40
Superior Series MCCB current limiting moulded case circuit breaker LK-Electric Company

MCCB

Embed Size (px)

DESCRIPTION

Circuit Breaker

Citation preview

  • Superior Series MCCBcurrent limitingmoulded case circuit breaker

    LK-Electric Company

  • 1The acronym LKE stands for Lauritz Knudsen Electric. In the late 1970s, the LKElectric Company was established in Singapore by its parent company, LKE(Europe) of Denmark. It is to manufacture LKs range of products, namely, theDomino, the Tabular of low tension switchboards, the ELC-24 medium voltagepanel and the Ring Main Unit (RMU).

    By the mid-80s, with an influx of technology from Denmark, a ComponentsDivision was set up. This was also to cater to the growing demands in the lowvoltage sector. Popular products such as the Switch Fuse of the QSA series,Miniature Circuit Breakers (MCB), Moulded Case Circuit Breakers (MCCB),Load Break Switches (LKs ELC-24) and Vacuum Circuit Breakers (LKs VB-1)were all produced in the Singapore factory.

    In 1992, the LKE Electric Company was established in Malaysia and by1994, has offices in Zhuhai, Shanghai and Beijing in China. At the same time,LKE Electric entered into a partnership with the Cubic Modular System A/Scompany of Denmark to produce the Cubic Modular Switchboard. And sincethen, there is no looking back for the company.

    The company is always striving to benefit its customers. Efforts in R&D areconstantly focused, especially with the current era of modern technology, toenable its products to be of a higher quality and safer, yet at the same time,aesthetically pleasing and affordable. The company also prides itself withupgrading of its production facilities, in keeping up with technology, to fulfillstringent process and quality control requirements. Building a relationship withthe customers and understanding their needs with a zero-defect andunbeatable range of products are the main objectives of LKE Electric.

    Focusing on these objectives, LKE Electric has become an industry leaderwith its MCCB Superior Series, 6 & 10kA MCB series, 12kV Load Break Switch(LBS) and Vacuum Load Break Switch (VLBS) and SF6 Breakers.

    The History of LKE Electric

  • 2LKE Electrics Superior Series Current Limiting MCCB was developed with thelatest technology for heavy duty usage: a magnetic trip unit for reliable qualitytripping when short circuit occurs, repulse force for moving and fix contactconstruction, zero arc distance for the arc chute moulded in with thread nut for thecase and cover and a long lasting BMC material for mounting, super mechanicaland electrical strength.

    ApplicationThe current limiting MCCB Superior series is suitable for circuit protection in

    individual enclosures, switchboards, lighting and power panels as well as motor-control centers. The MCCB is designed to protect systems against overload andshort circuits up to 65kA with the full range of accessories.

    MechanismThe MCCB Superior series is designed to be trip-free. This applies when the

    breaker contacts open under overload and short circuit conditions and even if thebreaker handle is held at the ON position. To eliminate single phasing, should anoverload or short circuit occur on any one phase, a common trip mechanism willdisconnect all phase contacts of a multipole breaker.

    MaterialThe Superior series circuit breakers housing is made of BMC material, which

    is unbreakable and has a very high dielectric strength, to ensure the highest levelof insulation. The same material is also used to segregate the live parts in betweenthe phases.

    AccessoriesTo enhance the Superior series MCCB, internal and external modules can be

    fitted onto the breaker. They are as follows: shunt trip coil undervoltage release auxiliary switch alarm switch motorized switch rotary handle plug-in kit (draw-out unit) auxiliary & alarm switch

    International StandardsThe MCCB Superior series conform and meet the requirements of these

    international governing bodies: IEC 60947-2 from the International Electrotechnical Committee BS EN60947-2 from British Standards BT/T14048-2 from China NEMA AB-1 from American Standards VDE 0660 from Germany.

    Superior Series Current Limiting MCCB

    NEMA

  • Having undergone rigid testings and achievingaccreditation from SIRIM QAS of Malaysia andTILVA from China, these test reports affirm thesuperior quality of LKE Electric CompanysCurrent Limiting Superior Series MCCB.

    Accreditation of the SuperiorSeries MCCB

    3

  • 4The MCCB Superior series has exceptional performance characteristics at the

    rated breaking current of 50KA. This includes:

    Limiting short-circuit current, lp, to 106KA (maximum peak let-through

    current)

    Interrupting fault current, Ic, 50.7KA at 436V

    Breaking time of approximately 0.00949 seconds

    Arc-quenching time at approximately 0.0066 seconds.

    As a result, the peak short circuit current (lp) is limited to the cut-

    off current (Ic). This leads to a substantial reduction in electrodynamic

    stresses in the overall system. l2 let-through (proportional to the

    shaded area) is considerably reduced, resulting in lower thermal

    stresses in down-stream equipment and connecting cables.

    Exceptional Current LimitingQuick-Breaking Performance

    Testing Current Wave Curve

  • 5Features1 BMC material for

    base and cover

    2 Arc chute

    3 Mounting for ST or

    UVT connection block

    4 Trip-free mechanism

    5 Moving contacts

    6 Clear and IEC-

    compliant markings

    7 Magnetic trip unit

    8 Thermal trip unit

    9 Compact size

    Featuresa Arching chamber

    b BMC

    c Handle

    d Magnetic trip unit

    e BMC

    f Tripping mechanism

    g Moving contact

    h Fixed contact

    i Thread nut

    2

    1

    6

    8

    7

    43

    5

    9

    cdba

    h g f e

    i

    The Superior Series MCCBan in-depth look

  • MCCB Arc Chamber (diagram 1)The MCCB arc chamber is specially designed with an arc channel as a

    flow guide to improve the capability of extinguishing the arc and reducing thearc distance.

    MCCB Base (diagram 2)Mounting screws are used to insert thread nuts in the MCCB base. The

    cover can withstand high electromagnetic force during a short-circuit; thisprevents the MCCB cover from tearing off. This is an improvement over self-taping screw of other models.

    Fixed Contact (diagram 3)The MCCB fixed contact does not have any mounting screws near the

    contact points. A steel screw can generate heat and the magnetic fluxsurrounding the conductor carrying the current can create a very hightemperature. If a short-circuit occurs, it will cause the contact points to bewelded or melted.

    Materials (diagram 4)The base and cover of the MCCB are made of a specially formulated

    material, i.e. bold moulded compound (BMC). It has a high-impact thermalstrength, fire resistant and capable of withstanding high electromagneticforces that occur during a short-circuit. Majority MCCB manufacturers in themarket use pheonolic compounds with less electrical and mechanicalstrength.

    Repulsive Force (diagram 5)An electromagnetic repulsive force is where the force works between a

    current of the movable conductor and a current (I) in the reversed directionof the fixed conductor. This is an improvement of the electromagnetic forceduring breaking over other models.

    The Technology of Tripping Devices

    Diagram 1

    Diagram 2

    Diagram 5 Diagram 4 Diagram 3

    6

  • 7Thermal Magnetic Type (Solenoid)

    MCCB Superior Series, all models

    Time-Delay Operation

    Time-delay operation occurs when an overcurrent heats and warps the bimetal

    to actuate the trip bar.

    Instantaneous Operation

    If the overcurrent is excessive and the magnetization of the solenoid coil

    strong enough to attract the armature, an instantaneous operation will

    actuate the trip bar.

    Hydraulic Magnetic Type

    MCCB Superior Series, selected models only

    Time-Delay Operation

    In an overcurrent flow situation, the magnetic force of the coil overcomes the

    spring and closes to the pole piece, thereby attracting the armature and

    actuates the trip bar. The delay is obtained by the viscosity of silicon oil.

    Instantaneous Operation

    If the overcurrent is excessive, the armature is instantly attracted without the

    influence of the moving core.

    The Technology of Tripping Devices

    Thermal magnetic tripping

    (available for all models)

    Hydraulic magnetic tripping

    (available for LKS-63 C and S

    and LKS-100 C models only )

  • 1.30 In (heated state) Operative Time (hr)1.05 In (cold state) Operative Time (hr)

    Thermodynamic Release Ambient Temperature; land +40C, marine +45C

    63 < In 100

    Operating Current forMagnetic Release (A)

    Table

    A

    Thermodynamic Release Ambient Temperature; land +40C, marine +45C

    1.05 In (cold state) Operative Time (h) 1.30 In (heated state) Operative Time (h)

    100 In 800

    630 In 800

    10 In 63 1

    2

    2

    2

    1

    2

    2

    2

    10In + 20%

    10In + 20%

    5In + 20%10In + 20%

    8In + 20%

    Rated Current (A)

    Operating Current forMagnetic Release (A)

    Table

    B

    10 In 63 2 2 12In + 20%

    Rated Current (A)

    Bi-metal Overload Tripping

    Bi-metal overloads are designed to protect the motor against overheating due

    to excessive current loading and at the same time, allow full utilization of its rating.

    To date, LKE designs MCCB according to the international standards (see below).

    These thermomagnetic overcurrent releases (bi-metal) are non-interchangeable

    thermomagnetic devises. They incorporate heat sensitive elements for protection

    against overcurrent and the rated current of the releases (Ith) must be equal to or

    greater than the operating current of the circuit breaker.

    Inverse Time Delay Tripping

    The thermodynamic release of LKEs circuit breaker affects the inverse time

    delay tripping, while the magnetic release affects an instantaneous tripping. It is

    shown in Table A (distribution circuit breaker) and Table B (motor protection circuit

    breakers).

    Tripping Characteristics

    Multiple of Set Current (A)

    1.05 (In > 63)

    1.05 (In < 63)

    > 2h

    > 1hour

    cold

    cold

    < 1hour warm

    < 2hour warm

    1.30 (In < 63)

    1.30 (In > 63)

    Tripping Time Operating Condition

    8

  • 9Further adjustments are unnecessary or allowed for the circuit breaker or its

    accessories during service as their settings have been fine tuned by LKE Electric.

    The handle of the circuit breaker has three positions which will indicate when

    the breaker is closed, opened or tripped respectively. When the handle is at the trip

    position, it must be pulled backward first so as to reset the breaker and be ready

    for closure.

    If the security seal of the circuit breaker is kept intact for 24 months from the

    delivery date, and instructions are followed for its storage and maintenance, any

    inherently defective product will be repaired and/or replaced at no further expense

    to the customer.

    Recommended Tightening Torque of the MCCB Terminal Screws

    Installation and Fittings

    Terminal Screw

    Pan head screw M8

    Pan head screw M5

    4.9 - 6.9

    2.3 - 3.4

    7.8 - 12.7

    13.7 - 22.5

    18.6 - 31.4

    22.5 - 37.2

    40.2 - 65.7

    Hex. socket head screw M8

    Hex. socket head screw M10

    Hex. socket head screw M11

    Hex. socket head screw M10 c/w terminal bar

    Hex. socket head screw M12 c/w terminal bar

    Tightening Torque (Nm)

    Preferred Conductor Sizewith Preference to Current Rating

    Current Range (A) Conductor Size (sq. mm)

    8

    12

    20

    25

    32

    50

    65

    85

    100

    130

    150

    175

    200

    225

    250

    275

    300

    350

    400

    1

    1.5

    2.5

    4

    6

    10

    16

    25

    35

    50

    50

    70

    95

    95

    120

    150

    185

    185

    240

    Copper Bar Dimensions forCurrents above 400A

    Rated Current (A)

    Copper Bars

    Dimension (mm)Number

    400

    500

    630

    800

    1000

    1250

    2 30 x 5

    40 x 5

    50 x 5

    60 x 5

    80 x 5

    100 x 5

    2

    2

    2

    2

    2

  • Arc Quenching Distance A & B (mm)Model Code

    LKS-100S LKS-100H LKS-225CLKS-225N

    LKS-225SLKS-225H LKS-400C

    LKS-400SLKS-400HLKS-600SLKS-600HLKS-800SLKS-800H

    LKS-63C 15

    20

    50

    60

    100

    LKS-63SLKS-100CLKS-100N

    Side view Front view

    measurements are in millimeter (mm)

    Arc Quenching Distance

    Due to the unique design of the arc chute with an Arc Top Plate, the arc quenching

    level is very low compared to other conventional models.

    10

  • 11

    It is very important to select and apply the right MCCB for a long lasting and

    trouble-free operation in a power system. The right selection requires a detailed

    understanding of the complete system and other influencing factors. The factors

    for selecting a MCCB are as follows:

    1 ) nominal current rating of the MCCB 2 ) fault current Icu, Ics

    3 ) other accessories required 4 ) number of poles

    Nominal Current

    To determine the nominal current of a MCCB, it is dependent on the full load

    current rating of the load and the scope of load enhancement in future.

    Fault Current Icu, Ics

    It is essential to calculate precisely the fault current that the MCCB will have to

    clear for a healthy and trouble-free life of the system down stream. The level of fault

    current at a specific point in a power system depends on following factors:

    a ) transformer size in KVA and the impedance

    b ) type of supply system

    c ) the distance between the transformer and the fault location

    d ) size and material of conductors and devices in between the transformer

    and the fault location

    e ) the impedance up to the fault junction.

    One can safely use an empirical formula, assuming a 5% impedance of the

    transformer, to arrive at the projected fault level at transformer terminals of the

    secondary side. This means that the projected fault current will be approximately

    20 times the full load current of the transformer. The impedance of the cables and

    devices up to MCCB further reduce the fault current.

    Icu: ultimate short circuit breaking capacity whereby the prescribed conditions

    according to a specified test sequence does not include the capability of

    the circuit breaker to carry its rated current continuously.

    Ics: service short circuit breaking capacity whereby the prescribed conditions

    according to a specified test sequence includes the capability of the circuit

    breaker to carry its rated current continuously.

    Other Accessories Required

    The selection of other accessories required will depend on the control and

    indications as required. The range available are as follows:

    a ) Under voltage release b ) Shunt-trip release

    c ) Auxiliary contact d ) Trip alarm contact

    e ) Rotary operating mechanism f ) Motor operating mechanism

    g ) Insulation barrier h ) Plug-in kit

    How to select a proper MCCB for protection

  • LKS-100C

    LKS-63S

    60

    12

    LKS-100N

    10

    Symmetrical 5 15 18 35 50 65

    Interrupting Capacity (kA)415V AC

    Bre

    aker

    Rate

    d C

    urr

    ent

    (A)

    Quick & Wide Selection Guide

    LKS-800H

    LKS-600H

    LKS-400H

    LKS-225H

    LKS-100H

    LKS-800S

    LKS-600S

    LKS-400S

    LKS-225S

    LKS-100S

    LKS-225C LKS-225N

    15

    20

    30

    40

    50

    75

    100

    125

    150

    160

    180

    200

    225

    250

    300

    315

    400

    500

    600

    700

    800

    The Superior series current limiting MCCB is available in 8 frame sizes, with ratings from 10A to 800A. Each

    frame size offers several interrupting capacities (Icu), up to 65kA, at AC 415V. Available in C, N, S and H

    configurations for various breaking capacity, the space-saving current limiting MCCB Superior series provides

    greater design flexibility than before. The C and N configurations are for general use in a general circuit. A best-

    seller worldwide, the C and N ranges from 60A to 800A in frame sizes. Also for general usage, the S and H

    configurations have a higher interrupting capacity, from 15A to 800A in frame sizes, is actually an upgrade from

    the C and N range.

    LKS-63C

  • 13

    68

    Model Code

    Ele

    ctr

    ical

    Chara

    cte

    rist

    ics

    AF Frame Size

    Ui

    P

    n

    Icu

    Rated Insulation Voltage(V), 50 Hz

    Poles

    OperationalPerformance

    Capability

    Rated Ultimate Short Circuit

    Breaking Capacity(kA)

    415V

    240V

    MC

    CB

    E

    lect

    rical

    & M

    echa

    nica

    l Fea

    ture

    sO

    verc

    urr

    ent

    Rele

    ase

    s

    Rated Service Short Circuit

    Breaking Capacity(kA)

    Adjustable Thermal & Magnetic Trip Unit

    Test Trip Button

    Weight (3 pole)

    Mechanic

    al

    Chara

    cte

    rist

    ics

    kg

    mm

    a

    b

    Ics

    a

    bc

    C N S H

    100

    690

    415

    3

    1500

    8500

    15, 20, 30, 40, 50, 60, 75, 100

    18 35 50 65

    35 70 100 130

    9 18 25 33

    18 35 50 65

    available

    available

    1.6

    90

    155

    LKS-100

    C S

    63

    690

    415

    3

    1000

    8500

    10,15, 20, 30, 40, 50, 63

    5 15

    10 30

    3 8

    6 15

    available

    available

    0.9

    75

    130

    68

    LKS-63

    A Rated Current at 40 C

    withcurrent

    w/ocurrent

    415V

    240V

    Ue Rated Voltage (V), 50 Hz

    c

    c

    Thermal & FixedMagnetic Trip Unit

  • 14

    86

    S H

    800

    690

    415

    3

    500

    2500

    700, 800

    50 65

    100 130

    25 33

    50 65

    available

    available

    available

    10.5

    210

    275

    103

    LKS-800

    S H

    600

    690

    415

    3

    1000

    4000

    500, 600

    50 65

    100 130

    25 33

    50 65

    available

    available

    available

    9.5

    210

    275

    103

    LKS-600

    S H

    400

    690

    415

    3

    1000

    4000

    250, 315, 350, 400

    50 65

    100 130

    25 33

    50 65

    available

    available

    6

    140

    257

    103

    LKS-400

    C N S H

    225

    690

    415

    3

    1000

    7000

    125, 160, 180, 200, 225

    18 35 50 65

    35 70 100 130

    9 18 25 33

    18 35 50 65

    available

    available

    3.5

    105

    165

    LKS-225

  • 15

    LKS-600 S, H

    LKS-400 S, H

    LKS-800 S, H

    LKS-225 C, N, S, H

    LKS-100 C, N, S, HLKS-63 C, S

    Outline Dimensions of the MCCB

  • LKS-63 C, S LKS-100 C, N, S, H

    Operating Characteristics & Ambient Compensation

    LKS-225 C, N, S, H

    LKS-600 S, H

    LKS-400 S, H

    LKS-800 S, H

    16

  • 17

    Auxiliary Contact (AUX)

    The auxiliary contact is used for remote signalling and control purposes. This

    consists of one or more than one potential free change-over contacts. It also acts

    as an indicator whether the circuit breakers status is opened or closed.

    Configurations: 1NO + 1NC

    2NO + 2NC

    Undervoltage Release (UVT)

    The undervoltage release is used to trip the MCCB when there is a drop in

    voltage. The UVT can also be used for remote tripping and electrical interlocking

    purposes. The tripping threshold is 35% to 70% of the rated voltage. Pick-up

    voltage is 85% of the rated coil voltage. The operating voltage is AC 220V or

    380V at 50/60Hz.

    Shunt Trip (ST)

    The shunt release is used for remote tripping of the MCCB under abnormal

    conditions. The operating voltage is 70% to 110% of the rated voltage.

    Alarm Switch (AS)

    When a tripping occurs in the MCCB, it is indicated by the alarm switch. The

    potential free change-over contacts can be utilized for indicative and circuit control

    purposes.

    Configurations: 1 NO + 1 NC

    2 NO + 2 NC

    Internal Accessories

    Auxiliary contact

    Undervoltage release

    Shunt release

    Alarm switch

  • Insulation Barrier

    The insulation barrier should be utilized on the MCCB to facilitate

    termination of cable links. Used on the incoming side of the MCCB, it

    provides additional safety as it is made of superior insulating materials

    that have good mechanical and electrical properties. The insulation

    barrier prevents accidental contacts and flash-over between each

    phase and is highly recommended for the breakers especially during

    installation of a switchboard.

    Plug-in Kit (PIK)

    The MCCB plug-in kit is designed to replace the standard

    terminal with a rear connection to improve the opening capability.

    Suitable for isolation, the plug-in kit has a better contact performance

    in the MCCB when there is less force and a low temperature. It is also

    important to note that the MCCB can be drawn out without

    disconnecting the incoming live cable.

    Rotary Handle (RH)

    The MCCB toggle handle operating mechanism is used to

    facilitate the ON/OFF operation when the MCCB is installed in the

    cubicles of distribution boards. It is designed to be attached directly

    onto the MCCB and transform the toggle handle movement into a

    rotation switch to serve as a position indicator switch.

    Motor Operating Mechanism (MOD)

    The motor-operated mechanism enables the MCCB to be

    switched ON or OFF automatically. The MCCB should also be

    equipped with an alarm switch for automatic resetting purposes.

    External Accessories

    Plug-in kit

    Rotary handle

    Motor operating mechanism

    18

  • 19

    Auxiliary Contact

    Frame Size

    Conventional Current (Ith)

    Durability Make & Break Capacity

    100A < In < 630A

    3

    0.3A

    10

    1

    0.3

    1

    1

    0.3

    6050

    360

    > 0.05

    10

    1

    0.3

    1

    1

    0.3

    10

    120

    > 0.05

    100A < In < 630A

    3

    0.3ARated Operational Current at AC 380V

    I/Ic

    U/Uc

    Cos

    Make

    I/Ic

    U/Uc

    Cos

    Number of cycles

    Frequency (t/s)

    Time (s)

    BreakCategoryAC-15

    Shunt Trip

    Internal Accessories Specification

    MCCB model

    Cut-off Switch

    OperatingVoltage

    Operating Time

    63 C, S equipped

    equipped

    equipped

    equipped

    equipped

    equipped

    240V 5 - 15 mins

    7 - 15 mins

    7 - 15 mins

    7 - 15 mins

    7 - 15 mins

    7 - 15 mins

    240V

    240V

    240V

    240V

    240V

    100 C, N, S & H

    225 C, N, S & H

    400 S & H

    600 S & H

    800 S & H

    Auxiliary Contact and Alarm Switch

    Open Position Close Position

    Circuit Breaker > 400A2 NO + 2 NC

    Circuit Breaker > 225A1 NO + 1 NC

    Circuit Breaker > 400A2 NO + 2 NC

    Circuit Breaker > 225A1 NO + 1 NC

  • External Accessories

    Installation and Fittings

    20

  • 21

    Shortest Distance between Hinge & Handle Center and available Shaft SpaceOutline & Mounting Drawing

    HandleDoor Hole for Handle

    Outline Dimensions of Rotary Handle & Door Hole

    Features

    can be pad-locked in both ON and OFF positions.

    when door is locked in ON position, can be opened in OFF position.

    protective class (based on IEC529 standards) at IP54.

  • Selection Table & Installation Guide for Accessories

    UVT* Undervoltage Release

    Shunt Trip* Remote Trip Unit

    Auxiliary Switch* On & Off Indication

    Name of Accessory LKS-63 LKS-100 LKS-225 LKS-400 LKS-630LKS-800

    Alarm Switch* Trip Indication

    Shunt Trip + Auxiliary Switch

    Shunt Trip + UVT

    2 Auxiliary Switch

    Auxiliary + UVT

    Alarm + Shunt Trip

    Alarm + Auxiliary Switch

    Alarm + UVT

    Alarm + Auxiliary + Shunt Trip

    Alarm + 2 Sets of Auxiliary

    Alarm + Auxiliary + UVT

    * 1. Only lead wire type is available* 2. For Alarm, Auxiliary, Switch and UVT,a module is

    mounted externally on the cover.

    item

    AlarmAuxiliary switch

    Shunt tripUVT

    symbolLeft Side Right Side

    MCCB On/Off Toggle

    22

  • 23

    ACMSAL - 225

    35.5

    Outline Drawings of AccessoriesDCBAModel CodeShunt Trip Release

    DCBAModel CodeUndervoltage Release

    DCBAModel CodeAlarm Switch

    ACMSVT - 100

    ACMSVT - 63 39 30.5 37.5 23.1

    30 29.5 23.4

    ACMSVT - 225 39.5 34.5 31.2 30.3

    ACMSVT - 400 58.5 35 63.4 28.3

    ACMSVT - 630 58.5 50.8 97 27.9

    ACMSST - 63 39 31 42 23.5

    ACMSST - 100 29 32.7 38.5 22

    ACMSST - 225 29 34.5 43 30

    ACMSST - 400 62.5 60 37.5 28

    ACMSST - 630 63.5 60 37.5 28

    ACMSAL - 100 29.5 30.6 37.5 23.6

    37.5 30.6 40 28.6

    ACMSAL - 400 55 63 28 29.5

    ACMSAL - 630 55 63 28 39

    measurements are in millimeter (mm)

  • 24

    Outline Drawings of Accessories

    ACMSAA - 630

    ACMSAA - 400

    ACMSAA - 225

    Auxiliary Switch

    DCBAModel CodeAuxiliary + Alarm Switch

    ACMSAA - 100 29.5 27 37.5 23.6

    37.5 30.6 40 38.6

    55 63 28 29.5

    55 63 28 39

    DCBAModel Code

    ACMSAX - 100

    ACMSAX - 225

    ACMSAX - 400

    ACMSAX - 630

    29.5

    37.5

    55

    55

    27

    30.6

    63

    63

    37.5

    40

    28

    28

    23.6

    28.6

    29.5

    39

    measurements are in millimeter (mm)

  • 25

    Outline Drawings of Accessories

    ACMRH - 400

    ACMRH - 225

    ACMRH - 630

    ACMRH - 100

    CBAModel CodeMotor Operating Mechanism

    DCBAModel CodeRotary Handle

    ACMRH - 50 100 25 49 68

    104 30 49 69

    143 35 55 72

    195 129 83 110

    195 129 83 110

    ACMSMOD - 400 226 132 143

    ACMSMOD - 630 226 207 143

    ACMSMOD - 100 117.5 90 91

    ACMSMOD - 225 156 105 101

    measurements are in millimeter (mm)

  • Plug-in Kitmodel code MZ1-100/30 MZ1-225/30 MZ1-400/30 MZ1-630/30

    A

    A1

    B

    B1

    C

    D

    D1

    E

    E1

    F

    F1

    G

    H

    H1

    J

    K

    L

    L1

    M

    m

    m1

    m2

    N

    92

    60

    30

    70

    104

    6

    0

    134

    0

    60

    M10

    13

    26

    16

    M10

    14

    90

    60

    M5

    0

    62

    122

    0

    108

    70

    38

    73

    106

    6

    10

    144

    26

    70

    25

    13

    34

    15

    6

    17.5

    105.5

    70

    M5

    108

    79

    134

    18

    136

    44 140

    50 58

    135 143

    175 184

    10 10

    13 13

    225 243

    32 0

    87 140

    28 44

    18 17

    40 53

    24 20

    8 11

    27 27

    144 210

    87 140

    M8 M8

    120 0

    79 146

    0 0

    15 15

    213

    measurements are in millimeter (mm)

    Outline Drawings of Accessories

    26

  • 27

    Short-circuit in a Network

    When a short-circuit in a network occurs, it will create a highly damaged and

    abnormal condition to the system, whereby the normal insulation of the system, be

    it the cables or equipment and load, are damaged.

    The function of the MCCB as a protection device, is to protect overloads and

    bring the effect of this faulty condition under control at a fast speed in order to

    reduce the damages.

    The LKE Superior series MCCB, with the right combination of accessories and

    proper selection to coordinate between the down-stream and up-stream of the

    rated current and fault level, is one of the more reliable circuit breaker protection

    device available.

    It is important to understand the full load current and fault level to determine

    the rated current and short-circuit kA of the MCCB before selecting the right

    MCCB to protect the down-stream cable, equipment and load.

    The value of the short-circuit current at a fault-junction depends mainly on:

    the kVA of the supply source, (either a transformer or generator).

    the type of supply system.

    the length and cross section of the cable and device lying in between the

    source of supply and fault-junction.

    Types of Short-circuit

    Before calculating the short-circuit current at any point of the network, one

    must be able to differentiate the various types of short-circuit. In a three-phase

    network, short-circuits are generally classified as below, depending on the number

    of conductor affected and with or without fault-to-earth.

    Definition of Short-circuit and Short-circuit Current

    Three-phase fault

    Isc = Uo z

    Two-phase fault

    Isc = Uo z

    One-phase shorted to Neutral

    Isc = Uo3 z

    Cross-country three-phaseshorted to Neutral

    Isc = Uoz = 1/z1 + 1/z2 + 1/z2

  • 28

    The Peak Value of the Short-circuit Current

    When an R-L series circuit is closed with an A/C source, the current

    component results in:

    1 ) an A/C component with a phase shift with respect to the voltage

    2 ) a D/C decaying component.

    The arc component is superimposed on the D/C component. The initial peak

    value of the short-circuit current depends on the voltage at the instance of the

    breaker closing. The two extreme cases are:

    a ) when the breaker is closed at peak voltage, the D/C component is zero and

    the fault current is symmetrical or balanced.

    b ) when the breaker is closed at zero voltage, the D/C component is

    asymmetrical or unbalanced.

  • 29

    The initial peak value depends on the instance of the breaker closing and on the

    factor K = R/X [Refer Fig.1]. In practical applications, the value of K lies mostly

    between 1.1 to 1.5. The electro-dynamic stress on the current carrying parts

    depends on this peak value Ip.

    Calculation of the Short-circuit Current close to the Transformer

    If the MCCB is used as a main switch, whether as a transfer switch or a

    distribution breaker close to the transformer, a rough estimate of the short-circuit

    current is sufficient. The percentage impedance of the transformer Z can be read

    out from the name plate. Otherwise, it is generally assumed as 5%. The short-

    circuit current can be calculated with the help of the following simple rule:

    Isc = In x 100/Z

    where,

    Isc - short-circuit current ( A )

    In - rated current of the transformer (Full load current)

    Z - percentage impedance of the transformer

    The rated current of the transformer is calculated as follows:

    In = S x 1000 /3 x Ue

    S = rating of transformer in kVA

    Ue = rated voltage at the low tension side in Volts

    e.g. :

    A transformer with S = 1000 kVA, Z = 5% and Ue = 415 V

    In = 1000 kVA x 1000 / 3 x 415 V = 1393 A

    Isc = 1393 A x 100 / 5 = 27860 A

    In this example, the short-circuit current close to the transformer is ~28 kA. The

    breaking capacity of the MCCB installed at this point must be higher than this

    value. This is applicable if a high breaking capacity MCCB with an ultimate short-

    circuit breaking capacity Icu = 35 kA or 50 kA is used here. It is immaterial whether

    the simple formula used above is sufficiently accurate or not. The selected circuit

    breaker will have enough capacity in reserve.

    The short-circuit current calculated above can also be read out from the table

    Rated and short-circuit currents of 3-phase standard transformers (refer to

    page 30).

    Determination of the Fault Current

  • Determination of the Fault Current at Transformer Terminal

    50

    100

    160

    200

    250

    315

    400

    500

    600

    700

    800

    900

    1000

    1250

    1500

    2000

    2500

    3000

    70

    139

    223

    278

    348

    448

    556

    696

    836

    975

    1115

    1254

    1393

    1741

    2089

    2786

    3482

    4179

    1391

    2782

    4452

    5565

    6956

    8765

    11130

    13912

    16714

    19500

    22286

    25072

    27860

    34820

    41780

    55720

    69640

    83580

    Transformer Rating (kVA)Rated Current (A)

    at full load currentShort-circuit Current (A)at secondary terminal

    Rated and Short-circuit Currents of 3-phase Standard Transformers at Secondary Terminal.

    Secondary rated voltage = 415V AC; percentage impedance of transformer Z = 5%

    30

  • 31

    Table

    D

    5

    5

    5

    5

    4.95

    4.9

    4.85

    4.75

    4.47

    5.5

    5.5

    5.5

    5.5

    5.45

    5.4

    5.35

    5.2

    4.85

    8.3

    8.3

    8.25

    8.2

    8.0

    7.9

    7.7

    7.3

    6.4

    10

    10

    9.9

    9.8

    9.5

    9.3

    9.0

    9

    7

    12.5

    12.3

    12.2

    12

    11.5

    11.1

    10

    9.6

    7.8

    16.4

    16.2

    16

    15.8

    14.6

    13.8

    12.8

    11

    8.6

    20

    20

    19.6

    19.2

    17

    16

    14.4

    12

    9

    24

    23.5

    23

    22

    19.2

    17.6

    15.6

    13

    9.3

    32

    30

    29

    27.7

    22

    20

    17

    13.7

    9.6

    38

    36

    34

    32

    24

    21.4

    18

    14

    9.7

    53

    47

    43

    39

    27

    2.2

    19

    14.6

    9.9

    Short-circuit Current (415V)

    100

    70

    60

    50

    30

    25

    20

    15

    10

    Upstream Fault Current (kA)

    Calculation of the Short-circuit Current in a Supply System

    In a supply system, the further away from the transformer, the higher the

    impedance. As such, the lower the value is for the short-circuit current. Each length

    of conductor or device in the circuit provides an impedance which reduces the

    short-circuit current. To calculate the maximum level possibility of the short-circuit

    current, all the impedances lying between the transformer and the MCCB must be

    considered, be it with formula or simple diagram.

    Rapid Determination of Fault Currents

    The following monogram provides a simple method of determining the fault

    current at any distance of cable from a transformer. To determine the fault current

    at the end of a line through monogram for a cable with a cross section of 3 x 95

    mm2 and at a length of 60 m is as follows:

    The upstream ( source ) fault current, e.g. 50 kA,

    e.g. If, length of cable = 60 m

    Cable cross section = 3 x 95 mm2

    Fault current at source = 50 kA

    Then, from the 80 m column in Table C, follow towards the cable size, and then

    down to Table D to the upstream fault current, at the intersection reads the current

    value, that is 12 kA.

    source

    fault current atfault junction

    It may be noted that a 100kA

    fault at upstream side can be

    reduced to a mere 5kA level

    at the end of a 150m long 70

    sq.mm cable.

    Table

    C

    70

    50

    35

    10

    6

    95

    70

    50

    35

    25

    16

    120

    95

    70

    50

    35

    25

    16

    10

    120

    70

    50

    35

    95

    25

    16

    16

    120

    95

    70

    50

    35

    25

    150

    120

    95

    25

    185

    150

    120

    70

    50

    35

    150

    95

    70

    50

    35

    185

    120

    95

    70

    50

    120

    95

    70

    461016253550

    4610162535

    2.546101625

    1.52.5461016

    1.52.54610

    1.52.546

    1.52.546

    Copper Cable Cross-section (mm2)

    150

    120

    80

    60

    45

    30

    20

    15

    12

    8

    6

    4

    3

    2

    1.5

    1.2

    Length of Cable (m)

  • 32

    Protection for Generators

    Frequency 50Hz - Voltage 400V

    Rated Power ofAlternator (kVA)

    630

    710

    800

    900

    1000

    1120

    1250

    1400

    1600

    1800

    2000

    2250

    2500

    2800

    3150

    3500

    909

    1025

    1155

    1299

    1443

    1617

    1804

    2021

    2309

    2598

    2887

    3248

    3608

    4041

    4547

    5052

    1250

    1250

    1250

    1600

    1600

    2000

    2000

    2500

    2500

    3200

    3200

    4000

    4000

    5000

    5000

    6300

    Rated Current ofAlternator (A)

    Rated Current ofCircuit Breaker (A)

    Frequency 60Hz - Voltage 450V

    Rated Power ofAlternator (kVA)

    760

    850

    960

    1080

    1200

    1344 - 1350

    1500

    1650 - 1680 - 1700

    1920 - 1900

    2160 - 2150

    2400

    2700

    3000

    3360

    3780

    4200

    975

    1091

    1232

    1386

    1540

    1724 - 1732

    1925

    2117 - 2155 - 2181

    2463 - 2438

    2771 - 2758

    3079

    3464

    3849

    4311

    4850

    5389

    1250

    1250

    1250

    1600

    1600

    2000

    2000

    2500

    2500

    3200

    3200

    4000

    4000

    5000

    5000

    6300

    Rated Current ofAlternator (A)

    Rated Current ofCircuit Breaker (A)

  • 33

    The IEC standard classifies the coordination of the breaker and contactor into

    the following 3 categories for damages on the contactor when a fault occurs on

    the load side:

    Category A coordination is when the magnetic contactor is damaged to the

    extent that it will require replacement. Other major components

    may also require replacement or complete assembly.

    Category B coordination is when repair requirements are only to the

    component parts, due to welding of contacts or melting of the

    thermal relay heater.

    Category C a perfect coordination is achieved when no damages are

    sustained by the contactor.

    Coordination with Wiring

    The wiring leading to the motor should be installed in accordance with

    international standards requirements.

    Coordination with Thermal Overload Relay

    In a system arrangement with a MCCB, contactor and thermal overload relay,

    the MCCB long time delay must exceed that of the thermal overload relays curve.

    This is important when any overload on the motor occurs, the thermal overload

    relay is able to operate instead of the MCCB.

    In case of a short-circuit or heavy overload such as a locked rotor, where the

    current may reach 5 to 7 times the motor rated current, the protection is then taken

    over by the MCCB.

    Coordination with Motor Starting Current

    Motors with starting times of 15s or less are generally considered safe, while

    those with starting times of longer than 15s are considered undesirable for any

    standard motors. Motors with starting times longer than 30s are considered

    dangerous and should be avoided altogether.

    Selection Principle

    1. The MCCB current rating should be higher than the motor full load current.

    2. The motor starting current and starting time should be below the minimum

    time/current curve of the MCCB. A margin of about 50% should be allowed for

    the starting time to allow for the voltage drop or increase of a mechanical load

    friction.

    3. The MCCB magnetic trip current should be 1.4 to 1.7 times the motor rated

    starting current ( lock-rotor current).

    4. For star- delta or auto-transformer starters, the MCCB magnetic trip should be

    at least 2 to 2.4 times the motor rated starting current (or lock-rotor current).

    Protection of Motor by Breakers

  • 34

    Capacitance Load

    The capacitors must be able to withstand a continuous overload of 30% due

    to the harmonic currents. As a result, the circuit breaker must be derated b 30%.

    where

    Zs = Impedance of Power Source

    Za = (Zs + Zt) Zm

    Zs + Zt + Zm

    Selection Guide

    Capacitor

    Capacity (kVAr)

    12.5

    20

    30

    50

    75

    90

    120

    150

    190

    225

    300

    18

    29

    44

    72

    110

    132

    173

    216

    274

    324

    433

    25

    40

    63

    100

    160

    200

    250

    320

    400

    500

    630

    Current at Capacity (A)

    Circuit Breaker

    Rating (A)

    Impedance in 3-phase Capacity(converted to 1000kVA standard capacity)

    Trans.Cap(kVA)

    % Impedanceof Trans.

    Zt (%)

    % Impedanceof MotorZm (%)

    Total % ifImpedance

    of Power SourceZA (%)

    50 33.4 + j37.8 82.2 + j493.2 28.98 + j36.33

    18.28 + j29.39

    13.46 + j23.03

    8.341 + j16.57

    6.161 + j12.64

    3.914 + j9.773

    2.064 + j6.696

    1.327 + j5.266

    0.957 + j4.372

    0.607 + j3.278

    0.449 + j25

    54.8 + j328.8

    41.1 + j24.8

    27.4 + j164.4

    20.55 + j123.3

    13.7 + j82.2

    8.22 + j49.32

    5.48 + j32.88

    4.11 + j24.66

    2.74 + j16.44

    2.055 + j12.33

    21.6 + j31.47

    16.0 + j24.8

    10.0 + j18.07

    7.4 + j13.8

    4.8 + j10.9

    2.56 + j7.62

    1.68 + j6.16

    1.22 + j5.21

    0.773 + j3.99

    0.57 + j3.035

    75

    100

    150

    200

    300

    500

    750

    1000

    1500

    2000

    Average Impedance in 3-phase Transformer

    TransformerCapacity

    (kVA)

    Impedance (%)

    % X% R

    50

    75

    100

    150

    200

    300

    500

    750

    1000

    1500

    2000

    1.67

    1.62

    1.60

    1.50

    1.48

    1.44

    1.28

    1.26

    1.22

    1.16

    1.14

    1.89

    2.36

    2.48

    2.71

    2.76

    3.27

    3.81

    4.62

    5.21

    5.99

    6.07

  • 35

    Selection Guide

    1.6 mm 8.92 0.103 0.143 0.287 0.123 0.182 0.344

    0.134 0.273 0.116 0.161 0.327

    0.127 0.256 0.115 0.152 0.308

    0.138 0.279 0.020 0.167 0.335

    0.126 0.261 0.110 0.152 0.314

    0.120 0.247 0.110 0.145 0.297

    0.116 0.236 0.110 0.140 0.283

    0.111 0.218 0.106 0.134 0.261

    0.105 0.204

    0.195

    0.187

    0.178

    0.172

    0.173

    0.155

    0.148

    0.142

    0.134

    0.126

    0.118

    0.112

    0.105

    0.104

    0.100

    0.100

    0.097

    0.095

    0.094

    0.092

    0.091

    0.090

    0.089

    0.087

    0.086

    0.127

    0.122

    0.118

    0.115

    0.111

    0.107

    0.104

    0.106

    0.101

    0.101

    0.099

    0.097

    0.095

    0.094

    0.245

    0.234

    0.225

    0.214

    0.206

    0.196

    0.186

    0.178

    0.170

    0.161

    0.151

    0.142

    0.134

    0.216

    0.091

    0.098

    0.095

    0.092

    0.087

    0.086

    0.087

    0.084

    0.084

    0.082

    0.080

    0.079

    0.078

    0.097

    0.096

    0.100

    0.092

    0.092

    0.092

    0.088

    0.086

    0.083

    0.083

    0.081

    0.079

    0.078

    0.076

    0.076

    0.075

    0.073

    0.073

    0.072

    5.65

    3.35

    9.24

    5.20

    3.33

    2.31

    1.30

    0.824

    0.623

    0.487

    0.378

    0.303

    0.230

    0.180

    0.144

    0.118

    0.092

    0.072

    0.057

    0.045

    0.037

    2.0 mm

    2.6 mm

    2

    3.5

    5.5

    8

    14

    22

    30

    38

    50

    60

    80

    100

    125

    150

    200

    250

    325

    400

    500

    Resistance

    Cable(mm2)

    Rw(m/m)

    Reactance Xw (m/m)

    50Hz 60Hz

    single core6cm distance

    single core,closed

    2-core,3-core

    single core6cm distance

    single core,closed

    2-core,3-core

    Impedance of Electric Cable

    NOTE: The resistance values are based on JIS C3307 660V grade polyvinyl chloride insulated and vinyl sheathed cable (w).The reactance value L = 0.05 + 0.4605 log10 D/r (m/H/km)

    (D = core center to center distance, then Xw = 2. fl x 10 -3 (m/m), f = frequency was calculated).

  • 36

    Selection Guide

    Impedance of Bus Duct (Zb)

    Rated Current(A)

    Resistance(m/m)

    Reactance (m/m)

    60Hz50Hz

    400 0.158

    0.127

    0.085

    0.065

    0.053

    0.041

    0.025

    0.020

    0.017

    600

    800

    1000

    1200

    1500

    2000

    2500

    3000

    0.039

    0.033

    0.024

    0.018

    0.014

    0.012

    0.014

    0.013

    0.011

    0.046

    0.039

    0.028

    0.022

    0.017

    0.014

    0.017

    0.016

    0.013

    Comparison of Different Methods of Starting

    Method ofStarting

    Ist/Idol

    Current (I) Torque (T)

    Ist/In Tst/Tdol Tst/Tn

    Direct-on-line 1 4 - 8 1 1 - 1.15

    0.33 1.32 - 2.64 0.33 0.33 - 0.49

    0.28 1.12 - 2.24 0.25 0.25 - 0.37

    0.39 1.56 - 3.12 0.36 0.36 - 0.54

    0.59 2.36 - 4.72 0.56 0.56 - 0.84

    0.7 0.7 0.5 0.5

    1.4 1.4 1 1

    2 2 1.4 1.4

    Star-delta

    Auto transformer 50%

    Auto transformer 60%

    Auto transformer 75%

    Rheostat, severity 0.7

    Rheostat, severity 1.4

    Rheostat, severity 2.0

  • 37

    What is Selectivity?

    Selectivity between 2 protective devices in series, such as the MCCB1

    & MCCB2, is also called discrimination. The purpose of selectivity is to

    coordinate the 2 circuit breakers in cascade, eg. A and B (see diagram). This

    means only the B breaker trips in case of fault occurring at C and a

    continuous supply of power to the remaining loads through the A breaker.

    Total and Partial Selectivity (Diagram 1 & 2)

    Total selectivity between A & B breakers is when fault occurs at C, up to

    the prospective short circuit current of the B breaker, and only when the B

    breaker is tripped while the A breaker remains untrip.

    Partial selectivity between A & B breakers is when the B breaker trips but

    the A breaker does not, but only for fault currents lower than the maximum

    prospective short circuit currents that may occur in the line connected to

    the B breaker. For a higher fault current, up to the maximum prospective

    short circuit current of the breaker B, both B & A breakers may trip

    together.

    Selectivity Techniques (Diagram 3)

    There are two techniques for ensuring selectivity:

    1. Current selectivity

    2. Time selectivity

    These 2 techniques are effected intervening in the operation of the

    breaker of setting the tripping current (Im) & the tripping time delay (Tm).

    Current Selectivity

    This technique is commonly used in low tension switchboards,

    achievable by adjusting the tripping unit current setting. For 2 breakers in

    series, the pick-up current on the upstream breaker is set to a value higher

    than the prospective short circuit current at the point of the fault junction of

    the down stream breaker.

    This selectivity technique is used particularly for links between main

    boards and secondary boards.

    Time Selectivity (Diagram 4)

    This time selectivity technique requires the selectivity circuit breaker

    a breaker with an adjustable time trip device:

    Time delay with adjustable unit in the breaker tripping system

    The breaker must be able to withstand the thermal & electrodynamic

    effect of the short circuit current for the period of the time delay.

    Selectivity

    Diagram 1

    Diagram 2

    Diagram 3

    Diagram 4

  • LKEs Low & Medium VoltageRange of Products

    capacity of products range from 380VAC 36kV and rated current from 5A 6300A

    LK-LBSCompressed Air

    Load BreakSwitch

    LK-VLBSVacuum

    Load Break

    Switch

    LK-GLBS SF6 Load Break Switch

    LK-VB1Vacuum Circuit Breaker

    LK-LTPMSF6 Ring Main Unit

    LK-LTHOSF6 Pole-MountedSwitch Disconnector

    LK-ATSAuto TransferSwitch

    LK-ACBAir Circuit Breaker

    LK-MCCB, LH-MX, LK-SF, LK-RCCBLow Voltage Circuit Breakers

    LK-LCASF6 Ring Main Unit

    LK-LCACompressed Air

    Ring Main Unit

    LK-CUBICLow VoltageSwitchboard

  • As standards, applications and designs may change from time to time, please contact our nearest agent for the latest information. For further technical references,

    please refer to the respective product catalogue.

    LK-Electric Co Pte LtdBlk 219 Henderson Industrial Park

    #06-03 Henderson Rd, 159546 SINGAPORE telephone 65 271 5388facsimile 65 271 5088

    LKE Electric (M) Sdn Bhd1 & 3 Jalan SS13/3C, Subang Jaya Industrial Estate

    47500 Petaling Jaya, Selangor D.E., MALAYSIAtelephone 603 5633 7010/7011

    facsimile 603 5633 8368, 5632 3014

    LK-Electric (Zhuhai) Co LtdNo 4, North of Industrial Area Xiangzhou

    Zhuhai, 519000 P.R. of CHINAtelephone 86 756 226 7005facsimile 86 756 226 7007

    CUBIC Electric (Shanghai) Co Ltd18th Floor, No 159 Handan RoadShanghai, 200437 P.R. of CHINA

    telephone 86 21 6555 7237facsimile 86 21 6555 7119

    LKE Electric Europe A/SEgestubben 16-26

    DK 5270, Odense, DENMARKtelephone 45 63 18 1560facsimile 45 63 18 1590

    [email protected]

    OPTIMAL SOLUTIONS

    SUPERIOR QUALITY

    I N S TA N T D E L I V E RY

    ALL ROUND SERVICE

    Printed in Malaysia 05/2002