MIcom

Embed Size (px)

DESCRIPTION

PX30

Citation preview

  • T&DProtection & Control

    MiCOM P433, P435, P437Distance Protection Devices

    MiCOM P433, P435, P437Distance Protection

    Devices

  • Application and scope

    The MiCOM P433, P435 andP437 Distance Protection Devicesare used for selective short-circuitprotection, ground fault protection(UK: earth fault) and overloadprotection in medium, high andextra high voltage systems. Thesystems can be operated as solidlygrounded, low impedancegrounded (UK: solidlyearthed/resistance earthed),resonant grounded (UK: PetersenCoil) or insulated neutral systems.

    The devices have the followingcommon main functions: Fault detection logic using

    Overcurrent Undervoltage Under-impedance with load

    blinding Neutral overcurrent and/or

    neutral displacement voltage Distance protection with

    Polygonal or circular trippingcharacteristics

    Six distance zones Zone 1 extension Timer stages per zone and two

    additional back-up timer stages Directional voltage memory

    Measuring circuit monitoring Back-up overcurrent time

    protection Protective signaling (channel

    aided scheme logic) Auto-reclosing control Definite time overcurrent

    protection, 4 stages Inverse time overcurrent

    protection, 1 stage, directional

    Over/undervoltage protection Over/underfrequency protection Thermal overload protection Switch-on-to-fault protection Circuit breaker failure protection Limit value monitoring Programmable scheme logic.

    The P433 and P435 distanceprotection devices have thefollowing additional main functionsespecially for ground fault detectionand direction determination inPetersen Coil grounded or insulatedneutral power systems:

    Directional power protection Ground fault direction

    determination using steady statevalues

    Transient ground fault directiondetermination (optional)

    Ground fault protection signaling Ground fault tripping

    The P435 and P437 distanceprotection devices have thefollowing additional main functionsfor use in HV/EHV power systems:

    Power swing blocking Auto-reclosing control (single and

    three pole) Automatic synchronism check

    (optional) Ground fault (short circuit)

    protection (UK: Directional earthfault protection, DEF)

    Ground fault (short circuit)protection signaling (UK: DEFscheme logic)

    All main functions are individuallyconfigurable and can be disabledor enabled by the user as desired.By means of a straight forward

    configuration procedure, the usercan adapt the device flexibly to thescope of protection required ineach particular application. Due tothe powerful, freely configurablelogic of the device, specialapplications can beaccommodated.

    In addition to the features listedabove, as well as comprehensiveself monitoring, the following globalfunctions are available in thedevices:

    Parameter subset selection (4 alternative setting groups)

    Operating data recording (time tagged signal logging)

    Overload data acquisition

    Overload recording (time tagged signal logging)

    Ground fault data acquisition

    Ground fault recording (time tagged signal logging)

    Measured fault data

    Fault recording (time tagged signal loggingtogether with disturbancerecording of all measuredsignals: phase and residual

    2

    MiCOM P433, P435, P437Distance Protection Devices

  • 3current, phase-ground voltages,neutral displacement and busbarreference voltage)

    The P433/435/437 are ofmodular design. The pluggablemodules are housed in a robustaluminium case and electricallyconnected via an analogue and adigital bus printed circuit board.

    The nominal currents or nominalvoltages, respectively of themeasuring inputs, can be set withthe help of function parameters.

    The nominal voltage range of theoptical coupler inputs is 24 to 250Vdc without internal switching.

    The auxiliary voltage input for thepower supply is a wide rangedesign with a nominal voltagerange of 48 to 250V dc and 100to 230V ac. An additional versionis available for the lower nominalvoltage range of 24 to 36V dc.

    All output relays are suitable forboth signals and trip duties.

    The optional PT 100 input is leadcompensated, balanced and

    linearised for PT 100 resistancethermometers per IEC 60751.

    The optional 0 to 20mA inputprovides open circuit and overloadmonitoring, zero suppressiondefined by a setting, plus the optionof linearising the input variable via20 adjustable interpolation points.

    Two freely selected measuredsignals (cyclically updatedmeasured operating data andstored measured fault data) can beoutput as a load independent directcurrent via the two optional 0 to20mA outputs. The characteristicsare defined via 3 adjustableinterpolation points allowing aminimum output current (4mA, forexample) for receiver side opencircuit monitoring, knee pointdefinition for fine scaling and alimitation to lower nominal currents(10mA, for example).

    Where sufficient output relays areavailable, a freely selectedmeasured variable can be output inBCD-coded form via contacts.

    Control and display

    Local control panel

    17 LED indicators, 12 of whichallow freely configurable functionassignment

    PC interface

    Communication interface(optional).

    Information exchange is via thelocal control panel, PC interfaceand the optional communicationinterface. Using this informationinterface, the devices can beintegrated with substation controlsystems or telecontrol systems.

    Figure 1: Functional overview

    ! "# "$%& & '( )'( )*+

    ,- . /.%%%" $0 00 &&'( /

    +

    & &" &//$ +..$ 1.2 1.2

    &

    34&"

    3567

    83!

    9:

    !

    "#

    &

    6;

    '(

    '(

    &'(

    ,-

    "

    0

    0

    97697!

    4:

    :76:7>)

    Phase selective undervoltagedetection (V).

    Undervoltage and under-impedancedetection can be enabledseparately.

    All fault detection measurementelements operate simultaneously.

    Inrush stabilisation

    The operate function of overcurrentdetection can be stabilised underinrush conditions if desired. The ratio of the second harmoniccomponent of the phase currents tothe fundamental serves as thecriterion. This stabilisation is eitherphase selective or effective acrossall three phases depending on thechosen setting.

    Fuse failure monitoring

    A failure of the measuring voltagecaused by a short circuit or linebreaks in the secondary circuit, canbe detected by the internal fusefailure monitoring function. In thisevent, the distance protectionfunction will automatically beblocked and if appropriate, theback-up overcurrent time protectionfunction will be activated.

    Phase selection

    P433 and P435 devices evaluatethe distance decision only for onefault loop. This loop is selecteddepending on the fault typedetermined by the fault detectionlogic and the set loop preference.

    P437 devices evaluate the distancedecision for all fault loops. These loops are selected dependingon the fault type determined by thefault detection logic and whereapplicable to the set looppreference, eg. if only phase-phaseloop should be evaluated in case ofphase-phase ground faults.

    Directional voltage memory

    Directional determination requires avoltage memory for the followingreasons:

    Measuring voltage is too smallfor short fault distances

    Transients in the presence ofcapacitive voltage transformers

    Protection of series compensatedlines.

    To eliminate these problems, thedistance protection devices areequipped with a voltage memorywith continuous writing of thephase-phase voltage VAB into a ringmemory as long as the voltage andfrequency conditions are satisfied.

    The directional determinationelement can access the voltagememory when the measuredvoltages fall below a set value.Frequency compensation allows thememory to be used as a validdirectional reference for up to 2seconds after fault inception.

    ) 7?= 9?=( ((

    7?=

    =?:

    '

    )

    ) );

    ((##'"(

    @//6&&/6&A/6&&A/6&0A.A/)A/"(

    / B // B $/&& B .%%.& B .%%

    @ /@

    A/6&&A/6&

    A /

    A /

    3=C

    /6& /6&&

    Figure 2:Fault detection characteristic(Setting values: see address list)

  • 5Distance and directionaldetermination

    For measured angles within therange 45 to +135, a forward direction decision isissued, for angles outside thisrange, a backward directiondecision ensues. The distancedecision is obtained by comparingthe measured impedance with theset polygonal or circular trippingcharacteristic (see Figure 3).

    Six independent distance zones canbe set in total. Each zone can beset as forward directional,backward directional or nondirectional to suit requirements.

    Additional zone extension factorsfor phase-phase and phase-groundloops may be set for zone 1. Zoneextension is controlled by integratedfunctions such as auto-reclosingcontrol, protective signaling or byan external signal.

    With the P433 and P435, the fourthzone can be used as a specialzone depending on the setoperating mode, eg. to allow auto-reclosing only on the overhead linesection in cable/line systems or tocompensate the bundle conductoreffect. With the P437, the sixthzone is permanently measured andcould be used in user definedscheme logic.

    Tripping timer stages

    Each of the distance zones isassigned a settable timer stage.Additional timers serve asdirectional and non-directionalback-up timer stages, respectively.Once the back-up timer stages haveelapsed, the tripping decisionproceeds independent of distancemeasurement.

    All timer stages are initialised whena fault is detected. All tripping timerstages can be used separately.

    Mutual compensation

    When protecting parallel lines, caremust be taken for the effect ofmutual coupling of the lines in thezero sequence system. The P437could optionally be equipped withan additional CT input to measurethe residual current of the parallelline. This current can be taken intoaccount by the calculation of theground fault loop impedances,depending on a settable ratio of theresidual currents of the two lines.

    Power swing blocking (P435 and P437 only)

    Power sings between generatorsdue to severe load variations orsystem faults, may cause measuredimpedances to enter distancezones. To avoid incorrect tripping,the devices measure the ratedchange of power over a two cyclewindow to implement blocking forthe duration of the swing.

    Switch-on-to-fault protection

    Closing of a circuit breaker mightinadvertently lead to a short circuitfault due to a maintenance groundclamp not yet removed, forexample.

    The function switch-on-to-faultprotection provides for anundelayed protective trippingduring a settable time after amanual close command has beenissued. Depending on the operatingmode, either a trip command withinitialisation of the fault detectionlogic or a zone extension ofdistance protection according to theset zone extension factors results.

    Measuring circuit monitoring

    The voltage measuring circuits needto be monitored for short circuitsand line breaks. In preference, theauxiliary contact of the voltagetransformer m.c.b. is used to blockthe voltage dependent protectionfunction in the event of a shortedmeasuring circuit. Additionally,internal monitoring can be activatedso as to check for plausibility of themeasured zero sequence andnegative sequence components ofcurrent and voltage. If voltageunbalance is diagnosed then all

    !

    "#$%$#'#()*

    ++# +,$#

    "#-$%$#&()*

    Figure 3:Tripping characteristic Zone 1(Setting values: see address list)

  • 6voltage dependent protectivefunctions such as distancemeasurement are blockedautomatically.

    Furthermore, negative sequencecurrent and voltage are monitoredfor compliance with set limit values.If the limit value is exceeded for aset period of time then a signal isissued.

    Current unbalance monitoring canbe used to implement functions suchas circuit breaker pole discrpancy.

    Back-up overcurrent timeprotection

    When a fault occurs in the voltagemeasuring circuit, distancemeasurement is no longer possible.In this case, a one stage back-upovercurrent time protection function(BUOC) can be enabledautomatically. Activation of the auto-reclose control function is optionalduring BUOC operation.

    Back-up overcurrent time protectionstarting can be blocked by inrushstabilisation if desired (seeDistance Protection).

    Channel aided scheme logic

    Protective signaling

    The distance reach is usually set tovalues below 100% line length soas to avoid overlapping of adjacentsubstations. Protective signaling(teleprotection scheme logic)extends the reach of protection to100% by a logic operation on thesignals transmitted by the remotesubstation.

    Protective signaling can beoperated using one of the followingschemes shown in the table below.

    With P437 phase selective signaltransmission is possible.

    Where required, the followingadditional features can beactivated:

    Weak infeed trip logic

    Echo

    Transient blocking

    Frequency monitoring (de-blocking)

    A test send signal can be triggeredvia any of the device interfaces.

    Automatic synchronism check(P435 and P437 only/optional)

    This function can be used inconjunction with automatic ormanual (re)closure. In non radialnetworks this ensures that reclosurewill proceed only if the synchronismconditions are met.

    Auto-reclosing control

    The internal auto-reclosing control(ARC) capabilty depends on thedevice type:

    P433: only 3 pole

    P435: 1/3 pole, start dependent

    P437: 1/3 pole, trip dependent.

    ARC cycles with an high speedreclosure (HSR) and up to ninesubsequent time delay reclosures(TDR) are possible. HSR and TDRare independently configurable. For special cases, tripping prior toan HSR or TDR can be delayed.Triggering of the ARC function viabinary inputs (tripping by aprotective device operating inparallel) can be effected.

    Single pole tripping of the P435and P437 devices is possible withsingle phase faults (1pG) andisolated two phase faults (2p). Via three binary inputs, the phaseselective tripping signals of aprotective device operating inparallel, can be used for aplausibility check of the devicesown tripping decision.

    HSR and TDR reclosures arecounted and signaled separately.

    Test HSR can be triggered via anyof the device interfaces.

    A7

    A7 A7

    A7 A7

    &

    .

    AD

    A7

    A7

    A7

    EA7E/

    &

    . A7/

    EA7E/

    "$. A81$/2$/

    !EA7E!E/E

    1&>;;)&>;:+2 $/ !EA7E

    $

    1&>;;)&>;:+2

    !EA7E

  • 7Tripping time characteristics of Inverse Time Overcurrent Protection

    F7

    F7

    F7

    =?;;5F=?9;8

    :?4F7?;:

    Ground fault (short circuit)protection (P435 and P437 only)

    In the event of single phase faultswith high fault contact resistances,conventional distance algorithmsmay not be sufficiently sensitive.This fault condition is covered bythe device with a highly sensitiveintegrated back-up protectionfunction, namely a zero sequencepower directional protectionfunction using current and voltageof the zero sequence network forfault and directional determination.When the set operate values VNG>and IN> are exceeded, detectionand selective clearance of singlepole faults can be performed.

    Ground fault (short circuit) protection signaling (P435 and P437 only)

    In order to achieve high speedtripping by the ground fault (short circuit) protection function, thedevice is equipped with asupplementary ground fault (short circuit) protection signallinglogic. The operating mode of thislogic function is in parallel to andindependent of the protectivesignalling function of distanceprotection. The only limitationswould result if a commontransmission channel is used.

    The following operating modes aresupported:

    Signal comparison releasescheme

    Signal comparison blockingscheme

    The following functions can beactivated as required to suit theindividual application:

    Weak infeed trip logic

    Echo

    Transient blocking

    Frequency monitoring

    A test send signal can be triggeredvia any of the device interfaces.

    Definite time overcurrentprotection

    A four stage definite timeovercurrent protection (DTOC)function can be activated in parallelto distance protection. Three separate measuring elementsare available for this purpose:

    Maximum phase current

    Negative sequence current

    Residual current

    Starting of the phase and negativesequence current stages can beblocked by inrush stabilisation (seedistance protection) if desired.

    Inverse time overcurrentprotection

    The single stage inverse timeovercurrent protection (IDMT)function operates with threeseparate measuring elements:

    Maximum phase current

    Negative sequence current

    Residual current

    For the individual measuringelements, the user can select from amultitude of tripping characteristics(see table below).

    The IDMT protection function can beoperated in directional mode. The directional decision can eitherbe accepted from the distancemeasuring element or can beformed from the negative sequencecurrent and voltage.

    Starting of the phase and negativesequence current stages can beblocked by inrush stabilisation ifrequired (see distance protection).

    No. Tripping time characteristic Constants and formulae (t in s)(k = 0.01 to 10.00) a b c R

    0 Definite time t = k

    Per IEC 60255-31 Normally inverse 0.14 0.022 Very inverse 13.5 1.002 Extremely inverse 80 2.004 Long time inverse 120 1.00

    Per ANSI/IEEE C37.112 Trip Release5 Moderately inverse 0.0515 0.0200 0.1140 4.856 Very inverse 19.6100 2.0000 0.4910 21.607 Extremely inverse 28.2000 2.0000 0.1217 29.10

    Per ANSI Trip Release8 Normally inverse 8.9341 2.0938 0.17966 9.009 Short time inverse 0.2663 1.2969 0.03393 0.5010 Long time inverse 5.6143 1.0000 2.18592 15.75

    Not per standard11 RI type inverse

    Not per standard11 RXIDG type inverse

  • 8Over/undervoltage protection

    The over/undervoltage timeprotection function evaluates thefundamental wave of the phasevoltages and neutral displacementvoltage, as well as the positivesequence voltage and negativesequence voltage obtained from thefundamental wave of the threephase-ground voltages. Two definite time delay overvoltagestages each are provided forevaluation of the neutraldisplacement voltage and negativesequence voltage. Two additionaldefinite time delay undervoltagestages each are provided forevaluation of the phase voltagesand positive sequence voltage.

    Phase voltage evaluation can beperformed using either the phase-phase voltages or the phase--ground voltages as desired.For evaluating the neutraldisplacement voltage, the user maychoose between the neutraldisplacement voltage formedinternally from the three phase-ground voltages and theneutral displacement voltage formedexternally (from the open deltawinding of the voltage transformer,for example) via the fourth voltagemeasuring input.

    Over/underfrequencyprotection

    Over/underfrequency protectionhas four stages. Each of these canbe operated in one of the followingmodes:

    Over/underfrequency monitoring

    Over/underfrequency monitoringcombined with differentialfrequency gradient monitoring(df/dt) for system decouplingapplications

    Over/underfrequency monitoringcombined with medium frequencygradient monitoring

    (f/t) for load sheddingapplications

    Directional power protection

    (P433 and P435 only)

    The directional power protectionmonitors exceeding active andreactive power limit, power dropand reversal of direction atunsymmetrically operated lines.Evaluation of the power isperformed using the fundamentalwave of the three phase currentsand of the three phase-groundvoltages.

    Thermal overload protection

    Using this function, thermaloverload protection for lines,transformers and stator windings ofHV motors can be realized. The highest of the three phasecurrents serves to track a first orderthermal replica according to IEC 60255-8. The tripping time isdetermined by the set thermal timeconstant of the protected objectand the set tripping level tripdepending on the accumulatedthermal load p:

    A warning signal can be issued inaccordance with the set warninglevel warning.

    Circuit breaker failureprotection

    With the trip command, a timerstage is started for the monitoring ofthe circuit breaker action. If thetimer elapses due to the persistenceof the general starting, a circuitbreaker failure signal is issued.This serves to issue a second tripcommand (retrip) or, according tothe users choice, to tripneighbouring protection device(upstream breaker).

    The input of a circuit breakerfailure signal via an appropriatelyconfigured binary input while thegeneral starting persists, effects anundelayed trip command.

    Ground fault directiondetermination using steadystate values(P433 and P435 only)

    The ground fault direction isdetermined by evaluating theneutral displacement voltage (eg. from the open delta winding ofthe voltage transformer) and theresidual current (eg. from a corebalance or window type currenttransformer). The directional characteristic can beset to suit the method of systemgrounding (cos measured forPetersen Coil and sin circuit forinsulated neutral). In the cos circuit, the adjustable sector anglealso has an effect so that faultydirection decisions (resulting, forinstance, from the phase angle errorof the current and voltagetransformers) can be suppressedeffectively. Operate sensitivity andsector angle can be set separatelyfor the forward and backwarddirection, respectively.

    Alternatively, an evaluation basedon current only can be performed.In this case, only the magnitude ofthe filtered residual current is usedas ground fault criterion.

    Both procedures operate with eitherthe filtered fundamental or the fifthharmonic component in accordancewith the chosen setting.

    Transient ground faultdirection determination(P433 and P435 only/optional)

    The ground fault direction isdetermined by evaluating theneutral displacement voltage,calculated from the three phase--ground voltages and theneutral current on the basis of thetransient ground fault measuringprocedure. The direction decision islatched. The user may select eithermanual or automatic resetting aftera set time delay.

    9F

    BG

    9F

  • 9Limit monitoring

    A multitude of currents, voltagesand the measured temperature aremonitored to aid operation of theprotected line. This function is notintended to be used for protectionpurposes, as it has an inherent onesecond delay.

    For example, for the 3-phasecurrents, the phase-ground voltagesand the phase-phase voltages thehighest and lowest value isdetermined. These are evaluatedusing an operate value and timedelay set by the user. Thereby, thesecurrents and voltages can bemonitored for exceeding an upperlimit or falling below a lower limit.

    Programmable logic

    User configurable logic enables theuser to set-up logic operations onbinary signals within a frameworkof Boolean equations. By means ofa straightforward configurationprocedure, any of the protectiondevice signals can be linked bylogic OR or AND operations withthe possibility of additionalnegation operations.

    The output signal of an equationcan be fed into a further, higherorder equation as an input signal,thus leading to a set of interlinkedBoolean equations.

    The output signal of each equationis fed to a separate timer stage withtwo timer elements each and achoice of operating modes. Thus theoutput signal of each equation canbe assigned a freely configurabletime characteristic.

    The two output signals of eachequation can be configured to eachavailable input signal after logic ORlinking. The user configurable logicfunction is then able to influence theindividual functions without externalwiring (block, reset, trigger, forexample).

    Via non-storable continuous signals,monostable trigger signals andbistable stored setting/resettingsignals, the Boolean equations canbe controlled externally via any ofthe devices interfaces.

    Global functions

    Functions operating globally allowthe adaptation of the devicesinterfaces to the protected powersystem, offer support duringcommissioning and testing,providing continuously updatedinformation on the operation, aswell as valuable analysis resultsfollowing events in the protectedsystem.

    Clock synchronization

    The devices incorporate an internalclock with a resolution of 1ms. All events are time tagged basedon this clock, entered in therecording memory appropriate totheir significance and signalled viathe communication interface.Alternatively, two externalsynchronisation signals can be used according to the selectedcommunication protocol: using one of the protocols MODBUS,DNP3.0, IEC 60870-5-103 or IEC 60870-5-101 the device will besynchronised by a time telegramfrom a higher level substationcontrol system or in any other case,it will be synchronised using theIRIG-B signal input. The internalclock will then be adjustedaccordingly and operate with anaccuracy of 10ms if synchronisedvia protocol and 1ms ifsynchronised via IRIG-B signal.

    Parameter subset selection

    The function parameters for settingthe protection functions are, to alarge extent, stored in fourindependent parameter subsets.Switching between these alternativesetting groups is readily achievedvia any of the devices interfaces.

    Operating data recording

    For the continuous recording ofprocesses in system operation or ofevents, non-volatile ring memoryentries are provided. The relevantsignals, each fully tagged with dateand time at signal start and signalend, are entered in chronologicalsequence. Included are controlactions such as enabling ordisabling of functions as well aslocal control triggering for testingand resetting. The onset and end ofevents in the network, as far asthese represent a deviation fromnormal operation (overload, groundfault or short circuit, for example)are recorded.

    Overload data acquisition

    Overload situations in the networkrepresent a deviation from normalsystem operation and can bepermitted for a brief period only.The overload protection functionsenabled in the protection andcontrol units recognise overloadsituations in the system and providefor acquisition of overload datasuch as the magnitude of theoverload current, the relativeheating during the overloadsituation and its duration.

    Overload recording

    While an overload conditionpersists in the network, the relevantsignals, each fully tagged with dateand time at signal start and signalend, are entered into a non-volatilememory in chronological sequence.The measured overload data, fullytagged with the date and time ofacquisition, are also entered. Up toeight overload situations can berecorded. If more than eightoverload situations occur withoutinterim memory clearance then theoldest overload recording isoverwritten.

  • 10

    Ground fault data acquisition

    While a ground fault in a networkwith isolated neutral or resonantgrounding represents a system fault,it is usually nevertheless possible, inthe first instance, to continue systemoperation without restrictions. The ground fault determinationfunctions enabled in the protectiondevice recognise ground faults inthe system and provide for theacquisition of the associated groundfault data such as, the magnitude ofthe neutral displacement voltageand the ground fault duration.

    Ground fault recording

    While a ground fault conditionpersists in the power system, therelevant signals, each fully taggedwith date and time at signal startand signal end, are entered into anon-volatile memory inchronological sequence. The measured ground fault data,fully tagged with the date and timeof acquisition, are also entered. Up to eight ground faults can berecorded. If more than eight groundfaults occur without interim memoryclearance then the oldest groundfault recording is overwritten.

    Fault data acquisition

    A short circuit within the network isdescribed as a fault. The shortcircuit protection functions enabledin the devices recognise shortcircuits within the system andtrigger acquisition of the associatedmeasured fault data such as, themagnitude of the short circuitcurrent and the fault duration. As acquisition time, either the endof the fault or the start of the tripcommand can be specified by theuser. Triggering via an externalsignal is also possible. The acquisition of the measuredfault data is performed in themeasuring loop selected by theprotective device and providesimpedances and reactances as wellas current, voltage and anglevalues. The fault distance isdetermined from the measured shortcircuit reactance and is read outwith reference to the set 100%value of the protected line section.The fault location is output eitherwith each general starting or onlywith a general startingaccompanied by a trip (accordingto the users choice).

    Fault recording

    Fault recording comprises event anddisturbance recording along withthe stored fault measurands. Whilea fault condition persists in thepower system, the relevant signals,each fully tagged with date andtime at signal start and signal end,are entered into a non-volatilememory in chronological sequence.The measured fault data, fullytagged with the date and time ofacquisition, are also entered.Furthermore, the sampled values ofall analogue input variables such asphase currents and phase-groundvoltages are recorded during afault. Up to eight faults can berecorded. If more than eight faultsoccur without interim memoryclearance then the oldest faultrecording is overwritten.

    Self monitoring

    Comprehensive self monitoringprocedures within the devicesensure that internal hardware orsoftware errors are detected and donot cause malfunctions of theprotective devices.

    As the auxiliary voltage is turnedon, a functional test is carried out.Cyclic self monitoring tests are runduring operation. If test resultsdeviate from the default value thenthe corresponding signal is enteredinto the non-volatile monitoringsignal memory. The result of thefault diagnosis determines whethera blocking of the protection devicewill occur or whether a warningonly is issued.

  • 11

    Control

    All data required for operation ofthe protection and control unit areentered from the integrated localcontrol panel. Data important forsystem management is also read outfrom here. The following tasks canbe handled via the local controlpanel:

    Readout and modification ofsettings

    Readout of cyclically updatedmeasured operating data andstate signals

    Readout of operating data logsand of monitoring signal logs

    Readout of event logs (afteroverload situations, ground faultsor short circuits in the powersystem)

    Resetting of the unit andtriggering of further controlfunctions designed to supporttesting and commissioning tasks

    The local control panel shown inFigure 4 comprises the local controlelements and functions describedbelow.

    Display

    (1) The integrated local controlpanel has an LCD display with4 x 20 alphanumericcharacters.

    17 LED indicators are provided forsignal display.

    (2) 5 LED indicators arepermanently assigned tosignals.

    (3) The remaining 12 LED indicatorsare available for freeassignment by the user. A separate adhesive label isprovided for user definedlabeling of these LED indicatorsaccording to the chosenconfiguration.

    Menu tree

    (4) By pressing the cursor keysand guided by the

    LCD display, the user moveswithin a plain text menu. All setting parameters andmeasured variables as well asall local control functions arearranged in this menu which isstandardised for all systemdevices. Changes to the settingscan be prepared and confirmedby means of the ENTER key

    which also serves to triggerlocal control functions. In theevent of erroneous entries, exitfrom the EDIT MODE withrejection of the entries ispossible at any time by meansof the CLEAR key . Whenthe EDIT MODE is not activated,pressing the CLEAR key has theeffect of resetting theindications. Pressing the READkey provides direct accessto a preselected point in themenu.

    Type label and PC interface

    (5) The upper covering flap islabeled with the device typedesignation. Located under theflap is the type identificationlabel with information on theorder number, serial numberand the nominal electricalvalues.

    (6) Located under the lowercovering flap is the serialinterface for connecting a PC.

    (7) To prevent unauthorizedopening of the lower flap, it canbe sealed using the attachedeyelets.

    1

    2

    6 74

    3

    5

    Figure 4: Local control panel

    Measured value panels

    The configuration of the localcontrol panel allows the installationof measured value Panels on theLCD display. The Panels areautomatically displayed for certainoperation conditions of the system.Priority increases from normaloperation to operation underoverload conditions and finally tooperation following a short circuit inthe system. The protection devicethus provides the measured valuedata relevant for the prevailingconditions.

    Password protection

    Access barriers protect the entermode in order to guard againstinadvertent or unauthorisedchanging of parameters ortriggering of control functions

  • 12

    Mechanical design

    The device is supplied in two casedesigns.

    Surface mounting case

    Flush mounting case

    With both case designs, connectionis via threaded terminal ends withthe option of either pin terminal orring terminal connection.

    Two 40TE flush mounted cases canbe combined to form a complete19 mounting rack.

    Figure 5 shows the modularhardware structure of the devices.The plug-in modules can becombined to suit individualrequirements. The device itself canidentify the fitted modules. During each startup, the numberand type of fitted modules areidentified and checked forcompliance with the permissibleconfigurations. As as function of thecomponents actually fitted, thecorresponding configurationparameters are then enabled forapplication.

    Transformer module T

    The transformer module converts themeasured currents and voltages tothe internal processing levels andprovides for electrical isolation.

    Processor module P

    The processor module performs theanalogue/digital conversion of themeasured variables as well as alldigital processing tasks.

    Transient ground faultevaluation module N

    The optional transient ground faultmodule evaluates the measuredvariables according to the transientground fault evaluation scheme.

    Local control module L

    The local control moduleencompasses all control and displayelements as well as a PC interfacefor running the operating program.The local control module is locatedbehind the front panel andconnected to the processor modulevia a ribbon cable.

    Communication module A

    The optional communication moduleprovides a serial informationinterface for the integration of theprotection and control unit into asubstation control system. The communication module isplugged into the processor module.

    Bus modules B

    Bus modules are printed circuitboards (PCBs) without any activecomponents. They provide theelectrical connection between theother modules. Two types of busmodules are used, namely theanalogue and the digital bus PCB.

    Binary I/O modules X

    The binary I/O modules areequipped with optical couplers forbinary signal input as well as outputrelays for the output of signals andcommands or combinations ofthese.

    Analogue module Y

    The analogue module is fitted witha PT 100 input, a 20 mA input andtwo 20 mA outputs. One outputrelay each is assigned to two 20 mA outputs. Additionally, fouroptical coupler inputs are available.

    Power supply module V

    The power supply module ensuresthe electrical isolation of the deviceas well as providing the powersupply. Depending on the chosendesign version, optical couplerinputs and output relays areprovided in addition.

    H @

    ))) D?

    )

    I&

    1&2& &

    &

    0

    &

    0

    # --

    ,-0,H

    - -

    0)

    "

    !I

    Figure 5: Hardware structure

  • 13

    Technical data

    General data

    DesignSurface mounting case suitable for wall installation orflush mounting case for 19 cabinets and for controlpanels

    Installation positionVertical 30

    Degree of protectionPer DIN VDE 0470 and EN 60529 or IEC 60529.IP 52; IP 20 for the rear connection area of the flushmounting case.

    WeightCase 40T: max. 7 kgCase 84T: max. 11 kg

    DimensionsSee dimensions

    Terminal connection diagramsSee Location and connections

    TerminalsPC interfaceDIN 41652 connector (X6), type D-Sub, 9 pin.

    Communication interface Optical plastic fibres (X7 and X8):

    F-SMA interface per DIN 47258 or IEC 60874-2 per plastic fibresorBFOC-(ST) interface 2.5 per DIN 47254-1 or IEC 60874-10 per glass fibreorLeads (X9, X10):Threaded terminal ends M2 for wire cross sections up to 1.5mm2

    IRIG-B interface (X11)BNC plug

    Current measuring inputsThreaded terminals for pin terminal connection:

    Threaded terminal ends M5, self centering with wire protection for conductor cross sections of 4mm2orThreaded terminals for ring terminal connection:In preparation

    Other inputs and outputsThreaded terminals for pin terminal connection:

    Threaded terminal ends M3, self centering withwire protection for conductor cross sections of 0.2to 2.5mm2orThreaded terminals for ring terminal connection:In preparation

    Creepage distances and clearancesPer EN 61010-1 and IEC 60664-1Pollution degree 3 working voltage 250V overvoltage category III, impulse test voltage 5kV

    TestsType testTests according to EN 60255-6 or IEC 60255-6

    EMCInterference suppressionPer EN 55022 or IEC CISPR 22, Class A

    1 MHz burst disturbance testPer EN 60255-22-1 or IEC 60255-22-1, Class III Common mode test voltage: 2.5kVDifferential test voltage: 1.0kVTest duration: > 2s, Source impedance: 200

    Immunity to electrostatic dischargePer EN 60255-22-2 or IEC 60255-22-2, Level 3 Contact discharge, single discharges: > 10Holding time: > 5s, Test voltage: 6kV Test generator: 50 to 100M, 150pF/330

    Immunity to radiated electromagnetic energyPer EN 61000-4-3 and ENV 50204, Level 3 Antenna distance to tested device:

    > 1m on all sidesTest field strength, freq. band 80 to 1000MHz:

    10V/mTest using AM: 1kHz /80%Single test at 900 MHz: AM 200Hz/100%

    Electrical fast transient or burst requirementsPer IEC 60255-22-4Test severity level 4Rise time of one pulse: 5nsImpulse duration (50% value): 50nsAmplitude: 4kV/2kV, resp.Burst duration: 15ms, Burst period: 300msBurst frequency: 2.5kHzSource impedance: 50

    Surge immunity testPer EN 61000-4-5 or IEC 61000-4-5, Level 4Testing of power supply circuitsunsymmetrically/symmetrically operated linesOpen circuit voltage front time/time to half value:

    1.2/50s, Short circuit current front time/time to half value:

    8/20s, Amplitude: 4/2kV, Pulse frequency: > 5/minSource impedance: 12/42

    Immunity to conducted disturbances inducedby radio frequency fieldsPer EN 61000-4-6 or IEC 61000-4-6, Level 3Disturbing test voltage: 10V

    Power frequency magnetic field immunityPer EN 61000-4-8 or IEC 61000-4-8, Level 4Frequency: 50Hz, Test field strength: 30A/m

    Alternating component (ripple) in dc auxiliaryenergizing quantityPer IEC 60255-1112%

    InsulationVoltage testPer IEC 60255-5 or EN 610102kV ac, 60sFor the voltage test of the power supply inputs, directvoltage (2.8kV dc) must be used. The PC interfacemust not be subjected to the voltage test.

    Impulse voltage withstand testPer IEC 60255-5Front time: 1.2s, Time to half value: 50sPeak value: 5kV, Source impedance: 500

    Mechanical robustnessVibration testPer EN 60255-21-1 or IEC 60255-21-1Test severity class 1Frequency range in operation:

    10 to 60Hz, 0.035mm, 60 to 150Hz, 0.5gFrequency range during transport:

    10 to 150Hz, 1 g

    Shock response and withstand test, bumptestPer EN 60255-21-2 or IEC 60255-21-2Test severity class 1Acceleration: 5g/15g, Pulse duration: 11ms

    Seismic testPer EN 60255-21-3 or IEC 60255-21-3Test procedure A, Class 1Frequency range:

    5 to 8Hz, 3.5mm/1.5mm8 to 35Hz, 10/5m/s2,

    3 x 1 cycle

    Routine testTests per EN 60255-6 or IEC 60255-6

    Voltage testPer IEC 60255-52.2kV ac, 1s For the voltage test of the power supply inputs, directvoltage (2.8kV dc) must be used. The PC interfacemust not be subjected to the voltage test.

    Additional thermal test100% controlled thermal endurance test, inputs loaded

    Environmental conditionsAmbient temperature rangeRecommended temperature range:

    5C to +55C or +23F to +131FLimit temperature range:

    25C to +70C or 13F to +158F

    Ambient humidity range 75% relative humidity (annual mean), up to 56 days at 95% relative humidity and 40C, condensation not permissible

    Solar radiationAvoid exposure of the front panel to direct solarradiation.

    RatingsMeasurement inputsNominal frequency fnom: 50 and 60Hz (settable)Operating range: 0.95 to 1.05fnomOver/Underfrequency protection: 40...70Hz

    CurrentNominal current Inom: 1 and 5A (settable)Nominal consumption per phase: < 0.1 VA at InomLoad rating:

    continuous: 4 Inomfor 10s: 30 Inomfor 1s: 100 Inom

    Nominal surge current: 250 InomVoltageNominal voltage Vnom: 50 to 130V ac (settable)Nominal consumption per phase:

    < 0.3VA at Vnom = 130V acLoad rating: continuous 150V ac

    Binary signal inputsNominal auxiliary voltage Vin,nom:

    24 to 250V dcOperating range: 0.8 to 1.1Vin,nom

    with a residual ripple of up to 12% of Vin,nomPower consumption per input:

    Vin = 19 to 110V dc: 0.5W 30%Vin > 110V dc: Vin x 5mA 30%

    Output relaysRated voltage: 250V dc, 250V acContinuous current: 5AShort duration current: 30A for 0.5sMaking capacity: 1000W (VA) at L/R = 40msBreaking capacity:

    0.2A at 220V dc and L/R = 40ms4A at 230V ac and cos = 0.4

    Analogue inputs and outputsDirect current inputInput current: 0 to 26mAValue range: 0.00 to 1.20 Idc,nom (Idc,nom = 20mA)Maximum permissible continuous current: 50mAMaximum permissible input voltage: 17VInput load: 100Open circuit monitoring: 0 to 10mA (adjustable)Overload monitoring: > 24.8mAZero suppression: 0.000 to 0.200 Idc,nom (adjustable)

    Resistance thermometer:Only PT 100 permitted, mapping curve per IEC 60751Value range: 40 to +215C

    (equivalent to 40 to +419F)3 wire configuration: max. 20 per conductor.Open and short circuited input permitted.Open circuit monitoring:

    > +215C (or > +419F) and < 40C (or < 40F)

  • 14

    Direct current outputOutput current: 0 to 20mAMaximum permissible load: 500Maximum output voltage: 15V

    Power supplyNominal auxiliary voltageVA,nom: 48 to 250V dc and 100 to 230V acor VA,nom: 24V dc (depends on ordering)

    Operating rangefor direct voltage: 0.8 to 1.1 VA,nomwith a residual ripple of up to 12% of VA,nomfor alternating voltage: 0.9 to 1.1 VA,nomNominal consumptionat VA = 220V dc/maximum number of modules fitted:In case 40TE:

    Initial position approx.: 13WActive position approx.: 29W

    In case 84TE:Initial position approx.: 13WActive position approx.: 37W

    Start-up peak current< 3A, duration 0.25ms

    Stored energy time 50ms for interruption of VA 220 dc

    PC interfaceTransmission rate: 300 to 115,200 baud (settable)

    Communication interfaceProtocol can be switched between: IEC 60870-5-103, IEC 60870-5-101, MODBUS, DNP 3.0Transmission rate: 300 to 38400 baud (settable)

    Wire leadsPer RS 485 or RS 422, 2kV isolation Distance to be bridged:

    peer-to-peer link: max. 1200mmulti-endpoint link: max. 100m

    Plastic fibre connectionOptical wavelength: typ. 660 nmOptical output: min. 7.5 dBmOptical sensitivity: min. 20 dBmOptical input: max. 5 dBmDistance to be bridged: max. 45m1)

    Glass fibre connection G 50/125Optical wavelength: typ. 820 nmOptical output: min. 19.8 dBmOptical sensitivity: min. 24 dBmOptical input: max. 10 dBmDistance to be bridged: max. 400m1)

    Glass fibre connection G 62,5/125Optical wavelength: typ. 820 nmOptical output: min. 16 dBmOptical sensitivity: min. 24 dBmOptical input: max. 10 dBmDistance to be bridged: max. 1400m1)

    IRIG-B interfaceFormat B122 Amplitude modulated, 1kHz carrier signal BCD time of year code

    1) Distance to be bridged for optical outputs and inputs that areequal on both ends, taking into account a system reserve of3dB and typical fibre attenuation.

    Typical characteristic dataMain functionMinimum output pulse for a trip command:

    0.1 to 10s (settable)Output pulse for a close command:

    0.1 to 10s (settable)

    Distance protectionMinimum fault detection time: 12msFault detector reset time 30ms 10ms Directional sensitivity:

    up to 2s after fault detection: 2s after fault detection and for switching on to fault: 200 mV 10%

    Shortest tripping time: P433/P435: approx. 19msP437: approx. 16ms

    Fault detection and measurement resetting ratio: 0.95

    Overcurrent time protectionShortest tripping time: approx. 25msStarting reset time approx. 25ms Starting and measurement resetting ratio: 0.95

    Over/undervoltage protectionShortest tripping time: approx. 40msStarting reset time approx. 30ms Starting resetting ratio: settable hyterisis 1...10%

    Deviations of the operate valuesReference conditionsSinusoidal signals with nominal frequency fnom, totalharmonic distortion 2%, ambient temperature 20C and nominal auxiliary voltage VA,nomDeviationDeviation relative to the set value under referenceconditions

    Distance protectionFault detector V, VNG>>: 3%Fault detector I>, I>>, IN

    Setting range 0.1 to 0.25 Inom: 5%Setting range > 0.25 Inom: 3%

    Fault detector Z< at k = 0, 30, 60, 90: 5%Impedance measurement Z<

    Deviation at K = 0, 90: 3%Deviation at K = 30, 60: 5%

    Directional determination: 3

    Measuring circuit monitoring Operate values Ineg, Vneg: 3%

    Back-up DTOC protectionOperate value I>: 3%

    Overcurrent time protection Operate values I>, IN>: 5%

    Over/undervoltage protection Operate values V: 3%

    Over/underfrequency protection Operate values f: 3%

    Directional power protection Operate values V: 3%

    Ground fault direction determination Using steady state values Operate values VNG>, IN.act, IN.reac, IN>: 3%Sector angle: 1

    Thermal overload protectionOperate value : 5%

    Deviations of the timer stagesReference conditionsSinusoidal signals with nominal frequency fnom, total harmonic distortion 2%, ambient temperature 20C and nominal auxiliary voltage VA,nomDeviationDeviation relative to the setting under referenceconditions

    Definite time stages1% +20...40ms

    Inverse time stages5% +10 to 25ms (measured variable greater than 2 Iref)for IEC characteristic extremely inverse and for thermaloverload protection:7.5% + 10 to 20ms

    Deviations in measured dataacquisitionReference conditionsSinusoidal signals with nominal frequency fnom, totalharmonic distortion 2%, ambient temperature 20C and nominal auxiliary voltage VA,nomDeviationDeviation relative to the relevant nominal value underreference conditions

    Operating dataCurrents/measuring inputs: 1%Voltages/measuring input: 0.5%Currents/internally calculated: 2% Voltages/internally calculated: 2%Active and reactive power: 2%Load angle: 1Frequency: 10mHz

    Fault dataShort circuit current and voltage: 3%Short circuit impedance and fault location: 5%

    Internal clockWith free running internal clock: < 1 min./monthWith external synchronization

    via protocol, synch. interval 1 min: < 10msvia IRIG-B signal input: 1ms

    Resolution in fault data acquisitionTime resolution20 sampled values per period

    Phase currentsDynamic range: 100 Inom or 25 Inom (settable)Amplitude resolution

    at Inom = 1A: 6.1mA rms. or 1.5mA rms.at Inom = 5A: 30,5mA rms. or 7.6mA rms.

    Residual currentsDynamic range: 16 IE,nomAmplitude resolution

    at Inom = 1A: 0.89mA rms.at Inom = 5A: 4.9mA rms.

    VoltagesDynamic range: 150VAmplitude resolution: 9,2 mV rms

  • 15

    Address list

    Function parameters

    Global functionsPC link (PC):Command blocking: No/YesSig./meas.val.block.: No/Yes

    Communication link (COMM1):Command block. USER: No/YesSig./meas.block.USER: No/Yes

    Binary and analogue output (OUTP):Outp.rel.block USER: No/Yes

    Main function (MAIN):Device on-line: No (= off) /Yes (= on)Time switching: Standard time/Daylight saving timeTest mode USER: No/YesNominal frequ. fnom: 50Hz/60HzRotary field: Clockwise rotation/Anti-clockwise rot.Inom CT prim.: 1..10000AIN,nom CT prim.: 1....10000AVnom VT prim.: 0.1....1000.0kVVNG,nom V.T. prim.: 0.1....1000.0kVInom device: 1.0A/5.0AIN,nom device: 1.0A/5.0AVnom VT sec.: 50...130VVNG,nom VT sec.: 50...130VDynamic range I: Highest range/Sensitive rangeConn. meas. circ. IP: Standard/OppositeConn. meas. circ. IN: Standard/OppositeMeas. value rel. IP: 0.000...0.200 InomMeas. value rel. IN: 0.000...0.200 IEnomMeas. value rel. V: 0.000...0.200VnomMeas. val. rel. VNG: 0.000...0.200 Vne,nomSettl. t. IP,max,del: 0.1... 15.0...60.0 minFct.assign. block. 1: see selection tableFct.assign. block. 2: see selection tableTrip cmd.block. USER: No/YesFct.assig.trip cmd.1: see selection tableFct.assig.trip cmd.2: see selection tableMin.dur. trip cmd. 1: 0.10...10.00sMin.dur. trip cmd. 2: 0.10...10.00sClose cmd.pulse time: 0.10...10.00sRC inh.by CB cl.: No/YesFct. assign. fault: see selection table

    Parameter subset selection (PSS):Control via USER: No/YesParam.subs.sel. USER:

    Parameter subset 1Parameter subset 2Parameter subset 3Parameter subset 4

    Keep time: 0.000...65.000s /Blocked

    Selfmonitoring (SFMON):Fct. assign. warning: see selection table

    Fault recording (FT_RC):Fct. assig. trigger: see selection tablePre fault time: 1...50 periodsPost fault time: 1...50 periodsMax. recording time: 5...750 periods

    Main functionsMain function (MAIN):Neutral point treat.:

    Low imped. groundingIsol./res.w.start.PGIsol./res.w/o st. PGShort durat. ground.

    Phase priority 2pG: Phase-to-phase loopPhase-to-ground loopC before A acyclicA bef. B bef. C cyclA before C acyclicC bef. B bef. A cyclB before A acyclicA before B acyclicC before B acyclicB before C acyclic

    Transfer for 1p: Ground/P or G =f(Imed,Imax)Op. mode rush restr.:

    WithoutNot phase selectivePhase selective

    I> lift rush restr.: 5.0...20.0 Inom/BlockedRush I(2*fn)/I(fn): 10...35%/Blocked

    Distance protection (DIST):Enabled USER: No/YesCVT stabilization: No/Yes(P437 only): Zone extens. For 1pG: No/Yes

    Power swing blocking (PSB): (P435/P437 only)Enabled USER: No/YesThreshold value: 1...50%Operate delay: 0.06...1.00sRelease delay: 0.06...1.00s

    Measuring circuit monitoring (MCMON): Enabled USER: No/YesCurrent monitoring: No/YesIneg>: 0.10...1.00 ImaxOp. mode volt. mon.:

    VnegVneg with curr. enabVneg w.CB cont.enab.

    Operate delay: 0.00...10.00sFF, V enabled USER: No/YesVpos, FF: 0.01VnomVneg, FF: 0.01...0.50 InomOperate delay FF, V: 0.00...10.00s

    (P435/P437 only):FF,Vref enabled USER No/Yes Oper. delay FF, Vref: 0.00...10.00s

    Back-up overcurrent protection (BUOC): Enabled USER: No/YesOperating mode:

    Without ARCWith ARC, 3p HSRWith ARC, 1/3p HSR (P435/P437 only)

    Switch-on-to-fault protection (SOTF):Enabled USER: No/YesOperating mode:

    Trip with starting/Trip with overreachManual close timer: 0.00...10.00s

    Protective signaling (PSIG):Enabled USER: No/Yes

    Autoreclosing control (ARC):Enabled USER: No/Yes

    Automatic synchonism check (ASC):Enabled USER: No/Yes

    Ground fault (short circuit) protect. (GFSC): (P435/P437 only)Enabled USER: No/YesIN>: 0.002...0.500 InomVNG>: 0.015...0.500VnomAngle phiG: 0...90Start. oper. delay: 0.00...10.00sStart. releas. delay: 0.00...10.00st1 (forward): 0.00...60.00s/Blocked

    t2 (backward): 0.00...60.00s/Blockedt3 (non-directional): 0.00...60.00s/BlockedCriteria tS active:

    Blocked/forward/non-directionalOperating mode tS: VNG dependent/IN dependentIref,N: 0.01...0.80 Inom/BlockedCharacteristic N:

    Definite TimeIEC Standard InverseIEC Very InverseIEC Extr. InverseIEC Long Time Inv.IEEE Moderately Inv.IEEE Very InverseIEEE Extremely Inv.ANSI Normally Inv.ANSI Short Time Inv.ANSI Long Time Inv.RI Type InverseRXIDG Type Inverse

    Factor kt,N: 0.05...10.00

    Ground fault (short circuit) protectionsignaling (GSCSG): (P435/P437 only)Enabled USER: No/YesOperating mode:

    Signal comp. release/Signal comp. block.Channel mode:

    Independent channel/Common channelTrip mode:

    1/3p pole trip w.HSR3p pole trip w.HSR3p pole trip w/o.HSR

    Tripping time: 0.00...10.00s/BlockedRelease time send: 0.00...10.00stBlock: 0.00...10.00sBlock. sig. nondir.: No/YesEcho on receive: No/YesOperate delay echo: 0.00...10.00s/BlockedPulse duration echo: 0.00...10.00stBlock echo: 0.00...10.00sWeak infeed trip:

    No/With directional r./With VNG> releaseOp.delay weak infeed: 0.00...10.00s/BlockedFrequency monitoring: No/Yes

    Definite time overcurrent protection (DTOC): Enabled USER: No/Yes

    Inverse time overcurrent protection (IDMT):Enabled USER: No/Yes

    Thermal overload protection (THERM):Enabled USER: No/YesIref: 0.10...4.00 InomFactor kP: 1.05...1.50 Time const. 1 (>Ibl): 1...1000 minTime const. 2(

  • 16

    Ground fault direction determination usingsteady state values (GFDSS):(P433/P435 only)Enabled USER: No/YesOperating mode:

    Steady state power/Steady state currentOper. mode GF (pow.):

    cos phi circuit/sin phi circuitEvaluation VNG: Calculated/MeasuredMeasuring direction: Standard/OppositeVNG>: 0.02...1.00Vnom(/3)tVNG>: 0.02...10.00sf/fnom (pow.meas.): 1/5f/fnom (curr.meas.): 1/5IN,act>/IN,reac> LS: 0.003...1.000 IN,nomSector angle LS: 80...89Operate delay LS: 0.00...100.00s/BlockedRelease delay LS: 0.00...10.00sIN,act>/IN,reac> BS: 0.003...1.000 IN,nomSector angle BS: 80...89Operate delay BS: 0.00...100.00s/BlockedRelease delay BS: 0.00...10.00sIN>: 0.003...1.000 IN,nomOperate delay IN: 0.00...100.00s/BlockedRelease delay IN: 0.00...10.00s

    Ground fault tripping (GFTRP): (P433/P435 only)Enabled USER: No/Yes

    Ground fault protection signaling (GFSIG): (P433/P435 only)Enabled USER: No/YesOperate delay: 0.00...10.00sSend reset time: 0.00...10.00sdc loop op. mode:

    Transm.relay break c/Transm.relay make co

    Transient ground fault directiondetermination (TGFD):(P433/P435 only)Enabled USER: No/YesEvaluation VNG: Sum (VA-B-C-G) /MeasuredMeasurem. direction: Standard/OppositeVNG>: 0.15...0.50Vnom(/3)Operate delay: 0.05...1.60sIN,p>: 0.10...0.50 InomBuffer time: 0...1200s/Blocked

    Limit value monitoring (LIMIT):Enabled USER: No/YesI>:/I>>:/I:/tI:/U:/tU:/U:/tU: 0.010...1.000 Unom/BlockedtU>: /tU>>: 1...1000s/Blocked

    with I = ldcIin:I>:/I>>:/I:/tI:/T:/tT (Ibl) high r. PSx: 0.10...1.00 InomI> (Ibl) sens. r.PSx: 0.05...1.00 InomOperat. mode V< PSx:

    W/o V< startingWith V< start. PGWith V< start.PG,PP

    V< PSx: 0.10...0.90Vnom(/3)Operat. mode Z< PSx:

    W/o Z< startingWith Z< starting P-GWith Z< start.PG,PP

    Xfw PSx:/Rfw,PG PSx:/Rfw,PP PSx:/Zfw,PG PSx:/Zfw,PP PSx:

    0.1...300.0 at Inom = 1.0A0.02...60.00 at Inom = 5.0A

    Zbw/Zfw PSx: 0.10...4.00 Z evaluation PSx:

    ZPG=VPG/(IP + kG*IN) /ZPG=VPG/2*IPIN> high range PSx: 0.10...2.00 InomIN> sens. range PSx: 0.05...2.00 InomtIN> PSx: 0.000...0.500sVNG> PSx: 0.02...1.00VnomVNG>> PSx: 0.20...1.00VnomtVNG>> PSx: 0.000...60.000sCharacteristic PSx: Circle/Polygonvalid for y = 1 to 6:

    Xy (polygon) PSx: Ry,PG (polygon) PSx: Ry,PP (polygon) PSx:

    0.10...200.00 at Inom = 1.0A0.02...40.00 at Inom = 5.0A

    y (polygon) PSx: 40...90y (polygon) PSx: 20...20Zy (circle) PSx:

    0.05...200.00 at Inom = 1.0A0.01...40.00 at Inom = 5.0A

    y (circle) PSx: 10...90Arc comp. circle PSx: No/Yesvalid for y = 1 to 7:

    Direction Ny PSx: Forward /Backward/Non-directional

    Oper.val.Vmemory PSx: 0.01...1.00Vnomvalid for y = 1 to 8:

    ty PSx: 0.00...10.00s/Blockedkze,PG HSR PSx: 1.00... 450.00 kze,PP HSR PSx: 1.00...450.00 kze,PG TDR PSx: 1.00...450.00 kze,PP TDR PSx: 1.00...450.00 t1,ze PSx: 0.00...10.00s/BlockedAbs. value kG PSx: 0.00...8.00 Angle kG PSx: 180...180

    (P435/P437 only): Op. mode zone 4 PSx: Normal1p:Z1/t1(3p)3p:Z1/t4Section cable - lineSection line - cableComp.bundle cond.eff1p:Z1/t1, 3p:Z1/t4

    (P435/P437 only):Trip zone 1 PG PSx: 1 pole/3 pole Trip zone 1 PP PSx:

    1 pole leading phase1 pole trailing phase3 pole

    (P437 only):Meas. start. 1pG PSx: PG loops/noneMeas. start. 2pG PSx: PG loops/PP loopMeas. start. 3pG PSx: PG loops/PP loops

    Backup overcurrent protection (BUOC): I> PSx: 0.50...8.00 InomtI> PSx: 0.00...10.00s/BlockedIN> PSx: 0.10...2.00 InomtIN> PSx: 0.00...10.00s/Blocked

    Protective signaling (PSIG):Enable PSx: No/YesOperating mode PSx:

    WithoutDir.trans.trip.underPUTTZone extensionRelease schemeBlocking schemeDC loop operat. modeReverse interlockingDirection comparison

    Tripping time PSx: 0.00...10.00s/BlockedRelease t. send PSx: 0.00...10.00sDC loop op. mode PSx:

    Transm.relay break c/Transm.relay make coEcho on receive PSx:

    WithoutOn receiveOn receive & V RRC PSx: 0.40...0.90Vnom(/3)Reclaim time PSx: 1.00...600.00sBlock. time int. PSx: 1...600sBlock. time ext. PSx: 0...600sZone ext.dur. RC PSx:

    Without/Following HSR/AlwaysParallel trip PSx:

    Without functionParall. bloc.w/o initParall. bloc.w. init

    (P435/P437 only):Operative time 2 PSx: 0.00...10.00sHSR oper. mode PSx:

    1 pole / 1/3 pole / 3 poleTrip time HSR PSx: 0.00...10.00s/BlockedDead time 1p PSx: 0.10...600.00sDead time max PSx: 0.10...600.00s

    (P437 only):Operating mode 2 PSx:

    Trip dependent/Start dependentTDiscrim PSx: 0.10...600.00s

    Automatic synchonism check (ASC):(P435/P437 only):Enable PSx: No/YesActive for HSR PSx: No/YesActive for TDR PSx: No/YesActive for RRC PSx: No/YesClos.rej.w.block PSx: No/YesOperative time PSx: 0.00...60.00sOperating mode PSx:

    Voltage checked

  • 17

    Sync. checkedVolt./sync. checked

    Op.mode volt.chk.PSx: Vref but not VV but not VrefNot V and not VrefNot V or not VrefVref & Z1 but not V

    V> volt.check PSx: 0.10...0.80Vnom(/3)V< volt. check PSx: 0.10Vnom(/3)tmin volt. check PSx: 0.00...10.00sMeasurement loop PSx:

    Loop A-G/B-G/C-G/A-B/B-C/C-AV> sync. check PSx: 0.40...1.20Vnom(/3)Delta Vmax PSx: 0.02...0.40VnomDelta fmax PSx: 0.01...1.00HzDelta phi max PSx: 5...100Phi offset PSx: 180...180tmin sync. check PSx: 0.00...10.00s

    Ground fault (short circuit) protect. (GFSC): (P435/P437 only)Enable PSx: No/Yes

    Ground fault (short circuit) protectionsignaling (GSCSG): (P435/P437 only)Enable PSx: No/Yes

    Definite time overcurrent protection (DTOC):Enable PSx: No/Yesvalid for y = > to >>>>:

    I y PSx: 0.10...20.00 InomtI y PSx: 0.00...30.00s/BlockedIneg y PSx: 0.10...20.00 InomtIneg y: 0.00...30.00s/BlockedIN y: 0.10...20.00 InomtIN y: 0.00...30.00s/Blocked

    Inverse time overcurrent protection (IDMT):Enable PSx: No/Yesvalid for y = P or neg or N:

    Iref,y PSx: 0.01...4.00 Inom/BlockedCharacteristic y PSx:

    Definite TimeIEC Standard InverseIEC Very InverseIEC Extr. InverseIEC Long Time Inv.IEEE Moderately Inv.IEEE Very InverseIEEE Extremely Inv.ANSI Normally Inv.ANSI Short Time Inv.ANSI Long Time Inv.RI-Type InverseRXIDG-Type Inverse

    Factor kt,y PSx: 0.05...10.00 Reset y PSx:

    Without delay/Delayed as per char.Direction y PSx:

    Forward directionalBackward directionalNon-directional

    Direct. meas. y PSx: Neq.sequ. Vneg, Ineg/Distance Zone4

    Op. w/o volt. PSx: Non-directional/Blocked

    Over/undervoltage protection (V):Enable PSx: No/YesOperating mode PSx: Delta/StarEvaluation VNG PSx: Calculated/MeasuredV> PSx: 0.20...1.50Vnom(/3)/BlockedV>> PSx: 0.20...1.50Vnom(/3)/BlockedtV> PSx: 0.00...100.00s/BlockedtV> 3 pole PSx: 0.00...100.00s/BlockedtV>> PSx: 0.00...100.00s/BlockedV< PSx: 0.20...1.50Vnom(/3)/BlockedV> PSx: 0.20...1.50Vnom/3/BlockedtVpos> PSx: 0.00...100.00s/BlockedtVpos>> PSx: 0.00...100.00s/Blocked

    Vpos< PSx: 0.20...1.50Vnom/3/BlockedVpos> PSx: 0.20...1.50Vnom/3/BlockedtVneg> PSx: 0.00...100.00s/BlockedtVneg>> PSx: 0.00...100.00s/BlockedVNG> PSx: 0.02...1.00Vnom(/3)/BlockedVNG>> PSx: 0.02...1.00Vnom(/3)/BlockedtVNG> PSx: 0.00...100.00s/BlockedtVNG>> PSx: 0.00...100.00s/BlockedtTransient PSx: 0.00...100.00s/BlockedHyst. V meas. PSx: 1...10%Hyst. V deduc. PSx: 1...10%

    Over/underfrequency protection (f):Enable PSx: No/Yesvalid for y = 1 ... 4

    Oper. mode fy PSx:f f with df/dtf w. Delta f/Delta t

    fy PSx: 40.00...70.00Hz/Blockedtfy PSx: 0.00...10.00s/Blockeddfy/dt PSx: 0.1...10.0Hz/s/BlockedDelta fy PSx: 0.01...5.00Hz/BlockedDelta ty PSx: 0.04...3.00s

    Directional power protection (P):(P433/P435 only)Enabled PSx: No/Yesvalid for y = > or >> or

  • 18

    Dimensions

    7>3?:J

    733?:J

    74>?:J

    97;?>

    9>9?8

    98=?9

    9:3?7

    97;?>9:;?8

    993?5

    733?:

    :?=747?;

    7:5

    784

    7::?>9=;

    Figure 6: Dimensional drawings for case 40TE

    Surface mounted case 40TE

    Flush mounted case 40TE with panel cutout

  • 19

    :?=

    >7=?=

    7:5

    784

    9:3?7

    7>3?:J

    733?:J

    74>?:J

    >;>?4

    >8>

    >47?8

    9:5?=

    94>?5

    9:?5

    :?=

    9:;?8

    993?5

    733?:

    >;>?4

    Figure 7: Dimensional drawings for case 84TE

    Surface mounted case 84TE

    Flush mounted case 84TE with panel cutout

  • 20

    Location and connections

    =7

    =7

    =9

    =9

    =;

    =;

    =>

    =>

    =:

    =:

    =8

    =8

    =3

    =3

    =4

    =4

    =5

    =5

    7=

    7=

    7 K

    > K>):#

    77

    77

    79

    79

    7;

    7;

    7>

    7>

    7:

    7:

    78

    78

    !

    4

    73

    73

    74

    74

    !

    8

    75

    75

    9=

    9=

    "

    4

    97

    97

    # !

    4

    !

    4

    !

    4

    =7

    =7

    =9

    =9

    =;

    =;

    =>

    =>

    =:

    =:

    =8

    =8

    =3

    =3

    =4

    =4

    =5

    =5

    7=

    7=

    !

    4

    > K>):#

    77

    77

    79

    79

    #

    7;

    7;

    7>

    7>

    7:

    7:

    78

    78

    !

    4

    73

    73

    74

    74

    !

    8

    75

    75

    9=

    9=

    "

    4

    97

    97

    $ !

    4

    !

    4

    =7

    =7

    =9

    =9

    =;

    =;

    =>

    =>

    =:

    =:

    =8

    =8

    =3

    =3

    =4

    =4

    =5

    =5

    7=

    7=

    $

    =7

    =7

    =9

    =9

    =;

    =;

    =>

    =>

    =:

    =:

    =8

    =8

    =3

    =3

    =4

    =4

    =5

    =5

    7=

    7=

    >K>#

    77

    77

    79

    79

    7;

    7;

    7>

    7>

    7:

    7:

    78

    78

    !

    4

    73

    73

    74

    74

    !

    8

    75

    75

    9=

    9=

    "

    4

    97

    97

    #>

    !84

    $

    =7

    =7

    =9

    =9

    =;

    =;

    =>

    =>

    =:

    =:

    =8

    =8

    =3

    =3

    =4

    =4

    =5

    =5

    7=

    7=

    "

    4

    !

    8

    !

    4

    $ !

    4

    #

    =7

    =7

    =9

    =9

    =;

    =;

    =>

    =>

    =:

    =:

    =8

    =8

    =3

    =3

    =4

    =4

    =5

    =5

    7=

    7=

    !

    4 > K

    77

    77

    79

    79

    #

    7;

    7;

    7>

    7>

    7:

    7:

    78

    78

    !

    4

    73

    73

    74

    74

    !

    8

    75

    75

    9=

    9=

    "

    4

    97

    97

    !

    4

    !

    4

    >):#7K

    %&'

    =7

    =7

    =9

    =9

    =;

    =;

    =>

    =>

    =:

    =:

    =8

    =8

    =3

    =3

    =4

    =4

    =5

    =5

    7=

    7=

    > K>):#

    77

    77

    79

    79

    7;

    7;

    7>

    7>

    7:

    7:

    78

    78

    !

    4

    73

    73

    74

    74

    !

    8

    75

    75

    9=

    9=

    "

    4

    97

    97

    # !

    4

    !

    4

    !

    4

    $

    (&'

    > K>#

    > K>):#

    8 > >>88

    "

    4

    !

    8

    !

    4

    !

    4

    #>>88

    >8888>8 >888>

    8> 8 8 8 > 8> 8 8 8 >

    (&'

    %&' (&'

    %&' (&'

    Figure 8: Location diagrams

  • 21

    .

    #'"#/

    $

    00

    1+

    2#/#134

    2#/

    556

    .

    (!78

    !

    9

    (7*8

    556

    .

    (!78

    !

    9

    (7*8

    556

    556

    :

    ;,$,#

    !

    9

    !

    !

    9

    :

    .

    ))34?34

    !

    "

    #$%

    @=*'$,#

    &

    A

    ;

    )

    B

    !

    9

    :

    .

    B

    B!

    !

    9

    :

    .

    C

    ))34?34

    !

    "

    #$%

    @5:834

    79;>:8

    12

    @=>9

    @=>7

    7

    9

    "7

    "9

    7

    9!7

    !9

    )

    ( ((

    &

    79;>:834

    @=;97

    7"

    7

    7!

    9! 79

    @=:9

    12

    #

    L

    !

    !12

    -127#

    9#

    79;>:834

    @=;7

    Figure 10: Connection example P433 (application in MV system with isolated/compensated neutral)

    Figure 11: Connection example P437 (application in HV system with double circuit line)

    Note: When using P1 - P2 and S1 - S2 identifications for the terminal polarity of CTs, the dot shown identifies the P1 and S1terminals

  • 23

    Ordering information

    "$*

    & &>;;% 5 = >

    ">=-6 ; %>=7

    "4>-6 4 %>=9

    ">+

    4+

    & &>;:% 5 =

    ">=-6 ; %>=7

    "4>-6 3 %>=9

    "4>-6 4 %>=;

    ">+

    4+

    & &>;3% 5 =

    "4>-6 3 %>=7

    "4>-6 4 %>=9

    ">+

    4+

    6/.D+ ;

    .6/.D+ >

    %

    > >

    : :

    L. =

    L.7+18+

    )4+2 7

    L.9+179+

    )78+2 9

    L.;+174+

    )9>+2 M&>;:)&>;3)4>-+N ;

    L.>+19>+

    );9+2 M&>;:)&>;3)4>-+N >

    &/+

    6B9> ;

    6B>49:=)7==9;= >

    6B9>+18+2 4

    6B>49:=)7==9;=+18+2 5

    L. =

    L. M&>;;)&>;:+N 7

    L. 9

    L. M&>;;)&>;:+N ;

    L. %>:7 5 7

    -8=43=%:%7=;

    L. %>:8 5

    +%"$+. = =

    /./ 9

    -8=43=%:%7=7)%7=;6 "#6!&;?=

    %"$+.

    /6>4:6 7

    6 9

    6 >

    0

    -.12 1/.D??2

    1-.2 %4=7

    .1-.2 %4=9

    .1-.2 %4=;

  • TRANSMISSION & DISTRIBUTION Protection & Control, 60 Route de Sartrouville, BP58, 78230 Le Pecq Cedex, FranceTel: +33 (0) 134 80 79 00 Fax: +33 (0) 134 80 79 13 Email: [email protected] Internet: www.tde.alstom.com

    2001 ALSTOM. ALSTOM, the ALSTOM logo and any alternative version thereof are trademarks and service marks of ALSTOM.MiCOM is a registered trademark of ALSTOM. Other names mentioned, registered or not, are the property of their respective companies.

    Our policy is one of continuous development. Accordingly the design of our products may change at any time. Whilst every effort is made to produce up to date literature, this brochure shouldonly be regarded as a guide and is intended for information purposes only. Its contents do not constitute an offer for sale or advice on the application of any product referred to in it.

    We cannot be held responsible for any reliance on any decisions taken on its contents without specific advice. P43

    */EN

    BR/

    Ab

    El

    ectro

    nic

    file

    upda

    ted

    only

    (col

    ours

    cha

    nged

    )