This document is not contractual - Kohler Co. reserves the right to modify any of the characteristics without notice, in a constant effort to improve the quality of its products. GBD5-05013 (KH750U) 05/19
KH750U Engine type DP222LCAlternator type KH03544TPerformance class G2
GENERAL CHARACTERISTICS
POWERESP PRP
VoltagekWe kVA kWe kVA
Standby Amps
DIMENSIONS SOUNDPROOFED VERSIONCommercial reference of the enclosure M230Length (mm) 5031Width (mm) 1690Height (mm) 2672Dry weight (kg) 5720Tank capacity (L) 610Acoustic pressure level @1m in dB(A) 92 -
DIMENSIONS COMPACT VERSIONLength (mm) 3470Width (mm) 1630Height (mm) 2185Dry weight (kg) 4080Tank capacity (L) 610
DESCRIPTIVE Kohler Co. Provides one-source responsibility for the
generating system and accessories. The generator set and its components are prototype-
tested, factory-built, and production-tested. A one-year limited warranty covers all systems and
components
POWER DEFINITIONPRP : Prime Power is available for an unlimited number of annual operating hours in variable load applications, in accordance with ISO 8528-1. ESP : The standby power rating is applicable for supplying emergency power in variable load applications in accordance with ISO 8528-1. Overload is not allowed
TERMS OF USEAccording to the standard, the nominal power assigned by the genset is given for 25°C Air Intlet Temperature, of a barometric pressure of 100 kPA (100 m A.S.L), and 30 % relative humidity. For particular conditions in your installation, refer to the derating table.ASSOCIATED UNCERTAINTYFor the generator sets used indoor, where the acoustic pressure levels depend on the installation conditions, it is not possible to specify the ambient noise level in the operating and maintenance instructions. You will also find in our operating and maintenance instructions a warning concerning the air noise dangers and the need to implement appropriate preventive measures.
Electronic governor Mechanically welded chassis with antivibration
suspension Main line circuit breaker Radiator for core temperature of 48/50°C max with
mechanical fan Protective grille for fan and rotating parts (CE option) 9 dB(A) silencer supplied separately Charger DC starting battery with electrolyte 24 V charge alternator and starter Delivered with oil and coolant -30°C Manual for use and installation
Frequency (Hz) Voltage (V) Standard control panel Optional control panel Optional control panelOptional control panel
60480/277 APM403APM802M80
208/120 744 930 676 845 2581
Sound power level guaranteed (Lwa) Acoustic pressure level @7m in dB(A) 82
1143 480/277 760 950 691 864
NA
KH750U ENGINE CHARACTERISTICS
GENERAL ENGINE DATAEngine model DOOSAN
Engine type DP222LC
Air inlet Turbo
Cylinders arrangement V
Number of cylinders 12
Displacement (L) 21.93
Charge Air coolant Air/Air DC
Bore (mm) x Stroke (mm) 128 x 142
Compression ratio 15 : 1
Speed (RPM) 1800
Pistons speed (m/s) 8.52 Maximum stand-by power at rated RPM (kW) 828
Frequency regulation, steady state (%) +/- 0.25%
BMEP (bar) 22.9
Governor type Electronic
COOLING SYSTEMRadiator & Engine capacity (L) -
Max water temperature (°C) -
Outlet water temperature (°C) -
Fan power (kW) 38
Fan air flow w/o restriction (m3/s) 16.2Available restriction on air flow (mm H2O) -
Type of coolant Glycol-Ethylene
Thermostat modulating range HT(°C) -
0.1 0.69
11.23
EMISSIONS Emission PM (g/kWh)
Emission CO (g/kWh)
Emission HC+NOx (g/kWh)
Emission HC (mg/Nm3) 5% O2 -
EXHAUSTExhaust gas temperature @ ESP 60Hz (°C) 493
Exhaust gas flow @ ESP 60Hz (L/s) 2170
Max. exhaust back pressure (mm H2O) 600
FUELConsumption @ 110% load (L/h) 203.8
Consumption @ 100% load (L/h) 183.2
Consumption @ 75% load (L/h) 134.4
Consumption @ 50% load (L/h) 91.3
Maximum fuel pump flow (L/h) 630
OILOil capacity (L) 40
Min. oil pressure (bar) 0.5
Max. oil pressure (bar) -
Oil consumption 100% load (L/h) 0.88
Oil sump capacity (L) -
HEAT BALANCEHeat rejection to exhaust (kW) 754
Radiated heat to ambient (kW) 77
Heat rejection to coolant (kW) 361
AIR INTAKEMax. intake restriction (mm H2O) -Intake air flow (L/s) 977
This document is not contractual - Kohler Co. reserves the right to modify any of the characteristics without notice, in a constant effort to improve the quality of its products. GBD5-05013 (KH750U) 05/19
KH750U ALTERNATOR CHARACTERISTICS
GENERAL DATA Alternator type KH03544TNumber of Phase Three phasePower factor (Cos Phi) 0.8Altitude (m) 0 to 1000Overspeed (rpm) 2250Number of pole 4Capacity for maintaining short circuit at 3 ln for 10 s Yes
Insulation class H T° class (H/125°), continuous 40°C H / 125°K T° class, standby 27°C H / 163°KAVR Regulation YesTotal Harmonic Distortion in no-load DHT (%) 2.5
Total Harmonic Distortion, on load DHT (%)
2.2
Wave form : NEMA=TIF <40Wave form : CEI=FHT <2Number of bearing 1Coupling DirectVoltage regulation at established rating (+/- %) 0.5
Recovery time (Delta U = 20% transient) (ms)
200
Protection class IP 23Technology Brushless
OTHER DATA Continuous Nominal Rating 40°C (kVA) 900Standby Rating 27°C (kVA) 970Efficiencies 100% of load (%) 96.6Air flow (m3/s) 1.08
Short circuit ratio (Kcc) 0.59Direct axis synchro reactance unsaturated (Xd) (%) 175.9Quadrature-axis synchro reactance unsaturated (Xq) (%)Open circuit time constant (T'do) (ms) 3700
Direct axis transient reactance saturated (X'd) (%) 13.9Short circuit transient time constant (T'd) (ms) 180Direct axis subtransient reactance saturated (X''d) (%) 7.5
Subtransient time constant (T"d) (ms) 15Quadrature-axis subtransient reactance saturated (X"q) (%) 12.3
Subtransient time constant (T"q) (ms) 14Zero sequence reactance unsaturated (Xo) (%) 2.28Negative sequence reactance saturated (X2) (%) 10.4Armature time constant (Ta) (ms) 71No load excitation current (io) (A) 0.7Full load excitation current (ic) (A) 4.3Full load excitation voltage (uc) (V) 38.1Engine start (Delta U = 20% perm. or 50% trans.) (kVA) 2580
Transient dip (4/4 load) - PF : 0,8 AR (%) 14.7
No load losses (W) 7147.2Heat rejection (W) 25342
DIMENSIONS
This document is not contractual - Kohler Co. reserves the right to modify any of the characteristics without notice, in a constant effort to improve the quality of its products. GBD5-05013 (KH750U) 05/19
122.1
Unbalanced load acceptance ratio (%) 100
Dimensions soundproofed versionM230 503116902672572061092-
Commercial reference of the enclosure Length (mm)Width (mm)Height (mm)Dry weight (kg)Tank capacity (L)Acoustic pressure level @1m in dB(A) Sound power level guaranteed (Lwa) Acoustic pressure level @7m in dB(A) 82
Dimensions DW compact version-
50831690244047801950
--
Commercial reference of the enclosure Length (mm)Width (mm)Height (mm)Dry weight (kg)Tank capacity (L)Acoustic pressure level @1m in dB(A) Sound power level guaranteed (Lwa) Acoustic pressure level @7m in dB(A) -
Dimensions DW soundproofed versionM230 DW
5083169029326410195092-
Commercial reference of the enclosure Length (mm)Width (mm)Height (mm)Dry weight (kg)Tank capacity (L)Acoustic pressure level @1m in dB(A) Sound power level guaranteed (Lwa) Acoustic pressure level @7m in dB(A) 82
KH750U CONTROL PANEL
APM802 dedicated to power plant mangementAPM403, basic generating set and power plant control
The APM303 is a versatile unit which can be operated in manual or automatic mode. It offers the following features:Measurements:phase-to-neutral and phase-to-phase voltages, fuel level(In option : active power currents, effective power, power factors, Kw/h energy meter, oil pressure and coolant temperature levels)Supervision:Modbus RTU communication on RS485Reports:(In option : 2 configurable reports)Safety features:Overspeed, oil pressure,coolant temperatures, minimum and maximum voltage, minimum and maximum frequency (Maximum active power P<66kVA)Traceability:Stack of 12 stored eventsFor further information, please refer to the data sheet for the APM303.
This document is not contractual - Kohler Co. reserves the right to modify any of the characteristics without notice, in a constant effort to improve the quality of its products. GBD5-05013 (KH750U) 05/19
The new APM802 command/control system is specifically designed for operating and monitoring power plants for markets including hospitals, data centres, banks, the oil and gas sector, industries, IPP, rental and mining.
The Human Machine Interface, designed in collaboration with a company specialising in interface design, facilitates operations with a large 100% touch screen. The pre-configured system for power plant applications features a brand new customisation function which complies with the international standard IEC 61131-3. New communication functions (PLC and regulation), improve the high level of equipment availability in the installation.
Advantages:Dedicated to power plant management.Specially researched ergonomics.High level of equipment availability.Modularity and long service life guaranteed.Making it easy to extend the installation
For more information, please refer to the sales documentation.
KH750UCONTROL PANEL
This document is not contractual - Kohler Co. reserves the right to modify any of the characteristics without notice, in a constant effort to improve the quality of its products. GBD5-05013 (KH750U) 05/19
M80, transfer of information
The M80 is a dual-function control unit. It can be used as a basic terminal block for connecting a control box and as an instrument panel with a direct read facility, with displays giving a global view of your generating set's basic parameters.
Offers the following functions:
Engine parameters: tachometer, working hours counter, coolant temperature indicator, oil pressure indicator, emergency stop button, customer connection terminal block, CE.