March 27, 2019 British Columbia Utilities Commission Suite 410, 900 Howe Street Vancouver, B.C. V6Z 2N3 Attention: Mr. Patrick Wruck, Commission Secretary and Manager, Regulatory Support Dear Mr. Wruck: Re: FortisBC Inc. (FBC) Project No. 1598987 Application for a Certificate of Public Convenience and Necessity (CPCN) for the Grand Forks Terminal Station Reliability Project (the Application) Response to Industrial Customers Group (ICG) Information Request (IR) No. 2 (Exhibit B-12) Refiling of Graphs in Response to Question 14.1 FBC writes pursuant to the letter filed by ICG dated March 25, 2019 (Exhibit C4-6). In its letter, ICG requested that FBC refile the graphs provided in response to ICG IR 2.14.1 (Exhibit B-12) requesting the graphs be made more clear. FBC has attached enlarged versions of the graphs as requested. If further information is required, please contact the undersigned. Sincerely, FORTISBC INC. Original signed: Doug Slater cc (email only): Registered Parties B-13-1

March 27, 2019 Suite 410, 900 Howe Street Vancouver, B.C....Application for a Certificate of Public Convenience and Necessity (CPCN) for the Grand Forks Terminal Station Reliability

  • Upload
    others

  • View
    0

  • Download
    0

Embed Size (px)

Citation preview

Page 1: March 27, 2019 Suite 410, 900 Howe Street Vancouver, B.C....Application for a Certificate of Public Convenience and Necessity (CPCN) for the Grand Forks Terminal Station Reliability

March 27, 2019

British Columbia Utilities Commission Suite 410, 900 Howe Street Vancouver, B.C. V6Z 2N3

Attention: Mr. Patrick Wruck, Commission Secretary and Manager, Regulatory Support

Dear Mr. Wruck:

Re: FortisBC Inc. (FBC)

Project No. 1598987

Application for a Certificate of Public Convenience and Necessity (CPCN) for the Grand Forks Terminal Station Reliability Project (the Application)

Response to Industrial Customers Group (ICG) Information Request (IR) No. 2 (Exhibit B-12) – Refiling of Graphs in Response to Question 14.1

FBC writes pursuant to the letter filed by ICG dated March 25, 2019 (Exhibit C4-6).

In its letter, ICG requested that FBC refile the graphs provided in response to ICG IR 2.14.1 (Exhibit B-12) requesting the graphs be made more clear. FBC has attached enlarged versions of the graphs as requested.

If further information is required, please contact the undersigned.

Sincerely,

FORTISBC INC.

Original signed:

Doug Slater

cc (email only): Registered Parties

B-13-1

ylapierr
CPCN Grand Forks Terminal Project
rocurran
Text Box
BCUC File 60075 Batch 59500
Page 2: March 27, 2019 Suite 410, 900 Howe Street Vancouver, B.C....Application for a Certificate of Public Convenience and Necessity (CPCN) for the Grand Forks Terminal Station Reliability

0

5000

10000

15000

20000

25000

30000

35000

0 500 1000 1500 2000 2500

kVA

Hours

GFT T12014 Summer Load Duration Curve

Page 3: March 27, 2019 Suite 410, 900 Howe Street Vancouver, B.C....Application for a Certificate of Public Convenience and Necessity (CPCN) for the Grand Forks Terminal Station Reliability

0

5000

10000

15000

20000

25000

30000

35000

0 500 1000 1500 2000 2500

kVA

Hours

GFT T12015 Summer Load Duration Curve

Page 4: March 27, 2019 Suite 410, 900 Howe Street Vancouver, B.C....Application for a Certificate of Public Convenience and Necessity (CPCN) for the Grand Forks Terminal Station Reliability

0

5000

10000

15000

20000

25000

30000

35000

0 500 1000 1500 2000 2500

kVA

Hours

GFT T12016 Summer Load Duration Curve

Page 5: March 27, 2019 Suite 410, 900 Howe Street Vancouver, B.C....Application for a Certificate of Public Convenience and Necessity (CPCN) for the Grand Forks Terminal Station Reliability

0

5000

10000

15000

20000

25000

30000

35000

0 500 1000 1500 2000 2500

kVA

Hours

GFT T12017 Summer Load Duration Curve

Page 6: March 27, 2019 Suite 410, 900 Howe Street Vancouver, B.C....Application for a Certificate of Public Convenience and Necessity (CPCN) for the Grand Forks Terminal Station Reliability

0

5000

10000

15000

20000

25000

30000

35000

0 500 1000 1500 2000 2500

kVA

Hours

GFT T12018 Summer Load Duration Curve

Page 7: March 27, 2019 Suite 410, 900 Howe Street Vancouver, B.C....Application for a Certificate of Public Convenience and Necessity (CPCN) for the Grand Forks Terminal Station Reliability

0

5000

10000

15000

20000

25000

30000

35000

0 500 1000 1500 2000 2500 3000

kVA

Hours

GFT T12013-14 Winter Load Duration Curve

Page 8: March 27, 2019 Suite 410, 900 Howe Street Vancouver, B.C....Application for a Certificate of Public Convenience and Necessity (CPCN) for the Grand Forks Terminal Station Reliability

0

5000

10000

15000

20000

25000

30000

35000

0 500 1000 1500 2000 2500 3000

kVA

Hours

GFT T12014-15 Winter Load Duration Curve

Page 9: March 27, 2019 Suite 410, 900 Howe Street Vancouver, B.C....Application for a Certificate of Public Convenience and Necessity (CPCN) for the Grand Forks Terminal Station Reliability

0

5000

10000

15000

20000

25000

30000

35000

0 500 1000 1500 2000 2500 3000

kVA

Hours

GFT T12015-16 Winter Load Duration Curve

Page 10: March 27, 2019 Suite 410, 900 Howe Street Vancouver, B.C....Application for a Certificate of Public Convenience and Necessity (CPCN) for the Grand Forks Terminal Station Reliability

0

5000

10000

15000

20000

25000

30000

35000

40000

0 500 1000 1500 2000 2500 3000

kVA

Hours

GFT T12016-17 Winter Load Duration Curve

Page 11: March 27, 2019 Suite 410, 900 Howe Street Vancouver, B.C....Application for a Certificate of Public Convenience and Necessity (CPCN) for the Grand Forks Terminal Station Reliability

0

5000

10000

15000

20000

25000

30000

35000

0 500 1000 1500 2000 2500 3000

kVA

Hours

GFT T12017-18 Winter Load Duration Curve