.6 5.0 4.8 4.6 4.6

Combinations1 Six Modules Seven Modules Eight ModulesRCME AH1 (Individual Modules) - 6 x 40 6 x 50 6 x 60 6 x 70 7 x 40 7 x 50 7 x 60 7 x 70 8 x 40 8 x 50 8 x 60 8 x 70Cooling Capacity kW 600 750 900 1050 700 875 1050 1225 800 1000 1200 1400ESEER (according to EN 14511) - 5.0 4.8 4.6 4.6 5.0 4.8 4.6 4.6 5.0 4.8 4.6 4.6

RHME AH1 Air Cooled Heat Pump

Combinations1 Individual Module Two Modules Three ModulesRHME AH1 (Factory Configued) -

40 50 60 7080 90 100 110 120 130 140 150 160

RHME AH1 (Individual Modules) - 40/40 40/50 50/50 50/60 60/60 60/70 70/70 50/50/50 50/50/60Cooling Capacity kW 95 119 143 160 190 262 238 262 286 303 320 357 381ESEER (according to EN 14511) - 4.0 3.8 3.8 3.8 4.3 4.3 4.2 4.2 4.1 4.1 4.0 4.4 4.3Heating Capacity kW 92 115 138 138 184 253 230 253 276 276 276 345 368

Combinations1 Three Modules Four Modules Five ModulesRHME AH1 (Factory Configued) - 170 180 190 200 210 4 x 40 4 x 50 4 x 60 4 x 70 5 x 40 5 x 50 5 x 60 5 x 70RHME AH1 (Individual Modules) - 50/60/60 60/60/60 60/60/70 60/70/70 70/70/70 - - - - - - - -Cooling Capacity kW 405 429 446 463 480 380 476 572 640 475 595 715 800ESEER (according to EN 14511) - 4.2 4.2 4.1 4.2 4.1 4.5 4.3 4.1 4.1 4.6 4.4 4.2 4.2Heating Capacity kW 391 414 414 414 414 368 460 552 552 460 575 690 690

Combinations1 Six Modules Seven Modules Eight ModulesRHME AH1 (Individual Modules) - 6 x 40 6 x 50 6 x 60 6 x 70 7 x 40 7 x 50 7 x 60 7 x 70 8 x 40 8 x 50 8 x 60 8 x 70Cooling Capacity kW 570 714 858 960 665 833 1001 1120 760 952 1144 1280ESEER (according to EN 14511) - 4.6 4.4 4.2 4.1 4.5 4.4 4.2 4.2 4.6 4.4 4.2 4.2Heating Capacity kW 552 690 828 828 644 805 966 966 736 920 1104 1104

RCME WH Water Cooled Cooling Only (Heating Option)

Combinations1 Individual Module Two Modules Three ModulesRCME WH (Individual Modules) - 40 50 60 70 2 x 40 2 x 50 2 x 60 2 x70 3 x 40 3 x 50 3 x 60 3 x70Cooling Capacity kW 140 180 215 240 280 360 430 480 420 540 645 720ESEER (according to EN 14511) - 5.4 5.7 5.7 5.7 6.1 6.1 6.2 6.2 6.3 6.6 6.6 6.6Heating Capacity kW 171 215 267 298 342 431 534 596 512 646 801 894

Combinations1 Four Modules Five Modules Six ModulesRCME WH (Individual Modules) - 4 x 40 4 x 50 4 x 60 4 x 70 5 x 40 5 x 50 5 x 60 5 x 70 6 x 40 6 x 50 6 x 60 6 x 70Cooling Capacity kW 560 720 860 960 700 900 1075 1200 840 1080 1290 1440ESEER (according to EN 14511) - 6.1 6.4 6.4 6.4 6.3 6.5 6.5 6.5 6.3 6.6 6.6 6.6Heating Capacity kW 683 862 1068 1192 854 1077 1336 1491 1025 1292 1603 1789

Combinations1 Seven Modules Eight ModulesRCME WH (Individual Modules) - 7 x 40 7 x 50 7 x 60 7 x 70 8 x 40 8 x 50 8 x 60 8 x 70Cooling Capacity kW 980 1260 1505 1680 1120 1440 1720 1920ESEER (according to EN 14511) - 6.2 6.5 6.5 6.5 6.3 6.5 6.5 6.5Heating Capacity kW 1196 1508 1870 2087 1366 1723 2137 2385

RCME CLH Condenserless Cooling Only

Combinations1 Individual Module Two Modules Three Modules Four ModulesRCME CLH (Individual Modules) - 40 50 60 2 x 40 2 x 50 2 x 60 3 x 40 3 x 50 3 x 60 4 x 40 4 x 50 4 x 60Cooling Capacity kW 135 170 205 270 340 410 405 510 615 540 680 820

Combinations1 Five Modules Six Modules Seven Modules Eight ModulesRCME CLH (Individual Modules) - 5 x 40 5 x 50 5 x 60 6 x 40 6 x 50 6 x 60 7 x 40 7 x 50 7 x 60 8 x 40 8 x 50 8 x 60Cooling Capacity kW 675 850 1025 810 1020 1230 945 1190 1435 1080 1360 1640

19

HelpingYou

Hitachi AppAvailable in several languages, the application is available

for free from Apple, Android and the web at this address:

http://hitachiac.tmti.net/product/

supporting software

20

http://www.hitachi-hitoolkit.com/chiller/users/login

Available in several languages

Hi-Toolkit for Industry selection softwareA user-friendly helpful sales aidDesigned as a valuable technical specification and financial tool for

air conditioning professionals working with commercial and industrial

chillers. The Hi-Toolkit for Industry software has been upgraded to

create a broad technical and financial proposal for your customers

and is fully compatible with all current operating systems and via

most hardware platforms including smartphone and tablet.

Select chillers and perform operation simulations on:

• ESEER, SCOP, SEER

• Seasonal performance and energy comsumption.

Save time when you are troubleshootingIn an increasingly technological environment and the

pressing need to save time, smartphone applications

have become indispensable in everyday life. Hitachi

have launched a smartphone application:

Hitachi Alarm Codes.

• Dedicated to Installing and service engineers,

troubleshoot all Hitachi products 24 hours a day,

7 days a week.

• Simply select your alarm code without the need

for bulky documentation.

• The app is able to quickly and easily diagnose all

faults even if the user is not familiar with Hitachi

products.

Quick and simple process

• Choose a model, output and product type

• The data sheet appears on your smartphone

• Add it to your favourites for future reference

• Send it as an e-mail attachment if you wish

21

ECM TechnologyRunning costs. Energy consumption. Life cycle. These are three issues that are becoming more and more

important in the choice of Indoor units. With these criteria

in mind, Johnson Controls offers the ECM range of FCU.

ECM technology comprises a brushless motor combined to

a dedicated electronic device (inverter). In comparison to

conventional units equipped with asynchronous 3-speed

motors, the fan coils can obtain a considerable energy

saving, by reducing power consumption up to 70%.

Air flow rate can be varied in continuously by means of

a 0~10V signal generated both by our controls or by

independent controls systems. The continuous air flow

control improves the acoustic comfort and allows a quick

response to the variation of thermal loads, enhancing the

stability of ambient temperature.

Advantages (compared to traditional brushed motors)

• Energy saving: electrical absorption reduced by up to 70%.

• Higher efficiency: possibility to adapt the air volume

and the capacities accordingly to the actual room loads.

• Higher comfort: reduced variation of the temperature

and relative humidity in the room.

• Extremely quiet operation.

• Reduced ware and higher reliability.

• Longer lift expectancy of the motor.

indoor units

Indoor unitsDriven by innovative trends and modern technology, the York® Indoor units have been designed around a platform of models, versions and accessories, which have been independently tested and certified by Eurovent. The York® Fan Coil range meets today's demanding requirements of performance, size, acoustics, low energy, ease of installation and maintenance.

Wired controlsJWC-3VRemote three speeds

controller

JWC-TJWC-3V + Electronic

thermostat and

Summer/Winter

switch

JWC-AUAutomatic JWC-T

JTM-BDigital Automatic

Remote controller

TMO 503 SV2Digital Automatic Remote

controller to be mounted

in the standard light

wall box

Infrared control

22

Features• New casing, with improved aesthetics

• Nine sizes suitable for horizontal or vertical

mounting with or without casing

• 3 fan speeds (choice of 6 fan speeds)

yfcn & yfcn ecm 2 & 4-pipe systems

indoor units - yfcn & yfcn ecm

YFCN Convertable Indoor Unit

Model (2-Pipe) 140 240 340 440 540 640 740 840 940max 1.23 1.81 2.57 3.12 4.09 4.79 5.58 6.47 7.60

Total Cooling Capacity 1 kW med 1.02 1.43 1.89 2.28 3.25 3.86 4.64 5.73 6.54min 0.67 1.01 1.65 1.83 2.19 2.83 3.56 4.03 4.88max 0.97 1.38 1.90 2.34 3.07 3.60 4.23 5.06 6.05

Sensible Cooling Capacity 1 kW med 0.79 1.07 1.38 1.68 2.40 2.86 3.47 4.43 5.11min 0.51 0.74 1.20 1.34 1.60 2.07 2.62 3.04 3.72max 1.55 2.20 3.07 3.76 4.83 5.88 6.71 8.43 10.08

Heating Capacity 2-Pipes 2 kW med 1.27 1.72 2.23 2.72 3.81 4.69 5.55 7.36 8.53min 0.82 1.18 1.94 2.16 2.53 3.39 4.20 5.06 6.22height 530 530 530 530 530 530 530 530 530

Dimensions 4 mm width 670 770 985 985 1200 1200 1415 1415 1415depth 225 225 225 225 225 225 225 255 255max 45 47 49 47 48 52 56 60 64

Sound Power Level dB(A) med 39 40 40 39 41 46 51 56 58min 32 30 36 33 31 37 42 45 50max 36 38 40 38 39 43 47 51 55

Sound Pressure Level 3 dB(A) med 30 31 31 30 32 37 42 47 49min 23 21 27 24 22 28 33 36 41

Power Supply V-ph-Hz 230 / 1 / 50 + E

1 Room temperature 27°C d.b., 19°C w.b. - Water temperature 7/12°C2 Room temperature 20°C - Water temperature 50°C3 The sound pressure levels are 9 dB(A) lower than the sound power levels and apply to the reverberant field of a 100 m3 room and a reverberation time of 0.5 sec4 Dimensions refer to the units with casing

Data shown is for 4 row cooling version, 2 pipe system.For performance of 3 row cooling version and/or 4 pipe system units please contact your local Hitachi Sales Office.

YFCN ECM Inverter Convertable Indoor Unit

Model 230 240 430 440 630 640 730 740 930 940max 10v 1.61 1.88 2.97 3.19 3.99 4.54 4.98 5.34 6.36 7.14

Total Cooling Capacity 1 kW med 5v 1.19 1.33 2.19 2.28 2.94 3.20 3.70 3.84 4.86 5.25min 1v 0.74 0.78 1.42 1.44 1.97 2.06 2.61 2.62 3.47 3.61max 1.30 1.44 2.28 2.41 3.11 3.41 3.84 4.03 5.20 5.63

Sensible Cooling Capacity 1 kW med 0.93 0.99 1.65 1.68 2.23 2.35 2.79 2.84 3.83 4.03min 0.56 0.57 1.04 1.04 1.47 1.49 1.93 1.91 2.65 2.71max 2.13 2.37 3.74 3.91 4.95 5.60 6.09 6.51 8.69 9.39

Heating Capacity 2-Pipes 2 kW med 1.53 1.63 2.70 2.75 3.59 3.87 4.47 4.61 6.41 6.70min 0.92 0.94 1.70 1.70 2.35 2.43 3.08 3.09 4.45 4.50max 1.63 - 2.74 - 3.68 - 4.63 - 5.98 -

Heating Capacity 4-Pipes 3 kW med 1.23 - 2.11 - 2.80 - 3.56 - 4.62 -min 0.81 - 1.47 - 2.00 - 2.65 - 3.40 -height 530 530 530 530 530 530 530 530 530 530

Dimensions 5 mm width 770 770 985 985 1200 1200 1415 1415 1415 1415depth 225 225 225 225 225 225 225 225 255 255max 51 51 51 51 54 54 57 57 64 64

Sound Power Level dB(A) med 41 41 42 42 44 44 48 48 55 55min 30 30 30 30 33 33 37 37 44 44max 42 42 42 42 45 45 48 48 55 55

Sound Pressure Level 4 dB(A) med 32 32 33 33 35 35 39 39 46 46min 21 21 21 21 24 24 28 28 35 35

Power Supply V-ph-Hz 230 / 1 / 50 + E

1 Room temperature 27°C d.b., 19°C w.b. - Water temperature 7/12°C2 Room temperature 20°C - Water temperature 50°C3 Room temperature 20°C - Water temperature 70/60°C4 The sound pressure levels are 9 dB(A) lower than the sound power levels and apply to the reverberant field of a 100 m3 room and a reverberation time of 0.5 sec5 Dimensions refer to the units with casing

• Multiple coil choices. Single or Dual

• Suction and discharge plenum optional

• Factory fitted valve packages.

4 available versions:

VC = Vertical Discharge with Casing

VCB = Vertical Discharge with Casing (floor)

HC = Horizontal Discharge with Casing

CD = Concealed unit without Casing

23

indoor units – yhky & yhky ecm

yhky & yhky ecm 2 & 4-pipe systems

Features• Cooling duty from 1.3 to 11.1 kW

• 2 & 4 pipes systems

• 2 sizes: 600x600 & 800x800

• Choice of 6 fan speeds

YHKY Cassette Indoor Unit

1 Room temperature 27°C d.b., 19°C w.b. - Water temperature 7/12°C2 Room temperature 20°C - Water temperature 50°C3 The sound pressure levels are 9 dB(A) lower than the sound power levels and apply to the reverberant field of a 100 m3 room and a reverberation time of 0.5 sec

For performance of 4 pipe system units please contact your local Hitachi Sales Office.

Model (2-Pipe) YHK 20-2 YHK 25-2 YHK 40-2 YHK 50-2 YHK 65-2 YHK 95-2 YHK 110-2max 1.98 2.68 4.33 5.02 6.16 9.51 11.10

Total Cooling Capacity 1 kW med 1.63 2.34 3.34 3.88 4.91 6.78 8.45min 1.27 1.84 2.25 2.94 4.21 5.31 5.31max 1.64 2.04 3.18 3.74 4.59 6.48 8.25

Sensible Cooling Capacity 1 kW med 1.32 1.75 2.39 2.81 3.58 4.48 6.09min 1.01 1.35 1.57 2.08 3.03 3.46 3.71max 2.64 3.35 5.23 6.17 7.77 10.71 14.00

Heating Capacity 2-Pipes 2 kW med 2.12 2.90 3.93 4.63 6.03 7.34 10.30min 1.62 2.22 2.56 3.43 5.12 5.61 6.13height 275 275 275 275 303 303 303

Dimensions mm width 575 575 575 575 820 820 820depth 575 575 575 575 820 820 820max 49 45 53 59 48 53 58

Sound Power Level dB(A) med 40 40 45 49 40 40 48min 33 33 33 41 33 34 34max 40 36 44 50 39 44 49

Sound Pressure Level 3 dB(A) med 31 31 36 40 31 31 39min 24 24 24 32 24 25 25

Power Supply V-ph-Hz 230 / 1 / 50 + E

YHKY ECM Inverter Cassette Indoor Unit

Model (2-Pipe) YHK ECM25-2 YHK ECM40-2 YHK ECM50-2 YHK ECM65-2 YHK ECM95-2max 10v 2.75 4.33 5.02 6.33 10.75

Total Cooling Capacity 1 kW med 5v 2.17 3.05 3.87 5.15 7.72min 1v 1.84 2.24 2.56 4.21 5.29max 2.09 3.18 3.74 4.72 7.94

Sensible Cooling Capacity 1 kW med 1.61 2.17 2.82 3.77 5.53min 1.35 1.57 1.81 3.03 3.69max 3.44 5.24 6.20 8.01 12.73

Heating Capacity 2-Pipes 2 kW med 2.67 3.58 4.63 6.35 8.83min 2.22 2.55 2.96 5.11 5.89height 275 275 275 303 303

Dimensions mm width 575 575 575 820 820depth 575 575 575 820 820max 49 45 53 59 48

Sound Power Level dB(A) med 40 40 45 49 40min 33 33 33 41 33max 40 36 44 50 39

Sound Pressure Level 3 dB(A) med 31 31 36 40 31min 24 24 24 32 24

Power Supply V-ph-Hz 230 / 1 / 50 + E

1 Room temperature 27°C d.b., 19°C w.b. - Water temperature 7/12°C2 Room temperature 20°C - Water temperature 50°C3 The sound pressure levels are 9 dB(A) lower than the sound power levels and apply to the reverberant field of a 100 m3 room and a reverberation time of 0.5 sec

For performance of 4 pipe system units please contact your local Hitachi Sales Office.

• Factory filled valve package

• Condensate pump integrated in all range

• Complete range of controls.

24

indoor units – yfcc & yfcc ecm

Model (2-Pipe) YFCC 130 YFCC 140 YFCC 230 YFCC 240 YFCC 330 YFCC 340max 1.50 1.74 2.37 2.57 3.34 4.02

Total Cooling Capacity 1 kW med 1.06 1.19 1.62 1.72 2.84 3.56min 0.88 0.97 1.37 1.44 1.97 2.49max 1.18 1.31 1.77 1.88 2.51 2.98

Sensible Cooling Capacity 1 kW med 0.81 0.88 1.19 1.24 2.11 2.63min 0.66 0.71 1.00 1.04 1.44 1.81max 1.93 2.10 2.86 3.12 4.02 4.77

Heating Capacity 2-Pipes 2 kW med 1.33 1.42 1.91 2.03 3.37 4.20min 1.08 1.14 1.60 1.69 2.30 2.90height 309 309 309 309 309 309

Dimensions mm width 592 592 592 592 592 592depth 592 592 970 970 1192 1192max 52 52 48 48 52 55

Sound Power Level dB(A) med 41 41 36 36 46 52min 35 35 33 33 35 41max 43 43 39 39 43 46

Sound Pressure Level 3 dB(A) med 32 32 27 27 37 43min 26 26 24 24 26 32

Power Supply V-ph-Hz 230 / 1 / 50 + E

1 Room temperature 27°C d.b., 19°C w.b. - Water temperature 7/12°C2 Room temperature 20°C - Water temperature 50°C3 The sound pressure levels are 9 dB(A) lower than the sound power levels and apply to the reverberant field of a 100 m3 room and a reverberation time of 0.5 sec

For performance of 4 pipe system units please contact your local Hitachi Sales Office.

YFCC ECM Inverter Coanda Cassette Indoor Unit

Model (2-Pipe) YFCC ECM 130 YFCC ECM 140 YFCC ECM 230 YFCC ECM 240 YFCC ECM 330 YFCC ECM 340max 1.56 1.81 3.16 3.50 3.75 4.02

Total Cooling Capacity 1 kW med 1.18 1.34 2.31 2.51 2.78 2.94min 0.82 0.91 1.46 1.55 1.87 1.95max 1.24 1.38 2.41 2.60 2.83 2.98

Sensible Cooling Capacity 1 kW med 0.91 0.99 1.73 1.84 2.06 2.15min 0.62 0.66 1.07 1.11 1.37 1.41max 2.02 2.20 3.85 4.32 4.54 4.78

Heating Capacity 2-Pipes 2 kW med 1.50 1.60 2.79 3.03 3.30 3.44min 1.02 1.07 1.72 1.82 2.19 2.25height 309 309 309 309 309 309

Dimensions mm width 592 592 592 592 592 592depth 592 592 970 970 1192 1192max 55 55 56 56 58 58

Sound Power Level dB(A) med 46 46 46 46 48 48min 35 35 34 34 36 36max 46 46 47 47 49 49

Sound Pressure Level 3 dB(A) med 37 37 37 37 39 39min 26 26 25 25 27 27

Power Supply V-ph-Hz 230 / 1 / 50 + E

1 Room temperature 27°C d.b., 19°C w.b. - Water temperature 7/12°C2 Room temperature 20°C - Water temperature 50°C3 The sound pressure levels are 9 dB(A) lower than the sound power levels and apply to the reverberant field of a 100 m3 room and a reverberation time of 0.5 sec

For performance of 4 pipe system units please contact your local Hitachi Sales Office.

yfcc & yfcc ecm 2 & 4-pipe systems

Features• Cooling duty from 0.9 to 4.0kW

• Coanda effect units

• 2 & 4 pipes systems

YFCC Coanda Cassette Indoor Unit

• Factory fitted valve packages

• 3 sizes: 600x600, 600x1000 & 600x12OO

• 6 fan speeds (3 pre-wired).

25

YHVP ECM Inverter Wall Mounted Indoor Unit

yhvp & yhvp ecm Wall Mounted 2-pipe system

indoor units – yhvp & yhvp ecm wall mounted

Model YHVP 1 YHVP 2 YHVP 3 YHVP 4max 1.87 2.18 3.03 3.81

Total Cooling Capacity 1 kW med 1.50 1.84 2.32 3.26min 1.24 1.43 1.89 2.62max 1.46 1.75 2.27 2.98

Sensible Cooling Capacity 1 kW med 1.14 1.43 1.69 2.47min 0.92 1.07 1.35 1.93max 2.58 3.09 3.86 5.07

Heating Capacity 2 kW med 2.00 2.39 2.84 4.20min 1.60 1.88 2.26 3.26max 322 322 322 322

Dimensions mm med 880 880 1185 1185min 212 212 212 212max 48 53 48 57

Sound Power Level dB(A) med 41 47 40 51min 35 39 35 43max 39 44 39 48

Sound Pressure Level 3 dB(A) med 32 38 31 42min 26 30 26 34

Power Supply V-ph-Hz 230 / 1 / 50 + E

Model YHVP ECM 1 YHVP ECM 2 YHVP ECM 3 YHVP ECM 4max 10v 2.00 2.26 3.29 3.75

Total Cooling Capacity 1 kW med 5v 1.58 1.87 2.53 3.05min 1v 1.17 1.47 1.83 2.34max 1.57 1.83 2.50 2.92

Sensible Cooling Capacity 1 kW med 1.20 1.46 1.86 2.29min 0.86 1.10 1.31 1.70max 2.78 3.23 4.25 4.99

Heating Capacity 2 kW med 2.12 2.58 3.15 3.88min 1.50 1.94 2.20 2.87height 322 322 322 322

Dimensions mm width 880 880 1185 1185depth 212 212 212 212max 52 55 53 57

Sound Power Level dB(A) med 46 47 45 49min 35 40 37 43max 43 46 44 48

Sound Pressure Level 3 dB(A) med 37 38 36 40min 26 31 28 34

Power Supply V-ph-Hz 230 / 1 / 50 + E

1 Room temperature 27°C d.b., 19°C w.b. - Water temperature 7/12°C2 Room temperature 20°C - Water temperature 50°C3 The sound pressure levels are 9 dB(A) lower than the sound power levels and apply to the reverberant field of a 100 m3 room and a reverberation time of 0.5 sec

Features• Available with standard AC motors or low energy EC motors

• Wired control or infrared control

• Automatic air louvre (-T and -MB variants only)

• Choice of 2 or 3-way valves fitted

• Condensate collection tray

• Air filter included

YHVP Wall Mounted Indoor UnitVersions:

Wired: YHVP Infrared: YHVP-T MB Electronic Board: YHVP-MB

Versions:

Wired: YHVP-ECM Infrared: YHVP-ECM-T MB Electronic Board: YHVP-MB

1 Room temperature 27°C d.b., 19°C w.b. - Water temperature 7/12°C2 Room temperature 20°C - Water temperature 50°C3 The sound pressure levels are 9 dB(A) lower than the sound power levels and apply to the reverberant field of a 100 m3 room and a reverberation time of 0.5 sec

26

indoor units – yhp-o & rhfp-o

yhp-o & rhfp-o 2&4-pipe systems

YHP-O Ductable Indoor Unit

Model 130 140 230 240 330 340 430 440max 1.93 2.15 3.42 3.85 5.20 5.68 7.40 8.22

Total Cooling Capacity 1 kW med 1.81 2.01 3.19 3.57 4.92 5.36 6.87 7.59min 1.58 1.74 2.94 3.27 4.44 4.80 5.95 6.51max 1.41 1.54 2.57 2.77 4.05 4.25 5.62 6.05

Sensible Cooling Capacity 1 kW med 1.31 1.43 2.37 2.55 3.80 3.99 5.16 5.54min 1.14 1.23 2.17 2.32 3.36 3.52 4.39 4.68max 2.39 2.40 4.25 4.69 6.79 7.31 9.41 10.30

Heating Capacity 2-Pipes 2 kW med 2.22 2.22 3.92 4.30 6.36 6.83 8.62 9.39min 1.91 1.90 3.57 3.90 5.63 6.00 7.29 7.85max 60 60 60 60 60 60 60 60

Available Pressure Pa med 50 50 50 50 50 50 50 50min 40 40 40 40 40 40 35 35height 218 218 248 248 248 248 248 248

Dimensions mm width 689 689 904 904 1119 1119 1570 1570depth 511 511 511 511 511 511 511 511max 50 50 51 51 57 57 58 58

Sound Power Level (outlet) dB(A) med 47 47 49 49 54 54 56 56min 44 44 46 46 51 51 52 52max 41 41 42 42 48 48 49 49

Sound Pressure Level3 (Outlet) dB(A) med 38 38 40 40 45 45 47 47min 35 35 37 37 42 42 43 43

Power Supply V-ph-Hz 230 / 1 / 50 + E

1 Room temperature 27°C d.b., 19°C w.b. - Water temperature 7/12°C2 Room temperature 20°C - Water temperature 50°C3 The sound pressure levels are 9 dB(A) lower than the sound power levels and apply to the reverberant field of a 100 m3 room and a reverberation time of 0.5 sec

For performance of 4 pipe system units please contact your local Hitachi Sales Office.

RHFP-O Ductable High Static Indoor Unit

Model 14 24 34 44 54 64 66 74 76max 6.11 8.44 11.18 14.23 18.52 24.19 29.59 33.09 40.83

Total Cooling Capacity 1 kW med 5.36 7.24 10.18 12.98 16.81 19.51 23.35 27.09 32.91min 4.28 5.16 9.06 11.33 15.04 12.99 14.92 23.06 27.59max 5.22 6.90 9.12 11.49 15.13 19.28 22.22 26.99 31.37

Sensible Cooling Capacity 1 kW med 4.41 5.71 8.10 10.25 13.42 14.94 16.96 21.22 24.40min 3.36 3.83 7.02 8.69 11.71 9.45 10.40 17.57 19.99max 8.86 11.78 15.54 19.64 24.79 43.60 49.77 61.14 70.64

Heating Capacity 2-Pipes 2 kW med 7.55 9.79 13.87 17.55 22.12 33.52 37.53 47.85 54.45min 5.80 6.58 12.04 14.92 19.39 20.86 22.58 39.34 44.20max 75 80 70 67 70 150 150 150 150

Available Pressure Pa med 50 50 50 50 50 150 150 150 150min 25 15 30 35 35 150 150 150 150height 310 310 360 360 435 488 488 588 588

Dimensions mm width 1233 1233 1233 1545 1545 1635 1635 1635 1635depth 748 748 748 903 903 1150 1150 1150 1150max 64 67 69 70 73 77 77 81 81

Sound Power Level (outlet) dB(A) med 59 62 65 68 70 71 71 75 75min 51 50 61 63 66 63 63 71 71max 55 58 60 61 64 68 68 72 72

Sound Pressure Level 3 (outlet) dB(A) med 50 53 56 59 61 62 62 66 66min 42 41 52 54 57 54 54 62 62

Power Supply V-ph-Hz 230 / 1 / 50 + E

1 Room temperature 27°C d.b., 19°C w.b. - Water temperature 7/12°C2 Room temperature 20°C - Water temperature 50°C3 Sound Pressure Level in a 100m2 room, at 1.5m distance and reverberating time of 0.5 sec

For performance of 3 row cooling version and/or 4 pipe system units please contact your local Hitachi Sales Office.

Features• Cooling duty from 1.9 to 40.8 kW

• Optional inlet & outlet plenums

• Optional electric heater

• Factory fitted valve packages

• Multiple Coil choices

27

Distributed by:

Specifications in this catalogue are subject to change to

allow Hitachi Air Conditioning Solutions to continue to

bring the latest innovations to its customers.

Hitachi Air Conditioning Europe SAS. (UK) Whitebrook Park, Lower Cookham Road, Maidenhead, Berkshire SL6 8YA, United Kingdom

tel: 01628 585 394email: [email protected]

Hitachi Air Conditioning Europe SAS. (Ireland)Unit 9, Bluebell Business Park, Old Naas Road, Dublin 12, Ireland

tel: 00 353 1 216 4406fax: 00 353 1 216 4407email: [email protected]

HACE GB 003_16