Manual Lms 4

Embed Size (px)

Citation preview

  • 8/13/2019 Manual Lms 4

    1/156

  • 8/13/2019 Manual Lms 4

    2/156

    All brand and product names are trademarks or registered trademarks of the ownerconcerned.

    Emergency On Call ServicePlease call your local representative:http://www.eaton.com/moeller/aftersalesorHotline of the After Sales Service:+49 (0) 180 5 223822 (de, en)[email protected]

    Original Operating InstructionsThe German-language edition of this document is the original operating manual.

    Translation of the original operating manualAll editions of this document other than those in German language are translations ofthe original German manual.

    1st published 2011, edition date 09/11

    2011 by Eaton Industries GmbH, 53105 Bonn

    Production: Thomas KrachtTranslation: globaldocs GmbH

    All rights reserved, including those of the translation.

    No part of this manual may be reproduced in any form (printed, photocopy, microfilmor any other process) or processed, duplicated or distributed by means of electronicsystems without written permission of Eaton Industries GmbH, Bonn.

    Subject to alteration without notice.

    http://www.eaton.com/moeller/aftersalesmailto:[email protected]?subject=Urgent%20Service%20Requestmailto:[email protected]?subject=Urgent%20Service%20Requestmailto:[email protected]?subject=Urgent%20Service%20Requestmailto:[email protected]?subject=Urgent%20Service%20Requesthttp://www.eaton.com/moeller/aftersales
  • 8/13/2019 Manual Lms 4

    3/156I

    Before commencing the installation

    Disconnect the power supply of the device.

    Ensure that devices cannot be accidentally restarted.

    Verify isolation from the supply.

    Earth and short circuit the device.

    Cover or enclose any adjacent live components.

    Follow the engineering instructions (AWA/IL) for thedevice concerned.

    Only suitably qualified personnel in accordance withEN 50110-1/-2 (VDE 0105 Part 100) may work on thisdevice/system.

    Before installation and before touching the device ensure that you are free of electrostatic charge.

    The functional earth (FE, PES) must be connected to theprotective earth (PE) or the potential equalisation. Thesystem installer is responsible for implementing thisconnection.

    Connecting cables and signal lines should be installed so that inductive or capacitive interference does not impair the automation functions.

    Install automation devices and related operating elementsin such a way that they are well protected againstunintentional operation.

    Suitable safety hardware and software measures shouldbe implemented for the I/O interface so that an opencircuit on the signal side does not result in undefinedstates in the automation devices.

    Ensure a reliable electrical isolation of the extra-lowvoltage of the 24 V supply. Only use power supply unitscomplying with IEC 60364-4-41 (VDE 0100 Part 410) orHD384.4.41 S2.

    Deviations of the mains voltage from the rated value mustnot exceed the tolerance limits given in the specifications,otherwise this may cause malfunction and dangerousoperation.

    Emergency stop devices complying with IEC/EN 60204-1must be effective in all operating modes of the automationdevices. Unlatching the emergency-stop devices must notcause a restart.

    Devices that are designed for mounting in housings orcontrol cabinets must only be operated and controlledafter they have been installed and with the housingclosed. Desktop or portable units must only be operatedand controlled in enclosed housings.

    Measures should be taken to ensure the proper restart ofprograms interrupted after a voltage dip or failure. Thisshould not cause dangerous operating states even for ashort time. If necessary, emergency-stop devices shouldbe implemented.

    Wherever faults in the automation system may causeinjury or material damage, external measures must be

    implemented to ensure a safe operating state in the eventof a fault or malfunction (for example, by means ofseparate limit switches, mechanical interlocks etc.).

    Depending on their degree of protection, frequencyinverters may contain live bright metal parts, moving orrotating components or hot surfaces during andimmediately after operation.

    Removal of the required covers, improper installation orincorrect operation of motor or frequency inverter maycause the failure of the device and may lead to seriousinjury or damage.

    The applicable national accident prevention and safetyregulations apply to all work carried on live frequencyinverters.

    The electrical installation must be carried out inaccordance with the relevant regulations (e. g. withregard to cable cross sections, fuses, PE).

    Transport, installation, commissioning and maintenancework must be carried out only by qualified personnel(IEC 60364, HD 384 and national occupational safetyregulations).

    Installations containing frequency inverters must beprovided with additional monitoring and protectivedevices in accordance with the applicable safetyregulations. Modifications to the frequency invertersusing the operating software are permitted.

    All covers and doors must be kept closed duringoperation.

    To reduce the hazards for people or equipment, the usermust include in the machine design measures that restrict the consequences of a malfunction or failure of the drive(increased motor speed or sudden standstill of motor).These measures include:

    Other independent devices for monitoring safety-related variables (speed, travel, end positions etc.).

    Electrical or non-electrical system-wide measures(electrical or mechanical interlocks).

    Never touch live parts or cable connections of thefrequency inverter after it has been disconnected from the power supply. Due to the charge in the capacitors, these parts may still be live after disconnection. Fitappropriate warning signs.

    E a t o n

    I n d u s t r

    i e s

    G m

    b H

    S a

    f e t y

    i n s t r u c t i o n s

    Danger!Dangerous electrical voltage!

  • 8/13/2019 Manual Lms 4

    4/156II

  • 8/13/2019 Manual Lms 4

    5/156

    09/11 MN03406003Z-EN

    1

    About this manual 5List of revisions 5Application notes 5Reading conventions 5Abbreviations and symbols 6 Units 6

    1 System Rapid Link 7System overview 8Checking the Delivery 9Ratings 10 Rating plate 10

    Key to part numbers RAMO 12 Key to part numbers RASP 13 General rated operational data 14Selection criteria 16Proper use 17 Designated power supply systems 17Maintenance and inspection 18Storage 18Internal DC link capacitors in RASP 18Service and warranty 18

    2 Engineering 19

    Rapid Link modules 19 Instance 20 Manual override switch 21 Power terminals 22Electrical power network 23 Mains connection and configuration 23 Mains voltage and frequency 23 Voltage balance 23 Total harmonic distortion (THD) 24 Idle power compensation devices 24 Mains chokes 24Safety and switching 25

    Fuses and cable cross-sections 25 Tripping currents at short-circuit 25 Power bus 26 Cable length 26 Residual current device (RCD) 27 Mains contactor 28EMC compliance 28Data bus ASi 29 Data cable 29 Data transfer 29 Head station 29 Accessing 29 Cable lengths and voltage drop 30Sensor inputs I3+I4 31Actuator output O3 32Fan connection F 32Motor and Application 33 Motor Selection 33

    Contents

  • 8/13/2019 Manual Lms 4

    6/156

    Contents 09/11 MN03406003Z-EN

    2

    Motor and circuit type 33 Automatic deceleration time extension on RASP 33 Change of rotation 33 Quick stop 34 Interlocked manual mode 35

    3 Installation 37Introduction 37Installation instructions 37 Mounting position 37 Free space 38 Fixing 38 Arrangement of power terminals 40Electrical Installation 41 Power bus 41

    Notes on replacing devices 49Functional earth on RASP 51 Data bus 52 Cable routing 52 Insulation test 53 Rapid Link modules 53

    4 Operation 55Checklist for commissioning 55Operational hazard warnings 56 Manual control 59 Commissioning the drive 59

    5 Motor starter RAMO 61Designation 61Features 61Connections 62Special technical data 63Operation 66 LED indicators 66Adjust dip switch 68 Current monitoring (DIP 1 - 4) 68 Current lower limit 68

    Sensor inputs I3 + I4 (DIP 5) 69 Quick stop and interlocked manual mode (DIP 6 + 8) 69 Phase reversal switch (DIP 7) 70 Monitoring the current lower limit (DIP 9) 70 AS-interface diagnostics (DIP 10) 70 Reading out the diagnostic status via the AS-Interface

    parameter channel 70

    6 RASP speed controllers 73Designation 73Features 73Connections 74

    Special technical data 75Operation 78 LED indicators 78Adjust dip switch 80 Thermistor and motor cable monitoring (DIP 1) 80

  • 8/13/2019 Manual Lms 4

    7/156

    09/11 MN03406003Z-EN Contents

    3

    AS-interface diagnostics (Pol 2) 81Diagnostics and error handling 81Automatic configuration for servicing 82 I/O configuration 82 Sensor inputs I3 + I4 (DIP 3) 83 Quick stop and interlocked manual mode (DIP 4 - 6) 83 Phase reversal switch (DIP 7) 84 Internal link 85 Configuring stop behaviour (DIP 8) 85 Summary 86Parameters 87 Parameter setting 87 Change parameter values 93 Parameterization with optional LCD keypad RASP-KEY-

    S1 93 LCD keypad RASP-KEY-S1 94

    Display unit 95 General information on menu navigation 95 Select parameters 97Basis parameters 99 Drives control (P6) 101 Motor (P7) 105 Protective functions (P8) 106 Fixed frequency setpoint value (P10) 107 U/f-characteristic curve (P11) 109 Braking (P12) 114 System parameter 117Operational data indicator (MON) 119

    Error and Warning messages (FLT) 121 Introduction 121 Error Messages 121 Acknowledge error message (Reset) 121 Fault log (FLT) 122 Alarm messages 122Setpoint input (REF) 123

    Appendix 125Dimensions 125 Rapid Link System 4.0 125Accessories 127

    Device fan RASP-FAN-S1 127 Connection cable XMX-CBL-3M4-USB 128 Optional keypad RASP-KEY-S1 129Parameter lists 130 Basis parameters (P1.1 = 1) 130 Experts parameters (P1.1 = 0) 136

    Index 149

  • 8/13/2019 Manual Lms 4

    8/156

    09/11 MN03406003Z-EN

    4

  • 8/13/2019 Manual Lms 4

    9/156

    09/11 MN03406003Z-EN

    5

    About this manual

    The subsequent chapters provide special information needed toconfigure, install and operate these Rapid Link function modules.

    List of revisions

    This manual has been fully revised with edition 09/11.

    Application notes

    Read this manual carefully, before you install the Rapid Linksystem and start using it. We assume that you are familiar withbasic physical concepts and are experienced in reading technicaldrawings and dealing with electrical equipment.

    Reading conventionsThe symbols used in this manual have the following meanings:

    X indicates actions to be taken.

    In order to make it easier to follow the manual, the name of thecurrent chapter is shown on the header of the left-hand page andthe name of the current section in shown on the header of theright-hand page. This does not apply to pages at the start of achapter or to empty pages at the end of a chapter.

    This manual is based on system manualAWB2190-1430. It contains descrip-tions for version RA 4.0 of functionmodules RAMO and RASP.

    h To incorporate RAMO and RASP version 4.0 in existingRapid Link systems of versions up to 3.0, additionalconfiguration and engineering are required.

    a

    h Indicates useful tips and additional information.

    h Caution!Warns of a hazardous situation that could result indamage to the product or components.

    iWarning!Warns about the possibility of serious property damageand minor injuries.

    j Danger!Warns about the possibility of major property damageand serious injuries or death.

    h To make it easier to understand some of the figuresincluded in this manual, the housing and other safety-relevant parts have been left out. The componentsdescribed here must be used only with a fitted enclosureand all necessary safety-relevant parts.

    h Please follow the notes in the IL03406019Z andIL03406020Z instructional leaflets.

    h All the specifications in this manual refer to the hardwareand software versions documented in it.

    h More information on the series described here can befound on the Internet under:

    www.moeller.netA SupportA Download Center

  • 8/13/2019 Manual Lms 4

    10/156

    09/11 MN03406003Z-EN

    6

    Abbreviations and symbols

    The following symbols and abbreviations are used in this manual:

    Units

    Every physical dimension included in this manual uses interna-tional metric system units, otherwise known as SI (Systme Inter-national dUnits) units. For the purpose of the equipment's ULcertification, some of these dimensions are accompanied by theirequivalents in imperial units.

    Tabelle 1: Unit conversion examples

    DIP Dual in-linepackage (microswitch)EMS Electronic Motor Starter

    EMC Electromagnetic compatibility

    ESD Electrostatic discharge

    Fct No. Function number

    FWD Clockwise rotating field (forward)

    LAS List of active stations

    LCS List ofCorruptedStation s

    LDS List of deactivated stations

    LOS List of offline stationsLPS List ofConfiguredStations

    PELV Functional low voltage with safe isolation(Protective Extra Low Voltage)

    REV Anticlockwise rotating field (reverse)

    PES Functional earth,PE - positiveearth cablescreenconnection

    PNU ParameterNumber

    DS Default s ettings

    The AS-Interface (Actuator-Sensor-Interface) logo isapplied to components that comply with standardsEN 50295 and IEC 6026-2.

    The DESINA logo (DEcentralized andStandardizedINstAllation technology) is applied here to compo-nents conforming to with the DESINA specification([email protected]).

    Designation US-American value SI value Conversion value US-Americandesignation

    Length 1 inch () 25.4 mm 0.0394 inch

    Power 1 HP = 1.014 PS 0.7457 kW 1.341 horsepower

    Torque 1 lbf in 0.113 Nm 8.851 pound-force inches

    Temperature 1 F (TF) -17.222 C (TC) TF = TC x 9/5 + 32 FahrenheitSpeed 1 rpm 1 min-1 1 Revolutions per minute

    Weight 1 lb 0.4536 kg 2.205 pound

  • 8/13/2019 Manual Lms 4

    11/156

    09/11 MN03406003Z-EN

    7

    1 System Rapid Link

    Rapid Link 4.0 is a modern, efficient drive and automation system.It is suitable for both simple and complex tasks in all materialhandling applications, but specially in horizontal conveyingsystems. Because the Rapid Link modules can be fitted into apower and data bus, it allows electrical drives to be installed andtaken into operation much more quickly and cost-efficiently thanwith conventional methods.

    Equipped with a power bus and data bus that are plugged intoeach Rapid Link module, the system is quick and easy to install.

    Customer and sector-specific requirements for material handlingapplications are the main focus of the innovative Rapid Linksystems design.

    The Rapid Link modules of the latest version, 4.0, provide tailoredsolutions with the following features:

    Protection type IP65, AS-Interface for communication and diagnostics, Plug-in terminal type to ISO 23570, Local operation/hand operation, Maintenance and manual override switches (optional), Electronic DOL and reversing starter RAMO, RASP frequency controlled speed control.

  • 8/13/2019 Manual Lms 4

    12/156

    System Rapid Link 09/11 MN03406003Z-EN

    8

    System overview

    Figure 1: Overview Rapid Link Module RA 4.0

    Function modules:a Motor starter RAMO (motor control unit)

    r Three-phase electronic DOL starter or reversing starter

    b Speed control unit RASPr Three-phase, frequency-controlled motor starter (fixed speeds, bidi-rectional, soft starting)

    Power bus:c Energy supply (3 AC 400 V) via circuit-breaker for overload and short-

    circuit protectiond Incoming supply for ribbon cablee Ribbon cable fr 400 V ACf End-piece for flat cableg Flexible busbar junction

    h Power adapter cable to flexible busbar junctioni Round cable for 400 V AC

    j Plug-in link for round cablek Power adapter cable to round cable junctionl Link for round cablem Power adapter cable (round cable) to power boxn AS-Interface supply via main cable

    Data bus:o AS-Interface flat cablep Link for M12 connector cablesq Extension M12

    Motor connection:r Unscreened motor cables Screened motor cable (EMC)

    3 400 V, N, PE50/60 Hz

    400 VM

    3

    400 VM

    3

  • 8/13/2019 Manual Lms 4

    13/156

    09/11 MN03406003Z-EN Checking the Delivery

    9

    Checking the Delivery

    RAMO and RASP are packaged and dispatched carefully. Thedevices should be shipped only in their original packaging withsuitable transportation materials. Please observe the labels andinstructions on the packaging and for handling the unpackeddevice.

    Open the packaging with adequate tools and inspect the contentsimmediately after receipt in order to ensure that they are completeand undamaged.

    The packaging must contain the following parts:

    Motor Control Unit RAMO-D or RAMO-W the instructional leaflet IL03406019Z.

    Speed Control Unit RASP-2, RASP-3, RASP-4 or RASP-5 the instructional leaflet IL03406020Z.

    h Before opening the packaging go over the nameplate on

    the packaging and check for whether the supplied compo-nent is the same type as the one you ordered (a section"Rating plate packaging, page 10).

    Figure 2: Equipment supplied (RAMO or RASP plus installation instructions)

  • 8/13/2019 Manual Lms 4

    14/156

    System Rapid Link 09/11 MN03406003Z-EN

    10

    Ratings

    The device-specific rated operational data of RAMO or RASP areprinted on the nameplate on the devices side.

    Rating plate

    Rating plate packagingExample: Motor starter

    Example: speed controller

    Rating plate position

    #

    RAMO-D02AI1S-C320S1

    INPUT/OUTPUT: 3~AC, Ue=400V, 50/60Hz

    POWER: 0,09..3kW/400V

    Made in Germany

    Article No. 150152

    IP 650-series01W11Release 00

    Slave ProfileS-7.4

    RASP-212AI1S0-C320S1

    Made in Germany

    Article No. 150180

    IP 650-series01W11Release 00

    Slave ProfileS-7.4

    INPUT: 3~AC, 3,2A, Ue=380-480V, 50/60HzOUTPUT: 3~AC, 2,4A, 0-Ue, 0-320HzPOWER: 0,75kW/400V

    RAMO-D02AI1S-C320S1 IEC/EN 60947-4-2IEC/EN 60947-5-1

    Made in Germany

    Slave ProfileS-7.4

    Article No. 150152INPUT/OUTPUT: 3AC, N, PE, Ue=400V, 50/60HzPOWER: 0,09..3kW/400V6,6A : AC 53a : 6-1,6 : 60-1S/N xxxx; wwWyy; Release 01

    RASP-212AI1S0-C320S1 IEC/EN 61800-3IEC/EN 61900-5-1

    Made in Germany

    Slave ProfileS-7.4

    Article No. 150180INPUT: 3AC, 3,2A, Ue=380-480V, 50/60HzOUTPUT: 3~AC, 2,4A, 0-Ue, 0-320HzPOWER: 0,75kW/400VS/N xxxx; wwWyy; Release 01

  • 8/13/2019 Manual Lms 4

    15/156

    09/11 MN03406003Z-EN Ratings

    11

    Nameplate dataThe inscription of the nameplates has the following meaning(example):

    Inscription Meaning

    RASP-202AI1S0-C320S1 Part no.:RASP = Speed controller (Speed ControlUnit)2 = 2.4 A, rated operational current0 = No built-in braking resistance2 = 230 V AC, control voltage for externalmotor brakesAI1 = AS-Interface profile 7.4S0 = -10 - +55 C, without fanC32 = Plug-in power connectors, atbottom

    0 = No option (standard equipment)S1 = Standard version

    Article no. 150181 Article No

    INPUT Power connection rating: Three-phase alternating current, 3~ AC, Input phase current 4.0 A, Voltage Ue = 380 - 480 V, Frequency 50 60 Hz.

    OUTPUT Load side (motor) rating: Three-phase alternating current, 3~ AC, Output phase current 3.3 A, Output voltage 0 - Ue

    Output frequency 0 - 320 Hz. POWER Assigned motor rating.

    1.1 kW at 400 V/1.5 HP at 460 V for a four-pole internally-cooled or surface-cooledthree-phase asynchronous motor. (1500rpm at 50 Hz/ 1800 rpm at 60 Hz).

    0-Series Serial number

    01W11 manufacturing dateWeek 01 of 2011.

    Release 00 Version 00

    Station profileS-7.4

    AS-InterfaceProfile 7.4

    IP65 Protection type of the housing: IP65

  • 8/13/2019 Manual Lms 4

    16/156

    System Rapid Link 09/11 MN03406003Z-EN

    12

    Key to part numbers RAMO

    The key to part numbers and the part no. of the motor starterRAMO are in the following order:

    Figure 3: Key to part numbers of RAMO motor starter

    RAMO - D 0 2 AI1 S - C32 0 S1 Description

    S1 = Standard version

    Kx = Customer-specific version (x = ID code)

    0 = No option (standard version)

    R = manual override switch

    C31 = Plug-in power connections, at right side

    C32 = Plug-in power connections, at bottom

    C33 = Plug-in power connections, at left side

    S = -10 - +55 C ambient air temperature during operation

    C = -30 - +55 C ambient air temperature during operation

    AI1 = AS-Interface, profile 7.4

    0 = No actuation for motor brakes

    2 = 230 V AC control voltage for external motor brakes

    0 = No control output

    A = Actuators output

    D = DOL starter

    W = Reversing starter

    RAMO = Motor starter (Motor Control Unit)

  • 8/13/2019 Manual Lms 4

    17/156

    09/11 MN03406003Z-EN Ratings

    13

    Key to part numbers RASP

    The key to part numbers and the part no. of the RASP speedcontroller are in the following order:

    Figure 4: Key to parts numbers of the RASP speed controller

    RASP - 2 0 2 AI1 S 0 - C32 0 S1 Description

    S1 = Standard version

    Kx = Special version (x = ID code)

    0 = No option (standard version)

    R = manual override switch

    C31 = Plug-in power connections, at right side

    C32 = Plug-in power connections, at bottom

    C33 = Plug-in power connections, at left side

    0 = No fan

    L = fan

    S = -10 - +40 C ambient air temperature during operation

    C = -30 - +40 C ambient air temperature during operation

    AI1 = AS-Interface, profile 7.4

    0 = No actuation for motor brakes

    2 = 230 V AC control voltage for external motor brakes

    0 = No braking resistance

    1 = With built-in braking resistance

    2 = 2.4 A rated operational current 3 = 3.3 A rated operational current

    4 = 4.3 A rated operational current

    5 = 5.6 A rated operational current

    RASP = Speed controller (Speed Control Unit)

  • 8/13/2019 Manual Lms 4

    18/156

    System Rapid Link 09/11 MN03406003Z-EN

    14

    General rated operational data

    Technical data Formulasign

    Unit Value

    RAMO RASP

    General

    Standards IEC/EN 60947-4-2 IEC/EN61800-3

    IEC/EN 60947-5-1 IEC/EN61800-5-1

    IEC/EN 61000-6-2

    IEC/EN 61000-6-4

    Approvals, certificates CE

    Production quality RoHS, ISO 9001

    Protection type (IEC/EN 60529) IP65Mounting position vertical (a page 37)

    Ambient air temperature

    Operation i oC -10 - +55 -10 - +40

    Storage i oC -30 - +70 -30 - +70

    Installation altitude H m 0 to 1000 a.s.l., above 1000 m with 1% performance reduction per 100 m,up to 2000 m.

    Humidity (IEC/EN 50178) pw % < 95 %, relative humidity, non-condensing

    Air quality

    Vibration (IEC/EN 60068-2-6) 6, constant amplitude 0.15 mm/const. acceleration 2 g 3 150 Hz, oscillation amplitude1 mm (Peak) at 3 to 15.8 Hz,maximum acceleration amplitude2 g at 15.8 to 150 Hz

    Mechanical shock resistance (IEC/EN60068-2-27)

    1000 shocks per axis Storage and transport: 15 g, 11 ms(in the packaging) UPS drop test

    Main circuit

    Feeder

    Rated operational voltage Ue V 3 AC 400 3 AC 400

    Rated operating voltage for brakecontrol (RAMO-Dx2,

    RASP-Wx2, RASP-xx2)

    Ue V 230 230

    Voltage levels ULN V 400 - 15 % to 415 + 10 % 380 - 15 % to 480 + 10 %

    Frequency range f LN Hz 50/60(47 - 63 Hz 0 %)

    50/60(45 - 66 Hz 0 %)

    System configuration Alternating voltage, center-point-earthed star network (TN-S network)Phase-earthed AC supply systems are not permissible.

    Mains switch-on frequency Number max. one time per minute

    Mains current THD % > 120

    Short-circuit current IK kA < 50

    Short-circuit protective device, type 1coordination (incoming unit power bus)

    RA-DI (Disconnect Control unit)PKZ/ZM25-8FAZ-3-B20 or FAZ-3-C20

  • 8/13/2019 Manual Lms 4

    19/156

    09/11 MN03406003Z-EN Ratings

    15

    1) Plus power supply for connected actuators (I3 + I4)

    2) Assigned motor rating for normal internally and externally ventilatedthree-phase asynchronous motors with 1500 rpm (at 50 Hz) or 1800rpm (at 60 Hz).

    Overvoltage category/degree of pollu-tion (DIN/VDE 0110)

    III/2 III

    Rated impulse withstand voltage Uimp kV 4 -

    Leakage current to PE earth (EN 50178) IPE m A - > 3.5

    Power section

    Instance RAMO-D: DOL starter with thyris-torsand bypass contacts

    Frequency inverter with internal DClink and IGBT inverter

    RAMO-W: Reversing starter withrelays, thyristors and bypasscontacts

    two-phase controlled

    Switch-on delay t ms 25 -

    off-delay t ms 35 -

    lifespan Number > 10 millions connections -

    Output voltage U2 V AC = ULN 0 - ULN

    Output frequency f 2 Hz = f LN 0 - 50 Hz,max. 320 Hz

    Rated operational current Ie A 6.6 2.4 - 3.3 - 4.3 - 5.6

    Adjustable motor protection I A 0.3 - 6.6 0.48 - 11.2

    Overload withstand capabilityFor 60 s every 600 s at +40oC IL A - 3.6 - 8.4

    For 2 s every 20 s at +40oC IL A - 4.8 - 11.2

    Allocated motor output (with motorprotection)

    - at 400 V, 50 Hz P2) kW 0.09 - 3 0.18 - 2.2

    - at 460 V, 60 Hz P2) HP - 1/2 - 3

    Control Voltage

    External control voltage for actuators(O3)

    U V 24 -

    Tolerance % -15 bis 20AS-Interface Specification

    Max. total power consumption from AS-Interface power supply unit (30 V)

    I m A 1601)

    Specification 7.4

    Station addresses Number 31

    I/O Codeor I/O configuration

    7 (hex)

    ID-code 4 (hex)

    Technical data Formulasign

    Unit Value

    RAMO RASP

  • 8/13/2019 Manual Lms 4

    20/156

    System Rapid Link 09/11 MN03406003Z-EN

    16

    Selection criteria

    Select RAMO or RASPc according to supply voltage ULN of thesupply systema and the rated operational current of the assignedmotorb . The motors circuit type (D or Y ) must be selectedaccording to the supply voltagea . The RASPs rated outputcurrent Ie must be greater than or equal to the rated motor current.For RAMO, current monitoring must be set to the rated motorcurrent.

    When selecting the drive, the following criteria must be known:

    Type of motor (three-phase asynchronous motor) Mains voltage = rated operating voltage of the motor

    (e.g. 3 AC ~ 400 V), Rated motor current (recommended value, dependent on the

    circuit type and the supply power supply) Load Torque, Starting torque, Ambient air temperature (rated value +40 C).

    Figure 5: Selection criteria

    h Caution!Do not connect or disconnect power connectors (mains,motor) while RAMO and RASP are operational.

    230 / 400 V / 4.6 / 2.61.1 0.81coskW

    min-11430 50 Hz

    A

    U, I, f

    h When connecting multiple motors in parallel to the output

    of the RAMO and RASP, the motor currents are addedgeometrically separated by effective and idle currentcomponents. When you select a RAMO and RASP, makesure that they can supply the total resulting current. Ifnecessary, for dampening and compensating the devi-ating current values, motor reactors or sinusoidal filtersmust be connected between RAMO or RASP and themotor.

    For parallel operation of several motors on the output ofa RASP or RAMO separate motor protection (e.g. a therm-istor) is required.

    h RASP onlyThe parallel connection of multiple motors in the outputof the RASP is only permitted with U/f-characteristiccontrol.

    Speed control with slip compensation (P11.8) increasesthe drive dynamics and optimizes the output. With thisfunction the frequency inverter calculates an electronicimage of the motor.

    In this operating mode only one motor can be operated onan output of the RASP. The motors rated current must beassigned to the rated operational current of the frequencyinverter (same rating).

  • 8/13/2019 Manual Lms 4

    21/156

    09/11 MN03406003Z-EN Proper use

    17

    Proper use

    Designated power supply systems

    Observe the instructions in this manual regarding physical and elec-trical layout, and commissioning and operation:

    Rapid Link must be operated only on 400V-three-phase systemswith earthed star point and separate N and PE conductors (TN-S network). It must not be operated unearthed.

    All Rapid Link function modules fulfil the safe isolation require-ments of IEC/EN 60947-1, Annex N, between the AS-Interfacevoltage and the 24 Vh and 400 Vh supplies.

    The thermistor circuits of RAMO and RASP have a double basicinsulation.

    All devices connected to the power and data bus must alsomeet the requirements for safe isolation according to IEC/EN 60947-1 Annex N or IEC/EN 60950. The 24 V DC powersupply unit must be earthed on the secondary side. The 30 V DCPSU for the AS-Interface power supply (interface control unit)must meet the safe isolation requirements according to SELV.

    Emergency switching off devices (to IEC/EN 60204-1, corre-sponds to DIN VDE 0113, part 1) must be present. Their func-tion must not be impaired in any way.

    Effective lightning protection measures must be implemented inthe plant to prevent damage to electronic components.

    RAMO and RASP are not devices for household use, and aredesigned exclusively for use in commercial applications.

    RAMO and RASP are electrical apparatus for controlling variable

    speed drives with three-phase motors. They are designed forinstallation in machines or for use in combination with othercomponents within a machine or system.

    After installation in a machine, the RAMO and RASP must not betaken into operation until the associated machine has beenconfirmed to comply with the safety requirements of MachinerySafety Directive (MSD) 89/392/EEC (meets the requirements ofEN 60204). The user of the equipment is responsible for ensuringthat the machine use complies with the relevant EU Directives.

    The CE markings applied to RAMO and RASP confirm that, whenused in a typical drive configuration, the apparatus complies withthe European Low Voltage Directive (LVD) and the EMC Directives(Directive 73/23/EEC, as amended by 93/68/EEC and Directive 89/336/EEC, as amended by 93/68/EEC).

    A connection to IT networks (networks without reference to earthpotential) is not permissible , since the devices built-in filtercapacitors connect the network with the earth potential (enclo-sure).

    The technical data and connection conditions must be observed.For additional information, see the nameplate of RAMO or RASPand the documentation.

    Any other usage constitutes improper use.

    j Danger!Incorrect engineering, installation, maintenance andoperation of the entire plant or machine, non-observationof the instructions in this manual and modifications byinsufficiently qualified persons can cause danger fromconnected actuators such as motors, hydraulic units etc.

    h Rapid Link is intended only for switching, protecting, andcontrolling three-phase motors in machines and plants. Anyother use is not proper use.

    The vendor does not accept liability for damage resultingfrom use other than the stated proper use.

    h At the output of RAMO and RASP (a section "Motorfeeder, page 45) you must not:

    connect a voltage or capacitive loads (e.g. phasecompensation capacitors),

    connect multiple RAMO and RASP in parallel, make a direct connection to the input (bypass).

  • 8/13/2019 Manual Lms 4

    22/156

  • 8/13/2019 Manual Lms 4

    23/156

    09/11 MN03406003Z-EN

    19

    2 Engineering

    Rapid Link modulesRapid Link modules RAMO and RASP are installed in the directvicinity of the drives. Their versions and mounting depend on therequired specifications and the local conditions. They can beconnected to the power and data bus at any point without havingto interrupt the bus. The below example with RAMO provides asimplified overview.

    a Sensor (light barriers)b RAMOc Motor connection cabled Power supply on power buse AS-Interface

    a

    b

    c

    d

    e

    e

  • 8/13/2019 Manual Lms 4

    24/156

    Engineering 09/11 MN03406003Z-EN

    20

    Instance

    External appearance of various versions (see for exampleSectionKey to part numbers RAMO, page 13)

    RAMO-WA-C32R : Reversing starter with Manual override switch; Plug-in power terminals at bottom, Actuator output O3

    RAMO-D-C320 : DOL starter with plug-in power terminals at bottom.

    RAMO-W-C310 : Reversing starterwithplug-in power terminals on right side.

    RASP-0-C320: Speed control with plug-in power terminals at bottom.

    RASP-L-C320 : Speed control with plug-in power terminals at bottom, with fan.

    Base without manual overrideswitch

    Base without manual override switch

    45 70

  • 8/13/2019 Manual Lms 4

    25/156

    09/11 MN03406003Z-EN Rapid Link modules

    21

    Manual override switch

    Versions RAMO-C3xR and RASP-C3xR feature a manualoverride switcha , which isolates all three phases of the Rapid

    Link modules from mains voltage.

    The contactor state of the manual override switch is shown in theillustration below.

    Figure 7: RAMO and RASP versions -C32R

    Contactor state 0 (= OFF) can be locked by pulling out the red

    locking collar padlocking device. If required, up to three padlockswith a yoke diameter of 7 mm or up to four padlocks with a yokediameter of 5 mm can be engaged in the cutout of the padlockingdevice.

    After completion of maintenance or repair work, the switch can bereleased again and returned to position I (= ON). The motor can

    then be restarted with a start signal in manual or automatic mode.

    Figure 6: Maintenance switch in position 0 = OFF

    h Before operating the manual override switch, the motormust have stopped.

    j Danger!For RASP the capacitor discharging time (at least fiveminutes) must be observed. This applies also for handlingthe motor.

    1

    4 35

    2

    e

    1 2 3

    L1 L2 L3 PE

    5 4

    N

    a

    e

    = 7 mm 3 x = 5 mm 4 x = 0.28 3 x = 0.20 4 x

    0 = OFF I = ON

  • 8/13/2019 Manual Lms 4

    26/156

    Engineering 09/11 MN03406003Z-EN

    22

    Power terminals

    Plug-in connections in power section for RAMO and RASP.

    a 5-pole power plug (3 AC 400 V, N, PE)

    b Motor feeder socket (DESINA)

    c Hazard warning, only RASP

    Figure 8: Example RAMO Figure 9: Example RASP

    a b

    ca b

    PIN Function

    1 L1

    2 L2

    3 L3

    4 N

    5

    PE PE

    PIN Function

    1 U1

    2 Coding adapter3 W 1

    4 Brake N (B1)

    5 Thermistor 1

    6 Brake L(230 Vh , B2)

    7 V1

    8 Thermistor T2

    PE PE

    1

    4 35

    2

    e

    1 4 6

    3 5 8PE 7

    j Danger!Dangerous voltage from internal DC link capacitors(observe discharge time)

    Pay attention to hazard warnings!

    DANGER5 MIN

  • 8/13/2019 Manual Lms 4

    27/156

    09/11 MN03406003Z-EN Electrical power network

    23

    Electrical power network

    Mains connection and configurationThe Rapid Link modules RAMO and RASP can be connected andoperated with all control-point grounded AC power networks (seeIEC 60364 for more information in this regard).

    The connection and operation of frequency inverters to asymmet-rically grounded TN networks (phase-grounded Delta network"Grounded Delta", USA) or non-grounded or high-resistancegrounded (over 30O ) IT networks is not permissible.

    Mains voltage and frequency

    The standardized rated operating voltages (IEC 60038, VDE017-1)for power suppliers (EVU) guarantee the following conditions at

    the transition points: Deviation from the rated value of voltage:

    maximum 10 % Deviation in voltage phase balance: maximum 3 % Deviation from rated value of the frequency:

    maximum 4 %

    The broad tolerance band of the RASP considers the rated value forEuropean as (EU: ULN = 230 V/400 V, 50 Hz) andAmerican as (USA: ULN = 240 V/480 V, 60 Hz) standard voltages:

    400 V, 50 Hz (EU) and 480 V, 60 Hz (USA)

    For the bottom voltage value, the permitted voltage drop of 4 %in the consumer circuits is also taken into account, therefore atotal of ULN - 14 %:

    380 V -15 % - 480 V +10 % (323 V -0 % - 528 V +0 %)

    The permitted frequency range in all voltage ranges is 50/60 Hzhere (45 Hz - 0 % 66 Hz + 0 %).

    Voltage balance

    Because of the uneven loading on the conductor and with thedirect connection of greater power ratings, deviations from theideal voltage form and asymmetrical voltages can be caused inthree-phase AC power networks. In consumers with a three-phasesupply, these asymmetries in the mains voltage can result inuneven loading of of the input phases and therefore to a prema-ture failure of downstream semiconductors, such as diodes inmains rectifiers or thyristors EMS.

    If this condition is not fulfilled, or symmetry at the connection loca-tion is not known, the use of a main choke in the mains-side feederunit of the power bus is recommended.

    Figure 10: AC power networks with grounded center point (TN-/TTnetworks)

    h Measures for electromagnetic compatibility are manda-tory in a magnet system, to meet the legal standards forEMC- and low-voltage regulations.

    Good grounding measures are a prerequisite for the effec-tive insert of further measures such as screen earth kit orfilters here. Without respective grounding measures,further steps are superfluous.

    L2

    N

    L1

    L3

    PE

    L2

    PEN

    L1

    L3

    h RAMO is currently available only for European standardvoltage:

    EU: ULN = 230 V/400 V for 50/60 Hz

    h RAMO is currently available only for:

    380 V -15 % - 415 V +10 %(323 V -0 % - 456 V +0 %)

    h In the project planning consider only AC power networksthat handle permitted asymmetric divergences in themains voltageF +3 %.

  • 8/13/2019 Manual Lms 4

    28/156

    Engineering 09/11 MN03406003Z-EN

    24

    Total harmonic distortion (THD)

    The THD (Total Harmonic Distortion) is a measurement for theoccurring harmonic distortion of the sinusoidal oscillation (mains

    power side) input variables. It is given in percent of the total value.

    With the RASP Rapid-Link modules, the permitted value for thetotal harmonic distortion THD >120 %.

    Idle power compensation devices

    Compensation on the power supply side is not required for theRAMO and RASP Rapid-Link modules.

    Mains chokes

    A main choke (also called commutation choke) increases thereactor of the power supply line. This extends the current flow

    period and dampens mains deviations.On RASP, a main choke limits the mains feedback to permissiblevalues. The harmonic current emissions that are fed back into themains network ("mains feedback") are reduced. This reduces themains-side apparent current to about 30 %.

    Main chokes attenuate interference from the supply systemtowards RAMO and RASP. This increases the electric strength ofRapid Link modules RAMO and RASP and extends their lifespan.

    Main chokes are designed based on the mains-side input current(ILN) of Rapid Link power bus.

    U1 = fundamental componentTHD k = 0.1l K = 10 % ~ -20 dB (THD suppression)

    THD (Total Harmonic Distortion)

    h In the AC power networks with non-choked reactivecurrent compensation devices, current deviations canenable parallel resonance and undefinable circumstances.

    In engineering the connection of RAMO and RASP to ACsupply systems with undefined conditions, consider usingmain chokes in the power bus feeder unit.

    K U

    22

    U+3

    2U

    42

    Un

    + + 2

    +

    U1

    2U+

    2

    2U

    32

    U4

    2 U

    n+ +

    2+ +

    ------------------------------------------------------------------------------------------- 100%=

    TH DU

    22

    U+3

    2U

    42

    Un

    + +2

    +

    U 1

    ------------------------------------------------------------------------------=

    h For the operation of RAMO and RASP, the application ofmain choke is not necessary. We do recommend howeverthat an upstream main choke is used since the networkquality is not known in most cases.

    While planning the project, consider that a main choke isonly assigned to a single Rapid Link power bus for decou-pling.

    When using an adapting transformer a main choke is notnecessary.

  • 8/13/2019 Manual Lms 4

    29/156

    09/11 MN03406003Z-EN Safety and switching

    25

    Safety and switching

    Fuses and cable cross-sectionsThe fuses and wire cross-sections allocated for power-side connec-tions depend on the rated mains current ILN of the Rapid Linkpower bus (without mains reactor).

    The national and regional standards (for example VDE 0113,EN 60204) must be observed and the necessary approvals (forexample UL) at the site of installation must be fulfilled.

    When the device is operated in a UL-approved system, use onlyUL-approved fuses, fuse bases and cables.

    The leakage currents to ground (to EN 50178) are greater than3.5 mA. The connection terminals marked PE and the housingmust be connected with the earth-current circuit.

    The cross-sections of the cables and cable protection fuses usedmust correspond with local standards.

    For an installation in accordance with UL Standards, the fuses andcopper cable that are UL-approved and have a heat-resistance of+60/75 C are to be used.

    For a permanent installation with insulation, use power cablesthat are suitable for the specified mains voltages.

    For RASP a fully (360) shielded low-impedance-screened cable on

    the motor side is required. The length of the motor cable dependson the RFI class and must not exceed 10 m for RASP.

    Tripping currents at short-circuit

    The tripping current must also be reliably reached in the event ofa short-circuit in one pole. Make sure that the total current of allmotors (including starting currents) or the charging current of allconnected speed control units RASP remains smaller than the trip-ping current when mains power is switched on.

    Example: Disconnect Control Unit RA-DI.

    Instead of the disconnect control unit RA-DI, you can use a 3-poleminiature circuit-breaker In F 25 A and B or C characteristic.Here, you must observe the following:

    The let-through energy I2t in the event of a short-circuit mustnot exceed 29800 A2s.

    Therefore the short-circuit current Icc at the mounting locationmust not exceed 10 kA (a characteristic curveFigure 11).

    h Attention! When selecting the cable cross-section, take the voltagedrop under load conditions into account.The consideration of other standards (e.g. VDE 0113 orVDE 0289) is the responsibility of the us-er.

    h Caution! The specified minimum PE conductor cross-sections (EN 50178, VDE 0160) must be maintained.

    h Choose the cross-section of the PE conductor in the motorlines at least as large as the cross-section of the phaselines (U, V, W).

    In = 20 to25 A1)

    Miniature circuit-breakers 20 A charac-teristic B

    Short-circuit trippingcurrent

    130 A (210 A) 60 100 A 100 200 A

    Minimum current onshort circuit in onepole

    150 A (250 A) 110 A 220 A

    Max. total current forall motors (includingstarting currents)

    110 A (170 A) 55 A 90 A

    1) The values in brackets apply when the short-circuit instantaneousrelease is set to 210 A.

    Figure 11: Cable protection with FAZ-3-B20

    2 A

    1 A

    0.5 A

    10 A13 A16 A20 A25 A32 A

    40 A

    50 A63 A

    4 A

    3 A

    6 A

    0.5 1.5 151 2 3 4 5 6 7 8 9 10

    103

    104

    105

    8

    6

    4

    2

    1.5

    8

    6

    4

    2

    8

    6

    4

    3

    1.5

    FAZ-BFAZ-C

    FAZ-...-B4HI

    Z i2d t[A2s]

    I cc eff [kA]

    20 A

    29800 A2s

    10 kA

    http://-/?-http://-/?-
  • 8/13/2019 Manual Lms 4

    30/156

    Engineering 09/11 MN03406003Z-EN

    26

    Power bus

    The power bus supplies Rapid Link modules RAMO and RASP withmains and auxiliary power. Plug-in outgoers can be quickly and

    safely connected at any point along the bus. The power bus canconsist either of a flexible busbar (ribbon cable) or standard roundcables.

    Cable length

    Observe the following when planning the lengths of the power buscabling:

    On a short circuit in one pole at the end of the power bus, forexample in the terminal board of the last consumer, theupstream safety device must trip. The level of short-circuitcurrent depends on: Cable length Conductor cross-section Short-circuit current at the incoming point

    The level of the application-specific voltage drop, whichdepends on: Cable length Conductor cross-section

    Current consumption of motors

    Calculate the short-circuit current and voltage drop according toDIN VDE 0100 to make sure that the protection requirements arefulfilled.

    You can calculate the cable length for the power bus as follows:

    h Caution! All devices connected to the apparatus and data bus

    must also meet the requirements for safe isolationaccording to IEC/EN 60947-1 Annex N orIEC/EN 60950.

    Power supply units for the AS-Interface power supplymust meet the safe isolation requirements according toSELV.

    For RASP a screened cable is not required on the mainsside.

    Figure 12: Example arrangement system Rapid Link with RAMO and RASP

    M3h

    1.5 mm 2

    4 mm24 mm2

    50/60 Hz

    Q1

    M3h

    M3h

    1.5 mm 2 1.5 mm 2

    RAMO RASP

    M3h

    1.5 mm 21.5 mm 2 1.5 mm 2

    1.5 mm 2

    RASP

    1.5 mm 2

    PES

    PES

    PES

    PES

    RAMO

    F 25 A

    210A

    L =U0 x 1000 Zv ZStich

    Irmzpower bus

    L = Length

    U0 = 230 V (no-load voltage 1-ph)Irm = Tripping current of short-circuit release, e.g.

    150 A for RA-DI

    zv = e.g. 100 mO (infeed series impedance)

    ZStich = 35.50 mO /m (spur line 1.5 mm2)

    zpower bus = 13.40 mO /m (power bus 4.0 mm2)21.50 mO /m (power bus 2.5 mm2)

  • 8/13/2019 Manual Lms 4

    31/156

    09/11 MN03406003Z-EN Safety and switching

    27

    The sum of mains currents from RAMO and RASP in continuousoperation must not exceed 25 A (power bus 4 mm2).

    Residual current device (RCD)

    RCD (Residual Current Device): Residual current device, residualcurrent circuit breaker (FI circuit breaker).

    Residual current circuit breakers protect persons and animals fromthe existence (not the origination) of impermissibly high touchvoltages. The prevent dangerous, in cases deadly injuries causedby electrical accidents and also serve as fire prevention.

    RASP work internally with rectified AC currents. If an error occurs,the DC currents can block an RCD circuit breaker of type A fromtriggering and therefore disable the protective functionality.

    On RASP safety-relevant leakage currents can occur during opera-tion when RASP is not earthed (due to a fault).

    Leakage currents to ground are mainly caused by foreign capaci-ties with RASP; between the motor phases and the shielding of themotor cable and via the Y-capacitors of the internal radio interfer-ence suppression filter. The size of the leakage current is mainlydependent upon the:

    length of the motor cable, shielding of the motor cable, height of the pulse frequency (switching frequency of the

    inverter), Radio interference suppression filter type Grounding measures at the site of the motor.

    Figure 13: Example: RAMO

    Demands placed on the group protection device with short-circuitPrecondition: Short-circuit current Ik must be greater than the trippingcurrent Irm of the short-circuit release.Ik depends on the impedance or length of the power bus and the spurline.

    h When selecting the cable cross-section, take the voltagedrop under load into account. The user is responsible forensuring compliance with further standards (forexample VDE 0113, VDE 0289).

    h The total current in the power bus changes proportionallywith the sum of all flowing motor currents.

    3 AC 400 Vh , 50/60 Hz

    Irm

    Ik

    Q1

    L

    M3h

    RAMO

    1.5 mm 2

    4 mm2

    I >

    h Attention! Residual current circuit breakers (RCD) are only to beinstalled between the AC power supply network and theRapid Link modules RAMO and RASP.

    j Warning! With RASP, only AC/DC sensitive residual current circuitbreakers (RCD part no. B) are to be used (EN 50178,IEC 755).

    Identification on the residual current devices

    AC/DC sensitive (RCD, partno. B)

    h The leakage current to ground is greater than 3.5 mA witha RASP. Based on the requirements of EN 50178, anincreased ground (PE) has to be connected. The cablecross-section must be at least 10 mm2 or consist of twoseparately connected ground cables.

  • 8/13/2019 Manual Lms 4

    32/156

    Engineering 09/11 MN03406003Z-EN

    28

    Mains contactor

    The mains contactor enables an operational switching on and offof the supply voltage and switching off in case of a fault.

    Select the mains contactor according to the total mains-sidecurrent (ILN) of a power bus (F 25 A) and utilization categoryAC-1 (IEC 60947).

    EMC compliance

    Electrical components in a system (machine) have a reciprocaleffect on each other. Each device not only emits interference but isalso affected by it. The interference can be produced by galvanic,capacitive and/or inductive sources or by electromagnetic radia-tion. In practice, the limit between line-conducted interference andemitted interference is around 30 MHz. Above 30 MHz, cables andconductors act like antennas that radiate electromagnetic waves.

    Electromagnetic compatibility (EMC) for frequency-controlleddrives (variable speed drives) RASP is implemented in accordancewith product standard IEC/EN 61800-3. This includes the complete

    power drive system (PDS), from the incoming unit to the motor,including all components and cables. This type of drive system canconsist of several individual drives (Rapid Link).

    The generic standards of the individual components in a PDScompliant with IEC/EN 61800-3 do not apply. These componentmanufacturers, however, must offer solutions that ensure stan-dards-compliant use.

    In Europe, maintaining the EMC Directives is mandatory.

    A declaration of conformity (CE) refers always to a "typical"magnet system (PDS). The responsibility to comply with the legallystipulated limit values and thus the provision of electromagneticcompatibility is ultimately the responsibility of the end user orsystem operator. This operator must also take measures to mini-mize or remove emission in the environment concerned (seeFigure14). He must also utilize means to increase the interference immu-nity of the devices of the system.

    With their high interference immunity up to category C3, RapidLink modules are ideal for use in harsh industrial networks (2ndenvironment).

    With line-conducted emission, RASP with built-in radio interfer-ence suppression filter ensure maintenance of the limit values ofcategory C3. This requires an EMC-compliant installation(a page 48) and the observation of permissible motor cablelengths and the inverters maximum switching frequency (f PWM).

    The required EMC measures should be taken into account in the

    engineering phase. Improvements and modifications duringmounting and installation or even at the installation site involveadditional and even considerably higher costs.

    h In engineering take into account that jog operation of aRapid link module must be carried out only through themodules AS-Interface control input and not through themains contactor.

    The maximum permitted operating frequency of the mainsvoltage is one time per minute (normal operation).

    Figure 14: EMC environment and category PCC = metering point (point of common coupling)

    1. Umgebung

    ffentliches Mittelspannungsnetz

    PCC

    Kategorie C1

    Kategorie C2

    Kategorie C1 / C2 Kategorie C1 / C2Kategorie C3 / C4

    Kategorie C3 / C4

    1. oder 2. Umgebung 2. Umgebung

    ffentlichesNiederspannungsnetz

    PrivatesNetz

    IndustrieNetz

    http://-/?-http://-/?-http://-/?-http://-/?-
  • 8/13/2019 Manual Lms 4

    33/156

    09/11 MN03406003Z-EN Data bus ASi

    29

    Data bus ASi

    The AS-Interface data bus is a system solution for networkingdifferent modules. AS-Interface networks are quick and easy toimplement.

    Data cable

    AS-Interface uses a geometrically coded, unscreened flat cable witha cross-section of 2 1.5 mm2. It is used to transfer both power and

    all data traffic between the PLC and I/O and also supplies theconnected devices with energy to a certain extent. The installationmeets the usual requirements. Engineering is simplified by full flexi-bility in system layout and mounting.

    When a link is connected to the flat cable, two metal pins piercethrough the cables jacket and into the two cores to establish acontact with the AS-Interface cable. There is no need to cut andstrip cables, apply ferrules or connect individual cores.

    Rapid Link function modules can be installed and removed anynumber of times at various locations. The AS-Interface ribboncable is self-healing, dust-tight and resistant to spray-water. The

    network can have a star, linear or tree structure.

    Data transfer

    For transmission the data is modulated onto the supply voltage.Each modules transmitter injects the data signals in the form ofchanges in current. This change in current induces a voltage in thedata coupling coils, which the receivers of all modules along theAS-Interface bus can read.

    The cycle time depends on the number of modules along the line(31 possible addresses). With 31 modules the cycle time is about

    5 ms and is calculated as follows:150 ms (no. of modules + 1).

    The response time to a control signal through an AS-Inter-face busis 25 ms 5 ms plus an AS-Interface cycle time of up to 5 ms.

    Head station

    The head station, for example interface control unit RA-IN, estab-lishes the connection to the PROFIBUS-DP field bus and, as master,manages all communications within the AS-Interface line.

    The head station contains a built-in power extender (PEX) which

    contains a data decoupler for up to 2.8 A at 30 VH AS-Interfacevoltage. The AS-Interface power extender is short-circuit-limited(self-resetting fuse, time-delay, 3 A).

    The head station requires a power supply unit with 30 VH to AS-Interface specification (SELV, smoothing, etc.) and with or withoutdata decoupling. Several interface control units RA-IN can besupplied by one PSU. For supply cables use standard round cableswith 3 1.5 mm2 or 3 2.5 mm2.

    Accessing

    Figure 15: AS-Interface-flat band conductor

    a Piercing pinsb Flat cable, protected against polarity reversal

    1 AS-Inter-face+

    2 -

    2

    3 4

    1

    a a

    b +

    10

    6.5

    4 2

    Figure 16: AS-Interface-network in star design

    h For notes about addressing and engineering AS-Interface see the manual of the master controller used.

    PROFIBUS-DP RA-IN PEX

    RA-IN PEX

    RA-IN PEX

    30 V H

  • 8/13/2019 Manual Lms 4

    34/156

    Engineering 09/11 MN03406003Z-EN

    30

    Cable lengths and voltage drop

    When planning the lengths of the AS-Interface line cabling,observe the following:

    The total length including all spur lines and M12 plug cablesof the function modules (calculate 0.9 m each for 0.5 m longM12 plug cables) must not exceed 100 m. This total lengthdoes not include the length of cabling between PSU and headstation.

    Each station must be supplied with at least 24 VH +10/15 %. The head station must be supplied with at least 26 VH.

    Calculate current demand and voltage drop to ensure that allsensors, actuators and the head station receive the requiredvoltage.

    Length of AS-Interface data cable:The length of the AS-Interface data cable with a cross-section of1.5 mm2 depends on the voltage at the head station and is gener-ally:

    AS-Interface voltage > 28 V: 80 m cable length AS-Interface voltage > 26 V: 60 m cable length

    Cable length between PSU and head station:The cable length between PSU and a master station is calculatedfrom the voltage drop.

    Voltage dropDU =Length l x current I x 2

    [V]

    Conductivity k x cross section A

    Length l=Voltage dropDU x conductivity k x cross section A

    [m]2 x current I

    Conductivity of copper: =57 m

    O mm2

    cU f 26 V

    F 2.5 mm2 b

    cU f 26 V

    a30 VH

    F 2.5 mm2 b

    c cU f 26 V

    F 2.5 mm2 b

    Figure 17: Structure of a data bus

    a Power supply unitb Head station for stringc Rapid Link modules:

    - Voltage at stationF 24 V- Plug cablef 1 m

  • 8/13/2019 Manual Lms 4

    35/156

    09/11 MN03406003Z-EN Sensor inputs I3+I4

    31

    Sensor inputs I3+I4

    Figure 18: Connection sockets of sensors I3 + I4

    Rapid Link modules RAMO and RASP have two M12 sockets (I3and I4) for direct connection of sensors, for example:

    optical (light barriers), inductive (proximity switches), mechanical (end switch).

    The length of the sensor connection cables for inputs I3 and I4 islimited to 5 m. The sensors are supplied with 24 V DC from RapidLink modules RAMO and RASP (AS-Inter-face supply voltage). Thetotal current of all sensors is limited to 160 mA. The sensor supplyis short-circuit proof. On overload or short circuit a group faultsignal is generated and indicated by a lit red Motor LED. When thefault has been rectified, the fault signal can be reset with theRESET command.

    The input signals of the sensors at I3 and I4 are either incorporateddirectly in the internal controller of RAMO and RASP or transmittedto a higher-level PLC through AS-Interface. Signal conditioningand incorporation in the control sequence is made with a DIPswitch for RAMO (a section "Adjust dip switch, page 68), and

    with parameters and DIP switch for RASP (a section "Parame-ters, page 87).

    h RASP only!With optional Y-connector RA-XM12-Y up to four sensorscan be connected to these two M12 sockets.

    1

    4 3

    2

    I3 + I4

    1 L+2 3 L4

    STOP

    h No capacitive sensors may be connected.

    I3

    I4

    UV

    F 20 m

    1

    2M 3 ~

    A-coded(IEC/EN 60947-5-2)1 = brown2 = white3 = blue4 = black

    Y connector RA-XM12-Y optical or inductivesensors

    N/O NC Sensor cables coding

    S I F 160 mA24 V DC

    mechanical sensors

    1

    32

    4

    1

    32

    4

    1

    32

    4

    1

    3

    4

    1

    4

    1

    4

    1

    3

    4

    1

    4

    1

    4

  • 8/13/2019 Manual Lms 4

    36/156

    09/11 MN03406003Z-EN

    32

    Actuator output O3

    Actuator output O3 (12M connectionsa figure 19) allows actu-ation of external signaling elements or relays. For this pin 2 of O3must be supplied externally with 24 V DC. Reference point is pin1. The actuator (indicator lamp, relay, valve) can be connected topin 4 (+24 V, max. 1 A). Reference point is pin 3.

    Figure 19: Connecting example actuator output O3

    Actuator output O3 is not actuated directly by I3 or I4 but onlythrough AS-Interface.Response times:

    Up to 20 ms About 25 ms 5 ms on quick stop

    The connection cable must not be longer than 20 m. The loadcurrent must not exceed the load current of 1 A. Output O3 isshort-circuit proof.

    On overload or short circuit a group fault signal is generated andindicated by a lit red Motor LED. The voltage at output O3(24 V DC) is automatically switched off. When the fault has beenrectified, the fault signal can be reset with the RESET command.

    Fan connection F

    Fan connection F is fitted only on RASP and already assigned bydefault in version RASP-SL-C.

    Figure 20: Device fan connection F

    The output voltage at fan connection F is 24 V and is controlledautomatically by the RASP.

    h RAMO-DA and RAMO-WA only!

    Actuator output AO3

    +24 V

    ASi

    +24 V

    03:2

    03:1

    0 V

    0 V

    03:4

    03:3

    2

    3 4

    1

    03

    1 0 V (power supplyunit)

    2 +24 V (power supplyunit)

    3 0 V actuator

    h RASP only!

    Device fan connection F.

    h Only the RASPs device fans must be connected to fanconnection F.

    Any other load connected here is considered contrary tointended use.

    03:4

    M

    03:3

    F

    1 -2 -3 0 V4 +24 V

    4 3

  • 8/13/2019 Manual Lms 4

    37/156

    09/11 MN03406003Z-EN Motor and Application

    33

    Motor and Application

    Motor Selection

    General recommendations for motor selection: To the output of Rapid Link modules RAMO and RASP three-phase

    AC motors with squirrel-cage rotor and surface-cooling can beconnected; the output is also suitable for three-phase asynchronousmotors. Other motor types, such as external-rotor motors, slip-ringmotors, reluctance motors, or synchronous or servo motors can alsobe connected provided their electrical and connection characteristicsare the same as those of asynchronous motors and their manufac-turer has approved them for the application.

    To the frequency-controlled RASP only motors with at leasttemperature class F (155 C max. continuous temperature)should be connected.

    Where possible, use four-pole motors (synchronous speed:1500 rpm at 50 Hz or 1800 rpm at 60 Hz).

    Operating conditions for S1 operation according to IEC 60034-1.

    When operating multiple motors in parallel on one RAMO andRASP, the motor output should not be more than three powerclasses apart.

    The rated current of motor and RAMO or RASP should be thesame (avoid overdimensioning the motor).

    Motor and circuit type

    The motors stator winding can be connected in a star or deltaconfiguration in accordance with the rated operational data on therating plate.

    The three-phase motor with rating plate according toFigure 21 can be operated in the Rapid Link system ( ULN= 400 V) only in astar circuit.

    The rated operational current of the motor with 2 A at 400 Vrequires a Rapid Link module (RAMO or RASP) with a rated oper-ational current of at least 2 A.

    For example:

    Automatic deceleration time extension on RASP

    In a drive system with AC-supplied motors the energy always flowsfrom the system with the higher frequency to the system with thelower frequency. The difference between the frequencies is theslip. Normally this means that the energy flows from a frequencyinverter to the motor.

    If the deceleration is set to a low value at the frequency inverter(a section "P6.6, page 102), the motor may not be able tofollow the deceleration ramp due its or its loads inertia. The direc-

    tion of energy flow then reverses and the motors rotational energyis fed back into the frequency inverters internal DC link. Thisresults in an increased DC link voltage and possibly to an over-voltage trip.

    To ensure reliable operation without overvoltage trippingfrequency-controlled drives RASP automatically adjust the deceler-ation time to motor and motor load. This prevents overvoltagetripping.

    Change of rotation

    Three-phase motors work with clockwise rotating fields (viewedfrom the motor shaft) when phase L1 is connected to U1, L2 to V1and L3 to W1. This default operating direction can be reversed

    Figure 21: Example of a motor ratings plate

    Figure 22: Circuit types: Star, Delta

    / 400 V230 3.5 / 20,75S1 0.79coskW

    rpm1430 50 Hz

    A

    U1 V1 W1

    W2 U2 V2

    U1 V1 W1

    W2 U2 V2

    RAMO- (max. output current 6.6 A, current limitation setto 2.1 A with DIP switch).

    RASP-2 (rated operational current 2.4 A)

    h Other operational characteristics and speeds are possibleonly with frequency-controlled Rapid Link module RASP(see a section "U/f-characteristic curve (P11), page109).

    h Notes

    RAMO(a section "Motor feeder, page 45) RASP(a section "Motor feeder, page 45,

    a section "Motor feeder on RASP, page 47)

    h In applications in which the motor can be driven by itsload (for example lowering hoist drives), a RASP withbuilt-in braking resistance should preferably be used. The

    braking resistance dissipates the fed back rotationalenergy from the motor as heat. But if the braking resis-tance is destroyed, for example through overload causedby a fault, the RASPs safety trip responds only with adelay because the extended deceleration time takeseffect. The load can therefore drive the motor past theapproached stop position. In applications with finitetravel paths this must be taken into account in the safetyconcept.

    The automatic ramp extension function of RASP in regen-erative operation can be disabled with P6.34.

  • 8/13/2019 Manual Lms 4

    38/156

    Engineering 09/11 MN03406003Z-EN

    34

    with gearboxes or different mounting positions. On RAMO-Wand RASP the operating direction can be reversed with DIP switch7 without changing the wiring.

    With the default settings (switch position Down) a clockwiserotating field is produced with control command FWD, and ananticlockwise rotating field with switch position Up. The LED indi-cates FWD for both directions.

    Quick stop

    Quick stop is a motor stop function in automatic mode through pin4 of the sensor inputs:

    I3/I4 on RAMO I3a/I4a on RASPThe input signals are processed directly in RAMO or RASP. PLC andbus cycle times have no effect on the switch-off times.

    Figure 24: Examples: Edge-controlled quick stop in automatic mode(pin 4 = I3 or I3a)

    a Internal response timeb Signal O1 from PLC through AS-Interfacec Internal signal to motor output as response to the rising edge of the

    sensor at pin 4 (Stop) and to the subsequently rising edge of PLC O1(Start)

    The type of edge control (rising, falling) for sensor inputsI3(a)/I4(a) is defined with DIP switches:

    DIP 3 on RASP (a page 80) DIP 5 on RAMO (a page 68)

    The input signal at pin 4 (rising edge) switches the motor outputoff. When the PLC output (O1) is reset (falling edge), the motoroutput can be switched on again. Whether or not the input signalis still applied when the PLC output is reset or restarted has noeffect.a figure 24.

    The "FWD" or "REV" LED flashes when the motor output isswitched off by means of quick stop and the PLC continues to setthe corresponding rotational direction bit.

    In operation the FWD or REV LED lights up when the PLC has setthe corresponding direction bit.

    Example of quick stop function for a vertical sorter with 360 degreeeccentric.

    Quick stop enables precise stopping of the drive when the limitswitch is reached. Through processing in RAMO or RASP the motor

    is switched off directly. PLC and bus cycle times have no influenceon the switch-off times.

    Figure 23: Example: Changing phase sequence

    Pin 4 Pin 4

    b b

    c c

    a a a a

    L1L2L3

    1 7 3U V W FWD

    FWD L1L2 L3

    1 7 3

    U V W

    FWDOFF

    7

    ON

    7

    Figure 25: Example: eccentric drive

    a upper break pointb lower break point

    STOP

    STOP a

    b

  • 8/13/2019 Manual Lms 4

    39/156

    09/11 MN03406003Z-EN Motor and Application

    35

    Interlocked manual mode

    In interlocked manual operation damage to conveyed goods orplant through incorrect handling can be avoided. Limit switches

    connected to inputs I3 and I4, for example, can be used to reliablylimit the travel path. This function also allows adjustment of, forexample, light barriers before automatic control through a PLC(AS-Interface) is activated.

    Figure 26: Interlocked manual operation(example: I3 level-controlled clockwise operation)

    a Internal response timeb Selector switch manual modec Output signalIn interlocked manual operation rotating field direction FWD isinhibited after a rising signal edge at I3 or during a continuoussignal. The motor can then be operated only in automatic mode or,with RAMO-W and RASP, in reverse direction in manual mode.Rotating field direction FWD in manual mode is possible again onlyafter a falling edge is registered at I3 or after a changeover toautomatic mode and back again). This also applies for sensor inputI4 and rotating field direction REV.

    On RAMO-D interlocked manual operation can be set to act

    only edge-controlled with DIP switches 6 and DIP 8 (a page 69).This allows continued manual operation in the same direction aftera break point is reached by simply briefly switching over to Auto-matic and back again.

    LED-signal under interlocked manual operation of RAMO-W andRASP:

    LED FWD or REV is lit when the associated operating direction isselected with the selector switch. LED FWD or REV flashes whilethe selector switch is operated but RAMO-W or RASP is switchedoff through interlocked manual operation. (For an example ofinterlocked manual operation with RASPa page 84).

    I3 I3

    b a

    0 0

    c c

    a a a a a

  • 8/13/2019 Manual Lms 4

    40/156

    09/11 MN03406003Z-EN

    36

  • 8/13/2019 Manual Lms 4

    41/156

    09/11 MN03406003Z-EN

    37

    3 Installation

    IntroductionThis chapter describes the mounting and electrical connection ofRapid Link modules RAMO and RASP.

    Installation instructions

    The mounting instructions in this manual apply for RAMO andRASP with standard equipment and protection type IP65.

    For installation instructions, see IL03406019Z for RAMO andIL03406020Z for RASP

    Mounting position

    Rapid Link modules RAMO and RASP are preferably installed verti-cally.

    h During installation and mounting cover the operatorcontrol and display elements and the connectors in thecontrol and power sections to prevent foreign bodiesentering them.

    On RASP it is also advisable to protect the cooling finsand, if fitted, the fan from ingress of foreign bodies.

    h Perform all installation work with the specified tools andwithout the use of excessive force.

    Figure 27: Mounting position RAMO and RASP

    F 90

    F 90

    F 90

    F 90

    F 90

    F 30

    F 30

    F 30

    h A mounting that is turned by 180 (stood on its head) isnot permissible.

  • 8/13/2019 Manual Lms 4

    42/156

    Installation 09/11 MN03406003Z-EN

    38

    Free space

    Depending on version, thermal clearances must be providedaround Rapid Link modules RAMO and RASP. On versions withmanual override switch (RAMO-R and RASP-R) or in thearea of the pluggable cable connectionsb , these must, in addi-tion, provide unobstructed handling. The table below lists therecommended minimum clearances.

    Fixing

    Rapid Link modules RAMO and RASP are mounted with screws.

    Fixing with screwsThe permitted maximum tightening torque for the fixing screws is1.3 Nm (11.5 lb-in).

    l

    Figure 28: Clearances for thermal air cooling(Example: RASP)

    a

    bc

    d d

    RAMO[mm]

    RASP[mm]

    a abovewithout manual overrideswitch

    25 100

    with manual override switch ~150 ~150

    B bottomwithout power connection 25 100

    with power connection ~100 ~100

    c front side

    without fan 15 25with fan - 50

    d sidewayswithout manual overrideswitch

    ~01) ~01)

    with manual override switch ~150 ~150

    without power connection ~01) ~01)

    with power connection ~100 ~100

    1) At an installation altitude up to 1000 m and at an ambient temper-ature of up to +40 C no clearance is required to the sides. Higherambient temperatures (up to a maximum of +50 C), pulse frequen-

    cies f PWM (up to maximum 16 kHz) and installation altitudes (up to2000 m) require clearance on all sides of at least 20 mm.

    h Clearance dimensions from the mounting base of RAMOand RASP.

    h For mobile installation with two prefitted screws(a page 39 and page 39) larger clearances are requiredfor handling.

    h Devices with high magnetic fields (e. g. reactors or trans-formers) should not be mounted close to the RAMO and

    RASP.

    h Install the RAMO and RASP only on a nonflammablemounting base (e.g., on a metal plate).

    h For dimensions and weights of RAMO and RASP see thetechnical data (pagea section "Dimensions, page125).

    h Washer and split washer provide a firm seat during fixing.

    2 x / 4 x 4 x 4 x

    M6 DIN 127, M6 DIN 125, M6

  • 8/13/2019 Manual Lms 4

    43/156

  • 8/13/2019 Manual Lms 4

    44/156

    Installation 09/11 MN03406003Z-EN

    40

    Arrangement of power terminals

    The standard arrangement of power terminals is vertical down-wards on versions RAMO--C32 and RASP--C32. A hori-

    zontal arrangement (RA-C31 or RA-C33) is not avail-able on all versions.If necessary, briefed specialists can rotate the black enclosure base tothe right or left by 90 degrees. To do this, remove the four screws inthe enclosure cover.

    Fix the enclosure cover at the side and lift off carefully.

    The enclosure base can now be rotated, for example 90 degreescounterclockwise (to the left). The power terminals now point tothe right. This corresponds with version -C31. With a rotation tothe right they correspond with version -C33.

    Finally carefully refit the enclosure cover.

    With the four screws secure the enclosure cover on the base.Tighten the screws in two passes, always tightening two diago-nally opposite screws at a time. For example, tighten all fourscrews to about 2 Nm and then to 5 Nm, always working in acrosswise pattern.

    Figure 33: Dismantling, enclosure cover

    h Caution!Do not reach into the opened base or the enclosure coveras this can damage assemblies and connections andimpair the devices function.

    Figure 34: Example: Lifting off enclosure cover on a RASP

    TORX 30 IP

    1

    2

    390 90 ( ... C33)( ... C31)

    h When assembling, make sure that the rubber seals areseated correctly (protection type IP65).

    h Use a suitable tool (Torx 30 IP) to tighten the screws to atorque of 5 Nm.

    Figure 35: Mounting enclosure coverExample: RASP-C31

    5 Nm (44.25 lb-in)

    TORX 30 IP

    5

    4

  • 8/13/2019 Manual Lms 4

    45/156

    09/11 MN03406003Z-EN Electrical Installation

    41

    Electrical Installation Power bus

    The Rapid Link system can have one of two types of power bus:

    Flexible (RA-C1...) busbar Round conductor (standard cable)

    Flexible (RA-C1-7...) busbarFlexible busbar RA-C1-7 is coded for protected against polarityreversal: One edge of the busbar is wedge-shaped. The busbarconnectors of all system components (ribbon cable outgoers) isshaped accordingly. The flexible busbar is inserted such that thewedge-shaped side is opposite the hinge of the opened busbarconnector.

    Laying the flexible busbarUnreel the flexible busbar, cut to length and lay it. An inscriptionon one side of the busbar provides guidance for coding. A metricmarker on the jacket aids with cutting to length.

    Where the flexible busbar is not laid within cable ducts, secure itto the ground with cable binders or cable clamps.

    j Danger!Electric shock hazard - risk of injuries!

    Carry out wiring work only if the unit is de-energized.

    h Caution!Fire hazard!

    Only use cables, protective switches, and contactors thatfeature the indicated permissible nominal current value.

    h Caution!With RASP earth leakage currents are greater than 3.5 mA(AC). According to product standard IEC/EN 61800-5-1

    an additional protective conductor must therefore beconnected to the RASPs heat sink.

    j Danger!The components in the RASP power section remain ener-gized up to five (5) minutes after the supply voltage hasbeen switched off (intermediate circuit capacitordischarging time).

    On RASP the motor feeder cable must be disconnected orwork on the motor terminal box performed only after thedischarging time.

    h Complete the following steps with the specified tools andwithout using force.

    Figure 36: Coding of flexible busbar RA-C1-7

    a Hinge

    h L+ and N are not used on Rapid Link modules RAMO andRASP.

    h Caution!The flexible busbar is not suitable for drawing in and mustnot be used as trailing cable!

    h In areas in which mechanical damage is likely to occur, werecommend laying the busbar in cable ducting for protec-tion.

    ML+PENL3L2L1

    a

  • 8/13/2019 Manual Lms 4

    46/156

    Installation 09/11 MN03406003Z-EN

    42

    End-pieces and lead-throughsOnce the flexible busbar has been laid, all free busbar ends mustbe safely terminated and sealed to IP65. To do this, use cable endpieces (RA-C1-END1) or bushings (RA-C1-DF).

    With bushing RA-C1-DF the flexible busbar can be fed into distri-bution module RA-C1-VM-7 in a control panel.

    X Cut the busbar to the required length.

    X Strip the flexible busbar to the required length (see also notebelow): for cable end piece to 19 mm, for distributor module to 50 mm, for control panel as required.

    End-piece mountingX First slide the lower (shorter) part of busbar end piece RA-C1-

    END1 onto the prepared flexible busbar.

    X Slot the individual conductors into the insulation channels in thebusbar end piece up to the stop.

    X Join the upper and lower sections with the two screws. Installedcorrectly, the flexible busbar offers protection type IP65.

    Connections, flexible busbar junctionFeeder and outgoer modules can be connected at any point alongthe flexible busbar without interrupting the busbars conductors.The connection is made with contact screws.

    Round conductorRound cable junction RA-C2-S1-4 is a T-piece for plug-in poweradapter cable RA-C3/C2-1,5HF. It allows direct connection of aRapid Link module (RAMO or RASP).

    Insulation piercing terminals are used for conductor contacting inthe power bus. The Die bushings are dimensioned for a conductorwith outer diameter from 10 to 16 mm.

    Figure 37: Bushing RA-C1-DF for ribbon cable

    Figure 38: RA-C1-CUT, hand ribbon cable cutter

    h For cutting to length we recommend tool RA-C1-CUT.

    h To strip the 7 4 mm2 flexible busbar we recommend toolRA-C1-AZ-4. If using a normal cable knife, do not cut intothe rubber jacket more than 0.7 mm as you may otherwisedamage the conductor insulation.

    Figure 39: RA-C1-AZ-4, tool for removing busbar jacket

    PIN Function wire numbers

    7 x 4 mm2

    1 L1 1

    2 L2 2

    3 L3 3

    4 N 4

    5 +24 V1) 5

    6 0 V1) 6

    PE PE green/yellow

    1) Not used for RAMO and RASP

    Figure 40: Pin assignment of ribbon cable junctionRA-C1-PLF1

    Figure 41: Round cable junction RA-C2-S1-4

    L2 L3N L1 PE

  • 8/13/2019 Manual Lms 4

    47/156

    09/11 MN03406003Z-EN Electrical Installation

    43

    Accessories (seal insert, locking clip, the fully wired bushing insert,etc.) is included as standard.

    X For mounting the round cable junction is secured to the

    substrate with suitable screws (M5).X Strip the round cables to a length of 130 mm (two radial cuts,

    one longitudinal cut), for example with wire stripper AM16 fromWeidmller.

    X Make a radial cut in the gaskets, lay the seals around the cable jacket and insert it in the provided U-shaped contour in thecable junction.

    X Insert the conductors into the insulation piercing terminal andsecure them with the screws one at a time.

    Assignment of terminals and conductors:

    X Turn in the screws [1] all the way to the stop (tightening torque0.5 to 1 Nm).

    X Place the cover on the base so that it rests fully on the base. Thescrews must be turned in all the way.

    X Secure the cover with the four screws.(size Pozidriv 2; 1.5 to 2 Nm).

    X To ensure protection type IP65 on cable binder [2] must befirmly tightened about each of the outer gaskets.

    X Slot the attached locking clip for the outgoer plug onto the twostuds of the bushing housing.

    Round conductor with Power boxPower box RA-C4-PB65 is a contact unit for uncut round cablesfrom 2.5 to 6 mm2, with protection type IP65.

    h To strip the cable, set the blade so that the conductorinsulation remains undamaged.

    h The supplied equipment includes two pairs of seals forcable outer diameters from 10 to 13 mm and from 13 to16 m. Only these matched gasket inserts guaranteeprotection type IP65 when used correctly.

    h The round cable must be laid without tension.Install only one conductor per terminal.

    PIN Function1 L1

    2 L2

    3 L3

    e e

    4 N

    5 24 V1)

    6 0 V1)

    PIN Function

    1 N

    2 L2

    3 n. c.

    4 +24 V1)

    1 2 3 4 5 6

    5 0 V1)

    6 L3

    7

    8 L1

    PE PE

    1) Not used for RAMO and RASP

    h The open gasket of the last round cable junction (at theend of the power bus) must be sealed with end-piece RA-C2-SBL.

    Figure 42: Power box RA-C4-PB65

    h The IP65 enclosure of the power box is supplied withoutgaskets (RA-C4-D).

    2

    1

  • 8/13/2019 Manual Lms 4

    48/156

    Installation 09/11 MN03406003Z-EN

    44

    Power plug and power adapter cable

    Power plug RAC3 (part no.: HAN Q5/0) always has thefollowing pin assignment.

    Having installed the power bus outgoers (RA-C1-PLF1,RA-C2-S1-4, RA-C4-PB65) you can connect the Rapid Link module(RAMO or RASP) to the power plug through the assigned poweradapter cables.

    Power adapter cables:

    PIN Function Power plug

    1 L1

    2 L2

    3 L3

    4 N

    5

    PE PE

    4 53

    1 2

    e

    RA-C3/C1-1,5HFfor RA-C1-PLF1

    RA-C3/C2-1,5HFfor RA-C2-S1-4

    RA-C4-PPB/C3-1M5for RA-C4-PB65

  • 8/13/2019 Manual Lms 4

    49/156

    09/11 MN03406003Z-EN Electrical Installation

    45

    Mains connection for RASP without control section for externalmotor brake.

    Mains connection for RASP with control section for external motor

    brake.

    Motor feederRAMO and RASP are connected to the motor through a socketconnector. The pin assignment of this motor feeder socketcomplies with the DESINA specification for:

    AC Motor (U, V, W) Temperature sensor (T1, T2) Motor brake (L, N)

    Operational safety of plug connectorsh All versions of RAMO require connection of the N

    conductor (400/230 V)

    L1 L2 L3

    RAMO

    N PE

    PE4321

    L1 L2 L3

    RASP-...xx0...

    PE

    PE321

    L1 L2 L3 N PE

    PE4321

    RASP-...xx2...

    h To increase the operational safety of the plug connection(inadvertent loosening of the locking clips) we recom-mend securing the connections with a cable binder at thelocking clip.

    Figure 43: Securing with cable binder

    PIN Function Arrangement of pins

    Motor outgoer socket Plug connectors

    1 U1

    2 Coding adapter

    3 W 1

    4 Brake N (B1)

    5 Thermistor 1

    6 Brake L (230 Vh , B2)

    7 V1

    8 Thermistor T2

    PE PE

    1 4 6

    3 5 8

    PE 7

    3 5 8

    1 4 6

    PE 7

  • 8/13/2019 Manual Lms 4

    50/156

    Installation 09/11 MN03406003Z-EN

    46

    Pins 5 and 8 of the motor feeder socket are used for monitoringthe motor cable and for thermistor protection.

    On motors without thermistor the cable ends (pins 5 and 8) mustbe connected in the motors terminal box).

    On motor cables without the conductors for pins 5 and 8 (forexample 4-core motor cables) the two connections must beconnected directly in the motor plug.

    External brakeA mechanical spring-loaded brake fitted to the motor (disk orspring-applied brake) brakes the motor shafts rotating motionwhen the brake coils supply voltage is switched off. If the brake isrequired to engage quickly, DC air solenoids are used. The brakeis, in this case, supplied with AC through a functional rectifier builtinto the motor.

    Rapid Link modules RAMO and RASP contain a faster electronicswitch for supplying and actuating the external motor brake with230 V AC. It is connected with pins 4 and 6 of the motor feedersocket. The highest permissible continuous holding current is0.6 A. For releasing the brake, up to 6 A are available for up to120 ms.

    The external brake is actuated as follows:

    With RAMO automatically with the start signal, in automaticand manual modes.

    With RASP by the built-in frequency inverter (a section"Braking (P12), page 114).

    h The PE connection of the motor feeder socket isconnected directly with the PE connection of the powerplug.

    Figure 44: General motor connection with cable monitoring (T1,T2)

    h On operation without thermistor the cable ends of pins 5and 8 must be bridged in the terminal box (cable moni-

    toring).

    Figure 45: General motor connection with therm-istor and cable monitoring

    5 8 1 7 3 PE

    T1 T2

    M3 h

    U V W PE

    e

    5 8 1 7 3 PE

    T1 T2

    M 3 hi

    U V W PEe

    Figure 46: External brake control

    M3 h

    L1 N

    230 V h

    6 4

    L N

    230 V h0.6 A

    u

  • 8/13/2019 Manual Lms 4

    51/156

    09/11 MN03406003Z-EN Electrical Installation

    47

    Motor feeder on RASPSpeed control unit RASP is frequency-controlled (with a built-infrequency inverter) and requires screened motor cables in themotor feeder.

    Figure 47: General connection with a 230 V AC brake

    j Danger!Dangerous touch voltage.

    For RASP 4.0 use fully insulated plastic plugs in the motorfeeder!

    h Caution!The motors metal enclosure must always be earthed, irre-spective of the type and version of motor cable used.

    1 74 6 3 PE

    M3 h

    PEWVULN

    e

    5 8

    T2T1

    Figure 48: Screened motor cable fir RASP.Highest permissible motor rating 10 m.

    h On operation without thermistor the cable ends of pins 5and 8 must be bridged in the terminal box (cable moni-

    toringa fig. 45).

    h For RASP 4.0 the motor cables screen braid has to beearthed only at the motor (PES).

    5 8 1 7 3 PE

    T1 T2

    M 3 hi

    U V W PE

    4 6

    N L

    e

    PES F

    1 0 m

  • 8/13/2019 Manual Lms 4

    52/156

    Installation 09/11 MN03406003Z-EN

    48

    Screen motor cable

    h Only required for RASP!

    X Stripping the motor cable ends (radial and longitudinal cut).

    X Then push the screen braid back to reveal the individualconductors.

    X Conductors B1 (= N)/B2(= L) for the external brake and T1/T2for the thermistor have a separate screen braid. These conduc-tors must be stripped separately.

    X Then slide the outer screen braid of the motor cable back

    towards the cable end far enough that conductors B1/B2 andT1/T2 are covered over a large area and connected with eachother.

    X At the motors terminal box connect the motor cables screenbraid to earth potential (PES).

    Figure 49: 360 screen contact at the motor terminal box

    a 360 contact screen for the motor cableb Clamp strap with screw for the screen braidX Con