28
HEAT PUMP OUTDOOR UNITS 13HPX MERIT ® Series R-410A Bulletin No. 210460 December 2009 Supersedes November 2009 ENGINEERING DATA SEER up to 14.5 1.5 to 5 Tons Cooling Capacity - 18,000 to 59,000 Btuh Heating Capacity - 16,800 to 57,000 Btuh MODEL NUMBER IDENTIFICATION 13 HP x - 024 - 230 - 2 Nominal SEER Unit Type HP = Heat Pump Outdoor Unit Refrigerant X = R-410A Nominal Cooling Capacity 018 = 1.5 tons 024 = 2 tons 030 = 2.5 tons 036 = 3 tons 042 = 3.5 tons 048 = 4 tons 060 = 5 tons Minor Revision Number Voltage 230 = 208/230V-1phase-60hz

MERIT Series R-410A - LennoxPROs.com · MERIT® Series R-410A Bulletin No. 210460 December 2009 Supersedes November 2009 ENGINEERING DATA SEER up to 14.5 1.5 to 5 Tons Cooling Capacity

  • Upload
    others

  • View
    0

  • Download
    0

Embed Size (px)

Citation preview

Page 1: MERIT Series R-410A - LennoxPROs.com · MERIT® Series R-410A Bulletin No. 210460 December 2009 Supersedes November 2009 ENGINEERING DATA SEER up to 14.5 1.5 to 5 Tons Cooling Capacity

H E A T P U M P O U T D O O R U N I T S

13HPXMERIT® Series

R-410A Bulletin No. 210460

December 2009Supersedes November 2009

E N G I N E E R I N G D ATA

SEER up to 14.51.5 to 5 Tons

Cooling Capacity - 18,000 to 59,000 BtuhHeating Capacity - 16,800 to 57,000 Btuh

MODEL NUMBER IDENTIFICATION

13 HP x - 024 - 230 - 2

Nominal SEER

Unit TypeHP = Heat Pump Outdoor Unit

RefrigerantX = R-410A

Nominal Cooling Capacity018 = 1.5 tons024 = 2 tons030 = 2.5 tons036 = 3 tons042 = 3.5 tons048 = 4 tons060 = 5 tons

Minor Revision Number

Voltage230 = 208/230V-1phase-60hz

Page 2: MERIT Series R-410A - LennoxPROs.com · MERIT® Series R-410A Bulletin No. 210460 December 2009 Supersedes November 2009 ENGINEERING DATA SEER up to 14.5 1.5 to 5 Tons Cooling Capacity

13HPX - 1.5 to 5 Ton Heat Pump / Page 2

FEATURES

EQUIPMENT Warranty

Compressor - limited warranty for five years in residential installations and five years in non-residential installations.All other covered components - five years in residential installations and one year in non-residential installations.Refer to Lennox Equipment Limited Warranty certificate included with unit for specific details.APPLICATIONS

SEER up to 14.5.HSPF (Region IV) up to 8.70.1.5 through 5 tons.Single phase power supply.Sound levels as low as 76 dBVertical air discharge allows concealment behind shrubs at grade level or out of sight on a roof.Designed for applications with remotely located indoor air handler units or gas furnaces with indoor add-on coils. When heat pumps are used with gas furnaces, a dual-fuel control (i.e. FM21) or a control system with dual-fuel capabilities (i.e. Harmony III™, LZP-2 or LZP-4) must be used (ordered extra).See Indoor Coils and Air Handlers sections for indoor unit data.Units shipped completely factory assembled, piped and wired. Each unit is test operated at the factory insuring proper operation.Installer must set outdoor unit, connect refrigerant lines and make electrical connections to complete job.For expanded ratings, see www.lennoxdavenet.com.

APPROVALS

Certified in Accordance with the USE certification program, which is based on AHRI Standard 210/240-2008.Sound rated in Lennox reverberant sound test room in Accordance with test conditions included in AHRI Standard 270-2008.Tested in the Lennox Research Laboratory environmental test room.Rated According to U.S. Department of Energy (DOE) test procedures.Units and components within bonded for grounding to meet safety standards for servicing required by UL, NEC and CEC.Units are UL listed and CSA certified.ISO 9001 Registered Manufacturing Quality System.

REFRIGERATION SYSTEM

R-410A RefrigerantNon-chlorine, ozone friendly, R-410A.Unit is factory pre-charged with refrigerant. See Specification table. Total system refrigerant charge is dependant on outdoor unit size, indoor unit size and refrigerant line length. Refer to Installation Instructions for “Indoor Unit Match-Up and Sub-Cooling Charge Levels” to determine correct amount of charge required.

B

C

D

E F

G

H

I

Contents

AHRI System Matches..................................................9Dimensions ...................................................................7Electrical Data...............................................................6Features........................................................................2Field Wiring ...................................................................8Installation Clearances .................................................8Model Number Identification .........................................1Optional Accessories - Must Be Ordered Extra ............6Sound Data ..................................................................8Specifications ...............................................................6

Page 3: MERIT Series R-410A - LennoxPROs.com · MERIT® Series R-410A Bulletin No. 210460 December 2009 Supersedes November 2009 ENGINEERING DATA SEER up to 14.5 1.5 to 5 Tons Cooling Capacity

13HPX - 1.5 to 5 Ton Heat Pump / Page 3

FEATURES

REFRIGERATION SYSTEM (C0NTINUED)

Outdoor Coil FanDirect drive fan moves large air volumes uniformly through entire condenser coil for high refrigerant cooling and heating capacity.Vertical air discharge minimizes operating sounds and eliminates damage to lawn and shrubs.Fan motor has sleeve bearings and is inherently protected.Motor totally enclosed for maximum protection from weather, dust and corrosion.Rain shield on motor provides additional protection from moisture.Louvered steel top fan guard furnished as standard.Fan service access accomplished by removal of top panel.Copper Tube/Enhanced Fin CoilLennox designed and fabricated coil.Ripple-edged aluminum fins.Copper tube construction.Lanced fins provide maximum exposure of fin surface to air stream resulting in excellent heat transfer.Fin collars grip tubing for maximum contact area.Flared shoulder tubing connections/silver soldering construction.Coil is factory tested under high pressure to ensure leakproof construction.Entire coil is accessible for cleaning.PVC coated steel wire coil guard furnished.Expansion Valve - Outdoor UnitDesigned and sized specifically for use in heat pump system.Sensing bulb is located on the suction line between the reversing valve and the compressor to sense evaporator suction temperature in any cycle.Factory installed and piped.High Pressure SwitchProtects the system from high pressure conditions that can be a result of fan failure or a blocked/dirty coil.Automatic reset.Loss of Charge SwitchHelps protect the compressor from damage due low refrigerant charge conditions.SPST, normally-closed switch, automatic reset switch mounted on suction line.High Capacity Liquid Line DrierFactory installed in the liquid line, the drier traps moisture or dirt that could contaminate the refrigerant system.100% molecular-sieve, bead type bi-flow drier.

B

C

D

E

Reversing Valve4-way interchange reversing valve effects a rapid change in direction of refrigerant flow resulting in quick changeover from cooling to heating and vice versa.Valve operates on pressure differential between outdoor unit and indoor unit of the system. Factory installed.

OPTIONS

Check/Expansion Valve KitsMust be ordered extra and field installed on certain indoor units. See Check/Expansion Valve Kit Usage Table.Chatleff-style fittings.Refrigerant Line KitsRefrigerant lines (suction & liquid) are shipped refrigeration clean. Lines are cleaned, dried, pressurized and sealed at factory.Suction line fully insulated.Lines are stubbed at both ends.Not available for -060 models. Must be field fabricated.

F

Page 4: MERIT Series R-410A - LennoxPROs.com · MERIT® Series R-410A Bulletin No. 210460 December 2009 Supersedes November 2009 ENGINEERING DATA SEER up to 14.5 1.5 to 5 Tons Cooling Capacity

13HPX - 1.5 to 5 Ton Heat Pump / Page 4

COMPRESSOR

Scroll CompressorCompressor features high efficiency with uniform suction flow, constant discharge flow and high volumetric efficiency and quiet operation.Compressor consists of two involute spiral scrolls matched together to generate a series of crescent shaped gas pockets between them.During compression, one scroll remains stationary while the other scroll orbits around it.Gas is drawn into the outer pocket, the pocket is sealed as the scroll rotates.As the spiral movement continues, gas pockets are pushed to the center of the scrolls. Volume between the pockets is simultaneously reduced.When pocket reaches the center, gas is now at high pressure and is forced out of a port located in the center of the fixed scrolls.During compression, several pockets are compressed simultaneously resulting in a smooth continuous compression cycle.Continuous flank contact, maintained by centrifugal force, minimizes gas leakage and maximizes efficiency.Scroll compressor is tolerant to the effects of slugging and contaminants. If this occurs, scrolls separate, allowing liquid or contaminants to be worked toward the center and discharged.Low gas pulses during compression reduces operational sound levels.Compressor motor is internally protected from excessive current and temperature.Muffler in discharge line reduces operating sound levels.Compressor is installed in the unit on resilient rubber mounts for vibration free operation.Compressor Crankcase Heater (Factory installed on -036-042-048-060 models)Protects against refrigerant migration that can occur during low ambient operation.

OPTIONS

Compressor Crankcase Heater (Optional for -018 -024-030 models)Protects against refrigerant migration that can occur during low ambient operation.Compressor Sound CoverA reinforced vinyl compressor cover containing a 1-1/2 inch thick batt of fiberglass insulation.All open edges are sealed with a one-inch wide hook and loop fastening tape.

G

CABINET

Heavy gauge steel cabinet with five station metal wash process.Powder paint finish provides superior rust and corrosion protection.Painted base section.Control box is conveniently located with all controls factory wired.Corner patch plate allows access to compressor components.Drainage holes are provided in base section for moisture removal.Refrigerant Line Connections, Electrical Inlets, Service ValvesSweat connection vapor and liquid lines are located on corner of unit cabinet.Fully serviceable brass service valves prevent corrosion and provide access to refrigerant system. Vapor valve can be fully shut off, while liquid valve may be front seated to manage refrigerant charge while servicing system.Refrigerant line connections and field wiring inlets are located in one central area of cabinet for easy access. See dimension drawing.

OPTIONS

Hail GuardsConstructed of louvered, heavy-gauge steel painted to match cabinet.Surrounds unit on all four sides to prevent damage to the coil.Mounting BaseProvides permanent foundation for outdoor units.High density polyethylene structural material is lightweight, sturdy, sound absorbing and will withstand the rigors of the sun, heat, cold, moisture, oil and refrigerant. Will not mildew or rot.Can be shipped singly or in packages of 6 to a carton.Unit Stand-Off KitBlack high density polyethylene feet are available to raise unit off of mounting surface away from damaging moisture.Four feet are furnished per order number.

H

FEATURES

Page 5: MERIT Series R-410A - LennoxPROs.com · MERIT® Series R-410A Bulletin No. 210460 December 2009 Supersedes November 2009 ENGINEERING DATA SEER up to 14.5 1.5 to 5 Tons Cooling Capacity

13HPX - 1.5 to 5 Ton Heat Pump / Page 5

CONTROLS

Defrost ControlSolid-state time/temperature defrost control is furnished as standard equipment.Control initiates a defrost cycle every 30, 60 or 90 minutes of compressor “on” time at outdoor coil temperatures below 42°F (factory setting 90 minutes).Anti-short cycle, timed-off control incorporated into the board.High and low pressure switch monitoring with five-trip lockout.Diagnostic LED’s furnished as an aid in troubleshooting.Conveniently located in control box.

OPTIONS

Compressor Hard Start KitSingle-phase units are equipped with a PSC compressor motor. This type of motor normally doesn’t need a potential relay and start capacitor.In conditions such as low voltage, this kit may be required to increase the compressor starting torque.Compressor Low Ambient Cut-OffNon-adjustable switch (low ambient cut-out) prevents compressor operation when outdoor temperature is below 35°F.FreezestatInstalls on or near the vapor line of the indoor coil or on the suction line.Senses suction line temperature and cycles the compressor off when suction line temperature falls below it’s setpoint.Opens at 29°F and closes at 58°F.Indoor Blower Off Delay RelayDelays the indoor blower-off time during the cooling cycle.See AHRI System Matches for usage.Low Ambient KitHeat pump in the cooling mode will operate satisfactorily down to 45°F outdoor air temperature without any additional controls.Low Ambient Control Kit can be field installed, allowing unit operation down to 30°F.Crankcase heater and freezestat should be installed on compressors equipped with a low ambient kit.A Compressor Low Ambient Cut-Off should be added to terminate compressor operation below recommended operation conditions.Low Pressure Switch Bypass ThermostatFor use in applications where the heat pump is operated in outdoor ambient temperatures below 15°F.Prevents nuisance trips from the low pressure switch.Wired in parallel with the low pressure switch.

I

Mild Weather KitHeat pump units operate satisfactorily in the heating mode at outdoor air temperatures up to 75°F.Mild Weather Kit can be field installed, allowing heating operation above 75°F.Monitor Kit - Service LightContains ambient compensating thermistor and service light thermostat.For use with thermostats requiring input for indicator lights.Outdoor Thermostat KitAn outdoor thermostat can be used to lock out some of the electric heating elements on indoor units where two stage control is applicable.Outdoor thermostat maintains the heating load on the low power input as long as possible before allowing the full power load to come on the line.Thermostat kit and mounting box must be ordered extra.ThermostatThermostat not furnished with unit. See Thermostat bulletins in Controls Section and Lennox Price Book.

FEATURES

Page 6: MERIT Series R-410A - LennoxPROs.com · MERIT® Series R-410A Bulletin No. 210460 December 2009 Supersedes November 2009 ENGINEERING DATA SEER up to 14.5 1.5 to 5 Tons Cooling Capacity

13HPX - 1.5 to 5 Ton Heat Pump / Page 6

SPECIFICATIONS General Data

Model No. 13HPX-018 13HPX-024 13HPX-030 13HPX-036 13HPX-042 13HPX-048 13HPX-060Nominal Tonnage 1.5 2 2.5 3 3.5 4 5

Connections (sweat)

Liquid line o.d. - in. 3/8 3/8 3/8 3/8 3/8 3/8 3/8Vapor line o.d. - in. 3/4 3/4 3/4 7/8 7/8 7/8 1-1/8

1 Refrigerant (R-410A) furnished 7 lbs. 1 oz. 6 lbs. 8 oz. 7 lbs.11 oz. 6 lbs. 5 oz. 9 lbs. 8 oz. 11 lbs.11 oz. 13 lbs. 12 oz.Outdoor Coil

Net face area sq. ft.

Outer coil 15.21 15.21 13.30 15.21 18.66 21.11 24.50Inner coil - - - - - - 12.60 14.50 17.95 20.31 23.56

Tube diameter - in. 5/16 5/16 5/16 5/16 5/16 5/16 5/16Number of rows 1 1 2 2 2 2 2

Fins per inch 22 22 22 22 22 22 22Outdoor Fan

Diameter - in. 18 18 18 18 22 22 22Number of blades 3 3 4 4 4 4 4

Motor hp 1/5 1/5 1/5 1/5 1/3 1/3 1/4Cfm 2400 2400 2440 2450 3890 3890 3830

Rpm 1130 1130 1095 1100 1080 1085 825Watts 166 166 194 190 400 375 330

Shipping Data - lbs. 1 package 140 150 170 180 220 250 255ELECTRICAL DATA

Line voltage data - 60 hz - 1ph 208/230V 208/230V 208/230V 208/230V 208/230V 208/230V 208/230V2 Maximum overcurrent protection (amps) 20 30 30 35 40 50 60

3 Minimum circuit ampacity 12.4 18 18.7 22 25.3 29 34.6Compressor Rated load amps 9.0 13.5 14.1 16.7 18.8 21.8 26.3

Locked rotor amps 39 53 59 70 90 100 120Power factor 0.96 0.97 0.98 0.98 0.94 0.95 0.98

Outdoor Fan Motor

Full load amps 1.1 1.1 1.1 1.1 1.7 1.7 1.7Locked rotor amps 1.9 1.9 1.9 1.9 4.1 4.1 3.1

OPTIONAL ACCESSORIES - MUST BE ORDERED EXTRACompressor Crankcase Heater 93M04 • • • Factory Factory Factory FactoryCompressor Hard Start Kit 10J42 • • • •

88M91 • • •Compressor Low Ambient Cut-Off 45F08 • • • • • • •Compressor Sound Cover 69J03 • • • • • • •Freezestat 3/8 in. tubing 93G35 • • • • • • •

5/8 in. tubing 50A93 • • • • • • •Hail Guards 92M89 •

92M88 • • •12W21 •92M90 •92M94 •

Indoor Blower Off Delay Relay 58M81 • • • • • • •4 Low Ambient Kit 54M89 • • • • • • •Low Pressure Switch Bypass Thermostat

13W07 • • • • • • •

Mild Weather Kit 33M07 • • • • • • •Monitor Kit - Service Light 76F53 • • • • • • •Mounting Base 69J06 • • • •

69J07 • • • • • • •Outdoor Thermostat Kit

Thermostat 56A87 • • • • • • •Mounting Box 31461 • • • • • • •

Refrigerant Line Sets

L15-41-20, L15-41-30, L15-41-40, L15-41-50

• • •

L15-65-30, L15-65-40, L15-65-50

• • •

Field Fabricate •Unit Stand-Off Kit 94J45 • • • • • • •

NOTE - Extremes of operating range are plus 10% and minus 5% of line voltage. 1 Refrigerant charge sufficient for 15 ft. length of refrigerant lines.2 HACR type circuit breaker or fuse.3 Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements.4 Crankcase Heater and Freezestat are recommended with Low Ambient Kit.

Page 7: MERIT Series R-410A - LennoxPROs.com · MERIT® Series R-410A Bulletin No. 210460 December 2009 Supersedes November 2009 ENGINEERING DATA SEER up to 14.5 1.5 to 5 Tons Cooling Capacity

13HPX - 1.5 to 5 Ton Heat Pump / Page 7

SIDE VIEW

SUCTION &LIQUID LINE

CONNECTIONS

INLET

AIR

INLET

AIR

DISCHARGE AIR

SIDE VIEW

TOP VIEW

CONDENSERCOIL FAN

COMPRESSOR

INLET AIR

INLET AIR

VAPOR LINECONNECTION

2-3/4 (70)

A

ELECTRICALINLETS

LIQUID LINECONNECTION 4-3/8

(111)6-3/8(162)

6-3/8(162)

TOP VIEW BASE SECTION

4-3/8(111)

4-3/8(111)

4-3/8(111)

4-3/8(111)

4-3/8(111)

COMPRESSOR

COIL DRAIN OUTLETS(Around perimeter of base)

OPTIONAL UNITSTAND-OFF KIT (4)

(Field Installed)

A

OPTIONAL UNITSTAND-OFF KIT (4)

(Field Installed)

2 (51)

3/4 (19)

C B

Model No.A B C

inches mm inches mm inches mm13HPX-01813HPX-02413HPX-036

24-1/4 616 33-1/4 845 32-1/2 826

13HPX-030 24-1/4 616 29-1/4 743 28-1/2 72413HPX-042 28-1/4 718 33-1/4 845 32-1/2 82613HPX-048 28-1/4 718 37 940 36-1/4 92113HPX-060 28-1/4 718 43-1/4 1099 42-1/2 1080

DIMENSIONS - INches (MM)

Page 8: MERIT Series R-410A - LennoxPROs.com · MERIT® Series R-410A Bulletin No. 210460 December 2009 Supersedes November 2009 ENGINEERING DATA SEER up to 14.5 1.5 to 5 Tons Cooling Capacity

13HPX - 1.5 to 5 Ton Heat Pump / Page 8

DISCONNECTSWITCH

(By Others)

OPTIONALOUTDOOR

THERMOSTAT LENNOXINDOOR UNIT

OPTIONALELECTRIC

HEAT

THERMOSTAT(Optional)

LENNOXOUTDOOR

UNIT

DISCONNECTSWITCH

(By Others)

A

B

CD

SeeNOTES

See NOTES

See NOTES

SeeNOTES

CONTROLBOX

A - Two Wire Power (see Electrical Data)B - Two or Three Wire Power (size to heater capacity)C - Twelve Wire Low Voltage 18 ga. minimum

Fourteen Wire Low Voltage with Optional Outdoor Thermo-stat

D - Eight Wire Low Voltage 18 ga. minimum Ten Wire Low Voltage with Optional Outdoor Thermostat

NOTE - Field Wiring Not FurnishedAll wiring must conform to NEC or CEC and local electrical codes.

NOTES:Service clearance of 30 in. (762 mm) must be maintained on

one of the sides adjacent to the control box.Clearance to one of the other three sides must be 36 in. (914

mm)Clearance to one of the remaining two sides may be 12 in. (305

mm) and the final side may be 6 in. (152 mm).A clearance of 24 in. must be maintained between two units.48 in. (1219 mm) clearance required on top of unit.

SOUND DATA

1 UnitModel No.

Octave Band Sound Power Levels dBA, re 10-12 WattsCenter Frequency - HZ

1 Sound RatingNumber (dB)

125 250 500 1000 2000 4000 800013HPX-018 70.5 67 68 67 65.5 60.5 57.5 7613HPX-024 67.5 66.5 69.5 70 66.5 60.5 56 7613HPX-030 70.5 69.5 71.5 72.5 67.5 63.5 60 7613HPX-036 69.5 70.5 71.5 69.5 68.5 62.5 60.5 7613HPX-042 75.5 79.5 79.5 75.5 70 63.5 58.5 8013HPX-048 75.5 74.5 75 73.5 70 66.5 63.5 8013HPX-060 79 75 75 73 69.5 64.5 58 80

NOTE - the octave sound power data does not include tonal correction. 1 Tested according to AHRI Standard 270-2008 test conditions.

FIELD WIRING INSTALLATION CLEARANCES - IN. (MM)

Page 9: MERIT Series R-410A - LennoxPROs.com · MERIT® Series R-410A Bulletin No. 210460 December 2009 Supersedes November 2009 ENGINEERING DATA SEER up to 14.5 1.5 to 5 Tons Cooling Capacity

13HPX - 1.5 to 5 Ton Heat Pump / Page 9

*TXV SUBSTITUTIONSIndoor Coils/Air Handlers with factory installed expansion valves that require field replacementModel No. Indoor Coil or Air

HandlerOrder No.

13HPX-030 CBX32M-042 49L2413HPX-030 CBX26UH-036 49L2413HPX-030 CBX27UH-036 49L2413HPX-030 CX34-42 49L2413HPX-036 CBX32M-042 49L2413HPX-036 CBX27UH-036 49L2413HPX-036 CBX26UH-036 49L2413HPX-036 CBX27UH-042 49L2413HPX-036 CBX40UH-042 49L2413HPX-036 CX34-42 49L2413HPX-036 CX34-44/48 49L2413HPX-042 CBX32MV-036 49L2513HPX-042 CBX40UHV-036 49L2513HPX-042 CBX26UH-048 49L2513HPX-042 CBX32M-036 49L2513HPX-042 CBX32M-042 49L2513HPX-042 CBX27UH-048 49L2513HPX-042 CX34-50/60 49L2513HPX-042 CX34-49C 49L25*Factory installed expansion valve on the indoor coil or air handler shown must be replaced with the expansion valve listed (ordered separately).

THERMAL EXPANSION VALVES (TXV)Model No. Order No.13HPX-018 49L2413HPX-024 49L2413HPX-030 49L2413HPX-036 49L2413HPX-042 49L2513HPX-048 91M0213HPX-060 91M02

NOTE - CX34 upflow coils and all Lennox air handlers (except CB26UH “R”) are shipped with a factory installed TXV. In most cases, no change out of the valve is needed. If a change out is required it will be listed in the following “TXV SUBSTITUTION” table. The correct TXV must be ordered and field installed. C33 coils and all horizontal and downflow coils are shipped without a TXV. The TXV must be ordered and field installed.

AHRI SYSTEM MATCHESModelNo. Capacity SEER EER Heat Capacity HSPF Coil or

Air Handler Furnace AHRIReferenceHigh Low

13HPX-018-230 (IV) 18,000 13.20 11.00 16,800 10,500 7.70 CB26UH-018 359564713HPX-018-230 (IV) 18,000 13.20 11.00 16,800 10,500 7.70 CBX26UH-018 359564813HPX-018-230 (IV) 18,100 13.20 11.60 16,700 10,400 7.70 CBX32MV-018/024 359564913HPX-018-230 (IV) 18,400 13.50 11.60 16,800 10,400 7.70 CBX32MV-024/030 359565013HPX-018-230 (IV) 18,100 13.50 11.60 16,900 10,600 7.70 CBX40UHV-024 359565113HPX-018-230 (IV) 18,400 13.50 11.60 16,800 10,500 8.00 CBX40UHV-030 359565213HPX-018-230 (V) 18,400 13.50 11.60 16,800 10,400 6.85 CBX32MV-024/030 359565313HPX-018-230 (V) 18,100 13.50 11.60 16,900 10,600 6.85 CBX40UHV-024 3595654

NOTES: Heat Pump suffixes: -230 (IV) = HSPF Region IV -230 (V) = HSPF Region V When used with gas furnaces, a dual-fuel control (i.e. FM21), a control system with dual-fuel capabilities (LZP-2 or LZP-4), or a thermostat with dual-fuel capabilities must be used (ordered extra). Certified in accordance with USE certification program which is based on AHRI Standard 210/240 with 25 ft. of connecting refrigerant lines; Cooling Ratings − 95°F outdoor air temperature and 80 °F db/67° F wb entering indoor coil air. High Temperature Heating Ratings − 47° F db/43° F wb outdoor air temperature and 70 °F db entering indoor coil air. Low Temperature Heating Ratings − 17 °F db/15° F wb outdoor air temperature and 70 °F db entering indoor coil air. All ratings include the use of a blower time delay relay (TDR). All Lennox variable-speed furnaces and Air Handlers have time delay capabilities. Other Furnaces and Air Handlers may require an optional time delay relay (58M81) for field installation. See furnace or air handler specifications to determine if relay is needed.*Most popular combination. Also see TXV Substitution Table.

Page 10: MERIT Series R-410A - LennoxPROs.com · MERIT® Series R-410A Bulletin No. 210460 December 2009 Supersedes November 2009 ENGINEERING DATA SEER up to 14.5 1.5 to 5 Tons Cooling Capacity

13HPX - 1.5 to 5 Ton Heat Pump / Page 10

AHRI SYSTEM MATCHESModelNo. Capacity SEER EER Heat Capacity HSPF Coil or

Air Handler Furnace AHRIReferenceHigh Low

13HPX-018-230 (V) 18,400 13.50 11.60 16,800 10,500 6.90 CBX40UHV-030 359565513HPX-024-230 (IV) 23,400 13.50 11.50 21,600 14,100 8.00 C33-25 G60UHV-36A-070 359557613HPX-024-230 (IV) 23,600 14.00 11.50 21,400 13,900 8.00 C33-25 G60UHV-36B-090 359557913HPX-024-230 (IV) 23,600 13.50 11.50 21,600 14,000 8.00 C33-25 G61MPV-36B-045 359557813HPX-024-230 (IV) 23,600 14.00 11.50 21,600 14,000 8.00 C33-25 G61MPV-36B-070 359557713HPX-024-230 (IV) 23,600 13.50 11.50 21,600 14,100 8.00 C33-25 G61MPV-36B-071 359557513HPX-024-230 (IV) 23,400 14.00 11.50 21,400 13,900 8.00 C33-25 G61MPV-36C-090 359558013HPX-024-230 (IV) 23,600 13.50 11.50 21,800 14,200 8.00 C33-25 G71MPP-36B-070 359557413HPX-024-230 (IV) 23,400 14.00 11.50 21,400 13,900 8.00 C33-25 G71MPP-36C-090 359557313HPX-024-230 (IV) 24,000 14.00 11.50 21,600 14,000 8.00 C33-31 G60UHV-36A-070 359558413HPX-024-230 (IV) 24,000 14.00 12.00 21,400 13,900 8.20 C33-31 G60UHV-36B-090 359558613HPX-024-230 (IV) 24,000 14.00 11.50 21,600 14,000 8.00 C33-31 G61MPV-36B-045 359558513HPX-024-230 (IV) 24,000 14.00 11.50 21,600 14,000 8.00 C33-31 G61MPV-36B-070 359558713HPX-024-230 (IV) 24,000 14.00 11.50 21,600 14,100 8.00 C33-31 G61MPV-36B-071 359558113HPX-024-230 (IV) 24,000 14.00 11.50 21,400 13,900 8.00 C33-31 G61MPV-36C-090 359558813HPX-024-230 (IV) 24,000 14.00 11.50 21,600 14,000 8.00 C33-31 G71MPP-36B-070 359558213HPX-024-230 (IV) 24,000 14.00 11.50 21,400 13,900 8.00 C33-31 G71MPP-36C-090 359558313HPX-024-230 (IV) 23,600 13.50 11.50 21,600 14,100 8.00 C33-36 G60UHV-36A-070 359559213HPX-024-230 (IV) 23,600 14.00 11.50 21,600 14,000 8.00 C33-36 G60UHV-36B-090 359559313HPX-024-230 (IV) 23,600 13.50 11.50 21,600 14,100 8.00 C33-36 G61MPV-36B-045 359559413HPX-024-230 (IV) 23,600 13.50 11.50 21,600 14,100 8.00 C33-36 G61MPV-36B-070 359559513HPX-024-230 (IV) 23,600 13.50 11.50 21,800 14,200 8.00 C33-36 G61MPV-36B-071 359559013HPX-024-230 (IV) 23,400 14.00 11.50 21,400 14,000 8.00 C33-36 G61MPV-36C-090 359559613HPX-024-230 (IV) 23,600 13.50 11.50 21,600 14,100 8.00 C33-36 G71MPP-36B-070 359558913HPX-024-230 (IV) 23,400 14.00 11.50 21,400 14,000 8.00 C33-36 G71MPP-36C-090 359559113HPX-024-230 (IV) 23,200 13.00 11.00 22,000 14,500 8.00 CBX26UH-024 359552813HPX-024-230 (IV) 23,400 13.00 11.00 22,200 14,700 8.00 CBX26UH-030 359552913HPX-024-230 (IV) 23,800 14.00 11.50 21,800 14,200 8.50 CBX27UH-024-230 359553013HPX-024-230 (IV) 23,200 13.00 11.00 22,400 14,700 8.00 CBX32M-030 359553113HPX-024-230 (IV) 22,800 13.00 11.00 21,800 14,300 8.00 CBX32MV-018/024 359553213HPX-024-230 (IV) 23,400 13.00 11.50 22,200 14,600 8.00 CBX32MV-024/030 359553313HPX-024-230 (IV) 23,600 13.50 11.00 22,200 14,700 8.50 CBX40UHV-024 359553413HPX-024-230 (IV) 23,600 13.50 11.50 22,200 14,600 8.50 CBX40UHV-030 359553513HPX-024-230 (IV) 23,400 13.50 11.50 21,600 14,100 8.00 CH33-36A G60UHV-36A-070 359553613HPX-024-230 (IV) 23,600 14.00 11.50 21,600 14,000 8.00 CH33-36B G60UHV-36B-090 359553813HPX-024-230 (IV) 23,600 13.50 11.50 21,600 14,100 8.00 CH33-36B G61MPV-36B-045 359553713HPX-024-230 (IV) 23,600 13.50 11.50 21,600 14,100 8.00 CH33-36B G61MPV-36B-070 359553913HPX-024-230 (IV) 23,600 13.50 11.50 21,800 14,200 8.00 CH33-36B G61MPV-36B-071 359554013HPX-024-230 (IV) 23,600 13.50 11.50 21,600 14,100 8.00 CH33-36B G71MPP-36B-070 359554113HPX-024-230 (IV) 23,600 14.00 11.50 21,600 14,100 8.00 CH33-36C G61MPV-36C-090 3595542

NOTES: Heat Pump suffixes: -230 (IV) = HSPF Region IV -230 (V) = HSPF Region V When used with gas furnaces, a dual-fuel control (i.e. FM21), a control system with dual-fuel capabilities (LZP-2 or LZP-4), or a thermostat with dual-fuel capabilities must be used (ordered extra). Certified in accordance with USE certification program which is based on AHRI Standard 210/240 with 25 ft. of connecting refrigerant lines; Cooling Ratings − 95°F outdoor air temperature and 80 °F db/67° F wb entering indoor coil air. High Temperature Heating Ratings − 47° F db/43° F wb outdoor air temperature and 70 °F db entering indoor coil air. Low Temperature Heating Ratings − 17 °F db/15° F wb outdoor air temperature and 70 °F db entering indoor coil air. All ratings include the use of a blower time delay relay (TDR). All Lennox variable-speed furnaces and Air Handlers have time delay capabilities. Other Furnaces and Air Handlers may require an optional time delay relay (58M81) for field installation. See furnace or air handler specifications to determine if relay is needed.*Most popular combination. Also see TXV Substitution Table.

Page 11: MERIT Series R-410A - LennoxPROs.com · MERIT® Series R-410A Bulletin No. 210460 December 2009 Supersedes November 2009 ENGINEERING DATA SEER up to 14.5 1.5 to 5 Tons Cooling Capacity

13HPX - 1.5 to 5 Ton Heat Pump / Page 11

AHRI SYSTEM MATCHESModelNo. Capacity SEER EER Heat Capacity HSPF Coil or

Air Handler Furnace AHRIReferenceHigh Low

13HPX-024-230 (IV) 23,600 14.00 11.50 21,600 14,100 8.00 CH33-36C G71MPP-36C-090 359554313HPX-024-230 (IV) 24,000 13.50 11.50 22,200 14,600 8.50 CR33-30/36 G60DFV-36A-070 359554613HPX-024-230 (IV) 23,800 14.00 11.50 22,000 14,400 8.50 CR33-30/36 G61MPV-36B-045 359554413HPX-024-230 (IV) 23,800 14.00 11.50 22,000 14,400 8.50 CR33-30/36 G61MPV-36B-070 359554513HPX-024-230 (IV) 23,800 13.50 11.50 22,200 14,500 8.50 CR33-30/36 G61MPV-36B-071 359554813HPX-024-230 (IV) 23,800 14.00 11.50 22,000 14,400 8.50 CR33-30/36 G71MPP-36B-070 359554713HPX-024-230 (IV) 23,400 13.50 11.50 21,600 14,100 8.00 CX34-25 G60UHV-36A-070 359555213HPX-024-230 (IV) 23,600 14.00 11.50 21,400 13,900 8.00 CX34-25 G60UHV-36B-090 359555513HPX-024-230 (IV) 23,600 13.50 11.50 21,600 14,000 8.00 CX34-25 G61MPV-36B-045 359555413HPX-024-230 (IV) 23,600 14.00 11.50 21,600 14,000 8.00 CX34-25 G61MPV-36B-070 359555313HPX-024-230 (IV) 23,600 13.50 11.50 21,600 14,100 8.00 CX34-25 G61MPV-36B-071 359555113HPX-024-230 (IV) 23,400 14.00 11.50 21,400 13,900 8.00 CX34-25 G61MPV-36C-090 359555613HPX-024-230 (IV) 23,600 13.50 11.50 21,800 14,200 8.00 CX34-25 G71MPP-36B-070 359555013HPX-024-230 (IV) 23,400 14.00 11.50 21,400 13,900 8.00 CX34-25 G71MPP-36C-090 359554913HPX-024-230 (IV) 24,000 14.00 11.50 21,600 14,000 8.00 CX34-31 G60UHV-36A-070 359556013HPX-024-230 (IV) 24,000 14.00 12.00 21,400 13,900 8.20 CX34-31 G60UHV-36B-090 359556213HPX-024-230 (IV) 24,000 14.00 11.50 21,600 14,000 8.00 CX34-31 G61MPV-36B-045 359556113HPX-024-230 (IV) 24,000 14.00 11.50 21,600 14,000 8.00 CX34-31 G61MPV-36B-070 359556313HPX-024-230 (IV) 24,000 14.00 11.50 21,600 14,100 8.00 CX34-31 G61MPV-36B-071 359555713HPX-024-230 (IV) 24,000 14.00 11.50 21,400 13,900 8.00 CX34-31 G61MPV-36C-090 359556413HPX-024-230 (IV) 24,000 14.00 11.50 21,600 14,000 8.00 CX34-31 G71MPP-36B-070 359555813HPX-024-230 (IV) 24,000 14.00 11.50 21,400 13,900 8.00 CX34-31 G71MPP-36C-090 359555913HPX-024-230 (IV) 23,600 13.50 11.50 21,600 14,100 8.00 CX34-36 G60UHV-36A-070 359556813HPX-024-230 (IV) 23,600 14.00 11.50 21,600 14,000 8.00 CX34-36 G60UHV-36B-090 359556913HPX-024-230 (IV) 23,600 13.50 11.50 21,600 14,100 8.00 CX34-36 G61MPV-36B-045 359557013HPX-024-230 (IV) 23,600 13.50 11.50 21,600 14,100 8.00 CX34-36 G61MPV-36B-070 359557113HPX-024-230 (IV) 23,600 13.50 11.50 21,800 14,200 8.00 CX34-36 G61MPV-36B-071 359556613HPX-024-230 (IV) 23,400 14.00 11.50 21,400 14,000 8.00 CX34-36 G61MPV-36C-090 359557213HPX-024-230 (IV) 23,600 13.50 11.50 21,600 14,100 8.00 CX34-36 G71MPP-36B-070 359556513HPX-024-230 (IV) 23,400 14.00 11.50 21,400 14,000 8.00 CX34-36 G71MPP-36C-090 359556713HPX-024-230 (V) 23,400 13.50 11.50 21,600 14,100 7.15 C33-25 G60UHV-36A-070 359570113HPX-024-230 (V) 23,600 14.00 11.50 21,400 13,900 7.25 C33-25 G60UHV-36B-090 359570413HPX-024-230 (V) 23,600 13.50 11.50 21,600 14,000 7.20 C33-25 G61MPV-36B-045 359570313HPX-024-230 (V) 23,600 14.00 11.50 21,600 14,000 7.20 C33-25 G61MPV-36B-070 359570213HPX-024-230 (V) 23,600 13.50 11.50 21,600 14,100 7.20 C33-25 G61MPV-36B-071 359570013HPX-024-230 (V) 23,400 14.00 11.50 21,400 13,900 7.20 C33-25 G61MPV-36C-090 359570513HPX-024-230 (V) 23,600 13.50 11.50 21,800 14,200 7.15 C33-25 G71MPP-36B-070 359569913HPX-024-230 (V) 23,400 14.00 11.50 21,400 13,900 7.20 C33-25 G71MPP-36C-090 359569813HPX-024-230 (V) 24,000 14.00 11.50 21,600 14,000 7.20 C33-31 G60UHV-36A-070 359570913HPX-024-230 (V) 24,000 14.00 12.00 21,400 13,900 7.25 C33-31 G60UHV-36B-090 3595711

NOTES: Heat Pump suffixes: -230 (IV) = HSPF Region IV -230 (V) = HSPF Region V When used with gas furnaces, a dual-fuel control (i.e. FM21), a control system with dual-fuel capabilities (LZP-2 or LZP-4), or a thermostat with dual-fuel capabilities must be used (ordered extra). Certified in accordance with USE certification program which is based on AHRI Standard 210/240 with 25 ft. of connecting refrigerant lines; Cooling Ratings − 95°F outdoor air temperature and 80 °F db/67° F wb entering indoor coil air. High Temperature Heating Ratings − 47° F db/43° F wb outdoor air temperature and 70 °F db entering indoor coil air. Low Temperature Heating Ratings − 17 °F db/15° F wb outdoor air temperature and 70 °F db entering indoor coil air. All ratings include the use of a blower time delay relay (TDR). All Lennox variable-speed furnaces and Air Handlers have time delay capabilities. Other Furnaces and Air Handlers may require an optional time delay relay (58M81) for field installation. See furnace or air handler specifications to determine if relay is needed.*Most popular combination. Also see TXV Substitution Table.

Page 12: MERIT Series R-410A - LennoxPROs.com · MERIT® Series R-410A Bulletin No. 210460 December 2009 Supersedes November 2009 ENGINEERING DATA SEER up to 14.5 1.5 to 5 Tons Cooling Capacity

13HPX - 1.5 to 5 Ton Heat Pump / Page 12

AHRI SYSTEM MATCHESModelNo. Capacity SEER EER Heat Capacity HSPF Coil or

Air Handler Furnace AHRIReferenceHigh Low

13HPX-024-230 (V) 24,000 14.00 11.50 21,600 14,000 7.20 C33-31 G61MPV-36B-045 359571013HPX-024-230 (V) 24,000 14.00 11.50 21,600 14,000 7.20 C33-31 G61MPV-36B-070 359571213HPX-024-230 (V) 24,000 14.00 11.50 21,600 14,100 7.20 C33-31 G61MPV-36B-071 359570613HPX-024-230 (V) 24,000 14.00 11.50 21,400 13,900 7.20 C33-31 G61MPV-36C-090 359571313HPX-024-230 (V) 24,000 14.00 11.50 21,600 14,000 7.20 C33-31 G71MPP-36B-070 359570713HPX-024-230 (V) 24,000 14.00 11.50 21,400 13,900 7.20 C33-31 G71MPP-36C-090 359570813HPX-024-230 (V) 23,600 13.50 11.50 21,600 14,100 7.30 C33-36 G60UHV-36A-070 359571713HPX-024-230 (V) 23,600 14.00 11.50 21,600 14,000 7.35 C33-36 G60UHV-36B-090 359571813HPX-024-230 (V) 23,600 13.50 11.50 21,600 14,100 7.30 C33-36 G61MPV-36B-045 359571913HPX-024-230 (V) 23,600 13.50 11.50 21,600 14,100 7.30 C33-36 G61MPV-36B-070 359572013HPX-024-230 (V) 23,600 13.50 11.50 21,800 14,200 7.30 C33-36 G61MPV-36B-071 359571513HPX-024-230 (V) 23,400 14.00 11.50 21,400 14,000 7.30 C33-36 G61MPV-36C-090 359572113HPX-024-230 (V) 23,600 13.50 11.50 21,600 14,100 7.30 C33-36 G71MPP-36B-070 359571413HPX-024-230 (V) 23,400 14.00 11.50 21,400 14,000 7.30 C33-36 G71MPP-36C-090 359571613HPX-024-230 (V) 23,200 13.00 11.00 22,000 14,500 7.25 CBX26UH-024 359560013HPX-024-230 (V) 23,400 13.00 11.00 22,200 14,700 7.35 CBX26UH-030 359560113HPX-024-230 (V) 23,800 14.00 11.50 21,800 14,200 7.60 CBX27UH-024-230 359560213HPX-024-230 (V) 23,200 13.00 11.00 22,400 14,700 7.35 CBX32M-030 359560313HPX-024-230 (V) 22,800 13.00 11.00 21,800 14,300 7.20 CBX32MV-018/024 359560413HPX-024-230 (V) 23,400 13.00 11.50 22,200 14,600 7.40 CBX32MV-024/030 359560513HPX-024-230 (V) 23,600 13.50 11.00 22,200 14,700 7.55 CBX40UHV-024 359560613HPX-024-230 (V) 23,600 13.50 11.50 22,200 14,600 7.55 CBX40UHV-030 359560713HPX-024-230 (V) 23,400 13.50 11.50 21,600 14,100 7.15 CH33-36A G60UHV-36A-070 359560813HPX-024-230 (V) 23,600 14.00 11.50 21,600 14,000 7.35 CH33-36B G60UHV-36B-090 359561013HPX-024-230 (V) 23,600 13.50 11.50 21,600 14,100 7.30 CH33-36B G61MPV-36B-045 359560913HPX-024-230 (V) 23,600 13.50 11.50 21,600 14,100 7.30 CH33-36B G61MPV-36B-070 359561113HPX-024-230 (V) 23,600 13.50 11.50 21,800 14,200 7.35 CH33-36B G61MPV-36B-071 359561213HPX-024-230 (V) 23,600 13.50 11.50 21,600 14,100 7.30 CH33-36B G71MPP-36B-070 359561313HPX-024-230 (V) 23,600 14.00 11.50 21,600 14,100 7.45 CH33-36C G61MPV-36C-090 359561413HPX-024-230 (V) 23,600 14.00 11.50 21,600 14,100 7.45 CH33-36C G71MPP-36C-090 359561513HPX-024-230 (V) 24,000 13.50 11.50 22,200 14,600 7.60 CR33-30/36 G60DFV-36A-070 359561813HPX-024-230 (V) 23,800 14.00 11.50 22,000 14,400 7.65 CR33-30/36 G61MPV-36B-045 359561613HPX-024-230 (V) 23,800 14.00 11.50 22,000 14,400 7.65 CR33-30/36 G61MPV-36B-070 359561713HPX-024-230 (V) 23,800 13.50 11.50 22,200 14,500 7.55 CR33-30/36 G61MPV-36B-071 359562013HPX-024-230 (V) 23,800 14.00 11.50 22,000 14,400 7.65 CR33-30/36 G71MPP-36B-070 359561913HPX-024-230 (V) 23,400 13.50 11.50 21,600 14,100 7.15 CX34-25 G60UHV-36A-070 359562413HPX-024-230 (V) 23,600 14.00 11.50 21,400 13,900 7.25 CX34-25 G60UHV-36B-090 359562713HPX-024-230 (V) 23,600 13.50 11.50 21,600 14,000 7.20 CX34-25 G61MPV-36B-045 359562613HPX-024-230 (V) 23,600 14.00 11.50 21,600 14,000 7.20 CX34-25 G61MPV-36B-070 359562513HPX-024-230 (V) 23,600 13.50 11.50 21,600 14,100 7.20 CX34-25 G61MPV-36B-071 3595623

NOTES: Heat Pump suffixes: -230 (IV) = HSPF Region IV -230 (V) = HSPF Region V When used with gas furnaces, a dual-fuel control (i.e. FM21), a control system with dual-fuel capabilities (LZP-2 or LZP-4), or a thermostat with dual-fuel capabilities must be used (ordered extra). Certified in accordance with USE certification program which is based on AHRI Standard 210/240 with 25 ft. of connecting refrigerant lines; Cooling Ratings − 95°F outdoor air temperature and 80 °F db/67° F wb entering indoor coil air. High Temperature Heating Ratings − 47° F db/43° F wb outdoor air temperature and 70 °F db entering indoor coil air. Low Temperature Heating Ratings − 17 °F db/15° F wb outdoor air temperature and 70 °F db entering indoor coil air. All ratings include the use of a blower time delay relay (TDR). All Lennox variable-speed furnaces and Air Handlers have time delay capabilities. Other Furnaces and Air Handlers may require an optional time delay relay (58M81) for field installation. See furnace or air handler specifications to determine if relay is needed.*Most popular combination. Also see TXV Substitution Table.

Page 13: MERIT Series R-410A - LennoxPROs.com · MERIT® Series R-410A Bulletin No. 210460 December 2009 Supersedes November 2009 ENGINEERING DATA SEER up to 14.5 1.5 to 5 Tons Cooling Capacity

13HPX - 1.5 to 5 Ton Heat Pump / Page 13

AHRI SYSTEM MATCHESModelNo. Capacity SEER EER Heat Capacity HSPF Coil or

Air Handler Furnace AHRIReferenceHigh Low

13HPX-024-230 (V) 23,400 14.00 11.50 21,400 13,900 7.20 CX34-25 G61MPV-36C-090 359562813HPX-024-230 (V) 23,600 13.50 11.50 21,800 14,200 7.15 CX34-25 G71MPP-36B-070 359562213HPX-024-230 (V) 23,400 14.00 11.50 21,400 13,900 7.20 CX34-25 G71MPP-36C-090 359562113HPX-024-230 (V) 24,000 14.00 11.50 21,600 14,000 7.20 CX34-31 G60UHV-36A-070 359563213HPX-024-230 (V) 24,000 14.00 12.00 21,400 13,900 7.25 CX34-31 G60UHV-36B-090 359563413HPX-024-230 (V) 24,000 14.00 11.50 21,600 14,000 7.20 CX34-31 G61MPV-36B-045 359563313HPX-024-230 (V) 24,000 14.00 11.50 21,600 14,000 7.20 CX34-31 G61MPV-36B-070 359563513HPX-024-230 (V) 24,000 14.00 11.50 21,600 14,100 7.20 CX34-31 G61MPV-36B-071 359562913HPX-024-230 (V) 24,000 14.00 11.50 21,400 13,900 7.20 CX34-31 G61MPV-36C-090 359563613HPX-024-230 (V) 24,000 14.00 11.50 21,600 14,000 7.20 CX34-31 G71MPP-36B-070 359563013HPX-024-230 (V) 24,000 14.00 11.50 21,400 13,900 7.20 CX34-31 G71MPP-36C-090 359563113HPX-024-230 (V) 23,600 13.50 11.50 21,600 14,100 7.30 CX34-36 G60UHV-36A-070 359564013HPX-024-230 (V) 23,600 14.00 11.50 21,600 14,000 7.35 CX34-36 G60UHV-36B-090 359564113HPX-024-230 (V) 23,600 13.50 11.50 21,600 14,100 7.30 CX34-36 G61MPV-36B-045 359564213HPX-024-230 (V) 23,600 13.50 11.50 21,600 14,100 7.30 CX34-36 G61MPV-36B-070 359564313HPX-024-230 (V) 23,600 13.50 11.50 21,800 14,200 7.30 CX34-36 G61MPV-36B-071 359563813HPX-024-230 (V) 23,400 14.00 11.50 21,400 14,000 7.30 CX34-36 G61MPV-36C-090 359564413HPX-024-230 (V) 23,600 13.50 11.50 21,600 14,100 7.30 CX34-36 G71MPP-36B-070 359563713HPX-024-230 (V) 23,400 14.00 11.50 21,400 14,000 7.30 CX34-36 G71MPP-36C-090 359563913HPX-030-230 (IV) 28,600 13.50 11.50 27,200 16,800 7.70 C33-25 G61MPV-36B-071 105346613HPX-030-230 (IV) 28,600 13.50 11.50 27,200 16,800 7.70 C33-25 G71MPP-36B-070 148897413HPX-030-230 (IV) 28,600 14.00 11.50 27,000 16,800 7.70 C33-25A G60UHV-36A-070 93120813HPX-030-230 (IV) 28,600 14.00 12.00 27,000 16,800 8.00 C33-25B G60UHV-36B-090 93098813HPX-030-230 (IV) 28,600 13.50 11.50 27,400 17,000 7.70 C33-25B G61MPV-36B-045 93098413HPX-030-230 (IV) 28,600 13.50 11.50 27,200 16,800 7.70 C33-25B G61MPV-36B-070 93096913HPX-030-230 (IV) 29,200 14.00 12.00 27,200 16,800 8.00 C33-31 G61MPV-36B-071 105346713HPX-030-230 (IV) 29,200 14.00 12.00 27,200 16,800 8.00 C33-31 G71MPP-36B-070 148901213HPX-030-230 (IV) 29,200 14.00 12.00 27,000 16,700 8.00 C33-31A G60UHV-36A-070 93113813HPX-030-230 (IV) 29,400 14.00 12.00 27,000 16,600 8.00 C33-31B G60UHV-36B-090 93107213HPX-030-230 (IV) 29,200 14.00 11.50 27,200 16,900 8.00 C33-31B G61MPV-36B-045 93105313HPX-030-230 (IV) 29,200 14.00 12.00 27,200 16,800 8.00 C33-31B G61MPV-36B-070 93130713HPX-030-230 (IV) 28,600 14.00 12.00 27,000 16,700 8.00 C33-36 G61MPV-36B-071 105346813HPX-030-230 (IV) 28,600 14.00 12.00 27,000 16,700 8.00 C33-36 G71MPP-36B-070 148901513HPX-030-230 (IV) 28,600 14.00 12.00 27,000 16,600 8.00 C33-36 G71MPP-36C-090 148959313HPX-030-230 (IV) 28,400 14.00 11.50 27,000 16,800 8.00 C33-36A G60UHV-36A-070 93125113HPX-030-230 (IV) 28,600 14.00 12.00 26,800 16,600 8.00 C33-36B G60UHV-36B-090 93139313HPX-030-230 (IV) 28,600 14.00 11.50 27,200 16,800 8.00 C33-36B G61MPV-36B-045 93099813HPX-030-230 (IV) 28,600 14.00 12.00 27,000 16,700 8.00 C33-36B G61MPV-36B-070 93132813HPX-030-230 (IV) 28,600 14.00 12.00 27,000 16,600 8.00 C33-36C G61MPV-36C-090 93123413HPX-030-230 (IV) 29,400 14.00 12.00 27,200 16,800 8.00 C33-38 G61MPV-36B-071 1053469

NOTES: Heat Pump suffixes: -230 (IV) = HSPF Region IV -230 (V) = HSPF Region V When used with gas furnaces, a dual-fuel control (i.e. FM21), a control system with dual-fuel capabilities (LZP-2 or LZP-4), or a thermostat with dual-fuel capabilities must be used (ordered extra). Certified in accordance with USE certification program which is based on AHRI Standard 210/240 with 25 ft. of connecting refrigerant lines; Cooling Ratings − 95°F outdoor air temperature and 80 °F db/67° F wb entering indoor coil air. High Temperature Heating Ratings − 47° F db/43° F wb outdoor air temperature and 70 °F db entering indoor coil air. Low Temperature Heating Ratings − 17 °F db/15° F wb outdoor air temperature and 70 °F db entering indoor coil air. All ratings include the use of a blower time delay relay (TDR). All Lennox variable-speed furnaces and Air Handlers have time delay capabilities. Other Furnaces and Air Handlers may require an optional time delay relay (58M81) for field installation. See furnace or air handler specifications to determine if relay is needed.*Most popular combination. Also see TXV Substitution Table.

Page 14: MERIT Series R-410A - LennoxPROs.com · MERIT® Series R-410A Bulletin No. 210460 December 2009 Supersedes November 2009 ENGINEERING DATA SEER up to 14.5 1.5 to 5 Tons Cooling Capacity

13HPX - 1.5 to 5 Ton Heat Pump / Page 14

AHRI SYSTEM MATCHESModelNo. Capacity SEER EER Heat Capacity HSPF Coil or

Air Handler Furnace AHRIReferenceHigh Low

13HPX-030-230 (IV) 29,400 14.00 12.00 27,200 16,800 8.00 C33-38 G71MPP-36B-070 148899213HPX-030-230 (IV) 29,400 14.00 12.00 27,000 16,700 8.00 C33-38B G60UHV-36B-090 93102213HPX-030-230 (IV) 29,400 14.00 12.00 27,400 17,000 8.00 C33-38B G61MPV-36B-045 93137213HPX-030-230 (IV) 29,400 14.00 12.00 27,200 16,800 8.00 C33-38B G61MPV-36B-070 93113913HPX-030-230 (IV) 28,400 14.00 11.50 27,200 16,800 8.00 C33-42 G61MPV-36B-071 105347013HPX-030-230 (IV) 28,400 14.00 11.50 27,200 16,800 8.00 C33-42 G71MPP-36B-070 148901113HPX-030-230 (IV) 28,600 14.00 12.00 27,000 16,600 8.00 C33-42B G60UHV-36B-090 93123513HPX-030-230 (IV) 28,600 13.50 11.50 27,200 16,900 8.00 C33-42B G61MPV-36B-045 93122313HPX-030-230 (IV) 28,400 14.00 11.50 27,200 16,800 8.00 C33-42B G61MPV-36B-070 93130413HPX-030-230 (IV) 28,800 13.50 11.50 27,800 17,200 8.00 CBX26UH-030 93104113HPX-030-230 (IV) 28,800 13.50 11.50 27,800 17,200 8.00 CBX26UH-036 93141013HPX-030-230 (IV) 29,000 14.00 12.00 27,400 16,500 8.50 CBX27UH-030-230 114520613HPX-030-230 (IV) 29,000 14.00 12.00 27,400 16,400 8.50 CBX27UH-036-230 114520713HPX-030-230 (IV) 28,600 13.50 11.50 27,600 17,200 8.20 CBX32M-030 93131913HPX-030-230 (IV) 28,600 13.50 11.50 27,800 17,300 8.20 CBX32M-036 93140313HPX-030-230 (IV) 28,600 13.50 11.50 28,000 17,300 8.20 CBX32M-042 93109913HPX-030-230 (IV) 28,800 14.00 12.00 27,600 17,000 8.20 CBX32MV-024/030 93130113HPX-030-230 (IV) 29,000 14.00 12.00 27,600 16,900 8.20 CBX32MV-036 93106813HPX-030-230 (IV) 28,800 14.00 12.00 27,600 17,000 8.20 CBX40UHV-030 329186713HPX-030-230 (IV) 29,000 14.00 12.00 27,600 16,900 8.20 CBX40UHV-036 329189513HPX-030-230 (IV) 28,400 13.50 11.50 27,000 16,800 7.70 CH33-36A G60UHV-36A-070 93099013HPX-030-230 (IV) 28,600 14.00 12.00 27,000 16,700 8.00 CH33-36B G60UHV-36B-090 93136713HPX-030-230 (IV) 28,400 13.50 11.50 27,200 16,900 8.00 CH33-36B G61MPV-36B-045 93118113HPX-030-230 (IV) 28,400 13.50 11.50 27,200 16,900 8.00 CH33-36B G61MPV-36B-070 93102513HPX-030-230 (IV) 28,400 13.50 11.50 27,200 16,900 8.00 CH33-36B G61MPV-36B-071 105347113HPX-030-230 (IV) 28,400 13.50 11.50 27,200 16,900 8.00 CH33-36B G71MPP-36B-070 148897713HPX-030-230 (IV) 28,800 14.00 12.00 27,400 16,900 8.20 CH33-36C G61MPV-36C-090 93125613HPX-030-230 (IV) 28,800 14.00 12.00 27,400 16,900 8.20 CH33-36C G71MPP-36C-090 148959613HPX-030-230 (IV) 29,000 14.00 12.00 27,000 16,800 8.00 CH33-42 G61MPV-36B-071 105347213HPX-030-230 (IV) 29,000 14.00 12.00 27,000 16,800 8.00 CH33-42 G71MPP-36B-070 148897513HPX-030-230 (IV) 29,200 14.00 11.50 27,200 16,900 8.00 CH33-42B G61MPV-36B-045 93102413HPX-030-230 (IV) 29,000 14.00 12.00 27,000 16,800 8.00 CH33-42B G61MPV-36B-070 93097713HPX-030-230 (IV) 28,800 14.00 11.50 27,600 17,000 8.20 CR33-30/36 G60DFV-36A-070 93132413HPX-030-230 (IV) 29,000 14.00 12.00 27,400 16,900 8.20 CR33-30/36 G60DFV-36B-090 93105713HPX-030-230 (IV) 28,800 13.50 11.50 27,800 17,200 8.20 CR33-30/36 G61MPV-36B-045 93140913HPX-030-230 (IV) 28,800 14.00 11.50 27,600 17,000 8.20 CR33-30/36 G61MPV-36B-070 93139513HPX-030-230 (IV) 28,800 14.00 11.50 27,600 17,000 8.20 CR33-30/36 G61MPV-36B-071 105347313HPX-030-230 (IV) 28,800 14.00 12.00 27,400 16,900 8.20 CR33-30/36 G61MPV-36C-090 93109313HPX-030-230 (IV) 28,800 14.00 11.50 27,600 17,000 8.20 CR33-30/36 G71MPP-36B-070 148902813HPX-030-230 (IV) 28,800 14.00 12.00 27,400 16,900 8.20 CR33-30/36 G71MPP-36C-090 1489587

NOTES: Heat Pump suffixes: -230 (IV) = HSPF Region IV -230 (V) = HSPF Region V When used with gas furnaces, a dual-fuel control (i.e. FM21), a control system with dual-fuel capabilities (LZP-2 or LZP-4), or a thermostat with dual-fuel capabilities must be used (ordered extra). Certified in accordance with USE certification program which is based on AHRI Standard 210/240 with 25 ft. of connecting refrigerant lines; Cooling Ratings − 95°F outdoor air temperature and 80 °F db/67° F wb entering indoor coil air. High Temperature Heating Ratings − 47° F db/43° F wb outdoor air temperature and 70 °F db entering indoor coil air. Low Temperature Heating Ratings − 17 °F db/15° F wb outdoor air temperature and 70 °F db entering indoor coil air. All ratings include the use of a blower time delay relay (TDR). All Lennox variable-speed furnaces and Air Handlers have time delay capabilities. Other Furnaces and Air Handlers may require an optional time delay relay (58M81) for field installation. See furnace or air handler specifications to determine if relay is needed.*Most popular combination. Also see TXV Substitution Table.

Page 15: MERIT Series R-410A - LennoxPROs.com · MERIT® Series R-410A Bulletin No. 210460 December 2009 Supersedes November 2009 ENGINEERING DATA SEER up to 14.5 1.5 to 5 Tons Cooling Capacity

13HPX - 1.5 to 5 Ton Heat Pump / Page 15

AHRI SYSTEM MATCHESModelNo. Capacity SEER EER Heat Capacity HSPF Coil or

Air Handler Furnace AHRIReferenceHigh Low

13HPX-030-230 (IV) 28,600 13.50 11.50 27,200 16,800 7.70 CX34-25 G61MPV-36B-071 105347413HPX-030-230 (IV) 28,600 13.50 11.50 27,200 16,800 7.70 CX34-25 G71MPP-36B-070 148900113HPX-030-230 (IV) 28,600 14.00 11.50 27,000 16,800 7.70 CX34-25A G60UHV-36A-070 93139713HPX-030-230 (IV) 28,600 14.00 12.00 27,000 16,800 8.00 CX34-25B G60UHV-36B-090 93112613HPX-030-230 (IV) 28,600 13.50 11.50 27,400 17,000 7.70 CX34-25B G61MPV-36B-045 93110313HPX-030-230 (IV) 28,600 13.50 11.50 27,200 16,800 7.70 CX34-25B G61MPV-36B-070 93123713HPX-030-230 (IV) 29,200 14.00 12.00 27,200 16,800 8.00 CX34-31 G61MPV-36B-071 105347513HPX-030-230 (IV) 29,200 14.00 12.00 27,200 16,800 8.00 CX34-31 G71MPP-36B-070 148898913HPX-030-230 (IV) 29,200 14.00 12.00 27,000 16,700 8.00 CX34-31A G60UHV-36A-070 93103013HPX-030-230 (IV) 29,400 14.00 12.00 27,000 16,600 8.00 CX34-31B G60UHV-36B-090 93104413HPX-030-230 (IV) 29,200 14.00 11.50 27,200 16,900 8.00 CX34-31B G61MPV-36B-045 93135813HPX-030-230 (IV) 29,200 14.00 12.00 27,200 16,800 8.00 CX34-31B G61MPV-36B-070 93110013HPX-030-230 (IV) 28,600 14.00 12.00 27,000 16,700 8.00 CX34-36 G61MPV-36B-071 105347613HPX-030-230 (IV) 28,600 14.00 12.00 27,000 16,700 8.00 CX34-36 G71MPP-36B-070 148900213HPX-030-230 (IV) 28,600 14.00 12.00 27,000 16,600 8.20 CX34-36 G71MPP-36C-090 148959513HPX-030-230 (IV) 28,400 14.00 11.50 27,000 16,800 8.00 CX34-36A G60UHV-36A-070 93130513HPX-030-230 (IV) 28,600 14.00 12.00 26,800 16,600 8.20 CX34-36B G60UHV-36B-090 93129913HPX-030-230 (IV) 28,600 14.00 11.50 27,200 16,800 8.00 CX34-36B G61MPV-36B-045 93115313HPX-030-230 (IV) 28,600 14.00 12.00 27,000 16,700 8.00 CX34-36B G61MPV-36B-070 93124413HPX-030-230 (IV) 28,600 14.00 12.00 27,000 16,600 8.20 CX34-36C G61MPV-36C-090 93124313HPX-030-230 (IV) 29,400 14.00 12.00 27,200 16,800 8.00 CX34-38 G61MPV-36B-071 105347713HPX-030-230 (IV) 29,400 14.00 12.00 27,200 16,800 8.00 CX34-38 G71MPP-36B-070 148902313HPX-030-230 (IV) 29,400 14.00 12.00 27,000 16,700 8.20 CX34-38B G60UHV-36B-090 93139613HPX-030-230 (IV) 29,400 14.00 12.00 27,400 17,000 8.00 CX34-38B G61MPV-36B-045 93105813HPX-030-230 (IV) 29,400 14.00 12.00 27,200 16,800 8.00 CX34-38B G61MPV-36B-070 93136513HPX-030-230 (IV) 28,400 14.00 11.50 27,200 16,800 8.00 CX34-42 G61MPV-36B-071 105347813HPX-030-230 (IV) 28,400 14.00 11.50 27,200 16,800 8.00 CX34-42 G71MPP-36B-070 148901913HPX-030-230 (IV) 28,600 14.00 12.00 27,000 16,600 8.00 CX34-42B G60UHV-36B-090 93122513HPX-030-230 (IV) 28,600 13.50 11.50 27,200 16,900 8.00 CX34-42B G61MPV-36B-045 93124813HPX-030-230 (IV) 28,400 14.00 11.50 27,200 16,800 8.00 CX34-42B G61MPV-36B-070 93134913HPX-030-230 (V) 28,600 13.50 11.50 27,200 16,800 6.70 C33-25 G71MPP-36B-070 148897313HPX-030-230 (V) 28,600 14.00 11.50 27,000 16,800 6.70 C33-25A G60UHV-36A-070 93134013HPX-030-230 (V) 28,600 14.00 12.00 27,000 16,800 7.00 C33-25B G60UHV-36B-090 93095513HPX-030-230 (V) 28,600 13.50 11.50 27,400 17,000 6.70 C33-25B G61MPV-36B-045 93104013HPX-030-230 (V) 28,600 13.50 11.50 27,200 16,800 6.70 C33-25B G61MPV-36B-070 93095313HPX-030-230 (V) 29,200 14.00 12.00 27,200 16,800 6.70 C33-31 G71MPP-36B-070 148898613HPX-030-230 (V) 29,200 14.00 12.00 27,000 16,700 7.00 C33-31A G60UHV-36A-070 93132613HPX-030-230 (V) 29,400 14.00 12.00 27,000 16,600 7.00 C33-31B G60UHV-36B-090 93110913HPX-030-230 (V) 29,200 14.00 11.50 27,200 16,900 6.70 C33-31B G61MPV-36B-045 93116513HPX-030-230 (V) 29,200 14.00 12.00 27,200 16,800 6.70 C33-31B G61MPV-36B-070 931085

NOTES: Heat Pump suffixes: -230 (IV) = HSPF Region IV -230 (V) = HSPF Region V When used with gas furnaces, a dual-fuel control (i.e. FM21), a control system with dual-fuel capabilities (LZP-2 or LZP-4), or a thermostat with dual-fuel capabilities must be used (ordered extra). Certified in accordance with USE certification program which is based on AHRI Standard 210/240 with 25 ft. of connecting refrigerant lines; Cooling Ratings − 95°F outdoor air temperature and 80 °F db/67° F wb entering indoor coil air. High Temperature Heating Ratings − 47° F db/43° F wb outdoor air temperature and 70 °F db entering indoor coil air. Low Temperature Heating Ratings − 17 °F db/15° F wb outdoor air temperature and 70 °F db entering indoor coil air. All ratings include the use of a blower time delay relay (TDR). All Lennox variable-speed furnaces and Air Handlers have time delay capabilities. Other Furnaces and Air Handlers may require an optional time delay relay (58M81) for field installation. See furnace or air handler specifications to determine if relay is needed.*Most popular combination. Also see TXV Substitution Table.

Page 16: MERIT Series R-410A - LennoxPROs.com · MERIT® Series R-410A Bulletin No. 210460 December 2009 Supersedes November 2009 ENGINEERING DATA SEER up to 14.5 1.5 to 5 Tons Cooling Capacity

13HPX - 1.5 to 5 Ton Heat Pump / Page 16

AHRI SYSTEM MATCHESModelNo. Capacity SEER EER Heat Capacity HSPF Coil or

Air Handler Furnace AHRIReferenceHigh Low

13HPX-030-230 (V) 28,600 14.00 12.00 27,000 16,700 7.00 C33-36 G71MPP-36B-070 148898113HPX-030-230 (V) 28,600 14.00 12.00 27,000 16,600 7.00 C33-36 G71MPP-36C-090 148958113HPX-030-230 (V) 28,400 14.00 11.50 27,000 16,800 7.00 C33-36A G60UHV-36A-070 93117313HPX-030-230 (V) 28,600 14.00 12.00 26,800 16,600 7.00 C33-36B G60UHV-36B-090 93118313HPX-030-230 (V) 28,600 14.00 11.50 27,200 16,800 7.00 C33-36B G61MPV-36B-045 93115713HPX-030-230 (V) 28,600 14.00 12.00 27,000 16,700 7.00 C33-36B G61MPV-36B-070 93106513HPX-030-230 (V) 28,600 14.00 12.00 27,000 16,600 7.00 C33-36C G61MPV-36C-090 93097613HPX-030-230 (V) 29,400 14.00 12.00 27,200 16,800 7.00 C33-38 G71MPP-36B-070 148900013HPX-030-230 (V) 29,400 14.00 12.00 27,000 16,700 7.00 C33-38B G60UHV-36B-090 93135013HPX-030-230 (V) 29,400 14.00 12.00 27,400 17,000 7.00 C33-38B G61MPV-36B-045 93110813HPX-030-230 (V) 29,400 14.00 12.00 27,200 16,800 7.00 C33-38B G61MPV-36B-070 93121813HPX-030-230 (V) 28,400 14.00 11.50 27,200 16,800 7.00 C33-42 G71MPP-36B-070 148900313HPX-030-230 (V) 28,600 14.00 12.00 27,000 16,600 7.00 C33-42B G60UHV-36B-090 93120113HPX-030-230 (V) 28,600 13.50 11.50 27,200 16,900 7.00 C33-42B G61MPV-36B-045 93129813HPX-030-230 (V) 28,400 14.00 11.50 27,200 16,800 7.00 C33-42B G61MPV-36B-070 93126013HPX-030-230 (V) 28,800 13.50 11.50 27,800 17,200 7.00 CBX26UH-030 93100113HPX-030-230 (V) 28,800 13.50 11.50 27,800 17,200 7.00 CBX26UH-036 93102313HPX-030-230 (V) 28,600 13.50 11.50 27,600 17,200 7.00 CBX32M-030 93134513HPX-030-230 (V) 28,600 13.50 11.50 27,800 17,300 7.00 CBX32M-036 93099913HPX-030-230 (V) 28,600 13.50 11.50 28,000 17,300 7.00 CBX32M-042 93120413HPX-030-230 (V) 28,800 14.00 12.00 27,600 17,000 7.00 CBX32MV-024/030 93136013HPX-030-230 (V) 29,000 14.00 12.00 27,600 16,900 7.00 CBX32MV-036 93115813HPX-030-230 (V) 28,800 14.00 12.00 27,600 17,000 7.00 CBX40UHV-030 329186813HPX-030-230 (V) 29,000 14.00 12.00 27,600 16,900 7.00 CBX40UHV-036 329189613HPX-030-230 (V) 28,400 13.50 11.50 27,000 16,800 6.70 CH33-36A G60UHV-36A-070 93101613HPX-030-230 (V) 28,600 14.00 12.00 27,000 16,700 7.00 CH33-36B G60UHV-36B-090 93106613HPX-030-230 (V) 28,400 13.50 11.50 27,200 16,900 6.70 CH33-36B G61MPV-36B-045 93121413HPX-030-230 (V) 28,400 13.50 11.50 27,200 16,900 6.70 CH33-36B G61MPV-36B-070 93137013HPX-030-230 (V) 28,400 13.50 11.50 27,200 16,900 6.70 CH33-36B G71MPP-36B-070 148902413HPX-030-230 (V) 28,800 14.00 12.00 27,400 16,900 7.00 CH33-36C G61MPV-36C-090 93138613HPX-030-230 (V) 28,800 14.00 12.00 27,400 16,900 7.00 CH33-36C G71MPP-36C-090 148960913HPX-030-230 (V) 29,000 14.00 12.00 27,000 16,800 7.00 CH33-42 G71MPP-36B-070 148903013HPX-030-230 (V) 29,200 14.00 11.50 27,200 16,900 7.00 CH33-42B G61MPV-36B-045 93095413HPX-030-230 (V) 29,000 14.00 12.00 27,000 16,800 7.00 CH33-42B G61MPV-36B-070 93140813HPX-030-230 (V) 28,800 14.00 11.50 27,600 17,000 7.00 CR33-30/36 G60DFV-36A-070 93135713HPX-030-230 (V) 29,000 14.00 12.00 27,400 16,900 7.00 CR33-30/36 G60DFV-36B-090 93138513HPX-030-230 (V) 28,800 13.50 11.50 27,800 17,200 7.00 CR33-30/36 G61MPV-36B-045 93129513HPX-030-230 (V) 28,800 14.00 11.50 27,600 17,000 7.00 CR33-30/36 G61MPV-36B-070 93126413HPX-030-230 (V) 28,800 14.00 12.00 27,400 16,900 7.00 CR33-30/36 G61MPV-36C-090 93101913HPX-030-230 (V) 28,800 14.00 11.50 27,600 17,000 7.00 CR33-30/36 G71MPP-36B-070 1489005

NOTES: Heat Pump suffixes: -230 (IV) = HSPF Region IV -230 (V) = HSPF Region V When used with gas furnaces, a dual-fuel control (i.e. FM21), a control system with dual-fuel capabilities (LZP-2 or LZP-4), or a thermostat with dual-fuel capabilities must be used (ordered extra). Certified in accordance with USE certification program which is based on AHRI Standard 210/240 with 25 ft. of connecting refrigerant lines; Cooling Ratings − 95°F outdoor air temperature and 80 °F db/67° F wb entering indoor coil air. High Temperature Heating Ratings − 47° F db/43° F wb outdoor air temperature and 70 °F db entering indoor coil air. Low Temperature Heating Ratings − 17 °F db/15° F wb outdoor air temperature and 70 °F db entering indoor coil air. All ratings include the use of a blower time delay relay (TDR). All Lennox variable-speed furnaces and Air Handlers have time delay capabilities. Other Furnaces and Air Handlers may require an optional time delay relay (58M81) for field installation. See furnace or air handler specifications to determine if relay is needed.*Most popular combination. Also see TXV Substitution Table.

Page 17: MERIT Series R-410A - LennoxPROs.com · MERIT® Series R-410A Bulletin No. 210460 December 2009 Supersedes November 2009 ENGINEERING DATA SEER up to 14.5 1.5 to 5 Tons Cooling Capacity

13HPX - 1.5 to 5 Ton Heat Pump / Page 17

AHRI SYSTEM MATCHESModelNo. Capacity SEER EER Heat Capacity HSPF Coil or

Air Handler Furnace AHRIReferenceHigh Low

13HPX-030-230 (V) 28,800 14.00 12.00 27,400 16,900 7.00 CR33-30/36 G71MPP-36C-090 148958213HPX-030-230 (V) 28,600 13.50 11.50 27,200 16,800 6.70 CX34-25 G71MPP-36B-070 148902613HPX-030-230 (V) 28,600 14.00 11.50 27,000 16,800 6.70 CX34-25A G60UHV-36A-070 93114913HPX-030-230 (V) 28,600 14.00 12.00 27,000 16,800 7.00 CX34-25B G60UHV-36B-090 93114813HPX-030-230 (V) 28,600 13.50 11.50 27,400 17,000 6.70 CX34-25B G61MPV-36B-045 93130813HPX-030-230 (V) 28,600 13.50 11.50 27,200 16,800 6.70 CX34-25B G61MPV-36B-070 93138713HPX-030-230 (V) 29,200 14.00 12.00 27,200 16,800 6.70 CX34-31 G71MPP-36B-070 148901313HPX-030-230 (V) 29,200 14.00 12.00 27,000 16,700 7.00 CX34-31A G60UHV-36A-070 93112313HPX-030-230 (V) 29,400 14.00 12.00 27,000 16,600 7.00 CX34-31B G60UHV-36B-090 93124213HPX-030-230 (V) 29,200 14.00 11.50 27,200 16,900 6.70 CX34-31B G61MPV-36B-045 93113713HPX-030-230 (V) 29,200 14.00 12.00 27,200 16,800 6.70 CX34-31B G61MPV-36B-070 93131213HPX-030-230 (V) 28,600 14.00 12.00 27,000 16,700 7.00 CX34-36 G71MPP-36B-070 148899013HPX-030-230 (V) 28,600 14.00 12.00 27,000 16,600 7.00 CX34-36 G71MPP-36C-090 148958913HPX-030-230 (V) 28,400 14.00 11.50 27,000 16,800 7.00 CX34-36A G60UHV-36A-070 93095713HPX-030-230 (V) 28,600 14.00 12.00 26,800 16,600 7.00 CX34-36B G60UHV-36B-090 93096613HPX-030-230 (V) 28,600 14.00 11.50 27,200 16,800 7.00 CX34-36B G61MPV-36B-045 93099613HPX-030-230 (V) 28,600 14.00 12.00 27,000 16,700 7.00 CX34-36B G61MPV-36B-070 93112713HPX-030-230 (V) 28,600 14.00 12.00 27,000 16,600 7.00 CX34-36C G61MPV-36C-090 93112213HPX-030-230 (V) 29,400 14.00 12.00 27,200 16,800 7.00 CX34-38 G71MPP-36B-070 148899913HPX-030-230 (V) 29,400 14.00 12.00 27,000 16,700 7.00 CX34-38B G60UHV-36B-090 93141113HPX-030-230 (V) 29,400 14.00 12.00 27,400 17,000 7.00 CX34-38B G61MPV-36B-045 93122913HPX-030-230 (V) 29,400 14.00 12.00 27,200 16,800 7.00 CX34-38B G61MPV-36B-070 93120913HPX-030-230 (V) 28,400 14.00 11.50 27,200 16,800 7.00 CX34-42 G71MPP-36B-070 148900813HPX-030-230 (V) 28,600 14.00 12.00 27,000 16,600 7.00 CX34-42B G60UHV-36B-090 93106113HPX-030-230 (V) 28,600 13.50 11.50 27,200 16,900 7.00 CX34-42B G61MPV-36B-045 93123813HPX-030-230 (V) 28,400 14.00 11.50 27,200 16,800 7.00 CX34-42B G61MPV-36B-070 93129313HPX-036-230 (IV) 33,400 13.50 11.00 34,200 22,000 8.20 C33-36 G60UHV-36B-090 351359313HPX-036-230 (IV) 33,400 13.50 11.00 34,000 22,000 8.20 C33-36 G61MPV-36C-090 351359413HPX-036-230 (IV) 33,400 13.50 11.00 34,000 22,000 8.20 C33-36 G71MPP-36C-090 351359513HPX-036-230 (IV) 34,400 13.50 11.00 34,400 22,400 8.20 C33-38 G60UHV-36A-070 351359613HPX-036-230 (IV) 34,800 14.00 11.50 34,200 22,000 8.20 C33-38 G60UHV-36B-090 351359713HPX-036-230 (IV) 34,400 13.00 11.00 34,600 22,400 8.00 C33-38 G61MPV-36B-045 351359813HPX-036-230 (IV) 34,400 13.50 11.00 34,400 22,200 8.00 C33-38 G61MPV-36B-070 351359913HPX-036-230 (IV) 34,200 13.50 11.00 34,400 22,200 8.00 C33-38 G61MPV-36B-071 351360013HPX-036-230 (IV) 34,400 13.50 11.00 34,400 22,200 8.00 C33-38 G71MPP-36B-070 351360113HPX-036-230 (IV) 33,400 13.50 11.00 34,200 22,000 8.20 C33-42 G60UHV-36B-090 351360213HPX-036-230 (IV) 34,400 14.00 11.50 34,000 22,000 8.00 C33-48 G60UHV-36B-090 351366213HPX-036-230 (IV) 34,400 13.50 11.50 33,800 21,800 8.00 C33-48 G61MPV-36C-090 351366313HPX-036-230 (IV) 34,400 13.50 11.50 33,800 21,800 8.00 C33-48 G71MPP-36C-090 351366413HPX-036-230 (IV) 34,000 13.00 11.00 34,800 22,600 8.20 CBX26UH-036 3513519

NOTES: Heat Pump suffixes: -230 (IV) = HSPF Region IV -230 (V) = HSPF Region V When used with gas furnaces, a dual-fuel control (i.e. FM21), a control system with dual-fuel capabilities (LZP-2 or LZP-4), or a thermostat with dual-fuel capabilities must be used (ordered extra). Certified in accordance with USE certification program which is based on AHRI Standard 210/240 with 25 ft. of connecting refrigerant lines; Cooling Ratings − 95°F outdoor air temperature and 80 °F db/67° F wb entering indoor coil air. High Temperature Heating Ratings − 47° F db/43° F wb outdoor air temperature and 70 °F db entering indoor coil air. Low Temperature Heating Ratings − 17 °F db/15° F wb outdoor air temperature and 70 °F db entering indoor coil air. All ratings include the use of a blower time delay relay (TDR). All Lennox variable-speed furnaces and Air Handlers have time delay capabilities. Other Furnaces and Air Handlers may require an optional time delay relay (58M81) for field installation. See furnace or air handler specifications to determine if relay is needed.*Most popular combination. Also see TXV Substitution Table.

Page 18: MERIT Series R-410A - LennoxPROs.com · MERIT® Series R-410A Bulletin No. 210460 December 2009 Supersedes November 2009 ENGINEERING DATA SEER up to 14.5 1.5 to 5 Tons Cooling Capacity

13HPX - 1.5 to 5 Ton Heat Pump / Page 18

AHRI SYSTEM MATCHESModelNo. Capacity SEER EER Heat Capacity HSPF Coil or

Air Handler Furnace AHRIReferenceHigh Low

13HPX-036-230 (IV) 34,200 13.00 11.00 34,800 22,600 8.50 CBX26UH-037 351366513HPX-036-230 (IV) 34,000 13.50 11.50 34,400 22,200 8.70 CBX27UH-036-230 351360813HPX-036-230 (IV) 35,200 14.50 12.00 34,400 22,000 8.70 CBX27UH-042-230 351360913HPX-036-230 (IV) 33,600 13.00 10.95 35,000 22,600 8.50 CBX32M-036 351361013HPX-036-230 (IV) 33,800 13.00 11.00 34,800 22,600 8.50 CBX32M-042 351361113HPX-036-230 (IV) 34,200 14.00 11.50 34,400 22,200 8.70 CBX32MV-036 351361213HPX-036-230 (IV) 33,600 13.50 11.00 34,200 22,000 8.20 CH33-36B G60UHV-36B-090 351361313HPX-036-230 (IV) 33,200 13.00 11.00 34,400 22,200 8.00 CH33-36B G61MPV-36B-070 351361413HPX-036-230 (IV) 33,200 13.00 11.00 34,400 22,200 8.00 CH33-36B G61MPV-36B-071 351361513HPX-036-230 (IV) 33,200 13.00 11.00 34,400 22,200 8.00 CH33-36B G71MPP-36B-070 351361613HPX-036-230 (IV) 33,600 13.50 11.00 34,200 22,000 8.50 CH33-36C G61MPV-36C-090 351361713HPX-036-230 (IV) 33,600 13.50 11.00 34,200 22,000 8.50 CH33-36C G71MPP-36C-090 351361813HPX-036-230 (IV) 34,200 13.50 11.00 34,200 22,200 8.20 CH33-42 G60UHV-36B-090 351361913HPX-036-230 (IV) 34,000 13.00 11.00 34,600 22,600 8.00 CH33-42 G61MPV-36B-045 351362013HPX-036-230 (IV) 33,800 13.00 11.00 34,400 22,400 8.00 CH33-42 G61MPV-36B-070 351362113HPX-036-230 (IV) 33,800 13.00 11.00 34,400 22,400 8.00 CH33-42 G61MPV-36B-071 351362213HPX-036-230 (IV) 33,800 13.00 11.00 34,400 22,400 8.00 CH33-42 G71MPP-36B-070 351362313HPX-036-230 (IV) 34,600 13.50 11.50 34,400 22,200 8.20 CH33-44/48 G60UHV-36B-090 351362413HPX-036-230 (IV) 34,200 13.00 11.00 34,800 22,600 8.20 CH33-44/48 G61MPV-36B-045 351362513HPX-036-230 (IV) 34,200 13.00 11.00 34,600 22,400 8.20 CH33-44/48 G61MPV-36B-070 351362613HPX-036-230 (IV) 34,200 13.00 11.00 34,600 22,400 8.20 CH33-44/48 G61MPV-36B-071 351362813HPX-036-230 (IV) 34,200 13.00 11.00 34,600 22,400 8.20 CH33-44/48 G71MPP-36B-070 351362913HPX-036-230 (IV) 34,600 14.00 11.50 34,000 22,000 8.20 CH33-48 G61MPV-36C-090 351363013HPX-036-230 (IV) 34,600 14.00 11.50 34,000 22,000 8.20 CH33-48 G71MPP-36C-090 351363113HPX-036-230 (IV) 33,600 13.50 11.00 34,400 22,200 8.50 CR33-30/36 G60DFV-36B-090 351363213HPX-036-230 (IV) 33,400 13.00 10.95 34,600 22,400 8.20 CR33-30/36 G61MPV-36B-070 351363313HPX-036-230 (IV) 33,400 13.00 10.95 34,800 22,400 8.20 CR33-30/36 G61MPV-36B-071 351363413HPX-036-230 (IV) 33,600 13.50 11.00 34,400 22,200 8.50 CR33-30/36 G61MPV-36C-090 351363513HPX-036-230 (IV) 33,400 13.00 10.95 34,600 22,400 8.20 CR33-30/36 G71MPP-36B-070 351363613HPX-036-230 (IV) 33,600 13.50 11.00 34,400 22,200 8.50 CR33-30/36 G71MPP-36C-090 351363713HPX-036-230 (IV) 34,200 14.00 11.50 34,200 22,000 8.20 CR33-48 G60DFV-36B-090 351363813HPX-036-230 (IV) 34,000 13.00 11.00 34,800 22,600 8.20 CR33-48 G61MPV-36B-045 351363913HPX-036-230 (IV) 34,000 13.00 11.00 34,400 22,400 8.20 CR33-48 G61MPV-36B-070 351364013HPX-036-230 (IV) 34,000 13.00 11.00 34,400 22,400 8.20 CR33-48 G61MPV-36B-071 351364113HPX-036-230 (IV) 34,200 13.50 11.50 34,200 22,000 8.20 CR33-48 G61MPV-36C-090 351364213HPX-036-230 (IV) 34,000 13.00 11.00 34,400 22,400 8.20 CR33-48 G71MPP-36B-070 351364313HPX-036-230 (IV) 34,200 13.50 11.50 34,200 22,000 8.20 CR33-48 G71MPP-36C-090 351364413HPX-036-230 (IV) 34,600 13.50 11.00 34,800 22,400 8.50 CR33-50/60 G61MPV-36B-071 351364513HPX-036-230 (IV) 35,000 14.00 11.50 34,400 22,200 8.70 CR33-50/60 G61MPV-36C-090 351364613HPX-036-230 (IV) 35,000 14.00 11.50 34,400 22,200 8.70 CR33-50/60 G71MPP-36C-090 3513647

NOTES: Heat Pump suffixes: -230 (IV) = HSPF Region IV -230 (V) = HSPF Region V When used with gas furnaces, a dual-fuel control (i.e. FM21), a control system with dual-fuel capabilities (LZP-2 or LZP-4), or a thermostat with dual-fuel capabilities must be used (ordered extra). Certified in accordance with USE certification program which is based on AHRI Standard 210/240 with 25 ft. of connecting refrigerant lines; Cooling Ratings − 95°F outdoor air temperature and 80 °F db/67° F wb entering indoor coil air. High Temperature Heating Ratings − 47° F db/43° F wb outdoor air temperature and 70 °F db entering indoor coil air. Low Temperature Heating Ratings − 17 °F db/15° F wb outdoor air temperature and 70 °F db entering indoor coil air. All ratings include the use of a blower time delay relay (TDR). All Lennox variable-speed furnaces and Air Handlers have time delay capabilities. Other Furnaces and Air Handlers may require an optional time delay relay (58M81) for field installation. See furnace or air handler specifications to determine if relay is needed.*Most popular combination. Also see TXV Substitution Table.

Page 19: MERIT Series R-410A - LennoxPROs.com · MERIT® Series R-410A Bulletin No. 210460 December 2009 Supersedes November 2009 ENGINEERING DATA SEER up to 14.5 1.5 to 5 Tons Cooling Capacity

13HPX - 1.5 to 5 Ton Heat Pump / Page 19

AHRI SYSTEM MATCHESModelNo. Capacity SEER EER Heat Capacity HSPF Coil or

Air Handler Furnace AHRIReferenceHigh Low

13HPX-036-230 (IV) 33,400 13.50 11.00 34,200 22,000 8.20 CX34-36 G60UHV-36B-090 351364913HPX-036-230 (IV) 33,400 13.50 11.00 34,000 22,000 8.20 CX34-36 G61MPV-36C-090 351365013HPX-036-230 (IV) 33,400 13.50 11.00 34,000 22,000 8.20 CX34-36 G71MPP-36C-090 351365113HPX-036-230 (IV) 34,400 13.50 11.00 34,400 22,400 8.20 CX34-38 G60UHV-36A-070 351365213HPX-036-230 (IV) 34,800 14.00 11.50 34,200 22,000 8.20 CX34-38 G60UHV-36B-090 351365313HPX-036-230 (IV) 34,400 13.00 11.00 34,600 22,400 8.00 CX34-38 G61MPV-36B-045 351365413HPX-036-230 (IV) 34,400 13.50 11.00 34,400 22,200 8.00 CX34-38 G61MPV-36B-070 351365513HPX-036-230 (IV) 34,200 13.50 11.00 34,400 22,200 8.00 CX34-38 G61MPV-36B-071 351365613HPX-036-230 (IV) 34,400 13.50 11.00 34,400 22,200 8.00 CX34-38 G71MPP-36B-070 351365713HPX-036-230 (IV) 33,400 13.50 11.00 34,200 22,000 8.20 CX34-42 G60UHV-36B-090 351365813HPX-036-230 (IV) 34,400 14.00 11.50 34,000 22,000 8.00 CX34-44/48 G60UHV-36B-090 351365913HPX-036-230 (IV) 34,400 13.50 11.50 33,800 21,800 8.00 CX34-44/48 G61MPV-36C-090 351366013HPX-036-230 (IV) 34,400 13.50 11.50 33,800 21,800 8.00 CX34-44/48 G71MPP-36C-090 351366113HPX-036-230 (V) 33,400 13.50 11.00 34,200 22,000 7.40 C33-36 G60UHV-36B-090 351355113HPX-036-230 (V) 33,400 13.50 11.00 34,000 22,000 7.35 C33-36 G61MPV-36C-090 351355213HPX-036-230 (V) 33,400 13.50 11.00 34,000 22,000 7.35 C33-36 G71MPP-36C-090 351355313HPX-036-230 (V) 34,400 13.50 11.00 34,400 22,400 7.30 C33-38 G60UHV-36A-070 351353513HPX-036-230 (V) 34,800 14.00 11.50 34,200 22,000 7.45 C33-38 G60UHV-36B-090 351353613HPX-036-230 (V) 34,400 13.00 11.00 34,600 22,400 7.30 C33-38 G61MPV-36B-045 351353713HPX-036-230 (V) 34,400 13.50 11.00 34,400 22,200 7.30 C33-38 G61MPV-36B-070 351353813HPX-036-230 (V) 34,200 13.50 11.00 34,400 22,200 7.30 C33-38 G61MPV-36B-071 351353913HPX-036-230 (V) 34,400 13.50 11.00 34,400 22,200 7.30 C33-38 G71MPP-36B-070 351354013HPX-036-230 (V) 33,400 13.50 11.00 34,200 22,000 7.40 C33-42 G60UHV-36B-090 351354113HPX-036-230 (V) 34,400 14.00 11.50 34,000 22,000 7.20 C33-48 G60UHV-36B-090 351354213HPX-036-230 (V) 34,400 13.50 11.50 33,800 21,800 7.15 C33-48 G61MPV-36C-090 351354313HPX-036-230 (V) 34,400 13.50 11.50 33,800 21,800 7.15 C33-48 G71MPP-36C-090 351352213HPX-036-230 (V) 34,000 13.00 11.00 34,800 22,600 7.40 CBX26UH-036 351351813HPX-036-230 (V) 34,200 13.00 11.00 34,800 22,600 7.55 CBX26UH-037 351352813HPX-036-230 (V) 34,000 13.50 11.50 34,400 22,200 7.70 CBX27UH-036-230 351352913HPX-036-230 (V) 35,200 14.50 12.00 34,400 22,000 7.80 CBX27UH-042-230 351353013HPX-036-230 (V) 33,600 13.00 10.95 35,000 22,600 7.55 CBX32M-036 351355413HPX-036-230 (V) 33,800 13.00 11.00 34,800 22,600 7.60 CBX32M-042 351355513HPX-036-230 (V) 34,200 14.00 11.50 34,400 22,200 7.75 CBX32MV-036 351353113HPX-036-230 (V) 33,600 13.50 11.00 34,200 22,000 7.35 CH33-36B G60UHV-36B-090 351353213HPX-036-230 (V) 33,200 13.00 11.00 34,400 22,200 7.25 CH33-36B G61MPV-36B-070 351353313HPX-036-230 (V) 33,200 13.00 11.00 34,400 22,200 7.25 CH33-36B G61MPV-36B-071 351353413HPX-036-230 (V) 33,200 13.00 11.00 34,400 22,200 7.25 CH33-36B G71MPP-36B-070 351354413HPX-036-230 (V) 33,600 13.50 11.00 34,200 22,000 7.50 CH33-36C G61MPV-36C-090 351354513HPX-036-230 (V) 33,600 13.50 11.00 34,200 22,000 7.50 CH33-36C G71MPP-36C-090 351355613HPX-036-230 (V) 34,200 13.50 11.00 34,200 22,200 7.30 CH33-42 G60UHV-36B-090 351355713HPX-036-230 (V) 34,000 13.00 11.00 34,600 22,600 7.20 CH33-42 G61MPV-36B-045 351355813HPX-036-230 (V) 33,800 13.00 11.00 34,400 22,400 7.20 CH33-42 G61MPV-36B-070 3513559

NOTES: Heat Pump suffixes: -230 (IV) = HSPF Region IV -230 (V) = HSPF Region V When used with gas furnaces, a dual-fuel control (i.e. FM21), a control system with dual-fuel capabilities (LZP-2 or LZP-4), or a thermostat with dual-fuel capabilities must be used (ordered extra). Certified in accordance with USE certification program which is based on AHRI Standard 210/240 with 25 ft. of connecting refrigerant lines; Cooling Ratings − 95°F outdoor air temperature and 80 °F db/67° F wb entering indoor coil air. High Temperature Heating Ratings − 47° F db/43° F wb outdoor air temperature and 70 °F db entering indoor coil air. Low Temperature Heating Ratings − 17 °F db/15° F wb outdoor air temperature and 70 °F db entering indoor coil air. All ratings include the use of a blower time delay relay (TDR). All Lennox variable-speed furnaces and Air Handlers have time delay capabilities. Other Furnaces and Air Handlers may require an optional time delay relay (58M81) for field installation. See furnace or air handler specifications to determine if relay is needed.*Most popular combination. Also see TXV Substitution Table.

Page 20: MERIT Series R-410A - LennoxPROs.com · MERIT® Series R-410A Bulletin No. 210460 December 2009 Supersedes November 2009 ENGINEERING DATA SEER up to 14.5 1.5 to 5 Tons Cooling Capacity

13HPX - 1.5 to 5 Ton Heat Pump / Page 20

AHRI SYSTEM MATCHESModelNo. Capacity SEER EER Heat Capacity HSPF Coil or

Air Handler Furnace AHRIReferenceHigh Low

13HPX-036-230 (V) 33,800 13.00 11.00 34,400 22,400 7.20 CH33-42 G61MPV-36B-071 351356013HPX-036-230 (V) 33,800 13.00 11.00 34,400 22,400 7.20 CH33-42 G71MPP-36B-070 351356113HPX-036-230 (V) 34,600 13.50 11.50 34,400 22,200 7.45 CH33-44/48 G60UHV-36B-090 351356213HPX-036-230 (V) 34,200 13.00 11.00 34,800 22,600 7.35 CH33-44/48 G61MPV-36B-045 351356313HPX-036-230 (V) 34,200 13.00 11.00 34,600 22,400 7.35 CH33-44/48 G61MPV-36B-070 351356413HPX-036-230 (V) 34,200 13.00 11.00 34,600 22,400 7.35 CH33-44/48 G61MPV-36B-071 351356513HPX-036-230 (V) 34,200 13.00 11.00 34,600 22,400 7.35 CH33-44/48 G71MPP-36B-070 351356613HPX-036-230 (V) 34,600 14.00 11.50 34,000 22,000 7.35 CH33-48 G61MPV-36C-090 351356713HPX-036-230 (V) 34,600 14.00 11.50 34,000 22,000 7.35 CH33-48 G71MPP-36C-090 351358313HPX-036-230 (V) 33,600 13.50 11.00 34,400 22,200 7.55 CR33-30/36 G60DFV-36B-090 351358413HPX-036-230 (V) 33,400 13.00 10.95 34,600 22,400 7.45 CR33-30/36 G61MPV-36B-070 351358513HPX-036-230 (V) 33,400 13.00 10.95 34,800 22,400 7.45 CR33-30/36 G61MPV-36B-071 351358613HPX-036-230 (V) 33,600 13.50 11.00 34,400 22,200 7.55 CR33-30/36 G61MPV-36C-090 351358713HPX-036-230 (V) 33,400 13.00 10.95 34,600 22,400 7.45 CR33-30/36 G71MPP-36B-070 351358813HPX-036-230 (V) 33,600 13.50 11.00 34,400 22,200 7.55 CR33-30/36 G71MPP-36C-090 351358913HPX-036-230 (V) 34,200 14.00 11.50 34,200 22,000 7.50 CR33-48 G60DFV-36B-090 351359013HPX-036-230 (V) 34,000 13.00 11.00 34,800 22,600 7.40 CR33-48 G61MPV-36B-045 351359113HPX-036-230 (V) 34,000 13.00 11.00 34,400 22,400 7.40 CR33-48 G61MPV-36B-070 351359213HPX-036-230 (V) 34,000 13.00 11.00 34,400 22,400 7.40 CR33-48 G61MPV-36B-071 351354613HPX-036-230 (V) 34,200 13.50 11.50 34,200 22,000 7.50 CR33-48 G61MPV-36C-090 351354713HPX-036-230 (V) 34,000 13.00 11.00 34,400 22,400 7.40 CR33-48 G71MPP-36B-070 351354813HPX-036-230 (V) 34,200 13.50 11.50 34,200 22,000 7.50 CR33-48 G71MPP-36C-090 351354913HPX-036-230 (V) 34,600 13.50 11.00 34,800 22,400 7.65 CR33-50/60 G61MPV-36B-071 351355013HPX-036-230 (V) 35,000 14.00 11.50 34,400 22,200 7.75 CR33-50/60 G61MPV-36C-090 351356813HPX-036-230 (V) 35,000 14.00 11.50 34,400 22,200 7.75 CR33-50/60 G71MPP-36C-090 351356913HPX-036-230 (V) 33,400 13.50 11.00 34,200 22,000 7.40 CX34-36 G60UHV-36B-090 351357013HPX-036-230 (V) 33,400 13.50 11.00 34,000 22,000 7.35 CX34-36 G61MPV-36C-090 351357113HPX-036-230 (V) 33,400 13.50 11.00 34,000 22,000 7.35 CX34-36 G71MPP-36C-090 351357213HPX-036-230 (V) 34,400 13.50 11.00 34,400 22,400 7.30 CX34-38 G60UHV-36A-070 351357313HPX-036-230 (V) 34,800 14.00 11.50 34,200 22,000 7.45 CX34-38 G60UHV-36B-090 351357413HPX-036-230 (V) 34,400 13.00 11.00 34,600 22,400 7.30 CX34-38 G61MPV-36B-045 351357513HPX-036-230 (V) 34,400 13.50 11.00 34,400 22,200 7.30 CX34-38 G61MPV-36B-070 351357613HPX-036-230 (V) 34,200 13.50 11.00 34,400 22,200 7.30 CX34-38 G61MPV-36B-071 351357713HPX-036-230 (V) 34,400 13.50 11.00 34,400 22,200 7.30 CX34-38 G71MPP-36B-070 351357813HPX-036-230 (V) 33,400 13.50 11.00 34,200 22,000 7.40 CX34-42 G60UHV-36B-090 351357913HPX-036-230 (V) 34,400 14.00 11.50 34,000 22,000 7.20 CX34-44/48 G60UHV-36B-090 351358013HPX-036-230 (V) 34,400 13.50 11.50 33,800 21,800 7.15 CX34-44/48 G61MPV-36C-090 351358113HPX-036-230 (V) 34,400 13.50 11.50 33,800 21,800 7.15 CX34-44/48 G71MPP-36C-090 351358213HPX-042-230 (IV) 42,500 14.00 11.50 40,500 25,000 7.70 C33-43 G71MPP-60C-110 149014613HPX-042-230 (IV) 42,500 14.00 11.50 40,500 25,000 7.70 C33-43C G60UHV-60C-090 93123313HPX-042-230 (IV) 42,500 14.00 12.00 40,000 24,800 7.70 C33-43C G60UHV-60C-110 93105213HPX-042-230 (IV) 42,500 14.00 11.50 40,500 25,000 7.70 C33-43C G61MPV-60C-110 93124013HPX-042-230 (IV) 42,500 13.50 11.50 40,500 25,200 7.70 C33-49 G61MPV-60C-091 1051717

NOTES: Heat Pump suffixes: -230 (IV) = HSPF Region IV -230 (V) = HSPF Region V When used with gas furnaces, a dual-fuel control (i.e. FM21), a control system with dual-fuel capabilities (LZP-2 or LZP-4), or a thermostat with dual-fuel capabilities must be used (ordered extra). Certified in accordance with USE certification program which is based on AHRI Standard 210/240 with 25 ft. of connecting refrigerant lines; Cooling Ratings − 95°F outdoor air temperature and 80 °F db/67° F wb entering indoor coil air. High Temperature Heating Ratings − 47° F db/43° F wb outdoor air temperature and 70 °F db entering indoor coil air. Low Temperature Heating Ratings − 17 °F db/15° F wb outdoor air temperature and 70 °F db entering indoor coil air. All ratings include the use of a blower time delay relay (TDR). All Lennox variable-speed furnaces and Air Handlers have time delay capabilities. Other Furnaces and Air Handlers may require an optional time delay relay (58M81) for field installation. See furnace or air handler specifications to determine if relay is needed.*Most popular combination. Also see TXV Substitution Table.

Page 21: MERIT Series R-410A - LennoxPROs.com · MERIT® Series R-410A Bulletin No. 210460 December 2009 Supersedes November 2009 ENGINEERING DATA SEER up to 14.5 1.5 to 5 Tons Cooling Capacity

13HPX - 1.5 to 5 Ton Heat Pump / Page 21

AHRI SYSTEM MATCHESModelNo. Capacity SEER EER Heat Capacity HSPF Coil or

Air Handler Furnace AHRIReferenceHigh Low

13HPX-042-230 (IV) 42,500 14.00 11.50 40,500 25,000 7.70 C33-49 G61MPV-60C-111 105171813HPX-042-230 (IV) 42,500 14.00 11.50 40,500 25,200 7.70 C33-49 G71MPP-60C-090 148985813HPX-042-230 (IV) 42,500 14.00 11.50 40,500 25,000 7.70 C33-49 G71MPP-60C-110 149015013HPX-042-230 (IV) 43,000 14.00 11.50 40,500 25,000 7.70 C33-49C G60UHV-60C-090 93103413HPX-042-230 (IV) 42,500 14.00 11.50 40,500 25,000 7.70 C33-49C G60UHV-60C-110 93097213HPX-042-230 (IV) 42,500 14.00 11.50 40,500 25,200 7.70 C33-49C G61MPV-60C-090 93111413HPX-042-230 (IV) 42,500 14.00 11.50 40,500 25,000 7.70 C33-49C G61MPV-60C-110 93136913HPX-042-230 (IV) 42,000 14.00 12.00 40,000 24,600 7.70 C33-50/60C G60UHV-60C-090 93127813HPX-042-230 (IV) 42,000 14.00 11.50 40,000 24,800 7.70 C33-50/60C G60UHV-60C-110 93126513HPX-042-230 (IV) 41,500 13.50 11.00 41,500 25,600 8.00 CBX26UH-042 93137613HPX-042-230 (IV) 41,500 13.50 11.00 41,500 25,600 8.00 CBX26UH-048 93105413HPX-042-230 (IV) 42,500 14.00 12.00 41,000 25,400 8.20 CBX27UH-042-230 114521013HPX-042-230 (IV) 42,500 14.00 12.00 41,000 25,400 8.20 CBX27UH-048-230 114521113HPX-042-230 (IV) 41,500 13.50 11.00 41,500 25,600 8.00 CBX32M-036 93100713HPX-042-230 (IV) 41,500 13.00 11.00 41,500 25,600 8.00 CBX32M-042 93104713HPX-042-230 (IV) 41,500 13.00 11.00 41,500 25,600 8.00 CBX32MV-036 93116213HPX-042-230 (IV) 43,000 14.00 12.00 41,000 25,400 8.50 CBX32MV-048-230 103180513HPX-042-230 (IV) 41,500 13.00 11.00 41,500 25,600 8.00 CBX40UHV-036 329189913HPX-042-230 (IV) 42,500 14.00 12.00 41,000 25,400 8.20 CBX40UHV-042 329194213HPX-042-230 (IV) 43,000 14.00 12.00 41,000 25,400 8.50 CBX40UHV-048 329198013HPX-042-230 (IV) 42,500 14.00 11.50 40,500 25,000 7.70 CH33-48C G60UHV-60C-090 93139113HPX-042-230 (IV) 43,000 14.00 11.50 40,500 25,200 7.70 CH33-50/60C G60UHV-60C-090 93141413HPX-042-230 (IV) 42,500 14.00 11.50 40,500 25,000 7.70 CH33-50/60C G60UHV-60C-110 93096113HPX-042-230 (IV) 42,500 14.00 11.50 40,500 25,200 7.70 CH33-50/60C G61MPV-60C-090 93118213HPX-042-230 (IV) 42,500 13.50 11.50 40,500 25,200 7.70 CH33-50/60C G61MPV-60C-091 105170413HPX-042-230 (IV) 42,500 14.00 11.50 40,500 25,000 7.70 CH33-50/60C G61MPV-60C-110 93111613HPX-042-230 (IV) 42,500 14.00 11.50 40,500 25,000 7.70 CH33-50/60C G61MPV-60C-111 105170513HPX-042-230 (IV) 42,500 14.00 11.50 40,500 25,200 7.70 CH33-50/60C G71MPP-60C-090 148985913HPX-042-230 (IV) 42,500 14.00 11.50 40,500 25,000 7.70 CH33-50/60C G71MPP-60C-110 149013513HPX-042-230 (IV) 42,500 14.00 12.00 40,000 24,800 7.70 CH33-60D G60UHV-60D-135 93096813HPX-042-230 (IV) 42,500 14.00 12.00 40,000 24,800 7.70 CH33-60D G61MPV-60D-135 93133713HPX-042-230 (IV) 42,500 14.00 12.00 40,000 24,800 7.70 CH33-60D G71MPP-60D-135 149040413HPX-042-230 (IV) 41,500 13.50 11.50 41,000 25,200 7.70 CR33-48 G60DFV-36B-090 93114513HPX-042-230 (IV) 41,500 13.50 11.50 40,500 25,000 7.70 CR33-48 G60DFV-60C-090 93124913HPX-042-230 (IV) 41,500 14.00 11.50 40,500 25,200 7.70 CR33-48 G60DFV-60C-110 93098213HPX-042-230 (IV) 41,500 13.50 11.50 41,000 25,200 7.70 CR33-48 G61MPV-36B-070 93137113HPX-042-230 (IV) 41,500 13.50 11.50 41,000 25,200 7.70 CR33-48 G61MPV-36B-071 105348613HPX-042-230 (IV) 41,500 13.50 11.50 40,500 25,200 7.70 CR33-48 G61MPV-60C-090 93098613HPX-042-230 (IV) 41,500 13.50 11.00 40,500 25,400 7.70 CR33-48 G61MPV-60C-091 105170613HPX-042-230 (IV) 41,500 13.50 11.50 40,500 25,200 7.70 CR33-48 G61MPV-60C-110 93121713HPX-042-230 (IV) 41,500 13.50 11.50 40,500 25,200 7.70 CR33-48 G61MPV-60C-111 105170713HPX-042-230 (IV) 41,500 13.50 11.50 41,000 25,200 7.70 CR33-48 G71MPP-36B-070 148902513HPX-042-230 (IV) 41,500 13.50 11.50 40,500 25,200 7.70 CR33-48 G71MPP-60C-090 1489852

NOTES: Heat Pump suffixes: -230 (IV) = HSPF Region IV -230 (V) = HSPF Region V When used with gas furnaces, a dual-fuel control (i.e. FM21), a control system with dual-fuel capabilities (LZP-2 or LZP-4), or a thermostat with dual-fuel capabilities must be used (ordered extra). Certified in accordance with USE certification program which is based on AHRI Standard 210/240 with 25 ft. of connecting refrigerant lines; Cooling Ratings − 95°F outdoor air temperature and 80 °F db/67° F wb entering indoor coil air. High Temperature Heating Ratings − 47° F db/43° F wb outdoor air temperature and 70 °F db entering indoor coil air. Low Temperature Heating Ratings − 17 °F db/15° F wb outdoor air temperature and 70 °F db entering indoor coil air. All ratings include the use of a blower time delay relay (TDR). All Lennox variable-speed furnaces and Air Handlers have time delay capabilities. Other Furnaces and Air Handlers may require an optional time delay relay (58M81) for field installation. See furnace or air handler specifications to determine if relay is needed.*Most popular combination. Also see TXV Substitution Table.

Page 22: MERIT Series R-410A - LennoxPROs.com · MERIT® Series R-410A Bulletin No. 210460 December 2009 Supersedes November 2009 ENGINEERING DATA SEER up to 14.5 1.5 to 5 Tons Cooling Capacity

13HPX - 1.5 to 5 Ton Heat Pump / Page 22

AHRI SYSTEM MATCHESModelNo. Capacity SEER EER Heat Capacity HSPF Coil or

Air Handler Furnace AHRIReferenceHigh Low

13HPX-042-230 (IV) 41,500 13.50 11.50 40,500 25,200 7.70 CR33-48 G71MPP-60C-110 149014413HPX-042-230 (IV) 42,500 14.00 12.00 41,000 25,200 8.20 CR33-50/60 G60DFV-60C-090 93137513HPX-042-230 (IV) 42,500 14.00 11.50 41,500 25,400 8.20 CR33-50/60 G60DFV-60C-110 93133013HPX-042-230 (IV) 42,000 14.00 11.50 41,500 25,400 8.20 CR33-50/60 G61MPV-60C-090 93118813HPX-042-230 (IV) 42,000 13.50 11.50 41,500 25,600 8.20 CR33-50/60 G61MPV-60C-091 105170813HPX-042-230 (IV) 42,500 14.00 11.50 41,500 25,400 8.20 CR33-50/60 G61MPV-60C-110 93120513HPX-042-230 (IV) 42,500 14.00 11.50 41,500 25,400 8.20 CR33-50/60 G61MPV-60C-111 105170913HPX-042-230 (IV) 42,000 14.00 11.50 41,500 25,400 8.20 CR33-50/60 G71MPP-60C-090 148986013HPX-042-230 (IV) 42,500 14.00 11.50 41,500 25,400 8.20 CR33-50/60 G71MPP-60C-110 149014313HPX-042-230 (IV) 42,000 13.00 11.00 42,000 26,000 8.00 CR33-50/60 93125713HPX-042-230 (IV) 42,500 14.00 11.50 41,000 25,400 8.20 CR33-60 G60UHV-60D-135 93125813HPX-042-230 (IV) 42,500 14.00 11.50 41,000 25,200 8.20 CR33-60 G61MPV-60D-135 93103513HPX-042-230 (IV) 42,500 14.00 11.50 41,000 25,200 8.20 CR33-60 G71MPP-60D-135 149039613HPX-042-230 (IV) 42,000 13.00 11.00 42,000 26,000 8.00 CR33-60 93112413HPX-042-230 (IV) 42,500 14.00 11.50 40,500 25,000 7.70 CX34-43 G71MPP-60C-110 149013113HPX-042-230 (IV) 42,500 14.00 11.50 40,500 25,000 7.70 CX34-43C G60UHV-60C-090 93112013HPX-042-230 (IV) 42,500 14.00 12.00 40,000 24,800 7.70 CX34-43C G60UHV-60C-110 93102113HPX-042-230 (IV) 42,500 14.00 11.50 40,500 25,000 7.70 CX34-43C G61MPV-60C-110 93099313HPX-042-230 (IV) 42,500 13.50 11.50 40,500 25,200 7.70 CX34-49 G61MPV-60C-091 105171013HPX-042-230 (IV) 42,500 14.00 11.50 40,500 25,000 7.70 CX34-49 G61MPV-60C-111 105171113HPX-042-230 (IV) 42,500 14.00 11.50 40,500 25,200 7.70 CX34-49 G71MPP-60C-090 148985313HPX-042-230 (IV) 42,500 14.00 11.50 40,500 25,000 7.70 CX34-49 G71MPP-60C-110 149013213HPX-042-230 (IV) 43,000 14.00 11.50 40,500 25,000 7.70 CX34-49C G60UHV-60C-090 93097013HPX-042-230 (IV) 42,500 14.00 11.50 40,500 25,000 7.70 CX34-49C G60UHV-60C-110 93108613HPX-042-230 (IV) 42,500 14.00 11.50 40,500 25,200 7.70 CX34-49C G61MPV-60C-090 93098913HPX-042-230 (IV) 42,500 14.00 11.50 40,500 25,000 7.70 CX34-49C G61MPV-60C-110 93101113HPX-042-230 (IV) 42,000 14.00 12.00 40,000 24,600 7.70 CX34-50/60C G60UHV-60C-090 93108013HPX-042-230 (IV) 42,000 14.00 11.50 40,000 24,800 7.70 CX34-50/60C G60UHV-60C-110 93098713HPX-042-230 (V) 42,500 14.00 11.50 40,500 25,000 6.70 C33-43 G71MPP-60C-110 149014213HPX-042-230 (V) 42,500 14.00 11.50 40,500 25,000 6.70 C33-43C G60UHV-60C-090 93112113HPX-042-230 (V) 42,500 14.00 12.00 40,000 24,800 6.70 C33-43C G60UHV-60C-110 93128113HPX-042-230 (V) 42,500 14.00 11.50 40,500 25,000 6.70 C33-43C G61MPV-60C-110 93120013HPX-042-230 (V) 42,500 14.00 11.50 40,500 25,200 6.70 C33-49 G71MPP-60C-090 148986313HPX-042-230 (V) 42,500 14.00 11.50 40,500 25,000 6.70 C33-49 G71MPP-60C-110 149014013HPX-042-230 (V) 43,000 14.00 11.50 40,500 25,000 6.70 C33-49C G60UHV-60C-090 93119213HPX-042-230 (V) 42,500 14.00 11.50 40,500 25,000 6.70 C33-49C G60UHV-60C-110 93113313HPX-042-230 (V) 42,500 14.00 11.50 40,500 25,200 6.70 C33-49C G61MPV-60C-090 93135913HPX-042-230 (V) 42,500 14.00 11.50 40,500 25,000 6.70 C33-49C G61MPV-60C-110 93118413HPX-042-230 (V) 42,000 14.00 12.00 40,000 24,600 6.70 C33-50/60C G60UHV-60C-090 93117513HPX-042-230 (V) 42,000 14.00 11.50 40,000 24,800 6.70 C33-50/60C G60UHV-60C-110 93124513HPX-042-230 (V) 41,500 13.50 11.00 41,500 25,600 7.00 CBX26UH-042 93118913HPX-042-230 (V) 41,500 13.50 11.00 41,500 25,600 6.70 CBX26UH-048 93125213HPX-042-230 (V) 41,500 13.50 11.00 41,500 25,600 6.70 CBX32M-036 931279

NOTES: Heat Pump suffixes: -230 (IV) = HSPF Region IV -230 (V) = HSPF Region V When used with gas furnaces, a dual-fuel control (i.e. FM21), a control system with dual-fuel capabilities (LZP-2 or LZP-4), or a thermostat with dual-fuel capabilities must be used (ordered extra). Certified in accordance with USE certification program which is based on AHRI Standard 210/240 with 25 ft. of connecting refrigerant lines; Cooling Ratings − 95°F outdoor air temperature and 80 °F db/67° F wb entering indoor coil air. High Temperature Heating Ratings − 47° F db/43° F wb outdoor air temperature and 70 °F db entering indoor coil air. Low Temperature Heating Ratings − 17 °F db/15° F wb outdoor air temperature and 70 °F db entering indoor coil air. All ratings include the use of a blower time delay relay (TDR). All Lennox variable-speed furnaces and Air Handlers have time delay capabilities. Other Furnaces and Air Handlers may require an optional time delay relay (58M81) for field installation. See furnace or air handler specifications to determine if relay is needed.*Most popular combination. Also see TXV Substitution Table.

Page 23: MERIT Series R-410A - LennoxPROs.com · MERIT® Series R-410A Bulletin No. 210460 December 2009 Supersedes November 2009 ENGINEERING DATA SEER up to 14.5 1.5 to 5 Tons Cooling Capacity

13HPX - 1.5 to 5 Ton Heat Pump / Page 23

AHRI SYSTEM MATCHESModelNo. Capacity SEER EER Heat Capacity HSPF Coil or

Air Handler Furnace AHRIReferenceHigh Low

13HPX-042-230 (V) 41,500 13.00 11.00 41,500 25,600 6.70 CBX32M-042 93126713HPX-042-230 (V) 41,500 13.00 11.00 41,500 25,600 6.70 CBX32MV-036 93101413HPX-042-230 (V) 43,000 14.00 12.00 41,000 25,400 7.30 CBX32MV-048-230 103180913HPX-042-230 (V) 43,000 14.00 12.00 41,000 25,400 7.30 CBX40UHV-048 329198113HPX-042-230 (V) 42,500 14.00 11.50 40,500 25,000 6.70 CH33-48C G60UHV-60C-090 93100213HPX-042-230 (V) 43,000 14.00 11.50 40,500 25,200 6.70 CH33-50/60C G60UHV-60C-090 93096713HPX-042-230 (V) 42,500 14.00 11.50 40,500 25,000 6.70 CH33-50/60C G60UHV-60C-110 93099413HPX-042-230 (V) 42,500 14.00 11.50 40,500 25,200 6.70 CH33-50/60C G61MPV-60C-090 93103213HPX-042-230 (V) 42,500 14.00 11.50 40,500 25,000 6.70 CH33-50/60C G61MPV-60C-110 93130613HPX-042-230 (V) 42,500 14.00 11.50 40,500 25,200 6.70 CH33-50/60C G71MPP-60C-090 148985513HPX-042-230 (V) 42,500 14.00 11.50 40,500 25,000 6.70 CH33-50/60C G71MPP-60C-110 149014813HPX-042-230 (V) 42,500 14.00 12.00 40,000 24,800 6.70 CH33-60D G60UHV-60D-135 93119613HPX-042-230 (V) 42,500 14.00 12.00 40,000 24,800 6.70 CH33-60D G61MPV-60D-135 93100413HPX-042-230 (V) 42,500 14.00 12.00 40,000 24,800 6.70 CH33-60D G71MPP-60D-135 149039313HPX-042-230 (V) 41,500 13.50 11.50 41,000 25,200 6.70 CR33-48 G60DFV-36B-090 93140413HPX-042-230 (V) 41,500 13.50 11.50 40,500 25,000 6.70 CR33-48 G60DFV-60C-090 93107413HPX-042-230 (V) 41,500 14.00 11.50 40,500 25,200 6.70 CR33-48 G60DFV-60C-110 93125513HPX-042-230 (V) 41,500 13.50 11.50 41,000 25,200 6.70 CR33-48 G61MPV-36B-070 93115613HPX-042-230 (V) 41,500 13.50 11.50 40,500 25,200 6.70 CR33-48 G61MPV-60C-090 93121313HPX-042-230 (V) 41,500 13.50 11.50 40,500 25,200 6.70 CR33-48 G61MPV-60C-110 93123613HPX-042-230 (V) 41,500 13.50 11.50 41,000 25,200 6.70 CR33-48 G71MPP-36B-070 148899513HPX-042-230 (V) 41,500 13.50 11.50 40,500 25,200 6.70 CR33-48 G71MPP-60C-090 148986113HPX-042-230 (V) 41,500 13.50 11.50 40,500 25,200 6.70 CR33-48 G71MPP-60C-110 149014513HPX-042-230 (V) 42,500 14.00 12.00 41,000 25,200 7.00 CR33-50/60 G60DFV-60C-090 93114013HPX-042-230 (V) 42,500 14.00 11.50 41,500 25,400 7.00 CR33-50/60 G60DFV-60C-110 93097413HPX-042-230 (V) 42,000 14.00 11.50 41,500 25,400 7.00 CR33-50/60 G61MPV-60C-090 93109013HPX-042-230 (V) 42,500 14.00 11.50 41,500 25,400 7.00 CR33-50/60 G61MPV-60C-110 93116013HPX-042-230 (V) 42,000 14.00 11.50 41,500 25,400 7.00 CR33-50/60 G71MPP-60C-090 148985613HPX-042-230 (V) 42,500 14.00 11.50 41,500 25,400 7.00 CR33-50/60 G71MPP-60C-110 149013713HPX-042-230 (V) 42,000 13.00 11.00 42,000 26,000 6.70 CR33-50/60 93133313HPX-042-230 (V) 42,500 14.00 11.50 41,000 25,400 7.00 CR33-60 G60UHV-60D-135 93110213HPX-042-230 (V) 42,500 14.00 11.50 41,000 25,200 7.00 CR33-60 G61MPV-60D-135 93137913HPX-042-230 (V) 42,500 14.00 11.50 41,000 25,200 7.00 CR33-60 G71MPP-60D-135 149040613HPX-042-230 (V) 42,000 13.00 11.00 42,000 26,000 6.70 CR33-60 93095613HPX-042-230 (V) 42,500 14.00 11.50 40,500 25,000 6.70 CX34-43 G71MPP-60C-110 149013413HPX-042-230 (V) 42,500 14.00 11.50 40,500 25,000 6.70 CX34-43C G60UHV-60C-090 93105013HPX-042-230 (V) 42,500 14.00 12.00 40,000 24,800 6.70 CX34-43C G60UHV-60C-110 93098513HPX-042-230 (V) 42,500 14.00 11.50 40,500 25,000 6.70 CX34-43C G61MPV-60C-110 93107813HPX-042-230 (V) 42,500 14.00 11.50 40,500 25,200 6.70 CX34-49 G71MPP-60C-090 148985713HPX-042-230 (V) 42,500 14.00 11.50 40,500 25,000 6.70 CX34-49 G71MPP-60C-110 149014113HPX-042-230 (V) 43,000 14.00 11.50 40,500 25,000 6.70 CX34-49C G60UHV-60C-090 93108413HPX-042-230 (V) 42,500 14.00 11.50 40,500 25,000 6.70 CX34-49C G60UHV-60C-110 93111013HPX-042-230 (V) 42,500 14.00 11.50 40,500 25,200 6.70 CX34-49C G61MPV-60C-090 931113

NOTES: Heat Pump suffixes: -230 (IV) = HSPF Region IV -230 (V) = HSPF Region V When used with gas furnaces, a dual-fuel control (i.e. FM21), a control system with dual-fuel capabilities (LZP-2 or LZP-4), or a thermostat with dual-fuel capabilities must be used (ordered extra). Certified in accordance with USE certification program which is based on AHRI Standard 210/240 with 25 ft. of connecting refrigerant lines; Cooling Ratings − 95°F outdoor air temperature and 80 °F db/67° F wb entering indoor coil air. High Temperature Heating Ratings − 47° F db/43° F wb outdoor air temperature and 70 °F db entering indoor coil air. Low Temperature Heating Ratings − 17 °F db/15° F wb outdoor air temperature and 70 °F db entering indoor coil air. All ratings include the use of a blower time delay relay (TDR). All Lennox variable-speed furnaces and Air Handlers have time delay capabilities. Other Furnaces and Air Handlers may require an optional time delay relay (58M81) for field installation. See furnace or air handler specifications to determine if relay is needed.*Most popular combination. Also see TXV Substitution Table.

Page 24: MERIT Series R-410A - LennoxPROs.com · MERIT® Series R-410A Bulletin No. 210460 December 2009 Supersedes November 2009 ENGINEERING DATA SEER up to 14.5 1.5 to 5 Tons Cooling Capacity

13HPX - 1.5 to 5 Ton Heat Pump / Page 24

AHRI SYSTEM MATCHESModelNo. Capacity SEER EER Heat Capacity HSPF Coil or

Air Handler Furnace AHRIReferenceHigh Low

13HPX-042-230 (V) 42,500 14.00 11.50 40,500 25,000 6.70 CX34-49C G61MPV-60C-110 93119713HPX-042-230 (V) 42,000 14.00 12.00 40,000 24,600 6.70 CX34-50/60C G60UHV-60C-090 93097813HPX-042-230 (V) 42,000 14.00 11.50 40,000 24,800 6.70 CX34-50/60C G60UHV-60C-110 93112913HPX-048-230 (IV) 48,000 13.00 11.00 45,000 29,200 7.70 C33-49 G61MPV-60C-111 105171913HPX-048-230 (IV) 48,000 13.00 11.00 45,000 29,200 7.70 C33-49 G71MPP-60C-110 149014913HPX-048-230 (IV) 48,500 13.50 11.00 45,000 29,200 7.70 C33-49C G60UHV-60C-090 93104813HPX-048-230 (IV) 48,000 13.50 11.00 45,000 29,000 7.70 C33-49C G60UHV-60C-110 93117213HPX-048-230 (IV) 48,000 13.00 11.00 45,000 29,200 7.70 C33-49C G61MPV-60C-110 93131513HPX-048-230 (IV) 48,000 13.50 11.00 44,500 29,000 7.70 C33-60D G60UHV-60D-135 93110713HPX-048-230 (IV) 48,000 13.50 11.00 45,000 29,200 7.70 C33-60D G61MPV-60D-135 93117813HPX-048-230 (IV) 48,000 13.50 11.00 45,000 29,200 7.70 C33-60D G71MPP-60D-135 149040013HPX-048-230 (IV) 48,000 13.00 11.00 45,500 29,400 8.00 CBX26UH-048 93123113HPX-048-230 (IV) 48,000 13.00 11.00 45,500 29,600 8.00 CBX26UH-060 93099713HPX-048-230 (IV) 47,500 13.50 11.00 45,500 29,200 8.20 CBX27UH-048-230 114521213HPX-048-230 (IV) 47,000 13.50 11.00 45,500 29,200 7.70 CBX27UH-060-230 114521313HPX-048-230 (IV) 47,000 13.00 10.85 46,000 29,800 8.00 CBX32M-048 93114113HPX-048-230 (IV) 47,000 13.00 10.80 46,000 29,800 8.00 CBX32M-060 109173713HPX-048-230 (IV) 47,500 13.50 11.00 45,500 29,400 8.00 CBX32MV-048 93121613HPX-048-230 (IV) 48,000 14.00 12.00 44,000 28,800 8.50 CBX32MV-060-230 103180613HPX-048-230 (IV) 47,500 13.50 11.00 45,500 29,400 8.00 CBX40UHV-048 329198213HPX-048-230 (IV) 48,000 14.00 12.00 44,000 28,800 8.50 CBX40UHV-060 329204513HPX-048-230 (IV) 48,000 13.50 11.00 45,000 29,400 7.70 CH33-50/60C G60UHV-60C-090 93136413HPX-048-230 (IV) 48,000 13.50 11.00 45,000 29,400 7.70 CH33-50/60C G60UHV-60C-110 93095213HPX-048-230 (IV) 48,000 13.00 11.00 45,500 29,400 7.70 CH33-50/60C G61MPV-60C-090 93125413HPX-048-230 (IV) 48,000 13.00 11.00 45,500 29,600 7.70 CH33-50/60C G61MPV-60C-091 105171213HPX-048-230 (IV) 48,000 13.00 11.00 45,500 29,400 7.70 CH33-50/60C G61MPV-60C-110 93112813HPX-048-230 (IV) 48,000 13.00 11.00 45,000 29,400 7.70 CH33-50/60C G61MPV-60C-111 105171313HPX-048-230 (IV) 48,000 13.00 11.00 45,500 29,400 7.70 CH33-50/60C G71MPP-60C-090 148986213HPX-048-230 (IV) 48,000 13.00 11.00 45,500 29,400 7.70 CH33-50/60C G71MPP-60C-110 149013613HPX-048-230 (IV) 47,500 13.50 11.00 44,500 29,000 7.70 CH33-60D G60UHV-60D-135 93106713HPX-048-230 (IV) 47,500 13.50 11.00 45,000 29,200 7.70 CH33-60D G61MPV-60D-135 93134113HPX-048-230 (IV) 47,500 13.50 11.00 45,000 29,200 7.70 CH33-60D G71MPP-60D-135 149040513HPX-048-230 (IV) 48,000 13.50 11.00 45,500 29,400 8.00 CR33-50/60 G60DFV-60C-090 93129213HPX-048-230 (IV) 48,000 13.50 11.00 45,500 29,400 8.00 CR33-50/60 G60DFV-60C-110 93121113HPX-048-230 (IV) 47,500 13.00 11.00 45,500 29,600 8.00 CR33-50/60 G61MPV-60C-090 93101313HPX-048-230 (IV) 47,500 13.00 10.90 45,500 29,800 7.70 CR33-50/60 G61MPV-60C-091 105171413HPX-048-230 (IV) 47,500 13.00 11.00 45,500 29,600 8.00 CR33-50/60 G61MPV-60C-110 93119013HPX-048-230 (IV) 47,500 13.00 11.00 45,500 29,400 8.00 CR33-50/60 G61MPV-60C-111 105171513HPX-048-230 (IV) 47,500 13.00 11.00 45,500 29,600 8.00 CR33-50/60 G71MPP-60C-090 148985413HPX-048-230 (IV) 48,000 13.50 11.00 45,500 29,400 7.70 CR33-60 G60DFV-60D-135 93116613HPX-048-230 (IV) 47,500 13.50 11.00 45,500 29,400 7.70 CR33-60 G61MPV-60D-135 93108713HPX-048-230 (IV) 47,500 13.50 11.00 45,500 29,400 7.70 CR33-60 G71MPP-60D-135 149039813HPX-048-230 (IV) 48,000 13.00 11.00 45,000 29,200 7.70 CX34-49 G61MPV-60C-111 1051716

NOTES: Heat Pump suffixes: -230 (IV) = HSPF Region IV -230 (V) = HSPF Region V When used with gas furnaces, a dual-fuel control (i.e. FM21), a control system with dual-fuel capabilities (LZP-2 or LZP-4), or a thermostat with dual-fuel capabilities must be used (ordered extra). Certified in accordance with USE certification program which is based on AHRI Standard 210/240 with 25 ft. of connecting refrigerant lines; Cooling Ratings − 95°F outdoor air temperature and 80 °F db/67° F wb entering indoor coil air. High Temperature Heating Ratings − 47° F db/43° F wb outdoor air temperature and 70 °F db entering indoor coil air. Low Temperature Heating Ratings − 17 °F db/15° F wb outdoor air temperature and 70 °F db entering indoor coil air. All ratings include the use of a blower time delay relay (TDR). All Lennox variable-speed furnaces and Air Handlers have time delay capabilities. Other Furnaces and Air Handlers may require an optional time delay relay (58M81) for field installation. See furnace or air handler specifications to determine if relay is needed.*Most popular combination. Also see TXV Substitution Table.

Page 25: MERIT Series R-410A - LennoxPROs.com · MERIT® Series R-410A Bulletin No. 210460 December 2009 Supersedes November 2009 ENGINEERING DATA SEER up to 14.5 1.5 to 5 Tons Cooling Capacity

13HPX - 1.5 to 5 Ton Heat Pump / Page 25

AHRI SYSTEM MATCHESModelNo. Capacity SEER EER Heat Capacity HSPF Coil or

Air Handler Furnace AHRIReferenceHigh Low

13HPX-048-230 (IV) 48,000 13.00 11.00 45,000 29,200 7.70 CX34-49 G71MPP-60C-110 149013813HPX-048-230 (IV) 48,500 13.50 11.00 45,000 29,200 7.70 CX34-49C G60UHV-60C-090 93138913HPX-048-230 (IV) 48,000 13.50 11.00 45,000 29,000 7.70 CX34-49C G60UHV-60C-110 93132013HPX-048-230 (IV) 48,000 13.00 11.00 45,000 29,200 7.70 CX34-49C G61MPV-60C-110 93116413HPX-048-230 (IV) 48,000 13.50 11.00 44,500 29,000 7.70 CX34-60D G60UHV-60D-135 93135113HPX-048-230 (IV) 48,000 13.50 11.00 45,000 29,200 7.70 CX34-60D G61MPV-60D-135 93119413HPX-048-230 (IV) 48,000 13.50 11.00 45,000 29,200 7.70 CX34-60D G71MPP-60D-135 149040113HPX-048-230 (V) 48,000 13.00 11.00 45,000 29,200 6.70 C33-49 G71MPP-60C-110 149014713HPX-048-230 (V) 48,500 13.50 11.00 45,000 29,200 6.70 C33-49C G60UHV-60C-090 93096313HPX-048-230 (V) 48,000 13.50 11.00 45,000 29,000 6.70 C33-49C G60UHV-60C-110 93103813HPX-048-230 (V) 48,000 13.00 11.00 45,000 29,200 6.70 C33-49C G61MPV-60C-110 93124613HPX-048-230 (V) 48,000 13.50 11.00 44,500 29,000 6.70 C33-60D G60UHV-60D-135 93113613HPX-048-230 (V) 48,000 13.50 11.00 45,000 29,200 6.70 C33-60D G61MPV-60D-135 93110113HPX-048-230 (V) 48,000 13.50 11.00 45,000 29,200 6.70 C33-60D G71MPP-60D-135 149039913HPX-048-230 (V) 48,000 13.00 11.00 45,500 29,400 6.70 CBX26UH-048 93132913HPX-048-230 (V) 48,000 13.00 11.00 45,500 29,600 7.00 CBX26UH-060 93137813HPX-048-230 (V) 47,000 13.00 10.85 46,000 29,800 7.00 CBX32M-048 93098313HPX-048-230 (V) 47,500 13.50 11.00 45,500 29,400 7.00 CBX32MV-048 93137713HPX-048-230 (V) 48,000 14.00 12.00 44,000 28,800 7.50 CBX32MV-060-230 103181013HPX-048-230 (V) 47,500 13.50 11.00 45,500 29,400 7.00 CBX40UHV-048 329198313HPX-048-230 (V) 48,000 14.00 12.00 44,000 28,800 7.50 CBX40UHV-060 329204613HPX-048-230 (V) 48,000 13.50 11.00 45,000 29,400 6.70 CH33-50/60C G60UHV-60C-090 93110413HPX-048-230 (V) 48,000 13.50 11.00 45,000 29,400 6.70 CH33-50/60C G60UHV-60C-110 93107513HPX-048-230 (V) 48,000 13.00 11.00 45,500 29,400 6.70 CH33-50/60C G61MPV-60C-090 93137413HPX-048-230 (V) 48,000 13.00 11.00 45,500 29,400 6.70 CH33-50/60C G61MPV-60C-110 93102813HPX-048-230 (V) 48,000 13.00 11.00 45,500 29,400 6.70 CH33-50/60C G71MPP-60C-090 148986413HPX-048-230 (V) 48,000 13.00 11.00 45,500 29,400 6.70 CH33-50/60C G71MPP-60C-110 149013313HPX-048-230 (V) 47,500 13.50 11.00 44,500 29,000 6.70 CH33-60D G60UHV-60D-135 93096213HPX-048-230 (V) 47,500 13.50 11.00 45,000 29,200 6.70 CH33-60D G61MPV-60D-135 93125313HPX-048-230 (V) 47,500 13.50 11.00 45,000 29,200 6.70 CH33-60D G71MPP-60D-135 149040213HPX-048-230 (V) 48,000 13.50 11.00 45,500 29,400 7.00 CR33-50/60 G60DFV-60C-090 93134813HPX-048-230 (V) 48,000 13.50 11.00 45,500 29,400 7.00 CR33-50/60 G60DFV-60C-110 93118713HPX-048-230 (V) 47,500 13.00 11.00 45,500 29,600 7.00 CR33-50/60 G61MPV-60C-090 93096513HPX-048-230 (V) 47,500 13.00 11.00 45,500 29,600 7.00 CR33-50/60 G61MPV-60C-110 93116913HPX-048-230 (V) 47,500 13.00 11.00 45,500 29,600 7.00 CR33-50/60 G71MPP-60C-090 148985113HPX-048-230 (V) 47,500 13.00 11.00 45,500 29,600 7.00 CR33-50/60 G71MPP-60C-110 149013913HPX-048-230 (V) 48,000 13.50 11.00 45,500 29,400 6.70 CR33-60 G60DFV-60D-135 93140713HPX-048-230 (V) 47,500 13.50 11.00 45,500 29,400 6.70 CR33-60 G61MPV-60D-135 93103113HPX-048-230 (V) 47,500 13.50 11.00 45,500 29,400 6.70 CR33-60 G71MPP-60D-135 149039513HPX-048-230 (V) 48,000 13.00 11.00 45,000 29,200 6.70 CX34-49 G71MPP-60C-110 149013013HPX-048-230 (V) 48,500 13.50 11.00 45,000 29,200 6.70 CX34-49C G60UHV-60C-090 93104613HPX-048-230 (V) 48,000 13.50 11.00 45,000 29,000 6.70 CX34-49C G60UHV-60C-110 93138413HPX-048-230 (V) 48,000 13.00 11.00 45,000 29,200 6.70 CX34-49C G61MPV-60C-110 930951

NOTES: Heat Pump suffixes: -230 (IV) = HSPF Region IV -230 (V) = HSPF Region V When used with gas furnaces, a dual-fuel control (i.e. FM21), a control system with dual-fuel capabilities (LZP-2 or LZP-4), or a thermostat with dual-fuel capabilities must be used (ordered extra). Certified in accordance with USE certification program which is based on AHRI Standard 210/240 with 25 ft. of connecting refrigerant lines; Cooling Ratings − 95°F outdoor air temperature and 80 °F db/67° F wb entering indoor coil air. High Temperature Heating Ratings − 47° F db/43° F wb outdoor air temperature and 70 °F db entering indoor coil air. Low Temperature Heating Ratings − 17 °F db/15° F wb outdoor air temperature and 70 °F db entering indoor coil air. All ratings include the use of a blower time delay relay (TDR). All Lennox variable-speed furnaces and Air Handlers have time delay capabilities. Other Furnaces and Air Handlers may require an optional time delay relay (58M81) for field installation. See furnace or air handler specifications to determine if relay is needed.*Most popular combination. Also see TXV Substitution Table.

Page 26: MERIT Series R-410A - LennoxPROs.com · MERIT® Series R-410A Bulletin No. 210460 December 2009 Supersedes November 2009 ENGINEERING DATA SEER up to 14.5 1.5 to 5 Tons Cooling Capacity

13HPX - 1.5 to 5 Ton Heat Pump / Page 26

AHRI SYSTEM MATCHESModelNo. Capacity SEER EER Heat Capacity HSPF Coil or

Air Handler Furnace AHRIReferenceHigh Low

13HPX-048-230 (V) 48,000 13.50 11.00 44,500 29,000 6.70 CX34-60D G60UHV-60D-135 93140513HPX-048-230 (V) 48,000 13.50 11.00 45,000 29,200 6.70 CX34-60D G61MPV-60D-135 93131013HPX-048-230 (V) 48,000 13.50 11.00 45,000 29,200 6.70 CX34-60D G71MPP-60D-135 149040313HPX-060-230 (IV) 58,500 13.50 11.00 56,000 36,400 7.70 C33-62D G60UHV-60D-135 351368113HPX-060-230 (IV) 58,500 13.00 11.00 56,500 36,800 7.70 C33-62D G61MPV-60D-135 351368213HPX-060-230 (IV) 58,500 13.00 11.00 56,500 36,800 7.70 C33-62D G71MPP-60D-135 351368313HPX-060-230 (IV) 58,500 13.00 11.00 57,000 37,000 8.00 CBX26UH-060 351352113HPX-060-230 (IV) 57,500 13.00 10.90 57,000 37,000 8.20 CBX27UH-060-230 351368613HPX-060-230 (IV) 58,000 13.00 10.95 57,000 37,000 8.00 CBX32MV-060 351368713HPX-060-230 (IV) 57,500 13.00 11.00 56,000 36,600 7.70 CBX32MV-068 351368813HPX-060-230 (IV) 58,000 13.00 11.00 57,000 37,000 8.00 CBX40UHV-060 351368913HPX-060-230 (IV) 58,000 13.00 11.00 56,500 36,800 7.70 CH33-60D G60UHV-60D-135 351369013HPX-060-230 (IV) 59,000 13.00 11.00 56,500 36,800 7.70 CH33-62D G60UHV-60D-135 351369113HPX-060-230 (IV) 58,500 13.50 11.00 56,000 36,400 7.70 CX34-62D G60UHV-60D-135 351369213HPX-060-230 (IV) 58,500 13.00 11.00 56,500 36,800 7.70 CX34-62D G61MPV-60D-135 351369313HPX-060-230 (IV) 58,500 13.00 11.00 56,500 36,800 7.70 CX34-62D G71MPP-60D-135 351369413HPX-060-230 (V) 58,500 13.50 11.00 56,000 36,400 7.05 C33-62D G60UHV-60D-135 351366613HPX-060-230 (V) 58,500 13.00 11.00 56,500 36,800 7.00 C33-62D G61MPV-60D-135 351366713HPX-060-230 (V) 58,500 13.00 11.00 56,500 36,800 7.00 C33-62D G71MPP-60D-135 351366813HPX-060-230 (V) 58,500 13.00 11.00 57,000 37,000 7.25 CBX26UH-060 351352013HPX-060-230 (V) 57,500 13.00 10.90 57,000 37,000 7.35 CBX27UH-060-230 351367113HPX-060-230 (V) 58,000 13.00 10.95 57,000 37,000 7.25 CBX32MV-060 351367213HPX-060-230 (V) 57,500 13.00 11.00 56,000 36,600 7.10 CBX32MV-068 351367313HPX-060-230 (V) 58,000 13.00 11.00 57,000 37,000 7.25 CBX40UHV-060 351367413HPX-060-230 (V) 58,000 13.00 11.00 56,500 36,800 7.05 CH33-60D G60UHV-60D-135 351367513HPX-060-230 (V) 59,000 13.00 11.00 56,500 36,800 7.05 CH33-62D G60UHV-60D-135 351367613HPX-060-230 (V) 58,500 13.50 11.00 56,000 36,400 7.05 CX34-62D G60UHV-60D-135 351367713HPX-060-230 (V) 58,500 13.00 11.00 56,500 36,800 7.00 CX34-62D G61MPV-60D-135 351367813HPX-060-230 (V) 58,500 13.00 11.00 56,500 36,800 7.00 CX34-62D G71MPP-60D-135 3513680

NOTES: Heat Pump suffixes: -230 (IV) = HSPF Region IV -230 (V) = HSPF Region V When used with gas furnaces, a dual-fuel control (i.e. FM21), a control system with dual-fuel capabilities (LZP-2 or LZP-4), or a thermostat with dual-fuel capabilities must be used (ordered extra). Certified in accordance with USE certification program which is based on AHRI Standard 210/240 with 25 ft. of connecting refrigerant lines; Cooling Ratings − 95°F outdoor air temperature and 80 °F db/67° F wb entering indoor coil air. High Temperature Heating Ratings − 47° F db/43° F wb outdoor air temperature and 70 °F db entering indoor coil air. Low Temperature Heating Ratings − 17 °F db/15° F wb outdoor air temperature and 70 °F db entering indoor coil air. All ratings include the use of a blower time delay relay (TDR). All Lennox variable-speed furnaces and Air Handlers have time delay capabilities. Other Furnaces and Air Handlers may require an optional time delay relay (58M81) for field installation. See furnace or air handler specifications to determine if relay is needed.*Most popular combination. Also see TXV Substitution Table.

Page 27: MERIT Series R-410A - LennoxPROs.com · MERIT® Series R-410A Bulletin No. 210460 December 2009 Supersedes November 2009 ENGINEERING DATA SEER up to 14.5 1.5 to 5 Tons Cooling Capacity
Page 28: MERIT Series R-410A - LennoxPROs.com · MERIT® Series R-410A Bulletin No. 210460 December 2009 Supersedes November 2009 ENGINEERING DATA SEER up to 14.5 1.5 to 5 Tons Cooling Capacity

NOTE - Due to Lennox’ ongoing commitment to quality, Specifications, Ratings and Dimensions subject to change without notice and without incurring liability. Improper installation, adjustment, alteration, service or maintenance can cause property damage or personal injury. Installation and service must be performed by a qualified installer and servicing agency. ©2009 Lennox Industries, Inc.

Visit us at www.lennox.com

For the latest technical information, www.lennoxdavenet.com

Contact us at 1-800-4-LENNOX

REVISIONS

Specifications Updated electrical data for -018-024-030-036-048-060

AHRI System Matches Updated all.