M-VR-ALL-V1.0
Manual Vibrating Fork Level Switches
www.ema-electronic.com
Vibrating Fork Level Switches Manual
VRT Smart Type
M-VRT-EN-V1.0
IP 65
3 2
■
Manual
20~60VDC
400mA Max.
PE + - Signal output
Power supply
1 2 3 4 5
L N
20~250VAC 50~60Hz
20~60VDC
4A/250VAC Max.
4A/60VDC Max.
NPN/PNP output:
PE LoadPower supply
1 2 3 4 5
+ -NPN PNP
■ Output of Switch2
PE
AB
20...250VAC / 20...60VDC
LEARNSET
Max. 250V / 4A
1 2 3 4
+L N
■ Hookup
Output TerminalTerminal for Power Supply
■ Mode of Connection
Relay output:
Power input
Signal output
Power input
Signal output Indicator
Sensitivity indicator
LEARN buttonSET button
Status switch Ground wire
1. Unlock: Hold "SET" button, for 10 sec., until the four LED flash to status of unlock. After unlock, it is back to normal operating mode.2. Lock: It is automatically locked if there is no button pressed in 60 sec. 3. NO/NC Setting: Press DIP switch to set NO or NC.4. Learn mode: Put fork part into the detected medium for 5 sec. and then operate "Unlock". After unlock, hold "LEARN" button for 5 sec., the LED1 ~ LED4 will flash orderly with frequency which is 1 time per sec. to start learning. If the four LEDs are all flash together, this learning is successful; if only the central two LEDs shine, this learning is failed and it is required to learn again.5. Sensitivity setting: Under status of unlock, press "SET" button to set sensitivity with checking the flash of LED1 to LED4. Sensitivity is from high to low by LED1 to LED4.Notice: To enter the second learning mode, please press "SET" button in 3 sec. after first learning finished. Otherwise the user shall be required to process the whole learning mode again to reset the setting. This function is to avoid of the false operation.Notice:1. The learning function of this type is not only to overcome the condition of the vibration absorption after the installation on the wall of tank but also to avoid of false operation caused by noise interference. 2. Factory setting is based on the density of water (1g/cm3). When the density of detected object is higher than or equal to 1g/cm3, it can be used normally without setting learning function. Otherwise it needs to reset learning function when the density of detected object is lower than 1g/cm3. 3. Sensitivity is set as the highest value in the factory and suitable to be used under the stable wave of medium. If the wave of medium fluctuates bigger, it is required to lower the sensitivity to avoid any error in warning.
Relay OUT
NPN OUT
PNP OUT
Switch 2
■ Technical Datasheet
Power supply
Response time
Ambient Temperature
Storage Temperature
Medium Temperature
Operating pressure
Detected substance
Mounting
Socket
Housing material
Fork material
Output
Electricity
20...60VDC NPN&PNP output
< 3 seconds
-40...+70°C
-40...+85°C
-40...+150°C
-1...+40 bar
It can be applied to detect any kind of powder,
solid,and liquid though the learning function
G1½”A,Flange, Fixture
M20 x 1.5
Alumimun Alloy
Stainless steel 316L
Relay, Load AC250V/4A, DC60V/4A
DC 3W Max. AC 15W Max.
NPN, Load 400mA
PNP, Load 400mA
EMCESD 6 Vk
EFT 2 V k
20...60VDC 20...250VAC Relay output
Protection classification IP 65
4- 15.00 130.00
155.00
-nll1
2G1
4.00
58.00 0.05±
A
A
19.000.00
-0.082-C0.5-nll
1
2G1
■ Dimensions
■ Accessories Specifications
Flange Fixture
Unit:mm VRT10 Standard ExtensionVRT11
117
8383
11
03
01
25
10
0
30
10
0
S4F0 S0C0
5 4
■ Installation
of materials is to make the switch horizontal at an angle of 15-20.2.Keep the switches away from the feed opening of the barrel to reduce the shock to materials, if unavoidable, a protection plate is necessary.3.The inlet of the connection box should be downward and the fixing nuts of power line must be tightened.4.The operators cannot use vibration rod to climb or hook any object when working within the barrel.
1.The ideal installation for reducing the shock to materials and the hanging
Shield to protect against flowing material.
Sufficient space for mounting and for adjusting.
Protective hood against condensation in the housing.
a
b
c
Incorrect mounting:Laterally mounted in filling curtain or under the feed opening.Incorrect fork orientationThe surface of fork is subjected to high load caused by discharging material; It may cause false function due to residual material.The switch will not work normally when the distance of mounting nozzle and barrel is over 2.4"(60mm).
ef
g
Correct mounting:
Fork is vertical towards bottom and mounted in any position far away fromthe feed opening of top side. Laterally mountedFork angled slightly downwards by 15~20 degree so as to reduce the shock and the hanging of the flowing materials. Laterally mounted with shieldWith a shield, length approx.10 in(250mm),width approx.8 in(200m),folk angled slightly downwards by 15~20 degree so as to reduce the shock of the flowing materials and prevent the improper stock from itself. In discharge hopperMax. nozzle length 2.4 in (60mm),so that no build-up occurs which prevents the fork from oscillating.
Top-mounteda
b
c
d
a
b c
7 6
8
Do not:damage the fork; bend the fork; shorten the fork; and lengthen the fork.
Mark on the hex nut.
The top of the fork is marked.
Tightened by a wrench.
Enclosed by PTFE thread seal tape.
Not wrested by hands.
www.ema-electronic.com
Stainless Steel Vibrating Fork Level Switches
VRS Smart Type
M-VRS-EN-V1.0
I P67 OilIP
■
Manual
3 / BU
2 / WH 1 / BN
5 / RE
4 / BK
Figure. A
Power-on indicator
Status indicator
Setting pushbutton
■ Hookup
■ Mode of Connection
1. Unlock: "SET" button for 10 secs until alternate red and green lights flash. The unit unlocks and returns to the operation mode. The red and green light stop flashing when "SET" button is released.2. Lock: It is automatically locked when there is no operation within 60 secs.3. NO / NC setting: Under the unlock condition, hold "SET" button for 3 secs and then the alternate red and green lights flash. When the green LED flashes, release the button to enter NO / NC setting mode and then press "SET" button once to adjust the required status.
4. Learning mode: Put the fork part into the detected medium with stability for 5 secs. Under the unlock condition, hold "SET" button for 3 secs and then the alternate red and green lights flash. When the red LED flashes, release the button. The red LED flashes once in a second orderly to express the status of waiting for learning. The red LED flashes and goes out twice to express the status of learning. The learning setting is successfully finished when the alternate red and green lights flash quickly. Otherwise, the red and green light flashes together and the user has to set the learning function again. To reset the learning, just press "SET" button again to enter second learning mode. Notice: To enter the second learning mode, please press "SET" button in 3 sec. after first learning finished. Otherwise the user shall be required to process the whole learning mode again to reset the setting. This function is to avoid of the false operation.Notice:1. The learning function of this type is not only to overcome the condition of the vibration absorption after the installation on the wall of tank but also to avoid of false operation caused by noise interference. 2. factory setting is based on the density of water (1g/cm3). When the density of detected object is higher than or equal to 1g/cm3, it can be used normally without setting learning function. Otherwise it needs to reset learning function when the density of detected object is lower than 1g/cm3.
Do not:damage the fork; bend the fork; shorten the fork; and lengthen the fork.
Figure. B
Tightened by a wrench.
Enclosed by PTFE thread seal tape.
Not wrested by hands.
WH: Ground connection
Red LED goes out Red LED flashes
BN+
BK
WH
RE
BU-
Relay
BN+
BK
WHNPN
PNP
BN+
BK
WH
RE
BU-
NPN
PNP RE
BU-
Power input
Loading
18~36VDC
200mA Max.
NPN/PNP output:
18~36VDC
Relay :output
Power input
Loading DC/AC 36V/1A
LEARN/ SET
11 10
::
:
::Setting pushbutton
Green LED: Power on/off
Red LED: Operation
Maximum
Minimum
Status Indicators■
LEARN/ SET
■ Technical Datasheet
-40...+70℃/-40...+158°F
-40...+85℃/-40...+185°F
-40...+100℃/
-40...+212°F
-1...+40bar
G¾"A
It can be used to detect any kind of powder, solid,
and liquid via the learning function
Power supply
Response time
Ambient Temperature
Storage Temperature
Medium Temperature
Operating pressure
Detected substance
Mounting
Socket
Housing material
Fork material
Output
Consumption
<1 second
Stainless steel 316L
Stainless steel 316L
Relay,Loading DC/AC 36V/1A
NPN/PNP, Load 200mA
Protection IP 68
18...36VDC
<2W (Relay)
<1W (PNP/NPN)
-40...+120℃/-40...+248°F
(145℃ max 1h)
Type
IP 69K
VRS10 VRS20
M12 Socket
13 12
1.The ideal installation for reducing the shock to materials and the hanging of materials is to make the switch horizontal at an angle of 15-20.2.Keep the switches away from the feed opening of the barrel to reduce the shock to materials, if unavoidable, a protection plate is necessary.3.The inlet of the connection box should be downward and the fixing nuts of power line must be tightened.4.The operators cannot use vibration rod to climb or hook any object when working within the barrel.
■ Installation
Correct mounting:Top-mountedFork is vertical towards bottom and mounted in any position far away fromthe feed opening of top side.Foam do not affect the Fork switch. Laterally mountedTo reduce the shock and the hanging of the flowing materials. Laterally mounted with shieldlength approx.10 in(250mm),width approx.8 in(200m), to reduce the shock of the flowing materials and prevent the improper stock from itself. In discharge hopperMax. nozzle length 2.4 in (60mm),so that no build-up occurs which prevents the fork from oscillating.
Incorrect mounting:Laterally mounted in filling curtain or under the feed opening.Incorrect fork orientationThe surface of fork is subjected to high load caused by discharging material,It may cause false function due to residual material.
a
b
c
d
ef
Pay attention to the position of the fork and liquid direction.
□
×□
15 14
■ Dimensions
38
45
12
4
45
68
VRS10
VRS20
Unit:mm
Unit:mm
0061US■ Welding adapter for sanitary sensors
Unit:mm
Dimensions
17 16
1. Preparations
!
► Bore a hole in the pipe or housing wall with the external diameter of the adapter (max. oversize: 0.2 mm). ► If possible, screw a cover plug into the adapter .
2. Welding operation
!The power of the welding device must be adapted to the thickness of the wall.
1 to the marking for front display of the sensor.
position for the spanner.2
► Fix the adapter at several points with sufficient holding force. Apply the fixing points at equal distance opposite each other.
► Apply the welding seams between the fixing points opposite each other. Ensure sufficient intervals between the individual sections(cooling phases to avoid glowing through / warping of the adapter due to overheating).
3. After welding
► Let the adapter cool down. ► Clean the thread from welding residues.
2
The welding operation must be carried out by authorised personnel. It must be carried out carefully and according to state-of-the-art technology. During welding and the following cooling phase the sensor must notbe in place. The surfaces must be free from any soiling. Welding tools must be suitable for the adapter and wall material.
►
► Adapter alignment:Tighten the sensor by a spanner until you can feel the end stop (this corresponds to a maximum tightening torque of 35 Nm). Note: Further tightening may affect the sealing effect.
Screw the sensor into the adapter. Avoid damage to the sealing areas.
Note: If the sensor can only be screwed into the thread with great resistance, stop the force. If it is not possible to rectify the thread, remove the adapter and weld in a new one.
►
►
Grease the sensor thread with lubricating paste (B). The paste must be suitable and approved for the application and compatible with the elastomers used.
►
►
4. Installation of Welding adapter for sanitary fork
Check (A) and (C) if there is an O-ring .Do not install it without any of O-ring .
A
B
C
19 18
0062US■ Clamp adapter for sanitary sensors
Dimensions
Unit:mm
2. Install the connection
Fix the sensor + adapter are fixed to the process connectionby a fixing part (coupling nut, clamp adapter, etc.).
Clamp the sensor + adapter into a clamping device . Tighten the clamping part slightly so that the adapter does not warp.
Tighten the sensor by a spanner until you can feel the end stop (this corresponds to a maximum tightening torque of 35 Nm). Note: Further tightening may affect the sealing effect.
Screw the sensor into the adapter. Avoid damage to the sealing areas.
Note: If the sensor can only be screwed into the thread with great resistance, stop the force. If it is not possible to rectify the thread, remove the adapter and weld in a new one.
►
►
Grease the sensor thread with lubricating paste (B). The paste must be suitable and approved for the application and compatible with the elastomers used.
►
►
►
If it is not possible to slide the fixing part down over the top of the unit: slide it up over the bottom of the unit before the adapter is mounted.
1. Installation of Clamp adapter for sanitary temperature sensor
Check (A) and (C) if there is an O-ring .Do not install it without any of O-ring .
A
BC
21 20
M VRT-CN-V1.0-
智能型音叉式料位开关说明书
VRT系列■中文简体
IP 65
23
供电电压
开关时间
环境温度
储藏温度
介质温度
操作压力
被测物料
连接方式
入线口直径
外壳材质
叉体材质
输出方式
功耗
20...60VDC NPN&PNP输出
<3秒
-40...+70°C
-40...+85°C
-40...+150°C
-1...+40 bar
通过学习功能,可适用任何粉末、颗粒和液体
G1½”A 镶件, ,法兰
M20 x 1.5
铝合金
高级不锈钢316L
继电器输出,负载AC250/4A DC60V/4A,
直流供电时3W Max. 交流供电时15W Max.
集电极开路(NPN)输出,负载400mA
集电极开路(PNP)输出,负载400mA
EMC ESD 6 kV
群脉冲 2 V k
能
误
误
20...60VDC 20...250VAC Relay输出
防护等级 IP65
25 24
单位:mm VRT10 标准型 VRT11 延长型
选购附件规格
S4F0 S0C0S4F0
117
8383
11
03
01
25
10
0
30
10
0
27 26
a
防止因进料冲击影响料位开关正常工作的防护板。
料位开关与周围物件及设备之间必须保留足够的安装与调试是空间。
防止在外罩内形成冷凝的防护罩。
b c
安装注意事项
29 28
音叉式料位开关说明书VRS 能智 型
www.ema-electronic.com
■
操作说明
■ 接线图
■ 端子图
图 B
3 / BU
2 / WH 1 / BN
5 / RE
4 / BK
白色线 棕色线
红色线
蓝色线 黑色线
图 A
状态指示电源指示
设定按钮
1、解锁:长按“SET”约10秒红绿灯交替亮,表示已经解锁并进入菜
单选择界面,红绿灯交替闪亮直到释放SET键为止。
2、锁定:在解锁状态下,若60秒内无按键按下,即自动锁定。
3、常开常闭的设定:在解锁或解锁后长按SET键3秒之后,红绿灯交
替亮,当在“绿灯”亮的时候释放按鈕即进入常开常闭设定模式,
此时单次按下“SET”键即可设定所需的状态。
M-VRS-CN-V1.0
I P67 OilIP
WH: 接地端子
红色LED灯灭 红色LED灯亮
BN+
BK
WHNPN
PNP
BN+
BK
WH
RE
BU-
NPN
PNP RE
BU-
电源供应
负载
18~36VDC
200mA Max.
NPN/PNP输出:
BN+
BK
WH
RE
BU-
Relay
18~36VDC
Relay输出:
电源供应
负载 DC/AC 36V/1A
LEARN/ SET
31
禁止:破坏振动棒;折弯振动棒;截短振动棒;加长振动棒。
4、学习模式:先将叉体放入待测介质中,稳定5秒。在解锁或解锁
后长按SET键3秒之后,红绿灯交替亮。在“红灯”亮时松开按
键,红灯1秒闪烁一次来表示等待确认学习。然后,按下“SET”
键,红灯亮灭2次表示正在学习,当红绿灯快速交替闪烁时,表
示学习成功。当红绿灯同时闪烁时,表示学习不成功。此时需
要重新学习,只要再次按下“SET”键,即进入第二次学习。
注:学习之后要在3秒之内按才能再次进入学习状态,否则须重
新选择学习模式,此功能为了防止误动作。
特别说明:
1、此智能型音叉的学习功能,一方面是为了克服叉体安装于桶壁后
出现的吸振现象,另一方面是为了防止杂讯干扰,避免误动作。32、产品的出厂设定值是以水的密度(1g/cm ),作为状态切换的基准,
3 当待测物的密度大于等于1g/cm 时,不需要重新学习即可正常使3 用。当待测物的密度小于1g/cm 时,则需要重新学习。
最大值
最小值
绿色LED,电源指示灯
红色LED,工作状态指示灯
::
:
■ 状态指示图
设定按钮::
用生料带密封 用扳手拧紧 勿用手拧
LEARN/ SET
33 32
■ 技术参数
1、安装时,可将开关以水平向下呈15~20度之夹角安装,以减少 物
料的冲击和 挂料现象的发生。
2、安装时应尽可能远离桶槽的进料口以避免物料冲击和误报警的发
生。如无法避免时,须在进料口与料位开关之间加装隔板保护。
3、接线盒入线口必须朝下,电源线入线口的固定螺母必须锁紧。
4、工作人员于桶槽内工作时,严禁利用振动棒攀爬或悬挂任何绳索
及物品。
■ 储存槽安装尺寸、实例及注意事项
供电电压 18...36VDC
开关时间 <1秒
环境温度 -40...+70℃/-40...+158°F
储藏温度 -40...+85℃/-40...+185°F
介质温度 -40...+100℃/
操作压力 -1...+40bar
被测物料
连接方式 G¾"A
电气接口 M12 连接器
外壳材质 高级不锈钢316L
叉体材质 高级不锈钢316L
继电器输出,负载DC/AC 36V/1A
NPN/PNP输出,负载200mA
<1W (PNP/NPN 输出)
<2W (继电器输出)
通过学习功能,可适用任何粉末、颗粒和液体
输出方式
保护等级 IP 68
功耗
-40...+212°F
-40...+120℃/-40...+248°F
(145℃ max 1h)
类型 标准型 VRS10 卫生型 VRS20
IP 69K 35 34
a
b
c
d
e
f
正确安装:
顶部安装,振动棒垂直向下,可安装在顶部(远离进料口)的任何
位置。泡沫对料位开关无影响。
横向安装,以减少物料的冲击及挂料现象的发生。
横向安装,料位开关上方有挡板(长度约为10"(250mm),宽度约
为8"(200mm)),可防止(d)物料在料位开关周围的不当堆积,并
可降低物料对于料位开关的冲击。
安装于卸料斗内,料位开关螺牙底端与桶壁之间的最大距离不超
过2.4"(60mm),可避免因物料的不当堆积而发生误报警的情况。
不正确的安装:
水平安装在填充壁上或进料口下方。
安装角度不正确(振动棒的表面因承受进料和卸料的高负荷压力而
容易出现故障)。
在管道中安装:注意叉体和水流方向,以便开关在管道中正确安装。
■ 尺寸图
单位:mm
38
45
12
4
45
68
VRS10
VRS20
单位:mm
□
×□
37 36
0061US
1. 前期准备
焊接操作必须由已授权人员进行实施。按照当前技术水平来仔细操作。在焊接和冷却阶段,音叉开关不可移动。表面必须无任何腐蚀。焊接工具必须适合连接件和管壁材料。
!
在管壁或者外壳壁钻一个孔,和适配器的外径一致。(最大超出0.2mm)如果可以,向适配器中拧入一个插头外盖。
2. 焊接操作
! 焊接设备的功率必须适用於外壁的厚度。
适配器对齐: 旋转标记 到音叉开关正面显示的位置;
扳手标记 供扳手可旋转的位置;
12
用足够的夹持力在若干点修复适配器,在对立面的相同距离应用修覆点。
在修覆点相互对立间应用焊键。在相互独立的区域间保证是有效的间隔(冷却阶段应避免由过热造成的透光或适配器翘曲)
3. 焊接后处理方式
让适配器冷却下来。
清理螺纹焊接残留物。
2
安装尺寸图
单位:mm
■ 焊接式卫生级适配器
39 38
4. 适用於卫生级音叉开关的焊接式适配器安装方式
用一个扳手将 拧紧,直到感觉已经达到了终点(这与最大扭矩35Nm一致)
注:进一步拧紧将会影响密封圈效果。
开关
将 拧入适配器,避免搅坏密封圈。
注意:若开关拧入螺纹内,并带有很大阻力,不要强迫这种拧法。如果不可能矫正螺纹,去掉此适配器,并且重新焊接一个新的。
开关
检查(A)处与(C)处是否有密封圈,缺一不可安装。
用润滑膏(B)涂抹开关螺纹。润滑膏必须通过应用批准,并且和弹性体的使用相兼容。
0062US
安装尺寸图
单位:mm
■ 卡盘式卫生级适配器
A
B
C
41 40
2. 安装连接
用安装工具(连接螺母、法兰夹具等)把音叉料位 和适配器固定连接。
开关
如果不能从适配器的顶端把螺母或法兰滑下来,那就在适配器被固定之前把螺母从底部滑上去。
1.适用於卫生级 的卡盘式适配器安装方式音叉开关
A
BC
将 拧入适配器,避免搅坏密封圈。
注意:若开关拧入螺纹内,并 带有很大阻力,不要强迫这种拧法。如果不可能矫正螺纹,去掉此适配器,并且重新焊接一个新的。
开关
检查(A)处与(C)处是否有密封圈,缺一不可安装。
用扳手 直到感觉已经达到了终点(与最大扭矩35Nm一致)注:进一步拧紧将会影响密封圈效果。
拧紧开关
将 和适配器固定在夹紧装置内。略微拧紧紧置装置,避免适配器扭曲变形。
开关
用润滑膏(B)涂抹开关螺纹。润滑膏必须通过应用批准,并且和弹性体的使用相兼容。
M VRT-CHT-V1.0-
智慧型音叉式料位开关说明书
VRT系列■中文繁体
IP 65
42
能
误
误
45 44
供电电压
开关时间
环境溫度
储藏 度溫
介质 度溫
操作压力
被测物料
连接方式
入线口直径
外壳材质
叉体材质
输出方式
功耗
20...60VDC NPN&PNP输出
<3秒
-40...+70°C
-40...+85°C
-40...+150°C
-1...+40 bar
通过学习功能,可适用任何粉末、颗粒和液体
G1½”A 镶件, ,法兰
M20 x 1.5
铝合金
高级不锈钢316L
继电器输出,负载AC250/4A DC60V/4A,
直流供电时3W Max. 交流供电时15W Max.
集电极开路(NPN)输出,负载400mA
集电极开路(PNP)输出,负载400mA
EMC ESD 6 kV
群脉冲 2 V k
20...60VDC 20...250VAC Relay输出
防护等级 IP65
单位:mm VRT10 标准型 VRT11 延长型
选购附件规格
S4F0 S0C0S4F0
117
8383
11
03
01
25
10
0
30
10
0
47 46
a
防止因进料冲击影响料位开关正常工作的防护板。
料位开关与周围物件及设备之间必须保留足够的安装与调试是空间。
防止在外罩内形成冷凝的防护罩。
b c
安装注意事项
49 48
音叉式料位开关说明书VRS 慧智 型
www.ema-electronic.com
M-VRS-CHT-V1.0
I P67 OilIP
50
禁止:破坏振动棒;折弯振动棒;截短振动棒;加长振动棒。
■
操作说明
4、学习模式:先将叉体放入待测介质中,稳定5秒。在解锁或解锁
后长按SET键3秒之后,红綠灯交替亮。在“红灯”亮时松开按
键,红灯1秒闪烁一次来表示等待确认学习。然后,按下“SET”
键,红灯亮灭2次表示正在学习,当红綠灯快速交替闪烁时,表
示学习成功。当红綠灯同时闪烁时,表示学习不成功。此时需
要重新学习,只要再次按下“SET”键,即进入第二次学习。
註:学习之后要在3秒之内按才能再次进入学习状态,否则须重
新选择学习模式,此功能为了防止 动作。
特别说明:
1、此智慧型音叉的学习功能,一方面是为了克服叉体安装於桶壁后
出现的吸振现象,另一方面是为了防止杂讯干扰,避免誤动作。32、产品的出厂设定值是以水的密度(1g/cm ),作为状态切換的基准,
3 当待测物的密度大於等於1g/cm 时,不需要重新学习即可正常使3 用。当待测物的密度小於1g/cm 时,则需要重新学习。
■ 端子图
图 B图 A
1、解锁:长按“SET”约10秒红綠灯交替亮,表示已经解锁並进入菜
单选择界面,红綠灯交替闪亮直到释放SET键为止。
2、锁定:在解锁状态下,若60秒内无按键按下,即自动锁定。
3、常开常闭的设定:在解锁或解锁后长按SET键3秒之后,红綠灯交
替亮,当在“綠灯”亮的时候释放按鈕即进入常开常闭设定模式,
此时单次按下“SET”键即可设定所需的状态。
3 / BU
2 / WH 1 / BN
5 / RE
4 / BK
白色線 棕色線
紅色線
藍色線 黑色線
■ 接線图
用生料带密封 用扳手拧紧 勿用手拧
状态指示电源指示
设定按钮
红色LED灯灭 红色LED灯亮
BN+
BK
WHNPN
PNP
BN+
BK
WH
RE
BU-
NPN
PNP RE
BU-
电源供应
负载
18~36VDC
200mA Max.
NPN/PNP输出:
BN+
BK
WH
RE
BU-
Relay
18~36VDC
Relay输出:
电源供应
负载 DC/AC 36V/1A
WH: 接地端子
LEARN/ SET
53 52
■ 状态指示图
最大值
最小值
綠色LED,电源指示灯
红色LED,工作状态指示灯
::
:
设定按钮::LEARN/ SET
■ 技术参数
供电电压 18...36VDC
开关时间 <1秒
环境溫度 -40...+70℃/-40...+158°F
储藏溫度 -40...+85℃/-40...+185°F
介质溫度 -40...+100℃/
连接方式 G¾"A
电气接口 M12 连接器
外壳材质 高级不锈钢316L
叉体材质 高级不锈钢316L
继电器输出,负载DC/AC 36V/1A
NPN/PNP输出,负载200mA
<1W (PNP/NPN 输出)
<2W (继电器输出)
输出方式
保护等级 IP 68
功耗
-40...+212°F
-40...+120℃/-40...+248°F
(145℃ max 1h)
类型 标准型 VRS10 卫生型 VRS20
IP 69K
操作压力 -1...+40bar
被测物料 通过学习功能,可适用任何粉末、颗粒和液体
55 54
a
正确安装:
顶部安装,振动棒垂直向下,可安装在顶部(远离进料口)的任何
位置。泡沫对料位开关无影响。
横向安装,以減少物料的冲击及挂料现象的发生。
横向安装,料位开关上方有挡板(长度约为10"(250mm),宽度约
为8"(200mm)),可防止(d)物料在料位开关周围的不当堆积,並
可降低物料对於料位开关的冲击。
安装於卸料斗内,料位开关螺牙底端与桶壁之间的最大距离不超
过2.4"(60mm),可避免因物料的不当堆积而发生误报警的情况。
不正确的安装:
水平安装在填充壁上或进料口下方。
安装角度不正确(振动棒的表面因承受进料和卸料的高负荷压力而
容易出现故障)。
1、安装时,可将开关以水平向下呈15~20度之夹 安装,以減少 物
料的冲击和掛料现象的发生。
2、安装时应尽可能远离桶槽的进料口以避免物料冲击和誤报警的发
生。如无法避免时,须在进料口与料位开关之间加装隔板保护。
3、接線盒入線口必须朝下,电源線入線口的固定螺母必须锁紧。
4、工作人员於桶槽内工作时,严禁利用振动棒攀爬或悬掛任何绳索
及物品。
■ 储存槽安装尺寸、实例及注意事项
b
c
d
e
f
在管道中安装:注意叉体和水流方向,以便开关在管道中正确安装。
□
×□
57 56
■ 外观图
单位:mm
38
45
12
4
45
68
VRS10
VRS20
单位:mm
0061US
安装尺寸图
单位:mm
■ 焊接式卫生级适配器
59 58
1. 前期准备
焊接操作必须由已授权人员进行实施。按照当前技术水平来仔细操作。在焊接和冷却阶段,音叉开关不可移动。表面必须无任何腐蚀。焊接工具必须适合连接件和管壁材料。
!
在管壁或者外壳壁钻一个孔,和适配器的外径一致。(最大超出0.2mm)如果可以,向适配器中拧入一个插头外盖。
2. 焊接操作
! 焊接设备的功率必须适用於外壁的厚度。
适配器对齐: 旋转标记 到音叉开关正面显示的位置;
扳手标记 供扳手可旋转的位置;
12
用足够的夹持力在某些点修复适配器,在对立面的相同距离应用修覆点。
在修覆点相互对立间应用焊键。在相互独立的区域间保证是有效的间隔(冷却阶段应避免由过热造成的透光或适配器翘曲)
3. 焊接后处理方式
让适配器冷却下来。
清理螺纹焊接残留物。
2
4. 适用於卫生级音叉开关的焊接式适配器安装方式
用一个扳手将 拧紧,直到感觉已经达到了终点(这与最大扭矩35Nm一致)
註:进一步拧紧将会影响密封圈效果。
开关
将 拧入适配器,避免搅坏密封圈。
注意:若开关拧入螺纹内,並带有很大阻力,不要强迫这种拧法。如果不可能矫正螺纹,去掉此适配器,並且重新焊接一个新的。
开关
检查(A)处与(C)处是否有密封圈,缺一不可安装。
用润滑膏(B)涂抹开关螺纹。润滑膏必须通过应用批准,並且和弹性体的使用相兼容。A
B
C
61 60
0062US
安装尺寸图
单位:mm
■ 卡盘式卫生级适配器
2. 安装连接
用安装工具(连接螺母、法兰夹具等)把音叉料位 和适配器固定连接。
开关
如果不能从适配器的顶端把螺母或法兰滑下来,那就在适配器被固定之前把螺母从底部滑上去。
1.适用於卫生级 的卡盘式适配器安装方式音叉开关
A
BC
将 拧入适配器,避免搅坏密封圈。
注意:若开关拧入螺纹内,並 带有很大阻力,不要强迫这种拧法。如果不可能矫正螺纹,去掉此适配器,並且重新焊接一个新的。
开关
检查(A)处与(C)处是否有密封圈,缺一不可安装。
用扳手 直到感觉已经达到了终点(与最大扭矩35Nm一致)註:进一步拧紧将会影响密封圈效果。
拧紧开关
将 和适配器固定在夹紧装置内。略微拧紧紧置装置,避免适配器扭曲变形。
开关
用润滑膏(B)涂抹开关螺纹。润滑膏必须通过应用批准,並且和弹性体的使用相兼容。
63 62